68
FAST S.p.A. ISO 9001:2000 - Cert.n° 0882/4 SELECTION, INSTALLATION, USE AND MAINTENANCE MANUAL FTA range Air conditioning units Air flow rate from 900 to 5000 m³/h

FTA range Air conditioning units - Arfit€¦ · FTA range Air conditioning units ... laid down by law 46/90 and/or DPR ... PMMxF Plenum with multiple circular delivery points

  • Upload
    vudan

  • View
    215

  • Download
    1

Embed Size (px)

Citation preview

���� ����� ��� ��� ��

FAST S.p.A.

ISO 9001:2000 - Cert.n° 0882/4 SELECTION,

INSTALLATION, USE

AND MAINTENANCE MANUAL

FTA range

Air conditioning unitsAir fl ow rate from 900 to 5000 m³/h

Contents English

General standards 4

Description of the unit 5

Description of components 5

Identification of the unit 6

Accessories 7

Compatibility of accessories 8

Nominal technical data 10

Characteristic ventilation curves 12

Pressure drops in the filters, due to dirt 20

Table showing heat exchange coil output 21

Table showing operating limits 21

Installation, use and maintenance manual 42

- General safety requirements 42

- Minimum operating spaces 43

- Handling 43

- Unit installation 43

- Installation - Connections 44

- Repositioning the internal components 46

- First start-up 46

- PTC2 control panel 46

Union base unit with accessories 47

Unit maintenance 48

Unit disposal 49

Diagnosis and fault solving 49

Wiring diagrams 50

- PTC2 connection diagram 50

- Connection diagram for the electric coils 53

- PX connection diagram 54

Size data 57

- Unit dimensions 57

- Plenum with post-heating electric coil 58

- Section of soft pocket filters 58

- Intake grille 59

- Delivery grille 59

- 2-damper mixing chamber 60

- 3-damper mixing chamber 61

- Plenum with multiple circular delivery points 62

- Closed delivery plenum 62

- 2-area damper 63

- Suction damper 63

- Silencers 64

- Section of intake fan 64

- PCT2, PX 65

General standards

The present manual is an

integral part of the docu-

mentation enclosed with the

machine.

It must be conserved for

future reference and must accompany

the machine throughout its working life.

The manual defines the purpose for which

the machine was built and establishes the

correct installation and use limits.

• All use, installation and maintenance

instructions of the unit are described

in this manual as well as the main

accident prevention standards.

• Read carefully and fully all informa-

tion contained in this manual before

the installation, start-up, use, main-

tenance and cleaning of the unit. Pay

particular attention to the use regu-

lations accompanied by the words

“DANGER” or “WARNING”: failure to

observe them could cause damage to

the machine and/or persons and pro-

perty.

• For irregularities not contemplated by

this manual, consult the local After

Sales Service.

• FAST S.p.A. decline any responsibility

for any damage due to the improper

use of the machine, and to a partial or

superficial reading of the information

contained in this manual.

• Installation and maintenance must be

carried out by trained and qualified

personnel, having the requirements

laid down by law 46/90 and/or DPR

380/2001 for electric/electronic and

air conditioning installations, with

consequent registration at the local

CHAMBER of COMMERCE. Otherwise

FAST S.p.A. decline all responsibility

regarding the safety of the product.

THE MANUFACTURER DECLINES ANY

RESPONS IB IL ITY FOR DAMAGE TO

PROPERTY, PERSONS OR ANIMALS CAUSED

BY THE NON-OBSERVANCE OF THE

INDICATIONS AND REGULATIONS CONTAINED

IN THIS MANUAL.

Even though a suitable risk analysis was

carried out during the design of the FTA

unit, pay ATTENTION to the pictograms on

the machine; these make it easier to read

the manual, quickly drawing the reader's

attention to risks that cannot be

avoided or sufficiently limited

with the adoption of protection

means and measures.

GENERAL DANGER SIGNS

Carefully observe all indications at the

side of the pictogram.

The non observance of the indi-

cations could cause hazardous

conditions with possible injury

to the operator and to the user

in general.

