1 A-101 DRAWING SYMBOLS REFERENCE SYMBOLS A COLUMN LINE NUMBER ELEVATION REFERENCES GENERAL REFERENCE DETAIL SECTION REFERENCE DETAIL REFERENCE INDICATES SHEET UPON WHICH DETAIL APPEARS INDICATES DETAIL NUMBER 4 A-401 2 A-301 3 A-201 2 A-301 OR OR 1 G-000 FIRST FLOOR 100'-0" UNDISTURBED EARTH DISTURBED EARTH GRAVEL OR CRUSHED STONE SAND ASPHALT CAST IN PLACE CONCRETE CONCRETE MASONRY PRECAST CONCRETE FACE AND COMMON BRICK MARBLE AND GRANITE STRUCTURAL CLAY TILE GROUT RUBBLE STONE ASHLAR STONE CAST STONE CUT STONE ALUMINUM BRONZE AND BRASS STEEL CHECKER PLATE FIRE BRICK GLAZED, FACED, VENEERED OR FINISHED ONE SIDE DIMENSIONAL FRAMING OR BLOCKING FINISH GRADE LUMBER PLYWOOD EARTHEN MATERIALS CONCRETE BRICK & TILE STONE METALS WOOD INSULATION & ACOUSTICAL MATERIALS GYPSUM MATERIALS PARTICLE BOARD ORIENTED STAND BOARD BATT, FIRE SAFING OR SOUND ATTENUATING BLANKET RIGID BOARD GYPSUM WALLBOARD PLASTER ACOUSTIC TILE OR PANELS FIBER PANEL CERAMIC TILE QUARRY TILE NON-DIMENSIONAL BLOCKING WOOD FLOORING GLUE-LAMINATED OR LVL MATERIAL SYMBOLS ABBREVIATIONS ABBREVIATION TERM(S) 3PLY THREE-PLY A/E ARCHITECT/ENGINEER A/V AUDIO VISUAL ABS ACRYLONITRILE BUTADIENE STYRENE ACS ACCESS ACST ACOUSTIC ACT ACOUSTICAL CEILING TILE AD AREA DRAIN ADA AMERICANS WITH DISABILITIES ACT ADJ ADJUSTABLE ADMIN ADMINISTRATION AFF ABOVE FINISHED FLOOR AHJ AUTHORITY HAVING JURISDICTION ALT ALTERNATE ALUM ALUMINUM ANSI AMERICAN NATIONAL STANDARDS INSTITUTE AP ACRYLIC PANEL APC ACOUSTICAL PANEL CEILING ARCH ARCHITECT ASPH ASPHALT ASSY ASSEMBLY ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS AUTO AUTOMATIC AUX AUXILIARY AVG AVERAGE AWI ARCHITECTURAL WOODWORKING INSTITUTE B&B BALLED AND BURLAPPED BD BOARD BF BOTH FACES BG BUMPER GUARD BKG BACKING BLDG BUILDING BLKHD BULKHEAD BLKT BLANKET BM BENCH MARK OR BEAM BN BULLNOSE BO BOTTOM OF BOC BACK OF CURB BOS BOTTOM OF STEEL BOT BOTTOM BRCG BRACING BRDG BRIDGING BRG BEARING BRKT BRACKET BS BOTHSIDES BSMT BASEMENT BUR BUILT-UP ROOFING C&P CARPET AND PAD CAC CEILING ATTENUATION CLASS CB CARRIAGE BOLT OR CATCH BASIN CD CONSTRUCTION OR CONTRACT DOCUMENTS CER CERAMIC CF CONTRACTOR FURNISHED CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED CG CORNER GUARD ABBREVIATION TERM(S) CH CHANNEL CHK COAT HOOK CI CURB INLET CIP CAST-IN-PLACE CIR CIRCLE CJ CONSTRUCTION OR CONTROL JOINT CL CENTER LINE CLG CEILING CLO CLOSET CLR CLEAR CMP CORRUGATED METAL PIPE CMPST COMPOSITE CMT CERAMIC MOSAIC TILE CMU CONCRETE MASONRY UNIT CO CARBON MONOXIDE CO2 CARBON DIOXIDE COL COLUMN CONC CONCRETE CONF CONFERENCE CONT CONTINUE OR CONTINUOUS COORD COORDINATE CORR CORRIDOR CPRS COMPRESSIBLE CPT CARPET CS CAST STONE CSK COUNTER SUNK CT CERAMIC TILE CTF CERAMIC TILE FLOOR CTR CENTER CTRL CONTROL CTT CERAMIC TILE TRIM CU CUBIC CURT CURTAIN CUST CUSTODIAN D DEEP, DEPTH AND PENNY (NAIL) dBA UNIT OF SOUND LEVEL DBL DOUBLE DEPT DEPARTMENT DET DETAIL DG DECORATIVE GLASS DIA DIAMETER DIAG DIAGRAM DISP DISPENSER DL DEAD LOAD DR DOOR DRS DRESSING ROOM DS DOWNSPOUT DT DRAIN TILE DW DISHWASHER DWG DRAWING E MODULUS OF ELASTICITY EA EACH EF EACH FACE EGSB EXTERIOR GYPSUM SHEATHING BOARD EIFS EXTERIOR INSULATION AND FINISH SYSTEM ABBREVIATION TERM(S) EJ EXPANSION JOINT EL ELEVATION ELEC ELECTRIC OR ELECTRICAL ELEV ELEVATOR EMER EMERGENCY EPA ENVIRONMENTAL PROTECTION AGENCY EPDM ETHYLENE PROPYLENE DIENE MONOMER EPS EXPANDED POLYSTYRENE BOARD INSULATION EPX EPOXY RESIN EQ EQUAL EQL SP EQUALLY SPACED EQUIP EQUIPMENT ESMT EASEMENT ETC ET CETERA AND SO FORTH EW EACH WAY EWS EYE WASH STATION EXCG EXISTING CORNER GUARD EXIST EXISTING EXP EXPAND, EXPANDED OR EXPANSION F FAHRENHEIT F/F FACE TO FACE FAB FABRIC FD FLOOR DRAIN FDTN FOUNDATION FE FIRE EXTINGUISHER FEC FIRE EXTINGUISHER CABINET FF&E FURNITURE, FIXTURE AND EQUIPMENT FH FIRE HYDRANT FHC FIRE HOSE CABINET FIN FINISH FIXT FIXTURE FL FLOORLINE FLR FLOOR FLR FIN FLOOR FINISH FM FACTORY MUTUAL FR FIRE RATING OR RESISTANT FR GL FRITTED GLASS FRMG FRAMING FRP FIBERGLASS REINFORCED PLASTIC FRZ FREEZER FT FOOT OR FEET FTNG FOOTING FURG FURRING FURN FURNITURE FWC FABRIC WALLCOVERING GA GAGE GALV GALVANIC OR GALVANIZED GC GENERAL CONTRACTOR GL GLASS GLZ GLAZING GMT GLASS MOSAIC TILE GR GROUT GR BM GRADE BEAM GSB GYPSUM SHEATHING BOARD GWB GYPSUM BOARD ABBREVIATION TERM(S) GYM GYMNASIUM GYP GYPSUM GYP BD GYPSUM BOARD H HIGH HB HOSE BIB HC HANDICAP HCP HANDICAPPED HDO HIGH DENSITY OVERLAY HDPE HIGH DENSITY POLYETHYLENE HDW HARDWARE HDWD HARDWOOD HGR HANGER HM HOLLOW METAL HMD HOLLOW METAL DOOR HMF HOLLOW METAL FRAME HORIZ HORIZONTAL HOSP HOSPITAL HSKPG HOUSEKEEPING HSS HOLLOW STRUCTURAL SECTION HT HEIGHT HW DOOR HARDWARE HYD HYDRANT Hz HERTZ IAQ INDOOR AIR QUALITY IB INTEGRAL BASE IBC INTERNATIONAL BUILDING CODE ID INSIDE DIAMETER INT DES INTERIOR DESIGN IF INSIDE FACE IMH INLET MANHOLE IMP INSULATED METAL PANEL IN INCH OR INCHES INSUL INSULATION INT INTERIOR INV INVERT INV EL INVERT ELEVATION ISO ISOMETRIC ITS INTERTEK TESTING SERVICES IW IRRIGATION WATER JAN JANITOR JT JOINT KIP THOUSAND POUNDS KIP FT THOUSAND FOOT POUNDS KIT KITCHEN KOP KNOCK OUT PANEL L ANGLE, LENGTH OR LONG LAB LABORATORY LAG LAGGING LAM LAMINATE LAU LAUNDRY LBS POUNDS LD BRG LOAD-BEARING LDPE LOW DENSITY POLYETHYLENE LF LINEAR FOOT (FEET) LIB LIBRARY ABBREVIATION TERM(S) LIN LINEAR LINO LINOLEUM LKR LOCKER LL LIVE LOAD LLH LONG LEG HORIZONTAL LLV LONG LEG VERTICAL LPT LOW POINT LT LIGHT LVL LEVEL LVT LUXURY VINYL TILE LWM LOW WATER MARK M MOMENT MAINT MAINTENANCE MATL MATERIAL MAX MAXIMUM MB MARKER BOARD MC MANHOLE COVER MDO MEDIUM DENSITY OVERLAY MECH MECHANICAL MED MEDICAL OR MEDICINE MEZZ MEZZANINE MFD MANUFACTURED MFG MANUFACTURING MFR MANUFACTURER MFR REC MANUFACTURER'S RECOMMENDATION MH MANHOLE MIN MINIMUM MISC MISCELLANEOUS mm MILLIMETER MOD BIT MODIFIED BITUMEN MT METAL TRIM MTD MOUNTED MTG MOUNTING MTL METAL MULL MULLION MW MICROWAVE MWP MEMBRANE WATERPROOFING N NEWTON OR NORTH NF NEAR FACE NFPA NATIONAL FIRE PROTECTION ASSOCIATION NIC NOT IN CONTRACT NO NUMBER NOM NOMINAL NRCA NATIONAL ROOFING CONTRACTORS ASSOCIATION NS NEAR SIDE NTS NOT TO SCALE O OXYGEN OA OVERALL OC ON CENTER OCC OCCUPY, OCCUPANTS OR OCCUPANCY OD OUTSIDE DIAMETER OF OUTSIDE FACE OF/CI OWNER FURNISHED/CONTRACTOR INSTALLED OF/OI OWNER FURNISHED/OWNER INSTALLED OFF OFFICE ABBREVIATION TERM(S) OH DR OVERHEAD COILING DOOR OPNG OPENING OPP OPPOSITE OR OPERATING ROOM ORD OVERFLOW ROOF DRAIN OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINSTRATION OVFL OVERFLOW OZ OUNCE P PAINT Pa PASCAL PART PARTIAL PASS PASSAGE PBD PARTICLEBOARD PC POINT OF CURVE OR POLYCARBONATE PRVC PRIVACY CURTAIN PCA PORTLAND CEMENT ASSOCIATION PCB POLYCHLORINATED BIPHENYL PCC PRECAST CONCRETE PCT PORCELAIN TILE PED PEDESTAL PERF PERFORATED PHAR PHARMACY PI POINT OF INTERSECTION PIB POLYISOBUTYLENE (PLASTIC) PIV POST INDICATOR VALVE PKG PACKAGE PLAM HIGH PRESSURE PLASTIC LAMINATE PLF POUNDS PER LINEAR FOOT PLYWD PLYWOOD PMF PROBABLE MAXIMUM FLOOD PO PURCHASE ORDER POLY POLYETHYLENE PLASTIC PP POLYPROPYLENE PLASTIC PR PAIR PREFAB PREFABRICATE PRELIM PRELIMINARY PREP PREPARATION PS POLYSTYRENE PLASTIC PSF POUNDS PER SQUARE FOOT PSI POUNDS PER SQUARE INCH PT PAINT OR PAINTED PTT PORCELAIN TILE TRIM PTUBE PNEUMATIC TUBE PVA POLYVINYL ACETATE PVC POLYVINYL CHLORIDE (PLASTIC) PVF POLYVINYL FLUORIDE (PLASTIC) QS QUARTZ SURFACE QT QUARRY TILE QTR QUARTER QTT QUARRY TILE TRIM QTY QUANTITY R RADIUS, RANGE, RISER OR THERMAL RESISTANCE RAB RABBETED RB RESILIENT OR RUBBER BASE ABBREVIATION TERM(S) RBF RUBBER FLOORING RCP REFLECTED CEILING PLAN RDG INS SOLID RIGID INSULATION REC RECESSED OR RECREATION RECIP RECIPROCAL REF REFRIGERATOR REINF REINFORCE REQ REQUIRE REQD REQUIRED REQT REQUIREMENT RESIL RESILIENT REST RESTROOM RF RESILIENT FLOORING RFS ROOM FINISH SCHEDULE RM ROOM RND ROUND RO ROUGH OPENING ROW RIGHT OF WAY RT RESILIENT TILE RV ROOF VENT SAN SANITARY SBS STYRENE BUTADIEN STYRENE SCP SCUPPER SD SMOKE DETECTOR OR STORM DRAIN SDT STATIC DISSIPATIVE TILE SECT SECTION SEP SEPARATE SF SAFETY FACTOR OR SQUARE FOOT (FEET) SHT SHEET SHTHG SHEATHING SIM SIMILAR SP SCIENTIFIC PANEL (TRESPA) OR STANDPIPE SPEC SPECIFICATION SPF SPRUCE-PINE-FIR SQ SQUARE SS SANITARY SEWER OR SOLID SURFACE SSCG STAINLESS STEEL CORNER GUARD SST STAINLESS STEEL ST STAIRS STN STONE (NATURAL) TILE STW STORM WATER STC SOUND TRANSMISSION COEFFICIENT STD STANDARD STIR STIRRUP STL STEEL STOR STORAGE STRUCT STRUCTURAL SUB FL SUBFLOOR SUSP SUSPEND OR SUSPENDED SVF SHEET VINYL FLOORING SYS SYSTEM T TREAD T&B TOP AND BOTTOM T&G TONGUE AND GROOVE TB TACKBOARD ABBREVIATION TERM(S) TCNA TILE COUNCIL OF NORTH AMERICA TEMP TEMPORARY TG TEMPERED GLASS THK THICKNESS THRU THROUGH THRUOUT THROUGHOUT TN TRUE NORTH TOC TOP OF CURB TOPO TOPOGRAPHY TOS TOP OF STEEL TOW TOP OF WALL TP TELEPHONE POLE OR TRANSLUCENT PLASTIC TS TENSILE STRENGTH TW TACK WALL TYP TYPICAL UBC UNIFORM BUILDING CODE UGND UNDERGROUND UL UNDERWRITERS LABORATORIES UNO UNLESS NOTED OTHERWISE UON UNLESS OTHERWISE NOTED UTIL UTILITY VAC VACUUM VB VINYL BASE VCT VINYL COMPOSITION TILE VENT VENTILATION OR VENTILATOR VERT VERTICAL VEST VESTIBULE VIF VERIFY IN FIELD VOC VOLATILE ORGANIC COMPOUND VS VENT STACK VTR VENT THROUGH ROOF VWC VINYL WALL COVERING W WIDE W/ WITH W/O WITHOUT W/W WALL-TO-WALL WB WOOD BASE WC WALL COVERING WD WOOD WH WATER HEATER WI WROUGHT IRON WP WALL PROTECTION WST WOOD STAIN WT WEIGHT OR WINDOW TREATMENT WWF WELDED WIRE FABRIC X BRACE CROSS BRACE XBRA CROSSBRACING XFER TRANSFER XL EXTRA LARGE XPS EXTRUDED POLYSTYRENE BOARD INSULATION XXH DOUBLE EXTRA HEAVY YD YARD YH YARD HYDRANT YI YARD INLET Z MODULUS OF SECTION 15 East Main, Suite 201 Vermillion SD 57069 Phone 605-624-1081 Vermillion 1221 N Street, Suite 600 Lincoln NE 68508 Phone 402-476-9700 Fax 402-476-9722 Lincoln CONVERT IFR TO CLASSROOM - FOSS FIELD ARMORY SIOUX FALLS, SOUTH DAKOTA G-001 COVER SHEET AND INDEX (THIS PAGE) A-101 DEMOLITION FLOOR AND REFECTED CEILING PLANS M-001 PLUMBING AND HVAC COVER SHEET INDEX OF DRAWING GENERAL ARCHITECTURAL MECHANICAL VICINITY MAP 95% REVIEW DOCUMENTS FOR: NATIONAL GUARD DR. FOSS FIELD ARMORY ADDRESS: 801 W NATIONAL GUARD DR. TO N MINNESOTA AVE. CFMO# SF466146 I-90 I-29 N. Minnesota Ave Sioux Falls Regional Airport See enlarged map above A-102 FURNITURE, FLOOR, AND REFLECTED CEILING PLANS A-201 INTERIOR ELEVATIONS, DETAILS AND WALL SECTIONS E-101 ELECTRICAL PLAN - DEMOLITION AND NEW ELECTRICAL E-501 ELECTRICAL DETAILS M-101 PLUMBING AND HVAC PLAN A-601 DOOR, FINISH AND WALL TYPE SCHEDULES AND DETAILS CODE INFORMATION CODE REVIEW 2018 INTERNATIONAL BUILDING CODE OCCUPANCY GROUP: B, BUSINESS FIRE SPRINKLER: NONE FIRE ALARM: NEW FIXTURES FIRE ALARM DETECTION: SMOKE ALARM COMMON PATH OF TRAVEL: 75'-0" MAX. FIRE PROTECTION FEATURES: FIRE RATED SEPARATION: 1 HR. EXISTING CORRIDOR ALLOWABLE BUILDING AREA: NO AREA ADDED TO BUILDING, INTERIOR REMODEL OCCUPANT LOAD FACTOR: 100 OFFICE AREAS 20 NET AREA, CLASSROOM NO. OF EXITS: 2 E-502 ELECTRICAL DETAILS AND SYMBOL LEGEND Cover Sheet and Index AUTHOR CHECKED: DAVIS DESIGN ALL RIGHTS RESERVED SHEET TITLE SHEET NUMBER ID ISSUE DATE: Description Date Revisions: 15 East Main, Suite 201 Vermillion SD 57069 Phone 605-624-1081 Vermillion 1221 N Street, Suite 600 Lincoln NE 68508 Phone 402-476-9700 Fax 402-476-9722 Lincoln G-001 07-16-2020 D.W. D.H. G-001 CLIENT INFORMATION PROJECT INFORMATION South Dakota Army National Guard 801 W National Guard Dr. Sioux Falls, S.D 57104 CFMO# SF466146 Convert IFR to Classroom - Foss Field Armory 20-0067 Job #

FOSS FIELD ARMORY · kop knock out panel l angle, length or long lab laboratory lag lagging lam laminate lau laundry ... all duct dimensions called out are interior free area dimensions

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: FOSS FIELD ARMORY · kop knock out panel l angle, length or long lab laboratory lag lagging lam laminate lau laundry ... all duct dimensions called out are interior free area dimensions

1

A-101

DRAWING SYMBOLS

REFERENCE SYMBOLS

A

COLUMN LINE NUMBER

ELEVATION REFERENCES

GENERAL REFERENCE DETAIL

SECTION REFERENCE

DETAIL REFERENCE

INDICATES SHEET UPON

WHICH DETAIL APPEARS

INDICATES DETAIL NUMBER

4

A-401

2

A-301

3

A-201

2

A-301

OR

OR

1

G-000

FIRST FLOOR

100'-0"

UNDISTURBED EARTH DISTURBED EARTH GRAVEL OR CRUSHED

STONE

SAND

ASPHALTCAST IN PLACE CONCRETE CONCRETE MASONRY PRECAST CONCRETE

FACE AND COMMON BRICK

MARBLE AND GRANITE

STRUCTURAL CLAY

TILE

GROUT

RUBBLE STONEASHLAR STONE CAST STONE CUT STONE

ALUMINUM BRONZE AND BRASS

STEEL

CHECKER PLATE

FIRE BRICK

GLAZED, FACED, VENEERED

OR FINISHED ONE SIDE

DIMENSIONAL FRAMING OR

BLOCKING

FINISH GRADE LUMBER

PLYWOOD

EARTHEN

MATERIALS

CONCRETE

BRICK & TILE

STONE

METALS

WOOD

INSULATION &

ACOUSTICAL

MATERIALS

GYPSUM

MATERIALS

PARTICLE BOARDORIENTED STAND BOARD

BATT, FIRE SAFING OR

SOUND ATTENUATING

BLANKET

RIGID BOARD

GYPSUM WALLBOARD PLASTER

ACOUSTIC TILE OR PANELS FIBER PANEL

CERAMIC TILE QUARRY TILE

NON-DIMENSIONAL

BLOCKING

WOOD FLOORING

GLUE-LAMINATED OR LVL

MATERIAL SYMBOLS

ABBREVIATIONS

ABBREVIATION TERM(S)

3PLY THREE-PLY

A/E ARCHITECT/ENGINEER

A/V AUDIO VISUAL

ABS ACRYLONITRILE BUTADIENE STYRENE

ACS ACCESS

ACST ACOUSTIC

ACT ACOUSTICAL CEILING TILE

AD AREA DRAIN

ADA AMERICANS WITH DISABILITIES ACT

ADJ ADJUSTABLE

ADMIN ADMINISTRATION

AFF ABOVE FINISHED FLOOR

AHJ AUTHORITY HAVING JURISDICTION

ALT ALTERNATE

ALUM ALUMINUM

ANSI AMERICAN NATIONAL STANDARDS INSTITUTE

AP ACRYLIC PANEL

APC ACOUSTICAL PANEL CEILING

ARCH ARCHITECT

ASPH ASPHALT

ASSY ASSEMBLY

ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS

AUTO AUTOMATIC

AUX AUXILIARY

AVG AVERAGE

AWI ARCHITECTURAL WOODWORKING INSTITUTE

B&B BALLED AND BURLAPPED

BD BOARD

BF BOTH FACES

BG BUMPER GUARD

BKG BACKING

BLDG BUILDING

BLKHD BULKHEAD

BLKT BLANKET

BM BENCH MARK OR BEAM

BN BULLNOSE

BO BOTTOM OF

BOC BACK OF CURB

BOS BOTTOM OF STEEL

BOT BOTTOM

BRCG BRACING

BRDG BRIDGING

BRG BEARING

BRKT BRACKET

BS BOTHSIDES

BSMT BASEMENT

BUR BUILT-UP ROOFING

C&P CARPET AND PAD

CAC CEILING ATTENUATION CLASS

CB CARRIAGE BOLT OR CATCH BASIN

CD CONSTRUCTION OR CONTRACT DOCUMENTS

CER CERAMIC

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED

CG CORNER GUARD

ABBREVIATION TERM(S)

CH CHANNEL

CHK COAT HOOK

CI CURB INLET

CIP CAST-IN-PLACE

CIR CIRCLE

CJ CONSTRUCTION OR CONTROL JOINT

CL CENTER LINE

CLG CEILING

CLO CLOSET

CLR CLEAR

CMP CORRUGATED METAL PIPE

CMPST COMPOSITE

CMT CERAMIC MOSAIC TILE

CMU CONCRETE MASONRY UNIT

CO CARBON MONOXIDE

CO2 CARBON DIOXIDE

COL COLUMN

CONC CONCRETE

CONF CONFERENCE

CONT CONTINUE OR CONTINUOUS

COORD COORDINATE

CORR CORRIDOR

CPRS COMPRESSIBLE

CPT CARPET

CS CAST STONE

CSK COUNTER SUNK

CT CERAMIC TILE

CTF CERAMIC TILE FLOOR

CTR CENTER

CTRL CONTROL

CTT CERAMIC TILE TRIM

CU CUBIC

CURT CURTAIN

CUST CUSTODIAN

D DEEP, DEPTH AND PENNY (NAIL)

dBA UNIT OF SOUND LEVEL

DBL DOUBLE

DEPT DEPARTMENT

DET DETAIL

DG DECORATIVE GLASS

DIA DIAMETER

DIAG DIAGRAM

DISP DISPENSER

DL DEAD LOAD

DR DOOR

DRS DRESSING ROOM

DS DOWNSPOUT

DT DRAIN TILE

DW DISHWASHER

DWG DRAWING

E MODULUS OF ELASTICITY

EA EACH

EF EACH FACE

EGSB EXTERIOR GYPSUM SHEATHING BOARD

EIFS EXTERIOR INSULATION AND FINISH SYSTEM

ABBREVIATION TERM(S)

EJ EXPANSION JOINT

EL ELEVATION

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMER EMERGENCY

EPA ENVIRONMENTAL PROTECTION AGENCY

EPDM ETHYLENE PROPYLENE DIENE MONOMER

EPS EXPANDED POLYSTYRENE BOARD INSULATION

EPX EPOXY RESIN

EQ EQUAL

EQL SP EQUALLY SPACED

EQUIP EQUIPMENT

ESMT EASEMENT

ETC ET CETERA AND SO FORTH

EW EACH WAY

EWS EYE WASH STATION

EXCG EXISTING CORNER GUARD

EXIST EXISTING

EXP EXPAND, EXPANDED OR EXPANSION

F FAHRENHEIT

F/F FACE TO FACE

FAB FABRIC

FD FLOOR DRAIN

FDTN FOUNDATION

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FF&E FURNITURE, FIXTURE AND EQUIPMENT

FH FIRE HYDRANT

FHC FIRE HOSE CABINET

FIN FINISH

FIXT FIXTURE

FL FLOORLINE

FLR FLOOR

FLR FIN FLOOR FINISH

FM FACTORY MUTUAL

FR FIRE RATING OR RESISTANT

FR GL FRITTED GLASS

FRMG FRAMING

FRP FIBERGLASS REINFORCED PLASTIC

FRZ FREEZER

FT FOOT OR FEET

FTNG FOOTING

FURG FURRING

FURN FURNITURE

FWC FABRIC WALLCOVERING

GA GAGE

GALV GALVANIC OR GALVANIZED

GC GENERAL CONTRACTOR

GL GLASS

GLZ GLAZING

GMT GLASS MOSAIC TILE

GR GROUT

GR BM GRADE BEAM

GSB GYPSUM SHEATHING BOARD

GWB GYPSUM BOARD

ABBREVIATION TERM(S)

GYM GYMNASIUM

GYP GYPSUM

GYP BD GYPSUM BOARD

H HIGH

HB HOSE BIB

HC HANDICAP

HCP HANDICAPPED

HDO HIGH DENSITY OVERLAY

HDPE HIGH DENSITY POLYETHYLENE

HDW HARDWARE

HDWD HARDWOOD

HGR HANGER

HM HOLLOW METAL

HMD HOLLOW METAL DOOR

HMF HOLLOW METAL FRAME

HORIZ HORIZONTAL

HOSP HOSPITAL

HSKPG HOUSEKEEPING

HSS HOLLOW STRUCTURAL SECTION

HT HEIGHT

HW DOOR HARDWARE

HYD HYDRANT

Hz HERTZ

IAQ INDOOR AIR QUALITY

IB INTEGRAL BASE

IBC INTERNATIONAL BUILDING CODE

ID INSIDE DIAMETER

INT DES INTERIOR DESIGN

IF INSIDE FACE

IMH INLET MANHOLE

IMP INSULATED METAL PANEL

IN INCH OR INCHES

INSUL INSULATION

INT INTERIOR

INV INVERT

INV EL INVERT ELEVATION

ISO ISOMETRIC

ITS INTERTEK TESTING SERVICES

IW IRRIGATION WATER

JAN JANITOR

JT JOINT

KIP THOUSAND POUNDS

KIP FT THOUSAND FOOT POUNDS

KIT KITCHEN

KOP KNOCK OUT PANEL

L ANGLE, LENGTH OR LONG

LAB LABORATORY

LAG LAGGING

LAM LAMINATE

LAU LAUNDRY

LBS POUNDS

LD BRG LOAD-BEARING

LDPE LOW DENSITY POLYETHYLENE

LF LINEAR FOOT (FEET)

LIB LIBRARY

ABBREVIATION TERM(S)

LIN LINEAR

LINO LINOLEUM

LKR LOCKER

LL LIVE LOAD

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

LPT LOW POINT

LT LIGHT

LVL LEVEL

LVT LUXURY VINYL TILE

LWM LOW WATER MARK

M MOMENT

MAINT MAINTENANCE

MATL MATERIAL

MAX MAXIMUM

MB MARKER BOARD

MC MANHOLE COVER

MDO MEDIUM DENSITY OVERLAY

MECH MECHANICAL

MED MEDICAL OR MEDICINE

MEZZ MEZZANINE

MFD MANUFACTURED

MFG MANUFACTURING

MFR MANUFACTURER

MFR REC MANUFACTURER'S RECOMMENDATION

MH MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

mm MILLIMETER

MOD BIT MODIFIED BITUMEN

MT METAL TRIM

MTD MOUNTED

MTG MOUNTING

MTL METAL

MULL MULLION

MW MICROWAVE

MWP MEMBRANE WATERPROOFING

N NEWTON OR NORTH

NF NEAR FACE

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NRCA NATIONAL ROOFING CONTRACTORS ASSOCIATION

NS NEAR SIDE

NTS NOT TO SCALE

O OXYGEN

OA OVERALL

OC ON CENTER

OCC OCCUPY, OCCUPANTS OR OCCUPANCY

OD OUTSIDE DIAMETER

OF OUTSIDE FACE

OF/CI OWNER FURNISHED/CONTRACTOR INSTALLED

OF/OI OWNER FURNISHED/OWNER INSTALLED

OFF OFFICE

ABBREVIATION TERM(S)

