1
A-101
DRAWING SYMBOLS
REFERENCE SYMBOLS
A
COLUMN LINE NUMBER
ELEVATION REFERENCES
GENERAL REFERENCE DETAIL
SECTION REFERENCE
DETAIL REFERENCE
INDICATES SHEET UPON
WHICH DETAIL APPEARS
INDICATES DETAIL NUMBER
4
A-401
2
A-301
3
A-201
2
A-301
OR
OR
1
G-000
FIRST FLOOR
100'-0"
UNDISTURBED EARTH DISTURBED EARTH GRAVEL OR CRUSHED
STONE
SAND
ASPHALTCAST IN PLACE CONCRETE CONCRETE MASONRY PRECAST CONCRETE
FACE AND COMMON BRICK
MARBLE AND GRANITE
STRUCTURAL CLAY
TILE
GROUT
RUBBLE STONEASHLAR STONE CAST STONE CUT STONE
ALUMINUM BRONZE AND BRASS
STEEL
CHECKER PLATE
FIRE BRICK
GLAZED, FACED, VENEERED
OR FINISHED ONE SIDE
DIMENSIONAL FRAMING OR
BLOCKING
FINISH GRADE LUMBER
PLYWOOD
EARTHEN
MATERIALS
CONCRETE
BRICK & TILE
STONE
METALS
WOOD
INSULATION &
ACOUSTICAL
MATERIALS
GYPSUM
MATERIALS
PARTICLE BOARDORIENTED STAND BOARD
BATT, FIRE SAFING OR
SOUND ATTENUATING
BLANKET
RIGID BOARD
GYPSUM WALLBOARD PLASTER
ACOUSTIC TILE OR PANELS FIBER PANEL
CERAMIC TILE QUARRY TILE
NON-DIMENSIONAL
BLOCKING
WOOD FLOORING
GLUE-LAMINATED OR LVL
MATERIAL SYMBOLS
ABBREVIATIONS
ABBREVIATION TERM(S)
3PLY THREE-PLY
A/E ARCHITECT/ENGINEER
A/V AUDIO VISUAL
ABS ACRYLONITRILE BUTADIENE STYRENE
ACS ACCESS
ACST ACOUSTIC
ACT ACOUSTICAL CEILING TILE
AD AREA DRAIN
ADA AMERICANS WITH DISABILITIES ACT
ADJ ADJUSTABLE
ADMIN ADMINISTRATION
AFF ABOVE FINISHED FLOOR
AHJ AUTHORITY HAVING JURISDICTION
ALT ALTERNATE
ALUM ALUMINUM
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
AP ACRYLIC PANEL
APC ACOUSTICAL PANEL CEILING
ARCH ARCHITECT
ASPH ASPHALT
ASSY ASSEMBLY
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
AUTO AUTOMATIC
AUX AUXILIARY
AVG AVERAGE
AWI ARCHITECTURAL WOODWORKING INSTITUTE
B&B BALLED AND BURLAPPED
BD BOARD
BF BOTH FACES
BG BUMPER GUARD
BKG BACKING
BLDG BUILDING
BLKHD BULKHEAD
BLKT BLANKET
BM BENCH MARK OR BEAM
BN BULLNOSE
BO BOTTOM OF
BOC BACK OF CURB
BOS BOTTOM OF STEEL
BOT BOTTOM
BRCG BRACING
BRDG BRIDGING
BRG BEARING
BRKT BRACKET
BS BOTHSIDES
BSMT BASEMENT
BUR BUILT-UP ROOFING
C&P CARPET AND PAD
CAC CEILING ATTENUATION CLASS
CB CARRIAGE BOLT OR CATCH BASIN
CD CONSTRUCTION OR CONTRACT DOCUMENTS
CER CERAMIC
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED
CG CORNER GUARD
ABBREVIATION TERM(S)
CH CHANNEL
CHK COAT HOOK
CI CURB INLET
CIP CAST-IN-PLACE
CIR CIRCLE
CJ CONSTRUCTION OR CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLO CLOSET
CLR CLEAR
CMP CORRUGATED METAL PIPE
CMPST COMPOSITE
CMT CERAMIC MOSAIC TILE
CMU CONCRETE MASONRY UNIT
CO CARBON MONOXIDE
CO2 CARBON DIOXIDE
COL COLUMN
CONC CONCRETE
CONF CONFERENCE
CONT CONTINUE OR CONTINUOUS
COORD COORDINATE
CORR CORRIDOR
CPRS COMPRESSIBLE
CPT CARPET
CS CAST STONE
CSK COUNTER SUNK
CT CERAMIC TILE
CTF CERAMIC TILE FLOOR
CTR CENTER
CTRL CONTROL
CTT CERAMIC TILE TRIM
CU CUBIC
CURT CURTAIN
CUST CUSTODIAN
D DEEP, DEPTH AND PENNY (NAIL)
dBA UNIT OF SOUND LEVEL
DBL DOUBLE
DEPT DEPARTMENT
DET DETAIL
DG DECORATIVE GLASS
DIA DIAMETER
DIAG DIAGRAM
DISP DISPENSER
DL DEAD LOAD
DR DOOR
DRS DRESSING ROOM
DS DOWNSPOUT
DT DRAIN TILE
DW DISHWASHER
DWG DRAWING
E MODULUS OF ELASTICITY
EA EACH
EF EACH FACE
EGSB EXTERIOR GYPSUM SHEATHING BOARD
EIFS EXTERIOR INSULATION AND FINISH SYSTEM
ABBREVIATION TERM(S)
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMER EMERGENCY
EPA ENVIRONMENTAL PROTECTION AGENCY
EPDM ETHYLENE PROPYLENE DIENE MONOMER
EPS EXPANDED POLYSTYRENE BOARD INSULATION
EPX EPOXY RESIN
EQ EQUAL
EQL SP EQUALLY SPACED
EQUIP EQUIPMENT
ESMT EASEMENT
ETC ET CETERA AND SO FORTH
EW EACH WAY
EWS EYE WASH STATION
EXCG EXISTING CORNER GUARD
EXIST EXISTING
EXP EXPAND, EXPANDED OR EXPANSION
F FAHRENHEIT
F/F FACE TO FACE
FAB FABRIC
FD FLOOR DRAIN
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF&E FURNITURE, FIXTURE AND EQUIPMENT
FH FIRE HYDRANT
FHC FIRE HOSE CABINET
FIN FINISH
FIXT FIXTURE
FL FLOORLINE
FLR FLOOR
FLR FIN FLOOR FINISH
FM FACTORY MUTUAL
FR FIRE RATING OR RESISTANT
FR GL FRITTED GLASS
FRMG FRAMING
FRP FIBERGLASS REINFORCED PLASTIC
FRZ FREEZER
FT FOOT OR FEET
FTNG FOOTING
FURG FURRING
FURN FURNITURE
FWC FABRIC WALLCOVERING
GA GAGE
GALV GALVANIC OR GALVANIZED
GC GENERAL CONTRACTOR
GL GLASS
GLZ GLAZING
GMT GLASS MOSAIC TILE
GR GROUT
GR BM GRADE BEAM
GSB GYPSUM SHEATHING BOARD
GWB GYPSUM BOARD
ABBREVIATION TERM(S)
GYM GYMNASIUM
GYP GYPSUM
GYP BD GYPSUM BOARD
H HIGH
HB HOSE BIB
HC HANDICAP
HCP HANDICAPPED
HDO HIGH DENSITY OVERLAY
HDPE HIGH DENSITY POLYETHYLENE
HDW HARDWARE
HDWD HARDWOOD
HGR HANGER
HM HOLLOW METAL
HMD HOLLOW METAL DOOR
HMF HOLLOW METAL FRAME
HORIZ HORIZONTAL
HOSP HOSPITAL
HSKPG HOUSEKEEPING
HSS HOLLOW STRUCTURAL SECTION
HT HEIGHT
HW DOOR HARDWARE
HYD HYDRANT
Hz HERTZ
IAQ INDOOR AIR QUALITY
IB INTEGRAL BASE
IBC INTERNATIONAL BUILDING CODE
ID INSIDE DIAMETER
INT DES INTERIOR DESIGN
IF INSIDE FACE
IMH INLET MANHOLE
IMP INSULATED METAL PANEL
IN INCH OR INCHES
INSUL INSULATION
INT INTERIOR
INV INVERT
INV EL INVERT ELEVATION
ISO ISOMETRIC
ITS INTERTEK TESTING SERVICES
IW IRRIGATION WATER
JAN JANITOR
JT JOINT
KIP THOUSAND POUNDS
KIP FT THOUSAND FOOT POUNDS
KIT KITCHEN
KOP KNOCK OUT PANEL
L ANGLE, LENGTH OR LONG
LAB LABORATORY
LAG LAGGING
LAM LAMINATE
LAU LAUNDRY
LBS POUNDS
LD BRG LOAD-BEARING
LDPE LOW DENSITY POLYETHYLENE
LF LINEAR FOOT (FEET)
LIB LIBRARY
ABBREVIATION TERM(S)
LIN LINEAR
LINO LINOLEUM
LKR LOCKER
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LPT LOW POINT
LT LIGHT
LVL LEVEL
LVT LUXURY VINYL TILE
LWM LOW WATER MARK
M MOMENT
MAINT MAINTENANCE
MATL MATERIAL
MAX MAXIMUM
MB MARKER BOARD
MC MANHOLE COVER
MDO MEDIUM DENSITY OVERLAY
MECH MECHANICAL
MED MEDICAL OR MEDICINE
MEZZ MEZZANINE
MFD MANUFACTURED
MFG MANUFACTURING
MFR MANUFACTURER
MFR REC MANUFACTURER'S RECOMMENDATION
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
mm MILLIMETER
MOD BIT MODIFIED BITUMEN
MT METAL TRIM
MTD MOUNTED
MTG MOUNTING
MTL METAL
MULL MULLION
MW MICROWAVE
MWP MEMBRANE WATERPROOFING
N NEWTON OR NORTH
NF NEAR FACE
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NRCA NATIONAL ROOFING CONTRACTORS ASSOCIATION
NS NEAR SIDE
NTS NOT TO SCALE
O OXYGEN
OA OVERALL
OC ON CENTER
OCC OCCUPY, OCCUPANTS OR OCCUPANCY
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OF/CI OWNER FURNISHED/CONTRACTOR INSTALLED
OF/OI OWNER FURNISHED/OWNER INSTALLED
OFF OFFICE
ABBREVIATION TERM(S)
OH DR OVERHEAD COILING DOOR
OPNG OPENING
OPP OPPOSITE
OR OPERATING ROOM
ORD OVERFLOW ROOF DRAIN
OSHA OCCUPATIONAL SAFETY AND HEALTH
ADMINSTRATION
OVFL OVERFLOW
OZ OUNCE
P PAINT
Pa PASCAL
PART PARTIAL
PASS PASSAGE
PBD PARTICLEBOARD
PC POINT OF CURVE OR POLYCARBONATE
PRVC PRIVACY CURTAIN
PCA PORTLAND CEMENT ASSOCIATION
PCB POLYCHLORINATED BIPHENYL
PCC PRECAST CONCRETE
PCT PORCELAIN TILE
PED PEDESTAL
PERF PERFORATED
PHAR PHARMACY
PI POINT OF INTERSECTION
PIB POLYISOBUTYLENE (PLASTIC)
PIV POST INDICATOR VALVE
PKG PACKAGE
PLAM HIGH PRESSURE PLASTIC LAMINATE
PLF POUNDS PER LINEAR FOOT
PLYWD PLYWOOD
PMF PROBABLE MAXIMUM FLOOD
PO PURCHASE ORDER
POLY POLYETHYLENE PLASTIC
PP POLYPROPYLENE PLASTIC
PR PAIR
PREFAB PREFABRICATE
PRELIM PRELIMINARY
PREP PREPARATION
PS POLYSTYRENE PLASTIC
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PAINT OR PAINTED
PTT PORCELAIN TILE TRIM
PTUBE PNEUMATIC TUBE
PVA POLYVINYL ACETATE
PVC POLYVINYL CHLORIDE (PLASTIC)
PVF POLYVINYL FLUORIDE (PLASTIC)
QS QUARTZ SURFACE
QT QUARRY TILE
QTR QUARTER
QTT QUARRY TILE TRIM
QTY QUANTITY
R RADIUS, RANGE, RISER OR THERMAL RESISTANCE
RAB RABBETED
RB RESILIENT OR RUBBER BASE
ABBREVIATION TERM(S)
RBF RUBBER FLOORING
RCP REFLECTED CEILING PLAN
RDG INS SOLID RIGID INSULATION
REC RECESSED OR RECREATION
RECIP RECIPROCAL
REF REFRIGERATOR
REINF REINFORCE
REQ REQUIRE
REQD REQUIRED
REQT REQUIREMENT
RESIL RESILIENT
REST RESTROOM
RF RESILIENT FLOORING
RFS ROOM FINISH SCHEDULE
RM ROOM
RND ROUND
RO ROUGH OPENING
ROW RIGHT OF WAY
RT RESILIENT TILE
RV ROOF VENT
SAN SANITARY
SBS STYRENE BUTADIEN STYRENE
SCP SCUPPER
SD SMOKE DETECTOR OR STORM DRAIN
SDT STATIC DISSIPATIVE TILE
SECT SECTION
SEP SEPARATE
SF SAFETY FACTOR OR SQUARE FOOT (FEET)
SHT SHEET
SHTHG SHEATHING
SIM SIMILAR
SP SCIENTIFIC PANEL (TRESPA) OR STANDPIPE
SPEC SPECIFICATION
SPF SPRUCE-PINE-FIR
SQ SQUARE
SS SANITARY SEWER OR SOLID SURFACE
SSCG STAINLESS STEEL CORNER GUARD
SST STAINLESS STEEL
ST STAIRS
STN STONE (NATURAL) TILE
STW STORM WATER
STC SOUND TRANSMISSION COEFFICIENT
STD STANDARD
STIR STIRRUP
STL STEEL
STOR STORAGE
STRUCT STRUCTURAL
SUB FL SUBFLOOR
SUSP SUSPEND OR SUSPENDED
SVF SHEET VINYL FLOORING
SYS SYSTEM
T TREAD
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
TB TACKBOARD
ABBREVIATION TERM(S)
TCNA TILE COUNCIL OF NORTH AMERICA
TEMP TEMPORARY
TG TEMPERED GLASS
THK THICKNESS
THRU THROUGH
THRUOUT THROUGHOUT
TN TRUE NORTH
TOC TOP OF CURB
TOPO TOPOGRAPHY
TOS TOP OF STEEL
TOW TOP OF WALL
TP TELEPHONE POLE OR TRANSLUCENT PLASTIC
TS TENSILE STRENGTH
TW TACK WALL
TYP TYPICAL
UBC UNIFORM BUILDING CODE
UGND UNDERGROUND
UL UNDERWRITERS LABORATORIES
UNO UNLESS NOTED OTHERWISE
UON UNLESS OTHERWISE NOTED
UTIL UTILITY
VAC VACUUM
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VENT VENTILATION OR VENTILATOR
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
VOC VOLATILE ORGANIC COMPOUND
VS VENT STACK
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
W WIDE
W/ WITH
W/O WITHOUT
W/W WALL-TO-WALL
WB WOOD BASE
WC WALL COVERING
WD WOOD
WH WATER HEATER
WI WROUGHT IRON
WP WALL PROTECTION
WST WOOD STAIN
WT WEIGHT OR WINDOW TREATMENT
WWF WELDED WIRE FABRIC
X BRACE CROSS BRACE
XBRA CROSSBRACING
XFER TRANSFER
XL EXTRA LARGE
XPS EXTRUDED POLYSTYRENE BOARD INSULATION
XXH DOUBLE EXTRA HEAVY
YD YARD
YH YARD HYDRANT
YI YARD INLET
Z MODULUS OF SECTION
15 East Main, Suite 201
Vermillion SD 57069
Phone 605-624-1081
Vermillion
1221 N Street, Suite 600
Lincoln NE 68508
Phone 402-476-9700
Fax 402-476-9722
Lincoln
CONVERT IFR TO CLASSROOM -
FOSS FIELD ARMORY
SIOUX FALLS, SOUTH DAKOTA
G-001 COVER SHEET AND INDEX (THIS PAGE)
A-101 DEMOLITION FLOOR AND REFECTED CEILING PLANS
M-001 PLUMBING AND HVAC COVER SHEET
INDEX OF DRAWING
GENERAL
ARCHITECTURAL
MECHANICAL
VICINITY MAP
95% REVIEW DOCUMENTS FOR:
NATIONAL GUARD DR.
F
O
S
S
F
I
E
L
D
A
R
M
O
R
Y
ADDRESS: 801 W NATIONAL GUARD DR.
TO N MINNESOTA
AVE.
CFMO# SF466146
I-90
I-29
N. M
innesota A
ve
Sioux Falls
Regional Airport
See enlarged map above
A-102 FURNITURE, FLOOR, AND REFLECTED CEILING PLANS
A-201 INTERIOR ELEVATIONS, DETAILS AND WALL SECTIONS
E-101 ELECTRICAL PLAN - DEMOLITION AND NEW
ELECTRICAL
E-501 ELECTRICAL DETAILS
M-101 PLUMBING AND HVAC PLAN
A-601 DOOR, FINISH AND WALL TYPE SCHEDULES AND DETAILS
CODE INFORMATION
CODE REVIEW 2018 INTERNATIONAL BUILDING CODE
OCCUPANCY GROUP: B, BUSINESS
FIRE SPRINKLER: NONE
FIRE ALARM: NEW FIXTURES
FIRE ALARM DETECTION: SMOKE ALARM
COMMON PATH OF TRAVEL: 75'-0" MAX.
FIRE PROTECTION FEATURES:
FIRE RATED SEPARATION: 1 HR. EXISTING CORRIDOR
ALLOWABLE BUILDING AREA: NO AREA ADDED TO BUILDING, INTERIOR REMODEL
OCCUPANT LOAD FACTOR: 100 OFFICE AREAS
20 NET AREA, CLASSROOM
NO. OF EXITS: 2
E-502 ELECTRICAL DETAILS AND SYMBOL LEGEND
Cover Sheet
and Index
AUTHOR
CHECKED:
DAVIS DESIGN ALL RIGHTS RESERVED
SHEET TITLE
SHEET NUMBER
ID
ISSUE DATE:
DescriptionDate
Revisions:
15 E
ast M
ain, S
uite 201
Verm
illion S
D 57069
Phone 605-624-1081
Verm
illion
1221 N
S
treet, S
uite 600
Lincoln N
E 68508
Phone 402-476-9700
Fax 402-476-9722
Lincoln
G-001
07-16-2020
D.W.
D.H.
G-0
01
CLIENT INFORMATION
PROJECT INFORMATION
South Dakota
Army National
Guard
801 W National Guard Dr.
Sioux Falls, S.D 57104
CFMO# SF466146
Convert IFR
to Classroom -
Foss Field
Armory
20-0067Job #
MECHANICAL
225
FOOD STORAGE
156
VESTIBULE
71
RIFLE RANGE
224
2
4
6
3 4
4
11
11
1
8
1010
9
13
14
15
16
16
OFFICE
229
MECHANICAL
225
WOMENS LATRINE
227
MENS LATRINE
155
OFFICE
79
FOOD STORAGE
156
FOOD PREPERATION
157
SCULLERY
251
TRAINING
ROOM
233
STORAGE
232
STORAGE
231
TRAINING
ROOM
230
CORRIDOR
70
VESTIBULE
71
VESTIBULE
71
RIFLE RANGE
224
ASSEMBLY HALL
161
CORRIDOR
162
STORAGE
FLAMMABLE
MATERIALS
158
ASSEMBLY HALL
159B
ELECTRICAL ROOM
142
TELEPHONE ROOM
141
FURNANCE ROOM
140
CORRIDOR
139
JANITOR
143
TRAINING ROOM
144
ELECTRICAL
179
CORRIDOR
177
CORRIDOR
177A
VESTIBULE
178
TRAINING ROOM
182
F.
E.
A.
B.
C.
D.
G.
KEY NOTES:
GENERAL NOTES:
REMOVE EXISTING H.M. DOOR, FRAME AND HARDWARE.
EXISTING L.V.T. FLOORING TO REMAIN. PROTECT FROM DAMAGE
DURING CONSTRUCTION.
SAW CUT AND REMOVE EXISTING CMU. REMOVE BRICK AND
INSULATION FOR NEW DOOR, FRAME AND LINTEL. SALVAGE
EXISTING BRICK FOR REUSE, IF NEEDED FOR INFILL AT LINTEL.
NEW BRICK SHALL BE TOOTHED-IN. REMOVE MASONRY, BRICK
AND INSULATION TO BELOW FLOOR TO ALLOW INSTALLATION OF
STOOP. COORDINATE EXTENT OF DEMOLITION WITH NEW
DETAILS. NEW BRICK SHALL BE TOOTHED-IN.
SAW CUT AND REMOVE EXISTING CMU. REMOVE BRICK AND 2"
RIGID INSUL FOR NEW WINDOW FRAME AND LINTEL.
COORDINATE EXTENT OF DEMOLITION WITH NEW DETAILS,
SHEET A-601 FOR SIZE OF WINDOW OPENING. LOCATE WINDOW
OPENING PER SHEET A-102. SALVAGE EXISTING BRICK FOR
REUSE, IF NEEDED FOR INFILL ABOVE LINTEL. NEW BRICK SHALL
BE TOOTHED-IN.
EXISTING PAINTED PRECAST CORED PLANK CEILING
STRUCTURE. BEARING OF CORED PLANK AT 10'-0" A.F.F.
SAWCUT AND REMOVE EXISTING SIDEWALK AND PAVING AS
REQUIRED TO INSTALL STOOP. REFER TO NEW DETAILS FOR
EXTENT OF REMOVAL.
REMOVE EXISTING G.W.B. CEILING AND HAT CHANNEL FRAMING
AS REQUIRED FOR INSTALLATION OF MECHANICAL ITEMS.
REINSTALL TO MATCH EXISTING. REFER TO MECHANICAL
DRAWINGS. COORDINATE EXTENT OF REMOVAL WITH CONTR.
SAW CUT AND REMOVE EXISTING FLOOR AS REQUIRED TO TIE
WASTE LINE INTO EXISTING. REFER TO MECHANICAL DRAWINGS.
PROTECT EXISTING EPOXY FLOOR ADJACENT TO DEMOLITION
WITH CARDBOARD, TAPED IN PLACE. PROTECT EXISTING
EQUIPMENT FROM DUST AND DEBRIS WITH FIRE RATED PLASTIC
SHEETING.
REMOVE EXISTING PARKING SIGNAGE. REINSTALL WHERE
DIRECTED BY OWNER.
PROVIDE REPLACEABLE STICKY WALK-OFF MATS DURING
CONSTRUCTION TO LIMIT THE SPREAD OF DUST.
SAW CUT AND REMOVE EXISTING CMU. REMOVE BRICK AND 2"
RIGID INSUL FOR NEW WINDOW FRAME AND LINTEL AS PART OF
ALTERNATE #1. COORDINATE EXTENT OF DEMOLITION WITH NEW
DETAILS, SHEET A-601 FOR SIZE OF WINDOW OPENING. LOCATE
WINDOW OPENING PER SHEET A-102. SALVAGE EXISTING BRICK
FOR REUSE, IF NEEDED FOR INFILL ABOVE LINTEL. NEW BRICK
SHALL BE TOOTHED-IN.
EXISTING OPENING IN PRECAST CORED-PLANK CEILING.
EXISTING WALK/PAVEMENT JOINT.
EXISTING BOLLARD TO REMAIN.
ALTERNATE #1. EXISTING BRICK EXP. JOINT. REMOVE BRICK AND
SEALANT AT JAMB OF WINDOW WHERE NEW WINDOW IS
INSTALLED.
REMOVE ADDITIONAL CONCRETE AT WALK AND PAVEMENT AS
REQUIRED TO INSTALL STOOP. SLOPE CONCRETE AT 5%
MAXIMUM ALONG WALK TO MEET EXISTING SURFACE OF WALK.
1
2
3
4
5
REMOVE ITEM'S SHOWN WITH HEAVY DASHED LINETYPE UNLESS
NOTED OTHERWISE.
WHERE DEMOLITION OCCURS NEXT TO EXISTING CONSTRUCTION
TO REMAIN, MATCH PATCH AND REPAIR DISTURBED AREA TO A
LEVEL CONSISTENT WITH THE EXISTING CONSTRUCTION TO
REMAIN.
PROTECT ALL ITEMS, MATERIALS AND/OR SURFACES NOT
SCHEDULED TO BE DEMOLISHED.
REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR
DEMOLITION OF MECHANICAL AND ELECTRICAL ITEMS.
AREAS OF DEMOLITION SHALL BE KEPT CLEAN AND SAFE.
DISPOSE OF DEBRIS DAILY AND CLEAN AREAS OF WORK UPON
COMPLETION.
KEEP DOORS TO SPACE CLOSED DURING DEMOLITION.
EXISTING PVC SIKA SARNAFIL ROOF IS UNDER A 20 YEAR
WARRANTY. WARRANTY SERIAL NO.: 0000012513-368313.1. NEW
WORK DONE TO EXISTING ROOFING SHALL MAINTAIN EXISTING
WARRANTY.
PROVIDE TEMPORARY, SECURE AND WEATHERPROOF
ENCLOSURES TO EXTERIOR OPENINGS TO PROTECT WALL
ASSEMBLY FROM WATER INTRUSION.
6
7
8
9
10
H.
11
12
13
14
15
16
MECHANICAL
225
FOOD STORAGE
156
VESTIBULE
71
RIFLE RANGE
224
7
5
12
12
Demolition
Floor and
Refected
Ceiling Plans
AUTHOR
CHECKED:
DAVIS DESIGN ALL RIGHTS RESERVED
SHEET TITLE
SHEET NUMBER
ID
ISSUE DATE:
DescriptionDate
Revisions:
15 E
ast M
ain, S
uite 201
Verm
illion S
D 57069
Phone 605-624-1081
Verm
illion
1221 N
S
treet, S
uite 600
Lincoln N
E 68508
Phone 402-476-9700
Fax 402-476-9722
Lincoln
A-101
07-16-2020
D.W.
D.H.
A-1
01
SCALE:
1
Demolition Floor Plan
1/4" = 1'-0"
CLIENT INFORMATION
PROJECT INFORMATION
South Dakota
Army National
Guard
801 W National Guard Dr.
Sioux Falls, S.D 57104
CFMO# SF466146
Convert IFR
to Classroom -
Foss Field
Armory
20-0067Job #
KEY PLAN
AREA OF WORK
SCALE:
1
Demolition Reflected Ceiling Plan
1/4" = 1'-0"
1
1
MECHANICAL
225
VESTIBULE
71
6
Classroom
224
Office
224D
Office
224C
Office
224B
Office
224A
Corridor
224-1
1
A-201
2
A-201
3
A-201
3'-8" 3'-4" 3'-4" 3'-8" 3'-8"
8'-10 5/8"
4 7/8"
4'-1 3/8"
4 7/8"
8'-8"
1'-0"
4'-0"
20'-4"
3'-8"
11'-0"
3'-8"
25'-0"
3'-8"
224
1A
A-201
224-1
224B224A
224C
224D
ALT #2
9
A-201
01
01
01
01
01
01
02
02
02
02
02
02
02
02
02
01
01
5
5
1
18
18
AW-1
AW-1
AW-1
AW-2
AW-1
2
9
PANEL L2
4
16
13'-3 1/8"
4 7/8"
13'-4 7/8"
17
11
2%
M
AX
.