VOLTAGE DANGER SIGN

Carefully observe all indications at the

side of the pictogram.

The signs indicate components

on the unit or, in the present

manual, identify areas that could genera-

te risks of an electrical nature.

GENERAL WARNING SIGNS

Carefully observe all indications to the

side of the pictogram that limit some

actions in order to ensure greater safety

for the operator.

M A I N G U A R A N T E E CONDITIONS

• The guarantee does not include pay-

ment for damages due to incorrect

installation by the installer.

• The guarantee does not include pay-

ment for damages due to the improper

use of the unit by the user.

• The manufacture is not responsible for

injuries to the installer or user, caused

by incorrect installation or improper

use of the unit;

• The equipment must be installed in

such a manner so as to permit mainte-

nance and/or repair operations;

• The guarantee does not cover in any

case costs due to turntable ladders,

scaffolding or other similar elevating

systems that are necessary to carry

out operations under guarantee.

The guarantee is not valid if:

• the services and repairs have been

carried out by unauthorised personnel

or companies;

• the unit has been previously repaired

or modified with non-original parts;

• the unit has not been suitably maintai-

ned;

• the instructions given in this manual

have not been observed;

• unauthorised modifications have been

made.

NB:

the manufacturer reserves the right to

carry out modifications at any time dee-

med necessary to improve its product, and

is not obliged to apply the said modifica-

tions to previously manufactured machi-

nes that have already been delivered or

are being constructed.

The general conditions are in any case

subject to the general sale conditions

foreseen on the stipulation of the con-

tract.

Air conditioning units - FTA range

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

The air conditioning units in the FTA

range have been designed for civil,

commercial and hotel use, for small

and medium sized rooms. The units are

designed to guarantee high head levels

and can be installed either vertically

or horizontally, thereby offering

greater versatility. Thanks to this type

of unit, several rooms can be served

via a distribution plenum. The units of

this range are characterised by their

compact size, low noise levels, and the

wide choice of accessories.

STRUCTURE

The load-bearing structure is made of

galvanised steel sandwich panels with

polyurethane insulation (density 40kg/

m³), 15 mm thick. The suction and

supply panels are fitted with flanges for

connecting any air pipes or accessories

envisaged. Special brackets supplied

with the unit make it easier to fix it to

the wall.

The condensate drip tray, in galvanised

steel, has a threaded drain connection

on both sides and can be used whether

the unit is installed horizontally or

vertically.

ELECTRIC FAN UNIT

Consist ing of high performance

centrifugal fans with double intake

and forward blades. The multispeed

electric motor, for which three speeds

can be selected from the control panel

(optional), is directly connected to the

fans.

HEAT EXCHANGE COIL

In copper piping and aluminium finning

blocked by the mechanical expansion of

the pipes.

Threaded pipe couplings for the

hydraulic connections and air drain

valve are supplied. Two versions are also

available with a direct expansion coil in

copper piping with aluminium finning

blocked by the mechanical expansion of

the pipes (3 or 4 rows).

FILTERING

The air is filtered through synthetic

filters, 50mm thick, in efficiency class

G4 (in compliance with standard EN

779), positioned at the suction point.

The filters can be easily accessed for

maintenance and cleaning. For the

VRFxF accessory, the air is filtered

through soft pocket filters with a

filtering degree of F6. For higher

filtering degrees, contact our Technical/

Sales Office.

Air conditioning units - FTA range

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

Description of the unit

Description of components

Identification of the unit

Air conditioning units - FTA range

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

FTA XX X X

Size- 09- 11- 15- 19- 24- 33- 40- 50

Version 3 : 3-row water coil4 : 4-row water coil 6 : 6-row water coil A : R410A direct expansion coil, 3 rows RightB : R410A direct expansion coil, 4 rows RightC : R407C direct expansion coil, 3 rows RightD : R407C direct expansion coil, 4 rows RightE : R410A direct expansion coil, 3 rows LeftF : R410A direct expansion coil, 4 rows LeftG : R407C direct expansion coil, 3 rows LeftH : R407C direct expansion coil, 4 rows Left

ConfigurationH : HorizontalV : Vertical X : Extractor

Accessories

M2SxF 2-damper mixing chamber Galvanised steel section complete with two air calibration dampers and fins in galvanised steel. Fin pitch 50mm; galvanised steel adjustment pin, 8mm, can be motor-driven.