OH DR OVERHEAD COILING DOOR

OPNG OPENING

OPP OPPOSITE

OR OPERATING ROOM

ORD OVERFLOW ROOF DRAIN

OSHA OCCUPATIONAL SAFETY AND HEALTH

ADMINSTRATION

OVFL OVERFLOW

OZ OUNCE

P PAINT

Pa PASCAL

PART PARTIAL

PASS PASSAGE

PBD PARTICLEBOARD

PC POINT OF CURVE OR POLYCARBONATE

PRVC PRIVACY CURTAIN

PCA PORTLAND CEMENT ASSOCIATION

PCB POLYCHLORINATED BIPHENYL

PCC PRECAST CONCRETE

PCT PORCELAIN TILE

PED PEDESTAL

PERF PERFORATED

PHAR PHARMACY

PI POINT OF INTERSECTION

PIB POLYISOBUTYLENE (PLASTIC)

PIV POST INDICATOR VALVE

PKG PACKAGE

PLAM HIGH PRESSURE PLASTIC LAMINATE

PLF POUNDS PER LINEAR FOOT

PLYWD PLYWOOD

PMF PROBABLE MAXIMUM FLOOD

PO PURCHASE ORDER

POLY POLYETHYLENE PLASTIC

PP POLYPROPYLENE PLASTIC

PR PAIR

PREFAB PREFABRICATE

PRELIM PRELIMINARY

PREP PREPARATION

PS POLYSTYRENE PLASTIC

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PT PAINT OR PAINTED

PTT PORCELAIN TILE TRIM

PTUBE PNEUMATIC TUBE

PVA POLYVINYL ACETATE

PVC POLYVINYL CHLORIDE (PLASTIC)

PVF POLYVINYL FLUORIDE (PLASTIC)

QS QUARTZ SURFACE

QT QUARRY TILE

QTR QUARTER

QTT QUARRY TILE TRIM

QTY QUANTITY

R RADIUS, RANGE, RISER OR THERMAL RESISTANCE

RAB RABBETED

RB RESILIENT OR RUBBER BASE

ABBREVIATION TERM(S)

RBF RUBBER FLOORING

RCP REFLECTED CEILING PLAN

RDG INS SOLID RIGID INSULATION

REC RECESSED OR RECREATION

RECIP RECIPROCAL

REF REFRIGERATOR

REINF REINFORCE

REQ REQUIRE

REQD REQUIRED

REQT REQUIREMENT

RESIL RESILIENT

REST RESTROOM

RF RESILIENT FLOORING

RFS ROOM FINISH SCHEDULE

RM ROOM

RND ROUND

RO ROUGH OPENING

ROW RIGHT OF WAY

RT RESILIENT TILE

RV ROOF VENT

SAN SANITARY

SBS STYRENE BUTADIEN STYRENE

SCP SCUPPER

SD SMOKE DETECTOR OR STORM DRAIN

SDT STATIC DISSIPATIVE TILE

SECT SECTION

SEP SEPARATE

SF SAFETY FACTOR OR SQUARE FOOT (FEET)

SHT SHEET

SHTHG SHEATHING

SIM SIMILAR

SP SCIENTIFIC PANEL (TRESPA) OR STANDPIPE

SPEC SPECIFICATION

SPF SPRUCE-PINE-FIR

SQ SQUARE

SS SANITARY SEWER OR SOLID SURFACE

SSCG STAINLESS STEEL CORNER GUARD

SST STAINLESS STEEL

ST STAIRS

STN STONE (NATURAL) TILE

STW STORM WATER

STC SOUND TRANSMISSION COEFFICIENT

STD STANDARD

STIR STIRRUP

STL STEEL

STOR STORAGE

STRUCT STRUCTURAL

SUB FL SUBFLOOR

SUSP SUSPEND OR SUSPENDED

SVF SHEET VINYL FLOORING

SYS SYSTEM

T TREAD

T&B TOP AND BOTTOM

T&G TONGUE AND GROOVE

TB TACKBOARD

ABBREVIATION TERM(S)

TCNA TILE COUNCIL OF NORTH AMERICA

TEMP TEMPORARY

TG TEMPERED GLASS

THK THICKNESS

THRU THROUGH

THRUOUT THROUGHOUT

TN TRUE NORTH

TOC TOP OF CURB

TOPO TOPOGRAPHY

TOS TOP OF STEEL

TOW TOP OF WALL

TP TELEPHONE POLE OR TRANSLUCENT PLASTIC

TS TENSILE STRENGTH

TW TACK WALL

TYP TYPICAL

UBC UNIFORM BUILDING CODE

UGND UNDERGROUND

UL UNDERWRITERS LABORATORIES

UNO UNLESS NOTED OTHERWISE

UON UNLESS OTHERWISE NOTED

UTIL UTILITY

VAC VACUUM

VB VINYL BASE

VCT VINYL COMPOSITION TILE

VENT VENTILATION OR VENTILATOR

VERT VERTICAL

VEST VESTIBULE

VIF VERIFY IN FIELD

VOC VOLATILE ORGANIC COMPOUND

VS VENT STACK

VTR VENT THROUGH ROOF

VWC VINYL WALL COVERING

W WIDE

W/ WITH

W/O WITHOUT

W/W WALL-TO-WALL

WB WOOD BASE

WC WALL COVERING

WD WOOD

WH WATER HEATER

WI WROUGHT IRON

WP WALL PROTECTION

WST WOOD STAIN

WT WEIGHT OR WINDOW TREATMENT

WWF WELDED WIRE FABRIC

X BRACE CROSS BRACE

XBRA CROSSBRACING

XFER TRANSFER

XL EXTRA LARGE

XPS EXTRUDED POLYSTYRENE BOARD INSULATION

XXH DOUBLE EXTRA HEAVY

YD YARD

YH YARD HYDRANT

YI YARD INLET

Z MODULUS OF SECTION

15 East Main, Suite 201

Vermillion SD 57069

Phone 605-624-1081

Vermillion

1221 N Street, Suite 600

Lincoln NE 68508

Phone 402-476-9700

Fax 402-476-9722

Lincoln

CONVERT IFR TO CLASSROOM -

FOSS FIELD ARMORY

SIOUX FALLS, SOUTH DAKOTA

G-001 COVER SHEET AND INDEX (THIS PAGE)

A-101 DEMOLITION FLOOR AND REFECTED CEILING PLANS

M-001 PLUMBING AND HVAC COVER SHEET

INDEX OF DRAWING

GENERAL

ARCHITECTURAL

MECHANICAL

VICINITY MAP

95% REVIEW DOCUMENTS FOR:

NATIONAL GUARD DR.

F

O

S

S

F

I

E

L

D

A

R

M

O

R

Y

ADDRESS: 801 W NATIONAL GUARD DR.

TO N MINNESOTA

AVE.

CFMO# SF466146

I-90

I-29

N. M

innesota A

ve

Sioux Falls

Regional Airport

See enlarged map above

A-102 FURNITURE, FLOOR, AND REFLECTED CEILING PLANS

A-201 INTERIOR ELEVATIONS, DETAILS AND WALL SECTIONS

E-101 ELECTRICAL PLAN - DEMOLITION AND NEW

ELECTRICAL

E-501 ELECTRICAL DETAILS

M-101 PLUMBING AND HVAC PLAN

A-601 DOOR, FINISH AND WALL TYPE SCHEDULES AND DETAILS

CODE INFORMATION

CODE REVIEW 2018 INTERNATIONAL BUILDING CODE

OCCUPANCY GROUP: B, BUSINESS

FIRE SPRINKLER: NONE

FIRE ALARM: NEW FIXTURES

FIRE ALARM DETECTION: SMOKE ALARM

COMMON PATH OF TRAVEL: 75'-0" MAX.

FIRE PROTECTION FEATURES:

FIRE RATED SEPARATION: 1 HR. EXISTING CORRIDOR

ALLOWABLE BUILDING AREA: NO AREA ADDED TO BUILDING, INTERIOR REMODEL

OCCUPANT LOAD FACTOR: 100 OFFICE AREAS

20 NET AREA, CLASSROOM

NO. OF EXITS: 2

E-502 ELECTRICAL DETAILS AND SYMBOL LEGEND

Cover Sheet

and Index

AUTHOR

CHECKED:

DAVIS DESIGN ALL RIGHTS RESERVED

SHEET TITLE

SHEET NUMBER

ID

ISSUE DATE:

DescriptionDate

Revisions:

15 E

ast M

ain, S

uite 201

Verm

illion S

D 57069

Phone 605-624-1081

Verm

illion

1221 N

S

treet, S

uite 600

Lincoln N

E 68508

Phone 402-476-9700

Fax 402-476-9722

Lincoln

G-001

07-16-2020

D.W.

D.H.

G-0

01

CLIENT INFORMATION

PROJECT INFORMATION

South Dakota

Army National

Guard

801 W National Guard Dr.

Sioux Falls, S.D 57104

CFMO# SF466146

Convert IFR

to Classroom -

Foss Field

Armory

20-0067Job #

darin.horst
Stamp
darin.horst
Date
Page 2: FOSS FIELD ARMORY · kop knock out panel l angle, length or long lab laboratory lag lagging lam laminate lau laundry ... all duct dimensions called out are interior free area dimensions

MECHANICAL

225

FOOD STORAGE

156

VESTIBULE

71

RIFLE RANGE

224

2

4

6

3 4

4

11

11

1

8

1010

9

13

14

15

16

16

OFFICE

229

MECHANICAL

225

WOMENS LATRINE

227

MENS LATRINE

155

OFFICE

79

FOOD STORAGE

156

FOOD PREPERATION

157

SCULLERY

251

TRAINING

ROOM

233

STORAGE

232

STORAGE

231

TRAINING

ROOM

230

CORRIDOR

70

VESTIBULE

71

VESTIBULE

71

RIFLE RANGE

224

ASSEMBLY HALL

161

CORRIDOR

162

STORAGE

FLAMMABLE

MATERIALS

158

ASSEMBLY HALL

159B

ELECTRICAL ROOM

142

TELEPHONE ROOM

141

FURNANCE ROOM

140

CORRIDOR

139

JANITOR

143

TRAINING ROOM

144

ELECTRICAL

179

CORRIDOR

177

CORRIDOR

177A

VESTIBULE

178

TRAINING ROOM

182

F.

E.

A.

B.

C.

D.

G.

KEY NOTES:

GENERAL NOTES:

REMOVE EXISTING H.M. DOOR, FRAME AND HARDWARE.

EXISTING L.V.T. FLOORING TO REMAIN. PROTECT FROM DAMAGE

DURING CONSTRUCTION.

SAW CUT AND REMOVE EXISTING CMU. REMOVE BRICK AND

INSULATION FOR NEW DOOR, FRAME AND LINTEL. SALVAGE

EXISTING BRICK FOR REUSE, IF NEEDED FOR INFILL AT LINTEL.

NEW BRICK SHALL BE TOOTHED-IN. REMOVE MASONRY, BRICK

AND INSULATION TO BELOW FLOOR TO ALLOW INSTALLATION OF

STOOP. COORDINATE EXTENT OF DEMOLITION WITH NEW

DETAILS. NEW BRICK SHALL BE TOOTHED-IN.

SAW CUT AND REMOVE EXISTING CMU. REMOVE BRICK AND 2"

RIGID INSUL FOR NEW WINDOW FRAME AND LINTEL.

COORDINATE EXTENT OF DEMOLITION WITH NEW DETAILS,

SHEET A-601 FOR SIZE OF WINDOW OPENING. LOCATE WINDOW

OPENING PER SHEET A-102. SALVAGE EXISTING BRICK FOR

REUSE, IF NEEDED FOR INFILL ABOVE LINTEL. NEW BRICK SHALL

BE TOOTHED-IN.

EXISTING PAINTED PRECAST CORED PLANK CEILING

STRUCTURE. BEARING OF CORED PLANK AT 10'-0" A.F.F.

SAWCUT AND REMOVE EXISTING SIDEWALK AND PAVING AS

REQUIRED TO INSTALL STOOP. REFER TO NEW DETAILS FOR

EXTENT OF REMOVAL.

REMOVE EXISTING G.W.B. CEILING AND HAT CHANNEL FRAMING

AS REQUIRED FOR INSTALLATION OF MECHANICAL ITEMS.

REINSTALL TO MATCH EXISTING. REFER TO MECHANICAL

DRAWINGS. COORDINATE EXTENT OF REMOVAL WITH CONTR.

SAW CUT AND REMOVE EXISTING FLOOR AS REQUIRED TO TIE

WASTE LINE INTO EXISTING. REFER TO MECHANICAL DRAWINGS.

PROTECT EXISTING EPOXY FLOOR ADJACENT TO DEMOLITION

WITH CARDBOARD, TAPED IN PLACE. PROTECT EXISTING

EQUIPMENT FROM DUST AND DEBRIS WITH FIRE RATED PLASTIC

SHEETING.

REMOVE EXISTING PARKING SIGNAGE. REINSTALL WHERE

DIRECTED BY OWNER.

PROVIDE REPLACEABLE STICKY WALK-OFF MATS DURING

CONSTRUCTION TO LIMIT THE SPREAD OF DUST.

SAW CUT AND REMOVE EXISTING CMU. REMOVE BRICK AND 2"

RIGID INSUL FOR NEW WINDOW FRAME AND LINTEL AS PART OF

ALTERNATE #1. COORDINATE EXTENT OF DEMOLITION WITH NEW

DETAILS, SHEET A-601 FOR SIZE OF WINDOW OPENING. LOCATE

WINDOW OPENING PER SHEET A-102. SALVAGE EXISTING BRICK

FOR REUSE, IF NEEDED FOR INFILL ABOVE LINTEL. NEW BRICK

SHALL BE TOOTHED-IN.

EXISTING OPENING IN PRECAST CORED-PLANK CEILING.

EXISTING WALK/PAVEMENT JOINT.

EXISTING BOLLARD TO REMAIN.

ALTERNATE #1. EXISTING BRICK EXP. JOINT. REMOVE BRICK AND

SEALANT AT JAMB OF WINDOW WHERE NEW WINDOW IS

INSTALLED.

REMOVE ADDITIONAL CONCRETE AT WALK AND PAVEMENT AS

REQUIRED TO INSTALL STOOP. SLOPE CONCRETE AT 5%

MAXIMUM ALONG WALK TO MEET EXISTING SURFACE OF WALK.

1

2

3

4

5

REMOVE ITEM'S SHOWN WITH HEAVY DASHED LINETYPE UNLESS

NOTED OTHERWISE.

WHERE DEMOLITION OCCURS NEXT TO EXISTING CONSTRUCTION

TO REMAIN, MATCH PATCH AND REPAIR DISTURBED AREA TO A

LEVEL CONSISTENT WITH THE EXISTING CONSTRUCTION TO

REMAIN.

PROTECT ALL ITEMS, MATERIALS AND/OR SURFACES NOT

SCHEDULED TO BE DEMOLISHED.

REFER TO MECHANICAL AND ELECTRICAL DRAWINGS FOR

DEMOLITION OF MECHANICAL AND ELECTRICAL ITEMS.

AREAS OF DEMOLITION SHALL BE KEPT CLEAN AND SAFE.

DISPOSE OF DEBRIS DAILY AND CLEAN AREAS OF WORK UPON

COMPLETION.

KEEP DOORS TO SPACE CLOSED DURING DEMOLITION.

EXISTING PVC SIKA SARNAFIL ROOF IS UNDER A 20 YEAR

WARRANTY. WARRANTY SERIAL NO.: 0000012513-368313.1. NEW

WORK DONE TO EXISTING ROOFING SHALL MAINTAIN EXISTING

WARRANTY.

PROVIDE TEMPORARY, SECURE AND WEATHERPROOF

ENCLOSURES TO EXTERIOR OPENINGS TO PROTECT WALL

ASSEMBLY FROM WATER INTRUSION.

6

7

8

9

10

H.

11

12

13

14

15

16

MECHANICAL

225

FOOD STORAGE

156

VESTIBULE

71

RIFLE RANGE

224

7

5

12

12

Demolition

Floor and

Refected

Ceiling Plans

AUTHOR

CHECKED:

DAVIS DESIGN ALL RIGHTS RESERVED

SHEET TITLE

SHEET NUMBER

ID

ISSUE DATE:

DescriptionDate

Revisions:

15 E

ast M

ain, S

uite 201

Verm

illion S

D 57069

Phone 605-624-1081

Verm

illion

1221 N

S

treet, S

uite 600

Lincoln N

E 68508

Phone 402-476-9700

Fax 402-476-9722

Lincoln

A-101

07-16-2020

D.W.

D.H.

A-1

01

SCALE:

1

Demolition Floor Plan

1/4" = 1'-0"

CLIENT INFORMATION

PROJECT INFORMATION

South Dakota

Army National

Guard

801 W National Guard Dr.

Sioux Falls, S.D 57104

CFMO# SF466146

Convert IFR

to Classroom -

Foss Field

Armory

20-0067Job #

KEY PLAN

AREA OF WORK

SCALE:

1

Demolition Reflected Ceiling Plan

1/4" = 1'-0"

1

1

darin.horst
Date
darin.horst
Stamp
Page 3: FOSS FIELD ARMORY · kop knock out panel l angle, length or long lab laboratory lag lagging lam laminate lau laundry ... all duct dimensions called out are interior free area dimensions

MECHANICAL

225

VESTIBULE

71

6

Classroom

224

Office

224D

Office

224C

Office

224B

Office

224A

Corridor

224-1

1

A-201

2

A-201

3

A-201

3'-8" 3'-4" 3'-4" 3'-8" 3'-8"

8'-10 5/8"

4 7/8"

4'-1 3/8"

4 7/8"

8'-8"

1'-0"

4'-0"

20'-4"

3'-8"

11'-0"

3'-8"

25'-0"

3'-8"

224

1A

A-201

224-1

224B224A

224C

224D

ALT #2

9

A-201

01

01

01

01

01

01

02

02

02

02

02

02

02

02

02

01

01

5

5

1

18

18

AW-1

AW-1

AW-1

AW-2

AW-1

2

9

PANEL L2

4

16

13'-3 1/8"

4 7/8"

13'-4 7/8"

17

11

2%

M

AX

.

5% MAX.

5% MAX.

RIFLE RANGE

224

PANEL L2

A.

B.

KEY NOTES:

DIMENSIONS OF DOOR AND WINDOW ROUGH OPENINGS

ARE NOMINAL AND DO NOT ACCOUNT FOR SHIM SPACE

AT EACH SIDE OF OPENING.

NEW BRICK SHALL BE TOOTHED-IN.

OWNER HAS LIMITED BRICK TYPE 1 (BLEND). VERIFY

OWNER QUANTITY AND AVAILABILITY OF SPECIAL TYPES

AS INDICATED.

PROVIDE COLORED MORTAR TO MATCH EXISTING. FIELD

VERIFY.

PROVIDE BRICK MOCK-UP TO VERIFY BRICK TEXTURE,

BLEND AND COLOR OF BRICK TYPE 1, BRICK TEXTURE

AND COLOR OF BRICK TYPE 2 AND MORTAR COLOR TO

MATCH EXISTING. REFER TO DETAIL 11/A-201 FOR BRICK

DETAILS.

OFFICE FURNITURE IS FOR DEMONSTRATION OF

PROPOSED LAYOUT FOR OWNER USE ONLY.

GENERAL NOTES:

ALUMINUM BLAST WINDOW. REFER TO SPECIFICATIONS

AND TO DETAILS, SHEET A-601.

DASHED LINE INDICATES CABINETS UNDER ALTERNATE

#2. REFER TO SHEET A-201.

REFRIGERATOR, BY ONWER

EXISTING LIGHT FIXTURE

EXISTING DOWNSPOUT.

EXISTING BRICK EXPANSION JOINT LOCATION. NEW

BRICK EXPANSION JOINT AT JAMB OF WINDOW TO

CONTINUE JOINT THROUGH NEW CONSTRUCTION.

CLOSE EXISTING OPENING IN PRECAST CORED CEILING

WITH 6" METAL STUD FRAMING AT 16" O.C., 16" THERMAL

BATT INSULATION AND 5/8" G.W.B. CEILING, PAINT G.W.B.

CEILING WHITE. PROVIDE BACKER ROD AND SEALANT

BETWEEN EDGE OF G.W.B AND EXISTING PRECAST

CORED PLANKS.

EXISTING OPENING FOR DUCTWORK ABOVE. REFER TO

MECHANICAL DRAWINGS.

TV MOUNTING BRACKET, REFER TO 10/A-201. VERIFY

EXACT LOCATION ON WALL WITH USERS.

WOOD BLINDS, REFER TO SPECIFICATIONS.

COFFEE MAKER, BY OWNER.

PRINTER, BY OWNER.

SHREDDER, BY OWNER.

OFFICE FURNITURE, TABLES AND CHAIRS BY OWNER.

PATCH AND PAINT EXISTING CEILING WITH G.W.B.

PATCH FLOOR WITH CONCRETE OVER COMPACTED AND

TESTED SUBGRADE WITH GRANULAR FILL AND VAPOR

BARRIER TO MATCH EXISTING. FINISH CONCRETE TO

ACCEPT EPOXY COATING BY OTHERS TO MATCH

EXISTING.

FIRE EXTINGUISHER CABINET, REFER TO 13/A-201

ALUMINUM BLAST WINDOW UNDER ALTERNATE #1.

REFER TO SPECIFICATIONS AND TO DETAILS, SHEET

A-601. NEW WORK AT THIS OPENING IS UNDER

ALTERNATE #1. IF ALTERNATE #1 IS NOT ACCEPTED,

CONTINUE WALL TYPE 02 THROUGH WINDOW OPENING.

C.

D.

E.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

F.

MECHANICAL

225

VESTIBULE

71

8

Classroom

224

Office

224D

Office

224C

Office

224B

Office

224A

Corridor

224-1

12

A-201

7

A2 A2

A2 A2

A2 A2

A2 A2

A2 A2

A2 A2

A2

A2

A2

A2

A2

A2

A2

A2

A1

A1

A1

X1

X1

PANEL L2

PP

X1

15

MECHANICAL

225

VESTIBULE

71

Classroom

224

Office

224D

Office

224C

Office

224B

Office

224A

Corridor

224-1

72"x30" 72"x30"

72"x30" 72"x30"

72"x30" 72"x30"

72"x30" 72"x30"

72"x30" 72"x30"

72"x30" 72"x30"

72"x30" 72"x30"

3

11

12

13

14

14

14

14

14

14

14

14

1414

14

14

14

14

PANEL L2

Furniture,

Floor, and

Reflected

Ceiling Plans

AUTHOR

CHECKED:

DAVIS DESIGN ALL RIGHTS RESERVED

SHEET TITLE

SHEET NUMBER

ID

ISSUE DATE:

DescriptionDate

Revisions:

15 E

ast M

ain, S

uite 201

Verm

illion S

D 57069

Phone 605-624-1081

Verm

illion

1221 N

S

treet, S

uite 600

Lincoln N

E 68508

Phone 402-476-9700

Fax 402-476-9722

Lincoln

A-102

07-16-2020

D.W.

D.H.

A-1

01

SCALE:

1

Floor Plan

1/4" = 1'-0"SCALE:

2

Reflected Ceiling Plan

1/4" = 1'-0"

CLIENT INFORMATION

PROJECT INFORMATION

South Dakota

Army National

Guard

801 W National Guard Dr.

Sioux Falls, S.D 57104

CFMO# SF466146

Convert IFR

to Classroom -

Foss Field

Armory

20-0067Job #

KEY PLAN

SCALE:

3

Furniture Plan

1/4" = 1'-0"

AREA OF WORK

darin.horst
Date
darin.horst
Stamp
Page 4: FOSS FIELD ARMORY · kop knock out panel l angle, length or long lab laboratory lag lagging lam laminate lau laundry ... all duct dimensions called out are interior free area dimensions

1'-7 1/2" 2'-9"

7

A-102

3'-0"

LOCK DOORS AND

DRAWERS AS INDICATED

8

A-102

2'-1

0"

VINYL BASE AT CABINET

TOE KICK AND AT CABINET

RETURN, TYPICAL.

4"

3'-0"

7

A-102

3'-0" 3'-0"

LOCK DOORS AND

DRAWERS AS INDICATED

2'-1

0"

VINYL BASE AT CABINET

TOE KICK AND AT CABINET

RETURN, TYPICAL.

4"

3'-0"3'-0"

7

A-102

2'-0"

LOCK DOORS AND

DRAWERS AS INDICATED

2'-1

0"

VINYL BASE AT CABINET

TOE KICK AND AT CABINET

RETURN, TYPICAL.

4"

3'-0" 1'-6" 2'-9"

7

A-102

2'-6" 2'-6"

LOCK DOORS AND

DRAWERS AS INDICATED

8

A-102

2'-1

0"

VINYL BASE AT CABINET

TOE KICK AND AT CABINET

RETURN, TYPICAL.

4"

2'-9" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0"1'-7 1/2"

1'-6" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0" 3'-0"1'-6"

1'-4

"1

0"

1'-8

"

6

A-102

5

A-102

4

A-102

1/4" MELAMINE BTM.

1/2" POPLAR DWR W/

MELAMINE INT.

SOLID

6"

1/4

"

4 3

/4

"

OVER 3/4" PLYWD.

1" SHELF

ADJ. SHELF AND DOOR

1/4" PLYWD.

WD. BASE 4" RUBBER BASE

3"

2'-0"

1 1

/2

"

1/4

"

1'-1

0"

4"

K.V. #255 WITH #256

BRACKETS

WITH 3 MM EDGES

PLAM OVER P. BD.

1'-8 1/2"

LOCKS, WHERE

INDICATED

2"

3"

FOR TYPE AND SIZE

SEE MECH. DWGS.

1/4

"

1 1

/2

"

3 1/2"

2'-0"

EDGE, TYP.

WATERFALL FRONT

3/4" POST FORMED PLAM C.T.

OVER 3/4" PLYWD.

SEAL AT

1/4" PLYWD.

1'-0"

2'-6

"

REFER TO

WALL TYPES

EDGES

ADJ. SHELF AND DOOR- PLAM

OVER P. BD. WITH 3 MM

K.V. #255 WITH #256 BRACKETS

OR EQUAL. (TYP. ALL SHELVES)

4" RUBBER BASE

1" SHELF

1'-8 1/2"

BACKSPLASH

4"

11"

8"

2'-3

" M

IN

. C

LE

AR

AN

CE

F

OR

A

DA

2'-1

0" M

AX

IM

UM

H

EIG

HT

F

OR

A

DA

TILE, SEE ELEV.

PLAM OVER P.B.

REMOVABLE 3/4"

WITH 3 MM EDGES

PLAM OVER P. BD.

5 1

/4

"

ADA CLEARANCE

KNEE VALANCE

1/4" PLYWD.

1'-0"

1'-6

"

REFER TO

WALL TYPES

K.V. #255 WITH #256 BRACKETS

OR EQUAL. (TYP. ALL SHELVES)

PLAM INT.

1/4" PLYWD.

1'-0"

1'-8

"

REFER TO

WALL TYPES

EDGES

ADJ. SHELF AND DOOR- PLAM

OVER P. BD. WITH 3 MM

K.V. #255 WITH #256 BRACKETS

OR EQUAL. (TYP. ALL SHELVES)

1" SHELF

1'-0

"

EDGE, TYP.

WATERFALL FRONT

SEAL AT

BACKSPLASH

4"

3/4" POST FORMED PLAM C.T.

1'-6"

HORIZ. J-BOX

ON 1 1/2" EPOXY ANGLE

WITH 3 MM EDGES

ESCUTCHEON

SCREW ATTACH WITH

DECORATIVE WASHERS

9"

MELAMINE INT. MELAMINE INT.

MELAMINE INT.

1" PLAM BOT.

WITH 3MM EDGES

6" CONCRETE

SLAB W/ #4'S @ 12"

O.C. EACH WAY ON

4" SLABFORM BY

VOIDFORM OR EQ.

2'-6"

#4 DOWELS

@ 12" O.C.

2'-0"

#4'S AT 12" O.C.

EPOXY INTO

EXIST. FTG. AND

FDN. WALL 4"

WITH HIT- HY 200

OR EQUAL

3'-4" (VERIFY)

#4'S @ 1'-4" O.C.

VERTICAL

8"

4'-0", VERIFY (x4'-2" WIDE)

EXIST. PAVEMENT

4'-0" V

ER

IF

Y1'-0"

1/2" EXP. JNT. W/

BACKER ROD AND

SEALANT. MATCH

EXISTING LOC.

2% MAX SLOPE, MATCH EXIST PVMNT.

EXIST.

FOUNDATION

3" 5 3/4" 8 3/8"

LVT FLOOR

PATCH TO

MATCH EXISTING.

#4'S AT 12" O.C.

EPOXY INTO

EXIST. FDN.

WALL 4" WITH

HIT- HY 200 OR

EQUAL

2'-6"

60°

COMPACT

SUBGRADE IN

8" LIFTS

PROVIDE NEW OR

SALVAGED S.S.

FLASHING TO MATCH

EXIST. AT NEW BRICK

CUSTOM BRICK,

TYP. AT RETURN

SET THRESHOLD IN FULL

BED OF SEALANT.

1/2" EXP. JNT. MAT. WITH

B.R. AND SEALANT.

6'-8

" A

.F

.F

. V

ER

IF

Y

8" V

ER

IF

Y

1'-10

"

L

C

ELEC. OUTLET

DATA OUTLET

T.V. MOUNT BY OWNER

SOLID WOOD BLOCKING

J-BOX

VERIFY SIZE

MET. STUDS, REFER TO WALL TYPES

1'-6"

Scale:

10

T.V. Mounting Detail

1 1/2" = 1'-0"

J-BOX

V

V

B

B

V = VELOUR FACE TO MATCH EXISTING

B = BARK FACE TO MATCH EXISTING

PROVIDE MODULAR BRICK SIZES:

3 5/8" x 2 1/4" x 7 5/8"

TYPE 1 CUSTOM BRICK TYPE 2 CUSTOM BRICK

PROVIDE IN 3 COLORS (BLEND) PROVIDE IN 1 COLOR

PROVIDE BRICK INDICATED AT JAMBS

OF WINDOWS AND DOORS

4"

4"

1"

VERIFY

54

" A

.F

.F

. (M

AX

.)