5% MAX.
5% MAX.
RIFLE RANGE
224
PANEL L2
A.
B.
KEY NOTES:
DIMENSIONS OF DOOR AND WINDOW ROUGH OPENINGS
ARE NOMINAL AND DO NOT ACCOUNT FOR SHIM SPACE
AT EACH SIDE OF OPENING.
NEW BRICK SHALL BE TOOTHED-IN.
OWNER HAS LIMITED BRICK TYPE 1 (BLEND). VERIFY
OWNER QUANTITY AND AVAILABILITY OF SPECIAL TYPES
AS INDICATED.
PROVIDE COLORED MORTAR TO MATCH EXISTING. FIELD
VERIFY.
PROVIDE BRICK MOCK-UP TO VERIFY BRICK TEXTURE,
BLEND AND COLOR OF BRICK TYPE 1, BRICK TEXTURE
AND COLOR OF BRICK TYPE 2 AND MORTAR COLOR TO
MATCH EXISTING. REFER TO DETAIL 11/A-201 FOR BRICK
DETAILS.
OFFICE FURNITURE IS FOR DEMONSTRATION OF
PROPOSED LAYOUT FOR OWNER USE ONLY.
GENERAL NOTES:
ALUMINUM BLAST WINDOW. REFER TO SPECIFICATIONS
AND TO DETAILS, SHEET A-601.
DASHED LINE INDICATES CABINETS UNDER ALTERNATE
#2. REFER TO SHEET A-201.
REFRIGERATOR, BY ONWER
EXISTING LIGHT FIXTURE
EXISTING DOWNSPOUT.
EXISTING BRICK EXPANSION JOINT LOCATION. NEW
BRICK EXPANSION JOINT AT JAMB OF WINDOW TO
CONTINUE JOINT THROUGH NEW CONSTRUCTION.
CLOSE EXISTING OPENING IN PRECAST CORED CEILING
WITH 6" METAL STUD FRAMING AT 16" O.C., 16" THERMAL
BATT INSULATION AND 5/8" G.W.B. CEILING, PAINT G.W.B.
CEILING WHITE. PROVIDE BACKER ROD AND SEALANT
BETWEEN EDGE OF G.W.B AND EXISTING PRECAST
CORED PLANKS.
EXISTING OPENING FOR DUCTWORK ABOVE. REFER TO
MECHANICAL DRAWINGS.
TV MOUNTING BRACKET, REFER TO 10/A-201. VERIFY
EXACT LOCATION ON WALL WITH USERS.
WOOD BLINDS, REFER TO SPECIFICATIONS.
COFFEE MAKER, BY OWNER.
PRINTER, BY OWNER.
SHREDDER, BY OWNER.
OFFICE FURNITURE, TABLES AND CHAIRS BY OWNER.
PATCH AND PAINT EXISTING CEILING WITH G.W.B.
PATCH FLOOR WITH CONCRETE OVER COMPACTED AND
TESTED SUBGRADE WITH GRANULAR FILL AND VAPOR
BARRIER TO MATCH EXISTING. FINISH CONCRETE TO
ACCEPT EPOXY COATING BY OTHERS TO MATCH
EXISTING.
FIRE EXTINGUISHER CABINET, REFER TO 13/A-201
ALUMINUM BLAST WINDOW UNDER ALTERNATE #1.
REFER TO SPECIFICATIONS AND TO DETAILS, SHEET
A-601. NEW WORK AT THIS OPENING IS UNDER
ALTERNATE #1. IF ALTERNATE #1 IS NOT ACCEPTED,
CONTINUE WALL TYPE 02 THROUGH WINDOW OPENING.
C.
D.
E.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
F.
MECHANICAL
225
VESTIBULE
71
8
Classroom
224
Office
224D
Office
224C
Office
224B
Office
224A
Corridor
224-1
12
A-201
7
A2 A2
A2 A2
A2 A2
A2 A2
A2 A2
A2 A2
A2
A2
A2
A2
A2
A2
A2
A2
A1
A1
A1
X1
X1
PANEL L2
PP
X1
15
MECHANICAL
225
VESTIBULE
71
Classroom
224
Office
224D
Office
224C
Office
224B
Office
224A
Corridor
224-1
72"x30" 72"x30"
72"x30" 72"x30"
72"x30" 72"x30"
72"x30" 72"x30"
72"x30" 72"x30"
72"x30" 72"x30"
72"x30" 72"x30"
3
11
12
13
14
14
14
14
14
14
14
14
1414
14
14
14
14
PANEL L2
Furniture,
Floor, and
Reflected
Ceiling Plans
AUTHOR
CHECKED:
DAVIS DESIGN ALL RIGHTS RESERVED
SHEET TITLE
SHEET NUMBER
ID
ISSUE DATE:
DescriptionDate
Revisions:
15 E
ast M
ain, S
uite 201
Verm
illion S
D 57069
Phone 605-624-1081
Verm
illion
1221 N
S
treet, S
uite 600
Lincoln N
E 68508
Phone 402-476-9700
Fax 402-476-9722
Lincoln
A-102
07-16-2020
D.W.
D.H.
A-1
01
SCALE:
1
Floor Plan
1/4" = 1'-0"SCALE:
2
Reflected Ceiling Plan
1/4" = 1'-0"
CLIENT INFORMATION
PROJECT INFORMATION
South Dakota
Army National
Guard
801 W National Guard Dr.
Sioux Falls, S.D 57104
CFMO# SF466146
Convert IFR
to Classroom -
Foss Field
Armory
20-0067Job #
KEY PLAN
SCALE:
3
Furniture Plan
1/4" = 1'-0"
AREA OF WORK
1'-7 1/2" 2'-9"
7
A-102
3'-0"
LOCK DOORS AND
DRAWERS AS INDICATED
8
A-102
2'-1
0"
VINYL BASE AT CABINET
TOE KICK AND AT CABINET
RETURN, TYPICAL.
4"
3'-0"
7
A-102
3'-0" 3'-0"
LOCK DOORS AND
DRAWERS AS INDICATED
2'-1
0"
VINYL BASE AT CABINET
TOE KICK AND AT CABINET
RETURN, TYPICAL.
4"
3'-0"3'-0"
7
A-102
2'-0"
LOCK DOORS AND
DRAWERS AS INDICATED
2'-1
0"
VINYL BASE AT CABINET
TOE KICK AND AT CABINET
RETURN, TYPICAL.
4"
3'-0" 1'-6" 2'-9"
7
A-102
2'-6" 2'-6"
LOCK DOORS AND
DRAWERS AS INDICATED
8
A-102
2'-1
0"
VINYL BASE AT CABINET
TOE KICK AND AT CABINET
RETURN, TYPICAL.
4"
2'-9" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0"1'-7 1/2"
1'-6" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0"1'-6"
1'-4
"1
0"
1'-8
"
6
A-102
5
A-102
4
A-102
1/4" MELAMINE BTM.
1/2" POPLAR DWR W/
MELAMINE INT.
SOLID
6"
1/4
"
4 3
/4
"
OVER 3/4" PLYWD.
1" SHELF
ADJ. SHELF AND DOOR
1/4" PLYWD.
WD. BASE 4" RUBBER BASE
3"
2'-0"
1 1
/2
"
1/4
"
1'-1
0"
4"
K.V. #255 WITH #256
BRACKETS
WITH 3 MM EDGES
PLAM OVER P. BD.
1'-8 1/2"
LOCKS, WHERE
INDICATED
2"
3"
FOR TYPE AND SIZE
SEE MECH. DWGS.
1/4
"
1 1
/2
"
3 1/2"
2'-0"
EDGE, TYP.
WATERFALL FRONT
3/4" POST FORMED PLAM C.T.
OVER 3/4" PLYWD.
SEAL AT
1/4" PLYWD.
1'-0"
2'-6
"
REFER TO
WALL TYPES
EDGES
ADJ. SHELF AND DOOR- PLAM
OVER P. BD. WITH 3 MM
K.V. #255 WITH #256 BRACKETS
OR EQUAL. (TYP. ALL SHELVES)
4" RUBBER BASE
1" SHELF
1'-8 1/2"
BACKSPLASH
4"
11"
8"
2'-3
" M
IN
. C
LE
AR
AN
CE
F
OR
A
DA
2'-1
0" M
AX
IM
UM
H
EIG
HT
F
OR
A
DA
TILE, SEE ELEV.
PLAM OVER P.B.
REMOVABLE 3/4"
WITH 3 MM EDGES
PLAM OVER P. BD.
5 1
/4
"
ADA CLEARANCE
KNEE VALANCE
1/4" PLYWD.
1'-0"
1'-6
"
REFER TO
WALL TYPES
K.V. #255 WITH #256 BRACKETS
OR EQUAL. (TYP. ALL SHELVES)
PLAM INT.
1/4" PLYWD.
1'-0"
1'-8
"
REFER TO
WALL TYPES
EDGES
ADJ. SHELF AND DOOR- PLAM
OVER P. BD. WITH 3 MM
K.V. #255 WITH #256 BRACKETS
OR EQUAL. (TYP. ALL SHELVES)
1" SHELF
1'-0
"
EDGE, TYP.
WATERFALL FRONT
SEAL AT
BACKSPLASH
4"
3/4" POST FORMED PLAM C.T.
1'-6"
HORIZ. J-BOX
ON 1 1/2" EPOXY ANGLE
WITH 3 MM EDGES
ESCUTCHEON
SCREW ATTACH WITH
DECORATIVE WASHERS
9"
MELAMINE INT. MELAMINE INT.
MELAMINE INT.
1" PLAM BOT.
WITH 3MM EDGES
6" CONCRETE
SLAB W/ #4'S @ 12"
O.C. EACH WAY ON
4" SLABFORM BY
VOIDFORM OR EQ.
2'-6"
#4 DOWELS
@ 12" O.C.
2'-0"
#4'S AT 12" O.C.
EPOXY INTO
EXIST. FTG. AND
FDN. WALL 4"
WITH HIT- HY 200
OR EQUAL
3'-4" (VERIFY)
#4'S @ 1'-4" O.C.
VERTICAL
8"
4'-0", VERIFY (x4'-2" WIDE)
EXIST. PAVEMENT
4'-0" V
ER
IF
Y1'-0"
1/2" EXP. JNT. W/
BACKER ROD AND
SEALANT. MATCH
EXISTING LOC.
2% MAX SLOPE, MATCH EXIST PVMNT.
EXIST.
FOUNDATION
3" 5 3/4" 8 3/8"
LVT FLOOR
PATCH TO
MATCH EXISTING.
#4'S AT 12" O.C.
EPOXY INTO
EXIST. FDN.
WALL 4" WITH
HIT- HY 200 OR
EQUAL
2'-6"
60°
COMPACT
SUBGRADE IN
8" LIFTS
PROVIDE NEW OR
SALVAGED S.S.
FLASHING TO MATCH
EXIST. AT NEW BRICK
CUSTOM BRICK,
TYP. AT RETURN
SET THRESHOLD IN FULL
BED OF SEALANT.
1/2" EXP. JNT. MAT. WITH
B.R. AND SEALANT.
6'-8
" A
.F
.F
. V
ER
IF
Y
8" V
ER
IF
Y
1'-10
"
L
C
ELEC. OUTLET
DATA OUTLET
T.V. MOUNT BY OWNER
SOLID WOOD BLOCKING
J-BOX
VERIFY SIZE
MET. STUDS, REFER TO WALL TYPES
1'-6"
Scale:
10
T.V. Mounting Detail
1 1/2" = 1'-0"
J-BOX
V
V
B
B
V = VELOUR FACE TO MATCH EXISTING
B = BARK FACE TO MATCH EXISTING
PROVIDE MODULAR BRICK SIZES:
3 5/8" x 2 1/4" x 7 5/8"
TYPE 1 CUSTOM BRICK TYPE 2 CUSTOM BRICK
PROVIDE IN 3 COLORS (BLEND) PROVIDE IN 1 COLOR
PROVIDE BRICK INDICATED AT JAMBS
OF WINDOWS AND DOORS
4"
4"
1"
VERIFY
54
" A
.F
.F
. (M
AX
.)
T.O
. C
AB
IN
ET
T
O F
IN
. F
LR
.
Interior
Elevations,
Details and
Wall Sections
AUTHOR
CHECKED:
DAVIS DESIGN ALL RIGHTS RESERVED
SHEET TITLE
SHEET NUMBER
ID
ISSUE DATE:
DescriptionDate
Revisions:
15 E
ast M
ain, S
uite 201
Verm
illion S
D 57069
Phone 605-624-1081
Verm
illion
1221 N
S
treet, S
uite 600
Lincoln N
E 68508
Phone 402-476-9700
Fax 402-476-9722
Lincoln
A-201
07-16-2020
D.W.
D.H.
A-1
01
CLIENT INFORMATION
PROJECT INFORMATION
South Dakota
Army National
Guard
801 W National Guard Dr.
Sioux Falls, S.D 57104
CFMO# SF466146
Convert IFR
to Classroom -
Foss Field
Armory
20-0067Job #
SCALE:
3
Elevation
1/4" = 1'-0" SCALE:
2
Elevation
1/4" = 1'-0" SCALE:
1A
Elevation (Alternate #2)
1/4" = 1'-0"
SCALE:
5
Cab. Section
3/4" = 1'-0" SCALE:
4
Cab. Section
3/4" = 1'-0"
SCALE:
1
Elevation
1/4" = 1'-0"
SCALE:
8
Cab. Section
3/4" = 1'-0" SCALE:
6
Cab. Section
3/4" = 1'-0"SCALE:
7
Cab. Section
3/4" = 1'-0"
SCALE:
9
Stoop Section
3/4" = 1'-0"SCALE:
11
Custom Brick Detail
3" = 1'-0"SCALE:
12
Bulkhead Detail
1 1/2" = 1'-0"SCALE:
13
FEC Cabinet Detail
1 1/2" = 1'-0"
2"
SEE SCHED.
HMF-1
Scale:
1
H.M. Frame Types
1/4" = 1'-0"
2"
SE
E S
CH
ED
UL
E
3 3
/8
"
2"
SEE SCHED.
HMF-2
2"
SE
E S
CH
ED
UL
E
2"
SE
E S
CH
EU
DL
E
A
Scale:
2
Door Types
1/4" = 1'-0"
B
GL-1 AT FIRE
RATED DOORS
SEE SCHED.
SE
E S
CH
EU
DL
E
2'-1
"
8"
4"
3'-7
"
2"
SEE SCHED.
2"
SE
E S
CH
ED
UL
E
4"
HMF-3
GL-2
SE
E S
CH
EU
DL
E
2'-1
"
C
SEE SCHED.
4"
8"
3'-7
"
Scale:
11
Bearing Detail
3" = 1'-0"
1 1/2" LONG SLOT AT BEAM FLANGE.
ANCHOR ROD SHALL BE LOCATED AT
CENTER OF SLOT, COORDINATE.
1/2"
5" x 7 5/8" x 3/4" EMBED PLATE WITH TWO
3/4" DIA. x 12" LONG ANCHOR RODS. CUT
CMU TO FIT EMBED PLATE.
Scale:
7
Head Detail
3" = 1'-0"
SEALANT IN 1/4" JOINT
8"x8" CMU. GROUT SOLID WITH 1#4
6 3/8"
Scale:
8
Jamb Detail
3" = 1'-0"
1'-2
" E
XIS
TIN
G W
AL
L T
HIC
KN
ES
S
VE
RIF
Y
BACKERROD AND
SEALANT EACH SIDE
OF WINDOW FRAME
3"
PATCH FACE BRICK
TO MATCH EXIST.
EXIST. BRICK
EXIST. C.M.U.
1-#4 IN CELL,
GROUT SOLID
8" x 8" CMU
REFER TO WALL
TYPES.
METAL CORNER
BEAD, TYP.
CORRUGATED
1" BRICK TIE
AT 16" O.C.
BACKER ROD AND
SEALANT IN 1/4" JOINT
BTW. GWB AND FRAME
ADHERED 5/8"
DRYWALL TO CMU
Scale:
9
Head Detail
3" = 1'-0"
R.O. AT 8'-8" A.F.F.
W8x18
BACKERROD AND
SEALANT EACH SIDE
3"
.060" EPDM. FLASHING, EXTEND
UP BEHIND MOISTURE BARRIER,
ADHERE TO SURFACES, SEAL
EDGES TO MASONRY BEYOND.
MOISTURE BARRIER, SEAL
AT PERIMETER.
EXTERIOR GYP. SHEATHING
OVER 1 5/8" MET. STUDS AT
16" O.C., MAX.
2" RIGID INSULATION
1/2" x 1'-1" x 3'-7" GALV.
PLATE, WELD TO BM.
WEEPS AT 24" O.C.
VERIFY
11
A-601
FILL CAVITY WITH
THERMAL INSUL.
3 3
/8
" V
ER
IF
Y
R.O. AT 8'-0" A.F.F.
W8x18
BACKERROD AND
SEALANT EACH SIDE
WD. SHIM
3"
MOISTURE BARRIER, SEAL
AT PERIMETER.
EXT. GYP. SHEATHING
OVER 1 5/8" MET. STUDS
AT 16" O.C., MAX.
2" RIGID INSULATION
WEEPS AT 24" O.C.
5 3/4"
SPRAY FOAM
FRAME SOLID
11
A-601
FILL CAVITY WITH
THERMAL INSUL.
2 - 3 5/8" MET. STD.
BOX HEADER
Scale:
10
Sill Detail
3" = 1'-0"
R.O. AT 3'-4" A.F.F.
BACKERROD AND
SEALANT EACH SIDE
1/4" WD. SHIM W/
FULL SPRAY FOAM
INSUL.
3" VERIFY
SILICONE SEAL
PENETRATIONS IN
FLASHING
TURN UP THRU-WALL
FLASHING 1/2", HEM EXP. EDGE
PRE-FIN .032" ALUMINUM
THRU-WALL FLASHING, FULL
WIDTH OF OPENING. HEM
EXPOSED EDGE. SILICONE SEAL
IN PLACE OVER BRICK. PROVIDE
DK. BRONZE TO MATCH EXIST.
BACKER ROD AND SEALANT
AT SILL. VERIFY LOC. WITH
WINDOW MFR.
TURN UP THRU-WALL
FLASHING AT JAMB AND SEAL
TO MASONRY
BR
IC
K T
YP
E 2
BR
IC
K T
YP
E 1
R.O. AT 8-0" A.F.F.
BR
IC
K T
YP
E 2
BR
IC
K T
YP
E 1
B.R. AND
SEALANT
STEEL LINTEL, REFER TO DET. FOR SIZE
2" RIGID INSUL.
2 1/2" x 3 1/2" LLV GALV.
ANGLE. SCREW TO
MASONRY AT 16" O.C.
1/4" JOINT WITH BACKER ROD AND
SEALANT. PROVIDE 1/2" JOINT AT
BRICK EXP. JOINT FOR AW-2
SILICONE SEAL BETWEEN
FLASHING AND BRICK.
1/4" SHIM. PROVIDE
1/2" SHIM AT B.E.J.
WITH FULL SPRAY
FOAM INSUL.
W8 BM.
BR
IC
K T
YP
E 2
BR
IC
K T
YP
E 2
2 - 3 5/8" MET. STD.
BOX HEADER
1/2" x 1'-1" x 3'-3" GALV.
PLATE, WELD TO BM.
.060" EPDM. FLASHING,
EXTNED UP BEHIND MOISTURE
BARRIER, ADHERE TO
SURFACES, SEAL EDGES TO
MASONRY BEYOND.
BR
IC
K T
YP
E 1
3'-4" A.F.F. (N.T.S.)
BR
IC
K T
YP
E 1
REFER TO
WALL TYPES.
R.O. AT 7-4" A.F.F.
REFER TO
WALL TYPES.
ACOUS. CLG.
TILE AND
SUSP. SYS.
3/4" PLAM (MARINE
GRADE) STOOL OVER
1/2" PLY. WD.
2 1/2" WOOD BLINDS
WITH DECORATIVE
WOOD VALANCE
HB-200-2 BRICK
TIE AT 16" O.C.
ALUM. WINDOW
2 1/2" x 3 1/2" GALV.
ANGLE. SCREW TO
MASONRY AT 16" O.C.
ALUM. WINDOW
RECEPTOR IF REQ'D.
ALUM. WINDOW
RECEPTOR IF REQ'D.
EXTEND REINF. INTO EXISTING GROUTED
MASONRY CELL BELOW 4" MIN. WITH
HIT-HY 200. IF NOT GROUTED EXTEND
REINF AS DEEP AS POSSIBLE, VERIFY,
GROUT SOLID.
GROUT CORE SOLID
1 1
/2
"
PLAM
PLAM
1/4" SHIM WITH FULL
SPRAY FOAM INSUL.
HGT. OF SUPPORTFACING
Interior Partition Schedule
SUPPORTTYPE
WIDTH
ACTUAL
NOTESRTG. INSUL.
MATERIAL
OPN'G DOOR FRAMERATING
MATERIALWIDTH
#
224
224A
HEIGHT THICKNESS
7'-0"
7'-0" 1 3/4"
LABELTYPE
S.C. WD.
TYPE
HMF-1 H.M.
Door and Frame Schedule
FRAME DETAILS OPN'G
R. JAMBHEAD L. JAMB HDWR #SILL
HW-2
# NOTES
224C 7'-0"
1 3/4"
1 3/4" S.C. WD.
HMF-1
H.M.
S.C. WD. B
HW-2
3'-0" HW-1
224B
3'-0"
3'-0"
3'-0"
7'-0" 1 3/4" S.C. WD.
HMF-1
H.M.
HW-2
12/A-60112/A-60113/A-601
3/A-6014/A-6015/A-601
224-1
224D 3'-0" 7'-0" 1 3/4" S.C. WD.
HMF-3 H.M.
HMF-1 H.M.
HW-3
HW-2
7'-0" 1 3/4" H.M.3'-0" A HMF-2 H.M. 8/A-6018/A-6017/A-601
224
224A
224C
224B
224-1
224D
C
C
C
C
60 MIN.
12/A-601
13/A-601
13/A-601
12/A-601 12/A-601
12/A-601
13/A-601
12/A-601
12/A-601
ROOM DESIGNATIONS FINISHBASE
MATERIALRM. NAME
224-1CORRIDOR
VB-1
Room Finish Schedule
SOUTHNORTH EAST WEST
224A
VB-1CLASSROOM
224
VB-1
1, 3, 4, 5, 6
1, 2, 10
RM. NO.
REMARKSFLOOR
MATERIAL
EXIST. LVT
CEILING
FINISH HEIGHT
1, 2, 3, 7, 8, 9, 10
1, 2, 10
PT-1 PT-1 PT-1PT-1
EXIST. LVT PT-1 PT-1 PT-1PT-1
PT-1 PT-1 PT-1PT-1
ACT-1 8'-6"
OFFICE EXIST. LVT 8'-6"
ACT-1
ACT-1
8'-0"
224B VB-1 PT-1PT-1 PT-1 PT-1 EXIST. LVTOFFICE
224C
ACT-1 8'-6"
PT-1 PT-1VB-1 PT-1OFFICE
PT-1 EXIST. LVT ACT-1 8'-6"
224D PT-1VB-1 PT-1PT-1PT-1OFFICE
EXIST. LVT ACT-1 8'-6" 1, 2 10
1, 2
Scale:
3
Jamb Detail
3" = 1'-0"
ADHERED
5/8" G.W.B.
SPRAY FOAM
FRAME SOLID
SEALANT EA.
SIDE OF FRAME
1/2
"
SEE FLOOR PLAN
FOR DOOR
HANDING, TYP.
1/2
"
5 3
/4
"
SPRAY FOAM
FRAME SOLID
SEALANT EA.
SIDE OF FRAME
1/2
"
SEE FLOOR PLAN
FOR DOOR
HANDING, TYP.
1/2
"
2"
5 3
/4
"
EXISTING
C.M.U.
REFER TO WALL
TYPES.
METAL CORNER
BEAD, TYP.
7 5
/8
"
Scale:
4
Jamb Detail
3" = 1'-0"
5 3/4"
4"
SEE FLOOR PLAN
FOR DOOR
HANDING, TYP.
SEALANT EA. SIDE
OF FRAME
7 5/8", VERIFY
SRAY FOAM
FRAME SOLID
Scale:
5
Head Detail
3" = 1'-0"
10
7'-4
"
B.O
. S
TE
EL
P
LA
TE
EXIST STEEL LINTEL, PAINT
TO MATCH EXISTING.
REFER TO WALL
TYPES.
Scale:
6
Jamb Detail
3" = 1'-0"
1'-2
" E
XIS
TIN
G W
AL
L T
HIC
KN
ES
S
SEE FLOOR PLAN
FOR DOOR
HANDING, TYP.
2"
5 3
/4
"
BACKERROD AND
SEALANT EACH SIDE
OF DOOR FRAME
3"
PATCH FACE
BRICK TO MATCH
EXIST.
SPRAY FOAM
FRAME SOLID
EXIST. BRICK
EXIST. C.M.U.
1-#4 IN CELL,
GROUT SOLID
8" x 8" CMU
REFER TO WALL
TYPES.
METAL CORNER
BEAD, TYP.
CORRUGATED
1" BRICK TIE
AT 16" O.C.
BACKER ROD AND
SEALANT IN 1/4" JOINT
ADHERED 5/8"
DRYWALL TO CMU
J-BEAD, HOLD OFF
OF DOOR FRAME 1/4"
2" RIGID
INSULATION
TREATED WOOD
BUCK WITH S.S.
FASTENER
EXTNED UP BEHIND MOISTURE
HB-200-2 BRICK
TIE AT 16" O.C.
SEE FLOOR PLAN
FOR DOOR
HANDING, TYP.
RE
FE
R T
O W
ALL T
YP
ES
FO
R W
ALL T
HIC
KN
ES
S
2"
TWO STUDS AT
JAMB, TYP.
1/2"
1/2"
Scale:
12
Jamb Detail
3" = 1'-0"
TWO 4" METAL
STUD HEADER IN
RUNNER
2"
SEE FLOOR PLAN
FOR DOOR
HANDING, TYP.
REFER TO WALL TYPES
FOR WALL THICKNESS
1/2" 1/2"
Scale:
13
Head Detail
3" = 1'-0"
SEALANT EA. SIDE
OF FRAME
SEALANT EA. SIDE
OF FRAME
F.O. ADJACENT WALL
WHERE INDICATED
2"
AW-1
R. JAMBHEAD
10/A-601 11/A-601
FRAME
TYPE
AW-2
Aluminum Window Schedule
MULLION DETAIL
GL-2
Glazing Schedule
L. JAMB
3/16" PLATINUM F BY GLASSOPOLIS
SILL
9/A-6019/A-601
9/A-6019/A-60110/A-601
FRAME DETAILS
14/A-601
14/A-60111/A-601
TYPE
GLASS
GL-1
CLEAR, TEMPERED
GL-3BALLISTIC/BLAST RATED, INSULATED, LOW-E, BRONZE TINTED
DESCRIPTION
NOTE: ALUMINUM WINDOW FRAMES SHALL BE 2 1/2" X 6" MAXIMUM.