M3SxF 3-damper mixing chamberGalvanised steel section complete with three air calibration dampers and fins in galvanised steel. Fin pitch 50mm; galvanised steel adjustment pin, 8mm, can be motor-driven.

FTFxF Section of soft pocket filters Galvanised steel section complete with soft pocket filters with a filtering degree of F6. For different filtering degrees, contact our Technical/Sales Office.

B1RxF 1-row water coil for 4-pipe systemsPositioned internally, downstream from the main coil, and made of copper piping and aluminium finning blocked by the mechanical expansion of the pipes. Threaded pipe couplings for the hydraulic connections and air drain valve are supplied.

B2RxF 2-row water coil for 4-pipe systemsPositioned internally, downstream from the main coil, and made of copper piping and aluminium finning blocked by the mechanical expansion of the pipes. Threaded pipe couplings for the hydraulic connections and air drain valve are supplied.

FTA 09 FTA 11 FTA 15 FTA 19 FTA 24 FTA 33 FTA 40 FTA 50

M2SxF M2S1F M2S1F M2S2F M2S3F M2S4F M2S4F M2S5F M2S5F

M3SxF M3S1F M3S1F M3S2F M3S3F M3S4F M3S4F M3S5F M3S5F

FTFxF FTF1F FTF1F FTF2F FTF3F FTF4F FTF4F FTF5F FTF5F

B1RxF B1R1F B1R1F B1R2F B1R3F B1R4F B1R4F B1R5F B1R5F

B2RxF B2R1F B2R1F B2R2F B2R3F B2R4F B2R4F B2R5F B2R5F

PBExF PBE1F PBE2F PBE3F PBE4F PBE5F PBE6F PBE7F PBE8F

SSLxF SSL1F SSL1F SSL2F SSL3F SSL4F SSL4F SSL5F SSL5F

S2ZxF S2Z1F S2Z1F S2Z2F S2Z3F S2Z4F S2Z4F S2Z5F S2Z5F

VRFxF VRF1F VRF2F VRF3F VRF4F VRF5F VRF6F VRF7F VRF8F

PMMxF PMM1F PMM1F PMM2F PMM3F PMM4F PMM4F PMM5F PMM5F

PMCxF PMC1F PMC1F PMC2F PMC3F PMC4F PMC4F PMC5F PMC5F

SAPxF SAP1F SAP1F SAP2F SAP3F SAP4F SAP4F SAP5F SAP5F

GMDxF GMD1F GMD1F GMD2F GMD3F GMD4F GMD4F GMD5F GMD5F

GAPxF GAP1F GAP1F GAP2F GAP3F GAP4F GAP4F GAP5F GAP5F

FPIxF FPI1F FPI1F FPI2F FPI3F FPI4F FPI4F FPI5F FPI5F

PX PX

PCT2 PCT2(*)

RG RG

TABLE SHOWING ACCESSORY COMPATIBILITY:

* ACTIV

ATIO

N W

ITH

RELAY (

NO

T S

UPPLIE

D)

PBExF Section with electric post-heating coilThe electric coil consists of armoured heaters fitted with a double safety thermostat.

SSLxF Module with silencer baffles Galvanised steel section complete with silencer baffles in rock wool covered with a polyethylene film to prevent scaling.

S2ZxF 2-area damper (70-30%)Galvanised steel damper with opposed fins for mixing the flow of external air and the flow of fresh air. Fin pitch 50mm; galvanised steel adjustment pin, 8mm, can be motor-driven.