T.O

. C

AB

IN

ET

T

O F

IN

. F

LR

.

Interior

Elevations,

Details and

Wall Sections

AUTHOR

CHECKED:

DAVIS DESIGN ALL RIGHTS RESERVED

SHEET TITLE

SHEET NUMBER

ID

ISSUE DATE:

DescriptionDate

Revisions:

15 E

ast M

ain, S

uite 201

Verm

illion S

D 57069

Phone 605-624-1081

Verm

illion

1221 N

S

treet, S

uite 600

Lincoln N

E 68508

Phone 402-476-9700

Fax 402-476-9722

Lincoln

A-201

07-16-2020

D.W.

D.H.

A-1

01

CLIENT INFORMATION

PROJECT INFORMATION

South Dakota

Army National

Guard

801 W National Guard Dr.

Sioux Falls, S.D 57104

CFMO# SF466146

Convert IFR

to Classroom -

Foss Field

Armory

20-0067Job #

SCALE:

3

Elevation

1/4" = 1'-0" SCALE:

2

Elevation

1/4" = 1'-0" SCALE:

1A

Elevation (Alternate #2)

1/4" = 1'-0"

SCALE:

5

Cab. Section

3/4" = 1'-0" SCALE:

4

Cab. Section

3/4" = 1'-0"

SCALE:

1

Elevation

1/4" = 1'-0"

SCALE:

8

Cab. Section

3/4" = 1'-0" SCALE:

6

Cab. Section

3/4" = 1'-0"SCALE:

7

Cab. Section

3/4" = 1'-0"

SCALE:

9

Stoop Section

3/4" = 1'-0"SCALE:

11

Custom Brick Detail

3" = 1'-0"SCALE:

12

Bulkhead Detail

1 1/2" = 1'-0"SCALE:

13

FEC Cabinet Detail

1 1/2" = 1'-0"

darin.horst
Date
darin.horst
Stamp
Page 5: FOSS FIELD ARMORY · kop knock out panel l angle, length or long lab laboratory lag lagging lam laminate lau laundry ... all duct dimensions called out are interior free area dimensions

2"

SEE SCHED.

HMF-1

Scale:

1

H.M. Frame Types

1/4" = 1'-0"

2"

SE

E S

CH

ED

UL

E

3 3

/8

"

2"

SEE SCHED.

HMF-2

2"

SE

E S

CH

ED

UL

E

2"

SE

E S

CH

EU

DL

E

A

Scale:

2

Door Types

1/4" = 1'-0"

B

GL-1 AT FIRE

RATED DOORS

SEE SCHED.

SE

E S

CH

EU

DL

E

2'-1

"

8"

4"

3'-7

"

2"

SEE SCHED.

2"

SE

E S

CH

ED

UL

E

4"

HMF-3

GL-2

SE

E S

CH

EU

DL

E

2'-1

"

C

SEE SCHED.

4"

8"

3'-7

"

Scale:

11

Bearing Detail

3" = 1'-0"

1 1/2" LONG SLOT AT BEAM FLANGE.

ANCHOR ROD SHALL BE LOCATED AT

CENTER OF SLOT, COORDINATE.

1/2"

5" x 7 5/8" x 3/4" EMBED PLATE WITH TWO

3/4" DIA. x 12" LONG ANCHOR RODS. CUT

CMU TO FIT EMBED PLATE.

Scale:

7

Head Detail

3" = 1'-0"

SEALANT IN 1/4" JOINT

8"x8" CMU. GROUT SOLID WITH 1#4

6 3/8"

Scale:

8

Jamb Detail

3" = 1'-0"

1'-2

" E

XIS

TIN

G W

AL

L T

HIC

KN

ES

S

VE

RIF

Y

BACKERROD AND

SEALANT EACH SIDE

OF WINDOW FRAME

3"

PATCH FACE BRICK

TO MATCH EXIST.

EXIST. BRICK

EXIST. C.M.U.

1-#4 IN CELL,

GROUT SOLID

8" x 8" CMU

REFER TO WALL

TYPES.

METAL CORNER

BEAD, TYP.

CORRUGATED

1" BRICK TIE

AT 16" O.C.

BACKER ROD AND

SEALANT IN 1/4" JOINT

BTW. GWB AND FRAME

ADHERED 5/8"

DRYWALL TO CMU

Scale:

9

Head Detail

3" = 1'-0"

R.O. AT 8'-8" A.F.F.

W8x18

BACKERROD AND

SEALANT EACH SIDE

3"

.060" EPDM. FLASHING, EXTEND

UP BEHIND MOISTURE BARRIER,

ADHERE TO SURFACES, SEAL

EDGES TO MASONRY BEYOND.

MOISTURE BARRIER, SEAL

AT PERIMETER.

EXTERIOR GYP. SHEATHING

OVER 1 5/8" MET. STUDS AT

16" O.C., MAX.

2" RIGID INSULATION

1/2" x 1'-1" x 3'-7" GALV.

PLATE, WELD TO BM.

WEEPS AT 24" O.C.

VERIFY

11

A-601

FILL CAVITY WITH

THERMAL INSUL.

3 3

/8

" V

ER

IF

Y

R.O. AT 8'-0" A.F.F.

W8x18

BACKERROD AND

SEALANT EACH SIDE

WD. SHIM

3"

MOISTURE BARRIER, SEAL

AT PERIMETER.

EXT. GYP. SHEATHING

OVER 1 5/8" MET. STUDS

AT 16" O.C., MAX.

2" RIGID INSULATION

WEEPS AT 24" O.C.

5 3/4"

SPRAY FOAM

FRAME SOLID

11

A-601

FILL CAVITY WITH

THERMAL INSUL.

2 - 3 5/8" MET. STD.

BOX HEADER

Scale:

10

Sill Detail

3" = 1'-0"

R.O. AT 3'-4" A.F.F.

BACKERROD AND

SEALANT EACH SIDE

1/4" WD. SHIM W/

FULL SPRAY FOAM

INSUL.

3" VERIFY

SILICONE SEAL

PENETRATIONS IN

FLASHING

TURN UP THRU-WALL

FLASHING 1/2", HEM EXP. EDGE

PRE-FIN .032" ALUMINUM

THRU-WALL FLASHING, FULL

WIDTH OF OPENING. HEM

EXPOSED EDGE. SILICONE SEAL

IN PLACE OVER BRICK. PROVIDE

DK. BRONZE TO MATCH EXIST.

BACKER ROD AND SEALANT

AT SILL. VERIFY LOC. WITH

WINDOW MFR.

TURN UP THRU-WALL

FLASHING AT JAMB AND SEAL

TO MASONRY

BR

IC

K T

YP

E 2

BR

IC

K T

YP

E 1

R.O. AT 8-0" A.F.F.

BR

IC

K T

YP

E 2

BR

IC

K T

YP

E 1

B.R. AND

SEALANT

STEEL LINTEL, REFER TO DET. FOR SIZE

2" RIGID INSUL.

2 1/2" x 3 1/2" LLV GALV.

ANGLE. SCREW TO

MASONRY AT 16" O.C.

1/4" JOINT WITH BACKER ROD AND

SEALANT. PROVIDE 1/2" JOINT AT

BRICK EXP. JOINT FOR AW-2

SILICONE SEAL BETWEEN

FLASHING AND BRICK.

1/4" SHIM. PROVIDE

1/2" SHIM AT B.E.J.

WITH FULL SPRAY

FOAM INSUL.

W8 BM.

BR

IC

K T

YP

E 2

BR

IC

K T

YP

E 2

2 - 3 5/8" MET. STD.

BOX HEADER

1/2" x 1'-1" x 3'-3" GALV.

PLATE, WELD TO BM.

.060" EPDM. FLASHING,

EXTNED UP BEHIND MOISTURE

BARRIER, ADHERE TO

SURFACES, SEAL EDGES TO

MASONRY BEYOND.

BR

IC

K T

YP

E 1

3'-4" A.F.F. (N.T.S.)

BR

IC

K T

YP

E 1

REFER TO

WALL TYPES.

R.O. AT 7-4" A.F.F.

REFER TO

WALL TYPES.

ACOUS. CLG.

TILE AND

SUSP. SYS.

3/4" PLAM (MARINE

GRADE) STOOL OVER

1/2" PLY. WD.

2 1/2" WOOD BLINDS

WITH DECORATIVE

WOOD VALANCE

HB-200-2 BRICK

TIE AT 16" O.C.

ALUM. WINDOW

2 1/2" x 3 1/2" GALV.

ANGLE. SCREW TO

MASONRY AT 16" O.C.

ALUM. WINDOW

RECEPTOR IF REQ'D.

ALUM. WINDOW

RECEPTOR IF REQ'D.

EXTEND REINF. INTO EXISTING GROUTED

MASONRY CELL BELOW 4" MIN. WITH

HIT-HY 200. IF NOT GROUTED EXTEND

REINF AS DEEP AS POSSIBLE, VERIFY,

GROUT SOLID.

GROUT CORE SOLID

1 1

/2

"

PLAM

PLAM

1/4" SHIM WITH FULL

SPRAY FOAM INSUL.

HGT. OF SUPPORTFACING

Interior Partition Schedule

SUPPORTTYPE

WIDTH

ACTUAL

NOTESRTG. INSUL.

MATERIAL

OPN'G DOOR FRAMERATING

MATERIALWIDTH

#

224

224A

HEIGHT THICKNESS

7'-0"

7'-0" 1 3/4"

LABELTYPE

S.C. WD.

TYPE

HMF-1 H.M.

Door and Frame Schedule

FRAME DETAILS OPN'G

R. JAMBHEAD L. JAMB HDWR #SILL

HW-2

# NOTES

224C 7'-0"

1 3/4"

1 3/4" S.C. WD.

HMF-1

H.M.

S.C. WD. B

HW-2

3'-0" HW-1

224B

3'-0"

3'-0"

3'-0"

7'-0" 1 3/4" S.C. WD.

HMF-1

H.M.

HW-2

12/A-60112/A-60113/A-601

3/A-6014/A-6015/A-601

224-1

224D 3'-0" 7'-0" 1 3/4" S.C. WD.

HMF-3 H.M.

HMF-1 H.M.

HW-3

HW-2

7'-0" 1 3/4" H.M.3'-0" A HMF-2 H.M. 8/A-6018/A-6017/A-601

224

224A

224C

224B

224-1

224D

C

C

C

C

60 MIN.

12/A-601

13/A-601

13/A-601

12/A-601 12/A-601

12/A-601

13/A-601

12/A-601

12/A-601

ROOM DESIGNATIONS FINISHBASE

MATERIALRM. NAME

224-1CORRIDOR

VB-1

Room Finish Schedule

SOUTHNORTH EAST WEST

224A

VB-1CLASSROOM

224

VB-1

1, 3, 4, 5, 6

1, 2, 10

RM. NO.

REMARKSFLOOR

MATERIAL

EXIST. LVT

CEILING

FINISH HEIGHT

1, 2, 3, 7, 8, 9, 10

1, 2, 10

PT-1 PT-1 PT-1PT-1

EXIST. LVT PT-1 PT-1 PT-1PT-1

PT-1 PT-1 PT-1PT-1

ACT-1 8'-6"

OFFICE EXIST. LVT 8'-6"

ACT-1

ACT-1

8'-0"

224B VB-1 PT-1PT-1 PT-1 PT-1 EXIST. LVTOFFICE

224C

ACT-1 8'-6"

PT-1 PT-1VB-1 PT-1OFFICE

PT-1 EXIST. LVT ACT-1 8'-6"

224D PT-1VB-1 PT-1PT-1PT-1OFFICE

EXIST. LVT ACT-1 8'-6" 1, 2 10

1, 2

Scale:

3

Jamb Detail

3" = 1'-0"

ADHERED

5/8" G.W.B.

SPRAY FOAM

FRAME SOLID

SEALANT EA.

SIDE OF FRAME

1/2

"

SEE FLOOR PLAN

FOR DOOR

HANDING, TYP.

1/2

"

5 3

/4

"

SPRAY FOAM

FRAME SOLID

SEALANT EA.

SIDE OF FRAME

1/2

"

SEE FLOOR PLAN

FOR DOOR

HANDING, TYP.

1/2

"

2"

5 3

/4

"

EXISTING

C.M.U.

REFER TO WALL

TYPES.

METAL CORNER

BEAD, TYP.

7 5

/8

"

Scale:

4

Jamb Detail

3" = 1'-0"

5 3/4"

4"

SEE FLOOR PLAN

FOR DOOR

HANDING, TYP.

SEALANT EA. SIDE

OF FRAME

7 5/8", VERIFY

SRAY FOAM

FRAME SOLID

Scale:

5

Head Detail

3" = 1'-0"

10

7'-4

"

B.O

. S

TE

EL

P

LA

TE

EXIST STEEL LINTEL, PAINT

TO MATCH EXISTING.

REFER TO WALL

TYPES.

Scale:

6

Jamb Detail

3" = 1'-0"

1'-2

" E

XIS

TIN

G W

AL

L T

HIC

KN

ES

S

SEE FLOOR PLAN

FOR DOOR

HANDING, TYP.

2"

5 3

/4

"

BACKERROD AND

SEALANT EACH SIDE

OF DOOR FRAME

3"

PATCH FACE

BRICK TO MATCH

EXIST.

SPRAY FOAM

FRAME SOLID

EXIST. BRICK

EXIST. C.M.U.

1-#4 IN CELL,

GROUT SOLID

8" x 8" CMU

REFER TO WALL

TYPES.

METAL CORNER

BEAD, TYP.

CORRUGATED

1" BRICK TIE

AT 16" O.C.

BACKER ROD AND

SEALANT IN 1/4" JOINT

ADHERED 5/8"

DRYWALL TO CMU

J-BEAD, HOLD OFF

OF DOOR FRAME 1/4"

2" RIGID

INSULATION

TREATED WOOD

BUCK WITH S.S.

FASTENER

EXTNED UP BEHIND MOISTURE

HB-200-2 BRICK

TIE AT 16" O.C.

SEE FLOOR PLAN

FOR DOOR

HANDING, TYP.

RE

FE

R T

O W

ALL T

YP

ES

FO

R W

ALL T

HIC

KN

ES

S

2"

TWO STUDS AT

JAMB, TYP.

1/2"

1/2"

Scale:

12

Jamb Detail

3" = 1'-0"

TWO 4" METAL

STUD HEADER IN

RUNNER

2"

SEE FLOOR PLAN

FOR DOOR

HANDING, TYP.

REFER TO WALL TYPES

FOR WALL THICKNESS

1/2" 1/2"

Scale:

13

Head Detail

3" = 1'-0"

SEALANT EA. SIDE

OF FRAME

SEALANT EA. SIDE

OF FRAME

F.O. ADJACENT WALL

WHERE INDICATED

2"

AW-1

R. JAMBHEAD

10/A-601 11/A-601

FRAME

TYPE

AW-2

Aluminum Window Schedule

MULLION DETAIL

GL-2

Glazing Schedule

L. JAMB

3/16" PLATINUM F BY GLASSOPOLIS

SILL

9/A-6019/A-601

9/A-6019/A-60110/A-601

FRAME DETAILS

14/A-601

14/A-60111/A-601

TYPE

GLASS

GL-1

CLEAR, TEMPERED

GL-3BALLISTIC/BLAST RATED, INSULATED, LOW-E, BRONZE TINTED

DESCRIPTION

NOTE: ALUMINUM WINDOW FRAMES SHALL BE 2 1/2" X 6" MAXIMUM.

Scale:

15

Alum. Window Frame Types

1/4" = 1'-0"

2 1/2"

3'-2 1/2"

2 1/2"

2'-7"

2 1/2"

AW-1 AW-2

2 1/2"

GL-3

2 1/2"

GL-3

2 1/2"

2 1/2"

1'-5"

2 1/2"

1'-5"

2 1/2"

2 1/2"

3'-2 1/4"

4'-7 1/2"

2'-7"

BALLISTIC/BLAST RATED

GL-3

GL-3

4'-7 1/2"

TYP.

Scale:

14

Mullion Detail

3" = 1'-0"

VE

RIF

Y

2 1/4"

Door, Finish

and Wall Type

Schedules

and Details

AUTHOR

CHECKED:

DAVIS DESIGN ALL RIGHTS RESERVED

SHEET TITLE

SHEET NUMBER

ID

ISSUE DATE:

DescriptionDate

Revisions:

15 E

ast M

ain, S

uite 201

Verm

illion S

D 57069

Phone 605-624-1081

Verm

illion

1221 N

S

treet, S

uite 600

Lincoln N

E 68508

Phone 402-476-9700

Fax 402-476-9722

Lincoln

A-601

07-16-2020

D.W.

D.H.

A-6

01

CLIENT INFORMATION

PROJECT INFORMATION

South Dakota

Army National

Guard

801 W National Guard Dr.

Sioux Falls, S.D 57104

CFMO# SF466146

Convert IFR

to Classroom -

Foss Field

Armory

20-0067Job #

darin.horst
Date
darin.horst
Stamp
Page 6: FOSS FIELD ARMORY · kop knock out panel l angle, length or long lab laboratory lag lagging lam laminate lau laundry ... all duct dimensions called out are interior free area dimensions

EXISTINGNEW

TO REMAIN

EXISTINGDEMO

1

1

NEW WORK KEYED NOTE SYMBOL

DEMOLITION KEYED NOTE SYMBOL

FINISHED FLOORFF

ROUND RETURN, EXHAUST OR RELIEF AIR DOWN

ROUND SUPPLY OR OUTSIDE AIR DUCT DOWN

RECTANGULAR RETURN, EXHAUST OR RELIEF AIR DOWN

RECTANGULAR SUPPLY OR OUTSIDE AIR DUCT DOWN

SIZE TAG

CFM100

10x10 L-1

XXX-1 EQUIPMENT TAG (SEE SCHEDULES, I.E. AHU-1 - AIR HANDLING UNIT)

TEE - OUTLET UP

TEE - OUTLET DOWN

TEE

ELBOW - 45°

ELBOW - OUTLET UP

ELBOW - OUTLET DOWN

ELBOW

CROSS

CAP

VALVE - SEE SPECIFICATIONS FOR TYPE

DIRECTION OF FLOW

DOWNWARD PIPE PITCH

MANUAL BALANCING VALVE

CHECK VALVE

LOUVER TAG

FLEX DUCT

TURNING VANES

ELEVATION CHANGE IN DIRECTION OF AIRFLOW, UP

ELEVATION CHANGE IN DIRECTION OF AIRFLOW, DOWN

MOTORIZED DAMPER

SPACE/DUCT PRESSURE SENSOR/TRANSMITTER

TEMPERATURE CONTROLS

SHEET METAL

DETAIL IDENTIFICATION

SECTION IDENTIFICATION

FIRE/SMOKE DAMPER

SMOKE DAMPER

FIRE DAMPER

MANUAL VOLUME DAMPER

DISCONNECT POINT

CONNECTION POINT

CFM

SIZE TAG

CFM

SIZE TAG

EA (OR RELA) DIFFUSER/REGISTER/GRILLE TAG

RA DIFFUSER/REGISTER/GRILLE TAG

SIZE TAG

CFM

SA DIFFUSER/REGISTER/GRILLE TAG

10x10 E-1

100

10x10 R-1

100

ROUND RETURN, EXHAUST OR RELIEF AIR UP

RECTANGULAR RETURN, EXHAUST OR RELIEF AIR UP

RECTANGULAR SUPPLY OR OUTSIDE AIR DUCT UP

OVAL DUCT SIZE (WIDTH/HEIGHT)

ROUND DUCT SIZE (DIAMETER)

RECTANGULAR DUCT SIZE (WIDTHxHEIGHT)

SPACE/DUCT HUMIDITY SENSOR/TRANSMITTER

THERMOSTAT OR SPACE/DUCT TEMPERATURE SENSOR/TRANSMITTER

10x8

10Ø

UP

100

10Ø S-1

DN

10x8Ø

DIVISION 23 - HVAC

SYMBOLS LEGEND

GENERAL

(TYP)

(E)

PIPING LEGEND

DIVISION 23 - HVAC

GLOW PRESSURE NATURAL GAS

ABBREVIATIONS

BELOW FINISHED FLOORBFF

AFF ABOVE FINISHED FLOOR

GENERAL

IE INVERT ELEVATION

EXISTING

NIC NOT IN CONTRACT

TYPICAL

OUTSIDE AIR

EXHAUST AIR

SUPPLY AIR

RETURN AIR

FAN COIL UNIT

MANUAL VOLUME DAMPER

EXHAUST FAN

CONDENSING UNITCU

VD

OA

EA

RA

SA

EF

FCU

F FURNACE

DIVISION 23 - HVAC

1

G-000

1

G-000

FD FIRE DAMPER

FSD FIRE/SMOKE DAMPER

VAV-1

1.0

VARIABLE AIR VOLUME BOX TAG

TAG

GPM

PIPING

CONCENTRIC REDUCER

2#G2 PSI NATURAL GAS

PART 1 - GENERAL

1.1 SUMMARY

A. THIS SECTION INCLUDES THE FOLLOWING:

1. PIPING MATERIALS AND INSTALLATION INSTRUCTIONS COMMON TO MOST PIPING SYSTEMS.

2. DIELECTRIC FITTINGS.

3. PLUMBING DEMOLITION.

1.2 SUBMITTALS

A. PRODUCT DATA: FOR THE FOLLOWING:

1. DIELECTRIC FITTINGS.

2. IN ADDITION TO ALL SUBMITTALS IDENTIFIED IN THE SPECIFICATION SECTIONS, SUBMITTALS SHALL BE PROVIDED UNDER THIS SECTION (220500) FOR ALL

PLUMBING FIXTURES AND EQUIPMENT SCHEDULED ON THE DRAWINGS OR IDENTIFIED IN KEYED NOTES.

1.3 QUALITY ASSURANCE

A. ELECTRICAL CHARACTERISTICS FOR PLUMBING EQUIPMENT: EQUIPMENT OF HIGHER ELECTRICAL CHARACTERISTICS THAN BASIS OF DESIGN MAY BE

FURNISHED PROVIDED SUCH PROPOSED EQUIPMENT IS APPROVED IN WRITING AND CONNECTING ELECTRICAL SERVICES, CIRCUIT BREAKERS, AND CONDUIT

SIZES ARE APPROPRIATELY MODIFIED AT NO COST TO THE OWNER. IF MINIMUM ENERGY RATINGS OR EFFICIENCIES ARE SPECIFIED, EQUIPMENT SHALL

COMPLY WITH REQUIREMENTS.

B. WHEN THE DRAWINGS AND/OR SPECIFICATIONS REFER TO ANY ITEM, ARTICLE, MATERIAL, METHOD, FABRICATION, ASSEMBLY OR CONSTRUCTION BY MEANS OF

ONE OR MORE MANUFACTURER'S TRADE NAME, CATALOG REFERENCE OR SIMILAR MEANS OF IDENTIFICATION OF MANUFACTURER, THE CONTRACTOR SHALL

FURNISH ONE OF THE MAKES SO IDENTIFIED WITHOUT SUBSTITUTION UNLESS OTHER MAKE OR MAKES HAVE BEEN APPROVED BY ADDENDUM TO THE

CONTRACT DOCUMENTS PRIOR TO THE RECEIPT OF BIDS. REQUESTS FOR THE APPROVAL OF ITEMS OF EQUAL QUALITY ARE REQUESTED TO BE MADE IN

WRITING TO THE ARCHITECT FIFTEEN (15) DAYS PRIOR TO THE DATE OF THE RECEIPT OF BIDS SO THAT A LIST OF ACCEPTABLE EQUAL QUALITY ITEMS CAN BE

MADE KNOWN TO ALL BIDDERS BY AN ADDENDUM. IF SUBSTITUTION FOR NAMED ITEMS, ARTICLES, MATERIALS, METHODS, FABRICATIONS, ASSEMBLY OR

CONSTRUCTION ARE APPROVED, THE CONTRACTOR ASSUMES ALL RESPONSIBILITY FOR COORDINATION AND PERFORMING THE RELATED CHANGES IN THE

WORK NECESSITATED BY SUCH SUBSTITUTIONS AND SHALL INCLUDE IN THE BID ALL COSTS INVOLVED THEREIN.

C. THE ENTIRE COST OF ALL CHANGES OF ANY TYPE DUE TO SUBSTITUTIONS FOR MATERIALS SPECIFIED SHALL BE BORNE BY THE CONTRACTOR AT NO EXTRA

COST TO THE OWNER.

D. UNSOLICITED AND VOLUNTARY DEDUCTS, ON THE PART OF THE CONTRACTOR FOR SUBSTITUTING UNAPPROVED EQUIPMENT, SHALL NOT BE CONSIDERED FOR

THE PURPOSE OF AWARDING THE CONTRACT.

E. THE ARCHITECT SHALL BE THE SOLE AND FINAL JUDGE AS TO THE SUITABILITY OF ITEMS SUBSTITUTED FOR THOSE SPECIFIED.

F. WHEN THE DRAWINGS SCHEDULE A MANUFACTURER AS THE BASIS OF DESIGN, THE CONTRACTOR ASSUMES ALL RESPONSIBILITY FOR COORDINATION AND

PERFORMING THE RELATED CHANGES IN THE WORK NECESSITATED BY UTILIZING ANOTHER MANUFACTURER LISTED AS ACCEPTABLE IN THE SPECIFICATIONS.

THE ENTIRE COST OF ALL ASSOCIATED CHANGES OF ANY TYPE SHALL BE BORNE BY THE CONTRACTOR AT NO EXTRA COST TO THE OWNER.

G. DRAWINGS AND SPECIFICATIONS SHALL BE TAKEN TOGETHER. PROVIDE WORK SPECIFIED AND NOT INDICATED, OR WORK INDICATED AND NOT SPECIFIED AS

THOUGH MENTIONED IN BOTH.

H. IN CASE OF DISCREPANCY BETWEEN DRAWINGS AND SPECIFICATIONS, OR WITHIN EITHER DOCUMENT, THE GREATER QUANTITY OF WORK AND / OR BETTER

QUALITY SHALL BE USED FOR ESTIMATING AND THE MATTER BROUGHT TO THE ARCHITECT'S ATTENTION FOR A WRITTEN DECISION.

1.4 COORDINATION

A. COORDINATION PROCESS BETWEEN TRADES:

1. KEEP INFORMED ABOUT THE WORK OF ALL OTHER TRADES ENGAGED IN THE PROJECT AND EXECUTE THE WORK IN SUCH A MANNER AS NOT TO DELAY OR

INTERFERE WITH THE PROGRESS OF OTHER CONTRACTORS. THIS CONTRACTOR SHALL SCHEDULE THE WORK SO THAT NO OTHER CONTRACTOR IS

DELAYED IN THE EXECUTION OF THE WORK. COMPLETE COOPERATION OF ALL TRADES IS EXPECTED. EMPLOY A COMPETENT FOREMAN ON JOB

THROUGHOUT THE ENTIRE PROJECT TO ENSURE THAT COORDINATION IS MAINTAINED.

2. SCHEDULE AND COORDINATE THE WORK OF THIS DIVISION WITH THE SCHEDULE OF THE CONTRACTOR TO PROGRESS THE WORK EXPEDITIOUSLY, AND TO

AVOID UNNECESSARY DELAYS.

3. EXAMINE FULLY THE DRAWINGS AND SPECIFICATIONS FOR OTHER CONTRACTORS FOR OTHER TRADES, AND COORDINATE THE INSTALLATION OF THIS WORK

WITH THE WORK OF THE OTHER CONTRACTORS. CONSULT AND COOPERATE WITH OTHER CONTRACTORS FOR DETERMINING SPACE REQUIREMENTS AND

FOR DETERMINING THAT ADEQUATE CLEARANCE IS ALLOWED WITH RESPECT TO THE EQUIPMENT, OTHER EQUIPMENT, AND THE BUILDING. THE OWNER'S

REPRESENTATIVE RESERVES THE RIGHT TO DETERMINE SPACE PRIORITY IN THE EVENT OF INTERFERENCE BETWEEN PIPING, CONDUIT, DUCTS, AND

EQUIPMENT OF THE VARIOUS CONTRACTORS.

4. CONFLICTS BETWEEN THE DRAWINGS AND THE SPECIFICATION SHALL BE CALLED TO THE ATTENTION OF THE OWNER'S REPRESENTATIVE AND ARCHITECT.

IF CLARIFICATION IS NOT ASKED FOR PRIOR TO THE TAKING OF BIDS, IT WILL BE ASSUMED THAT NONE IS REQUIRED AND THAT THE CONTRACTOR IS IN

AGREEMENT WITH THE DRAWINGS AND SPECIFICATIONS AS ISSUED. IF CLARIFICATION IS REQUIRED AFTER THE CONTRACT IS AWARDED, SUCH

CLARIFICATION WILL BE MADE BY THE ARCHITECT AND THEIR DECISION WILL BE FINAL.

5. COORDINATE THE INSTALLATION OF ALL SYSTEM COMPONENTS WITH ALL OTHER TRADES, INCLUDING STRUCTURAL COMPONENTS AND ELECTRICAL

TRADES. ALLOCATE SPACE IN THE DIFFERENT AREAS TO ALLOW FOR THE INSTALLATION OF DUCTWORK, PIPING, SPRINKLERS, WASTE AND VENTS, AND

MECHANICAL EQUIPMENT ABOVE CEILINGS AND IN EQUIPMENT SPACES. RECOMMEND REROUTING, RESIZING OR RELOCATION OF MECHANICAL

COMPONENTS, IF NECESSARY, SO ALL TRADES CAN INSTALL THEIR SYSTEMS IN THE SPACE ALLOTTED. ANY PROPOSED CHANGES FROM THE SYSTEMS

LAYOUT, ON THE DRAWINGS, SHALL BE DONE IN ACCORDANCE WITH THE DESIGN CRITERIA SPECIFIED IN THE APPLICABLE CODES AND SHALL BE SUBJECT

TO THE REVIEW AND ACCEPTANCE OF THE ARCHITECT.