Scale:
15
Alum. Window Frame Types
1/4" = 1'-0"
2 1/2"
3'-2 1/2"
2 1/2"
2'-7"
2 1/2"
AW-1 AW-2
2 1/2"
GL-3
2 1/2"
GL-3
2 1/2"
2 1/2"
1'-5"
2 1/2"
1'-5"
2 1/2"
2 1/2"
3'-2 1/4"
4'-7 1/2"
2'-7"
BALLISTIC/BLAST RATED
GL-3
GL-3
4'-7 1/2"
TYP.
Scale:
14
Mullion Detail
3" = 1'-0"
VE
RIF
Y
2 1/4"
Door, Finish
and Wall Type
Schedules
and Details
AUTHOR
CHECKED:
DAVIS DESIGN ALL RIGHTS RESERVED
SHEET TITLE
SHEET NUMBER
ID
ISSUE DATE:
DescriptionDate
Revisions:
15 E
ast M
ain, S
uite 201
Verm
illion S
D 57069
Phone 605-624-1081
Verm
illion
1221 N
S
treet, S
uite 600
Lincoln N
E 68508
Phone 402-476-9700
Fax 402-476-9722
Lincoln
A-601
07-16-2020
D.W.
D.H.
A-6
01
CLIENT INFORMATION
PROJECT INFORMATION
South Dakota
Army National
Guard
801 W National Guard Dr.
Sioux Falls, S.D 57104
CFMO# SF466146
Convert IFR
to Classroom -
Foss Field
Armory
20-0067Job #
EXISTINGNEW
TO REMAIN
EXISTINGDEMO
1
1
NEW WORK KEYED NOTE SYMBOL
DEMOLITION KEYED NOTE SYMBOL
FINISHED FLOORFF
ROUND RETURN, EXHAUST OR RELIEF AIR DOWN
ROUND SUPPLY OR OUTSIDE AIR DUCT DOWN
RECTANGULAR RETURN, EXHAUST OR RELIEF AIR DOWN
RECTANGULAR SUPPLY OR OUTSIDE AIR DUCT DOWN
SIZE TAG
CFM100
10x10 L-1
XXX-1 EQUIPMENT TAG (SEE SCHEDULES, I.E. AHU-1 - AIR HANDLING UNIT)
TEE - OUTLET UP
TEE - OUTLET DOWN
TEE
ELBOW - 45°
ELBOW - OUTLET UP
ELBOW - OUTLET DOWN
ELBOW
CROSS
CAP
VALVE - SEE SPECIFICATIONS FOR TYPE
DIRECTION OF FLOW
DOWNWARD PIPE PITCH
MANUAL BALANCING VALVE
CHECK VALVE
LOUVER TAG
FLEX DUCT
TURNING VANES
ELEVATION CHANGE IN DIRECTION OF AIRFLOW, UP
ELEVATION CHANGE IN DIRECTION OF AIRFLOW, DOWN
MOTORIZED DAMPER
SPACE/DUCT PRESSURE SENSOR/TRANSMITTER
TEMPERATURE CONTROLS
SHEET METAL
DETAIL IDENTIFICATION
SECTION IDENTIFICATION
FIRE/SMOKE DAMPER
SMOKE DAMPER
FIRE DAMPER
MANUAL VOLUME DAMPER
DISCONNECT POINT
CONNECTION POINT
CFM
SIZE TAG
CFM
SIZE TAG
EA (OR RELA) DIFFUSER/REGISTER/GRILLE TAG
RA DIFFUSER/REGISTER/GRILLE TAG
SIZE TAG
CFM
SA DIFFUSER/REGISTER/GRILLE TAG
10x10 E-1
100
10x10 R-1
100
ROUND RETURN, EXHAUST OR RELIEF AIR UP
RECTANGULAR RETURN, EXHAUST OR RELIEF AIR UP
RECTANGULAR SUPPLY OR OUTSIDE AIR DUCT UP
OVAL DUCT SIZE (WIDTH/HEIGHT)
ROUND DUCT SIZE (DIAMETER)
RECTANGULAR DUCT SIZE (WIDTHxHEIGHT)
SPACE/DUCT HUMIDITY SENSOR/TRANSMITTER
THERMOSTAT OR SPACE/DUCT TEMPERATURE SENSOR/TRANSMITTER
10x8
10Ø
UP
100
10Ø S-1
DN
10x8Ø
DIVISION 23 - HVAC
SYMBOLS LEGEND
GENERAL
(TYP)
(E)
PIPING LEGEND
DIVISION 23 - HVAC
GLOW PRESSURE NATURAL GAS
ABBREVIATIONS
BELOW FINISHED FLOORBFF
AFF ABOVE FINISHED FLOOR
GENERAL
IE INVERT ELEVATION
EXISTING
NIC NOT IN CONTRACT
TYPICAL
OUTSIDE AIR
EXHAUST AIR
SUPPLY AIR
RETURN AIR
FAN COIL UNIT
MANUAL VOLUME DAMPER
EXHAUST FAN
CONDENSING UNITCU
VD
OA
EA
RA
SA
EF
FCU
F FURNACE
DIVISION 23 - HVAC
1
G-000
1
G-000
FD FIRE DAMPER
FSD FIRE/SMOKE DAMPER
VAV-1
1.0
VARIABLE AIR VOLUME BOX TAG
TAG
GPM
PIPING
CONCENTRIC REDUCER
2#G2 PSI NATURAL GAS
PART 1 - GENERAL
1.1 SUMMARY
A. THIS SECTION INCLUDES THE FOLLOWING:
1. PIPING MATERIALS AND INSTALLATION INSTRUCTIONS COMMON TO MOST PIPING SYSTEMS.
2. DIELECTRIC FITTINGS.
3. PLUMBING DEMOLITION.
1.2 SUBMITTALS
A. PRODUCT DATA: FOR THE FOLLOWING:
1. DIELECTRIC FITTINGS.
2. IN ADDITION TO ALL SUBMITTALS IDENTIFIED IN THE SPECIFICATION SECTIONS, SUBMITTALS SHALL BE PROVIDED UNDER THIS SECTION (220500) FOR ALL
PLUMBING FIXTURES AND EQUIPMENT SCHEDULED ON THE DRAWINGS OR IDENTIFIED IN KEYED NOTES.
1.3 QUALITY ASSURANCE
A. ELECTRICAL CHARACTERISTICS FOR PLUMBING EQUIPMENT: EQUIPMENT OF HIGHER ELECTRICAL CHARACTERISTICS THAN BASIS OF DESIGN MAY BE
FURNISHED PROVIDED SUCH PROPOSED EQUIPMENT IS APPROVED IN WRITING AND CONNECTING ELECTRICAL SERVICES, CIRCUIT BREAKERS, AND CONDUIT
SIZES ARE APPROPRIATELY MODIFIED AT NO COST TO THE OWNER. IF MINIMUM ENERGY RATINGS OR EFFICIENCIES ARE SPECIFIED, EQUIPMENT SHALL
COMPLY WITH REQUIREMENTS.
B. WHEN THE DRAWINGS AND/OR SPECIFICATIONS REFER TO ANY ITEM, ARTICLE, MATERIAL, METHOD, FABRICATION, ASSEMBLY OR CONSTRUCTION BY MEANS OF
ONE OR MORE MANUFACTURER'S TRADE NAME, CATALOG REFERENCE OR SIMILAR MEANS OF IDENTIFICATION OF MANUFACTURER, THE CONTRACTOR SHALL
FURNISH ONE OF THE MAKES SO IDENTIFIED WITHOUT SUBSTITUTION UNLESS OTHER MAKE OR MAKES HAVE BEEN APPROVED BY ADDENDUM TO THE
CONTRACT DOCUMENTS PRIOR TO THE RECEIPT OF BIDS. REQUESTS FOR THE APPROVAL OF ITEMS OF EQUAL QUALITY ARE REQUESTED TO BE MADE IN
WRITING TO THE ARCHITECT FIFTEEN (15) DAYS PRIOR TO THE DATE OF THE RECEIPT OF BIDS SO THAT A LIST OF ACCEPTABLE EQUAL QUALITY ITEMS CAN BE
MADE KNOWN TO ALL BIDDERS BY AN ADDENDUM. IF SUBSTITUTION FOR NAMED ITEMS, ARTICLES, MATERIALS, METHODS, FABRICATIONS, ASSEMBLY OR
CONSTRUCTION ARE APPROVED, THE CONTRACTOR ASSUMES ALL RESPONSIBILITY FOR COORDINATION AND PERFORMING THE RELATED CHANGES IN THE
WORK NECESSITATED BY SUCH SUBSTITUTIONS AND SHALL INCLUDE IN THE BID ALL COSTS INVOLVED THEREIN.
C. THE ENTIRE COST OF ALL CHANGES OF ANY TYPE DUE TO SUBSTITUTIONS FOR MATERIALS SPECIFIED SHALL BE BORNE BY THE CONTRACTOR AT NO EXTRA
COST TO THE OWNER.
D. UNSOLICITED AND VOLUNTARY DEDUCTS, ON THE PART OF THE CONTRACTOR FOR SUBSTITUTING UNAPPROVED EQUIPMENT, SHALL NOT BE CONSIDERED FOR
THE PURPOSE OF AWARDING THE CONTRACT.
E. THE ARCHITECT SHALL BE THE SOLE AND FINAL JUDGE AS TO THE SUITABILITY OF ITEMS SUBSTITUTED FOR THOSE SPECIFIED.
F. WHEN THE DRAWINGS SCHEDULE A MANUFACTURER AS THE BASIS OF DESIGN, THE CONTRACTOR ASSUMES ALL RESPONSIBILITY FOR COORDINATION AND
PERFORMING THE RELATED CHANGES IN THE WORK NECESSITATED BY UTILIZING ANOTHER MANUFACTURER LISTED AS ACCEPTABLE IN THE SPECIFICATIONS.
THE ENTIRE COST OF ALL ASSOCIATED CHANGES OF ANY TYPE SHALL BE BORNE BY THE CONTRACTOR AT NO EXTRA COST TO THE OWNER.
G. DRAWINGS AND SPECIFICATIONS SHALL BE TAKEN TOGETHER. PROVIDE WORK SPECIFIED AND NOT INDICATED, OR WORK INDICATED AND NOT SPECIFIED AS
THOUGH MENTIONED IN BOTH.
H. IN CASE OF DISCREPANCY BETWEEN DRAWINGS AND SPECIFICATIONS, OR WITHIN EITHER DOCUMENT, THE GREATER QUANTITY OF WORK AND / OR BETTER
QUALITY SHALL BE USED FOR ESTIMATING AND THE MATTER BROUGHT TO THE ARCHITECT'S ATTENTION FOR A WRITTEN DECISION.
1.4 COORDINATION
A. COORDINATION PROCESS BETWEEN TRADES:
1. KEEP INFORMED ABOUT THE WORK OF ALL OTHER TRADES ENGAGED IN THE PROJECT AND EXECUTE THE WORK IN SUCH A MANNER AS NOT TO DELAY OR
INTERFERE WITH THE PROGRESS OF OTHER CONTRACTORS. THIS CONTRACTOR SHALL SCHEDULE THE WORK SO THAT NO OTHER CONTRACTOR IS
DELAYED IN THE EXECUTION OF THE WORK. COMPLETE COOPERATION OF ALL TRADES IS EXPECTED. EMPLOY A COMPETENT FOREMAN ON JOB
THROUGHOUT THE ENTIRE PROJECT TO ENSURE THAT COORDINATION IS MAINTAINED.
2. SCHEDULE AND COORDINATE THE WORK OF THIS DIVISION WITH THE SCHEDULE OF THE CONTRACTOR TO PROGRESS THE WORK EXPEDITIOUSLY, AND TO
AVOID UNNECESSARY DELAYS.
3. EXAMINE FULLY THE DRAWINGS AND SPECIFICATIONS FOR OTHER CONTRACTORS FOR OTHER TRADES, AND COORDINATE THE INSTALLATION OF THIS WORK
WITH THE WORK OF THE OTHER CONTRACTORS. CONSULT AND COOPERATE WITH OTHER CONTRACTORS FOR DETERMINING SPACE REQUIREMENTS AND
FOR DETERMINING THAT ADEQUATE CLEARANCE IS ALLOWED WITH RESPECT TO THE EQUIPMENT, OTHER EQUIPMENT, AND THE BUILDING. THE OWNER'S
REPRESENTATIVE RESERVES THE RIGHT TO DETERMINE SPACE PRIORITY IN THE EVENT OF INTERFERENCE BETWEEN PIPING, CONDUIT, DUCTS, AND
EQUIPMENT OF THE VARIOUS CONTRACTORS.
4. CONFLICTS BETWEEN THE DRAWINGS AND THE SPECIFICATION SHALL BE CALLED TO THE ATTENTION OF THE OWNER'S REPRESENTATIVE AND ARCHITECT.
IF CLARIFICATION IS NOT ASKED FOR PRIOR TO THE TAKING OF BIDS, IT WILL BE ASSUMED THAT NONE IS REQUIRED AND THAT THE CONTRACTOR IS IN
AGREEMENT WITH THE DRAWINGS AND SPECIFICATIONS AS ISSUED. IF CLARIFICATION IS REQUIRED AFTER THE CONTRACT IS AWARDED, SUCH
CLARIFICATION WILL BE MADE BY THE ARCHITECT AND THEIR DECISION WILL BE FINAL.
5. COORDINATE THE INSTALLATION OF ALL SYSTEM COMPONENTS WITH ALL OTHER TRADES, INCLUDING STRUCTURAL COMPONENTS AND ELECTRICAL
TRADES. ALLOCATE SPACE IN THE DIFFERENT AREAS TO ALLOW FOR THE INSTALLATION OF DUCTWORK, PIPING, SPRINKLERS, WASTE AND VENTS, AND
MECHANICAL EQUIPMENT ABOVE CEILINGS AND IN EQUIPMENT SPACES. RECOMMEND REROUTING, RESIZING OR RELOCATION OF MECHANICAL
COMPONENTS, IF NECESSARY, SO ALL TRADES CAN INSTALL THEIR SYSTEMS IN THE SPACE ALLOTTED. ANY PROPOSED CHANGES FROM THE SYSTEMS
LAYOUT, ON THE DRAWINGS, SHALL BE DONE IN ACCORDANCE WITH THE DESIGN CRITERIA SPECIFIED IN THE APPLICABLE CODES AND SHALL BE SUBJECT
TO THE REVIEW AND ACCEPTANCE OF THE ARCHITECT.
6. THE FOLLOWING LIST, IN DESCENDING ORDER, IS THE PRECEDENCE ASSIGNED THE WORK ITEMS FOR SPACE PRIORITY. RECESSED LIGHT FIXTURES AND
SPACE FOR THEIR INSTALLATION HAS FIRST PRIORITY, FUTURE UTILITY SPACE HAS SECOND PRIORITY, ETC.
a. RECESSED LIGHT FIXTURES AND ACCESS ABOVE LIGHT FIXTURES REQUIRED FOR MAINTENANCE.
b. SPACE DESIGN FOR FUTURE UTILITY PLACEMENT.
c. GRAVITY FLOW PLUMBING WASTE AND ROOF DRAINAGE, AND ANY OTHER SYSTEM THAT RELIES ON GRAVITY FOR FLOW.
d. DUCTWORK AND APPURTENANCES.
e. CABLE TRAY.
f. ELECTRICAL CONDUIT OVER TWO INCHES IN DIAMETER.
g. PRESSURIZED DOMESTIC WATER PIPING AND HVAC PIPING.
h. PLUMBING VENTS.
7. AFTER AWARD OF THE CONTRACT, AND PRIOR TO START OF CONSTRUCTION, THE GENERAL CONTRACTOR SHALL SCHEDULE A MEETING WITH THE
CONTRACTOR AND ALL SUBCONTRACTORS RESPONSIBLE OF THE WORK ITEMS LISTED ABOVE. THE PURPOSE OF THE MEETING IS TO INTRODUCE THE
COORDINATION PROGRAM AND TO DETERMINE ITS IMPLEMENTATION IN RELATION TO THE PROGRESS SCHEDULE.
8. ALL CONTRACTORS AND SUBCONTRACTORS SHALL PARTICIPATE IN THE COORDINATION PROCESS. PARTICIPATION IS MANDATORY. IF A CONTRACTOR OR
SUBCONTRACTOR FAILS TO PARTICIPATE IN THE COORDINATION PROCESS, THE OWNER RESERVES THE RIGHT TO DO THE FOLLOWING:
a. STOP ANY AND ALL CONSTRUCTION PROGRESS PAYMENTS FOR ANY WORK PERFORMED BY THE CONTRACTOR. SUCH PAYMENTS WILL BE REINSTATED
ONLY AFTER THE CONTRACTOR OR SUBCONTRACTOR RESUMES PARTICIPATION IN THE COORDINATION PROCESS.
b. RELOCATE AND RESIZE CONTRACTOR'S WORK COMPONENTS AS NECESSARY TO ENSURE ALL COMPONENTS WILL BE INSTALLED AS INTENDED. IN THE
EVENT THE CONTRACTOR DID NOT PARTICIPATE IN THE COORDINATION PROCESS, THEY WILL NOT BE ENTITLED TO ANY CONTRACT COST INCREASES OR
TIME EXTENSIONS DUE TO OWNER INITIATED CHANGES IN THE WORK.
c. THE CONTRACTOR SHALL ALSO BE HELD RESPONSIBLE FOR ANY UNNECESSARY REWORK BY OTHER TRADE CONTRACTORS THAT IS ATTRIBUTABLE TO
THE FAILURE TO PARTICIPATE IN THE COORDINATION PROCESS.
d. THE CONTRACT DRAWINGS ARE SCHEMATIC IN NATURE AND DO NOT SHOW EVERY FITTING AND APPURTENANCE FOR EACH UTILITY BECAUSE OF THE
SCALE OF THE DRAWINGS. EACH CONTRACTOR IS EXPECTED TO HAVE INCLUDED IN THE BID SUFFICIENT FITTINGS, MATERIAL, AND LABOR TO ALLOW
FOR ADJUSTMENTS IN ROUTING OF UTILITIES MADE NECESSARY BY THE COORDINATION PROCESS. THE CONTRACTOR WILL NOT BE ALLOWED ANY
CONTRACT COST EXTRA OR TIME EXTENSION FOR CHANGES DICTATED BY THE COORDINATION PROCESS.
e. UTILITY INSTALLATION IN CONGESTED AREAS IS DEPENDENT ON THE SEQUENCE OF UTILITY INSTALLATION AS MUCH AS IT IS DEPENDENT ON THE
PHYSICAL SIZE OF THE UTILITIES. THE CONTRACTORS SHALL USE THE COORDINATION PROCESS TO PROPERLY SEQUENCE THE INSTALLATION OF
UTILITIES AS APPROPRIATE TO ENSURE THE ABOVE CEILING AND CONGESTED AREA UTILITY INSTALLATION IS SATISFACTORY.
PART 2 - PRODUCTS
2.1 JOINING MATERIALS
A. SOLDER FILLER METALS: ASTM B 32, LEAD-FREE ALLOYS. INCLUDE WATER-FLUSHABLE FLUX ACCORDING TO ASTM B 813.
2.2 DIELECTRIC FITTINGS
A. DESCRIPTION: COMBINATION FITTING OF COPPER ALLOY AND FERROUS MATERIALS WITH THREADED, SOLDER-JOINT, PLAIN, OR WELD-NECK END CONNECTIONS
THAT MATCH PIPING SYSTEM MATERIALS.
B. INSULATING MATERIAL: SUITABLE FOR SYSTEM FLUID, PRESSURE, AND TEMPERATURE.
C. DIELECTRIC UNIONS: FACTORY-FABRICATED, UNION ASSEMBLY, FOR 250-PSIG MINIMUM WORKING PRESSURE AT 180 DEG F.
D. DIELECTRIC NIPPLES: ELECTROPLATED STEEL NIPPLE WITH INERT AND NONCORROSIVE, THERMOPLASTIC LINING; PLAIN, THREADED, OR GROOVED ENDS; AND
300-PSIG MINIMUM WORKING PRESSURE AT 225 DEG F.
PART 3 - EXECUTION
3.1 PIPING SYSTEMS - COMMON REQUIREMENTS
A. DRAWING PLANS, SCHEMATICS, AND DIAGRAMS INDICATE GENERAL LOCATION AND ARRANGEMENT OF PIPING SYSTEMS. INDICATED LOCATIONS AND
ARRANGEMENTS WERE USED TO SIZE PIPE AND CALCULATE FRICTION LOSS, EXPANSION, PUMP SIZING, AND OTHER DESIGN CONSIDERATIONS. INSTALL PIPING
AS INDICATED UNLESS DEVIATIONS TO LAYOUT ARE APPROVED.
B. CONTRACTOR SHALL NOT CHANGE INDICATED SIZES WITHOUT WRITTEN APPROVAL OF ENGINEER. PROVIDE ALL NECESSARY OFFSETS AND CROSSOVERS,
WHETHER INDICATED ON THE DRAWINGS OR NOT.
C. DO NOT RUN PIPING THROUGH TRANSFORMER VAULTS AND OTHER ELECTRICAL OR ELECTRONIC EQUIPMENT SPACES AND ENCLOSURES.
D. INSTALL PIPING IN CONCEALED LOCATIONS, UNLESS OTHERWISE INDICATED AND EXCEPT IN EQUIPMENT ROOMS AND SERVICE AREAS.
E. INSTALL PIPING AT RIGHT ANGLES OR PARALLEL TO BUILDING WALLS. DIAGONAL RUNS ARE PROHIBITED UNLESS SPECIFICALLY INDICATED OTHERWISE.
F. INSTALL PIPING ABOVE ACCESSIBLE CEILINGS TO ALLOW SUFFICIENT SPACE FOR CEILING PANEL REMOVAL.
G. INSTALL PIPING TO PERMIT VALVE SERVICING.
H. INSTALL PIPING AT INDICATED SLOPES, OR PITCHED TO DRAIN WHERE SLOPES ARE NOT INDICATED.
I. INSTALL PIPING FREE OF SAGS AND BENDS.
J. INSTALL FITTINGS FOR CHANGES IN DIRECTION AND BRANCH CONNECTIONS.
K. INSTALL PIPING TO ALLOW APPLICATION OF INSULATION.
L. SELECT SYSTEM COMPONENTS WITH PRESSURE RATING EQUAL TO OR GREATER THAN SYSTEM OPERATING PRESSURE.
M. VERIFY FINAL EQUIPMENT LOCATIONS FOR ROUGHING-IN.
3.2 PIPING JOINT CONSTRUCTION
A. REAM ENDS OF PIPES AND TUBES AND REMOVE BURRS. BEVEL PLAIN ENDS OF STEEL PIPE.
B. REMOVE SCALE, SLAG, DIRT, AND DEBRIS FROM INSIDE AND OUTSIDE OF PIPE AND FITTINGS BEFORE ASSEMBLY.
C. SOLDERED JOINTS: APPLY ASTM B 813, WATER-FLUSHABLE FLUX, UNLESS OTHERWISE INDICATED, TO TUBE END. CONSTRUCT JOINTS ACCORDING TO
ASTM B 828 OR CDA'S "COPPER TUBE HANDBOOK," USING LEAD-FREE SOLDER ALLOY COMPLYING WITH ASTM B 32.
D. THREADED JOINTS: THREAD PIPE WITH TAPERED PIPE THREADS ACCORDING TO ASME B1.20.1. CUT THREADS FULL AND CLEAN USING SHARP DIES. REAM
THREADED PIPE ENDS TO REMOVE BURRS AND RESTORE FULL ID. JOIN PIPE FITTINGS AND VALVES AS FOLLOWS:
1. APPLY APPROPRIATE TAPE OR THREAD COMPOUND TO EXTERNAL PIPE THREADS UNLESS DRY SEAL THREADING IS SPECIFIED.
2. DAMAGED THREADS: DO NOT USE PIPE OR PIPE FITTINGS WITH THREADS THAT ARE CORRODED OR DAMAGED. DO NOT USE PIPE SECTIONS THAT HAVE
CRACKED OR OPEN WELDS.
E. MECHANICALLY FORMED, COPPER-TUBE-OUTLET JOINTS ARE NOT ALLOWED.
3.3 PIPING CONNECTIONS
A. MAKE CONNECTIONS ACCORDING TO THE FOLLOWING, UNLESS OTHERWISE INDICATED:
1. INSTALL UNIONS, IN PIPING NPS 2 AND SMALLER, AT FINAL CONNECTION TO EACH PIECE OF EQUIPMENT.
2. WET PIPING SYSTEMS:
a. NPS 2 AND SMALLER: INSTALL DIELECTRIC COUPLING AND NIPPLE FITTINGS TO CONNECT PIPING MATERIALS OF DISSIMILAR METALS.
b. BRONZE VALVES WILL NOT BE CONSIDERED SUFFICIENT AS A DIELECTRIC BREAK BETWEEN DISSIMILAR METALS.
END OF SECTION 220500
SECTION 220517 - SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING
PART 1 - GENERAL
1.1 SUMMARY
A. SECTION INCLUDES:
1. SLEEVES.
PART 2 - PRODUCTS
2.1 SLEEVES
A. GALVANIZED-STEEL-PIPE SLEEVES: ASTM A 53/A 53M, TYPE E, GRADE B, SCHEDULE 40, ZINC COATED, WITH PLAIN ENDS.
PART 3 - EXECUTION
3.1 SLEEVE INSTALLATION
A. INSTALL SLEEVES FOR PIPING PASSING THROUGH PENETRATIONS IN NEW AND EXISTING FLOORS, ROOFS, AND WALLS.
B. INSTALL SLEEVES IN CONCRETE FLOORS, CONCRETE ROOF SLABS, AND CONCRETE AND MASONRY WALLS AS NEW SLABS AND WALLS ARE CONSTRUCTED.
1. PERMANENT SLEEVES ARE NOT REQUIRED FOR HOLES FORMED BY CORE DRILL OR MOLDED-PE OR -PP SLEEVES,.
2. CUT SLEEVES TO LENGTH FOR MOUNTING FLUSH WITH BOTH SURFACES.
3. USING GROUT, SEAL THE SPACE OUTSIDE OF SLEEVES.
4. INSTALL SLEEVES THAT ARE LARGE ENOUGH TO PROVIDE 1/4-INCH ANNULAR CLEAR SPACE BETWEEN SLEEVE AND PIPE OR PIPE INSULATION.
5. SEAL ANNULAR SPACE BETWEEN SLEEVE AND PIPING OR PIPING INSULATION; USE JOINT SEALANTS APPROPRIATE FOR SIZE, DEPTH, AND LOCATION OF
JOINT.