VRFxF Fan intake section with G4 filterFan unit to be positioned at the intake point, with the accessory M3SxF, contained in a galvanised steel section fitted with flat filters with an efficiency level of G4 (EN779)

PMMxF Plenum with multiple circular delivery points

PMCxF Closed supply plenum

SAPxF Suction damperAir calibration damper with galvanised steel fins. Fin pitch 50mm; galvanised steel adjustment pin, 8mm, can be motor-driven.

GMDxF Delivery grille with adjustable finsGrille with double row of fins that can be adjusted when emitting air into the room. Can be installed directly on the equipment (removing the flanges) or on the wall.

GAPxF Suction grilleWith fins fixed at an angle of 45°; can be installed directly on the equipment (removing the flanges) or on the wall.

FPIxF Frame filter (filter already in units)

PX Selector-only control panel

PCT2 Selector/thermostat/switch control panel

RG Adjustment kit complete with electrical and power panelThe control kit allows for the control of the functions of the unit and it includes: microprocessor control with LCD room terminal. The controller with 230Vac supply and 8VA power input (without additional loads), IP30 protection class (with dedicated protections) is equipped with 2 phase-cut outputs, 10 ON/OFF outputs (relay type) under voltage (230Vac), 4 0..10V outputs, 8 digital inputs, 4 NTC inputs and 4 universal inputs.The LDC teminal visualises the state of operation of the unit and any malfunctioning, besides controlling the settings of the unit.Tthe control, based upon the retun sensor, controls the 3-way valve ON/OFF type 230Vac, 2-stages electric batteries (with a dedicated electric power board), actuators for dampers type ON/OFF 230Vac, filters pressure switches, humidity sensor.

Air conditioning units - FTA range

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

Compatibility of accessories

The diagrams showing the various ways of combining the accessories with the standard units can be found below. The selection of a suction/supply accessory module precludes the choice of other accessories in the vertical direction, but not in the horizontal direction.

For example: if the “SAPxF” accessory is used at the suction point, it is not compatible with accessory “S2ZxF” but can be used with accessory “SSLxF” or “FTPxF”. The diagrams show a horizontal and vertical configuration of the unit respectively.

The diagrams may not fully represent all the available combinations: you are, however, advised to respect the rules laid out and to contact the Fast Technical/Sales Office if necessary.

HORIZONTAL

NB:- Warning: for safety reasons, you are advised to avoid positioning the FTFxF “Pocket filters” module near the PBExF module.- Warning: when using the PBExF accessory, the unit delivery must not fall below 60% of normal envisaged delivery.- The VRFxF accessory is fitted with an electronic rotation speed variator.- The M3SxF accessory must be combined with the VRFxF accessory.- The VRFxF accessory can be selected even if it is not combined with the M3SxF accessory.