6. THE FOLLOWING LIST, IN DESCENDING ORDER, IS THE PRECEDENCE ASSIGNED THE WORK ITEMS FOR SPACE PRIORITY. RECESSED LIGHT FIXTURES AND

SPACE FOR THEIR INSTALLATION HAS FIRST PRIORITY, FUTURE UTILITY SPACE HAS SECOND PRIORITY, ETC.

a. RECESSED LIGHT FIXTURES AND ACCESS ABOVE LIGHT FIXTURES REQUIRED FOR MAINTENANCE.

b. SPACE DESIGN FOR FUTURE UTILITY PLACEMENT.

c. GRAVITY FLOW PLUMBING WASTE AND ROOF DRAINAGE, AND ANY OTHER SYSTEM THAT RELIES ON GRAVITY FOR FLOW.

d. DUCTWORK AND APPURTENANCES.

e. CABLE TRAY.

f. ELECTRICAL CONDUIT OVER TWO INCHES IN DIAMETER.

g. PRESSURIZED DOMESTIC WATER PIPING AND HVAC PIPING.

h. PLUMBING VENTS.

7. AFTER AWARD OF THE CONTRACT, AND PRIOR TO START OF CONSTRUCTION, THE GENERAL CONTRACTOR SHALL SCHEDULE A MEETING WITH THE

CONTRACTOR AND ALL SUBCONTRACTORS RESPONSIBLE OF THE WORK ITEMS LISTED ABOVE. THE PURPOSE OF THE MEETING IS TO INTRODUCE THE

COORDINATION PROGRAM AND TO DETERMINE ITS IMPLEMENTATION IN RELATION TO THE PROGRESS SCHEDULE.

8. ALL CONTRACTORS AND SUBCONTRACTORS SHALL PARTICIPATE IN THE COORDINATION PROCESS. PARTICIPATION IS MANDATORY. IF A CONTRACTOR OR

SUBCONTRACTOR FAILS TO PARTICIPATE IN THE COORDINATION PROCESS, THE OWNER RESERVES THE RIGHT TO DO THE FOLLOWING:

a. STOP ANY AND ALL CONSTRUCTION PROGRESS PAYMENTS FOR ANY WORK PERFORMED BY THE CONTRACTOR. SUCH PAYMENTS WILL BE REINSTATED

ONLY AFTER THE CONTRACTOR OR SUBCONTRACTOR RESUMES PARTICIPATION IN THE COORDINATION PROCESS.

b. RELOCATE AND RESIZE CONTRACTOR'S WORK COMPONENTS AS NECESSARY TO ENSURE ALL COMPONENTS WILL BE INSTALLED AS INTENDED. IN THE

EVENT THE CONTRACTOR DID NOT PARTICIPATE IN THE COORDINATION PROCESS, THEY WILL NOT BE ENTITLED TO ANY CONTRACT COST INCREASES OR

TIME EXTENSIONS DUE TO OWNER INITIATED CHANGES IN THE WORK.

c. THE CONTRACTOR SHALL ALSO BE HELD RESPONSIBLE FOR ANY UNNECESSARY REWORK BY OTHER TRADE CONTRACTORS THAT IS ATTRIBUTABLE TO

THE FAILURE TO PARTICIPATE IN THE COORDINATION PROCESS.

d. THE CONTRACT DRAWINGS ARE SCHEMATIC IN NATURE AND DO NOT SHOW EVERY FITTING AND APPURTENANCE FOR EACH UTILITY BECAUSE OF THE

SCALE OF THE DRAWINGS. EACH CONTRACTOR IS EXPECTED TO HAVE INCLUDED IN THE BID SUFFICIENT FITTINGS, MATERIAL, AND LABOR TO ALLOW

FOR ADJUSTMENTS IN ROUTING OF UTILITIES MADE NECESSARY BY THE COORDINATION PROCESS. THE CONTRACTOR WILL NOT BE ALLOWED ANY

CONTRACT COST EXTRA OR TIME EXTENSION FOR CHANGES DICTATED BY THE COORDINATION PROCESS.

e. UTILITY INSTALLATION IN CONGESTED AREAS IS DEPENDENT ON THE SEQUENCE OF UTILITY INSTALLATION AS MUCH AS IT IS DEPENDENT ON THE

PHYSICAL SIZE OF THE UTILITIES. THE CONTRACTORS SHALL USE THE COORDINATION PROCESS TO PROPERLY SEQUENCE THE INSTALLATION OF

UTILITIES AS APPROPRIATE TO ENSURE THE ABOVE CEILING AND CONGESTED AREA UTILITY INSTALLATION IS SATISFACTORY.

PART 2 - PRODUCTS

2.1 JOINING MATERIALS

A. SOLDER FILLER METALS: ASTM B 32, LEAD-FREE ALLOYS. INCLUDE WATER-FLUSHABLE FLUX ACCORDING TO ASTM B 813.

2.2 DIELECTRIC FITTINGS

A. DESCRIPTION: COMBINATION FITTING OF COPPER ALLOY AND FERROUS MATERIALS WITH THREADED, SOLDER-JOINT, PLAIN, OR WELD-NECK END CONNECTIONS

THAT MATCH PIPING SYSTEM MATERIALS.

B. INSULATING MATERIAL: SUITABLE FOR SYSTEM FLUID, PRESSURE, AND TEMPERATURE.

C. DIELECTRIC UNIONS: FACTORY-FABRICATED, UNION ASSEMBLY, FOR 250-PSIG MINIMUM WORKING PRESSURE AT 180 DEG F.

D. DIELECTRIC NIPPLES: ELECTROPLATED STEEL NIPPLE WITH INERT AND NONCORROSIVE, THERMOPLASTIC LINING; PLAIN, THREADED, OR GROOVED ENDS; AND

300-PSIG MINIMUM WORKING PRESSURE AT 225 DEG F.

PART 3 - EXECUTION

3.1 PIPING SYSTEMS - COMMON REQUIREMENTS

A. DRAWING PLANS, SCHEMATICS, AND DIAGRAMS INDICATE GENERAL LOCATION AND ARRANGEMENT OF PIPING SYSTEMS. INDICATED LOCATIONS AND

ARRANGEMENTS WERE USED TO SIZE PIPE AND CALCULATE FRICTION LOSS, EXPANSION, PUMP SIZING, AND OTHER DESIGN CONSIDERATIONS. INSTALL PIPING

AS INDICATED UNLESS DEVIATIONS TO LAYOUT ARE APPROVED.

B. CONTRACTOR SHALL NOT CHANGE INDICATED SIZES WITHOUT WRITTEN APPROVAL OF ENGINEER. PROVIDE ALL NECESSARY OFFSETS AND CROSSOVERS,

WHETHER INDICATED ON THE DRAWINGS OR NOT.

C. DO NOT RUN PIPING THROUGH TRANSFORMER VAULTS AND OTHER ELECTRICAL OR ELECTRONIC EQUIPMENT SPACES AND ENCLOSURES.

D. INSTALL PIPING IN CONCEALED LOCATIONS, UNLESS OTHERWISE INDICATED AND EXCEPT IN EQUIPMENT ROOMS AND SERVICE AREAS.

E. INSTALL PIPING AT RIGHT ANGLES OR PARALLEL TO BUILDING WALLS. DIAGONAL RUNS ARE PROHIBITED UNLESS SPECIFICALLY INDICATED OTHERWISE.

F. INSTALL PIPING ABOVE ACCESSIBLE CEILINGS TO ALLOW SUFFICIENT SPACE FOR CEILING PANEL REMOVAL.

G. INSTALL PIPING TO PERMIT VALVE SERVICING.

H. INSTALL PIPING AT INDICATED SLOPES, OR PITCHED TO DRAIN WHERE SLOPES ARE NOT INDICATED.

I. INSTALL PIPING FREE OF SAGS AND BENDS.

J. INSTALL FITTINGS FOR CHANGES IN DIRECTION AND BRANCH CONNECTIONS.

K. INSTALL PIPING TO ALLOW APPLICATION OF INSULATION.

L. SELECT SYSTEM COMPONENTS WITH PRESSURE RATING EQUAL TO OR GREATER THAN SYSTEM OPERATING PRESSURE.

M. VERIFY FINAL EQUIPMENT LOCATIONS FOR ROUGHING-IN.

3.2 PIPING JOINT CONSTRUCTION

A. REAM ENDS OF PIPES AND TUBES AND REMOVE BURRS. BEVEL PLAIN ENDS OF STEEL PIPE.

B. REMOVE SCALE, SLAG, DIRT, AND DEBRIS FROM INSIDE AND OUTSIDE OF PIPE AND FITTINGS BEFORE ASSEMBLY.

C. SOLDERED JOINTS: APPLY ASTM B 813, WATER-FLUSHABLE FLUX, UNLESS OTHERWISE INDICATED, TO TUBE END. CONSTRUCT JOINTS ACCORDING TO

ASTM B 828 OR CDA'S "COPPER TUBE HANDBOOK," USING LEAD-FREE SOLDER ALLOY COMPLYING WITH ASTM B 32.

D. THREADED JOINTS: THREAD PIPE WITH TAPERED PIPE THREADS ACCORDING TO ASME B1.20.1. CUT THREADS FULL AND CLEAN USING SHARP DIES. REAM

THREADED PIPE ENDS TO REMOVE BURRS AND RESTORE FULL ID. JOIN PIPE FITTINGS AND VALVES AS FOLLOWS:

1. APPLY APPROPRIATE TAPE OR THREAD COMPOUND TO EXTERNAL PIPE THREADS UNLESS DRY SEAL THREADING IS SPECIFIED.

2. DAMAGED THREADS: DO NOT USE PIPE OR PIPE FITTINGS WITH THREADS THAT ARE CORRODED OR DAMAGED. DO NOT USE PIPE SECTIONS THAT HAVE

CRACKED OR OPEN WELDS.

E. MECHANICALLY FORMED, COPPER-TUBE-OUTLET JOINTS ARE NOT ALLOWED.

3.3 PIPING CONNECTIONS

A. MAKE CONNECTIONS ACCORDING TO THE FOLLOWING, UNLESS OTHERWISE INDICATED:

1. INSTALL UNIONS, IN PIPING NPS 2 AND SMALLER, AT FINAL CONNECTION TO EACH PIECE OF EQUIPMENT.

2. WET PIPING SYSTEMS:

a. NPS 2 AND SMALLER: INSTALL DIELECTRIC COUPLING AND NIPPLE FITTINGS TO CONNECT PIPING MATERIALS OF DISSIMILAR METALS.

b. BRONZE VALVES WILL NOT BE CONSIDERED SUFFICIENT AS A DIELECTRIC BREAK BETWEEN DISSIMILAR METALS.

END OF SECTION 220500

SECTION 220517 - SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING

PART 1 - GENERAL

1.1 SUMMARY

A. SECTION INCLUDES:

1. SLEEVES.

PART 2 - PRODUCTS

2.1 SLEEVES

A. GALVANIZED-STEEL-PIPE SLEEVES: ASTM A 53/A 53M, TYPE E, GRADE B, SCHEDULE 40, ZINC COATED, WITH PLAIN ENDS.

PART 3 - EXECUTION

3.1 SLEEVE INSTALLATION

A. INSTALL SLEEVES FOR PIPING PASSING THROUGH PENETRATIONS IN NEW AND EXISTING FLOORS, ROOFS, AND WALLS.

B. INSTALL SLEEVES IN CONCRETE FLOORS, CONCRETE ROOF SLABS, AND CONCRETE AND MASONRY WALLS AS NEW SLABS AND WALLS ARE CONSTRUCTED.

1. PERMANENT SLEEVES ARE NOT REQUIRED FOR HOLES FORMED BY CORE DRILL OR MOLDED-PE OR -PP SLEEVES,.

2. CUT SLEEVES TO LENGTH FOR MOUNTING FLUSH WITH BOTH SURFACES.

3. USING GROUT, SEAL THE SPACE OUTSIDE OF SLEEVES.

4. INSTALL SLEEVES THAT ARE LARGE ENOUGH TO PROVIDE 1/4-INCH ANNULAR CLEAR SPACE BETWEEN SLEEVE AND PIPE OR PIPE INSULATION.

5. SEAL ANNULAR SPACE BETWEEN SLEEVE AND PIPING OR PIPING INSULATION; USE JOINT SEALANTS APPROPRIATE FOR SIZE, DEPTH, AND LOCATION OF

JOINT.

C. SLEEVES ARE NOT REQUIRED FOR PIPES PASSING THROUGH INTERIOR GYPSUM BOARD OR METAL PARTITIONS; HOWEVER, ALL PENETRATIONS SHALL BE MADE

CLEAN AND NEAT.

1. OPENINGS SHALL BE LARGE ENOUGH TO PROVIDE 1/4-INCH ANNULAR CLEAR SPACE BETWEEN INTERIOR PARTITION AND PIPE OR PIPE INSULATION.

2. SEAL ANNULAR SPACE BETWEEN INTERIOR PARTITION AND PIPING OR PIPING INSULATION; USE JOINT SEALANTS APPROPRIATE FOR SIZE, DEPTH, AND

LOCATION OF JOINT.

D. FIRE-BARRIER PENETRATIONS: MAINTAIN INDICATED FIRE RATING OF WALLS, PARTITIONS, CEILINGS, AND FLOORS AT PIPE PENETRATIONS. SEAL PIPE

PENETRATIONS WITH FIRESTOP MATERIALS.

3.2 SLEEVE AND SLEEVE-SEAL SCHEDULE

A. USE SLEEVES AND SLEEVE SEALS FOR THE FOLLOWING PIPING-PENETRATION APPLICATIONS:

1. INTERIOR CONCRETE OR MASONRY WALLS:

a. PIPING, ALL SIZES: GALVANIZED-STEEL-PIPE SLEEVES.

END OF SECTION 220517

SECTION 220523 - GENERAL-DUTY VALVES FOR PLUMBING PIPING

PART 1 - GENERAL

1.1 SUMMARY

A. SECTION INCLUDES:

1. BRONZE BALL VALVES.

2. BRONZE LIFT CHECK VALVES.

3. BRONZE SWING CHECK VALVES.

1.2 ACTION SUBMITTALS

A. PRODUCT DATA: FOR EACH TYPE OF VALVE INDICATED.

PART 2 - PRODUCTS

2.1 GENERAL REQUIREMENTS FOR VALVES

A. VALVE PRESSURE AND TEMPERATURE RATINGS: NOT LESS THAN INDICATED AND AS REQUIRED FOR SYSTEM PRESSURES AND TEMPERATURES.

B. VALVE SIZES: SAME AS UPSTREAM PIPING UNLESS OTHERWISE INDICATED.

C. ALL VALVES IN INSULATED PIPING, NO EXCEPTIONS: WITH 2-INCH STEM EXTENSIONS AND THE FOLLOWING FEATURES:

1. BALL VALVES: WITH EXTENDED OPERATING HANDLE.

2.2 BRONZE BALL VALVES

A. TWO-PIECE, FULL-PORT, BRONZE BALL VALVES WITH BRONZE TRIM:

1. DESCRIPTION:

a. STANDARD: MSS SP-110.

b. SWP RATING: 150 PSIG.

c. CWP RATING: 600 PSIG.

d. BODY DESIGN: TWO PIECE.

e. BODY MATERIAL: BRONZE.

f. ENDS: THREADED OR SOLDERED.

g. SEATS: PTFE OR TFE.

h. STEM: BRONZE.

i. BALL: CHROME-PLATED BRASS.

j. PORT: FULL.

PART 3 - EXECUTION

3.1 VALVE INSTALLATION

A. INSTALL VALVES WITH UNIONS OR FLANGES AT EACH PIECE OF EQUIPMENT ARRANGED TO ALLOW SERVICE, MAINTENANCE, AND EQUIPMENT REMOVAL

WITHOUT SYSTEM SHUTDOWN.

B. FURNISH AND INSTALL VALVES IN PLUMBING SYSTEMS, WHETHER INDICATED ON THE PLANS OR NOT, FOR THE PURPOSE OF PROVIDING THE BALANCE AND

ISOLATION OF EQUIPMENT OR FIXTURES FOR INSPECTION, MAINTENANCE, AND REPAIR. INSTALL CHECK VALVES WHERE FLOW REVERSAL IS UNDESIRABLE, BUT

CAN BE EXPECTED TO OCCUR.

C. INSTALL VALVES TO ISOLATE INDIVIDUAL OR GROUPS OF FIXTURES OR EQUIPMENT ON BRANCH RUNOUTS FROM PIPING MAINS. THIS IS IN ADDITION TO VALVES

AT EACH FIXTURE OR EQUIPMENT ITEM.

D. INSTALL VALVE STOP AT THE BASE OF PIPE RISERS AND AT EACH FLOOR LEVEL OF THE DOMESTIC PLUMBING AND OTHER PIPING SYSTEMS.

E. LOCATE VALVES FOR EASY ACCESS AND PROVIDE SEPARATE SUPPORT WHERE NECESSARY.

F. INSTALL NPS 2 INCH AND SMALLER VALVES IN HORIZONTAL PIPING WITH STEM VERTICALLY DOWN OR HORIZONTALLY TO BE VISIBLE FROM FLOOR.

G. INSTALL VALVES IN POSITION TO ALLOW FULL STEM MOVEMENT.

3.2 GENERAL REQUIREMENTS FOR VALVE APPLICATIONS

A. IF VALVE APPLICATIONS ARE NOT INDICATED, USE THE FOLLOWING:

1. SHUTOFF SERVICE: BALL VALVES.

B. IF VALVES WITH SPECIFIED SWP CLASSES OR CWP RATINGS ARE NOT AVAILABLE, THE SAME TYPES OF VALVES WITH HIGHER SWP CLASSES OR CWP RATINGS

MAY BE SUBSTITUTED.

3.3 DOMESTIC, HOT- AND COLD-WATER VALVE SCHEDULE

A. PIPE NPS 2 AND SMALLER:

1. BALL VALVES: TWO PIECE, FULL PORT, BRONZE WITH BRONZE TRIM.

2. BRONZE SWING CHECK VALVES: CLASS 125, BRONZE DISC.

END OF SECTION 220523

SECTION 220529 - HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

PART 1 - GENERAL

A. SECTION INCLUDES:

1. METAL PIPE HANGERS AND SUPPORTS.

2. METAL FRAMING SYSTEMS.

3. FASTENER SYSTEMS.

PART 2 - PRODUCTS

2.1 METAL PIPE HANGERS AND SUPPORTS

A. GALVANIZED-STEEL PIPE HANGERS AND SUPPORTS:

1. DESCRIPTION: MSS SP-58, TYPES 1 THROUGH 58, FACTORY-FABRICATED COMPONENTS.

2. GALVANIZED METALLIC COATINGS: PREGALVANIZED OR HOT DIPPED.

3. NONMETALLIC COATINGS: PLASTIC COATING, JACKET, OR LINER.

4. HANGER RODS: CONTINUOUS-THREAD ROD, NUTS, AND WASHER MADE OF GALVANIZED STEEL.

B. COPPER PIPE HANGERS:

1. DESCRIPTION: MSS SP-58, TYPES 1 THROUGH 58, COPPER-COATED-STEEL, FACTORY-FABRICATED COMPONENTS.

2. HANGER RODS: CONTINUOUS-THREAD ROD, NUTS, AND WASHER MADE OF COPPER-COATED STEEL.

2.2 METAL FRAMING SYSTEMS

A. MFMA MANUFACTURER METAL FRAMING SYSTEMS:

1. DESCRIPTION: SHOP- OR FIELD-FABRICATED PIPE-SUPPORT ASSEMBLY FOR SUPPORTING MULTIPLE PARALLEL PIPES.

2. STANDARD: MFMA-4.

3. CHANNELS: CONTINUOUS SLOTTED STEEL CHANNEL WITH INTURNED LIPS.

4. CHANNEL NUTS: FORMED OR STAMPED STEEL NUTS OR OTHER DEVICES DESIGNED TO FIT INTO CHANNEL SLOT AND, WHEN TIGHTENED, PREVENT SLIPPING

ALONG CHANNEL.

5. HANGER RODS: CONTINUOUS-THREAD ROD, NUTS, AND WASHER MADE OF GALVANIZED STEEL.

6. METALLIC COATING: GALVANIZED.

PART 3 - EXECUTION

3.1 HANGER AND SUPPORT INSTALLATION

A. METAL PIPE-HANGER INSTALLATION: COMPLY WITH MSS SP-69 AND MSS SP-89. INSTALL HANGERS, SUPPORTS, CLAMPS, AND ATTACHMENTS AS REQUIRED TO

PROPERLY SUPPORT PIPING FROM THE BUILDING STRUCTURAL ELEMENTS SUCH AS ROOF JOISTS OR CONCRETE DECKS.

B. SUPPORTING PIPING FROM THE BUILDING ROOF DECK IS NOT PERMITTED.

C. FASTENER SYSTEM INSTALLATION:

1. DO NOT USE POWDER ACTUATED FASTENERS.

D. CHAIN, WIRE, STRAP, OR PERFORATED STRAP HANGERS WILL NOT BE PERMITTED.

E. CONTRACTOR SHALL SELECT THE SIZE OF HANGERS AND SUPPORTS TO EXACTLY FIT THE PIPE SIZE FOR BARE PIPING.

F. INSULATED PIPING:

1. CONTRACTOR SHALL SELECT THE SIZE OF HANGERS AND SUPPORTS TO EXACTLY FIT AROUND PIPING INSULATION WITH SADDLE OR SHIELD FOR INSULATED

PIPING. SWALLOWING THE PIPE HANGER WITH INSULATION WILL NOT BE PERMITTED..

2. INSTALL MSS SP-58, TYPE 40, PROTECTIVE SHIELDS ON INSULATED PIPING. SHIELDS SHALL SPAN AN ARC OF 180 DEGREES.

3. SHIELD DIMENSIONS FOR PIPE: NOT LESS THAN THE FOLLOWING:

a. NPS 1/4 TO NPS 3-1/2: 12 INCHES LONG AND 0.048 INCH THICK.

3.2 HANGER AND SUPPORT SCHEDULE

A. PIPING HANGERS AND SUPPORTS: UNLESS OTHERWISE INDICATED, INSTALL THE FOLLOWING TYPES:

1. VERTICAL PIPING: MSS TYPE 8 OR 42, CLAMPS.

2. INDIVIDUAL, STRAIGHT, HORIZONTAL PIPING RUNS 2-INCH AND SMALLER: MSS TYPE 10, ADJUSTABLE, SWIVEL RING BAND HANGERS.

3. INDIVIDUAL, STRAIGHT, HORIZONTAL PIPING RUNS 2-1/2 INCH AND LARGER: MSS TYPE 1, ADJUSTABLE, GALVANIZED STEEL CLEVIS HANGERS.

B. ROD DIAMETER MAY BE REDUCED ONE SIZE FOR DOUBLE-ROD HANGERS, TO A MINIMUM OF 3/8 INCH.

C. INSTALL HANGERS FOR COPPER TUBING WITH THE FOLLOWING MAXIMUM HORIZONTAL SPACING AND MINIMUM ROD DIAMETERS:

1. NPS 3/4 AND SMALLER: 60 INCHES WITH 3/8-INCH ROD.

D. INSTALL SUPPORTS FOR VERTICAL COPPER TUBING EVERY 10 FEET.

E. INSTALL HANGERS FOR CAST-IRON SOIL PIPING WITH THE FOLLOWING MAXIMUM HORIZONTAL SPACING AND MINIMUM ROD DIAMETERS:

1. NPS 1-1/2 AND NPS 2: 60 INCHES WITH 3/8-INCH ROD.

2. SPACING FOR 10-FOOT LENGTHS MAY BE INCREASED TO 10 FEET. SPACING FOR FITTINGS IS LIMITED TO 60 INCHES.

F. INSTALL SUPPORTS FOR VERTICAL CAST-IRON SOIL PIPING EVERY 15 FEET.

G. FOR CAST IRON SOIL PIPE, PROVIDE AT LEAST ONE HANGER ON EACH FULL LENGTH OF PIPE CLOSE TO THE HUB. PROVIDE AT LEAST ONE HANGER WITHIN 24

INCHES OF EACH FITTING, AND WHEREVER ELSE REQUIRED TO PREVENT SAGGING DUE TO LOAD. PROVIDE A HANGER AT UPPER ANGLE OF EACH DROP.

WHERE MULTIPLE FITTINGS ARE USED, HANGERS SHALL BE LOCATED NOT MORE THAN 4 FEET ON CENTER AND ADJACENT TO HUBS ON FITTING.

H. FOR CAST IRON NO-HUB SOIL PIPE, PROVIDE PIPE HANGERS ON BOTH SIDES OF THE STAINLESS STEEL COUPLING AT EACH JOINT. PROVIDE TWO HANGERS ON

EACH FULL LENGTH OF PIPE CLOSE TO THE JOINTS. PROVIDE ONE HANGER AT EACH COUPLING ON ALL FITTINGS. WHERE MULTIPLE FITTINGS ARE USED,

PROVIDE A 16-GAUGE, CONTINUOUS TROUGH WITH HANGERS TO SUPPORT THE TROUGH AT 4 FEET ON CENTER.

I. COMPLY WITH MSS SP-69 FOR PIPE-HANGER SELECTIONS AND APPLICATIONS THAT ARE NOT SPECIFIED.

J. USE HANGERS AND SUPPORTS WITH GALVANIZED METALLIC COATINGS FOR PIPING AND EQUIPMENT THAT WILL NOT HAVE FIELD-APPLIED FINISH.

K. USE NONMETALLIC COATINGS ON ATTACHMENTS FOR ELECTROLYTIC PROTECTION WHERE ATTACHMENTS ARE IN DIRECT CONTACT WITH COPPER TUBING.

L. USE GALVANIZED-STEEL PIPE HANGERS AND SUPPORTS, METAL TRAPEZE PIPE HANGERS, AND METAL FRAMING SYSTEMS AND ATTACHMENTS FOR GENERAL

SERVICE APPLICATIONS.

M. USE COPPER-PLATED PIPE HANGERS AND COPPER ATTACHMENTS FOR COPPER PIPING AND TUBING.

N. SADDLES AND SHIELDS: UNLESS OTHERWISE INDICATED AND EXCEPT AS SPECIFIED IN PIPING SYSTEM SECTIONS, INSTALL THE FOLLOWING TYPES:

1. PROTECTION SHIELDS (MSS TYPE 40): OF LENGTH RECOMMENDED IN WRITING BY MANUFACTURER TO PREVENT CRUSHING INSULATION.

O. COMPLY WITH MFMA-103 FOR METAL FRAMING SYSTEM SELECTIONS AND APPLICATIONS.

END OF SECTION 220529

SECTION 220553 - IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT

PART 1 - GENERAL

1.1 SUMMARY

A. SECTION INCLUDES:

1. PIPE LABELS.

PART 2 - PRODUCTS

2.1 PIPE LABELS

A. GENERAL REQUIREMENTS FOR MANUFACTURED PIPE LABELS: PREPRINTED, COLOR-CODED, WITH LETTERING INDICATING SERVICE, AND SHOWING FLOW

DIRECTION.

B. SELF-ADHESIVE PIPE LABELS: PRINTED PLASTIC WITH CONTACT-TYPE, PERMANENT-ADHESIVE BACKING.

C. PIPE LABEL CONTENTS: INCLUDE IDENTIFICATION OF PIPING SERVICE USING SAME DESIGNATIONS OR ABBREVIATIONS AS USED ON DRAWINGS, PIPE SIZE, AND

AN ARROW INDICATING FLOW DIRECTION.

1. FLOW-DIRECTION ARROWS: INTEGRAL WITH PIPING SYSTEM SERVICE LETTERING TO ACCOMMODATE BOTH DIRECTIONS, OR AS SEPARATE UNIT ON EACH

PIPE LABEL TO INDICATE FLOW DIRECTION.

2. LETTERING SIZE: AT LEAST 1-1/2 INCHES HIGH.

PART 3 - EXECUTION

3.1 PIPE LABEL INSTALLATION

A. LOCATE PIPE LABELS WHERE PIPING IS EXPOSED OR ABOVE ACCESSIBLE CEILINGS IN FINISHED SPACES; MACHINE ROOMS; ACCESSIBLE MAINTENANCE SPACES

SUCH AS SHAFTS, TUNNELS, AND PLENUMS; AND EXTERIOR EXPOSED LOCATIONS AS FOLLOWS:

1. NEAR EACH VALVE AND CONTROL DEVICE.

2. NEAR EACH BRANCH CONNECTION, EXCLUDING SHORT TAKEOFFS FOR FIXTURES AND TERMINAL UNITS. WHERE FLOW PATTERN IS NOT OBVIOUS, MARK

EACH PIPE AT BRANCH.

3. NEAR PENETRATIONS THROUGH WALLS, FLOORS, CEILINGS, AND INACCESSIBLE ENCLOSURES.

4. NEAR MAJOR EQUIPMENT ITEMS AND OTHER POINTS OF ORIGINATION AND TERMINATION.

5. SPACED AT MAXIMUM INTERVALS OF 50 FEET ALONG EACH RUN. REDUCE INTERVALS TO 25 FEET IN AREAS OF CONGESTED PIPING AND EQUIPMENT.

