DRAWING TITLE
DRAWING
NUMBER
FP000
DRAWING SCHEDULE
DA
TE
IS
SU
E
FIRE PROTECTION COVER SHEET
FIRE PROTECTION
COVER SHEET
KCB
LEG
KCB
FP000
Drawing Number:
Date: 02/19/2021
Drawing Title:
Approved:
Checked:
Drawn:
Drawing Set:
Project Name:
No. Date Revisions
Scale:
Job Number:
80% CDs
Notes:
1002 West 9th Avenue, King of Prussia, PA 19406610-989-3800 - www.cvmprofessional.com
MECHANICAL ENGINEER
CHESTNUT ENGINEERING
2 E Lancaster Ave, 2nd Flr.,
Ardmore, PA 19003
610-642-1750
CIVIL ENGINEER/SURVEYOR
NORTH COUNTRY ENGINEERING, INC.
706 Chippewa Square, Suite 102
Marquette, MI 49855
906-226-7683
Seal:
PROJECT MANAGER, LEAD DESIGNER,
STRUCTURAL ENGINEER
UPS MARQUETTE
ARCHITECT
TPD ARCHITECTS, LLC
109 Hewett Road
Wyncote, PA 19095
215-887-2460
FIRE PROTECTION GROUND FLOOR PLANFP100
FIRE PROTECTION LEGEND
PRE-ACTION FIRE PROTECTION PIPING
DRY PIPE FIRE PROTECTION PIPING
FIRE DEPARTMENT HOSE CONNECTION
FIRE PUMP/FIRE PROTECTION PIPING
TOTAL DEVELOPED HEAD(DYNAMIC)
PC PLUMBING CONTRACTOR
VIF
TYP
(R)
TDH
(RL)
RPM
PRV
PSI
REVOLUTIONS PER MINUTE
EXISTING TO BE RELOCATED
EXISTING TO BE REMOVED
POUNDS PER SQUARE INCH
PRESSURE REDUCING VALVE
VERIFY IN FIELD
TYPICAL
GC
PA
NTS
NO
NIC
N/A
NC
SW
MIN
MAX
MC
JP
HP
DP
FDHC
FP
FD
DWG
(E)
EX
CLG
CONT
DN
AFF
AP
JOCKEY PUMP
GENERAL CONTRACTOR
SAFEWASTE
NOT TO SCALE
NOT IN CONTRACT
NOT APPLICABLE
MECHANICAL CONTRACTOR
EXISTING TO REMAIN
ABOVE FINISHED FLOOR
ACCESS PANEL
FLOOR DRAIN
HORSE POWER
NORMALLY OPEN
NORMALLY CLOSED
CONTINUED
MINIMUM
MAXIMUM
DRAWING
EXISTING
CEILING
DOWN
ABBREVIATIONS
PIPE ANCHOR
PIPE GUIDE
GATE VALVE W/ TAMPER SWITCH
EXISTING TO BE RELOCATED
CAP
(RL)
UNION
PIPE DROP
PIPE DOWN
PIPE UP
D
E
EXISTING TO BE REMOVED
EXISTING TO REMAIN
EXISTING TO BE REMOVED
EXISTING TO REMAIN
CUT AND CAP
CONNECT NEW TO EXISTING
(R)
(E)
NEW WORK
CONCEALED PENDANT HEAD
EXPOSED PENDANT HEAD
RECESSED PENDANT
SIDEWALL SPRINKLER HEAD
FIRE DEPARTMENT SIAMESE CONNECTION
FIRE PUMP TEST CONNECTION
EXTENDED COVERAGE UPRIGHT HEAD
STANDPIPE HOSE CONNECTION
UPRIGHT SPRINKLER HEAD
DRY UPRIGHT SPRINKLER HEAD
FLOW SWITCH
BALL VALVE W/ TAMPER SWITCH
BUTTERFLY VALVE W/ TAMPER SWITCH
PRESSURE GAGE W/ BALL VALVE
DOUBLE CHECK VALVE
CHECK VALVE
VERTICAL VALVE
SYMBOLS
T
T
B
F
(N) NEW WORK
(TYPICAL FOR OTHER HEAD TYPES)
(TYPICAL FOR OTHER HEAD TYPES)
AHJ AUTHORITY HAVING JURISDICTION
DSP DRY STANDPIPE
GENERAL FIRE PROTECTION REQUIREMENTS:
1. FURNISH ALL EQUIPMENT, MATERIALS, AND LABOR NECESSARY
FOR A COMPLETE FIRE SUPPRESSION SYSTEM.