PBExF

PLENUM WITH

ELECTRICAL COIL

SSLxF

SILENCERS

PMCxF

CLOSED

PLENUM

PMMxF

PLENUM WITH

MULTIPLE CIRCULAR

INTAKE

SAPxF

DAMPER

GMDxF

SUPPLY

GRILLE

M2SxF

2 WAY MIXING

BOX

SSLxF

SILENCER

2 D

AM

PE

R

INTAKE UNIT SUPPLY

FTFxF

PBExF

PLENUM WITH

ELECTRICAL

COIL

SSLxF

SILENCERS

or

Type 3, 4 , 6 Type A, B

Accessories B1R, B2R

Accessories B1R, B2R

or

type 3, 4 , 6 type A, B

FPIxF

FILTER FRAME

FTFxF

BAG FILTERS

PMCxF

CLOSED

PLENUM

PMMxF

PLENUM WITH

MULTIPLE CIRCULAR

INTAKE

SAPxF

DAMPER

GMDxF

SUPPLY

GRILLE

FTFxF

BAG FILTERS

M3SxF

3 WAY MIXING

BOX

VRFxF

EXHAUST

SECTION

FTFxF

BAG FILTERS

SSLxF

SILENCERS

GAPxF

INTAKE GRILLE

SAPxF

DAMPER

3 D

AM

PE

R

SSLxF

SILENCER

GAPxF

INTAKE GRILLE

SAPxF

DAMPER

FTFxF

BAG FILTERS

S2ZxF

2 WAY MIXING BOX

UN

IQU

E F

LO

W O

R

2 F

RO

NTA

L D

AM

PE

R

BAG FILTERS

Air conditioning units - FTA range

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

VERTICAL

NB:- Warning: for safety reasons, you are advised to avoid positioning the FTFxF “Pocket filters” module near the PBExF module.- Warning: when using the PBExF accessory, the unit delivery must not fall below 60% of normal envisaged delivery.- The VRFxF accessory is fitted with an electronic rotation speed variator.- The M3SxF accessory must be combined with the VRFxF accessory.- The VRFxF accessory can be selected even if it is not combined with the M3SxF accessory.

PBExF

PLENUM WITH

ELECTRICAL

COIL

SSLxF

SILENCERS

PMCxF

CLOSED

PLENUM

PMMxF

PLENUM WITH

MULTIPLE CIRCULAR

INTAKE

SAPxF

DAMPER

GMDxF

SUPPLY

GRILLE

NOTHING

UNIT SUPPLY

PBExF

PLENUM WITH

ELECTRICAL

COIL

SSLxF

SILENCERS

PMCxF

CLOSED

PLENUM

PMMxF

PLENUM WITH

MULTIPLE CIRCULAR

INTAKE

SAPxF

DAMPER

GMDxF

SUPPLY

GRILLE

or

type 3, 4 , 6 type A, B

Accessories B1R, B2R

accessories B1R, B2R

oppure

type 3, 4 , 6 type A, B

M2SxF

2 WAY MIXING

BOX

SSLxF

SILENCERS

2 D

AM

PE

R FTFxF

BAG FILTERS

M3SxF

3 WAY MIXING

BOX

VRFxF FTFxF

BAG FILTERS

SSLxF

SILENCERS

GAPxF

INTAKE GRILLE

SAPxF

DAMPER

3 D

AM

PE

R

SSLxF

SILENCERS

GAPxF

INTAKE GRILLE

SAPxF

DAMPER

FTFxF

BAG FILTERS

S2ZxF

2 WAY MIXING BOX

FPIxF

FILTER FRAME

INTAKE

UN

IQU

E F

LO

W O

R

2 F

RO

NTA

L D

AM

PE

R

EXHAUST

SECTION

Air conditioning units - FTA range

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

Air conditioning units - FTA range

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

Nominal technical data

Model FTA 09 FTA 11 FTA 15 FTA 19 FTA 24 FTA 33 FTA 40 FTA 50

Nominal air flow ratem³/h 900 1100 1500 1900 2400 3300 4000 5000

l/s 250 306 417 528 667 917 1111 1389

Effective static pressure (1) Pa 140 320 270 250 185 250 245 200

Cooling capacity with 3-row coil (2)total kW 4.7 5.3 8.2 10.3 13.8 16.9 21.4 24.7

sensible kW 3.2 3.6 5.4 6.9 9.1 11.4 14.5 16.8

Cooling capacity with 4-row coil (2)total kW 4.7 5.7 8.7 12.4 17.3 21.7 27.2 31.8

sensible kW 3.5 4.2 6.2 8.3 11.2 14.3 18.0 21.3

Cooling capacity with 6-row coil (2)total kW 5.4 6.7 11.7 15.5 20.6 26.3 33.5 39.6

sensible kW 3.9 4.7 7.5 9.8 12.8 16.6 20.9 25.0

Cooling capacity with 3-row direct

expansion coil R-407C (3)

total kW 5.1 5.5 8.4 11.0 15.2 17.5 23.8 26.1

sensible kW 3.5 3.9 5.9 7.6 10.3 12.4 16.4 18.5

Cooling capacity with 4-row direct

expansion coil R-407C (3)

total kW 5.9 6.5 9.9 12.8 17.6 20.6 27.7 30.8

sensible kW 4.0 4.5 6.6 8.6 11.5 14.0 18.3 20.9

Cooling capacity with 3-row direct

expansion coil R-410A (3)