B. PIPE LABEL SCHEDULE:

1. DOMESTIC COLD WATER PIPING:

a. BACKGROUND COLOR: GREEN

b. LETTER COLOR: WHITE

c. LABEL: CW OR COLD WATER

2. DOMESTIC HOT WATER PIPING:

a. BACKGROUND COLOR: YELLOW

b. LETTER COLOR: BLACK

c. LABEL: HW OR HOT WATER

END OF SECTION 220553

SECTION 220719 - PLUMBING PIPING INSULATION

PART 1 - GENERAL

1.1 SUMMARY

A. SECTION INCLUDES INSULATING THE FOLLOWING PLUMBING PIPING SERVICES:

1. DOMESTIC COLD-WATER PIPING.

2. DOMESTIC HOT-WATER PIPING.

1.2 ACTION SUBMITTALS

A. PRODUCT DATA: FOR EACH TYPE OF PRODUCT INDICATED. INCLUDE THERMAL CONDUCTIVITY, WATER-VAPOR PERMEANCE THICKNESS, AND JACKETS (BOTH

FACTORY- AND FIELD-APPLIED, IF ANY).

1.3 QUALITY ASSURANCE

A. INSTALLER QUALIFICATIONS: SKILLED MECHANICS EMPLOYED BY A COMPANY ENGAGED IN THIS TYPE OF WORK AS THEIR PRIMARY BUSINESS FOR A MINIMUM

OF THREE YEARS.

PART 2 - PRODUCTS

2.1 INSULATION MATERIALS

A. MINERAL-FIBER, PREFORMED PIPE INSULATION:

1. PRODUCTS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE ONE OF THE FOLLOWING:

a. FIBREX INSULATIONS INC.; COREPLUS 1200.

b. JOHNS MANVILLE; MICRO-LOK.

c. KNAUF INSULATION; 1000-DEGREE PIPE INSULATION.

d. MANSON INSULATION INC.; ALLEY-K.

e. OWENS CORNING; FIBERGLAS PIPE INSULATION.

2. TYPE I, 850 DEG F MATERIALS: MINERAL OR GLASS FIBERS BONDED WITH A THERMOSETTING RESIN. COMPLY WITH ASTM C 547, TYPE I, GRADE A, WITH

FACTORY-APPLIED ASJ-SSL.

2.2 ADHESIVES, MASTICS, SEALANTS AND TAPES

A. MATERIALS SHALL BE COMPATIBLE WITH INSULATION MATERIALS, JACKETS, AND SUBSTRATES AND FOR BONDING INSULATION TO ITSELF AND TO SURFACES TO

BE INSULATED.

PART 3 - EXECUTION

3.1 PREPARATION

A. SURFACE PREPARATION: CLEAN AND DRY SURFACES TO RECEIVE INSULATION. REMOVE MATERIALS THAT WILL ADVERSELY AFFECT INSULATION APPLICATION.

3.2 GENERAL INSTALLATION REQUIREMENTS

A. INSTALL INSULATION MATERIALS, ACCESSORIES, AND FINISHES WITH SMOOTH, STRAIGHT, AND EVEN SURFACES; FREE OF VOIDS THROUGHOUT THE LENGTH OF

PIPING INCLUDING FITTINGS, VALVES, AND SPECIALTIES. THE APPEARANCE OF FINISHED WORK SHALL BE OF EQUAL IMPORTANCE AS ITS MECHANICAL

CORRECTNESS AND EFFICIENCY.

B. INSTALL INSULATION WITH LONGITUDINAL SEAMS AT TOP AND BOTTOM OF HORIZONTAL RUNS.

C. INSTALL MULTIPLE LAYERS OF INSULATION WITH LONGITUDINAL AND END SEAMS STAGGERED.

D. INSTALL INSULATION WITH TIGHT LONGITUDINAL SEAMS AND END JOINTS. BOND SEAMS AND JOINTS WITH ADHESIVE RECOMMENDED BY INSULATION MATERIAL

MANUFACTURER.

E. INSTALL INSULATION WITH LEAST NUMBER OF JOINTS PRACTICAL.

F. WHERE VAPOR BARRIER IS INDICATED, SEAL JOINTS, SEAMS, AND PENETRATIONS IN INSULATION AT HANGERS, SUPPORTS, ANCHORS, AND OTHER

PROJECTIONS WITH VAPOR-BARRIER MASTIC.

1. INSTALL INSULATION CONTINUOUSLY THROUGH HANGERS.

G. APPLY ADHESIVES, MASTICS, AND SEALANTS AT MANUFACTURER'S RECOMMENDED COVERAGE RATE AND WET AND DRY FILM THICKNESSES.

H. FINISH INSTALLATION WITH SYSTEMS AT OPERATING CONDITIONS. REPAIR JOINT SEPARATIONS AND CRACKING DUE TO THERMAL MOVEMENT.

3.3 PENETRATIONS

A. .

B. INSULATION INSTALLATION AT INTERIOR WALL AND PARTITION PENETRATIONS (THAT ARE NOT FIRE RATED): INSTALL INSULATION CONTINUOUSLY THROUGH

WALLS AND PARTITIONS.

C. INSULATION INSTALLATION AT FIRE-RATED WALL AND PARTITION PENETRATIONS:

1. PIPE: INSTALL INSULATION CONTINUOUSLY THROUGH PENETRATIONS OF FIRE-RATED WALLS AND PARTITIONS.

2. SEAL PENETRATIONS THROUGH FIRE-RATED ASSEMBLIES.

3.4 INDOOR PIPING INSULATION SCHEDULE

A. DOMESTIC COLD WATER:

1. NPS 1 AND SMALLER: INSULATION SHALL BE THE FOLLOWING:

a. MINERAL-FIBER, PREFORMED PIPE INSULATION, TYPE I: 1/2 INCH THICK.

B. DOMESTIC HOT AND RECIRCULATED HOT WATER:

1. ALL PIPE SIZES: INSULATION SHALL BE THE FOLLOWING:

a. MINERAL-FIBER, PREFORMED PIPE INSULATION, TYPE I: 1 INCH THICK.

END OF SECTION 220719

SECTION 221116 - DOMESTIC WATER PIPING

PART 1 - GENERAL

1.1 SUMMARY

A. SECTION INCLUDES:

1. ABOVEGROUND DOMESTIC WATER PIPES, TUBES, AND FITTINGS INSIDE BUILDINGS.

1.2 CLOSEOUT SUBMITTALS

A. SYSTEM PURGING AND DISINFECTING ACTIVITIES REPORT: FOR INCLUSION IN SEPARATE TEST REPORTS SECTION OF OPERATION AND MAINTENANCE MANUAL.

PART 2 - PRODUCTS

2.1 COPPER TUBE AND FITTINGS

A. HARD COPPER TUBE: ASTM B 88, TYPE L WATER TUBE, DRAWN TEMPER.

B. WROUGHT-COPPER, SOLDER-JOINT FITTINGS: ASME B16.22, WROUGHT-COPPER PRESSURE FITTINGS.

C. COPPER UNIONS:

1. MSS SP-123.

2. CAST-COPPER-ALLOY, HEXAGONAL-STOCK BODY.

3. BALL-AND-SOCKET, METAL-TO-METAL SEATING SURFACES.

4. SOLDER-JOINT OR THREADED ENDS.

PART 3 - EXECUTION

3.1 FIELD QUALITY CONTROL

A. PERFORM THE FOLLOWING TESTS AND INSPECTIONS:

1. PIPING INSPECTIONS:

a. DO NOT ENCLOSE, COVER, OR PUT PIPING INTO OPERATION UNTIL IT HAS BEEN INSPECTED AND APPROVED BY AUTHORITIES HAVING JURISDICTION.

2. PIPING TESTS:

a. CAP AND SUBJECT PIPING TO STATIC WATER PRESSURE OF 50 PSIG ABOVE OPERATING PRESSURE, WITHOUT EXCEEDING PRESSURE RATING OF PIPING

SYSTEM MATERIALS. ISOLATE TEST SOURCE AND ALLOW IT TO STAND FOR FOUR HOURS. LEAKS AND LOSS IN TEST PRESSURE CONSTITUTE DEFECTS

THAT MUST BE REPAIRED.

B. NOTIFY ARCHITECT AND OWNER NO FEWER THAN TWO (2) DAYS IN ADVANCE OF TESTING TO ALLOW FOR OBSERVATION OF TESTS.

C. PREPARE TEST AND INSPECTION REPORTS.

3.2 CLEANING

A. CLEAN AND DISINFECT POTABLE DOMESTIC WATER PIPING AS FOLLOWS:

1. PURGE NEW PIPING AND PARTS OF EXISTING PIPING THAT HAVE BEEN ALTERED, EXTENDED, OR REPAIRED BEFORE USING.

2. USE PURGING AND DISINFECTING PROCEDURES PRESCRIBED BY AUTHORITIES HAVING JURISDICTION; IF METHODS ARE NOT PRESCRIBED, USE

PROCEDURES DESCRIBED IN EITHER AWWA C651 OR AWWA C652 OR FOLLOW PROCEDURES DESCRIBED BELOW:

a. FLUSH PIPING SYSTEM WITH CLEAN, POTABLE WATER UNTIL DIRTY WATER DOES NOT APPEAR AT OUTLETS.

b. FILL AND ISOLATE SYSTEM ACCORDING TO EITHER OF THE FOLLOWING:

1) FILL SYSTEM OR PART THEREOF WITH WATER/CHLORINE SOLUTION WITH AT LEAST 50 PPM OF CHLORINE. ISOLATE WITH VALVES AND ALLOW TO

STAND FOR 24 HOURS.

2) FILL SYSTEM OR PART THEREOF WITH WATER/CHLORINE SOLUTION WITH AT LEAST 200 PPM OF CHLORINE. ISOLATE AND ALLOW TO STAND FOR

THREE HOURS.

c. FLUSH SYSTEM WITH CLEAN, POTABLE WATER UNTIL NO CHLORINE IS IN WATER COMING FROM SYSTEM AFTER THE STANDING TIME.

d. REPEAT PROCEDURES IF BIOLOGICAL EXAMINATION SHOWS CONTAMINATION.

e. SUBMIT WATER SAMPLES IN STERILE BOTTLES TO AUTHORITIES HAVING JURISDICTION.

B. PREPARE AND SUBMIT REPORTS OF PURGING AND DISINFECTING ACTIVITIES. INCLUDE COPIES OF WATER-SAMPLE APPROVALS FROM AUTHORITIES HAVING

JURISDICTION.

3.3 PIPING SCHEDULE

A. TRANSITION AND SPECIAL FITTINGS WITH PRESSURE RATINGS AT LEAST EQUAL TO PIPING RATING MAY BE USED IN APPLICATIONS BELOW UNLESS OTHERWISE

INDICATED.

B. ABOVEGROUND DOMESTIC WATER PIPING, NPS 2 AND SMALLER, SHALL BE THE FOLLOWING:

1. HARD COPPER TUBE, ASTM B 88, TYPE L; WROUGHT-COPPER, SOLDER-JOINT FITTINGS; AND SOLDERED JOINTS.

3.4 VALVE SCHEDULE

END OF SECTION 221116

SECTION 221316 - SANITARY WASTE AND VENT PIPING

1.1 SUMMARY

A. SECTION INCLUDES:

1. PIPE, TUBE, AND FITTINGS.

2. SPECIALTY PIPE FITTINGS.

PART 2 - PRODUCTS

2.1 PIPING MATERIALS

2.2 HUB-AND-SPIGOT, CAST-IRON SOIL PIPE AND FITTINGS

A. PIPE AND FITTINGS: ASTM A 74, SERVICE CLASS(ES).

1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCTS BY ONE OF THE FOLLOWING:

a. AB & I.

b. CHARLOTTE.

c. NEWAGE CASTING.

d. TYLER PIPE.

B. GASKETS: ASTM C 564, RUBBER.

2.3 HUBLESS, CAST-IRON SOIL PIPE AND FITTINGS

A. PIPE AND FITTINGS: ASTM A 888 AND CISPI 301.

1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCTS BY ONE OF THE FOLLOWING:

a. AB & I.

b. CHARLOTTE.

c. NEWAGE CASTING.

d. TYLER PIPE.

B. CISPI, HUBLESS-PIPING COUPLINGS:

1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCTS BY ONE OF THE FOLLOWING:

a. ANACO-HUSKY.

b. CHARLOTTE.

c. FERNCO INC.

d. MISSION RUBBER COMPANY; A DIVISION OF MCP INDUSTRIES, INC.

e. NEWAGE CASTING.

f. TYLER PIPE.

2. STANDARDS: ASTM C 1277 AND CISPI 310.

3. DESCRIPTION: STAINLESS-STEEL CORRUGATED SHIELD WITH STAINLESS-STEEL BANDS AND TIGHTENING DEVICES; AND ASTM C 564, RUBBER SLEEVE WITH

INTEGRAL, CENTER PIPE STOP.

2.4 PIPING INSTALLATION

A. INSTALL SOIL AND WASTE DRAINAGE AND VENT PIPING AT THE FOLLOWING MINIMUM SLOPES UNLESS OTHERWISE INDICATED:

1. BUILDING SANITARY DRAIN: 2 PERCENT DOWNWARD IN DIRECTION OF FLOW FOR PIPING NPS 3 AND SMALLER; 2 PERCENT DOWNWARD IN DIRECTION OF

FLOW FOR PIPING NPS 4 AND LARGER.

2. HORIZONTAL SANITARY DRAINAGE PIPING: 2 PERCENT DOWNWARD IN DIRECTION OF FLOW.

3. VENT PIPING: 1 PERCENT DOWN TOWARD VERTICAL FIXTURE VENT OR TOWARD VENT STACK.

B. PROHIBITED FITTINGS: NO DOUBLE HUB OR DOUBLE TEE BRANCH OR DOUBLE COMBINATION FITTINGS SHALL BE USED ON SOIL OR WASTE LINES. THE DRILLING

AND TAPPING OF BUILDING DRAINS, SOIL, WASTE, OR VENT PIPES AND THE USE OF SADDLE HUBS OR BANDS IS PROHIBITED. ANY FITTINGS OR CONNECTION

WHICH HAS AN ENLARGEMENT CHAMBER OR RECESS WITH A LEDGE, SHOULDER, OR REDUCTION OF THE PIPE AREA THAT OFFERS AN OBSTRUCTION TO THE

FLOW THROUGH THE DRAIN IS PROHIBITED.

2.5 FIELD QUALITY CONTROL

A. DURING INSTALLATION, NOTIFY AUTHORITIES HAVING JURISDICTION AT LEAST 24 HOURS BEFORE INSPECTION MUST BE MADE. PERFORM TESTS SPECIFIED

BELOW IN PRESENCE OF AUTHORITIES HAVING JURISDICTION.

1. ROUGHING-IN INSPECTION: ARRANGE FOR INSPECTION OF PIPING BEFORE CONCEALING OR CLOSING-IN AFTER ROUGHING-IN AND BEFORE SETTING

FIXTURES.

2. FINAL INSPECTION: ARRANGE FOR FINAL INSPECTION BY AUTHORITIES HAVING JURISDICTION TO OBSERVE TESTS SPECIFIED BELOW AND TO ENSURE

COMPLIANCE WITH REQUIREMENTS.

B. REINSPECTION: IF AUTHORITIES HAVING JURISDICTION FIND THAT PIPING WILL NOT PASS TEST OR INSPECTION, MAKE REQUIRED CORRECTIONS AND ARRANGE

FOR REINSPECTION.

C. REPORTS: PREPARE INSPECTION REPORTS AND HAVE THEM SIGNED BY AUTHORITIES HAVING JURISDICTION.

D. NOTIFY ARCHITECT AND OWNER NO FEWER THAN TWO (2) DAYS IN ADVANCE OF TESTING TO ALLOW FOR OBSERVATION OF TESTS.

E. TEST SANITARY DRAINAGE AND VENT PIPING ACCORDING TO PROCEDURES OF AUTHORITIES HAVING JURISDICTION OR, IN ABSENCE OF PUBLISHED

PROCEDURES, AS FOLLOWS:

1. TEST FOR LEAKS AND DEFECTS IN NEW PIPING AND PARTS OF EXISTING PIPING THAT HAVE BEEN ALTERED, EXTENDED, OR REPAIRED. IF TESTING IS

PERFORMED IN SEGMENTS, SUBMIT SEPARATE REPORT FOR EACH TEST, COMPLETE WITH DIAGRAM OF PORTION OF PIPING TESTED.

2. LEAVE UNCOVERED AND UNCONCEALED NEW, ALTERED, EXTENDED, OR REPLACED DRAINAGE AND VENT PIPING UNTIL IT HAS BEEN TESTED AND

APPROVED. EXPOSE WORK THAT WAS COVERED OR CONCEALED BEFORE IT WAS TESTED.

3. ROUGHING-IN PLUMBING TEST PROCEDURE: TEST DRAINAGE AND VENT PIPING EXCEPT OUTSIDE LEADERS ON COMPLETION OF ROUGHING-IN. CLOSE

OPENINGS IN PIPING SYSTEM AND FILL WITH WATER TO POINT OF OVERFLOW, BUT NOT LESS THAN 10-FOOT HEAD OF WATER. FROM 15 MINUTES BEFORE

INSPECTION STARTS TO COMPLETION OF INSPECTION, WATER LEVEL MUST NOT DROP. INSPECT JOINTS FOR LEAKS.

4. PREPARE REPORTS FOR TESTS AND REQUIRED CORRECTIVE ACTION.

2.6 PIPING SCHEDULE

A. ABOVEGROUND, SOIL, WASTE AND VENT PIPING ALL SIZES SHALL BE ANY OF THE FOLLOWING:

1. SERVICE CLASS, CAST-IRON SOIL PIPE AND FITTINGS; GASKETS; AND GASKETED JOINTS.

2. HUBLESS, CAST-IRON SOIL PIPE AND FITTINGS; CISPI HUBLESS-PIPING COUPLINGS; AND COUPLED JOINTS.

3. DISSIMILAR PIPE-MATERIAL COUPLINGS: SHIELDED, NONPRESSURE TRANSITION COUPLINGS.

B. UNDERGROUND, SOIL, WASTE, AND VENT PIPING ALL SIZES SHALL BE ANY OF THE FOLLOWING:

1. SERVICE CLASS, CAST-IRON SOIL PIPING; GASKETS; AND GASKETED JOINTS.

2. DISSIMILAR PIPE-MATERIAL COUPLINGS: UNSHIELDED, NONPRESSURE TRANSITION COUPLINGS.

END OF SECTION 221316

SECTION 230500 - COMMON WORK RESULTS FOR HVAC

PART 1 - GENERAL

1.1 SUMMARY

A. THIS SECTION INCLUDES THE FOLLOWING:

1. PIPING MATERIALS AND INSTALLATION INSTRUCTIONS COMMON TO MOST PIPING SYSTEMS.

2. HVAC DEMOLITION.

1.2 SUBMITTALS

A. PRODUCT DATA: FOR THE FOLLOWING:

1. IN ADDITION TO ALL SUBMITTALS IDENTIFIED IN THE SPECIFICATION SECTIONS, SUBMITTALS SHALL BE PROVIDED UNDER THIS SECTION (230500) FOR ALL

HVAC EQUIPMENT SCHEDULED ON THE DRAWINGS OR IDENTIFIED IN KEYED NOTES.

1.3 QUALITY ASSURANCE

A. SEE 220500.

1.4 COORDINATION

A. SEE 220500

PART 2 - PRODUCTS

2.1 NOT USED.

PART 3 - EXECUTION

3.1 HVAC DEMOLITION

A. DISCONNECT, DEMOLISH, AND REMOVE HVAC SYSTEMS, EQUIPMENT, AND COMPONENTS INDICATED TO BE REMOVED.

1. DUCTS TO BE REMOVED: REMOVE PORTION OF DUCTS INDICATED TO BE REMOVED.

B. IF PIPE, INSULATION, OR EQUIPMENT TO REMAIN IS DAMAGED IN APPEARANCE OR IS UNSERVICEABLE, AS PART OF THE CONSTRUCTION PROCESS, REMOVE

DAMAGED OR UNSERVICEABLE PORTIONS AND REPLACE WITH NEW PRODUCTS OF EQUAL CAPACITY AND QUALITY.

END OF SECTION 230500

SECTION 230553 - IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT

PART 1 - GENERAL

1.1 SUMMARY

A. SECTION INCLUDES:

1. DUCT LABELS.

PART 2 - PRODUCTS

2.1 DUCT LABELS

A. SELF-ADHESIVE DUCT LABELS: PRINTED PLASTIC WITH CONTACT TYPE, PERMANENT ADHESIVE BACKING.

B. ADHESIVE: CONTACT-TYPE PERMANENT ADHESIVE, COMPATIBLE WITH LABEL AND WITH SUBSTRATE.

C. DUCT LABEL CONTENTS: INCLUDE IDENTIFICATION OF DUCT SERVICE USING SAME DESIGNATIONS OR ABBREVIATIONS AS USED ON DRAWINGS, DUCT SIZE, AND

AN ARROW INDICATING FLOW DIRECTION.

1. FLOW-DIRECTION ARROWS: INTEGRAL WITH DUCT SYSTEM SERVICE LETTERING TO ACCOMMODATE BOTH DIRECTIONS, OR AS SEPARATE UNIT ON EACH

DUCT LABEL TO INDICATE FLOW DIRECTION.

2. LETTERING SIZE: AT LEAST 1-1/2 INCHES HIGH.

PART 3 - EXECUTION

3.1 DUCT LABEL INSTALLATION

A. INSTALL SELF-ADHESIVE DUCT LABELS WITH PERMANENT ADHESIVE ON AIR DUCTS PER THE FOLLOWING:

1. SUPPLY AIR DUCTS (COOLING/HEATING):

a. BACKGROUND COLOR: BLUE

b. LETTER COLOR: WHITE

c. LABEL: SUPPLY AIR

2. RETURN AIR DUCTS:

a. BACKGROUND COLOR: GREEN

b. LETTER COLOR: WHITE

c. LABEL: RETURN AIR

B. LOCATE LABELS NEAR POINTS WHERE DUCTS ENTER INTO CONCEALED SPACES AND AT MAXIMUM INTERVALS OF 50 FEET IN EACH SPACE WHERE DUCTS ARE

EXPOSED OR 25 FEET IN AREAS WHERE CONCEALED BY REMOVABLE CEILING SYSTEM.

END OF SECTION 230553

SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC

PART 1 - GENERAL

1.1 SUMMARY

A. SECTION INCLUDES:

1. BALANCING AIR SYSTEMS.

1.2 INFORMATIONAL SUBMITTALS

A. CERTIFIED TAB REPORTS AND INSTRUMENT CALIBRATION REPORTS.

1.3 QUALITY ASSURANCE

A. TAB CONTRACTOR QUALIFICATIONS: ENGAGE A TAB ENTITY CERTIFIED BY NEBB OR TABB.

1. TAB FIELD SUPERVISOR: EMPLOYEE OF THE TAB CONTRACTOR AND CERTIFIED BY NEBB OR TABB.

2. TAB TECHNICIAN: EMPLOYEE OF THE TAB CONTRACTOR AND WHO IS CERTIFIED BY AABC NEBB OR TABB AS A TAB TECHNICIAN.

PART 2 - PRODUCTS (NOT APPLICABLE)

PART 3 - EXECUTION

3.1 GENERAL PROCEDURES FOR TESTING AND BALANCING

A. PERFORM TESTING AND BALANCING PROCEDURES ON EACH SYSTEM ACCORDING TO THE PROCEDURES CONTAINED IN ASHRAE 111, NEBB'S "PROCEDURAL

STANDARDS FOR TESTING, ADJUSTING, AND BALANCING OF ENVIRONMENTAL SYSTEMS," OR SMACNA'S "HVAC SYSTEMS - TESTING, ADJUSTING, AND

BALANCING" AND IN THIS SECTION.

B. MARK EQUIPMENT AND BALANCING DEVICES, INCLUDING DAMPER-CONTROL POSITIONS, VALVE POSITION INDICATORS, FAN-SPEED-CONTROL LEVERS, AND

SIMILAR CONTROLS AND DEVICES, WITH PAINT OR OTHER SUITABLE, PERMANENT IDENTIFICATION MATERIAL TO SHOW FINAL SETTINGS.

3.2 TOLERANCES

A. SET HVAC SYSTEM'S AIR FLOW RATES AND WATER FLOW RATES WITHIN PLUS OR MINUS 10 PERCENT.

3.3 FINAL REPORT

A. GENERAL: PREPARE A CERTIFIED WRITTEN REPORT; TABULATE AND DIVIDE THE REPORT INTO SEPARATE SECTIONS FOR TESTED SYSTEMS AND BALANCED

SYSTEMS.

1. INCLUDE A CERTIFICATION SHEET AT THE FRONT OF THE REPORT'S BINDER, SIGNED AND SEALED BY THE CERTIFIED TESTING AND BALANCING ENGINEER.

2. INCLUDE A LIST OF INSTRUMENTS USED FOR PROCEDURES, ALONG WITH PROOF OF CALIBRATION.

3.4 ADDITIONAL TESTS

A. WITHIN 90 DAYS OF COMPLETING TAB, PERFORM ADDITIONAL TAB TO VERIFY THAT BALANCED CONDITIONS ARE BEING MAINTAINED THROUGHOUT AND TO

CORRECT UNUSUAL CONDITIONS.

B. SEASONAL PERIODS: IF INITIAL TAB PROCEDURES WERE NOT PERFORMED DURING NEAR-PEAK SUMMER AND WINTER CONDITIONS, PERFORM ADDITIONAL TAB

DURING NEAR-PEAK SUMMER AND WINTER CONDITIONS.

END OF SECTION 230593

SECTION 230713 - DUCT INSULATION

PART 1 - GENERAL

1.1 SUMMARY

A. SECTION INCLUDES INSULATING THE FOLLOWING DUCT SERVICES:

1. INDOOR SUPPLYAIR.

1.2 ACTION SUBMITTALS

A. PRODUCT DATA: FOR EACH TYPE OF PRODUCT INDICATED. INCLUDE THERMAL CONDUCTIVITY, WATER-VAPOR PERMEANCE THICKNESS, AND JACKETS (BOTH

FACTORY- AND FIELD-APPLIED IF ANY).

1.3 QUALITY ASSURANCE

A. INSTALLER QUALIFICATIONS: SKILLED MECHANICS EMPLOYED BY A COMPANY ENGAGED IN THIS TYPE OF WORK AS THEIR PRIMARY BUSINESS FOR A MINIMUM

OF THREE YEARS.

PART 2 - PRODUCTS

2.1 INSULATION MATERIALS

A. MINERAL-FIBER BLANKET INSULATION: MINERAL OR GLASS FIBERS BONDED WITH A THERMOSETTING RESIN. COMPLY WITH ASTM C 553, TYPE II AND

ASTM C 1290, TYPE III WITH FACTORY-APPLIED FSK JACKET OR WHITE PSK JACKET WHERE INDICATED ON DRAWINGS.

PART 3 - EXECUTION

3.1 GENERAL INSTALLATION REQUIREMENTS

A. INSTALL INSULATION MATERIALS, ACCESSORIES, AND FINISHES WITH SMOOTH, STRAIGHT, AND EVEN SURFACES; FREE OF VOIDS THROUGHOUT THE LENGTH OF

DUCTS AND FITTINGS. THE APPEARANCE OF FINISHED WORK SHALL BE OF EQUAL IMPORTANCE AS ITS MECHANICAL CORRECTNESS AND EFFICIENCY.

B. ADHESIVES AND MASTICS SHALL BE COMPATIBLE WITH THE MATERIALS BEING INSTALLED AND SHALL BE INSTALLED PER MANUFACTURERS

RECOMMENDATIONS. A COMPLETE VAPOR BARRIER SHALL BE PROVIDED ON ALL BELOW AMBIENT SYSTEMS.

3.2 INSTALLATION OF MINERAL-FIBER INSULATION

A. BLANKET INSULATION INSTALLATION ON DUCTS AND PLENUMS: SECURE WITH INSULATION PINS.

1. INSTALL EITHER CAPACITOR-DISCHARGE-WELD PINS AND SPEED WASHERS OR CUPPED-HEAD, CAPACITOR-DISCHARGE-WELD PINS ON SIDES AND BOTTOM

OF HORIZONTAL DUCTS AND SIDES OF VERTICAL DUCTS AS FOLLOWS:

a. ON DUCT SIDES WITH DIMENSIONS 12 INCHES AND SMALLER, PINS ARE NOT REQUIRED.

b. ON DUCT SIDES WITH DIMENSIONS LARGER THAN 12 INCHES, PLACE PINS AT MAXIMUM 12 INCHES O.C. EACH WAY, AND 3 INCHES MAXIMUM FROM

INSULATION JOINTS. AT A MINIMUM, ALL DUCT SIDES OVER 12 INCHES SHALL BE PROVIDED WITH PINS ALONG LONGITUDINAL CENTERLINE OF DUCT.

INSTALL ADDITIONAL PINS TO HOLD INSULATION TIGHTLY AGAINST SURFACE AT CROSS BRACING.

c. PINS MAY BE OMITTED FROM TOP SURFACE OF HORIZONTAL, RECTANGULAR DUCTS AND PLENUMS.

3.3 INDOOR DUCT AND PLENUM INSULATION SCHEDULE

A. SUPPLY AIR DUCT INSULATION SHALL BE THE FOLLOWING:

1. MINERAL-FIBER BLANKET: 2 INCHES THICK AND 1.5-LB/CU. FT. NOMINAL DENSITY.

END OF SECTION 230713

SECTION 233113 - METAL DUCTS

PART 1 - GENERAL

1.1 SUMMARY

A. SECTION INCLUDES:

1. SINGLE-WALL RECTANGULAR DUCTS AND FITTINGS.

2. SINGLE-WALL ROUND DUCTS AND FITTINGS.

3. HIGH EFFICIENCY TAKEOFF.

6. SEALANTS AND GASKETS.

7. HANGERS AND SUPPORTS.

1.2 PERFORMANCE REQUIREMENTS

A. DELEGATED DUCT DESIGN: DUCT CONSTRUCTION, INCLUDING SHEET METAL THICKNESSES, SEAM AND JOINT CONSTRUCTION, REINFORCEMENTS, AND

HANGERS AND SUPPORTS, SHALL COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE" AND PERFORMANCE

REQUIREMENTS AND DESIGN CRITERIA INDICATED IN "DUCT SCHEDULE" ARTICLE.