C. SLEEVES ARE NOT REQUIRED FOR PIPES PASSING THROUGH INTERIOR GYPSUM BOARD OR METAL PARTITIONS; HOWEVER, ALL PENETRATIONS SHALL BE MADE
CLEAN AND NEAT.
1. OPENINGS SHALL BE LARGE ENOUGH TO PROVIDE 1/4-INCH ANNULAR CLEAR SPACE BETWEEN INTERIOR PARTITION AND PIPE OR PIPE INSULATION.
2. SEAL ANNULAR SPACE BETWEEN INTERIOR PARTITION AND PIPING OR PIPING INSULATION; USE JOINT SEALANTS APPROPRIATE FOR SIZE, DEPTH, AND
LOCATION OF JOINT.
D. FIRE-BARRIER PENETRATIONS: MAINTAIN INDICATED FIRE RATING OF WALLS, PARTITIONS, CEILINGS, AND FLOORS AT PIPE PENETRATIONS. SEAL PIPE
PENETRATIONS WITH FIRESTOP MATERIALS.
3.2 SLEEVE AND SLEEVE-SEAL SCHEDULE
A. USE SLEEVES AND SLEEVE SEALS FOR THE FOLLOWING PIPING-PENETRATION APPLICATIONS:
1. INTERIOR CONCRETE OR MASONRY WALLS:
a. PIPING, ALL SIZES: GALVANIZED-STEEL-PIPE SLEEVES.
END OF SECTION 220517
SECTION 220523 - GENERAL-DUTY VALVES FOR PLUMBING PIPING
PART 1 - GENERAL
1.1 SUMMARY
A. SECTION INCLUDES:
1. BRONZE BALL VALVES.
2. BRONZE LIFT CHECK VALVES.
3. BRONZE SWING CHECK VALVES.
1.2 ACTION SUBMITTALS
A. PRODUCT DATA: FOR EACH TYPE OF VALVE INDICATED.
PART 2 - PRODUCTS
2.1 GENERAL REQUIREMENTS FOR VALVES
A. VALVE PRESSURE AND TEMPERATURE RATINGS: NOT LESS THAN INDICATED AND AS REQUIRED FOR SYSTEM PRESSURES AND TEMPERATURES.
B. VALVE SIZES: SAME AS UPSTREAM PIPING UNLESS OTHERWISE INDICATED.
C. ALL VALVES IN INSULATED PIPING, NO EXCEPTIONS: WITH 2-INCH STEM EXTENSIONS AND THE FOLLOWING FEATURES:
1. BALL VALVES: WITH EXTENDED OPERATING HANDLE.
2.2 BRONZE BALL VALVES
A. TWO-PIECE, FULL-PORT, BRONZE BALL VALVES WITH BRONZE TRIM:
1. DESCRIPTION:
a. STANDARD: MSS SP-110.
b. SWP RATING: 150 PSIG.
c. CWP RATING: 600 PSIG.
d. BODY DESIGN: TWO PIECE.
e. BODY MATERIAL: BRONZE.
f. ENDS: THREADED OR SOLDERED.
g. SEATS: PTFE OR TFE.
h. STEM: BRONZE.
i. BALL: CHROME-PLATED BRASS.
j. PORT: FULL.
PART 3 - EXECUTION
3.1 VALVE INSTALLATION
A. INSTALL VALVES WITH UNIONS OR FLANGES AT EACH PIECE OF EQUIPMENT ARRANGED TO ALLOW SERVICE, MAINTENANCE, AND EQUIPMENT REMOVAL
WITHOUT SYSTEM SHUTDOWN.
B. FURNISH AND INSTALL VALVES IN PLUMBING SYSTEMS, WHETHER INDICATED ON THE PLANS OR NOT, FOR THE PURPOSE OF PROVIDING THE BALANCE AND
ISOLATION OF EQUIPMENT OR FIXTURES FOR INSPECTION, MAINTENANCE, AND REPAIR. INSTALL CHECK VALVES WHERE FLOW REVERSAL IS UNDESIRABLE, BUT
CAN BE EXPECTED TO OCCUR.
C. INSTALL VALVES TO ISOLATE INDIVIDUAL OR GROUPS OF FIXTURES OR EQUIPMENT ON BRANCH RUNOUTS FROM PIPING MAINS. THIS IS IN ADDITION TO VALVES
AT EACH FIXTURE OR EQUIPMENT ITEM.
D. INSTALL VALVE STOP AT THE BASE OF PIPE RISERS AND AT EACH FLOOR LEVEL OF THE DOMESTIC PLUMBING AND OTHER PIPING SYSTEMS.
E. LOCATE VALVES FOR EASY ACCESS AND PROVIDE SEPARATE SUPPORT WHERE NECESSARY.
F. INSTALL NPS 2 INCH AND SMALLER VALVES IN HORIZONTAL PIPING WITH STEM VERTICALLY DOWN OR HORIZONTALLY TO BE VISIBLE FROM FLOOR.
G. INSTALL VALVES IN POSITION TO ALLOW FULL STEM MOVEMENT.
3.2 GENERAL REQUIREMENTS FOR VALVE APPLICATIONS
A. IF VALVE APPLICATIONS ARE NOT INDICATED, USE THE FOLLOWING:
1. SHUTOFF SERVICE: BALL VALVES.
B. IF VALVES WITH SPECIFIED SWP CLASSES OR CWP RATINGS ARE NOT AVAILABLE, THE SAME TYPES OF VALVES WITH HIGHER SWP CLASSES OR CWP RATINGS
MAY BE SUBSTITUTED.
3.3 DOMESTIC, HOT- AND COLD-WATER VALVE SCHEDULE
A. PIPE NPS 2 AND SMALLER:
1. BALL VALVES: TWO PIECE, FULL PORT, BRONZE WITH BRONZE TRIM.
2. BRONZE SWING CHECK VALVES: CLASS 125, BRONZE DISC.
END OF SECTION 220523
SECTION 220529 - HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT
PART 1 - GENERAL
A. SECTION INCLUDES:
1. METAL PIPE HANGERS AND SUPPORTS.
2. METAL FRAMING SYSTEMS.
3. FASTENER SYSTEMS.
PART 2 - PRODUCTS
2.1 METAL PIPE HANGERS AND SUPPORTS
A. GALVANIZED-STEEL PIPE HANGERS AND SUPPORTS:
1. DESCRIPTION: MSS SP-58, TYPES 1 THROUGH 58, FACTORY-FABRICATED COMPONENTS.
2. GALVANIZED METALLIC COATINGS: PREGALVANIZED OR HOT DIPPED.
3. NONMETALLIC COATINGS: PLASTIC COATING, JACKET, OR LINER.
4. HANGER RODS: CONTINUOUS-THREAD ROD, NUTS, AND WASHER MADE OF GALVANIZED STEEL.
B. COPPER PIPE HANGERS:
1. DESCRIPTION: MSS SP-58, TYPES 1 THROUGH 58, COPPER-COATED-STEEL, FACTORY-FABRICATED COMPONENTS.
2. HANGER RODS: CONTINUOUS-THREAD ROD, NUTS, AND WASHER MADE OF COPPER-COATED STEEL.
2.2 METAL FRAMING SYSTEMS
A. MFMA MANUFACTURER METAL FRAMING SYSTEMS:
1. DESCRIPTION: SHOP- OR FIELD-FABRICATED PIPE-SUPPORT ASSEMBLY FOR SUPPORTING MULTIPLE PARALLEL PIPES.
2. STANDARD: MFMA-4.
3. CHANNELS: CONTINUOUS SLOTTED STEEL CHANNEL WITH INTURNED LIPS.
4. CHANNEL NUTS: FORMED OR STAMPED STEEL NUTS OR OTHER DEVICES DESIGNED TO FIT INTO CHANNEL SLOT AND, WHEN TIGHTENED, PREVENT SLIPPING
ALONG CHANNEL.
5. HANGER RODS: CONTINUOUS-THREAD ROD, NUTS, AND WASHER MADE OF GALVANIZED STEEL.
6. METALLIC COATING: GALVANIZED.
PART 3 - EXECUTION
3.1 HANGER AND SUPPORT INSTALLATION
A. METAL PIPE-HANGER INSTALLATION: COMPLY WITH MSS SP-69 AND MSS SP-89. INSTALL HANGERS, SUPPORTS, CLAMPS, AND ATTACHMENTS AS REQUIRED TO
PROPERLY SUPPORT PIPING FROM THE BUILDING STRUCTURAL ELEMENTS SUCH AS ROOF JOISTS OR CONCRETE DECKS.
B. SUPPORTING PIPING FROM THE BUILDING ROOF DECK IS NOT PERMITTED.
C. FASTENER SYSTEM INSTALLATION:
1. DO NOT USE POWDER ACTUATED FASTENERS.
D. CHAIN, WIRE, STRAP, OR PERFORATED STRAP HANGERS WILL NOT BE PERMITTED.
E. CONTRACTOR SHALL SELECT THE SIZE OF HANGERS AND SUPPORTS TO EXACTLY FIT THE PIPE SIZE FOR BARE PIPING.
F. INSULATED PIPING:
1. CONTRACTOR SHALL SELECT THE SIZE OF HANGERS AND SUPPORTS TO EXACTLY FIT AROUND PIPING INSULATION WITH SADDLE OR SHIELD FOR INSULATED
PIPING. SWALLOWING THE PIPE HANGER WITH INSULATION WILL NOT BE PERMITTED..
2. INSTALL MSS SP-58, TYPE 40, PROTECTIVE SHIELDS ON INSULATED PIPING. SHIELDS SHALL SPAN AN ARC OF 180 DEGREES.
3. SHIELD DIMENSIONS FOR PIPE: NOT LESS THAN THE FOLLOWING:
a. NPS 1/4 TO NPS 3-1/2: 12 INCHES LONG AND 0.048 INCH THICK.
3.2 HANGER AND SUPPORT SCHEDULE
A. PIPING HANGERS AND SUPPORTS: UNLESS OTHERWISE INDICATED, INSTALL THE FOLLOWING TYPES:
1. VERTICAL PIPING: MSS TYPE 8 OR 42, CLAMPS.
2. INDIVIDUAL, STRAIGHT, HORIZONTAL PIPING RUNS 2-INCH AND SMALLER: MSS TYPE 10, ADJUSTABLE, SWIVEL RING BAND HANGERS.
3. INDIVIDUAL, STRAIGHT, HORIZONTAL PIPING RUNS 2-1/2 INCH AND LARGER: MSS TYPE 1, ADJUSTABLE, GALVANIZED STEEL CLEVIS HANGERS.
B. ROD DIAMETER MAY BE REDUCED ONE SIZE FOR DOUBLE-ROD HANGERS, TO A MINIMUM OF 3/8 INCH.
C. INSTALL HANGERS FOR COPPER TUBING WITH THE FOLLOWING MAXIMUM HORIZONTAL SPACING AND MINIMUM ROD DIAMETERS:
1. NPS 3/4 AND SMALLER: 60 INCHES WITH 3/8-INCH ROD.
D. INSTALL SUPPORTS FOR VERTICAL COPPER TUBING EVERY 10 FEET.
E. INSTALL HANGERS FOR CAST-IRON SOIL PIPING WITH THE FOLLOWING MAXIMUM HORIZONTAL SPACING AND MINIMUM ROD DIAMETERS:
1. NPS 1-1/2 AND NPS 2: 60 INCHES WITH 3/8-INCH ROD.
2. SPACING FOR 10-FOOT LENGTHS MAY BE INCREASED TO 10 FEET. SPACING FOR FITTINGS IS LIMITED TO 60 INCHES.
F. INSTALL SUPPORTS FOR VERTICAL CAST-IRON SOIL PIPING EVERY 15 FEET.
G. FOR CAST IRON SOIL PIPE, PROVIDE AT LEAST ONE HANGER ON EACH FULL LENGTH OF PIPE CLOSE TO THE HUB. PROVIDE AT LEAST ONE HANGER WITHIN 24
INCHES OF EACH FITTING, AND WHEREVER ELSE REQUIRED TO PREVENT SAGGING DUE TO LOAD. PROVIDE A HANGER AT UPPER ANGLE OF EACH DROP.
WHERE MULTIPLE FITTINGS ARE USED, HANGERS SHALL BE LOCATED NOT MORE THAN 4 FEET ON CENTER AND ADJACENT TO HUBS ON FITTING.
H. FOR CAST IRON NO-HUB SOIL PIPE, PROVIDE PIPE HANGERS ON BOTH SIDES OF THE STAINLESS STEEL COUPLING AT EACH JOINT. PROVIDE TWO HANGERS ON
EACH FULL LENGTH OF PIPE CLOSE TO THE JOINTS. PROVIDE ONE HANGER AT EACH COUPLING ON ALL FITTINGS. WHERE MULTIPLE FITTINGS ARE USED,
PROVIDE A 16-GAUGE, CONTINUOUS TROUGH WITH HANGERS TO SUPPORT THE TROUGH AT 4 FEET ON CENTER.
I. COMPLY WITH MSS SP-69 FOR PIPE-HANGER SELECTIONS AND APPLICATIONS THAT ARE NOT SPECIFIED.
J. USE HANGERS AND SUPPORTS WITH GALVANIZED METALLIC COATINGS FOR PIPING AND EQUIPMENT THAT WILL NOT HAVE FIELD-APPLIED FINISH.
K. USE NONMETALLIC COATINGS ON ATTACHMENTS FOR ELECTROLYTIC PROTECTION WHERE ATTACHMENTS ARE IN DIRECT CONTACT WITH COPPER TUBING.
L. USE GALVANIZED-STEEL PIPE HANGERS AND SUPPORTS, METAL TRAPEZE PIPE HANGERS, AND METAL FRAMING SYSTEMS AND ATTACHMENTS FOR GENERAL
SERVICE APPLICATIONS.
M. USE COPPER-PLATED PIPE HANGERS AND COPPER ATTACHMENTS FOR COPPER PIPING AND TUBING.
N. SADDLES AND SHIELDS: UNLESS OTHERWISE INDICATED AND EXCEPT AS SPECIFIED IN PIPING SYSTEM SECTIONS, INSTALL THE FOLLOWING TYPES:
1. PROTECTION SHIELDS (MSS TYPE 40): OF LENGTH RECOMMENDED IN WRITING BY MANUFACTURER TO PREVENT CRUSHING INSULATION.
O. COMPLY WITH MFMA-103 FOR METAL FRAMING SYSTEM SELECTIONS AND APPLICATIONS.
END OF SECTION 220529
SECTION 220553 - IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT
PART 1 - GENERAL
1.1 SUMMARY
A. SECTION INCLUDES:
1. PIPE LABELS.
PART 2 - PRODUCTS
2.1 PIPE LABELS
A. GENERAL REQUIREMENTS FOR MANUFACTURED PIPE LABELS: PREPRINTED, COLOR-CODED, WITH LETTERING INDICATING SERVICE, AND SHOWING FLOW
DIRECTION.
B. SELF-ADHESIVE PIPE LABELS: PRINTED PLASTIC WITH CONTACT-TYPE, PERMANENT-ADHESIVE BACKING.
C. PIPE LABEL CONTENTS: INCLUDE IDENTIFICATION OF PIPING SERVICE USING SAME DESIGNATIONS OR ABBREVIATIONS AS USED ON DRAWINGS, PIPE SIZE, AND
AN ARROW INDICATING FLOW DIRECTION.
1. FLOW-DIRECTION ARROWS: INTEGRAL WITH PIPING SYSTEM SERVICE LETTERING TO ACCOMMODATE BOTH DIRECTIONS, OR AS SEPARATE UNIT ON EACH
PIPE LABEL TO INDICATE FLOW DIRECTION.
2. LETTERING SIZE: AT LEAST 1-1/2 INCHES HIGH.
PART 3 - EXECUTION
3.1 PIPE LABEL INSTALLATION
A. LOCATE PIPE LABELS WHERE PIPING IS EXPOSED OR ABOVE ACCESSIBLE CEILINGS IN FINISHED SPACES; MACHINE ROOMS; ACCESSIBLE MAINTENANCE SPACES
SUCH AS SHAFTS, TUNNELS, AND PLENUMS; AND EXTERIOR EXPOSED LOCATIONS AS FOLLOWS:
1. NEAR EACH VALVE AND CONTROL DEVICE.
2. NEAR EACH BRANCH CONNECTION, EXCLUDING SHORT TAKEOFFS FOR FIXTURES AND TERMINAL UNITS. WHERE FLOW PATTERN IS NOT OBVIOUS, MARK
EACH PIPE AT BRANCH.
3. NEAR PENETRATIONS THROUGH WALLS, FLOORS, CEILINGS, AND INACCESSIBLE ENCLOSURES.
4. NEAR MAJOR EQUIPMENT ITEMS AND OTHER POINTS OF ORIGINATION AND TERMINATION.
5. SPACED AT MAXIMUM INTERVALS OF 50 FEET ALONG EACH RUN. REDUCE INTERVALS TO 25 FEET IN AREAS OF CONGESTED PIPING AND EQUIPMENT.
B. PIPE LABEL SCHEDULE:
1. DOMESTIC COLD WATER PIPING:
a. BACKGROUND COLOR: GREEN
b. LETTER COLOR: WHITE
c. LABEL: CW OR COLD WATER
2. DOMESTIC HOT WATER PIPING:
a. BACKGROUND COLOR: YELLOW
b. LETTER COLOR: BLACK
c. LABEL: HW OR HOT WATER
END OF SECTION 220553
SECTION 220719 - PLUMBING PIPING INSULATION
PART 1 - GENERAL
1.1 SUMMARY
A. SECTION INCLUDES INSULATING THE FOLLOWING PLUMBING PIPING SERVICES:
1. DOMESTIC COLD-WATER PIPING.
2. DOMESTIC HOT-WATER PIPING.
1.2 ACTION SUBMITTALS
A. PRODUCT DATA: FOR EACH TYPE OF PRODUCT INDICATED. INCLUDE THERMAL CONDUCTIVITY, WATER-VAPOR PERMEANCE THICKNESS, AND JACKETS (BOTH
FACTORY- AND FIELD-APPLIED, IF ANY).
1.3 QUALITY ASSURANCE
A. INSTALLER QUALIFICATIONS: SKILLED MECHANICS EMPLOYED BY A COMPANY ENGAGED IN THIS TYPE OF WORK AS THEIR PRIMARY BUSINESS FOR A MINIMUM
OF THREE YEARS.
PART 2 - PRODUCTS
2.1 INSULATION MATERIALS
A. MINERAL-FIBER, PREFORMED PIPE INSULATION:
1. PRODUCTS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE ONE OF THE FOLLOWING:
a. FIBREX INSULATIONS INC.; COREPLUS 1200.
b. JOHNS MANVILLE; MICRO-LOK.
c. KNAUF INSULATION; 1000-DEGREE PIPE INSULATION.
d. MANSON INSULATION INC.; ALLEY-K.
e. OWENS CORNING; FIBERGLAS PIPE INSULATION.
2. TYPE I, 850 DEG F MATERIALS: MINERAL OR GLASS FIBERS BONDED WITH A THERMOSETTING RESIN. COMPLY WITH ASTM C 547, TYPE I, GRADE A, WITH
FACTORY-APPLIED ASJ-SSL.
2.2 ADHESIVES, MASTICS, SEALANTS AND TAPES
A. MATERIALS SHALL BE COMPATIBLE WITH INSULATION MATERIALS, JACKETS, AND SUBSTRATES AND FOR BONDING INSULATION TO ITSELF AND TO SURFACES TO
BE INSULATED.
PART 3 - EXECUTION
3.1 PREPARATION
A. SURFACE PREPARATION: CLEAN AND DRY SURFACES TO RECEIVE INSULATION. REMOVE MATERIALS THAT WILL ADVERSELY AFFECT INSULATION APPLICATION.
3.2 GENERAL INSTALLATION REQUIREMENTS
A. INSTALL INSULATION MATERIALS, ACCESSORIES, AND FINISHES WITH SMOOTH, STRAIGHT, AND EVEN SURFACES; FREE OF VOIDS THROUGHOUT THE LENGTH OF
PIPING INCLUDING FITTINGS, VALVES, AND SPECIALTIES. THE APPEARANCE OF FINISHED WORK SHALL BE OF EQUAL IMPORTANCE AS ITS MECHANICAL
CORRECTNESS AND EFFICIENCY.
B. INSTALL INSULATION WITH LONGITUDINAL SEAMS AT TOP AND BOTTOM OF HORIZONTAL RUNS.
C. INSTALL MULTIPLE LAYERS OF INSULATION WITH LONGITUDINAL AND END SEAMS STAGGERED.
D. INSTALL INSULATION WITH TIGHT LONGITUDINAL SEAMS AND END JOINTS. BOND SEAMS AND JOINTS WITH ADHESIVE RECOMMENDED BY INSULATION MATERIAL
MANUFACTURER.
E. INSTALL INSULATION WITH LEAST NUMBER OF JOINTS PRACTICAL.
F. WHERE VAPOR BARRIER IS INDICATED, SEAL JOINTS, SEAMS, AND PENETRATIONS IN INSULATION AT HANGERS, SUPPORTS, ANCHORS, AND OTHER
PROJECTIONS WITH VAPOR-BARRIER MASTIC.
1. INSTALL INSULATION CONTINUOUSLY THROUGH HANGERS.
G. APPLY ADHESIVES, MASTICS, AND SEALANTS AT MANUFACTURER'S RECOMMENDED COVERAGE RATE AND WET AND DRY FILM THICKNESSES.
H. FINISH INSTALLATION WITH SYSTEMS AT OPERATING CONDITIONS. REPAIR JOINT SEPARATIONS AND CRACKING DUE TO THERMAL MOVEMENT.
3.3 PENETRATIONS
A. .
B. INSULATION INSTALLATION AT INTERIOR WALL AND PARTITION PENETRATIONS (THAT ARE NOT FIRE RATED): INSTALL INSULATION CONTINUOUSLY THROUGH
WALLS AND PARTITIONS.
C. INSULATION INSTALLATION AT FIRE-RATED WALL AND PARTITION PENETRATIONS:
1. PIPE: INSTALL INSULATION CONTINUOUSLY THROUGH PENETRATIONS OF FIRE-RATED WALLS AND PARTITIONS.
2. SEAL PENETRATIONS THROUGH FIRE-RATED ASSEMBLIES.
3.4 INDOOR PIPING INSULATION SCHEDULE
A. DOMESTIC COLD WATER:
1. NPS 1 AND SMALLER: INSULATION SHALL BE THE FOLLOWING:
a. MINERAL-FIBER, PREFORMED PIPE INSULATION, TYPE I: 1/2 INCH THICK.
B. DOMESTIC HOT AND RECIRCULATED HOT WATER:
1. ALL PIPE SIZES: INSULATION SHALL BE THE FOLLOWING:
a. MINERAL-FIBER, PREFORMED PIPE INSULATION, TYPE I: 1 INCH THICK.
END OF SECTION 220719
SECTION 221116 - DOMESTIC WATER PIPING
PART 1 - GENERAL
1.1 SUMMARY
A. SECTION INCLUDES:
1. ABOVEGROUND DOMESTIC WATER PIPES, TUBES, AND FITTINGS INSIDE BUILDINGS.
1.2 CLOSEOUT SUBMITTALS
A. SYSTEM PURGING AND DISINFECTING ACTIVITIES REPORT: FOR INCLUSION IN SEPARATE TEST REPORTS SECTION OF OPERATION AND MAINTENANCE MANUAL.
PART 2 - PRODUCTS
2.1 COPPER TUBE AND FITTINGS
A. HARD COPPER TUBE: ASTM B 88, TYPE L WATER TUBE, DRAWN TEMPER.
B. WROUGHT-COPPER, SOLDER-JOINT FITTINGS: ASME B16.22, WROUGHT-COPPER PRESSURE FITTINGS.
C. COPPER UNIONS:
1. MSS SP-123.
2. CAST-COPPER-ALLOY, HEXAGONAL-STOCK BODY.
3. BALL-AND-SOCKET, METAL-TO-METAL SEATING SURFACES.
4. SOLDER-JOINT OR THREADED ENDS.
PART 3 - EXECUTION
3.1 FIELD QUALITY CONTROL
A. PERFORM THE FOLLOWING TESTS AND INSPECTIONS:
1. PIPING INSPECTIONS:
a. DO NOT ENCLOSE, COVER, OR PUT PIPING INTO OPERATION UNTIL IT HAS BEEN INSPECTED AND APPROVED BY AUTHORITIES HAVING JURISDICTION.
2. PIPING TESTS:
a. CAP AND SUBJECT PIPING TO STATIC WATER PRESSURE OF 50 PSIG ABOVE OPERATING PRESSURE, WITHOUT EXCEEDING PRESSURE RATING OF PIPING
SYSTEM MATERIALS. ISOLATE TEST SOURCE AND ALLOW IT TO STAND FOR FOUR HOURS. LEAKS AND LOSS IN TEST PRESSURE CONSTITUTE DEFECTS
THAT MUST BE REPAIRED.
B. NOTIFY ARCHITECT AND OWNER NO FEWER THAN TWO (2) DAYS IN ADVANCE OF TESTING TO ALLOW FOR OBSERVATION OF TESTS.
C. PREPARE TEST AND INSPECTION REPORTS.
3.2 CLEANING
A. CLEAN AND DISINFECT POTABLE DOMESTIC WATER PIPING AS FOLLOWS:
1. PURGE NEW PIPING AND PARTS OF EXISTING PIPING THAT HAVE BEEN ALTERED, EXTENDED, OR REPAIRED BEFORE USING.
2. USE PURGING AND DISINFECTING PROCEDURES PRESCRIBED BY AUTHORITIES HAVING JURISDICTION; IF METHODS ARE NOT PRESCRIBED, USE
PROCEDURES DESCRIBED IN EITHER AWWA C651 OR AWWA C652 OR FOLLOW PROCEDURES DESCRIBED BELOW:
a. FLUSH PIPING SYSTEM WITH CLEAN, POTABLE WATER UNTIL DIRTY WATER DOES NOT APPEAR AT OUTLETS.
b. FILL AND ISOLATE SYSTEM ACCORDING TO EITHER OF THE FOLLOWING:
1) FILL SYSTEM OR PART THEREOF WITH WATER/CHLORINE SOLUTION WITH AT LEAST 50 PPM OF CHLORINE. ISOLATE WITH VALVES AND ALLOW TO
STAND FOR 24 HOURS.
2) FILL SYSTEM OR PART THEREOF WITH WATER/CHLORINE SOLUTION WITH AT LEAST 200 PPM OF CHLORINE. ISOLATE AND ALLOW TO STAND FOR
THREE HOURS.
c. FLUSH SYSTEM WITH CLEAN, POTABLE WATER UNTIL NO CHLORINE IS IN WATER COMING FROM SYSTEM AFTER THE STANDING TIME.
d. REPEAT PROCEDURES IF BIOLOGICAL EXAMINATION SHOWS CONTAMINATION.
e. SUBMIT WATER SAMPLES IN STERILE BOTTLES TO AUTHORITIES HAVING JURISDICTION.