total kW 5.7 6.3 9.6 12.5 17.0 20.0 26.8 30.0

sensible kW 3.8 4.2 6.3 8.1 10.9 13.2 17.4 19.9

Cooling capacity with 4-row direct

expansion coil R-410A (3)

total kW 6.6 7.3 11.0 14.2 19.2 23.0 30.5 34.5

sensible kW 4.2 4.7 7.0 9.1 12.1 14.8 19.4 22.3

Heating capacity with 3-row coil (4) kW 11.7 13.4 19.7 25.2 33.3 41.7 53.4 62.4

Heating capacity with 4-row coil (4) kW 14.2 16.6 23.9 30.8 40.6 52.2 65.8 78.3

Heating capacity with 6-row coil (4) kW 15.7 18.5 26.6 34.2 44.3 58.0 72.6 87.5

Heating capacity with 1-row water coil for 4-pipe

system (8)kW 5.2 5.7 9.2 11.4 15.9 18.3 25.2 27.7

Heating capacity with 2-row water coil for 4-pipe

system (8)kW 8.4 9.5 14.2 17.9 24.3 29.9 38.9 44.9

Heating capacity with 3-row coil (5) kW 4.6 5.3 7.8 9.9 13.1 16.4 21.0 24.5

Heating capacity with 4-row coil (5) kW 5.5 6.4 9.3 12.1 16.0 20.6 25.9 30.8

Heating capacity with 6-row coil (5) kW 6.1 7.2 10.5 13.6 17.6 23.0 28.9 34.8

Heating capacity with 2-row water coil for 4-pipe

system (5)kW 2.2 2.4 4.0 4.9 6.9 7.9 10.9 12.0

Heating capacity with 1-row water coil for 4-pipe

system (5)kW 3.6 4.1 6.2 7.8 10.6 13.0 16.9 19.5

Electric coil capacity kW 4 6 8 10 12 16 20 24

Number of stages of electric coil no. 2 2 2 2 2 2 2 2

Electric coil power supply Volt-Ph-Hz 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50

Fans no. 1 2 2 1 1 2 2 2

Motors no. 1 2 2 1 1 2 2 2

Total input power of fans W 357 713 713 886 874 1771 1771 2852

Input current of fans A 1.6 3.1 3.1 3.9 3.8 7.7 7.7 12.4

Fan power supply V-Ph-Hz 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50 230-1-50

Poles no. 2 2 2 4 4 4 4 4

Flat filter efficiency (6) G4 G4 G4 G4 G4 G4 G4 G4

Pocket filter efficiency (6) F6 F6 F6 F6 F6 F6 F6 F6

Sound power level (7) dB(A) 63 66 67 72 74 75 76 79

Connections

Coil manifolds Ø inches 1" 1" 1" 1" 1" 1" 1" 1"

Direct expansion coil piping in Øi mm 16 16 16 16 16 16 22 22

out Øu mm 22 22 22 22 22 22 28 28

Condensate discharge Ø inches ¾ ¾ ¾ ¾ ¾ ¾ ¾ ¾

Dimensions and weight

Height mm 300 300 300 390 390 390 390 390

Width mm 700 700 1050 1050 1475 1475 2100 2100

Length mm 700 700 700 850 850 850 1000 1000

Net weight of standard unit

3-row coil kg 27 32 43 59 77 85 132 138

4-row coil kg 28 33 45 60 78 86 135 140

6-row coil kg 30 35 47 62 81 89 139 144

note (1) at nominal flow rate with 3-row coil

note (2) Temperature of incoming air 27°C d.b. 19°C w.b.; water temperature (In-Out) 7°C 12°C

note (3) Temperature of incoming air 27°C d.b. 19°C w.b.; average evap. temp. 5°C