PART 2 - PRODUCTS

2.1 SINGLE-WALL RECTANGULAR DUCTS AND FITTINGS

A. GENERAL FABRICATION REQUIREMENTS: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE" BASED ON INDICATED

STATIC-PRESSURE CLASS UNLESS OTHERWISE INDICATED.

2.2 SINGLE-WALL ROUND DUCTS AND FITTINGS

1. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCTS BY ONE OF THE FOLLOWING:

a. DUCTS ON DEMAND.

b. EASTERN SHEET METAL.

c. LAPINE METAL PRODUCTS.

d. LINDAB INC.

e. MCGILL AIRFLOW LLC.

f. NORLOCK.

g. SEMCO INCORPORATED.

h. SET DUCT MANUFACTURING.

i. SHEET METAL CONNECTORS, INC.

j. SPIRAL MANUFACTURING CO., INC.

k. SPIRAL PIPE OF TEXAS.

B. TRANSVERSE JOINTS, LONGITUDINAL SEAMS, TEES AND LATERALS: COMPLY WITH APPLICABLE FIGURES FROM SMACNA'S "HVAC DUCT CONSTRUCTION

STANDARDS - METAL AND FLEXIBLE,"

C. FABRICATE ROUND DUCTS LARGER THAN 12 INCHES IN DIAMETER WITH SPIRAL SEAM.

2.3 HIGH EFFICIENCY TAKEOFF

A. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCTS BY ONE OF THE FOLLOWING:

1. DUCTMATE INDUSTRIES.

2. ELGIN MANUFACTURING.

3. SHEET METAL CONNECTORS, INC.

B. SOLID BODY, GALVANIZED STEEL. DAMPERS SHALL BE QUADRANT LOCKING HARDWARE WITH 1-1/2 INCH INSULATION STANDOFF.

2.4 SHEET METAL MATERIALS

A. GENERAL MATERIAL REQUIREMENTS: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE" FOR ACCEPTABLE MATERIALS,

MATERIAL THICKNESSES, AND DUCT CONSTRUCTION METHODS UNLESS OTHERWISE INDICATED. SHEET METAL MATERIALS SHALL BE FREE OF PITTING, SEAM

MARKS, ROLLER MARKS, STAINS, DISCOLORATIONS, AND OTHER IMPERFECTIONS.

B. GALVANIZED SHEET STEEL: COMPLY WITH ASTM A 653/A 653M.

1. GALVANIZED COATING DESIGNATION: G90.

2.5 DUCT LINER

A. POLYESTER DUCT LINER: DUCTMATE INDUSTRIES, “POLYARMOR.”

B. FLEXIBLE ELASTOMERIC DUCT LINER: ARMACELL AP COILFLEX ACOUSTIC DUCT LINER.

C. SHOP APPLICATION OF DUCT LINER: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE," FIGURE 7-11, "FLEXIBLE DUCT

LINER INSTALLATION."

2.6 SEALANT AND GASKETS

A. WATER-BASED AND SOLVENT-BASED JOINT AND SEAM SEALANT:

1. APPLICATION METHOD: BRUSH OR CAULK. WHEN CAULKING, BACK BRUSH SEALANT INTO JOINT.

2. SOLIDS CONTENT: MINIMUM 65 PERCENT.

3. SERVICE TEMPERATURE -25 F TO 160 F.

4. WATER RESISTANT.

5. MOLD AND MILDEW RESISTANT.

6. VOC: MAXIMUM 30 G/L (LESS WATER) FOR WATER BASED. MAXIMUM 80 G/L (LESS WATER FOR SOLVENT BASED.

7. MAXIMUM STATIC-PRESSURE CLASS: 15-INCH WG, POSITIVE AND NEGATIVE.

8. SERVICE: INDOOR OR OUTDOOR.

9. SUBSTRATE: COMPATIBLE WITH GALVANIZED SHEET STEEL (BOTH PVC COATED AND BARE), STAINLESS.

10. SEALANT SHALL BE RATED FOR ALL SMACNA HVAC PRESSURE CLASSES.

11. SURFACE BURNING CHARACTERISTICS: MAXIMUM FLAME SPREAD INDEX OF 25 AND MAXIMUM SMOKE DEVELOPED INDEX OF 50 WHEN TESTED ACCORDING

TO UL 181; CERTIFIED BY AND NRTL.

B. TDC/TDF AND APPLIED DUCT FLANGE GASKETS:

1. DOMESTICALLY MANUFACTURED.

2. 600% ELONGATION.

3. NON-OXIDIZING.

4. NON-SLUMPING / NON-SAGGING.

5. SOLID CONTENT 100%.

6. 5/8” X 3/16” MINIMUM.

7. GASKET SHALL BE RATED FOR ALL SMACNA HVAC PRESSURE CLASSES.

8. SURFACE BURNING CHARACTERISTICS: MAXIMUM FLAME SPREAD INDEX OF 25 AND MAXIMUM SMOKE DEVELOPED INDEX OF 50 WHEN TESTED ACCORDING

TO UL 723; CERTIFIED BY AND NRTL.

C. FLANGE GASKETS: BUTYL RUBBER, NEOPRENE, OR EPDM POLYMER WITH POLYISOBUTYLENE PLASTICIZER.

D. ROUND DUCT JOINT O-RING SEALS:

1. SEAL SHALL PROVIDE MAXIMUM LEAKAGE CLASS OF 3 CFM/100 SQ. FT. AT 1-INCH WG AND SHALL BE RATED FOR10-INCH WG STATIC-PRESSURE CLASS,

POSITIVE OR NEGATIVE.

2.7 HANGERS AND SUPPORTS

A. HANGER RODS FOR NONCORROSIVE ENVIRONMENTS: CADMIUM-PLATED STEEL RODS AND NUTS.

B. STEEL CABLES FOR GALVANIZED-STEEL DUCTS: GALVANIZED STEEL COMPLYING WITH ASTM A 603.

C. STEEL CABLE END CONNECTIONS: CADMIUM-PLATED STEEL ASSEMBLIES WITH BRACKETS, SWIVEL, AND BOLTS DESIGNED FOR DUCT HANGER SERVICE; WITH

AN AUTOMATIC-LOCKING AND CLAMPING DEVICE.

D. DUCT ATTACHMENTS: SHEET METAL SCREWS, BLIND RIVETS, OR SELF-TAPPING METAL SCREWS; COMPATIBLE WITH DUCT MATERIALS.

E. TRAPEZE AND RISER SUPPORTS:

1. SUPPORTS FOR GALVANIZED-STEEL DUCTS: GALVANIZED-STEEL SHAPES AND PLATES.

PART 3 - EXECUTION

3.1 HANGER AND SUPPORT INSTALLATION

A. COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE," CHAPTER 5, "HANGERS AND SUPPORTS."

B. WIRE DUCT HANGERS SHALL NOT BE USED.

3.2 PAINTING

A. PAINT INTERIOR OF METAL DUCTS THAT ARE VISIBLE THROUGH REGISTERS AND GRILLES AND THAT DO NOT HAVE DUCT LINER. APPLY ONE COAT OF FLAT,

BLACK, LATEX PAINT OVER A COMPATIBLE GALVANIZED-STEEL PRIMER.

3.3 DUCT SCHEDULE

A. FABRICATE DUCTS WITH GALVANIZED SHEET STEEL EXCEPT AS OTHERWISE INDICATED.

B. SUPPLY DUCTS:

1. PRESSURE CLASS: POSITIVE 2-INCH WG TO 4-INCH AS REQUIRED FOR APPLICATION.

2. MINIMUM SMACNA SEAL CLASS: A.

3. SMACNA LEAKAGE CLASS FOR RECTANGULAR: 6.

4. SMACNA LEAKAGE CLASS FOR ROUND AND FLAT OVAL: 3.

C. RETURN DUCTS:

1. PRESSURE CLASS: POSITIVE OR NEGATIVE 2-INCH WG.

2. MINIMUM SMACNA SEAL CLASS: A.

3. SMACNA LEAKAGE CLASS FOR RECTANGULAR: 6.

4. SMACNA LEAKAGE CLASS FOR ROUND AND FLAT OVAL: 3.

D. INTERMEDIATE REINFORCEMENT:

1. GALVANIZED-STEEL DUCTS: GALVANIZED STEEL.

E. LINER:

1. RETURN AIR DUCTS WHERE INDICATED ON PLANS: POLYESTER OR FLEXIBLE ELASTOMERIC, 1 INCH THICK.

2. TRANSFER DUCTS: POLYESTER OR FLEXIBLE ELASTOMERIC, 1 INCH THICK.

F. ELBOW CONFIGURATION:

1. RECTANGULAR DUCT: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE," FIGURE 4-2, "RECTANGULAR ELBOWS."

a. RADIUS TYPE RE 1 WITH MINIMUM 1.5 RADIUS-TO-DIAMETER RATIO.

b. RADIUS TYPE RE 3 WITH MINIMUM 1.0 RADIUS-TO-DIAMETER RATIO AND TWO VANES.

c. MITERED TYPE RE 2 WITH VANES COMPLYING WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE," FIGURE 4-3, "VANES

AND VANE RUNNERS," AND FIGURE 4-4, "VANE SUPPORT IN ELBOWS."

2. ROUND DUCT: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE," FIGURE 3-4, "ROUND DUCT ELBOWS."

a. MINIMUM RADIUS-TO-DIAMETER RATIO AND ELBOW SEGMENTS: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND

FLEXIBLE," TABLE 3-1, "MITERED ELBOWS." ELBOWS WITH LESS THAN 90-DEGREE CHANGE OF DIRECTION HAVE PROPORTIONATELY FEWER SEGMENTS.

1) RADIUS-TO DIAMETER RATIO: 1.5.

b. ROUND ELBOWS, 12 INCHES AND SMALLER IN DIAMETER: STAMPED OR PLEATED.

c. ROUND ELBOWS, 14 INCHES AND LARGER IN DIAMETER: STANDING SEAM OR WELDED.

G. BRANCH CONFIGURATION:

1. RECTANGULAR DUCT: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE," FIGURE 4-6, "BRANCH CONNECTION."

a. RECTANGULAR MAIN TO RECTANGULAR BRANCH: 45-DEGREE ENTRY.

b. RECTANGULAR MAIN TO ROUND BRANCH: HIGH EFFICIENCY TAKEOFF. IF A VOLUME CONTROL DAMPER IS REQUIRED AT THE BRANCH, PROVIDE A HIGH

EFFICIENCY TAKEOFF WITH INTEGRAL QUADRANT LOCKING DAMPER AND 1-1/2 INCH INSULATION STANDOFF.

2. ROUND: COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE," FIGURE 3-5, "90 DEGREE TEES AND LATERALS," AND

FIGURE 3-6, "CONICAL TEES." SADDLE TAPS ARE PERMITTED IN EXISTING DUCT.

a. VELOCITY 1000 FPM OR LOWER: 90-DEGREE TAP.

b. VELOCITY 1000 FPM OR HIGHER: 45-DEGREE LATERAL.

H. TRANSITION AND OFFSET CONFIGURATION:

1. RECTANGULAR DUCT; COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE," FIGURE 4-7, "OFFSETS AND

TRANSITIONS."

a. OFFSET TYPE 1: ANGLED, MAXIMUM 30 DEGREES.

b. OFFSET TYPE 2: ANGLED, MAXIMUM 30 DEGREES.

c. CONCENTRIC TRANSITION: 45 DEGREES MAXIMUM.

d. ECCENTRIC TRANSITION: 30 DEGREES MAXIMUM.

END OF SECTION 233113

SECTION 233300 - AIR DUCT ACCESSORIES

PART 1 - GENERAL

1.1 SUMMARY

A. SECTION INCLUDES:

1. MANUAL VOLUME DAMPERS.

2. FLANGE CONNECTORS.

3. FLEXIBLE CONNECTORS.

4. FLEXIBLE DUCTS.

5. DUCT ACCESSORY HARDWARE.

PART 2 - PRODUCTS

2.1 ASSEMBLY DESCRIPTION

A. COMPLY WITH NFPA 90A, "INSTALLATION OF AIR CONDITIONING AND VENTILATING SYSTEMS," AND WITH NFPA 90B, "INSTALLATION OF WARM AIR HEATING AND

AIR CONDITIONING SYSTEMS."

B. COMPLY WITH SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE" FOR ACCEPTABLE MATERIALS, MATERIAL THICKNESSES, AND DUCT

CONSTRUCTION METHODS UNLESS OTHERWISE INDICATED. SHEET METAL MATERIALS SHALL BE FREE OF PITTING, SEAM MARKS, ROLLER MARKS, STAINS,

DISCOLORATIONS, AND OTHER IMPERFECTIONS.

2.2 MATERIALS

A. GALVANIZED SHEET STEEL: COMPLY WITH ASTM A 653/A 653M.

1. GALVANIZED COATING DESIGNATION: G90.

B. REINFORCEMENT SHAPES AND PLATES: GALVANIZED-STEEL REINFORCEMENT WHERE INSTALLED ON GALVANIZED SHEET METAL DUCTS;

2.3 DAMPER MANUFACTURERS

A. MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCTS BY ONE OF THE FOLLOWING:

1. AIR BALANCE INC.; A DIVISION OF MESTEK, INC.

2. GREENHECK FAN CORPORATION.

3. NAILOR INDUSTRIES INC.

4. NCA MANUFACTURING, INC.

5. POTTORFF.

6. RUSKIN COMPANY.

2.4 MANUAL VOLUME DAMPERS

2.5 ROUND MANUAL VOLUME DAMPERS

A. STANDARD, STEEL, MANUAL VOLUME DAMPERS:

1. STANDARD LEAKAGE RATING, WITH LINKAGE OUTSIDE AIRSTREAM.

2. SUITABLE FOR HORIZONTAL OR VERTICAL APPLICATIONS.

3. FRAMES:

a. GALVANIZED OR STAINLESS-STEEL, 0.040-INCH MINIMUM THICKNESS, 6 INCHES DEEP.

b. FLANGELESS FRAMES FOR INSTALLING IN DUCTS.

4. BLADES:

a. MULTIPLE OR SINGLE BLADE.

b. GALVANIZED OR STAINLESS-STEEL, 0.040 INCH THICK.

5. BLADE AXLES: GALVANIZED STEEL OR STAINLESS STEEL.

6. BEARINGS:

a. OIL-IMPREGNATED BRONZE.

b. DAMPERS IN DUCTS WITH PRESSURE CLASSES OF 3-INCH WG OR LESS SHALL HAVE AXLES FULL LENGTH OF DAMPER BLADES AND BEARINGS AT BOTH

ENDS OF OPERATING SHAFT.

7. TIE BARS AND BRACKETS: GALVANIZED STEEL.

B. JACKSHAFT:

1. SIZE: 0.5-INCH DIAMETER.

2. MATERIAL: GALVANIZED-STEEL PIPE ROTATING WITHIN PIPE-BEARING ASSEMBLY MOUNTED ON SUPPORTS AT EACH MULLION AND AT EACH END OF

MULTIPLE-DAMPER ASSEMBLIES.

3. LENGTH AND NUMBER OF MOUNTINGS: AS REQUIRED TO CONNECT LINKAGE OF EACH DAMPER IN MULTIPLE-DAMPER ASSEMBLY.

C. DAMPER HARDWARE:

1. LOCKING HAND QUADRANT: ZINC-PLATED, DIE-CAST CORE WITH DIAL AND HANDLE MADE OF 3/32-INCH THICK ZINC-PLATED STEEL, AND LOCKING MEANS.

2. INCLUDE CENTER HOLE TO SUIT DAMPER OPERATING-ROD SIZE.

3. INCLUDE A MINIMUM OF 1-1/2 INCH STANDOFF FOR INSULATED DUCT MOUNTING.

2.6 FLEXIBLE CONNECTORS

A. MATERIALS: FLAME-RETARDANT OR NONCOMBUSTIBLE FABRICS.

B. COATINGS AND ADHESIVES: COMPLY WITH UL 181, CLASS 1.

C. METAL-EDGED CONNECTORS: FACTORY FABRICATED WITH A FABRIC STRIP 3-1/2 INCHES WIDE ATTACHED TO TWO STRIPS OF 2-3/4-INCH WIDE, 0.028-INCH THICK,

GALVANIZED SHEET STEEL OR 0.032-INCH THICK ALUMINUM SHEETS. PROVIDE METAL COMPATIBLE WITH CONNECTED DUCTS.

D. INDOOR SYSTEM, FLEXIBLE CONNECTOR FABRIC: GLASS FABRIC DOUBLE COATED WITH NEOPRENE.

2.7 FLEXIBLE DUCTS

A. INSULATED, FLEXIBLE DUCT: UL 181, CLASS 1, 2-PLY VINYL FILM SUPPORTED BY HELICALLY WOUND, SPRING-STEEL WIRE; FIBROUS-GLASS INSULATION;

POLYETHYLENE VAPOR-BARRIER FILM.

1. PRESSURE RATING: 10-INCH WG POSITIVE AND 1.0-INCH WG NEGATIVE.

2. MAXIMUM AIR VELOCITY: 4000 FPM.

3. TEMPERATURE RANGE: MINUS 10 TO PLUS 160 DEG F.

4. INSULATION R-VALUE: COMPLY WITH ASHRAE/IESNA 90.1.

B. FLEXIBLE DUCT CONNECTORS:

1. CLAMPS: STAINLESS-STEEL BAND WITH CADMIUM-PLATED HEX SCREW TO TIGHTEN BAND WITH A WORM-GEAR ACTION IN SIZES 3 THROUGH 18 INCHES, TO

SUIT DUCT SIZE.

2.8 DUCT ACCESSORY HARDWARE

A. ADHESIVES: HIGH STRENGTH, QUICK SETTING, NEOPRENE BASED, WATERPROOF, AND RESISTANT TO GASOLINE AND GREASE.

PART 3 - EXECUTION

3.1 INSTALLATION

A. INSTALL DUCT ACCESSORIES ACCORDING TO APPLICABLE DETAILS IN SMACNA'S "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE" FOR METAL

DUCTS.

B. INSTALL DUCT ACCESSORIES OF MATERIALS SUITED TO DUCT MATERIALS; USE GALVANIZED-STEEL ACCESSORIES IN GALVANIZED-STEEL, STAINLESS-STEEL

ACCESSORIES IN STAINLESS-STEEL DUCTS.

C. INSTALL DUCT ACCESS DOORS ON SIDES OF DUCTS TO ALLOW FOR INSPECTING, ADJUSTING, AND MAINTAINING ACCESSORIES AND EQUIPMENT AS REQUIRED.

D. INSTALL FLEXIBLE CONNECTORS TO CONNECT DUCTS TO EQUIPMENT.

E. CONNECT CEILING-MOUNTED SUPPLY DIFFUSERS TO DUCTS DIRECTLY OR WITH MAXIMUM 36-INCH LENGTHS OF FLEXIBLE DUCT CLAMPED IN PLACE. DO NOT

USE FLEXIBLE DUCTS TO CHANGE DIRECTION OR FOR CONNECTIONS TO EXHAUST OR RETURN REGISTERS OR GRILLES.

F. CONNECT FLEXIBLE DUCTS TO METAL DUCTS WITH STAINLESS STEEL BAND CLAMPS.

END OF SECTION 233300

PLUMBING

and HVAC

Cover Sheet

AUTHOR

CHECKED:

DAVIS DESIGN ALL RIGHTS RESERVED

SHEET TITLE

SHEET NUMBER

ID

ISSUE DATE:

DescriptionDate

Revisions:

15 E

ast M

ain, S

uite 201

Verm

illion S

D 57069

Phone 605-624-1081

Verm

illion

1221 N

S

treet, S

uite 600

Lincoln N

E 68508

Phone 402-476-9700

Fax 402-476-9722

Lincoln

M-001

07-16-2020

MA

BMS

M-001.dw

g

GENERAL NOTES

GENERAL NOTES

DIVISION 23 - HVAC

1.THE FOLLOWING NOTES APPLY TO ALL DRAWINGS AS APPLICABLE.

CONTRACTOR TO FIELD VERIFY ALL EXISTING CONDITIONS.

CONTRACTOR SHALL NOTIFY ARCHITECT/ENGINEER OF ANY

DISCREPANCIES OR CONFLICTS ENCOUNTERED ON THE PROJECT PRIOR

TO PROCEEDING WITH THE WORK.

ALL WORK SHALL CONFORM TO THE LOCALLY ADOPTED CODE AND/OR

CODE AMENDMENTS AND SHALL BE APPROVED BY THE LOCAL

AUTHORITY HAVING JURISDICTION.

ALL CONTRACTORS ARE RESPONSIBLE TO COORDINATE WITH ALL

OTHER TRADES. CHANGES REQUIRED DUE TO LACK OF COORDINATION

WILL BE AT THE CONTRACTORS EXPENSE.

DRAWINGS ARE DIAGRAMMATIC IN NATURE. CONTRACTOR IS

RESPONSIBLE FOR PROVIDING ALL COMPONENTS FITTINGS AND

EQUIPMENT REQUIRED TO INSTALL A COMPLETE AND FUNCTIONING

SYSTEM IN ACCORDANCE WITH THE DESIGN INTENT.

DO NOT SCALE FROM THESE DRAWINGS. REFER TO ARCHITECTURAL

AND STRUCTURAL DRAWINGS FOR DIMENSIONS.

THE LOCATIONS OF EXISTING COMPONENTS WERE OBTAINED FROM

EXISTING DRAWINGS AND FIELD INVESTIGATION. THE LOCATIONS OF THE

COMPONENTS ARE SHOWN FOR THE CONVENIENCE OF THE

CONTRACTOR, ACCURACY OF THE INFORMATION SHOWN IS NOT

GUARANTEED. THE CONTRACTOR IS RESPONSIBLE FOR THE

VERIFICATION OF ALL EXISTING CONDITIONS PRIOR TO SUBMITTING BIDS.

SITE VISITS SHALL BE FULLY COORDINATED WITH THE OWNER.

PROTECT EXISTING DATA CABLING, FURNITURE, CARPET AND OTHER

SYSTEMS AND APPURTENANCES FROM DAMAGE DURING THE COURSE

OF CONSTRUCTION. REPAIR OR REPLACE DAMAGED ITEMS AT NO COST

TO OWNER.

THE OWNER HAS THE RIGHT TO RETAIN ALL SALVAGEABLE MATERIAL.

ANY MATERIAL THE OWNER CHOOSES NOT TO ACCEPT SHALL BE

REMOVED FROM THE SITE AND PROPERLY DISPOSED OF BY THE

CONTRACTOR.

DEMOLITION THAT CREATES NOISE OR VIBRATION (CORE DRILLING,

CUTTING, ETC.) SHALL BE COORDINATED WITH THE OWNERS SCHEDULE

AND MAY TAKE PLACE ON NIGHTS OR WEEKENDS.

COORDINATE ALL SYSTEM SHUTDOWNS WITH THE OWNER, SHUTDOWNS

MAY REQUIRE NIGHT OR WEEKEND WORK.

COORDINATE ALL BELOW GRADE PIPING WITH FOOTINGS, COLUMNS AND

GRADE BEAMS, PROVIDE SLEEVES WHERE REQUIRED.

ABOVE CEILING INSPECTIONS WILL TAKE PLACE PRIOR TO PADDING OUT

EACH AREA, COORDINATE WITH ARCHITECT AND OWNER.

COORDINATE ALL HANGERS WITH INSTALLATION OF METAL BUILDING

SIMPLE SAVER INSULATION SYSTEM AND ITS VAPOR BARRIER.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

14.

1. THE FOLLOWING NOTES APPLY TO ALL DRAWINGS AS APPLICABLE.

PROVIDE TEMPORARY SPACERS BELOW PIPING TO RECEIVE INSULATION

OR COORDINATE WITH INSULATOR AND PROVIDE SUFFICIENT HANGER

ROD LENGTH TO ALLOW INSULATOR TO DROP HANGER FOR

INSTALLATION OF PIPE INSULATION WITHOUT CRUSHING. DO NOT

SWALLOW PIPE HANGERS IN INSULATION.

PROVIDE TEMPORARY SPACERS BELOW DUCTWORK SUPPORTED BY

TRAPEZE HANGERS TO RECEIVE INSULATION TO ALLOW FOR

INSTALLATION OF DUCT INSULATION WITHOUT CRUSHING. DO NOT

SWALLOW TRAPEZE DUCT HANGERS IN INSULATION.

UNLESS NOTED OTHERWISE, ALL DUCT DIMENSIONS CALLED OUT ARE

INTERIOR FREE AREA DIMENSIONS.

AT CONTRACTORS OPTION, EQUIVALENT ROUND DUCT DIMENSIONS MAY

BE UTILIZED IN LIEU OF RECTANGULAR DUCT DIMENSIONS IDENTIFIED ON

DRAWINGS. EQUIVALENT DIAMETER SHALL BE CALCULATED PER

SMACNA REQUIREMENTS FOR EQUAL FRICTION. UTILIZING EQUIVALENT

AREA IS NOT ACCEPTABLE. AS-BUILT DOCUMENTS SHALL BE UPDATED

ACCORDINGLY.

AT CONTRACTORS OPTION, TO COORDINATE WITH OTHER TRADES AND

BUILDING ELEMENTS, EQUIVALENT RECTANGULAR DUCT DIMENSIONS

MAY BE UTILIZED IN LIEU OF RECTANGULAR DUCT DIMENSIONS

IDENTIFIED ON DRAWINGS. EQUIVALENT SIZING SHALL HAVE EQUAL

FRICTION. DUCT ASPECT RATIO OF RESIZED DUCT SHALL NOT BE

GREATER THAN 3:1 WITHOUT ENGINEERS APPROVAL. UTILIZING

EQUIVALENT AREA IS NOT ACCEPTABLE. AS-BUILT DOCUMENTS SHALL

BE UPDATED ACCORDINGLY.

ALL ROUND DUCTWORK SERVING AIR TERMINALS SHALL BE CONNECTED

TO MAINS WITH A HIGH EFFICIENCY TAKEOFF INCLUDING DAMPER WITH

QUADRANT LOCK HANDLE AND INSULATION STANDOFF, SEE

SPECIFICATIONS.

DUCT BRANCH SIZES SHALL MATCH DIFFUSER NECK SIZES UNLESS

NOTED OTHERWISE.

BRONZE BALL VALVES WILL NOT BE ACCEPTED AS A SUFFICIENT

DIELECTRIC BREAK, SEE SPECIFICATIONS FOR DIELECTRIC FITTING

REQUIREMENTS.

NOT ALL PIPING COMPONENTS AND VALVES ARE SHOWN ON PLAN

DRAWINGS, REFERENCE DETAILS, PIPING SCHEMATICS AND

SPECIFICATIONS FOR PIPING VALVES AND COMPONENTS REQUIRED.

UNLESS NOTED OTHERWISE, EXISTING RTU SHALL BE PROVIDED WITH A

THERMOSTAT OR CONTROL SENSOR WHETHER INDICATED ON THE

PLANS OR NOT.

UNLESS NOTED OTHERWISE, ALL LOW VOLTAGE CONTROL WIRING

INTERCONNECTING MECHANICAL EQUIPMENT AND ANY ASSOCIATED

THERMOSTATS SHALL BE INSTALLED BY MECHANICAL CONTRACTOR.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

CLIENT INFORMATION

PROJECT INFORMATION

South Dakota

Army National

Guard

801 W National Guard Dr.

Sioux Falls, S.D 57104

CFMO# 466134

IFR

Remediation -

Foss Field

Armory

19-0102Job #

GENERAL NOTES

DIVISION 22 - PLUMBING

THE FOLLOWING NOTES APPLY TO ALL DRAWINGS AS APPLICABLE.

PROVIDE TEMPORARY SPACERS BELOW PIPING TO RECEIVE INSULATION

OR COORDINATE WITH INSULATOR AND PROVIDE SUFFICIENT HANGER

ROD LENGTH TO ALLOW INSULATOR TO DROP HANGER FOR

INSTALLATION OF PIPE INSULATION WITHOUT CRUSHING. DO NOT

SWALLOW PIPE HANGERS IN INSULATION.

BRONZE BALL VALVES WILL NOT BE ACCEPTED AS A SUFFICIENT

DIELECTRIC BREAK, SEE SPECIFICATIONS FOR DIELECTRIC FITTING

REQUIREMENTS.

NOT ALL PIPING COMPONENTS AND VALVES ARE SHOWN ON PLAN

DRAWINGS, REFERENCE DETAILS, PIPING SCHEMATICS AND

SPECIFICATIONS FOR PIPING VALVES AND COMPONENTS REQUIRED.

ALL INDIRECT WASTE DRAIN PIPING FROM KITCHEN EQUIPMENT SHALL

BE COPPER.

ALL FINAL EQUIPMENT CONNECTIONS TO KITCHEN EQUIPMENT SHALL BE

BY PLUMBING CONTRACTOR.

ALL PLUMBING PIPING IS MODELED WITH A LEVEL SLOPE FOR CLARITY.

CONTRACTOR IS RESPONSIBLE TO SET ELEVATIONS AND SLOPES OF

PIPING TO MEET CODE AND REQUIRED INVERT ELEVATIONS IN ADDITION

TO COORDINATING WITH STRUCTURE AND ALL OTHER TRADES.

1.

2.

3.

4.

5.

6.

7.

13.

15.