B. PREPARE AND SUBMIT REPORTS OF PURGING AND DISINFECTING ACTIVITIES. INCLUDE COPIES OF WATER-SAMPLE APPROVALS FROM AUTHORITIES HAVING
JURISDICTION.
3.3 PIPING SCHEDULE
A. TRANSITION AND SPECIAL FITTINGS WITH PRESSURE RATINGS AT LEAST EQUAL TO PIPING RATING MAY BE USED IN APPLICATIONS BELOW UNLESS OTHERWISE
INDICATED.
B. ABOVEGROUND DOMESTIC WATER PIPING, NPS 2 AND SMALLER, SHALL BE THE FOLLOWING:
1. HARD COPPER TUBE, ASTM B 88, TYPE L; WROUGHT-COPPER, SOLDER-JOINT FITTINGS; AND SOLDERED JOINTS.
3.4 VALVE SCHEDULE
END OF SECTION 221116
SECTION 221316 - SANITARY WASTE AND VENT PIPING
1.1 SUMMARY
A. SECTION INCLUDES:
1. PIPE, TUBE, AND FITTINGS.
2. SPECIALTY PIPE FITTINGS.
PART 2 - PRODUCTS
2.1 PIPING MATERIALS
2.2 HUB-AND-SPIGOT, CAST-IRON SOIL PIPE AND FITTINGS
A. PIPE AND FITTINGS: ASTM A 74, SERVICE CLASS(ES).
1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCTS BY ONE OF THE FOLLOWING:
a. AB & I.
b. CHARLOTTE.
c. NEWAGE CASTING.
d. TYLER PIPE.
B. GASKETS: ASTM C 564, RUBBER.
2.3 HUBLESS, CAST-IRON SOIL PIPE AND FITTINGS
A. PIPE AND FITTINGS: ASTM A 888 AND CISPI 301.
1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCTS BY ONE OF THE FOLLOWING:
a. AB & I.
b. CHARLOTTE.
c. NEWAGE CASTING.
d. TYLER PIPE.
B. CISPI, HUBLESS-PIPING COUPLINGS:
1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCTS BY ONE OF THE FOLLOWING:
a. ANACO-HUSKY.
b. CHARLOTTE.
c. FERNCO INC.
d. MISSION RUBBER COMPANY; A DIVISION OF MCP INDUSTRIES, INC.
e. NEWAGE CASTING.
f. TYLER PIPE.
2. STANDARDS: ASTM C 1277 AND CISPI 310.
3. DESCRIPTION: STAINLESS-STEEL CORRUGATED SHIELD WITH STAINLESS-STEEL BANDS AND TIGHTENING DEVICES; AND ASTM C 564, RUBBER SLEEVE WITH
INTEGRAL, CENTER PIPE STOP.
2.4 PIPING INSTALLATION
A. INSTALL SOIL AND WASTE DRAINAGE AND VENT PIPING AT THE FOLLOWING MINIMUM SLOPES UNLESS OTHERWISE INDICATED:
1. BUILDING SANITARY DRAIN: 2 PERCENT DOWNWARD IN DIRECTION OF FLOW FOR PIPING NPS 3 AND SMALLER; 2 PERCENT DOWNWARD IN DIRECTION OF
FLOW FOR PIPING NPS 4 AND LARGER.
2. HORIZONTAL SANITARY DRAINAGE PIPING: 2 PERCENT DOWNWARD IN DIRECTION OF FLOW.
3. VENT PIPING: 1 PERCENT DOWN TOWARD VERTICAL FIXTURE VENT OR TOWARD VENT STACK.
B. PROHIBITED FITTINGS: NO DOUBLE HUB OR DOUBLE TEE BRANCH OR DOUBLE COMBINATION FITTINGS SHALL BE USED ON SOIL OR WASTE LINES. THE DRILLING
AND TAPPING OF BUILDING DRAINS, SOIL, WASTE, OR VENT PIPES AND THE USE OF SADDLE HUBS OR BANDS IS PROHIBITED. ANY FITTINGS OR CONNECTION
WHICH HAS AN ENLARGEMENT CHAMBER OR RECESS WITH A LEDGE, SHOULDER, OR REDUCTION OF THE PIPE AREA THAT OFFERS AN OBSTRUCTION TO THE
FLOW THROUGH THE DRAIN IS PROHIBITED.
2.5 FIELD QUALITY CONTROL
A. DURING INSTALLATION, NOTIFY AUTHORITIES HAVING JURISDICTION AT LEAST 24 HOURS BEFORE INSPECTION MUST BE MADE. PERFORM TESTS SPECIFIED
BELOW IN PRESENCE OF AUTHORITIES HAVING JURISDICTION.
1. ROUGHING-IN INSPECTION: ARRANGE FOR INSPECTION OF PIPING BEFORE CONCEALING OR CLOSING-IN AFTER ROUGHING-IN AND BEFORE SETTING
FIXTURES.
2. FINAL INSPECTION: ARRANGE FOR FINAL INSPECTION BY AUTHORITIES HAVING JURISDICTION TO OBSERVE TESTS SPECIFIED BELOW AND TO ENSURE
COMPLIANCE WITH REQUIREMENTS.
B. REINSPECTION: IF AUTHORITIES HAVING JURISDICTION FIND THAT PIPING WILL NOT PASS TEST OR INSPECTION, MAKE REQUIRED CORRECTIONS AND ARRANGE
FOR REINSPECTION.
C. REPORTS: PREPARE INSPECTION REPORTS AND HAVE THEM SIGNED BY AUTHORITIES HAVING JURISDICTION.
D. NOTIFY ARCHITECT AND OWNER NO FEWER THAN TWO (2) DAYS IN ADVANCE OF TESTING TO ALLOW FOR OBSERVATION OF TESTS.
E. TEST SANITARY DRAINAGE AND VENT PIPING ACCORDING TO PROCEDURES OF AUTHORITIES HAVING JURISDICTION OR, IN ABSENCE OF PUBLISHED
PROCEDURES, AS FOLLOWS:
1. TEST FOR LEAKS AND DEFECTS IN NEW PIPING AND PARTS OF EXISTING PIPING THAT HAVE BEEN ALTERED, EXTENDED, OR REPAIRED. IF TESTING IS
PERFORMED IN SEGMENTS, SUBMIT SEPARATE REPORT FOR EACH TEST, COMPLETE WITH DIAGRAM OF PORTION OF PIPING TESTED.
2. LEAVE UNCOVERED AND UNCONCEALED NEW, ALTERED, EXTENDED, OR REPLACED DRAINAGE AND VENT PIPING UNTIL IT HAS BEEN TESTED AND
APPROVED. EXPOSE WORK THAT WAS COVERED OR CONCEALED BEFORE IT WAS TESTED.
3. ROUGHING-IN PLUMBING TEST PROCEDURE: TEST DRAINAGE AND VENT PIPING EXCEPT OUTSIDE LEADERS ON COMPLETION OF ROUGHING-IN. CLOSE
OPENINGS IN PIPING SYSTEM AND FILL WITH WATER TO POINT OF OVERFLOW, BUT NOT LESS THAN 10-FOOT HEAD OF WATER. FROM 15 MINUTES BEFORE
INSPECTION STARTS TO COMPLETION OF INSPECTION, WATER LEVEL MUST NOT DROP. INSPECT JOINTS FOR LEAKS.
4. PREPARE REPORTS FOR TESTS AND REQUIRED CORRECTIVE ACTION.
2.6 PIPING SCHEDULE
A. ABOVEGROUND, SOIL, WASTE AND VENT PIPING ALL SIZES SHALL BE ANY OF THE FOLLOWING:
1. SERVICE CLASS, CAST-IRON SOIL PIPE AND FITTINGS; GASKETS; AND GASKETED JOINTS.
2. HUBLESS, CAST-IRON SOIL PIPE AND FITTINGS; CISPI HUBLESS-PIPING COUPLINGS; AND COUPLED JOINTS.
3. DISSIMILAR PIPE-MATERIAL COUPLINGS: SHIELDED, NONPRESSURE TRANSITION COUPLINGS.
B. UNDERGROUND, SOIL, WASTE, AND VENT PIPING ALL SIZES SHALL BE ANY OF THE FOLLOWING:
1. SERVICE CLASS, CAST-IRON SOIL PIPING; GASKETS; AND GASKETED JOINTS.
2. DISSIMILAR PIPE-MATERIAL COUPLINGS: UNSHIELDED, NONPRESSURE TRANSITION COUPLINGS.
END OF SECTION 221316
SECTION 230500 - COMMON WORK RESULTS FOR HVAC
PART 1 - GENERAL
1.1 SUMMARY
A. THIS SECTION INCLUDES THE FOLLOWING:
1. PIPING MATERIALS AND INSTALLATION INSTRUCTIONS COMMON TO MOST PIPING SYSTEMS.
2. HVAC DEMOLITION.
1.2 SUBMITTALS
A. PRODUCT DATA: FOR THE FOLLOWING:
1. IN ADDITION TO ALL SUBMITTALS IDENTIFIED IN THE SPECIFICATION SECTIONS, SUBMITTALS SHALL BE PROVIDED UNDER THIS SECTION (230500) FOR ALL
HVAC EQUIPMENT SCHEDULED ON THE DRAWINGS OR IDENTIFIED IN KEYED NOTES.
1.3 QUALITY ASSURANCE
A. SEE 220500.
1.4 COORDINATION
A. SEE 220500
PART 2 - PRODUCTS
2.1 NOT USED.
PART 3 - EXECUTION
3.1 HVAC DEMOLITION
A. DISCONNECT, DEMOLISH, AND REMOVE HVAC SYSTEMS, EQUIPMENT, AND COMPONENTS INDICATED TO BE REMOVED.
1. DUCTS TO BE REMOVED: REMOVE PORTION OF DUCTS INDICATED TO BE REMOVED.
B. IF PIPE, INSULATION, OR EQUIPMENT TO REMAIN IS DAMAGED IN APPEARANCE OR IS UNSERVICEABLE, AS PART OF THE CONSTRUCTION PROCESS, REMOVE
DAMAGED OR UNSERVICEABLE PORTIONS AND REPLACE WITH NEW PRODUCTS OF EQUAL CAPACITY AND QUALITY.
END OF SECTION 230500
SECTION 230553 - IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT
PART 1 - GENERAL
1.1 SUMMARY
A. SECTION INCLUDES:
1. DUCT LABELS.
PART 2 - PRODUCTS
2.1 DUCT LABELS
A. SELF-ADHESIVE DUCT LABELS: PRINTED PLASTIC WITH CONTACT TYPE, PERMANENT ADHESIVE BACKING.
B. ADHESIVE: CONTACT-TYPE PERMANENT ADHESIVE, COMPATIBLE WITH LABEL AND WITH SUBSTRATE.
C. DUCT LABEL CONTENTS: INCLUDE IDENTIFICATION OF DUCT SERVICE USING SAME DESIGNATIONS OR ABBREVIATIONS AS USED ON DRAWINGS, DUCT SIZE, AND
AN ARROW INDICATING FLOW DIRECTION.
1. FLOW-DIRECTION ARROWS: INTEGRAL WITH DUCT SYSTEM SERVICE LETTERING TO ACCOMMODATE BOTH DIRECTIONS, OR AS SEPARATE UNIT ON EACH
DUCT LABEL TO INDICATE FLOW DIRECTION.
2. LETTERING SIZE: AT LEAST 1-1/2 INCHES HIGH.
PART 3 - EXECUTION
3.1 DUCT LABEL INSTALLATION
A. INSTALL SELF-ADHESIVE DUCT LABELS WITH PERMANENT ADHESIVE ON AIR DUCTS PER THE FOLLOWING:
1. SUPPLY AIR DUCTS (COOLING/HEATING):
a. BACKGROUND COLOR: BLUE
b. LETTER COLOR: WHITE
c. LABEL: SUPPLY AIR
2. RETURN AIR DUCTS:
a. BACKGROUND COLOR: GREEN
b. LETTER COLOR: WHITE
c. LABEL: RETURN AIR
B. LOCATE LABELS NEAR POINTS WHERE DUCTS ENTER INTO CONCEALED SPACES AND AT MAXIMUM INTERVALS OF 50 FEET IN EACH SPACE WHERE DUCTS ARE
EXPOSED OR 25 FEET IN AREAS WHERE CONCEALED BY REMOVABLE CEILING SYSTEM.
END OF SECTION 230553
SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC
PART 1 - GENERAL
1.1 SUMMARY
A. SECTION INCLUDES:
1. BALANCING AIR SYSTEMS.
1.2 INFORMATIONAL SUBMITTALS
A. CERTIFIED TAB REPORTS AND INSTRUMENT CALIBRATION REPORTS.
1.3 QUALITY ASSURANCE
A. TAB CONTRACTOR QUALIFICATIONS: ENGAGE A TAB ENTITY CERTIFIED BY NEBB OR TABB.
1. TAB FIELD SUPERVISOR: EMPLOYEE OF THE TAB CONTRACTOR AND CERTIFIED BY NEBB OR TABB.
2. TAB TECHNICIAN: EMPLOYEE OF THE TAB CONTRACTOR AND WHO IS CERTIFIED BY AABC NEBB OR TABB AS A TAB TECHNICIAN.
PART 2 - PRODUCTS (NOT APPLICABLE)
PART 3 - EXECUTION
3.1 GENERAL PROCEDURES FOR TESTING AND BALANCING
A. PERFORM TESTING AND BALANCING PROCEDURES ON EACH SYSTEM ACCORDING TO THE PROCEDURES CONTAINED IN ASHRAE 111, NEBB'S "PROCEDURAL
STANDARDS FOR TESTING, ADJUSTING, AND BALANCING OF ENVIRONMENTAL SYSTEMS," OR SMACNA'S "HVAC SYSTEMS - TESTING, ADJUSTING, AND
BALANCING" AND IN THIS SECTION.
B. MARK EQUIPMENT AND BALANCING DEVICES, INCLUDING DAMPER-CONTROL POSITIONS, VALVE POSITION INDICATORS, FAN-SPEED-CONTROL LEVERS, AND
SIMILAR CONTROLS AND DEVICES, WITH PAINT OR OTHER SUITABLE, PERMANENT IDENTIFICATION MATERIAL TO SHOW FINAL SETTINGS.
3.2 TOLERANCES
A. SET HVAC SYSTEM'S AIR FLOW RATES AND WATER FLOW RATES WITHIN PLUS OR MINUS 10 PERCENT.
3.3 FINAL REPORT
A. GENERAL: PREPARE A CERTIFIED WRITTEN REPORT; TABULATE AND DIVIDE THE REPORT INTO SEPARATE SECTIONS FOR TESTED SYSTEMS AND BALANCED
SYSTEMS.
1. INCLUDE A CERTIFICATION SHEET AT THE FRONT OF THE REPORT'S BINDER, SIGNED AND SEALED BY THE CERTIFIED TESTING AND BALANCING ENGINEER.
2. INCLUDE A LIST OF INSTRUMENTS USED FOR PROCEDURES, ALONG WITH PROOF OF CALIBRATION.
3.4 ADDITIONAL TESTS
A. WITHIN 90 DAYS OF COMPLETING TAB, PERFORM ADDITIONAL TAB TO VERIFY THAT BALANCED CONDITIONS ARE BEING MAINTAINED THROUGHOUT AND TO
CORRECT UNUSUAL CONDITIONS.
B. SEASONAL PERIODS: IF INITIAL TAB PROCEDURES WERE NOT PERFORMED DURING NEAR-PEAK SUMMER AND WINTER CONDITIONS, PERFORM ADDITIONAL TAB
DURING NEAR-PEAK SUMMER AND WINTER CONDITIONS.
END OF SECTION 230593
SECTION 230713 - DUCT INSULATION
PART 1 - GENERAL
1.1 SUMMARY
A. SECTION INCLUDES INSULATING THE FOLLOWING DUCT SERVICES:
1. INDOOR SUPPLYAIR.
1.2 ACTION SUBMITTALS
A. PRODUCT DATA: FOR EACH TYPE OF PRODUCT INDICATED. INCLUDE THERMAL CONDUCTIVITY, WATER-VAPOR PERMEANCE THICKNESS, AND JACKETS (BOTH
FACTORY- AND FIELD-APPLIED IF ANY).
1.3 QUALITY ASSURANCE
A. INSTALLER QUALIFICATIONS: SKILLED MECHANICS EMPLOYED BY A COMPANY ENGAGED IN THIS TYPE OF WORK AS THEIR PRIMARY BUSINESS FOR A MINIMUM
OF THREE YEARS.
PART 2 - PRODUCTS
2.1 INSULATION MATERIALS
A. MINERAL-FIBER BLANKET INSULATION: MINERAL OR GLASS FIBERS BONDED WITH A THERMOSETTING RESIN. COMPLY WITH ASTM C 553, TYPE II AND
ASTM C 1290, TYPE III WITH FACTORY-APPLIED FSK JACKET OR WHITE PSK JACKET WHERE INDICATED ON DRAWINGS.
PART 3 - EXECUTION
3.1 GENERAL INSTALLATION REQUIREMENTS
A. INSTALL INSULATION MATERIALS, ACCESSORIES, AND FINISHES WITH SMOOTH, STRAIGHT, AND EVEN SURFACES; FREE OF VOIDS THROUGHOUT THE LENGTH OF
DUCTS AND FITTINGS. THE APPEARANCE OF FINISHED WORK SHALL BE OF EQUAL IMPORTANCE AS ITS MECHANICAL CORRECTNESS AND EFFICIENCY.
B. ADHESIVES AND MASTICS SHALL BE COMPATIBLE WITH THE MATERIALS BEING INSTALLED AND SHALL BE INSTALLED PER MANUFACTURERS
RECOMMENDATIONS. A COMPLETE VAPOR BARRIER SHALL BE PROVIDED ON ALL BELOW AMBIENT SYSTEMS.
3.2 INSTALLATION OF MINERAL-FIBER INSULATION
A. BLANKET INSULATION INSTALLATION ON DUCTS AND PLENUMS: SECURE WITH INSULATION PINS.
1. INSTALL EITHER CAPACITOR-DISCHARGE-WELD PINS AND SPEED WASHERS OR CUPPED-HEAD, CAPACITOR-DISCHARGE-WELD PINS ON SIDES AND BOTTOM
OF HORIZONTAL DUCTS AND SIDES OF VERTICAL DUCTS AS FOLLOWS:
a. ON DUCT SIDES WITH DIMENSIONS 12 INCHES AND SMALLER, PINS ARE NOT REQUIRED.
b. ON DUCT SIDES WITH DIMENSIONS LARGER THAN 12 INCHES, PLACE PINS AT MAXIMUM 12 INCHES O.C. EACH WAY, AND 3 INCHES MAXIMUM FROM
INSULATION JOINTS. AT A MINIMUM, ALL DUCT SIDES OVER 12 INCHES SHALL BE PROVIDED WITH PINS ALONG LONGITUDINAL CENTERLINE OF DUCT.
INSTALL ADDITIONAL PINS TO HOLD INSULATION TIGHTLY AGAINST SURFACE AT CROSS BRACING.
c. PINS MAY BE OMITTED FROM TOP SURFACE OF HORIZONTAL, RECTANGULAR DUCTS AND PLENUMS.
3.3 INDOOR DUCT AND PLENUM INSULATION SCHEDULE
A. SUPPLY AIR DUCT INSULATION SHALL BE THE FOLLOWING:
1. MINERAL-FIBER BLANKET: 2 INCHES THICK AND 1.5-LB/CU. FT. NOMINAL DENSITY.
END OF SECTION 230713
SECTION 233113 - METAL DUCTS
PART 1 - GENERAL
1.1 SUMMARY
A. SECTION INCLUDES:
1. SINGLE-WALL RECTANGULAR DUCTS AND FITTINGS.
2. SINGLE-WALL ROUND DUCTS AND FITTINGS.
3. HIGH EFFICIENCY TAKEOFF.
6. SEALANTS AND GASKETS.
7. HANGERS AND SUPPORTS.
1.2 PERFORMANCE REQUIREMENTS
A. DELEGATED DUCT DESIGN: DUCT CONSTRUCTION, INCLUDING SHEET METAL THICKNESSES, SEAM AND JOINT CONSTRUCTION, REINFORCEMENTS, AND
HANGERS AND SUPPORTS, SHALL COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE" AND PERFORMANCE
REQUIREMENTS AND DESIGN CRITERIA INDICATED IN "DUCT SCHEDULE" ARTICLE.
PART 2 - PRODUCTS
2.1 SINGLE-WALL RECTANGULAR DUCTS AND FITTINGS
A. GENERAL FABRICATION REQUIREMENTS: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE" BASED ON INDICATED
STATIC-PRESSURE CLASS UNLESS OTHERWISE INDICATED.
2.2 SINGLE-WALL ROUND DUCTS AND FITTINGS
1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCTS BY ONE OF THE FOLLOWING:
a. DUCTS ON DEMAND.
b. EASTERN SHEET METAL.
c. LAPINE METAL PRODUCTS.
d. LINDAB INC.
e. MCGILL AIRFLOW LLC.
f. NORLOCK.
g. SEMCO INCORPORATED.
h. SET DUCT MANUFACTURING.
i. SHEET METAL CONNECTORS, INC.
j. SPIRAL MANUFACTURING CO., INC.
k. SPIRAL PIPE OF TEXAS.
B. TRANSVERSE JOINTS, LONGITUDINAL SEAMS, TEES AND LATERALS: COMPLY WITH APPLICABLE FIGURES FROM SMACNA'S "HVAC DUCT CONSTRUCTION
STANDARDS - METAL AND FLEXIBLE,"
C. FABRICATE ROUND DUCTS LARGER THAN 12 INCHES IN DIAMETER WITH SPIRAL SEAM.
2.3 HIGH EFFICIENCY TAKEOFF
A. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCTS BY ONE OF THE FOLLOWING:
1. DUCTMATE INDUSTRIES.
2. ELGIN MANUFACTURING.
3. SHEET METAL CONNECTORS, INC.
B. SOLID BODY, GALVANIZED STEEL. DAMPERS SHALL BE QUADRANT LOCKING HARDWARE WITH 1-1/2 INCH INSULATION STANDOFF.
2.4 SHEET METAL MATERIALS
A. GENERAL MATERIAL REQUIREMENTS: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE" FOR ACCEPTABLE MATERIALS,
MATERIAL THICKNESSES, AND DUCT CONSTRUCTION METHODS UNLESS OTHERWISE INDICATED. SHEET METAL MATERIALS SHALL BE FREE OF PITTING, SEAM
MARKS, ROLLER MARKS, STAINS, DISCOLORATIONS, AND OTHER IMPERFECTIONS.
B. GALVANIZED SHEET STEEL: COMPLY WITH ASTM A 653/A 653M.
1. GALVANIZED COATING DESIGNATION: G90.
2.5 DUCT LINER
A. POLYESTER DUCT LINER: DUCTMATE INDUSTRIES, “POLYARMOR.”
B. FLEXIBLE ELASTOMERIC DUCT LINER: ARMACELL AP COILFLEX ACOUSTIC DUCT LINER.
C. SHOP APPLICATION OF DUCT LINER: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE," FIGURE 7-11, "FLEXIBLE DUCT
LINER INSTALLATION."
2.6 SEALANT AND GASKETS
A. WATER-BASED AND SOLVENT-BASED JOINT AND SEAM SEALANT:
1. APPLICATION METHOD: BRUSH OR CAULK. WHEN CAULKING, BACK BRUSH SEALANT INTO JOINT.
2. SOLIDS CONTENT: MINIMUM 65 PERCENT.
3. SERVICE TEMPERATURE -25 F TO 160 F.
4. WATER RESISTANT.
5. MOLD AND MILDEW RESISTANT.
6. VOC: MAXIMUM 30 G/L (LESS WATER) FOR WATER BASED. MAXIMUM 80 G/L (LESS WATER FOR SOLVENT BASED.
7. MAXIMUM STATIC-PRESSURE CLASS: 15-INCH WG, POSITIVE AND NEGATIVE.
8. SERVICE: INDOOR OR OUTDOOR.
9. SUBSTRATE: COMPATIBLE WITH GALVANIZED SHEET STEEL (BOTH PVC COATED AND BARE), STAINLESS.
10. SEALANT SHALL BE RATED FOR ALL SMACNA HVAC PRESSURE CLASSES.
11. SURFACE BURNING CHARACTERISTICS: MAXIMUM FLAME SPREAD INDEX OF 25 AND MAXIMUM SMOKE DEVELOPED INDEX OF 50 WHEN TESTED ACCORDING
TO UL 181; CERTIFIED BY AND NRTL.
B. TDC/TDF AND APPLIED DUCT FLANGE GASKETS:
1. DOMESTICALLY MANUFACTURED.
2. 600% ELONGATION.
3. NON-OXIDIZING.
4. NON-SLUMPING / NON-SAGGING.
5. SOLID CONTENT 100%.
6. 5/8” X 3/16” MINIMUM.
7. GASKET SHALL BE RATED FOR ALL SMACNA HVAC PRESSURE CLASSES.
8. SURFACE BURNING CHARACTERISTICS: MAXIMUM FLAME SPREAD INDEX OF 25 AND MAXIMUM SMOKE DEVELOPED INDEX OF 50 WHEN TESTED ACCORDING
TO UL 723; CERTIFIED BY AND NRTL.
C. FLANGE GASKETS: BUTYL RUBBER, NEOPRENE, OR EPDM POLYMER WITH POLYISOBUTYLENE PLASTICIZER.
D. ROUND DUCT JOINT O-RING SEALS:
1. SEAL SHALL PROVIDE MAXIMUM LEAKAGE CLASS OF 3 CFM/100 SQ. FT. AT 1-INCH WG AND SHALL BE RATED FOR10-INCH WG STATIC-PRESSURE CLASS,
POSITIVE OR NEGATIVE.
2.7 HANGERS AND SUPPORTS
A. HANGER RODS FOR NONCORROSIVE ENVIRONMENTS: CADMIUM-PLATED STEEL RODS AND NUTS.
B. STEEL CABLES FOR GALVANIZED-STEEL DUCTS: GALVANIZED STEEL COMPLYING WITH ASTM A 603.
C. STEEL CABLE END CONNECTIONS: CADMIUM-PLATED STEEL ASSEMBLIES WITH BRACKETS, SWIVEL, AND BOLTS DESIGNED FOR DUCT HANGER SERVICE; WITH
AN AUTOMATIC-LOCKING AND CLAMPING DEVICE.
D. DUCT ATTACHMENTS: SHEET METAL SCREWS, BLIND RIVETS, OR SELF-TAPPING METAL SCREWS; COMPATIBLE WITH DUCT MATERIALS.
E. TRAPEZE AND RISER SUPPORTS:
1. SUPPORTS FOR GALVANIZED-STEEL DUCTS: GALVANIZED-STEEL SHAPES AND PLATES.
PART 3 - EXECUTION
3.1 HANGER AND SUPPORT INSTALLATION
A. COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE," CHAPTER 5, "HANGERS AND SUPPORTS."
B. WIRE DUCT HANGERS SHALL NOT BE USED.
3.2 PAINTING
A. PAINT INTERIOR OF METAL DUCTS THAT ARE VISIBLE THROUGH REGISTERS AND GRILLES AND THAT DO NOT HAVE DUCT LINER. APPLY ONE COAT OF FLAT,
BLACK, LATEX PAINT OVER A COMPATIBLE GALVANIZED-STEEL PRIMER.