note (4) Temperature of incoming air 10°C; water temperature (In-Out) 70°C 60°C

note (5) Temperature of incoming air 20°C; water temperature (In-Out) 45°C 40°C

note (6) in compliance with EN 779

note (7) Sound power in compliance with UNI EN ISO 9614

note (8) Temperature of incoming air 15°C; water temperature (In-Out) 70°C 60°C

� �

Air conditioning units - FTA range

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

Sizes

DESCRIPTION 09 11 15 19 24 33 40 50

Suction grille GAPxF 2 2 2 3 3 3 4 4

Supply grille with double adjustable fins GMDxF 3 3 4 4 4 4 6 6

Suction damper SAPxF 5 5 7 9 13 13 18 18

Damper for 2 opposite areas 70/30 S2ZxF 5 5 8 10 14 14 19 19

2-damper mixing chamber M2SxF 23 23 35 37 43 43 69 69

3-damper mixing chamber M3SxF 27 27 31 40 50 50 99 99

Section of soft pocket filters FTFxF 20 20 27 29 39 39 70 70

All closed supply plenum PMCxF 15 15 20 22 28 28 54 54

Fan intake section with filter VRFxF 19 22 27 36 43 55 61 62

Plenum with multiple circular delivery points PMMxF 16 16 21 23 29 29 56 56

Section of silencers SSLxF 25 25 33 37 47 47 80 80

Plenum with 2-stage post-heating electric coil PBExF 16 16 21 23 29 30 57 58

1-row post-heating water coil B1RxF 12 12 15 16 21 21 27 27

2-row post-heating water coil B2RxF 13 13 17 19 25 25 33 33

Section of flat filters with intake at base FPIxF 3 3 5 5 6 6 7 7

The weight of the accessories is expressed in kg.

Weight of the accessories

The weights of the accessories for the

FTA units are shown below.

For further information, contact the Fast

S.p.a. Technical/Sales Office.

� !

Air conditioning units - FTA range

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

Characteristic ventilation curves

The following diagrams show the

effective static supply/pressure curves

(at the inlet) of the FTA units.

These curves refer to units with a 3-row

coil and a 0% obstruction level of the G4

filter.

For units configured or differently,

or with different accessories, it is

necessary to reduce the effective static

pressure with the values of the pressure

drops of the added components.

The values of these pressure drops can

be obtained from the tables beneath

the charts.