7/16/2020

Page 7: FOSS FIELD ARMORY · kop knock out panel l angle, length or long lab laboratory lag lagging lam laminate lau laundry ... all duct dimensions called out are interior free area dimensions

MECHANICAL

225

FOOD STORAGE

VESTIBULE

71

Classroom

224

Office

224D

Office

224C

Office

224B

Office

224A

Corridor

224-1

T

2"W

S-2

1/2"CW

1/2"HW

2"W

EXISTING HWH

IMB-1

T

IMB-1(REFRIGRTATOR)

1

1

2

10x8

6Ø S-1

100

8Ø S-1

150

8Ø S-1

150

8Ø S-1

150

8Ø S-1

150

8Ø S-1

150

8Ø S-1

150

8Ø S-1

150

8Ø S-1

150

8Ø S-1

175

10x10R-110x10 R-1

10x10 R-1

10x10 R-1

22x22 R-1

6Ø S-1

125

8x10

16x10

22x10

22x10

8Ø8Ø

VD

VD

VD

VD

VDVD

VDVD

22x10

VD

VD

8Ø 8Ø

8

Ø

3

VD

10x10 10x10

10x1010x10

2

10x8

10x8

10x8

1-1/2"V

9

P-101

1/2"CW

OFFICE

229

MECHANICAL

225

WOMENS LATRINE

227

MENS LATRINE

155

OFFICE

79

FOOD STORAGE

156

FOOD PREPERATION

157

SCULLERY

251

TRAINING

ROOM

233

STORAGE

232

STORAGE

231

TRAINING

ROOM

230

CORRIDOR

70

VESTIBULE

71

VESTIBULE

71

ASSEMBLY HALL

161

CORRIDOR

162

STORAGE

FLAMMABLE

MATERIALS

158

ASSEMBLY HALL

159B

ELECTRICAL ROOM

142

TELEPHONE ROOM

141

FURNANCE ROOM

140

CORRIDOR

139

JANITOR

143

TRAINING ROOM

144

ELECTRICAL

179

CORRIDOR

177

CORRIDOR

177A

VESTIBULE

178

TRAINING ROOM

182

Classroom

224

Office

224D

Office

224C

Office

224B

Office

224A

Corridor

224-1

T

2"W

S-2

1/2"CW

1/2"HW

2"W

EXISTING HWH

IMB-1

T

IMB-1(REFRIGRTATOR)

1

1

2

10x8

6Ø S-1

100

8Ø S-1

150

8Ø S-1

150

8Ø S-1

150

8Ø S-1

150

8Ø S-1

150

8Ø S-1

150

8Ø S-1

150

8Ø S-1

150

8Ø S-1

175

10x10R-1 10x10 R-1

10x10 R-110x10 R-1

22x22 R-1

6Ø S-1

125

8x10

16x10

22x10

22x10

8Ø 8Ø

8Ø8Ø

8Ø 8Ø

VD

VD

VD

VD

VD VD

VD VD

22x10

VD

VD

8Ø 8Ø

8

Ø

3

VD

10x10 10x10

10x1010x10

2

10x8

10x8

10x8

1-1/2"V

9

P-101

1/2"CW

S

1-1/2"W

1-1/2"V

CO

ABOVE

BACKSPLASH

SCALE:

2

NO SCALE

SINK ISOMETRIC

2"W

FD

1-1/2"V

1

W

A

2

W

L

W

30° MAX.

L

W

W

WW

1

A

L

2

W

W

L

30° MAX.

W

SCALE:

4

NO SCALE

OFFSET AND

TRANSITION DETAIL

OFFSET TYPE 1

(MITERED)

OFFSET TYPE 2

(MITERED)

CONCENTRIC TRANSITION

A (MAX.)=45° DIVERGING, 60° CONVERGING

ECCENTRIC TRANSITION

A (MAX.)=30°

CEILING

4"

ELEVATION

OPEN ON TOP

OPEN ON BACKSIDE

OPEN ON SIDE

ELEVATION

1.5D

3D

M

IN

.

AIR

F

LO

W

D

PLAN

4"

SEE PLANS FOR SIZE/TYPE

RETURN GRILLE

CEILING

3D MIN.

SCALE:

5

NO SCALE

SOUND TRAP

DETAIL AT GRILLE

NOTE:

SOUND TRAP TO HAVE SAME INSIDE NET DIMENSIONS AS

INDICATED FOR OPENING

SEE PLANS

SEE PLANS

1" ACOUSTICAL

DUCT LINER

(SEE SPECS)

3D

M

IN

.

AIR

F

LO

W

D

PLAN

SEE PLANS FOR SIZE/TYPE

RETURN GRILLE

1" ACOUSTICAL

DUCT LINER

(SEE SPECS)

1.5

D

3D MIN.

OPEN ON TOP

D

D

3D MIN

D

AIR

FL

OW

WALL

3D MIN

SCALE:

3

NO SCALE

SOUND TRAP

DETAIL AT WALL

NOTE:

SOUND TRAP TO HAVE SAME

INSIDE NET DIMENSIONS AS

INDICATED FOR OPENING.

SEAL AROUND

DUCT AT THE WALL

1" ACOUSTICAL

DUCT LINER

(SEE SPECS)

NOTE:

SOUND TRAP TO HAVE SAME

INSIDE NET DIMENSIONS AS

INDICATED FOR OPENING.

D

MIN

SUPPLY DUCT-SEE

PLANS FOR SIZES

DIFFUSER NECK

CEILING

SUPPLY DIFFUSER

Ø = X"

X +

1

"

1" MIN.

FLEXIBLE DUCTWORK

MAXIMUM LENGTH AS

DETERMINED IN

SPECIFICATIONS

REGAIN BOX TO BE CONSTRUCTED,

INSULATED AND SUPPORTED SEE

SPECIFICATIONS

X + 1"

SCALE:

7

NO SCALE

SUPPLY DIFFUSER/DUCT

CONNECTION DETAIL

DAMPER STANDOFF

DAMPER

QUADRANT

LOCK

SCALE:

6

NO SCALE

HIGH EFFICIENCY

TAKEOFF DETAIL

HANGERS FOR STACKED DUCTS

TRAPEZE HANGERS

12"MAX. SPACING

BAND

HANGER STRAP

SCREWS

1"MIN.

3"

ANGLES

NUTS

ROD

STRAP HANGERS

NOTES:

1. REINFORCEMENT MAY BE USED FOR ATTACHMENT IF IT QUALIFIES FOR BOTH DUTIES. DO NOT EXCEED

LOAD RATING FOR METHOD USED.

2. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION AND ALLOWABLE USES.

SLING, AVOID

DISRUPTION OF

INSULATION

PREFERRED

STRAP

ATTACHMENT

SIZE BOLT(S)

FOR LOAD

LOAD RATED

FASTENERS

HANGER

STRAP

BAND OF SAME SIZE

AS HANGER STRAP

HANGER RODS

OR STRAP

STRAP OR ANGLE

ROD

ALTERNATE

LOCATION

INSULATION SHALL

RUN CONTINUOUS

THRU HANGER

HANGER

CABLE

CABLE

CLAMP

CABLE, AVOID

DISRUPTION OF

INSULATION

SCALE:

8

NO SCALE

DUCT HANGER DETAIL

CONNECT NEW CW HERE

SCALE:

9

NO SCALE

EXISTING WATER HEATER

Plumbing and

HVAC Plan

AUTHOR

CHECKED:

DAVIS DESIGN ALL RIGHTS RESERVED

SHEET TITLE

SHEET NUMBER

ID

ISSUE DATE:

DescriptionDate

Revisions:

15 E

ast M

ain, S

uite 201

Verm

illion S

D 57069

Phone 605-624-1081

Verm

illion

1221 N

S

treet, S

uite 600

Lincoln N

E 68508

Phone 402-476-9700

Fax 402-476-9722

Lincoln

M-101

07-16-2020

MA

BMS

A-1

01

SCALE:

1

PLUMBING AND HVAC PLAN

1/4" = 1'-0"

CLIENT INFORMATION

PROJECT INFORMATION

South Dakota

Army National

Guard

801 W National Guard Dr.

Sioux Falls, S.D 57104

CFMO# SF466146

Convert IFR

to Classroom -

Foss Field

Armory

20-0067Job #

KEY PLAN

AREA OF WORK

1. SEE SHEET M-001 FOR GENERAL NOTES.

GENERAL HVAC NOTES

DEMOLITION KEYED NOTES

REMOVE EXISTING BMS SENSOR AND COORDINATE WITH NEW WORK.

REMOVE EXISTING 18x18 LINED SUPPLY AND RETURN AIR DUCT DROPS

AND ELBOWS FROM RTU. NEW UNLINED DUCTWORK TO BE PROVIDED

AS PART OF NEW WORK.

DO NOT TEAR UP FLOOR IN FORMER IFR SPACE, SINK WASTE MUST

RUN IN FURRED OUT WALL. REMOVE AND PATCH CONCRETE IN

MECHANICAL ROOM AS REQUIRED TO CONNECT TO EXISTING DRAIN.

HVAC PLAN KEYED NOTES

CONTROLS WORK SHALL BE BY BUILDING CONTROLS CONTRACTOR

CLIMATE SYSTEMS, INC. INSTALL RELOCATED/NEW SENSOR TO

OPERATE PACKAGED RTU. COORDINATE OCCUPIED/UNOCCUPIED

TIMES WITH OWNER DURING SETUP. ADD OUTSIDE AIR DAMPER

CONTROL SEQUENCE INCLUDING ECONOMIZER SEQUENCE. OUTSIDE

AIR SHALL CLOSE DURING UNOCCUPIED PERIODS.

INSTALL LENNOX MODEL 14D90 ECONOMIZER KIT WITH 53W64

ENTHALPY SENSOR ON EXISTING LENNOX KGA060 ROOFTOP UNIT.

BALANCE TO 400 CFM OUTSIDE AIR AT MINIMUM POSITION. PROVIDE

WITH BAROMETRIC RELIEF. INSTALL LENNOX MODEL 13R98 HAIL

GUARD ON EXISTING LENNOX ROOFTOP UNIT. COMB EXISTING COILS

PRIOR TO INSTALLATION OF HAIL GUARDS. BALANCE UNIT TO

AIRFLOWS INDICATED.

1

1

2

2

3

7/16/2020

Page 8: FOSS FIELD ARMORY · kop knock out panel l angle, length or long lab laboratory lag lagging lam laminate lau laundry ... all duct dimensions called out are interior free area dimensions

MECHANICAL

225

FOOD STORAGE

156

VESTIBULE

71

RIFLE RANGE

224

21

PANEL L2

72"x30" 72"x30"

72"x30" 72"x30"

72"x30" 72"x30"

72"x30" 72"x30"

72"x30" 72"x30"

72"x30" 72"x30"

72"x30" 72"x30"

MECHANICAL

225

FOOD STORAGE

156

VESTIBULE

71

Classroom

224

Office

224D

Office

224C

Office

224B

Office

224A

Corridor

224-1

A2 A2

A2 A2

A2 A2

A2 A2

A2 A2

A2 A2

A2

A2

A2

A2

A2

A2

A2

A2

A1

A1

A1

X1

X1

33

3

3

PANEL L2

C

O

C

O

C

O

C

O

C

O

C

O

C

O

C

O

PP

2

3

5

5

5

4

3

3

3

3

X1

MECHANICAL

225

WOMENS LATRINE

227

MENS LATRINE

155

OFFICE

79

FOOD STORAGE

156

FOOD PREPERATION

157

SCULLERY

251

STORAGE

232

CORRIDOR

70

VESTIBULE

71

VESTIBULE

71

ASSEMBLY HALL

161

CORRIDOR

162

STORAGE

FLAMMABLE

MATERIALS

158

ASSEMBLY HALL

159B

ELECTRICAL ROOM

142

TELEPHONE ROOM

141

FURNANCE ROOM

140

CORRIDOR

139

JANITOR

143

TRAINING ROOM

144

ELECTRICAL

179

CORRIDOR

177

CORRIDOR

177A

VESTIBULE

178

TRAINING ROOM

182

Classroom

224

Office

224D

Office

224C

Office

224B

Office

224A

Corridor

224-1

72"x30" 72"x30"

72"x30" 72"x30"

72"x30" 72"x30"

72"x30" 72"x30"

72"x30" 72"x30"

72"x30" 72"x30"

72"x30" 72"x30"

EXISTING PUNCH

DOWN BLOCKS

EXISTING DATA

RACK

PANEL L2

6

F

J J

F

44"

GFI

2

2

(2)(2)

44"

(2)

44"

2

2

2

2

2

22

(2)(2)

(2)

(2)

(2)

(2)

7

7

8

8

PANEL L5

(EXISTING)

PANEL E

(EXISTING)

MAIN

SWITCHBOARD

(EXISTING)

FA

FACP

EXISTING

EXISTING

EXISTING

10

10

F

10

9

10

(2)

44"

(2)

(2)

(2)

(2)

WAP

(1)

11

11

11

11

11

12

1

GFI

13

13

13

(2)

44"

(2)

(2)

(2)

Electrical

Plan-

Demolition

and New

AUTHOR

CHECKED:

DAVIS DESIGN ALL RIGHTS RESERVED

SHEET TITLE

SHEET NUMBER

ID

ISSUE DATE:

DescriptionDate

Revisions:

15 E

ast M

ain, S

uite 201

Verm

illion S

D 57069

Phone 605-624-1081

Verm

illion

1221 N

S

treet, S

uite 600

Lincoln N

E 68508

Phone 402-476-9700

Fax 402-476-9722

Lincoln

E-101

07-16-2020

TIG

JPD

CLIENT INFORMATION

PROJECT INFORMATION

South Dakota

Army National

Guard

801 W National Guard Dr.

Sioux Falls, S.D 57104

CFMO# SF466146

Convert IFR

to Classroom -

Foss Field

Armory

20-0067Job #

SCALE:

1

ELECTRICAL PLAN - DEMOLITION

1/8" = 1'-0"

SCALE:

2

LIGHTING PLAN - NEW

1/8" = 1'-0"

LIMIT OF CONSTRUCTION, COORDINATE ANY WORK EXTRA WORK WITH OWNER.

CONNECT TO A SPARE 20A/1 POLE CIRCUIT BREAKER IN PANEL L2.

PROVIDE AND INSTALL LINE VOLTAGE OCCUPANCY SENSOR BY GREENGATE MODEL

#OAC-DT-2000-MV OR EQUAL.

PROVIDE AND INSTALL SP15 HEAVY DUTY POWER PACK BY GREENGATE OR EQUAL.

PROVIDE AND INSTALL LOW VOLTAGE VACANCY CEILING SENSOR BY GREENGATE MODEL

#VAC-P-1500-R OR EQUAL. VACANCY SENSORS SHALL BE CONNECTED TO POWER PACK SHOWN ON

PLAN.

PROVIDE AND INSTALL NEW 110 PUNCH DOWN BLOCK IN TELEPHONE ROOM 141. SEE DETAIL ON E-502.

PROVIDE WALL MOUNTED HDMI CONNECTOR AND PROVIDE 50'-0" LONG HDMI CABLE AND ROUTE IN

1-1/4" CONDUIT FROM MONITOR LOCATION TO WORKSTATION, COIL EXTRA CABLE LENGTH AS

NEEDED. CONFIRM WITH OWNER FOR FINAL MOUNTING HEIGHT OF HDMI CONNECTOR FOR MONITOR.

CONFIRM HEIGHT FOR RECEPTACLE AT DATA JACK FOR MONITOR.

ELECTRICAL CONTRACTOR SHALL PROVIDE J-HOOK PATH FROM CLASSROOM TO TELEPHONE ROOM

141. PROPOSED ROUTE IS SHOWN ON PLAN. PATH IS SHOWN TO KEEP DATA CABLING RUN UNDER

300'-0". COORDINATE FINAL J-HOOK PATH TO ACCOMMODATE FOR CABLING LIMITATIONS.

FIRE ALARM DEVICE SHALL BE ROUTED BACK TO EXISTING FIRE-LITE FIRE ALARM CONTROL PANEL IN

ELECTRICAL ROOM 179. EXISTING FIRE ALARM SYSTEM IS A DIGITAL ADDRESSABLE FIRE ALARM

SYSTEM MODEL #MS-9200UDLS. VERIFY CAPACITY OF FIRE ALARM CONTROL PANEL AND PROVIDE

EXTENDER PANEL IF NEEDED.

PROVIDE AND INSTALL EZ PATH PASS THROUGH SERIES 33 FOR LOW VOLTAGE WIRE. SEAL AROUND

OUTER EDGES OF PATHWAYS. INSTALL AT A MINIMUM OF 6" ABOVE CEILING. SEE DETAIL ON SHEET

E-502.

EXISTING CONDUIT PENETRATION INTO TELEPHONE ROOM 141 SHALL BE USED.

NEW SMOKE DETECTOR SHALL BE INSTALLED AND CONNECTED TO THE EXISTING FIRE-LITE FIRE

ALARM SYSTEM. CONTRACTOR MAY TIE INTO NEAREST DETECTION DEVICE PROVIDED CIRCUIT WILL

SUPPORT THE ADDITIONAL DEVICE.

ELECTRICAL KEYED NOTES

SCALE:

3

POWER AND SYSTEMS - NEW

1/8" = 1'-0"

LIMIT OF CONSTRUCTION, COORDINATE ANY WORK EXTRA WORK WITH OWNER.

ELECTRICAL CONTRACTOR SHALL DISCONNECT AND REMOVE ALL ELECTRICAL LIGHT FIXTURES,

DEVICES AND ASSOCIATED CONDUIT AND CIRCUIT WIRING BACK TO SOURCE PANEL. INDOOR FIRING

RANGE HAS BEEN SHELLED OUT. A COUPLE OF LIGHT FIXTURES AND RECEPTACLES REMAIN IN THE

SPACE. ROUGH-IN BOXES THAT ARE SURFACE MOUNTED TO CMU SHALL BE REMOVED. ROUGH-IN

BOXES THAT ARE RECESSED WITH IN CMU SHALL HAVE A BLANK COVER PLATE INSTALLED AND

STUB-UP ABANDONED UNLESS AT A LOCATION THAT CAN BE RE-USED AS SHOWN ON NEW POWER

PLAN. ANY ELECTRICAL POWER TO MECHANICAL EQUIPMENT THAT IS NOT DESIGNATED TO BE

REMOVED ON MECHANICAL DRAWINGS SHALL REMAIN. COORDINATE WITH MECHANICAL DRAWINGS

FOR EXISTING EQUIPMENT.

DEMOLITION KEYED NOTES

1

2

1

2

3

4

5

6

1. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE, STATE AND

ALL LOCAL CODES.

2. SEE ARCHITECTURAL SERIES SHEET FOR EXACT AREAS AND WALLS AFFECTED BY THE

DEMOLITION AND REMODEL.

3. DEMOLITION SHOWN IS AS REQUIRED FOR THE COMPLETE PROJECT. THE CONTRACTOR SHALL

COORDINATE THE DEMOLITION EFFORT WITH THE WORK OF OTHER TRADES. PROVIDE TEMPORARY

POWER AND LIGHTS AS REQUIRED TO ALLOW THE WORK OF OTHER TRADES TO PROCEED OR AS

REQUIRED TO ALLOW THE OWNER TO OCCUPY THE SPACE.

4. ALL OF THE EQUIPMENT AND DEVICES SHOWN ON THIS DRAWING ARE EXISTING. THE LOCATIONS

OF THE EQUIPMENT AND DEVICES WERE OBTAINED FROM EXISTING DRAWINGS AND FIELD

INVESTIGATION. THE LOCATIONS OF THE EXISTING EQUIPMENT AND DEVICES ARE SHOWN FOR THE

CONVENIENCE OF THE CONTRACTOR. ACCURACY OF THE INFORMATION SHOWN IS NOT

GUARANTEED. THE CONTRACTOR IS RESPONSIBLE FOR THE VERIFICATION OF ALL EXISTING

CONDITIONS PRIOR TO SUBMITTING BIDS. SITE VISITS PRIOR TO SUBMISSION OF BIDS NEED TO BE

FULLY COORDINATED WITH THE OWNER.

5. ACTUAL CIRCUITING IS NOT SHOWN. CIRCUIT INFORMATION FOR ALL AFFECTED CIRCUITS SHALL BE

VERIFIED PRIOR TO COMMENCING WORK. ACCURACY OF THE INFORMATION SHOWN AND INCLUDED

ON THE PANEL SCHEDULES IS NOT GUARANTEED.

6. FIXTURES AND DEVICES INDICATED TO BE REMOVED, WHICH ARE LOCATED ON CEILINGS OR WALLS

ALSO INDICATED TO BE REMOVED, SHALL HAVE FIXTURES, DEVICE AND ALL ASSOCIATED CIRCUIT

WIRING,CONDUIT, AND RACEWAYS REMOVED BACK TO NEAREST JUNCTION BOX, OR DEVICE NOT

INDICATED TO BE REMOVED. THE CONTRACTOR SHALL PROVIDE ALL NECESSARY WIRE, CONDUIT,

DEVICES AND CONNECTIONS NECESSARY TO ENSURE CIRCUIT CONTINUITY OF THE REMAINING

DEVICES.

7. FIXTURES AND DEVICES INDICATED TO BE REMOVED, WHICH ARE LOCATED ON CEILINGS OR WALLS

NOT INDICATED TO BE REMOVED, SHALL HAVE FIXTURES, DEVICE AND ALL ASSOCIATED CIRCUIT

WIRING REMOVED BACK TO NEAREST JUNCTION BOX OR DEVICE NOT INDICATED TO BE REMOVED.

EXISTING BOX AND ASSOCIATED CONDUIT SHALL REMAIN. PROVIDE BLANK COVER PLATE FOR

REMAINING OPENING. COVER PLATE FINISH TO MATCH EXISTING IN SAME ROOM. THE CONTRACTOR

SHALL PROVIDE ALL NECESSARY WIRE, CONDUIT, DEVICES AND CONNECTIONS NECESSARY TO

ENSURE CIRCUIT CONTINUITY OF THE REMAINING DEVICES.

8. WHERE WALLS OR CEILINGS ARE INDICATED TO BE REMOVED, ELECTRICAL CONTRACTOR SHALL

REVIEW EXISTING ELECTRICAL INSTALLATIONS WITHIN, THROUGH, OR ABOVE COMPONENT BEING

REMOVED, AND MAKE PROVISIONS TO SUPPORT ANY RACEWAY, OR CABLE NOT REQUIRED TO BE

REMOVED. ALL ELECTRICAL INSTALLATIONS AFTER DEMOLITION SHALL BE COMPLIANT WITH NEC

FOR SUPPORT AND INSTALLATION.

9. THE OWNER HAS THE RIGHT TO RETAIN ALL SALVAGEABLE MATERIAL. ANY MATERIAL THE OWNER

CHOOSES NOT TO ACCEPT SHALL BE REMOVED FROM THE SITE AND PROPERLY DISPOSED OF BY

THE CONTRACTOR. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR THE REMOVAL OF ANY PCB

BALLAST. COORDINATE A MEETING WITH THE OWNER TO DISCUSS SALVAGEABLE MATERIAL AND

DEVICES PRIOR TO COMMENCING DEMOLITION.

10. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE LABELING OF SPARE OR ABANDONED

CIRCUITS AND/OR CIRCUIT BREAKERS IN ALL PANELS AFFECTED BY THE DEMOLITION. SPARE

CIRCUITS AND/OR CIRCUIT BREAKERS MAY BE REUSED FOR THE CIRCUITING OF THE NEW OR

REMODELED AREA AS SPACE AND PANEL LOADING WILL ALLOW. CONTRACTOR SHALL BE

RESPONSIBLE FOR THE RE-LABELING OF PANEL SCHEDULES AS NEW CIRCUITS ARE TERMINATED IN

EXISTING PANELS AND SHALL NOTIFY OWNER AND ENGINEER OF RECORD OF ALL CHANGES MADE

TO PANEL SCHEDULES.

11. THE GENERAL CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE PROPER RESTORATION

OF ALL EXISTING SURFACES REQUIRING PATCHING, PLASTERING, PAINTING AND/OR OTHER REPAIR

DUE TO THE DEMOLITION WORK DONE BY THE ELECTRICAL CONTRACTOR, UNDER THE TERMS OF

THIS SPECIFICATION. CLOSE AND SEAL ALL OPENINGS, REPAIR ALL SURFACES, ETC., AS REQUIRED.

12. PROJECT WORK INCLUDES PARTIAL DEMOLITION OF AREA. ALL LIGHT FIXTURES, DEVICES,

ASSOCIATED WIRING AND CONDUIT (NOT SHOWN) IN AREAS OF DEMOLITION SHALL BE REMOVED

UNLESS OTHERWISE NOTED. THE CONTRACTOR SHALL DISABLE ALL CIRCUITS AT THE SOURCE

PANEL BOARD, DISCONNECT CONDUIT AT FIRST JOINT DOWN STREAM OF PANEL BOARD AND

REMOVE ALL COMPONENTS DOWN STREAM. CONTRACTOR SHALL FIELD VERIFY DEMOLITION

REQUIREMENTS AS NECESSARY TO DEVELOP BID.

13. PROVIDE MINIMUM [2] DAYS ADVANCE NOTICE OF OUTAGES TO ANY INDIVIDUAL NORMAL OR

EMERGENCY POWER PANEL, OR CIRCUITS OUTSIDE THE AREA OF WORK. COORDINATE WITH

OWNER FOR ALL ANTICIPATED OUTAGES. OWNER HAS FINAL APPROVAL ON TIME AND EXTENT OF

POWER OUTAGE.

14. COORDINATE AND PERFORM A WALK-THROUGH WITH THE OWNER TO GO THROUGH LIST OF

SPECIAL CONCERNS AND AREAS AFFECTED DURING ANY OUTAGE.

15. POWER TO EXISTING AREAS, WALLS OR SECTIONS NOT BEING REMODELED, SHALL BE MAINTAINED

AT ALL TIMES EXCEPT FOR SHORT TERM OUTAGES NECESSARY FOR RECONNECTION OF EXISTING

CIRCUITS. COORDINATE AND SCHEDULE OUTAGES WITH THE OWNER.

16. PROTECT EXISTING FURNITURE, CARPET AND OTHER APPURTENANCES FROM DAMAGE DURING

THE COURSE OF CONSTRUCTION. REPLACE DAMAGED ITEMS FREE OF COST TO THE OWNER.

17. MAINTAIN THE PROJECT SITE FREE AND CLEAR OF RUBBISH AND DEBRIS ON A WEEKLY BASIS.

GENERAL DEMOLITION NOTES

1. SEE SHEET E-502 FOR SYMBOL LEGEND.

2. SEE ARCHITECTURAL SERIES SHEETS FOR REFLECTED CEILING PLANS.

3. SEE SHEET E-501 FOR LIGHTING INSTALLATION DETAILS AND GENERAL DETAILS.

4. FIXTURE TYPES HAVE BEEN SELECTED FOR LOOK AND PERFORMANCE. ALTERNATE LIGHT

FIXTURES MAY BE SUBMITTED FOR PRIOR APPROVAL IF A FOOT-CANDLE LEVEL PRINTOUT FOR THE

CEILING AND 30" WORK PLANE HEIGHT IS INCLUDED AND REQUEST IS RECEIVED 10 DAYS PRIOR TO

BID DATE.

5. SEE ARCHITECTURAL SERIES SHEETS FOR ARCHITECTURAL ELEVATIONS AND MORE PRECISE

LOCATIONS OF ALL WALL MOUNTED ELECTRICAL DEVICES. COORDINATE LOCATION OF SWITCH

HEIGHTS WITH CASEWORK, FURNITURE AND EQUIPMENT LAYOUTS PRIOR TO ROUGH-IN. SEE

ARCHITECTURAL CASEWORK ELEVATIONS FOR CABINET HEIGHTS AND LAYOUTS.

6. COORDINATE FINAL LOCATIONS OF ALL LIGHT FIXTURES WITH MECHANICAL DUCTWORK. DO NOT

SUPPORT FIXTURES FROM DUCTWORK, SUPPORT ONLY TO STRUCTURE.

7. CEILING MOUNTED DEVICES SHALL BE CENTERED IN CEILING TILE WHERE INSTALLED IN

ACOUSTICAL TILE CEILING.

8. ALL CIRCUITS SHALL HAVE SEPARATE NEUTRAL WIRES BUT CAN SHARE AN INSULATED GREEN

GROUND WIRES (NOT SHOWN) IN MINIMUM 3/4" EMT CONDUIT WITH STEEL COMPRESSION FITTINGS.

AC, MC, BX CABLE SHALL NOT BE USED AND WILL NOT BE ACCEPTED IN ANY FASHION. (TYPICAL)

9. ALL EXIT SIGNS TO BE WIRED INTO A CONTINUOUS HOT NON SWITCHED PORTION OF THE CIRCUIT.

10. FIXTURES SHOWN AS EMERGENCY FIXTURES ARE TO BE PROVIDED WITH BATTERY BACKUP SO

FIXTURE TURNS ON TO 100% IN THE EVENT OF A POWER FAILURE. PROVIDE CONTINUOUS HOT

NON-SWITCHED WIRE TO EACH EMERGENCY FIXTURE.

11. NO BOXES SHALL BE MOUNTED BACK TO BACK. SEE DETAIL ON SHEET E-501.

12. SEE SHEET E-501 FOR DETAIL FOR WIRE TAP DETAIL.

13. SEE SHEET E-501 FOR DETAIL FOR JUNCTION BOX LABELING DETAIL

14. ALL LOW VOLTAGE WIRING SHALL BE PLENUM RATED AND PROPERLY SUPPORTED. LAYING CABLE

ACROSS CEILING GRID IS NOT CONSIDERED PROPERLY SUPPORTED.