3.3 DUCT SCHEDULE
A. FABRICATE DUCTS WITH GALVANIZED SHEET STEEL EXCEPT AS OTHERWISE INDICATED.
B. SUPPLY DUCTS:
1. PRESSURE CLASS: POSITIVE 2-INCH WG TO 4-INCH AS REQUIRED FOR APPLICATION.
2. MINIMUM SMACNA SEAL CLASS: A.
3. SMACNA LEAKAGE CLASS FOR RECTANGULAR: 6.
4. SMACNA LEAKAGE CLASS FOR ROUND AND FLAT OVAL: 3.
C. RETURN DUCTS:
1. PRESSURE CLASS: POSITIVE OR NEGATIVE 2-INCH WG.
2. MINIMUM SMACNA SEAL CLASS: A.
3. SMACNA LEAKAGE CLASS FOR RECTANGULAR: 6.
4. SMACNA LEAKAGE CLASS FOR ROUND AND FLAT OVAL: 3.
D. INTERMEDIATE REINFORCEMENT:
1. GALVANIZED-STEEL DUCTS: GALVANIZED STEEL.
E. LINER:
1. RETURN AIR DUCTS WHERE INDICATED ON PLANS: POLYESTER OR FLEXIBLE ELASTOMERIC, 1 INCH THICK.
2. TRANSFER DUCTS: POLYESTER OR FLEXIBLE ELASTOMERIC, 1 INCH THICK.
F. ELBOW CONFIGURATION:
1. RECTANGULAR DUCT: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE," FIGURE 4-2, "RECTANGULAR ELBOWS."
a. RADIUS TYPE RE 1 WITH MINIMUM 1.5 RADIUS-TO-DIAMETER RATIO.
b. RADIUS TYPE RE 3 WITH MINIMUM 1.0 RADIUS-TO-DIAMETER RATIO AND TWO VANES.
c. MITERED TYPE RE 2 WITH VANES COMPLYING WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE," FIGURE 4-3, "VANES
AND VANE RUNNERS," AND FIGURE 4-4, "VANE SUPPORT IN ELBOWS."
2. ROUND DUCT: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE," FIGURE 3-4, "ROUND DUCT ELBOWS."
a. MINIMUM RADIUS-TO-DIAMETER RATIO AND ELBOW SEGMENTS: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND
FLEXIBLE," TABLE 3-1, "MITERED ELBOWS." ELBOWS WITH LESS THAN 90-DEGREE CHANGE OF DIRECTION HAVE PROPORTIONATELY FEWER SEGMENTS.
1) RADIUS-TO DIAMETER RATIO: 1.5.
b. ROUND ELBOWS, 12 INCHES AND SMALLER IN DIAMETER: STAMPED OR PLEATED.
c. ROUND ELBOWS, 14 INCHES AND LARGER IN DIAMETER: STANDING SEAM OR WELDED.
G. BRANCH CONFIGURATION:
1. RECTANGULAR DUCT: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE," FIGURE 4-6, "BRANCH CONNECTION."
a. RECTANGULAR MAIN TO RECTANGULAR BRANCH: 45-DEGREE ENTRY.
b. RECTANGULAR MAIN TO ROUND BRANCH: HIGH EFFICIENCY TAKEOFF. IF A VOLUME CONTROL DAMPER IS REQUIRED AT THE BRANCH, PROVIDE A HIGH
EFFICIENCY TAKEOFF WITH INTEGRAL QUADRANT LOCKING DAMPER AND 1-1/2 INCH INSULATION STANDOFF.
2. ROUND: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE," FIGURE 3-5, "90 DEGREE TEES AND LATERALS," AND
FIGURE 3-6, "CONICAL TEES." SADDLE TAPS ARE PERMITTED IN EXISTING DUCT.
a. VELOCITY 1000 FPM OR LOWER: 90-DEGREE TAP.
b. VELOCITY 1000 FPM OR HIGHER: 45-DEGREE LATERAL.
H. TRANSITION AND OFFSET CONFIGURATION:
1. RECTANGULAR DUCT; COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE," FIGURE 4-7, "OFFSETS AND
TRANSITIONS."
a. OFFSET TYPE 1: ANGLED, MAXIMUM 30 DEGREES.
b. OFFSET TYPE 2: ANGLED, MAXIMUM 30 DEGREES.
c. CONCENTRIC TRANSITION: 45 DEGREES MAXIMUM.
d. ECCENTRIC TRANSITION: 30 DEGREES MAXIMUM.
END OF SECTION 233113
SECTION 233300 - AIR DUCT ACCESSORIES
PART 1 - GENERAL
1.1 SUMMARY
A. SECTION INCLUDES:
1. MANUAL VOLUME DAMPERS.
2. FLANGE CONNECTORS.
3. FLEXIBLE CONNECTORS.
4. FLEXIBLE DUCTS.
5. DUCT ACCESSORY HARDWARE.
PART 2 - PRODUCTS
2.1 ASSEMBLY DESCRIPTION
A. COMPLY WITH NFPA 90A, "INSTALLATION OF AIR CONDITIONING AND VENTILATING SYSTEMS," AND WITH NFPA 90B, "INSTALLATION OF WARM AIR HEATING AND
AIR CONDITIONING SYSTEMS."
B. COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE" FOR ACCEPTABLE MATERIALS, MATERIAL THICKNESSES, AND DUCT
CONSTRUCTION METHODS UNLESS OTHERWISE INDICATED. SHEET METAL MATERIALS SHALL BE FREE OF PITTING, SEAM MARKS, ROLLER MARKS, STAINS,
DISCOLORATIONS, AND OTHER IMPERFECTIONS.
2.2 MATERIALS
A. GALVANIZED SHEET STEEL: COMPLY WITH ASTM A 653/A 653M.
1. GALVANIZED COATING DESIGNATION: G90.
B. REINFORCEMENT SHAPES AND PLATES: GALVANIZED-STEEL REINFORCEMENT WHERE INSTALLED ON GALVANIZED SHEET METAL DUCTS;
2.3 DAMPER MANUFACTURERS
A. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCTS BY ONE OF THE FOLLOWING:
1. AIR BALANCE INC.; A DIVISION OF MESTEK, INC.
2. GREENHECK FAN CORPORATION.
3. NAILOR INDUSTRIES INC.
4. NCA MANUFACTURING, INC.
5. POTTORFF.
6. RUSKIN COMPANY.
2.4 MANUAL VOLUME DAMPERS
2.5 ROUND MANUAL VOLUME DAMPERS
A. STANDARD, STEEL, MANUAL VOLUME DAMPERS:
1. STANDARD LEAKAGE RATING, WITH LINKAGE OUTSIDE AIRSTREAM.
2. SUITABLE FOR HORIZONTAL OR VERTICAL APPLICATIONS.
3. FRAMES:
a. GALVANIZED OR STAINLESS-STEEL, 0.040-INCH MINIMUM THICKNESS, 6 INCHES DEEP.
b. FLANGELESS FRAMES FOR INSTALLING IN DUCTS.
4. BLADES:
a. MULTIPLE OR SINGLE BLADE.
b. GALVANIZED OR STAINLESS-STEEL, 0.040 INCH THICK.
5. BLADE AXLES: GALVANIZED STEEL OR STAINLESS STEEL.
6. BEARINGS:
a. OIL-IMPREGNATED BRONZE.
b. DAMPERS IN DUCTS WITH PRESSURE CLASSES OF 3-INCH WG OR LESS SHALL HAVE AXLES FULL LENGTH OF DAMPER BLADES AND BEARINGS AT BOTH
ENDS OF OPERATING SHAFT.
7. TIE BARS AND BRACKETS: GALVANIZED STEEL.
B. JACKSHAFT:
1. SIZE: 0.5-INCH DIAMETER.
2. MATERIAL: GALVANIZED-STEEL PIPE ROTATING WITHIN PIPE-BEARING ASSEMBLY MOUNTED ON SUPPORTS AT EACH MULLION AND AT EACH END OF
MULTIPLE-DAMPER ASSEMBLIES.
3. LENGTH AND NUMBER OF MOUNTINGS: AS REQUIRED TO CONNECT LINKAGE OF EACH DAMPER IN MULTIPLE-DAMPER ASSEMBLY.
C. DAMPER HARDWARE:
1. LOCKING HAND QUADRANT: ZINC-PLATED, DIE-CAST CORE WITH DIAL AND HANDLE MADE OF 3/32-INCH THICK ZINC-PLATED STEEL, AND LOCKING MEANS.
2. INCLUDE CENTER HOLE TO SUIT DAMPER OPERATING-ROD SIZE.
3. INCLUDE A MINIMUM OF 1-1/2 INCH STANDOFF FOR INSULATED DUCT MOUNTING.
2.6 FLEXIBLE CONNECTORS
A. MATERIALS: FLAME-RETARDANT OR NONCOMBUSTIBLE FABRICS.
B. COATINGS AND ADHESIVES: COMPLY WITH UL 181, CLASS 1.
C. METAL-EDGED CONNECTORS: FACTORY FABRICATED WITH A FABRIC STRIP 3-1/2 INCHES WIDE ATTACHED TO TWO STRIPS OF 2-3/4-INCH WIDE, 0.028-INCH THICK,
GALVANIZED SHEET STEEL OR 0.032-INCH THICK ALUMINUM SHEETS. PROVIDE METAL COMPATIBLE WITH CONNECTED DUCTS.
D. INDOOR SYSTEM, FLEXIBLE CONNECTOR FABRIC: GLASS FABRIC DOUBLE COATED WITH NEOPRENE.
2.7 FLEXIBLE DUCTS
A. INSULATED, FLEXIBLE DUCT: UL 181, CLASS 1, 2-PLY VINYL FILM SUPPORTED BY HELICALLY WOUND, SPRING-STEEL WIRE; FIBROUS-GLASS INSULATION;
POLYETHYLENE VAPOR-BARRIER FILM.
1. PRESSURE RATING: 10-INCH WG POSITIVE AND 1.0-INCH WG NEGATIVE.
2. MAXIMUM AIR VELOCITY: 4000 FPM.
3. TEMPERATURE RANGE: MINUS 10 TO PLUS 160 DEG F.
4. INSULATION R-VALUE: COMPLY WITH ASHRAE/IESNA 90.1.
B. FLEXIBLE DUCT CONNECTORS:
1. CLAMPS: STAINLESS-STEEL BAND WITH CADMIUM-PLATED HEX SCREW TO TIGHTEN BAND WITH A WORM-GEAR ACTION IN SIZES 3 THROUGH 18 INCHES, TO
SUIT DUCT SIZE.
2.8 DUCT ACCESSORY HARDWARE
A. ADHESIVES: HIGH STRENGTH, QUICK SETTING, NEOPRENE BASED, WATERPROOF, AND RESISTANT TO GASOLINE AND GREASE.
PART 3 - EXECUTION
3.1 INSTALLATION
A. INSTALL DUCT ACCESSORIES ACCORDING TO APPLICABLE DETAILS IN SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE" FOR METAL
DUCTS.
B. INSTALL DUCT ACCESSORIES OF MATERIALS SUITED TO DUCT MATERIALS; USE GALVANIZED-STEEL ACCESSORIES IN GALVANIZED-STEEL, STAINLESS-STEEL
ACCESSORIES IN STAINLESS-STEEL DUCTS.
C. INSTALL DUCT ACCESS DOORS ON SIDES OF DUCTS TO ALLOW FOR INSPECTING, ADJUSTING, AND MAINTAINING ACCESSORIES AND EQUIPMENT AS REQUIRED.
D. INSTALL FLEXIBLE CONNECTORS TO CONNECT DUCTS TO EQUIPMENT.
E. CONNECT CEILING-MOUNTED SUPPLY DIFFUSERS TO DUCTS DIRECTLY OR WITH MAXIMUM 36-INCH LENGTHS OF FLEXIBLE DUCT CLAMPED IN PLACE. DO NOT
USE FLEXIBLE DUCTS TO CHANGE DIRECTION OR FOR CONNECTIONS TO EXHAUST OR RETURN REGISTERS OR GRILLES.
F. CONNECT FLEXIBLE DUCTS TO METAL DUCTS WITH STAINLESS STEEL BAND CLAMPS.
END OF SECTION 233300
PLUMBING
and HVAC
Cover Sheet
AUTHOR
CHECKED:
DAVIS DESIGN ALL RIGHTS RESERVED
SHEET TITLE
SHEET NUMBER
ID
ISSUE DATE:
DescriptionDate
Revisions:
15 E
ast M
ain, S
uite 201
Verm
illion S
D 57069
Phone 605-624-1081
Verm
illion
1221 N
S
treet, S
uite 600
Lincoln N
E 68508
Phone 402-476-9700
Fax 402-476-9722
Lincoln
M-001
07-16-2020
MA
BMS
M-001.dw
g
GENERAL NOTES
GENERAL NOTES
DIVISION 23 - HVAC
1.THE FOLLOWING NOTES APPLY TO ALL DRAWINGS AS APPLICABLE.
CONTRACTOR TO FIELD VERIFY ALL EXISTING CONDITIONS.
CONTRACTOR SHALL NOTIFY ARCHITECT/ENGINEER OF ANY
DISCREPANCIES OR CONFLICTS ENCOUNTERED ON THE PROJECT PRIOR
TO PROCEEDING WITH THE WORK.
ALL WORK SHALL CONFORM TO THE LOCALLY ADOPTED CODE AND/OR
CODE AMENDMENTS AND SHALL BE APPROVED BY THE LOCAL
AUTHORITY HAVING JURISDICTION.
ALL CONTRACTORS ARE RESPONSIBLE TO COORDINATE WITH ALL
OTHER TRADES. CHANGES REQUIRED DUE TO LACK OF COORDINATION
WILL BE AT THE CONTRACTORS EXPENSE.
DRAWINGS ARE DIAGRAMMATIC IN NATURE. CONTRACTOR IS
RESPONSIBLE FOR PROVIDING ALL COMPONENTS FITTINGS AND
EQUIPMENT REQUIRED TO INSTALL A COMPLETE AND FUNCTIONING
SYSTEM IN ACCORDANCE WITH THE DESIGN INTENT.
DO NOT SCALE FROM THESE DRAWINGS. REFER TO ARCHITECTURAL
AND STRUCTURAL DRAWINGS FOR DIMENSIONS.
THE LOCATIONS OF EXISTING COMPONENTS WERE OBTAINED FROM
EXISTING DRAWINGS AND FIELD INVESTIGATION. THE LOCATIONS OF THE
COMPONENTS ARE SHOWN FOR THE CONVENIENCE OF THE
CONTRACTOR, ACCURACY OF THE INFORMATION SHOWN IS NOT
GUARANTEED. THE CONTRACTOR IS RESPONSIBLE FOR THE
VERIFICATION OF ALL EXISTING CONDITIONS PRIOR TO SUBMITTING BIDS.
SITE VISITS SHALL BE FULLY COORDINATED WITH THE OWNER.
PROTECT EXISTING DATA CABLING, FURNITURE, CARPET AND OTHER
SYSTEMS AND APPURTENANCES FROM DAMAGE DURING THE COURSE
OF CONSTRUCTION. REPAIR OR REPLACE DAMAGED ITEMS AT NO COST
TO OWNER.
THE OWNER HAS THE RIGHT TO RETAIN ALL SALVAGEABLE MATERIAL.
ANY MATERIAL THE OWNER CHOOSES NOT TO ACCEPT SHALL BE
REMOVED FROM THE SITE AND PROPERLY DISPOSED OF BY THE
CONTRACTOR.
DEMOLITION THAT CREATES NOISE OR VIBRATION (CORE DRILLING,
CUTTING, ETC.) SHALL BE COORDINATED WITH THE OWNERS SCHEDULE
AND MAY TAKE PLACE ON NIGHTS OR WEEKENDS.
COORDINATE ALL SYSTEM SHUTDOWNS WITH THE OWNER, SHUTDOWNS
MAY REQUIRE NIGHT OR WEEKEND WORK.
COORDINATE ALL BELOW GRADE PIPING WITH FOOTINGS, COLUMNS AND
GRADE BEAMS, PROVIDE SLEEVES WHERE REQUIRED.
ABOVE CEILING INSPECTIONS WILL TAKE PLACE PRIOR TO PADDING OUT
EACH AREA, COORDINATE WITH ARCHITECT AND OWNER.
COORDINATE ALL HANGERS WITH INSTALLATION OF METAL BUILDING
SIMPLE SAVER INSULATION SYSTEM AND ITS VAPOR BARRIER.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
14.
1. THE FOLLOWING NOTES APPLY TO ALL DRAWINGS AS APPLICABLE.
PROVIDE TEMPORARY SPACERS BELOW PIPING TO RECEIVE INSULATION
OR COORDINATE WITH INSULATOR AND PROVIDE SUFFICIENT HANGER
ROD LENGTH TO ALLOW INSULATOR TO DROP HANGER FOR
INSTALLATION OF PIPE INSULATION WITHOUT CRUSHING. DO NOT
SWALLOW PIPE HANGERS IN INSULATION.
PROVIDE TEMPORARY SPACERS BELOW DUCTWORK SUPPORTED BY
TRAPEZE HANGERS TO RECEIVE INSULATION TO ALLOW FOR
INSTALLATION OF DUCT INSULATION WITHOUT CRUSHING. DO NOT
SWALLOW TRAPEZE DUCT HANGERS IN INSULATION.
UNLESS NOTED OTHERWISE, ALL DUCT DIMENSIONS CALLED OUT ARE
INTERIOR FREE AREA DIMENSIONS.
AT CONTRACTORS OPTION, EQUIVALENT ROUND DUCT DIMENSIONS MAY
BE UTILIZED IN LIEU OF RECTANGULAR DUCT DIMENSIONS IDENTIFIED ON
DRAWINGS. EQUIVALENT DIAMETER SHALL BE CALCULATED PER
SMACNA REQUIREMENTS FOR EQUAL FRICTION. UTILIZING EQUIVALENT
AREA IS NOT ACCEPTABLE. AS-BUILT DOCUMENTS SHALL BE UPDATED
ACCORDINGLY.
AT CONTRACTORS OPTION, TO COORDINATE WITH OTHER TRADES AND
BUILDING ELEMENTS, EQUIVALENT RECTANGULAR DUCT DIMENSIONS
MAY BE UTILIZED IN LIEU OF RECTANGULAR DUCT DIMENSIONS
IDENTIFIED ON DRAWINGS. EQUIVALENT SIZING SHALL HAVE EQUAL
FRICTION. DUCT ASPECT RATIO OF RESIZED DUCT SHALL NOT BE
GREATER THAN 3:1 WITHOUT ENGINEERS APPROVAL. UTILIZING
EQUIVALENT AREA IS NOT ACCEPTABLE. AS-BUILT DOCUMENTS SHALL
BE UPDATED ACCORDINGLY.
ALL ROUND DUCTWORK SERVING AIR TERMINALS SHALL BE CONNECTED
TO MAINS WITH A HIGH EFFICIENCY TAKEOFF INCLUDING DAMPER WITH
QUADRANT LOCK HANDLE AND INSULATION STANDOFF, SEE
SPECIFICATIONS.
DUCT BRANCH SIZES SHALL MATCH DIFFUSER NECK SIZES UNLESS
NOTED OTHERWISE.
BRONZE BALL VALVES WILL NOT BE ACCEPTED AS A SUFFICIENT
DIELECTRIC BREAK, SEE SPECIFICATIONS FOR DIELECTRIC FITTING
REQUIREMENTS.
NOT ALL PIPING COMPONENTS AND VALVES ARE SHOWN ON PLAN
DRAWINGS, REFERENCE DETAILS, PIPING SCHEMATICS AND
SPECIFICATIONS FOR PIPING VALVES AND COMPONENTS REQUIRED.
UNLESS NOTED OTHERWISE, EXISTING RTU SHALL BE PROVIDED WITH A
THERMOSTAT OR CONTROL SENSOR WHETHER INDICATED ON THE
PLANS OR NOT.
UNLESS NOTED OTHERWISE, ALL LOW VOLTAGE CONTROL WIRING
INTERCONNECTING MECHANICAL EQUIPMENT AND ANY ASSOCIATED
THERMOSTATS SHALL BE INSTALLED BY MECHANICAL CONTRACTOR.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
CLIENT INFORMATION
PROJECT INFORMATION
South Dakota
Army National
Guard
801 W National Guard Dr.
Sioux Falls, S.D 57104
CFMO# 466134
IFR
Remediation -
Foss Field
Armory
19-0102Job #
GENERAL NOTES
DIVISION 22 - PLUMBING
THE FOLLOWING NOTES APPLY TO ALL DRAWINGS AS APPLICABLE.
PROVIDE TEMPORARY SPACERS BELOW PIPING TO RECEIVE INSULATION
OR COORDINATE WITH INSULATOR AND PROVIDE SUFFICIENT HANGER
ROD LENGTH TO ALLOW INSULATOR TO DROP HANGER FOR
INSTALLATION OF PIPE INSULATION WITHOUT CRUSHING. DO NOT
SWALLOW PIPE HANGERS IN INSULATION.
BRONZE BALL VALVES WILL NOT BE ACCEPTED AS A SUFFICIENT
DIELECTRIC BREAK, SEE SPECIFICATIONS FOR DIELECTRIC FITTING
REQUIREMENTS.
NOT ALL PIPING COMPONENTS AND VALVES ARE SHOWN ON PLAN
DRAWINGS, REFERENCE DETAILS, PIPING SCHEMATICS AND
SPECIFICATIONS FOR PIPING VALVES AND COMPONENTS REQUIRED.
ALL INDIRECT WASTE DRAIN PIPING FROM KITCHEN EQUIPMENT SHALL
BE COPPER.
ALL FINAL EQUIPMENT CONNECTIONS TO KITCHEN EQUIPMENT SHALL BE
BY PLUMBING CONTRACTOR.
ALL PLUMBING PIPING IS MODELED WITH A LEVEL SLOPE FOR CLARITY.
CONTRACTOR IS RESPONSIBLE TO SET ELEVATIONS AND SLOPES OF
PIPING TO MEET CODE AND REQUIRED INVERT ELEVATIONS IN ADDITION
TO COORDINATING WITH STRUCTURE AND ALL OTHER TRADES.
1.
2.
3.
4.
5.
6.
7.
13.
15.
7/16/2020
MECHANICAL
225
FOOD STORAGE
VESTIBULE
71
Classroom
224
Office
224D
Office
224C
Office
224B
Office
224A
Corridor
224-1
T
2"W
S-2
1/2"CW
1/2"HW
2"W
EXISTING HWH
IMB-1
T
IMB-1(REFRIGRTATOR)
1
1
2
10x8
6Ø S-1
100
8Ø S-1
150
8Ø S-1
150
8Ø S-1
150
8Ø S-1
150
8Ø S-1
150
8Ø S-1
150
8Ø S-1
150
8Ø S-1
150
8Ø S-1
175
10x10R-110x10 R-1
10x10 R-1
10x10 R-1
22x22 R-1
6Ø S-1
125
8x10
16x10
22x10
22x10
8Ø8Ø
8Ø
8Ø
8Ø
8Ø
VD
VD
VD
VD
VDVD
VDVD
22x10
VD
VD
8Ø 8Ø
8
Ø
8Ø
3
VD
10x10 10x10
10x1010x10
2
10x8
10x8
10x8
1-1/2"V
9
P-101
1/2"CW
OFFICE
229
MECHANICAL
225
WOMENS LATRINE
227
MENS LATRINE
155
OFFICE
79
FOOD STORAGE
156
FOOD PREPERATION
157
SCULLERY
251
TRAINING
ROOM
233
STORAGE
232
STORAGE
231
TRAINING
ROOM
230
CORRIDOR
70
VESTIBULE
71
VESTIBULE
71
ASSEMBLY HALL
161
CORRIDOR
162
STORAGE
FLAMMABLE
MATERIALS
158
ASSEMBLY HALL
159B
ELECTRICAL ROOM
142
TELEPHONE ROOM
141
FURNANCE ROOM
140
CORRIDOR
139
JANITOR
143
TRAINING ROOM
144
ELECTRICAL
179
CORRIDOR
177
CORRIDOR
177A
VESTIBULE
178
TRAINING ROOM
182
Classroom
224
Office
224D
Office
224C
Office
224B
Office
224A
Corridor
224-1
T
2"W
S-2
1/2"CW
1/2"HW
2"W
EXISTING HWH
IMB-1
T
IMB-1(REFRIGRTATOR)
1
1
2
10x8
6Ø S-1
100
8Ø S-1
150
8Ø S-1
150
8Ø S-1
150
8Ø S-1
150
8Ø S-1
150
8Ø S-1
150
8Ø S-1
150
8Ø S-1
150
8Ø S-1
175
10x10R-1 10x10 R-1
10x10 R-110x10 R-1
22x22 R-1
6Ø S-1
125
8x10
16x10
22x10
22x10
8Ø 8Ø
8Ø8Ø
8Ø 8Ø
VD
VD
VD
VD
VD VD
VD VD
22x10
VD
VD
8Ø 8Ø
8
Ø
8Ø
3
VD
10x10 10x10
10x1010x10
2
10x8
10x8
10x8
1-1/2"V
9
P-101
1/2"CW
S
1-1/2"W
1-1/2"V
CO
ABOVE
BACKSPLASH
SCALE:
2
NO SCALE
SINK ISOMETRIC
2"W
FD
1-1/2"V
1
W
A
2
W
L
W
30° MAX.
L
W
W
WW
1
A
L
2
W
W
L
30° MAX.
W
SCALE:
4
NO SCALE
OFFSET AND
TRANSITION DETAIL
OFFSET TYPE 1
(MITERED)
OFFSET TYPE 2
(MITERED)
CONCENTRIC TRANSITION
A (MAX.)=45° DIVERGING, 60° CONVERGING
ECCENTRIC TRANSITION
A (MAX.)=30°
CEILING
4"
ELEVATION
OPEN ON TOP
OPEN ON BACKSIDE
OPEN ON SIDE
ELEVATION
1.5D
3D
M
IN
.
AIR
F
LO
W
D
PLAN
4"
SEE PLANS FOR SIZE/TYPE
RETURN GRILLE
CEILING
3D MIN.
SCALE:
5
NO SCALE
SOUND TRAP
DETAIL AT GRILLE
NOTE:
SOUND TRAP TO HAVE SAME INSIDE NET DIMENSIONS AS
INDICATED FOR OPENING
SEE PLANS
SEE PLANS
1" ACOUSTICAL
DUCT LINER
(SEE SPECS)
3D
M
IN
.
AIR
F
LO
W
D
PLAN
SEE PLANS FOR SIZE/TYPE
RETURN GRILLE
1" ACOUSTICAL
DUCT LINER
(SEE SPECS)
1.5
D
3D MIN.
OPEN ON TOP
D
D
3D MIN
D
AIR
FL
OW
WALL
3D MIN
SCALE:
3
NO SCALE
SOUND TRAP
DETAIL AT WALL
NOTE:
SOUND TRAP TO HAVE SAME
INSIDE NET DIMENSIONS AS
INDICATED FOR OPENING.