2. INSTALLATION SHALL MEET NFPA AND ALL LOCAL REQUIREMENTS.
3. TEST ALL FIRE PROTECTION PIPING INSTALLED UNDER THIS
CONTRACT IN ACCORDANCE WITH NFPA #13. CORRECT AND
RETEST ALL LEAKS. TAKE ALL NECESSARY PRECAUTIONS TO
PREVENT FREEZING AND ANY DAMAGE TO EQUIPMENT AND
PIPING. ALL TESTS WILL BE WITNESSED BY THE OWNERS
REPRESENTATIVE AND BUILDING AND FIRE DEPARTMENT
INSPECTORS. PROVIDE CONTRACTOR'S MATERIAL AND TEST
CERTIFICATE TO OWNER.
4. CONTRACTOR SHALL HAVE "START WORK" PERMIT IN HAND FORM
THE AHJ PRIOR TO FABRICATION OR INSTALLATION OF ANY PART
OF THE SYSTEM.
SPRINKLER NOTES:
1. ALL PIPE TO BE SCHEDULE 40 BLACK STEEL PIPE MEETING OR
EXCEEDING ASTM A-135 REQUIREMENTS.
2. ALL SCREW FITTINGS TO BE CAST IRON AND OR MALLEABLE IRON
MEETING OR EXCEEDING ANSI B16.4 AND ANSI B16.3.
3. ALL GROOVED (ROLLED ONLY, NO CUT GROOVES) FITTINGS TO BE
MALLEABLE IRON MEETING OR EXCEEDING ASTM A-536
REQUIREMENTS.
4. ALL HANGERS TO MEET OR EXCEED NFPA PAMPHLET REQUIREMENTS.
SPRINKLER SCHEDULE
SYMBOL TYPE MANUFACTURER MODEL # K FACTOR ORIFICE
THE VIKING
CORPORATION
OR EQUAL
CONCEALED
PENDENT
MODEL
SIN VK 462
5.6 1/2"
FINISH
WHITE FACTORY
PAINTED COVER
THE VIKING
CORPORATION
OR EQUAL
UPRIGHT
NATURAL BRASS
TAMPER SWITCH
STEEL PIPE
THREADED LIGHTWALL
NOMINAL PIPE
STEEL PIPE EXCEPT
THREADED LIGHTWALL
MAXIMUM DISTANCE BETWEEN HANGERS
12-0
12-0
SIZE (in.)
1"
N/A
N/A
15-0
12-0
12-0
12-0
2"
15-0
12-0
15-0
12-0
6"
15-0
N/A
15-0
N/A
15-0
N/A
3"
15-0
12-0
5"4"
15-0
N/A
8"
15-0
N/A
3/4" 1 1/4" 1 1/2" 2 1/2" 3 1/2"
LIGHT HAZARD ORDINARY HAZARD
Protection
Area
ft
Spacing
(max.)
ft
2
Spacing
(max.)
ft
Protection
Area
ft
CONSTRUCTION
TYPE
Noncombustible
obstructed and
unobstructed and
combustible
unobstructed
225 15 130 15
168 15 130 15
Combustible
obstructed
Note: For hydraulically calculated systems only.
Protection Areas and Maximum Spacing
(Standard Spray Upright/Standard Spray Pendent)
2
SPRINKLER NOTES:
1. ALL SCREW FITTINGS TO BE CAST IRON AND OR MALLEABLE IRON
MEETING OR EXCEEDING ANSI B16.4 AND ANSI B16.3.
2. ALL GROOVED FITTINGS TO BE MALLEABLE IRON MEETING OR
EXCEEDING ASTM A-536 REQUIREMENTS.
3. ALL HANGERS TO MEET OR EXCEED NFPA PAMPHLET REQUIREMENTS.
SYSTEM PIPE SIZE LOCATION SCHEDULE OR TYPEMATERIAL FITTING JOINT
BLACK STEEL GROOVEDABOVE GRADE BLACK STEEL VICTAULICSCH 10
2-1/2" AND
ABOVE
FIRE PROTECTION PIPE & FITTING SCHEDULE
BLACK STEEL THREADEDABOVE GRADE
BLACK STEEL THREADED
SCH 40WET
LESS THAN
2-1/2"
WET
02/05/2021
30%
C
Ds
FP000
1
SCALE: NONE
FIRE PROTECTION SERVICE RISER SCHEMATIC
TO SPRINKLER
SYSTEM
DRAIN PIPE TO EXTERIOR
FP SERVICE.
