Upload
karik
View
34
Download
0
Tags:
Embed Size (px)
DESCRIPTION
Front End Equipment Protection System. Currently there are 55 FEEPS Systems in Service This consists of: 43 Version 1 system 4 Version 2 systems (16ID, 16BM, 22ID, 22BM) 3 Version 2.5 systems (23ID, 24ID & 31ID) 5 Version 3.0 systems (11BM, 21ID, 23BM, 26ID & 30ID). - PowerPoint PPT Presentation
Citation preview
Safety Interlocks Group
Front End Equipment Protection System
• Currently there are 55 FEEPS Systems in Service– This consists of:
• 43 Version 1 system• 4 Version 2 systems (16ID, 16BM, 22ID, 22BM)
• 3 Version 2.5 systems (23ID, 24ID & 31ID)
• 5 Version 3.0 systems (11BM, 21ID, 23BM, 26ID & 30ID)
Safety Interlocks Group
Front End Equipment Protection SystemVersion Differences
• Version 1 Systems:– Local control panel, for controls– Love Controllers, for DIW interlocks– Single Ion Pump interlocks
• Version 2.0 Systems:– Panel view touch screen, for controls– Analog module for DIW interlocks – Single Ion Pump interlocks
• Version 2.5 Systems:– Panel view touch screen, for control– Analog module for DIW interlocks – All adjacent Ion Pump’s interlocked
• Version 3.0 Systems:– EPICS control – Analog module for DIW interlocks – All adjacent Ion Pump’s interlocked– Remote Fast Valve Control– Remote Reset of Vat Chassis– Fault & Warning stack added to Epics– Fault Paging System incorporated
Safety Interlocks Group
Front End Equipment Protection System Version 1 Vacuum Controls Zones
Beamline VacuumFront-End VacuumStorage Ring Vacuum
IP 2 IP 3 IP 4 IP 5 IP 6 IP 7 IP 8 BL Vac. Pump.
FM 1 FM 2 FM 3BPM 1 BPM 2
PS 1 SV FV PS 2 SS 1 SS 2 FEV
BeWin
IP 1
Beam Direction
BIV
Safety Interlocks Group
Front End Equipment Protection System Version 2.5 & 3.0 Vacuum Controls Zones
Beamline Vacuum
Front-End Vacuum
Storage Ring Vacuum
IP 2 IP 3 IP 4 IP 5 IP 6 IP 7 IP 8 BL Vac. Pump.
FM 1 FM 2 FM 3BPM 1 BPM 2
PS 1 SV FV PS 2 SS 1 SS 2 FEV
BeWin
IP 1
Beam Direction
BIV
Safety Interlocks Group
Front End Equipment Protection SystemOld Operator EPICS Displays
Safety Interlocks Group
Front End Equipment Protection SystemNew Operator EPICS Displays
Safety Interlocks Group
Front End Equipment Protection SystemNew Engineering EPICS Display
Safety Interlocks Group
Front End Equipment Protection System
• Upcoming Changes– Upgrade Version 2.5 systems to 3.0 (23ID, 24ID & 31ID)
– Version 1 Round 1 -- DIW Upgrade -- (Starting with BM’s)• Remove Love Controllers & install Analog Modules• Install new Version of Code• Upgrade Epics controls
– Version 1 Round 2 -- Vacuum Upgrade –• Add all ion pumps into the interlocks• Standardize all I/O• Add additional Vat controls