SEAL AROUND
DUCT AT THE WALL
1" ACOUSTICAL
DUCT LINER
(SEE SPECS)
NOTE:
SOUND TRAP TO HAVE SAME
INSIDE NET DIMENSIONS AS
INDICATED FOR OPENING.
D
MIN
SUPPLY DUCT-SEE
PLANS FOR SIZES
DIFFUSER NECK
CEILING
SUPPLY DIFFUSER
Ø = X"
X +
1
"
1" MIN.
FLEXIBLE DUCTWORK
MAXIMUM LENGTH AS
DETERMINED IN
SPECIFICATIONS
REGAIN BOX TO BE CONSTRUCTED,
INSULATED AND SUPPORTED SEE
SPECIFICATIONS
X + 1"
SCALE:
7
NO SCALE
SUPPLY DIFFUSER/DUCT
CONNECTION DETAIL
DAMPER STANDOFF
DAMPER
QUADRANT
LOCK
SCALE:
6
NO SCALE
HIGH EFFICIENCY
TAKEOFF DETAIL
HANGERS FOR STACKED DUCTS
TRAPEZE HANGERS
12"MAX. SPACING
BAND
HANGER STRAP
SCREWS
1"MIN.
3"
ANGLES
NUTS
ROD
STRAP HANGERS
NOTES:
1. REINFORCEMENT MAY BE USED FOR ATTACHMENT IF IT QUALIFIES FOR BOTH DUTIES. DO NOT EXCEED
LOAD RATING FOR METHOD USED.
2. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION AND ALLOWABLE USES.
SLING, AVOID
DISRUPTION OF
INSULATION
PREFERRED
STRAP
ATTACHMENT
SIZE BOLT(S)
FOR LOAD
LOAD RATED
FASTENERS
HANGER
STRAP
BAND OF SAME SIZE
AS HANGER STRAP
HANGER RODS
OR STRAP
STRAP OR ANGLE
ROD
ALTERNATE
LOCATION
INSULATION SHALL
RUN CONTINUOUS
THRU HANGER
HANGER
CABLE
CABLE
CLAMP
CABLE, AVOID
DISRUPTION OF
INSULATION
SCALE:
8
NO SCALE
DUCT HANGER DETAIL
CONNECT NEW CW HERE
SCALE:
9
NO SCALE
EXISTING WATER HEATER
Plumbing and
HVAC Plan
AUTHOR
CHECKED:
DAVIS DESIGN ALL RIGHTS RESERVED
SHEET TITLE
SHEET NUMBER
ID
ISSUE DATE:
DescriptionDate
Revisions:
15 E
ast M
ain, S
uite 201
Verm
illion S
D 57069
Phone 605-624-1081
Verm
illion
1221 N
S
treet, S
uite 600
Lincoln N
E 68508
Phone 402-476-9700
Fax 402-476-9722
Lincoln
M-101
07-16-2020
MA
BMS
A-1
01
SCALE:
1
PLUMBING AND HVAC PLAN
1/4" = 1'-0"
CLIENT INFORMATION
PROJECT INFORMATION
South Dakota
Army National
Guard
801 W National Guard Dr.
Sioux Falls, S.D 57104
CFMO# SF466146
Convert IFR
to Classroom -
Foss Field
Armory
20-0067Job #
KEY PLAN
AREA OF WORK
1. SEE SHEET M-001 FOR GENERAL NOTES.
GENERAL HVAC NOTES
DEMOLITION KEYED NOTES
REMOVE EXISTING BMS SENSOR AND COORDINATE WITH NEW WORK.
REMOVE EXISTING 18x18 LINED SUPPLY AND RETURN AIR DUCT DROPS
AND ELBOWS FROM RTU. NEW UNLINED DUCTWORK TO BE PROVIDED
AS PART OF NEW WORK.
DO NOT TEAR UP FLOOR IN FORMER IFR SPACE, SINK WASTE MUST
RUN IN FURRED OUT WALL. REMOVE AND PATCH CONCRETE IN
MECHANICAL ROOM AS REQUIRED TO CONNECT TO EXISTING DRAIN.
HVAC PLAN KEYED NOTES
CONTROLS WORK SHALL BE BY BUILDING CONTROLS CONTRACTOR
CLIMATE SYSTEMS, INC. INSTALL RELOCATED/NEW SENSOR TO
OPERATE PACKAGED RTU. COORDINATE OCCUPIED/UNOCCUPIED
TIMES WITH OWNER DURING SETUP. ADD OUTSIDE AIR DAMPER
CONTROL SEQUENCE INCLUDING ECONOMIZER SEQUENCE. OUTSIDE
AIR SHALL CLOSE DURING UNOCCUPIED PERIODS.
INSTALL LENNOX MODEL 14D90 ECONOMIZER KIT WITH 53W64
ENTHALPY SENSOR ON EXISTING LENNOX KGA060 ROOFTOP UNIT.
BALANCE TO 400 CFM OUTSIDE AIR AT MINIMUM POSITION. PROVIDE
WITH BAROMETRIC RELIEF. INSTALL LENNOX MODEL 13R98 HAIL
GUARD ON EXISTING LENNOX ROOFTOP UNIT. COMB EXISTING COILS
PRIOR TO INSTALLATION OF HAIL GUARDS. BALANCE UNIT TO
AIRFLOWS INDICATED.
1
1
2
2
3
7/16/2020
MECHANICAL
225
FOOD STORAGE
156
VESTIBULE
71
RIFLE RANGE
224
21
PANEL L2
72"x30" 72"x30"
72"x30" 72"x30"
72"x30" 72"x30"
72"x30" 72"x30"
72"x30" 72"x30"
72"x30" 72"x30"
72"x30" 72"x30"
MECHANICAL
225
FOOD STORAGE
156
VESTIBULE
71
Classroom
224
Office
224D
Office
224C
Office
224B
Office
224A
Corridor
224-1
A2 A2
A2 A2
A2 A2
A2 A2
A2 A2
A2 A2
A2
A2
A2
A2
A2
A2
A2
A2
A1
A1
A1
X1
X1
33
3
3
PANEL L2
C
O
C
O
C
O
C
O
C
O
C
O
C
O
C
O
PP
2
3
5
5
5
4
3
3
3
3
X1
MECHANICAL
225
WOMENS LATRINE
227
MENS LATRINE
155
OFFICE
79
FOOD STORAGE
156
FOOD PREPERATION
157
SCULLERY
251
STORAGE
232
CORRIDOR
70
VESTIBULE
71
VESTIBULE
71
ASSEMBLY HALL
161
CORRIDOR
162
STORAGE
FLAMMABLE
MATERIALS
158
ASSEMBLY HALL
159B
ELECTRICAL ROOM
142
TELEPHONE ROOM
141
FURNANCE ROOM
140
CORRIDOR
139
JANITOR
143
TRAINING ROOM
144
ELECTRICAL
179
CORRIDOR
177
CORRIDOR
177A
VESTIBULE
178
TRAINING ROOM
182
Classroom
224
Office
224D
Office
224C
Office
224B
Office
224A
Corridor
224-1
72"x30" 72"x30"
72"x30" 72"x30"
72"x30" 72"x30"
72"x30" 72"x30"
72"x30" 72"x30"
72"x30" 72"x30"
72"x30" 72"x30"
EXISTING PUNCH
DOWN BLOCKS
EXISTING DATA
RACK
PANEL L2
6
F
J J
F
44"
GFI
2
2
(2)(2)
44"
(2)
44"
2
2
2
2
2
22
(2)(2)
(2)
(2)
(2)
(2)
7
7
8
8
PANEL L5
(EXISTING)
PANEL E
(EXISTING)
MAIN
SWITCHBOARD
(EXISTING)
FA
FACP
EXISTING
EXISTING
EXISTING
10
10
F
10
9
10
(2)
44"
(2)
(2)
(2)
(2)
WAP
(1)
11
11
11
11
11
12
1
GFI
13
13
13
(2)
44"
(2)
(2)
(2)
Electrical
Plan-
Demolition
and New
AUTHOR
CHECKED:
DAVIS DESIGN ALL RIGHTS RESERVED
SHEET TITLE
SHEET NUMBER
ID
ISSUE DATE:
DescriptionDate
Revisions:
15 E
ast M
ain, S
uite 201
Verm
illion S
D 57069
Phone 605-624-1081
Verm
illion
1221 N
S
treet, S
uite 600
Lincoln N
E 68508
Phone 402-476-9700
Fax 402-476-9722
Lincoln
E-101
07-16-2020
TIG
JPD
CLIENT INFORMATION
PROJECT INFORMATION
South Dakota
Army National
Guard
801 W National Guard Dr.
Sioux Falls, S.D 57104
CFMO# SF466146
Convert IFR
to Classroom -
Foss Field
Armory
20-0067Job #
SCALE:
1
ELECTRICAL PLAN - DEMOLITION
1/8" = 1'-0"
SCALE:
2
LIGHTING PLAN - NEW
1/8" = 1'-0"
LIMIT OF CONSTRUCTION, COORDINATE ANY WORK EXTRA WORK WITH OWNER.
CONNECT TO A SPARE 20A/1 POLE CIRCUIT BREAKER IN PANEL L2.
PROVIDE AND INSTALL LINE VOLTAGE OCCUPANCY SENSOR BY GREENGATE MODEL
#OAC-DT-2000-MV OR EQUAL.
PROVIDE AND INSTALL SP15 HEAVY DUTY POWER PACK BY GREENGATE OR EQUAL.
PROVIDE AND INSTALL LOW VOLTAGE VACANCY CEILING SENSOR BY GREENGATE MODEL
#VAC-P-1500-R OR EQUAL. VACANCY SENSORS SHALL BE CONNECTED TO POWER PACK SHOWN ON
PLAN.
PROVIDE AND INSTALL NEW 110 PUNCH DOWN BLOCK IN TELEPHONE ROOM 141. SEE DETAIL ON E-502.
PROVIDE WALL MOUNTED HDMI CONNECTOR AND PROVIDE 50'-0" LONG HDMI CABLE AND ROUTE IN
1-1/4" CONDUIT FROM MONITOR LOCATION TO WORKSTATION, COIL EXTRA CABLE LENGTH AS
NEEDED. CONFIRM WITH OWNER FOR FINAL MOUNTING HEIGHT OF HDMI CONNECTOR FOR MONITOR.
CONFIRM HEIGHT FOR RECEPTACLE AT DATA JACK FOR MONITOR.
ELECTRICAL CONTRACTOR SHALL PROVIDE J-HOOK PATH FROM CLASSROOM TO TELEPHONE ROOM
141. PROPOSED ROUTE IS SHOWN ON PLAN. PATH IS SHOWN TO KEEP DATA CABLING RUN UNDER
300'-0". COORDINATE FINAL J-HOOK PATH TO ACCOMMODATE FOR CABLING LIMITATIONS.
FIRE ALARM DEVICE SHALL BE ROUTED BACK TO EXISTING FIRE-LITE FIRE ALARM CONTROL PANEL IN
ELECTRICAL ROOM 179. EXISTING FIRE ALARM SYSTEM IS A DIGITAL ADDRESSABLE FIRE ALARM
SYSTEM MODEL #MS-9200UDLS. VERIFY CAPACITY OF FIRE ALARM CONTROL PANEL AND PROVIDE
EXTENDER PANEL IF NEEDED.
PROVIDE AND INSTALL EZ PATH PASS THROUGH SERIES 33 FOR LOW VOLTAGE WIRE. SEAL AROUND
OUTER EDGES OF PATHWAYS. INSTALL AT A MINIMUM OF 6" ABOVE CEILING. SEE DETAIL ON SHEET
E-502.
EXISTING CONDUIT PENETRATION INTO TELEPHONE ROOM 141 SHALL BE USED.
NEW SMOKE DETECTOR SHALL BE INSTALLED AND CONNECTED TO THE EXISTING FIRE-LITE FIRE
ALARM SYSTEM. CONTRACTOR MAY TIE INTO NEAREST DETECTION DEVICE PROVIDED CIRCUIT WILL
SUPPORT THE ADDITIONAL DEVICE.
ELECTRICAL KEYED NOTES
SCALE:
3
POWER AND SYSTEMS - NEW
1/8" = 1'-0"
LIMIT OF CONSTRUCTION, COORDINATE ANY WORK EXTRA WORK WITH OWNER.
ELECTRICAL CONTRACTOR SHALL DISCONNECT AND REMOVE ALL ELECTRICAL LIGHT FIXTURES,
DEVICES AND ASSOCIATED CONDUIT AND CIRCUIT WIRING BACK TO SOURCE PANEL. INDOOR FIRING
RANGE HAS BEEN SHELLED OUT. A COUPLE OF LIGHT FIXTURES AND RECEPTACLES REMAIN IN THE
SPACE. ROUGH-IN BOXES THAT ARE SURFACE MOUNTED TO CMU SHALL BE REMOVED. ROUGH-IN
BOXES THAT ARE RECESSED WITH IN CMU SHALL HAVE A BLANK COVER PLATE INSTALLED AND
STUB-UP ABANDONED UNLESS AT A LOCATION THAT CAN BE RE-USED AS SHOWN ON NEW POWER
PLAN. ANY ELECTRICAL POWER TO MECHANICAL EQUIPMENT THAT IS NOT DESIGNATED TO BE
REMOVED ON MECHANICAL DRAWINGS SHALL REMAIN. COORDINATE WITH MECHANICAL DRAWINGS
FOR EXISTING EQUIPMENT.
DEMOLITION KEYED NOTES
1
2
1
2
3
4
5
6
1. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE, STATE AND
ALL LOCAL CODES.
2. SEE ARCHITECTURAL SERIES SHEET FOR EXACT AREAS AND WALLS AFFECTED BY THE
DEMOLITION AND REMODEL.
3. DEMOLITION SHOWN IS AS REQUIRED FOR THE COMPLETE PROJECT. THE CONTRACTOR SHALL
COORDINATE THE DEMOLITION EFFORT WITH THE WORK OF OTHER TRADES. PROVIDE TEMPORARY
POWER AND LIGHTS AS REQUIRED TO ALLOW THE WORK OF OTHER TRADES TO PROCEED OR AS
REQUIRED TO ALLOW THE OWNER TO OCCUPY THE SPACE.
4. ALL OF THE EQUIPMENT AND DEVICES SHOWN ON THIS DRAWING ARE EXISTING. THE LOCATIONS
OF THE EQUIPMENT AND DEVICES WERE OBTAINED FROM EXISTING DRAWINGS AND FIELD
INVESTIGATION. THE LOCATIONS OF THE EXISTING EQUIPMENT AND DEVICES ARE SHOWN FOR THE
CONVENIENCE OF THE CONTRACTOR. ACCURACY OF THE INFORMATION SHOWN IS NOT
GUARANTEED. THE CONTRACTOR IS RESPONSIBLE FOR THE VERIFICATION OF ALL EXISTING
CONDITIONS PRIOR TO SUBMITTING BIDS. SITE VISITS PRIOR TO SUBMISSION OF BIDS NEED TO BE
FULLY COORDINATED WITH THE OWNER.
5. ACTUAL CIRCUITING IS NOT SHOWN. CIRCUIT INFORMATION FOR ALL AFFECTED CIRCUITS SHALL BE
VERIFIED PRIOR TO COMMENCING WORK. ACCURACY OF THE INFORMATION SHOWN AND INCLUDED
ON THE PANEL SCHEDULES IS NOT GUARANTEED.
6. FIXTURES AND DEVICES INDICATED TO BE REMOVED, WHICH ARE LOCATED ON CEILINGS OR WALLS
ALSO INDICATED TO BE REMOVED, SHALL HAVE FIXTURES, DEVICE AND ALL ASSOCIATED CIRCUIT
WIRING,CONDUIT, AND RACEWAYS REMOVED BACK TO NEAREST JUNCTION BOX, OR DEVICE NOT
INDICATED TO BE REMOVED. THE CONTRACTOR SHALL PROVIDE ALL NECESSARY WIRE, CONDUIT,
DEVICES AND CONNECTIONS NECESSARY TO ENSURE CIRCUIT CONTINUITY OF THE REMAINING
DEVICES.
7. FIXTURES AND DEVICES INDICATED TO BE REMOVED, WHICH ARE LOCATED ON CEILINGS OR WALLS
NOT INDICATED TO BE REMOVED, SHALL HAVE FIXTURES, DEVICE AND ALL ASSOCIATED CIRCUIT
WIRING REMOVED BACK TO NEAREST JUNCTION BOX OR DEVICE NOT INDICATED TO BE REMOVED.
EXISTING BOX AND ASSOCIATED CONDUIT SHALL REMAIN. PROVIDE BLANK COVER PLATE FOR
REMAINING OPENING. COVER PLATE FINISH TO MATCH EXISTING IN SAME ROOM. THE CONTRACTOR
SHALL PROVIDE ALL NECESSARY WIRE, CONDUIT, DEVICES AND CONNECTIONS NECESSARY TO
ENSURE CIRCUIT CONTINUITY OF THE REMAINING DEVICES.
8. WHERE WALLS OR CEILINGS ARE INDICATED TO BE REMOVED, ELECTRICAL CONTRACTOR SHALL
REVIEW EXISTING ELECTRICAL INSTALLATIONS WITHIN, THROUGH, OR ABOVE COMPONENT BEING
REMOVED, AND MAKE PROVISIONS TO SUPPORT ANY RACEWAY, OR CABLE NOT REQUIRED TO BE
REMOVED. ALL ELECTRICAL INSTALLATIONS AFTER DEMOLITION SHALL BE COMPLIANT WITH NEC
FOR SUPPORT AND INSTALLATION.
9. THE OWNER HAS THE RIGHT TO RETAIN ALL SALVAGEABLE MATERIAL. ANY MATERIAL THE OWNER
CHOOSES NOT TO ACCEPT SHALL BE REMOVED FROM THE SITE AND PROPERLY DISPOSED OF BY
THE CONTRACTOR. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR THE REMOVAL OF ANY PCB
BALLAST. COORDINATE A MEETING WITH THE OWNER TO DISCUSS SALVAGEABLE MATERIAL AND
DEVICES PRIOR TO COMMENCING DEMOLITION.
10. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE LABELING OF SPARE OR ABANDONED
CIRCUITS AND/OR CIRCUIT BREAKERS IN ALL PANELS AFFECTED BY THE DEMOLITION. SPARE
CIRCUITS AND/OR CIRCUIT BREAKERS MAY BE REUSED FOR THE CIRCUITING OF THE NEW OR
REMODELED AREA AS SPACE AND PANEL LOADING WILL ALLOW. CONTRACTOR SHALL BE
RESPONSIBLE FOR THE RE-LABELING OF PANEL SCHEDULES AS NEW CIRCUITS ARE TERMINATED IN
EXISTING PANELS AND SHALL NOTIFY OWNER AND ENGINEER OF RECORD OF ALL CHANGES MADE
TO PANEL SCHEDULES.
11. THE GENERAL CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE PROPER RESTORATION
OF ALL EXISTING SURFACES REQUIRING PATCHING, PLASTERING, PAINTING AND/OR OTHER REPAIR
DUE TO THE DEMOLITION WORK DONE BY THE ELECTRICAL CONTRACTOR, UNDER THE TERMS OF
THIS SPECIFICATION. CLOSE AND SEAL ALL OPENINGS, REPAIR ALL SURFACES, ETC., AS REQUIRED.
12. PROJECT WORK INCLUDES PARTIAL DEMOLITION OF AREA. ALL LIGHT FIXTURES, DEVICES,
ASSOCIATED WIRING AND CONDUIT (NOT SHOWN) IN AREAS OF DEMOLITION SHALL BE REMOVED
UNLESS OTHERWISE NOTED. THE CONTRACTOR SHALL DISABLE ALL CIRCUITS AT THE SOURCE
PANEL BOARD, DISCONNECT CONDUIT AT FIRST JOINT DOWN STREAM OF PANEL BOARD AND
REMOVE ALL COMPONENTS DOWN STREAM. CONTRACTOR SHALL FIELD VERIFY DEMOLITION
REQUIREMENTS AS NECESSARY TO DEVELOP BID.
13. PROVIDE MINIMUM [2] DAYS ADVANCE NOTICE OF OUTAGES TO ANY INDIVIDUAL NORMAL OR
EMERGENCY POWER PANEL, OR CIRCUITS OUTSIDE THE AREA OF WORK. COORDINATE WITH
OWNER FOR ALL ANTICIPATED OUTAGES. OWNER HAS FINAL APPROVAL ON TIME AND EXTENT OF
POWER OUTAGE.
14. COORDINATE AND PERFORM A WALK-THROUGH WITH THE OWNER TO GO THROUGH LIST OF
SPECIAL CONCERNS AND AREAS AFFECTED DURING ANY OUTAGE.
15. POWER TO EXISTING AREAS, WALLS OR SECTIONS NOT BEING REMODELED, SHALL BE MAINTAINED
AT ALL TIMES EXCEPT FOR SHORT TERM OUTAGES NECESSARY FOR RECONNECTION OF EXISTING
CIRCUITS. COORDINATE AND SCHEDULE OUTAGES WITH THE OWNER.
16. PROTECT EXISTING FURNITURE, CARPET AND OTHER APPURTENANCES FROM DAMAGE DURING
THE COURSE OF CONSTRUCTION. REPLACE DAMAGED ITEMS FREE OF COST TO THE OWNER.
17. MAINTAIN THE PROJECT SITE FREE AND CLEAR OF RUBBISH AND DEBRIS ON A WEEKLY BASIS.
GENERAL DEMOLITION NOTES
1. SEE SHEET E-502 FOR SYMBOL LEGEND.
2. SEE ARCHITECTURAL SERIES SHEETS FOR REFLECTED CEILING PLANS.
3. SEE SHEET E-501 FOR LIGHTING INSTALLATION DETAILS AND GENERAL DETAILS.
4. FIXTURE TYPES HAVE BEEN SELECTED FOR LOOK AND PERFORMANCE. ALTERNATE LIGHT
FIXTURES MAY BE SUBMITTED FOR PRIOR APPROVAL IF A FOOT-CANDLE LEVEL PRINTOUT FOR THE
CEILING AND 30" WORK PLANE HEIGHT IS INCLUDED AND REQUEST IS RECEIVED 10 DAYS PRIOR TO
BID DATE.
5. SEE ARCHITECTURAL SERIES SHEETS FOR ARCHITECTURAL ELEVATIONS AND MORE PRECISE
LOCATIONS OF ALL WALL MOUNTED ELECTRICAL DEVICES. COORDINATE LOCATION OF SWITCH
HEIGHTS WITH CASEWORK, FURNITURE AND EQUIPMENT LAYOUTS PRIOR TO ROUGH-IN. SEE
ARCHITECTURAL CASEWORK ELEVATIONS FOR CABINET HEIGHTS AND LAYOUTS.
6. COORDINATE FINAL LOCATIONS OF ALL LIGHT FIXTURES WITH MECHANICAL DUCTWORK. DO NOT
SUPPORT FIXTURES FROM DUCTWORK, SUPPORT ONLY TO STRUCTURE.
7. CEILING MOUNTED DEVICES SHALL BE CENTERED IN CEILING TILE WHERE INSTALLED IN
ACOUSTICAL TILE CEILING.
8. ALL CIRCUITS SHALL HAVE SEPARATE NEUTRAL WIRES BUT CAN SHARE AN INSULATED GREEN
GROUND WIRES (NOT SHOWN) IN MINIMUM 3/4" EMT CONDUIT WITH STEEL COMPRESSION FITTINGS.
AC, MC, BX CABLE SHALL NOT BE USED AND WILL NOT BE ACCEPTED IN ANY FASHION. (TYPICAL)
9. ALL EXIT SIGNS TO BE WIRED INTO A CONTINUOUS HOT NON SWITCHED PORTION OF THE CIRCUIT.
10. FIXTURES SHOWN AS EMERGENCY FIXTURES ARE TO BE PROVIDED WITH BATTERY BACKUP SO
FIXTURE TURNS ON TO 100% IN THE EVENT OF A POWER FAILURE. PROVIDE CONTINUOUS HOT
NON-SWITCHED WIRE TO EACH EMERGENCY FIXTURE.
11. NO BOXES SHALL BE MOUNTED BACK TO BACK. SEE DETAIL ON SHEET E-501.
12. SEE SHEET E-501 FOR DETAIL FOR WIRE TAP DETAIL.
13. SEE SHEET E-501 FOR DETAIL FOR JUNCTION BOX LABELING DETAIL
14. ALL LOW VOLTAGE WIRING SHALL BE PLENUM RATED AND PROPERLY SUPPORTED. LAYING CABLE
ACROSS CEILING GRID IS NOT CONSIDERED PROPERLY SUPPORTED.
15. ALL WIRING SHALL BE CONCEALED IN ROOMS UNLESS INDICATED BY KEYED NOTE OR WRITTEN
APPROVAL OF THE ENGINEER OR ARCHITECT.
16. WHERE WORK WILL OCCUR IN OCCUPIED AREAS PROTECT EXISTING FURNITURE, FLOORING AND
OTHER APPURTENANCES FROM DAMAGE DURING THE COURSE OF CONSTRUCTION. REPLACE OR
REPAIR DAMAGED ITEMS AT NO COST TO OWNER.
17. EXAMINE THE ARCHITECTURAL DRAWINGS AND FAMILIARIZE YOURSELF WITH THE NEW
CONSTRUCTION MATERIALS WHICH MAY AFFECT YOUR WORK.
18. RE-LABEL ALL EXISTING PANEL SCHEDULES THAT HAVE CHANGED WITH CORRECT ROOM
INFORMATION AND LOAD DESCRIPTION.
19. FOR 120 VOLT LIGHTING CIRCUITS WHERE CIRCUIT LENGTH EXCEEDS 75 FEET, #10AWG SHALL BE
USED. WHERE CIRCUIT EXCEEDS 125 FEET, #8AWG SHALL BE USED FOR FIRST 75 FEET. (MIN.)
20. ELECTRICAL CONTRACTOR TO SEAL ALL PENETRATIONS THROUGH FIRE RATED WALLS/FLOORS
THAT ELECTRICIAN CREATES. SEE DETAILS ON SHEET E5-1. ALL RACEWAYS ROUTED THROUGH
WALLS, AND FLOORS SHALL BE SEALED AS REQUIRED BY AND IN ACCORDANCE WITH NEC
PARAGRAPHS 230.8, 300.5(G) AND 300.7(A)."
21. ALL DEVICES SHOWN SHALL BE MOUNTED AT 18" A.F.F. UNLESS INDICATED OTHERWISE. SEE
ARCHITECTURAL SERIES SHEETS FOR ARCHITECTURAL ELEVATIONS AND MORE PRECISE
LOCATIONS OF ALL ELECTRICAL GEAR.
22. ALL DATA JACKS SHOWN SHALL BE ROUGH-IN BOXES AND STUB UP CONDUITS EXTENDED TO
WITHIN 6" OF NEAREST J-HOOK PATH. PROVIDE PULL STRING WITH PLASTIC BUSHING. PROVIDE AND
CAT 6 BLUE CABLE FOR DATA. ALL BOXES SHALL HAVE BOX SUPPORTS. DATA SHALL TERMINATE IN
110 PUNCH DOWN BLOCKS TELEPHONE ROOM, SEE DETAILS ON SHEET E-501 FOR MORE
INFORMATION.