REFER TO CIVIL DWGS FOR
CONTINUATION
PRESSURE GAGE (TYP)
ALARM CHECK VALVE
OS&Y GATE VALVE WITH
TAMPER SWITCH
FLOW SWITCH
FLOOREXTERIOR
EXTERIOR POST
INDICATOR
END OF REMOTE
BRANCH LINE OR MAIN
PITCH
GRADEFINISHED FLOOR
FP000
2
SCALE: NONE
INSPECTORS TEST CONNECTION DETAIL
45° ELBOW
SIGHTGLASS WITH SMOOTH
BORE, CORRSOION RESISTANT
ORIFICE EQUAL TO THE FLOW
ON ONE SPRINKLER
VALVE (NORMALLY CLOSED)
EXTERIOR WALL
WALL PENETRATION
AND SLEEVE
SPLASH GUARD
7'-0" MAX AFF
02/19/2021
80%
C
Ds
GENERAL NEW WORK NOTES:
1. ALL WAREHOUSE AREAS ARE CLASSIFIED AS ORDINARY
HAZARD GROUP 2 (0.3 GPM/SF OVER 2500 SF, AS REQUIRED
BY UPS). ALL OFFICES AREAS ARE CLASSIFIED AS LIGHT
HAZARD (0.15 GPM/SF OVER 1500 SF, AS REQUIRED BY UPS)
2. HEADS IN AUTO SHOP SHALL PROTECT A MAXIMUM OF 70 SF
PER UPS STANDARDS.
3. NEW HEAD LOCATIONS AND PIPE ROUTING SHALL BE
COORDINATED WITH LIGHTING AND STRUCTURE.
4. PIPE SIZES ARE SHOWN FOR COORDINATION ONLY. ALL
SIZES SHALL BE DETERMINE BY FPC THROUGH HYDRAULIC
CALCULATIONS.
5. ALL HEADS AND PIPING REQUIRED BELOW CONVEYORS
WILL BE PROVIDED BY OTHERS.
6. A MUNICIPAL WATER SERVICE IS NOT AVAILABLE ON SITE.
ALL FIRE PROTECTION WATER WILL COME FROM THE ON
SITE STORAGE TANK.
PUMP HOUSE
WELL
100,000 GALLON, INSULATED,
GROUND LEVEL SUCTION FIRE
PROTECTION STORAGE TANK
SCREENED VENT AT
TOP OF TANK
4" OVERFLOW PIPE
EXTERNAL LADDER
HATCH COVER (MIN 24")
INTERNAL LADDER
SAFETY CAGE
LADDER SECURITY COVER
WATER LEVEL INDICATOR
1-1/2" EMERGENCY DRAIN VALVE
LISTED RENEWABLE-DISC
GLOBE VALVE
10 KW ELECTRIC
TANK HEATER
TANK HEATER
CIRCULATION PUMP
2-1/2" HOT WATER
CIRCULATION PIPE
BURIED FP TO
BUILDING.
REFER TO CIVIL
DWGS FOR CONT.
ANTI-VORTEX PLATE
AND FITTING
ACCESSIBLE
CONCRETE PIT
BELOW FROST LINE
FIRE PUMP DIESEL
STORAGE TANK
DIESEL
FIRE PUMP
JOCKEY PUMP
VENT
FILL LINE
10987654321
E E
B B
A
D D
C C
7.5 8.3
7.3 8.5
6" FP SERVICE. REFER TO CIVIL
DWGS FOR CONTINUATION
ZONE RISER
F
T
INSPECTORS TEST
CONNECTION
T
POST INDICATOR VALVE
REFER TO
MEZZANINE PLAN FOR
CONTINUATION (TYP)
SYSTEM DRAIN
1098
B
A
8.5
B.8
8.1
202
TSG STORAGE
ROOM
200
MECHANICAL
AREA
201
SERVER
ROOM
FIRE PROTECTION
GROUND FLOOR
PLAN
KCB
LEG
KCB
FP100
Drawing Number:
Date: 02/19/2021
Drawing Title:
Approved:
Checked:
Drawn:
Drawing Set:
Project Name:
No. Date Revisions
Scale:
Job Number:
80% CDs
Notes:
1002 West 9th Avenue, King of Prussia, PA 19406610-989-3800 - www.cvmprofessional.com
MECHANICAL ENGINEER
CHESTNUT ENGINEERING
2 E Lancaster Ave, 2nd Flr.,
Ardmore, PA 19003
610-642-1750
CIVIL ENGINEER/SURVEYOR
NORTH COUNTRY ENGINEERING, INC.
706 Chippewa Square, Suite 102
Marquette, MI 49855
906-226-7683
Seal:
PROJECT MANAGER, LEAD DESIGNER,
STRUCTURAL ENGINEER
UPS MARQUETTE
ARCHITECT
TPD ARCHITECTS, LLC
109 Hewett Road
Wyncote, PA 19095
215-887-2460
FP100
1
SCALE: 1/8" = 1' - 0"
FIRE PROTECTION GROUND FLOOR PLAN
FP100
3
SCALE: 1/4" = 1' - 0"
FIRE PROTECTION PUMP HOUSE PLAN
FP100
2
SCALE: 1/8" = 1' - 0"
FIRE PROTECTION MEZZANINE PLAN