15. ALL WIRING SHALL BE CONCEALED IN ROOMS UNLESS INDICATED BY KEYED NOTE OR WRITTEN

APPROVAL OF THE ENGINEER OR ARCHITECT.

16. WHERE WORK WILL OCCUR IN OCCUPIED AREAS PROTECT EXISTING FURNITURE, FLOORING AND

OTHER APPURTENANCES FROM DAMAGE DURING THE COURSE OF CONSTRUCTION. REPLACE OR

REPAIR DAMAGED ITEMS AT NO COST TO OWNER.

17. EXAMINE THE ARCHITECTURAL DRAWINGS AND FAMILIARIZE YOURSELF WITH THE NEW

CONSTRUCTION MATERIALS WHICH MAY AFFECT YOUR WORK.

18. RE-LABEL ALL EXISTING PANEL SCHEDULES THAT HAVE CHANGED WITH CORRECT ROOM

INFORMATION AND LOAD DESCRIPTION.

19. FOR 120 VOLT LIGHTING CIRCUITS WHERE CIRCUIT LENGTH EXCEEDS 75 FEET, #10AWG SHALL BE

USED. WHERE CIRCUIT EXCEEDS 125 FEET, #8AWG SHALL BE USED FOR FIRST 75 FEET. (MIN.)

20. ELECTRICAL CONTRACTOR TO SEAL ALL PENETRATIONS THROUGH FIRE RATED WALLS/FLOORS

THAT ELECTRICIAN CREATES. SEE DETAILS ON SHEET E5-1. ALL RACEWAYS ROUTED THROUGH

WALLS, AND FLOORS SHALL BE SEALED AS REQUIRED BY AND IN ACCORDANCE WITH NEC

PARAGRAPHS 230.8, 300.5(G) AND 300.7(A)."

21. ALL DEVICES SHOWN SHALL BE MOUNTED AT 18" A.F.F. UNLESS INDICATED OTHERWISE. SEE

ARCHITECTURAL SERIES SHEETS FOR ARCHITECTURAL ELEVATIONS AND MORE PRECISE

LOCATIONS OF ALL ELECTRICAL GEAR.

22. ALL DATA JACKS SHOWN SHALL BE ROUGH-IN BOXES AND STUB UP CONDUITS EXTENDED TO

WITHIN 6" OF NEAREST J-HOOK PATH. PROVIDE PULL STRING WITH PLASTIC BUSHING. PROVIDE AND

CAT 6 BLUE CABLE FOR DATA. ALL BOXES SHALL HAVE BOX SUPPORTS. DATA SHALL TERMINATE IN

110 PUNCH DOWN BLOCKS TELEPHONE ROOM, SEE DETAILS ON SHEET E-501 FOR MORE

INFORMATION.

23. COORDINATE ALL POWER LOCATIONS FOR EQUIPMENT WITH EQUIPMENT THAT IS SUPPLIED AND

WITH ALL TRADES.

24. ALL ELECTRICAL DEVICES ARE TO BE COORDINATED WITH FURNITURE INSTALLATION PRIOR TO

ROUGH-IN TO AVOID ANY CONFLICTS WITH FURNITURE SYSTEM PANELS.

25. ALL NEW AND EXISTING RECEPTACLES THAT ARE FOUND TO BE WITHIN 6' OF A SINK OR WATER

SOURCE THAT ARE NOT A GFI DEVICE OR GFI PROTECTED WITH ANOTHER DEVICE OR CIRCUIT

BREAKER ARE TO BE CHANGED OUT TO A PROPER GFI DEVICE PRIOR TO FINAL INSPECTION.

GENERAL LIGHTING NOTES

7

8

9

10

11

12

13

7/16/2020

Page 9: FOSS FIELD ARMORY · kop knock out panel l angle, length or long lab laboratory lag lagging lam laminate lau laundry ... all duct dimensions called out are interior free area dimensions

Electrical

Details

AUTHOR

CHECKED:

DAVIS DESIGN ALL RIGHTS RESERVED

SHEET TITLE

SHEET NUMBER

ID

ISSUE DATE:

DescriptionDate

Revisions:

15 E

ast M

ain, S

uite 201

Verm

illion S

D 57069

Phone 605-624-1081

Verm

illion

1221 N

S

treet, S

uite 600

Lincoln N

E 68508

Phone 402-476-9700

Fax 402-476-9722

Lincoln

E-501

07-16-2020

TIG

JPD

FOR ALL COMBUSTIBLE WALLS PLASTER RING MUST

BE FLUSH WITH OUTER SURFACE OF WALL. FOR ALL

NON-COMBUSTIBLE WALLS PLASTER RING MUST BE

WITHIN 1/8" FROM OUTER SURFACE OF WALL.

GYPSUM BOARD

STUD

BOX

SUPPORT

OFFSET

CADDY QUICK MOUNT BOX

SUPPORT CADDY BOX

SUPPORT #H23, H4, H53 (AS

APPROPRIATE)

ELECTRICAL CONTRACTOR TO SIZE DEPTH

OF PLASTER RING TO INCLUDE BOX

SUPPORT OFFSET, THICKNESS OF DRYWALL

AND WALL COVERING (IF USED)

SOME EXAMPLES:

-3/4" PLASTER RING FOR SINGLE LAYER

5/8" GYPSUM BOARD WALL FINISH

-1" PLASTER RING FOR TWO LAYER

WALL FINISH 1/2" OVER 1/4"

SCALE:

1

BOX SUPPORT

NO SCALE

PLAN VIEW 2

4" SQUARE BOX

12

" M

NI.

STUD

METAL WALL

PLAN VIEW 1

OR

CADDY BOX

SUPPORT

(NOTE 1)

NOTES:

1. PROVIDE BOX SUPPORT FOR ALL BOXES

2-GANG OR LARGER. TYPE BY CONTRACTOR.

2. OUTLETS ON ADJACENT WALLS THAT ARE FIRE

RATED WALLS, SHALL HAVE TWO STUDS

BETWEEN BOXES.

SEE ARCHITECTURAL

PLANS FOR WALL

CONSTRUCTION.

BOX BRACE

(NOTE 1)

SEE ARCHITECTURAL

PLANS FOR WALL

CONSTRUCTION.

SCALE:

ELECTRICAL OUTLETS

IN COMMON WALL

2

NO SCALE

1" MINERAL WOOL PACKING

NOTE:

WALL SECTION

1. MATERIALS AND CONFIGURATION SHOWN

ARE FOR UL SYSTEM # 147(D).

1/4" MIN., 1 1/4" MAX.

ANNULAR SPACE

1/2" DEPTH CP-25WB

OR CP-25N/S CAULK

28 GAUGE STEEL SLEEVE

WITH 1/2" MIN. OVERLAP

6" RIGID STEEL, 4" EMT OR

1" FLEXIBLE CONDUIT MAX.

ONE OR TWO HOUR RATED

GYPSUM WALLBOARD ASSEMBLY

1/4" BEAD OF CP-25WB

CAULK, BOTH SIDES OF WALL

1" MINERAL WOOL PACKING

NOTE:

WALL SECTION

1/4" MIN., 1 1/4" MAX.

ANNULAR SPACE

28 GAUGE STEEL SLEEVE

WITH 1/2" MIN. OVERLAP

1/2" DEPTH CP-25WB

OR CP-25N/S CAULK

6" RIGID STEEL, 4" EMT, 1"

FLEXIBLE CONDUIT MAX.

PIPE OR DUCT

CMU

1/4" BEAD OF CP-25WB

CAULK, BOTH SIDES OF WALL

1. MATERIALS AND CONFIGURATION SHOWN

ARE FOR UL SYSTEM # 147(D).

FLEX CONDUIT PER

SPECIFICATIONS

CONDUIT TO

OTHER FIXTURES

LIGHT

FIXTURES

CONDUIT TO

PANELBOARD

OR OTHER

FIXTURES.

4" SQUARE OR

OCTAGON BOX.

4 TAP MAX.

LIGHT

FIXTURES

NOTES:

CIRCUIT #'S

CIRCUIT #'S

CIR

CU

IT

#

'S

CIR

CU

IT

#

'S

1. LABEL JUNCTION BOX COVER &

CONDUITS WITH BLACK

PERMANENT MARKER.

2. SPRAY PAINT JUNCTION BOX

COVERS PER SPECIFICATIONS.

3. SEE SPECIFICATION SECTION

260553 FOR ADDITIONAL

INFORMATION.

4. WHERE COVERS ARE PAINTED,

LABEL CIRCUIT ON INSIDE OF

COVER PRIOR TO PAINTING.

JUNCTION BOX

TAG WIRING

INSIDE.

BRANCH

CIRCUIT

CONDUIT.

(TYPICAL)

VOLTAGE

PANEL #

SCALE:

7

J-BOX LABELING DETAIL

NO SCALE

SCALE:

ACCESSIBLE CEILING

FIXTURE WIRE TAP

5

NO SCALE

SCALE:

BREACH SEALING DETAIL

ONE AND TWO HOUR FIRE-STOP

3

NO SCALE

SCALE:

BREACH SEALING DETAIL

ONE AND TWO HOUR FIRE-STOP

4

NO SCALE

CLIENT INFORMATION

PROJECT INFORMATION

South Dakota

Army National

Guard

801 W National Guard Dr.

Sioux Falls, S.D 57104

CFMO# SF466146

Convert IFR

to Classroom -

Foss Field

Armory

20-0067Job #

1

2

3

4

5

6

7

8

9

10

The Wire marking Will Be Left to Right

Face Plates Will Be Marked with a Label Machine.

Mark the Wire at the Jack.

Same as Back Field

First # Is Telecom Room #

Telephone Jack

Telephone Wire

4-9/16"x 4-9/16"x 2-5/8" Deep

with Single Plaster Ring

Wall

Conduit

Ceiling

Bushing

1" Conduit

110-001

110-002

110-003

110-004

110-005

110-006

110-007

110-008

DUPLEX

JACKS

Leave slack for Cat-6

at Wire Rack/Cable Tray

SCALE:

COMMUNICATIONS WIRE

INSTALLATION & MARKING DETAILS

6

NO SCALE

SCALE:

8

COMMUNICATION LABELING DETAIL

NO SCALE

7/16/2020

Page 10: FOSS FIELD ARMORY · kop knock out panel l angle, length or long lab laboratory lag lagging lam laminate lau laundry ... all duct dimensions called out are interior free area dimensions

Electrical

Details and

Symbol

Legend

AUTHOR

CHECKED:

DAVIS DESIGN ALL RIGHTS RESERVED

SHEET TITLE

SHEET NUMBER

ID

ISSUE DATE:

DescriptionDate

Revisions:

15 E

ast M

ain, S

uite 201

Verm

illion S

D 57069

Phone 605-624-1081

Verm

illion

1221 N

S

treet, S

uite 600

Lincoln N

E 68508

Phone 402-476-9700

Fax 402-476-9722

Lin

co

ln

E-502

07-16-2020

TIG

JPD

1. Floor or Wall Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Wall may also be constructed of any UL

Classified Concrete Blocks*. Diam of opening to be 4 in. (102 mm).

See Concrete Blocks category (CAZT) in the Fire Resistance Directory for names of manufacturers.

2. Steel Sleeve - (Optional) - Nom 4 in. (102 mm) diam Schedule 10 to Schedule 40 steel pipe or rigid steel conduit cast or grouted into concrete floor or wall flush with floor or wall

surfaces.

3. Firestop Device* - One firestop device module centered within the opening. The firestop device module consists of a 3 by 3 by 10-1/2 in. (76 by 76 by 267 mm) long galv steel tube

with an intumescent material lining. Firestop device module to be installed in accordance with the accompanying installation instructions. The space between the firestop device

module and the periphery of the opening shall be min 0 in. ( 0 mm, point contact) to max 1/2 in. (13 mm). Firestop device module secured in place by means of steel restraint plates

sized to accommodate the firestop device module. Steel restraint plates each provided with a closed cell silicone gasket and sized to lap approx 1/2 in. (13 mm) on floor or wall

surfaces. Steel restraint plate installed on both sides of floor or wall and secured to firestop device module with steel set screws. The firestop device module is to be installed with its

ends projecting an equal distance beyond each surface of the floor or wall assembly. As an option, firestop device may be cast or grouted into wall assembly. When device is cast or

grouted in place, the steel restraint plates are optional.

SPECIFIED TECHNOLOGIES INC - EZ PATH Series 33 Fire Rated Pathway

3A. Firestop Device* - Extension Module - (Optional, Not Shown) - Module attached to ends of 3 by 3 by 10-1/2 in. (76 by 76 by 267 mm) long firestop device (Item 3) to increase its

length to facilitate installation in thicker floors or walls. Each module consists of a 3 by 3 by 6 in. (76 by 76 by 152 mm) long galv steel tube with an intumescent material lining.

Extension module to be installed in accordance with the accompanying installation instructions. When module is used, firestop device (Item 3) and extension module(s) secured in

place by means of steel plates installed with gasketing material supplied with product. Steel plates installed on both sides of floor or wall and secured to each device or extension

module(s) by means of steel set screws provided with plates. Firestop device and extension module(s) assembly to be installed with ends projecting an equal distance beyond each

surface of the floor or wall assembly.

SPECIFIED TECHNOLOGIES INC - EZ PATH Extension

4. Fill, Void or Cavity Material* - Sealant or Putty - Prior to installation of steel restraint plates, min 1 in. (25 mm) thickness of sealant or putty installed in annular space flush with top

surface of floor or both surfaces of wall.

SPECIFIED TECHNOLOGIES INC - SpecSeal 100, 101, 102, 105, 120 or 129 Sealant, SpecSeal Putty

5. Cables - Within the loading area for each firestop device module, the cables may represent a 0 to 100 percent visual fill. Cable fill to be distributed at a uniform height across the

width of the firestop device module. Cables to be rigidly supported on both sides of the floor or wall assembly. Any combination of the following types of cables may be used:

A. Max 400 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with polyvinyl chloride (PVC) jacketing and insulation.

B. Max 350 kcmil single copper conductor power cable with XLPE jacket and insulation

C. Max 7/C No. 12 AWG copper conductor control cable with PVC or XLPE jacket and insulation.

D. Max 3/C No. 10 AWG metal clad or armored cable with steel or aluminum jacket.

E. Max 3/C No. 8 AWG NM cable (Romex) with PVC insulation and jacket.

F. Max 4 pair No. 22 AWG (or smaller) copper conductor data cable with PVC or plenum rated jacketing and insulation.

G. Max RG/U coaxial cable with fluorinated ethylene insulation and jacketing.

H. Optical fiber cable with PVC or polyethylene (PE) jacket and insulation and having a max diam of 5/8 in. (16 mm).

I. Optical Fiber Raceway+ - Max 1-1/2 in. (38 mm) diam (or smaller) optical fiber raceway ("innerduct") formed of either PVC or polyvinylidene fluoride (PVDF) with optical fiber

cable fill. Raceways installed in accordance with the National Electrical Code (NFPA 70).

When Item 5A, 5B, 5C, 5D or 5E is used, the F Rating is 2 hr and the T Rating is 3/4 hr. When max 200 pair No. 24 AWG telecommunication cable is used or when Item

5F, 5G, 5H or 5I is used, the F Rating is 4 hr and the T Rating is 1 hr.

The L Rating for each empty firestop device module is less than 1 cfm at ambient and at 400F. When Item 5A is used, the L Rating for each firestop device module with

100 percent visual fill is 4 cfm at ambient and 3 cfm at 400F. When Item 5F is used, the L Rating for each firestop device module with 100 percent visual fill is 1.3 cfm at

ambient and less than 1 cfm at 400F.When Item 5G or 5H is used, the L Rating for each firestop device module with 100 percent visual fill is 7 cfm at ambient and 2 cfm

at 400F.

+Bearing the UL Listing Mark

*Bearing the UL Classification Mark

Section A-A

A

A

SCALE:

10

PUNCH DOWN BLOCK DETAIL

NO SCALE

EXISTING PLYWOOD MOUNTING PANEL

110 PUNCH BLOCK DATA

RACK TERMINATIONS

110 PUNCH BLOCK JACK

TERMINATIONS

NOTES:

1. ALL 110 PUNCH DOWN BLOCKS SHOWN IN HALF TONE ARE EXISTING

2. ELECTRICAL CONTRACTOR SHALL ADJUST AND RE-SECURE EXISTING YELLOW LOW VOLTAGE CABLES TERMINATED ON 110 PUNCH DOWN BLOCK

SO NEW 110 PUNCH DOWN BLOCK CAN BE INSTALLED. CABLES SHALL BE SECURED TO PLYWOOD AS NEEDED FOR NEW PUNCH DOWN BLOCK

INSTALLATION. SEE PHOTO FOR CABLES.

3. INSTALL NEW 100 PAIR 110 PUNCH DOWN BLOCK

4. ROUTE AND TERMINATE CAT 6 CABLING FROM DATA JACK TO PUNCH DOWN BLOCK.

5. PROVIDE JUMPER CABLE FROM BOTTOM ROW PUNCH DOWN BLOCK TO TOP ROW PUNCH DOWN BLOCK

6. ROUTE AND TERMINATE CAT 6 CABLING FROM PUNCH DOWN BLOCK TO DATA RACK ADJACENT TO PUNCH DOWN BLOCKS.

7. SEE PHOTO FOR EXISTING PUNCH DOWN BLOCKS.

8. EXISTING PHONE JACK SHALL REMAIN.

2

3

3

4

5

5

6

EXISTING WIRE

MANGEMENT

A

CEILING OUTLET, A = FIXTURE TYPE, a =

SWITCH

LIGHT FIXTURE

STRIP LIGHT FIXTURE

COVE/UNDER CABINET LIGHT FIXTURE

WALL BRACKET FIXTURE

NIGHT LIGHT

WALLWASH FIXTURE

TRACK LIGHT FIXTURE

POLE LUMINAIRE(S)

BOLLARD LUMINAIRE

EMERGENCY LIGHT FIXTURE WALL MOUNT

INDICATES FIXTURE WITH EMERGENCY

BATTERY OR EMERGENCY CIRCUIT

EXIT SIGN, (DIRECTIONAL ARROWS AS

INDICATED; SHADED SIDE INDICATES FACE)

EXIT SIGN WALL MOUNTED, (DIRECTIONAL

ARROWS AS INDICATED; SHADED SIDE

INDICATES FACE)

EXIT SIGN WALL MOUNTED, WITH EMERGENCY

HEADS, (SHADED SIDE INDICATES FACE)

SYMBOL DESCRIPTION

A

A

A

BASKET LIGHT FIXTURE

A

A

A

A

A

A

A A

A

A

NL

A

A

A

CEILING FAN FIXTURE

A

WALL BRACKET LIGHT FIXTURE

DESCRIPTIONSYMBOL

SPST SWITCH

DOUBLE POLE, DOUBLE THROW SWITCH

THREE-WAY SWITCH

FOUR-WAY SWITCH

SWITCH WITH PILOT LIGHT

DIMMER SWITCH

SWITCH FOR DARK ROOM SAFE LIGHT AND WHITE

LIGHT

KEY SWITCH

TIMER SWITCH

MOMENTARY CONTACT SWITCH

PHOTO CELL

TIME CLOCK

TIME SWITCH

PUSHBUTTON

PUSHBUTTON START/STOP

LIGHTING CONTACTOR

4

P

D

RW

K

MC

TS

MS

C

P

TC

PB

C

3

2

T

REMOTE CONTROL SWITCH

MOTION SENSOR SWITCH

SWITCHING

COMMUNICATIONS

SYMBOL DESCRIPTION

LIGHTING

DATA OUTLET WALL

COMBINATION TELEPHONE/DATA OUTLET

INTERCOM OUTLET

TELEPHONE OUTLET

BUZZER

CHIME

CENTRAL DICTATION

KEY PAD

PROGRAM BELL

MONITOR

TERMINAL BOARD, SEE PLANS

FOR IDENTIFICATION

TELEPHONE PANELBOARD

MICROPHONE WALL

PA CALL

MICROPHONE FLOOR

SPEAKER OUTLET, CEILIING

SPEAKER OUTLET, WALL

VOLUME CONTROL, SOUND

TELEVISION OUTLET, CEILING

CLOCK CEILING MOUNT

CLOCK OUTLET

SECURITY CAMERA

I

B

CH

CD

M

M

PA

M

S

S

V

TV

C

C

HD

SB

PA

S SPEAKER OUTLET, FLOOR

PA SPEAKER

SCHOOL BELL

DESCRIPTIONSYMBOL

POWER DEVICES

AS INDICATED)

UFACTURERS RE-

COMENDATIONS

TVSS

FM - FUSE PER MAN-

NEMA 1 ENCLOSURE TYPE

NO. OF SWITCHED POLES

AMPACITY

NF - NON FUSED

AF - AMP FUSE (SIZE

SCHEMATIC DIAGRAM NO.

NF - NON FUSED

FM - FUSE PER MAN-

NEMA 1 ENCLOSURE TYPE

AMPACITY

NO. OF SWITCHED POLES

AF - AMP FUSE (SIZE

DUPLEX RECEPTACLE

HORIZONTALLY MOUNTED DUPLEX RECEPTACLE

TAMPER-PROOF DUPLEX RECEPTACLE

SINGLE RECEPTACLE

GFIC RECEPTACLE

SPLIT DUPLEX RECEPTACLE

TVSS DUPLEX RECEPTACLE (BLUE)

RANGE RECEPTACLE

WP RECEPTACLE

EXPLOSION PROOF RECEPTACLE

X-RAY RECEPTACLE

CEILING RECEPTACLE

SPECIAL RECEPTACLE, SEE PLANS

FOUR PLEX RECEPTACLE

SINGLE GANG FLOOR BOX, POWER

PLUGMOLD/WIREMOLD, WITH NO. OF OUTLETS AS

INDICATED

J-BOX FLOOR BOX, POWER

JUNCTION BOX

JUNCTION BOX WALL

MOTOR WITH HORSE POWER AS NOTED

CIRCUIT BREAKER OR FUSIBLE DISCONNECT

DISCONNECT SWITCH, SURFACE MOUNTED, 600V,

30A,3 POLE U.O.N.

MOTOR STARTER

COMBINATION MAGNETIC MOTOR STARTER AND

DISCONNECT SWITCH SURFACE MOUNTED

LIGHTING PANEL AND OR POWER PANEL

MCC OR DISTRIBUTION PANEL

TRANSFORMER

AUTOMATIC TRANSFER SWITCH

VARIABLE SPEED DRIVE

METER SOCKET

AS INDICATED)

UFACTURERS RE-

COMENDATIONS

EXP

SINGLE GANG FLOOR BOX, 4-PLEX POWER

GFI

WIU

WP

T

J

J

J

TR

ATS

VFD

M

WHILE IN USE RECEPTACLE COVER

HAND DRYER

M

FT

OL

TE

MC

WIRELESS INTERNET ANTENNA

MOTOR RATED SWITCH

FUSED SWITCH

OVERLOAD PROTECTED SWITCH

THERMAL SWITCH

MOTOR CONTROL SWITCH

NURSE CALL

SYMBOL DESCRIPTION

DOCTOR'S REGISTER MASTER PANEL

NURSE CALL MASTER STATION

NURSE CALL BEEPER

NURSE CALL CENTRAL EQUIPMENT

NURSE CALL CORRIDOR DOME LIGHT WALL

NURSE CALL CORRIDOR DOME LIGHT CEILING

NURSE CALL BEDSIDE STATION

NURSE CALL EMERGENCY STATION

NURSE CALL CODE BLUE STATION

NURSE CALL CODE BLUE ANNUNCIATOR

NURSE CALL STAFF/DUTY STATION

NURSE CALL STAFF PRESENT STATION

NURSE CALL STAFF STATION

NURSE CALL DUTY STATION

OXYGEN ALARM PANEL

GI ALARM

FILM ILLUMINATOR

NURSE CALL LOCATOR DEVICE

NCM

DRM

NB

D

E

CB

SD

OXA

GIA

N

N

B

SP

S

FI

BBA

BLOOD BANK ALARM

NCP

NURSE CALL MASTER PANEL

CBA

NCC

NC

DESCRIPTIONSYMBOL

FIRE ALARM

FA MANUAL PULL STATION

FA SPEAKER, CEILING

FA STROBE, WALL

FA BELL

FA HORN AND STROBE, CEILING

FA SPEAKER, WALL

FA HORN, WALL

FA SPEAKER AND STROBE, WALL

HEAT DETECTOR

SMOKE DETECTOR INSTALL IN DUCT

SMOKE DETECTOR

ELECTRO-MAGNETIC DOOR HOLDER/RELEASE

POST INDICATOR VALVE

GATE VALVE SWITCH

WATERFLOW ALARM SWITCH

FAN SHUT-OFF RELAY

FIRE ALARM MASTER PANEL

FIRE ALARM ANNUNCIATOR PANEL

FIRE ALARM PHONE JACK

AUTOMATIC FIRE SMOKE DAMPER

AUTOMATIC SMOKE DAMPER

F

D

F

F

F

PIV

GV

WFA

R

FA

FAA

SD/FD

F

SD

FA STROBE, CEILINGF

RACEWAYS

SYMBOL DESCRIPTION

STUB CONDUIT UP AND CONNECT AS REQUIRED

STUB CONDUIT DOWN AND CONNECT AS

REQUIRED

SURFACE RACEWAY

WIRING IN CONDUIT, CONCEALED

WIRING IN CONDUIT, EXPOSED

WIRING IN CONDUIT, CONCEALED IN FLOOR

HOME RUN TO PANEL, 2 WIRES UNLESS

OTHERWISE INDICATED

EXISTING CONDUIT AND WIRING TO REMAIN

EXISTING CONDUIT AND WIRING TO BE REMOVED

FIRE ALARM SYSTEM

SOUND SYSTEM CONDUIT

NURSE CALL SYSTEM

MONITOR SYSTEM CONDUIT

CABLE TV SYSTEM

CENTRAL DICTATION SYSTEM CONDUIT

INTERCOM SYSTEM CONDUIT

EMERGENCY CIRCUIT

X

X

EM

CATV

I

CD

FA

S

N

M

X

MISCELLANEOUS

SYMBOL DESCRIPTION

R

E

E2

R2

E1

R1

GFI

WP

EXP

NL

DENOTES GROUND FAULT

EXPLOSION PROOF

DENOTES WEATHERPROOF

INDICATES NIGHT LIGHT FIXTURE

INDICATES ITEM TO BE REMOVED

INDICATES ITEM TO REMAIN

THERMOSTAT

HEATER, ELECTRIC

INDICATES BREAK

H

T

TYPICAL MOUNTING HEIGHTS

HEIGHTS ARE TO CENTER LINE

UNLESS NOTED OTHERWISE

RECEPTACLES

SWITCHES

THERMOSTATS

FIRE ALARM HORN STROBE

FIRE ALARM CHIME

FIRE ALARM STROBE LIGHT

PANEL BOARDS TO TOP

CABINETS TO TOP

DISCONNECTS

PHONE OR DATA OUTLETS

PHONE DATA OUTLETS

18"

48"

48"

84"

84"

84"

72"

72"

60"

18"

18"

ELECTRICAL SYMBOLS

NOTE;

THIS SYMBOL LEGEND IS FOR REFERENCE ONLY.

NOT ALL SYMBOLS ARE USED ON THIS PROJECT.

TVSS 4-PLEX RECEPTACLE (BLUE)

A

EMERGENCY LIGHT FIXTURE CEILING MOUNT

FS

FLOW SWITCH

INDICATES ITEM WHICH HAS BEEN RE-ADJUSTED.

INDICATES ITEM TO BE RE-ADJUSTED.

DISCONNECTION SHOULD NOT BE REQUIRED.

INDICATES ITEM WHICH HAS BEEN RELOCATED.

RECONNECT TO CIRCUITING AS SHOWN.

INDICATES ITEM TO BE RELOCATED. SEE NEW

PLANS FOR NEW LOCATION. DISCONNECTION OF

CIRCUIT WIRING WILL BE REQUIRED.

RC

TS

TAMPER SWITCH

LOW VOLTAGE (DIGITAL) SWITCH

LV

CARD READER

ELECTRIC STRIKEES

CR

CRITICAL EMERGENCY CIRCUIT

EQ

EQUIPMENT EMERGENCY CIRCUIT

LS

LIFE SAFETY EMERGENCY CIRCUIT

FULLY CONTROLLED RECEPTACLE

FC

HC

HALF CONTROLLED RECEPTACLE

ACCESS CONTROL

SYMBOL DESCRIPTION

POWER SUPPLYPS

DOOR CONTROL DEVICE

ADA OPERATOR

DCD

ADA

RADIO FREQUENCY RECEIVERRFR

GENERATOR ENUNCIATOR PANELANN

DOOR POSITION SWITCH

DP

ELECTRIC LOCKSET

EL

REQUEST TO EXIT DEVICE

ED

CR

KP

3P/30A/NEMA 1/NF

3P/SIZE 0/NEMA 1/NF/SD02

COMBINATION TELEPHONE/DATA OUTLET CEILING

COMPUTER OUTLET CEILING

TELEPHONE OUTLET CEILING

TELEPHONE FLOOR BOX

COMPUTER OUTLET FLOOR

COMBINATION TELEPHONE/DATA OUTLET FLOOR

PB

START/STOP

FA HORN, CEILING

FA HORN AND STROBE, WALLS

S

S

FA SPEAKER AND STROBE, CEILINGS

FAC

FA CHIME

TVTELEVISION OUTLET, WALL

F

F

F

F

F

F

F

CLIENT INFORMATION

PROJECT INFORMATION

South Dakota

Army National

Guard

801 W National Guard Dr.

Sioux Falls, S.D 57104

CFMO# SF466146

Convert IFR

to Classroom -

Foss Field

Armory

20-0067Job #

SCALE:

9

EZ PATH DETAIL

NO SCALE

8

7/16/2020