23. COORDINATE ALL POWER LOCATIONS FOR EQUIPMENT WITH EQUIPMENT THAT IS SUPPLIED AND
WITH ALL TRADES.
24. ALL ELECTRICAL DEVICES ARE TO BE COORDINATED WITH FURNITURE INSTALLATION PRIOR TO
ROUGH-IN TO AVOID ANY CONFLICTS WITH FURNITURE SYSTEM PANELS.
25. ALL NEW AND EXISTING RECEPTACLES THAT ARE FOUND TO BE WITHIN 6' OF A SINK OR WATER
SOURCE THAT ARE NOT A GFI DEVICE OR GFI PROTECTED WITH ANOTHER DEVICE OR CIRCUIT
BREAKER ARE TO BE CHANGED OUT TO A PROPER GFI DEVICE PRIOR TO FINAL INSPECTION.
GENERAL LIGHTING NOTES
7
8
9
10
11
12
13
7/16/2020
Electrical
Details
AUTHOR
CHECKED:
DAVIS DESIGN ALL RIGHTS RESERVED
SHEET TITLE
SHEET NUMBER
ID
ISSUE DATE:
DescriptionDate
Revisions:
15 E
ast M
ain, S
uite 201
Verm
illion S
D 57069
Phone 605-624-1081
Verm
illion
1221 N
S
treet, S
uite 600
Lincoln N
E 68508
Phone 402-476-9700
Fax 402-476-9722
Lincoln
E-501
07-16-2020
TIG
JPD
FOR ALL COMBUSTIBLE WALLS PLASTER RING MUST
BE FLUSH WITH OUTER SURFACE OF WALL. FOR ALL
NON-COMBUSTIBLE WALLS PLASTER RING MUST BE
WITHIN 1/8" FROM OUTER SURFACE OF WALL.
GYPSUM BOARD
STUD
BOX
SUPPORT
OFFSET
CADDY QUICK MOUNT BOX
SUPPORT CADDY BOX
SUPPORT #H23, H4, H53 (AS
APPROPRIATE)
ELECTRICAL CONTRACTOR TO SIZE DEPTH
OF PLASTER RING TO INCLUDE BOX
SUPPORT OFFSET, THICKNESS OF DRYWALL
AND WALL COVERING (IF USED)
SOME EXAMPLES:
-3/4" PLASTER RING FOR SINGLE LAYER
5/8" GYPSUM BOARD WALL FINISH
-1" PLASTER RING FOR TWO LAYER
WALL FINISH 1/2" OVER 1/4"
SCALE:
1
BOX SUPPORT
NO SCALE
PLAN VIEW 2
4" SQUARE BOX
12
" M
NI.
STUD
METAL WALL
PLAN VIEW 1
OR
CADDY BOX
SUPPORT
(NOTE 1)
NOTES:
1. PROVIDE BOX SUPPORT FOR ALL BOXES
2-GANG OR LARGER. TYPE BY CONTRACTOR.
2. OUTLETS ON ADJACENT WALLS THAT ARE FIRE
RATED WALLS, SHALL HAVE TWO STUDS
BETWEEN BOXES.
SEE ARCHITECTURAL
PLANS FOR WALL
CONSTRUCTION.
BOX BRACE
(NOTE 1)
SEE ARCHITECTURAL
PLANS FOR WALL
CONSTRUCTION.
SCALE:
ELECTRICAL OUTLETS
IN COMMON WALL
2
NO SCALE
1" MINERAL WOOL PACKING
NOTE:
WALL SECTION
1. MATERIALS AND CONFIGURATION SHOWN
ARE FOR UL SYSTEM # 147(D).
1/4" MIN., 1 1/4" MAX.
ANNULAR SPACE
1/2" DEPTH CP-25WB
OR CP-25N/S CAULK
28 GAUGE STEEL SLEEVE
WITH 1/2" MIN. OVERLAP
6" RIGID STEEL, 4" EMT OR
1" FLEXIBLE CONDUIT MAX.
ONE OR TWO HOUR RATED
GYPSUM WALLBOARD ASSEMBLY
1/4" BEAD OF CP-25WB
CAULK, BOTH SIDES OF WALL
1" MINERAL WOOL PACKING
NOTE:
WALL SECTION
1/4" MIN., 1 1/4" MAX.
ANNULAR SPACE
28 GAUGE STEEL SLEEVE
WITH 1/2" MIN. OVERLAP
1/2" DEPTH CP-25WB
OR CP-25N/S CAULK
6" RIGID STEEL, 4" EMT, 1"
FLEXIBLE CONDUIT MAX.
PIPE OR DUCT
CMU
1/4" BEAD OF CP-25WB
CAULK, BOTH SIDES OF WALL
1. MATERIALS AND CONFIGURATION SHOWN
ARE FOR UL SYSTEM # 147(D).
FLEX CONDUIT PER
SPECIFICATIONS
CONDUIT TO
OTHER FIXTURES
LIGHT
FIXTURES
CONDUIT TO
PANELBOARD
OR OTHER
FIXTURES.
4" SQUARE OR
OCTAGON BOX.
4 TAP MAX.
LIGHT
FIXTURES
NOTES:
CIRCUIT #'S
CIRCUIT #'S
CIR
CU
IT
#
'S
CIR
CU
IT
#
'S
1. LABEL JUNCTION BOX COVER &
CONDUITS WITH BLACK
PERMANENT MARKER.
2. SPRAY PAINT JUNCTION BOX
COVERS PER SPECIFICATIONS.
3. SEE SPECIFICATION SECTION
260553 FOR ADDITIONAL
INFORMATION.
4. WHERE COVERS ARE PAINTED,
LABEL CIRCUIT ON INSIDE OF
COVER PRIOR TO PAINTING.
JUNCTION BOX
TAG WIRING
INSIDE.
BRANCH
CIRCUIT
CONDUIT.
(TYPICAL)
VOLTAGE
PANEL #
SCALE:
7
J-BOX LABELING DETAIL
NO SCALE
SCALE:
ACCESSIBLE CEILING
FIXTURE WIRE TAP
5
NO SCALE
SCALE:
BREACH SEALING DETAIL
ONE AND TWO HOUR FIRE-STOP
3
NO SCALE
SCALE:
BREACH SEALING DETAIL
ONE AND TWO HOUR FIRE-STOP
4
NO SCALE
CLIENT INFORMATION
PROJECT INFORMATION
South Dakota
Army National
Guard
801 W National Guard Dr.
Sioux Falls, S.D 57104
CFMO# SF466146
Convert IFR
to Classroom -
Foss Field
Armory
20-0067Job #
1
2
3
4
5
6
7
8
9
10
The Wire marking Will Be Left to Right
Face Plates Will Be Marked with a Label Machine.
Mark the Wire at the Jack.
Same as Back Field
First # Is Telecom Room #
Telephone Jack
Telephone Wire
4-9/16"x 4-9/16"x 2-5/8" Deep
with Single Plaster Ring
Wall
Conduit
Ceiling
Bushing
1" Conduit
110-001
110-002
110-003
110-004
110-005
110-006
110-007
110-008
DUPLEX
JACKS
Leave slack for Cat-6
at Wire Rack/Cable Tray
SCALE:
COMMUNICATIONS WIRE
INSTALLATION & MARKING DETAILS
6
NO SCALE
SCALE:
8
COMMUNICATION LABELING DETAIL
NO SCALE
7/16/2020
Electrical
Details and
Symbol
Legend
AUTHOR
CHECKED:
DAVIS DESIGN ALL RIGHTS RESERVED
SHEET TITLE
SHEET NUMBER
ID
ISSUE DATE:
DescriptionDate
Revisions:
15 E
ast M
ain, S
uite 201
Verm
illion S
D 57069
Phone 605-624-1081
Verm
illion
1221 N
S
treet, S
uite 600
Lincoln N
E 68508
Phone 402-476-9700
Fax 402-476-9722
Lin
co
ln
E-502
07-16-2020
TIG
JPD
1. Floor or Wall Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Wall may also be constructed of any UL
Classified Concrete Blocks*. Diam of opening to be 4 in. (102 mm).
See Concrete Blocks category (CAZT) in the Fire Resistance Directory for names of manufacturers.
2. Steel Sleeve - (Optional) - Nom 4 in. (102 mm) diam Schedule 10 to Schedule 40 steel pipe or rigid steel conduit cast or grouted into concrete floor or wall flush with floor or wall
surfaces.
3. Firestop Device* - One firestop device module centered within the opening. The firestop device module consists of a 3 by 3 by 10-1/2 in. (76 by 76 by 267 mm) long galv steel tube
with an intumescent material lining. Firestop device module to be installed in accordance with the accompanying installation instructions. The space between the firestop device
module and the periphery of the opening shall be min 0 in. ( 0 mm, point contact) to max 1/2 in. (13 mm). Firestop device module secured in place by means of steel restraint plates
sized to accommodate the firestop device module. Steel restraint plates each provided with a closed cell silicone gasket and sized to lap approx 1/2 in. (13 mm) on floor or wall
surfaces. Steel restraint plate installed on both sides of floor or wall and secured to firestop device module with steel set screws. The firestop device module is to be installed with its
ends projecting an equal distance beyond each surface of the floor or wall assembly. As an option, firestop device may be cast or grouted into wall assembly. When device is cast or
grouted in place, the steel restraint plates are optional.
SPECIFIED TECHNOLOGIES INC - EZ PATH Series 33 Fire Rated Pathway
3A. Firestop Device* - Extension Module - (Optional, Not Shown) - Module attached to ends of 3 by 3 by 10-1/2 in. (76 by 76 by 267 mm) long firestop device (Item 3) to increase its
length to facilitate installation in thicker floors or walls. Each module consists of a 3 by 3 by 6 in. (76 by 76 by 152 mm) long galv steel tube with an intumescent material lining.
Extension module to be installed in accordance with the accompanying installation instructions. When module is used, firestop device (Item 3) and extension module(s) secured in
place by means of steel plates installed with gasketing material supplied with product. Steel plates installed on both sides of floor or wall and secured to each device or extension
module(s) by means of steel set screws provided with plates. Firestop device and extension module(s) assembly to be installed with ends projecting an equal distance beyond each
surface of the floor or wall assembly.
SPECIFIED TECHNOLOGIES INC - EZ PATH Extension
4. Fill, Void or Cavity Material* - Sealant or Putty - Prior to installation of steel restraint plates, min 1 in. (25 mm) thickness of sealant or putty installed in annular space flush with top
surface of floor or both surfaces of wall.
SPECIFIED TECHNOLOGIES INC - SpecSeal 100, 101, 102, 105, 120 or 129 Sealant, SpecSeal Putty
5. Cables - Within the loading area for each firestop device module, the cables may represent a 0 to 100 percent visual fill. Cable fill to be distributed at a uniform height across the
width of the firestop device module. Cables to be rigidly supported on both sides of the floor or wall assembly. Any combination of the following types of cables may be used:
A. Max 400 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with polyvinyl chloride (PVC) jacketing and insulation.
B. Max 350 kcmil single copper conductor power cable with XLPE jacket and insulation
C. Max 7/C No. 12 AWG copper conductor control cable with PVC or XLPE jacket and insulation.
D. Max 3/C No. 10 AWG metal clad or armored cable with steel or aluminum jacket.
E. Max 3/C No. 8 AWG NM cable (Romex) with PVC insulation and jacket.
F. Max 4 pair No. 22 AWG (or smaller) copper conductor data cable with PVC or plenum rated jacketing and insulation.
G. Max RG/U coaxial cable with fluorinated ethylene insulation and jacketing.
H. Optical fiber cable with PVC or polyethylene (PE) jacket and insulation and having a max diam of 5/8 in. (16 mm).
I. Optical Fiber Raceway+ - Max 1-1/2 in. (38 mm) diam (or smaller) optical fiber raceway ("innerduct") formed of either PVC or polyvinylidene fluoride (PVDF) with optical fiber
cable fill. Raceways installed in accordance with the National Electrical Code (NFPA 70).
When Item 5A, 5B, 5C, 5D or 5E is used, the F Rating is 2 hr and the T Rating is 3/4 hr. When max 200 pair No. 24 AWG telecommunication cable is used or when Item
5F, 5G, 5H or 5I is used, the F Rating is 4 hr and the T Rating is 1 hr.
The L Rating for each empty firestop device module is less than 1 cfm at ambient and at 400F. When Item 5A is used, the L Rating for each firestop device module with
100 percent visual fill is 4 cfm at ambient and 3 cfm at 400F. When Item 5F is used, the L Rating for each firestop device module with 100 percent visual fill is 1.3 cfm at
ambient and less than 1 cfm at 400F.When Item 5G or 5H is used, the L Rating for each firestop device module with 100 percent visual fill is 7 cfm at ambient and 2 cfm
at 400F.
+Bearing the UL Listing Mark
*Bearing the UL Classification Mark
Section A-A
A
A
SCALE:
10
PUNCH DOWN BLOCK DETAIL
NO SCALE
EXISTING PLYWOOD MOUNTING PANEL
110 PUNCH BLOCK DATA
RACK TERMINATIONS
110 PUNCH BLOCK JACK
TERMINATIONS
NOTES:
1. ALL 110 PUNCH DOWN BLOCKS SHOWN IN HALF TONE ARE EXISTING
2. ELECTRICAL CONTRACTOR SHALL ADJUST AND RE-SECURE EXISTING YELLOW LOW VOLTAGE CABLES TERMINATED ON 110 PUNCH DOWN BLOCK
SO NEW 110 PUNCH DOWN BLOCK CAN BE INSTALLED. CABLES SHALL BE SECURED TO PLYWOOD AS NEEDED FOR NEW PUNCH DOWN BLOCK
INSTALLATION. SEE PHOTO FOR CABLES.
3. INSTALL NEW 100 PAIR 110 PUNCH DOWN BLOCK
4. ROUTE AND TERMINATE CAT 6 CABLING FROM DATA JACK TO PUNCH DOWN BLOCK.
5. PROVIDE JUMPER CABLE FROM BOTTOM ROW PUNCH DOWN BLOCK TO TOP ROW PUNCH DOWN BLOCK
6. ROUTE AND TERMINATE CAT 6 CABLING FROM PUNCH DOWN BLOCK TO DATA RACK ADJACENT TO PUNCH DOWN BLOCKS.
7. SEE PHOTO FOR EXISTING PUNCH DOWN BLOCKS.
8. EXISTING PHONE JACK SHALL REMAIN.
2
3
3
4
5
5
6
EXISTING WIRE
MANGEMENT
A
CEILING OUTLET, A = FIXTURE TYPE, a =
SWITCH
LIGHT FIXTURE
STRIP LIGHT FIXTURE
COVE/UNDER CABINET LIGHT FIXTURE
WALL BRACKET FIXTURE
NIGHT LIGHT
WALLWASH FIXTURE
TRACK LIGHT FIXTURE
POLE LUMINAIRE(S)
BOLLARD LUMINAIRE
EMERGENCY LIGHT FIXTURE WALL MOUNT
INDICATES FIXTURE WITH EMERGENCY
BATTERY OR EMERGENCY CIRCUIT
EXIT SIGN, (DIRECTIONAL ARROWS AS
INDICATED; SHADED SIDE INDICATES FACE)
EXIT SIGN WALL MOUNTED, (DIRECTIONAL
ARROWS AS INDICATED; SHADED SIDE
INDICATES FACE)
EXIT SIGN WALL MOUNTED, WITH EMERGENCY
HEADS, (SHADED SIDE INDICATES FACE)
SYMBOL DESCRIPTION
A
A
A
BASKET LIGHT FIXTURE
A
A
A
A
A
A
A A
A
A
NL
A
A
A
CEILING FAN FIXTURE
A
WALL BRACKET LIGHT FIXTURE
DESCRIPTIONSYMBOL
SPST SWITCH
DOUBLE POLE, DOUBLE THROW SWITCH
THREE-WAY SWITCH
FOUR-WAY SWITCH
SWITCH WITH PILOT LIGHT
DIMMER SWITCH
SWITCH FOR DARK ROOM SAFE LIGHT AND WHITE
LIGHT
KEY SWITCH
TIMER SWITCH
MOMENTARY CONTACT SWITCH
PHOTO CELL
TIME CLOCK
TIME SWITCH
PUSHBUTTON
PUSHBUTTON START/STOP
LIGHTING CONTACTOR
4
P
D
RW
K
MC
TS
MS
C
P
TC
PB
C
3
2
T
REMOTE CONTROL SWITCH
MOTION SENSOR SWITCH
SWITCHING
COMMUNICATIONS
SYMBOL DESCRIPTION
LIGHTING
DATA OUTLET WALL
COMBINATION TELEPHONE/DATA OUTLET
INTERCOM OUTLET
TELEPHONE OUTLET
BUZZER
CHIME
CENTRAL DICTATION
KEY PAD
PROGRAM BELL
MONITOR
TERMINAL BOARD, SEE PLANS
FOR IDENTIFICATION
TELEPHONE PANELBOARD
MICROPHONE WALL
PA CALL
MICROPHONE FLOOR
SPEAKER OUTLET, CEILIING
SPEAKER OUTLET, WALL
VOLUME CONTROL, SOUND
TELEVISION OUTLET, CEILING
CLOCK CEILING MOUNT
CLOCK OUTLET
SECURITY CAMERA
I
B
CH
CD
M
M
PA
M
S
S
V
TV
C
C
HD
SB
PA
S SPEAKER OUTLET, FLOOR
PA SPEAKER
SCHOOL BELL
DESCRIPTIONSYMBOL
POWER DEVICES
AS INDICATED)
UFACTURERS RE-
COMENDATIONS
TVSS
FM - FUSE PER MAN-
NEMA 1 ENCLOSURE TYPE
NO. OF SWITCHED POLES
AMPACITY
NF - NON FUSED
AF - AMP FUSE (SIZE
SCHEMATIC DIAGRAM NO.
NF - NON FUSED
FM - FUSE PER MAN-
NEMA 1 ENCLOSURE TYPE
AMPACITY
NO. OF SWITCHED POLES
AF - AMP FUSE (SIZE
DUPLEX RECEPTACLE
HORIZONTALLY MOUNTED DUPLEX RECEPTACLE
TAMPER-PROOF DUPLEX RECEPTACLE
SINGLE RECEPTACLE
GFIC RECEPTACLE
SPLIT DUPLEX RECEPTACLE
TVSS DUPLEX RECEPTACLE (BLUE)
RANGE RECEPTACLE
WP RECEPTACLE
EXPLOSION PROOF RECEPTACLE
X-RAY RECEPTACLE
CEILING RECEPTACLE
SPECIAL RECEPTACLE, SEE PLANS
FOUR PLEX RECEPTACLE
SINGLE GANG FLOOR BOX, POWER
PLUGMOLD/WIREMOLD, WITH NO. OF OUTLETS AS
INDICATED
J-BOX FLOOR BOX, POWER
JUNCTION BOX
JUNCTION BOX WALL
MOTOR WITH HORSE POWER AS NOTED
CIRCUIT BREAKER OR FUSIBLE DISCONNECT
DISCONNECT SWITCH, SURFACE MOUNTED, 600V,
30A,3 POLE U.O.N.
MOTOR STARTER
COMBINATION MAGNETIC MOTOR STARTER AND
DISCONNECT SWITCH SURFACE MOUNTED
LIGHTING PANEL AND OR POWER PANEL
MCC OR DISTRIBUTION PANEL
TRANSFORMER
AUTOMATIC TRANSFER SWITCH
VARIABLE SPEED DRIVE
METER SOCKET
AS INDICATED)
UFACTURERS RE-
COMENDATIONS
EXP
SINGLE GANG FLOOR BOX, 4-PLEX POWER
GFI
WIU
WP
T
J
J
J
TR
ATS
VFD
M
WHILE IN USE RECEPTACLE COVER
HAND DRYER
M
FT
OL
TE
MC
WIRELESS INTERNET ANTENNA
MOTOR RATED SWITCH
FUSED SWITCH
OVERLOAD PROTECTED SWITCH
THERMAL SWITCH
MOTOR CONTROL SWITCH
NURSE CALL
SYMBOL DESCRIPTION
DOCTOR'S REGISTER MASTER PANEL
NURSE CALL MASTER STATION
NURSE CALL BEEPER
NURSE CALL CENTRAL EQUIPMENT
NURSE CALL CORRIDOR DOME LIGHT WALL
NURSE CALL CORRIDOR DOME LIGHT CEILING
NURSE CALL BEDSIDE STATION
NURSE CALL EMERGENCY STATION
NURSE CALL CODE BLUE STATION
NURSE CALL CODE BLUE ANNUNCIATOR
NURSE CALL STAFF/DUTY STATION
NURSE CALL STAFF PRESENT STATION
NURSE CALL STAFF STATION
NURSE CALL DUTY STATION
OXYGEN ALARM PANEL
GI ALARM
FILM ILLUMINATOR
NURSE CALL LOCATOR DEVICE
NCM
DRM
NB
D
E
CB
SD
OXA
GIA
N
N
B
SP
S
FI
BBA
BLOOD BANK ALARM
NCP
NURSE CALL MASTER PANEL
CBA
NCC
NC
DESCRIPTIONSYMBOL
FIRE ALARM
FA MANUAL PULL STATION
FA SPEAKER, CEILING
FA STROBE, WALL
FA BELL
FA HORN AND STROBE, CEILING
FA SPEAKER, WALL
FA HORN, WALL
FA SPEAKER AND STROBE, WALL
HEAT DETECTOR
SMOKE DETECTOR INSTALL IN DUCT
SMOKE DETECTOR
ELECTRO-MAGNETIC DOOR HOLDER/RELEASE
POST INDICATOR VALVE
GATE VALVE SWITCH
WATERFLOW ALARM SWITCH
FAN SHUT-OFF RELAY
FIRE ALARM MASTER PANEL
FIRE ALARM ANNUNCIATOR PANEL
FIRE ALARM PHONE JACK
AUTOMATIC FIRE SMOKE DAMPER
AUTOMATIC SMOKE DAMPER
F
D
F
F
F
PIV
GV
WFA
R
FA
FAA
SD/FD
F
SD
FA STROBE, CEILINGF
RACEWAYS
SYMBOL DESCRIPTION
STUB CONDUIT UP AND CONNECT AS REQUIRED
STUB CONDUIT DOWN AND CONNECT AS
REQUIRED
SURFACE RACEWAY
WIRING IN CONDUIT, CONCEALED
WIRING IN CONDUIT, EXPOSED
WIRING IN CONDUIT, CONCEALED IN FLOOR
HOME RUN TO PANEL, 2 WIRES UNLESS
OTHERWISE INDICATED
EXISTING CONDUIT AND WIRING TO REMAIN
EXISTING CONDUIT AND WIRING TO BE REMOVED
FIRE ALARM SYSTEM
SOUND SYSTEM CONDUIT
NURSE CALL SYSTEM
MONITOR SYSTEM CONDUIT
CABLE TV SYSTEM
CENTRAL DICTATION SYSTEM CONDUIT
INTERCOM SYSTEM CONDUIT
EMERGENCY CIRCUIT
X
X
EM
CATV
I
CD
FA
S
N
M
X
MISCELLANEOUS
SYMBOL DESCRIPTION
R
E
E2
R2
E1
R1
GFI
WP
EXP
NL
DENOTES GROUND FAULT
EXPLOSION PROOF
DENOTES WEATHERPROOF
INDICATES NIGHT LIGHT FIXTURE
INDICATES ITEM TO BE REMOVED
INDICATES ITEM TO REMAIN
THERMOSTAT
HEATER, ELECTRIC
INDICATES BREAK
H
T
TYPICAL MOUNTING HEIGHTS
HEIGHTS ARE TO CENTER LINE
UNLESS NOTED OTHERWISE
RECEPTACLES
SWITCHES
THERMOSTATS
FIRE ALARM HORN STROBE
FIRE ALARM CHIME
FIRE ALARM STROBE LIGHT
PANEL BOARDS TO TOP
CABINETS TO TOP
DISCONNECTS
PHONE OR DATA OUTLETS
PHONE DATA OUTLETS
18"
48"
48"
84"
84"
84"
72"
72"
60"
18"
18"
ELECTRICAL SYMBOLS
NOTE;
THIS SYMBOL LEGEND IS FOR REFERENCE ONLY.
NOT ALL SYMBOLS ARE USED ON THIS PROJECT.
TVSS 4-PLEX RECEPTACLE (BLUE)
A
EMERGENCY LIGHT FIXTURE CEILING MOUNT
FS
FLOW SWITCH
INDICATES ITEM WHICH HAS BEEN RE-ADJUSTED.
INDICATES ITEM TO BE RE-ADJUSTED.
DISCONNECTION SHOULD NOT BE REQUIRED.
INDICATES ITEM WHICH HAS BEEN RELOCATED.
RECONNECT TO CIRCUITING AS SHOWN.
INDICATES ITEM TO BE RELOCATED. SEE NEW
PLANS FOR NEW LOCATION. DISCONNECTION OF
CIRCUIT WIRING WILL BE REQUIRED.
RC
TS
TAMPER SWITCH
LOW VOLTAGE (DIGITAL) SWITCH
LV
CARD READER
ELECTRIC STRIKEES
CR
CRITICAL EMERGENCY CIRCUIT
EQ
EQUIPMENT EMERGENCY CIRCUIT
LS
LIFE SAFETY EMERGENCY CIRCUIT
FULLY CONTROLLED RECEPTACLE
FC
HC
HALF CONTROLLED RECEPTACLE
ACCESS CONTROL
SYMBOL DESCRIPTION
POWER SUPPLYPS
DOOR CONTROL DEVICE
ADA OPERATOR
DCD
ADA
RADIO FREQUENCY RECEIVERRFR
GENERATOR ENUNCIATOR PANELANN
DOOR POSITION SWITCH
DP
ELECTRIC LOCKSET
EL
REQUEST TO EXIT DEVICE
ED
CR
KP
3P/30A/NEMA 1/NF
3P/SIZE 0/NEMA 1/NF/SD02
COMBINATION TELEPHONE/DATA OUTLET CEILING
COMPUTER OUTLET CEILING
TELEPHONE OUTLET CEILING
TELEPHONE FLOOR BOX
COMPUTER OUTLET FLOOR
COMBINATION TELEPHONE/DATA OUTLET FLOOR
PB
START/STOP
FA HORN, CEILING
FA HORN AND STROBE, WALLS
S
S
FA SPEAKER AND STROBE, CEILINGS
FAC
FA CHIME
TVTELEVISION OUTLET, WALL
F
F
F
F
F
F
F
CLIENT INFORMATION
PROJECT INFORMATION
South Dakota
Army National
Guard
801 W National Guard Dr.
Sioux Falls, S.D 57104
CFMO# SF466146
Convert IFR
to Classroom -
Foss Field
Armory
20-0067Job #
SCALE:
9
EZ PATH DETAIL
NO SCALE
8
7/16/2020