" # #" $ #% # #% $ #& # #& $ #$ # #'( )* + ,- ./- 0123)// .4 5 06

#$ #7 # #7 $ #& # # $ # # 8 # # 9 # # : # # ; # # 7 # # # 7 7 # #5 3 ./- 010<-

= > ? @ A @ A B C D ? E > F G H I B J KFLOW RATE m³/h 400 500 600 700 800 900 1000

Suction grille - GAPxF Pa -4 -7 -9 -12 -15 -19 -23

Anti-freeze damper - SAPxF Pa 0 0 -1 -1 -1 -1 -2

Intake silencers - SSLxF Pa -6 -10 -13 -18 -22 -28 -34

Intake fan - VRFxF Pa 445 437 419 374 305 220 87

3-damper mixing chamber - M3SxF Pa -1 -1 -2 -3 -3 -4 -5

2-damper mixing chamber - M2SxF Pa 0 0 -1 -1 -1 -1 -2

Mixing chamber with 2 front dampers - S2ZxF Pa -1 -1 -2 -2 -3 -3 -4

Soft pocket filters - FTFxF Pa -6 -9 -12 -16 -21 -25 -31

4-row coil compared with the 3-row coil Pa -7 -10 -14 -19 -24 -30 -36

6-row coil compared with the 3-row coil Pa -11 -16 -23 -30 -38 -47 -57

2-row post-heating water coil - B2RxF Pa -11 -16 -23 -30 -38 -47 -57

1-row post-heating water coil - B1RxF Pa -3 -5 -7 -9 -11 -14 -17

Electric post-heating coil - PBExF Pa -2 -3 -4 -5 -6 -8 -9

Silencers - SSLxF Pa -6 -10 -13 -18 -22 -28 -34

Soft pocket filters - FTFxF Pa -6 -9 -12 -16 -21 -25 -31

Closed supply plenum - PMCxF Pa 0 0 0 0 0 0 0

Supply plenum with circular vents - PMMxF Pa 0 0 0 -1 -1 -1 -1

Supply damper - SAPxF Pa 0 0 -1 -1 -1 -1 -2

Supply grille - GMDxF Pa -1 -2 -3 -4 -5 -6 -7

X version (without coils) Pa 11 16 23 30 38 47 57

FTA 09-3R

� L

Air conditioning units - FTA range

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

M N NM O NP N NP O NQ N NQ O NO N NRS TU V WX YZX [\]̂TZZ Y_ ` [a

NO Nb N Nb O NO N N c N N d N N e N N f N N b N N N b b N N b M N N` ^ YZX [\[gX

h i j k l k l m n o j p i q r s t m u v

FTA 11-3R

FLOW RATE m³/h 500 600 700 800 900 1000 1100 1200

Suction grille - GAPxF Pa -7 -9 -12 -15 -19 -23 -27 -32

Anti-freeze damper - SAPxF Pa -2 -3 -4 -5 -6 -7 -9 -10

Intake silencers - SSLxF Pa -10 -14 -18 -23 -29 -35 -41 -48

Intake fan - VRFxF Pa 449 444 441 437 432 429 424 411

3-damper mixing chamber - M3SxF Pa -1 -2 -3 -3 -4 -5 -6 -7

2-damper mixing chamber - M2SxF Pa -2 -3 -4 -5 -6 -7 -9 -10

Mixing chamber with 2 front dampers - S2ZxF Pa -6 -8 -11 -14 -17 -21 -25 -29

Soft pocket filters - FTFxF Pa -9 -12 -16 -21 -25 -31 -37 -43

4-row coil compared with the 3-row coil Pa -10 -14 -19 -24 -30 -36 -43 -50

6-row coil compared with the 3-row coil Pa -16 -23 -30 -38 -47 -57 -68 -79

2-row post-heating water coil - B2RxF Pa -16 -23 -30 -38 -47 -57 -67 -78

1-row post-heating water coil - B1RxF Pa -5 -7 -9 -11 -14 -17 -20 -23

Electric post-heating coil - PBExF Pa -3 -4 -5 -6 -8 -9 -11 -13

Silencers - SSLxF Pa -10 -14 -18 -23 -29 -35 -41 -48

Soft pocket filters - FTFxF Pa -9 -12 -16 -21 -25 -31 -37 -43

Closed supply plenum - PMCxF Pa 0 0 0 0 0 0 0 0

Supply plenum with circular vents - PMMxF Pa 0 0 -1 -1 -1 -1 -1 -2

Supply damper - SAPxF Pa -2 -3 -4 -5 -6 -7 -9 -10

Supply grille - GMDxF Pa -2 -3 -4 -5 -6 -7 -9 -10

X version (without coils) Pa 16 23 30 38 47 57 68 79

� �

Air conditioning units - FTA range

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

w x xw y xz x xz y x{ x x{ y xy x x

|} ~� � �� ��� ����~�� �� � ��

xy x� x x� y xy x x � x x � x x � � x x � z x x � y x x � � x x� � ��� �����

� � � � � � � � � � � � � � � � � � � �

FTA 15-3R

FLOW RATE m³/h 500 700 900 1100 1300 1500 1700

Suction grille - GAPxF Pa -5 -8 -13 -19 -26 -33 -42

Anti-freeze damper - SAPxF Pa -1 -2 -3 -4 -5 -7 -9

Intake silencers - SSLxF Pa -3 -6 -10 -14 -19 -25 -31

Intake fan - VRFxF Pa 454 446 437 429 392 339 264

3-damper mixing chamber - M3SxF Pa -1 -3 -4 -6 -8 -10 -13

2-damper mixing chamber - M2SxF Pa -1 -2 -3 -4 -5 -7 -9

Mixing chamber with 2 front dampers - S2ZxF Pa -3 -5 -8 -11 -15 -19 -24

Soft pocket filters - FTFxF Pa -9 -16 -25 -37 -49 -64 -80

4-row coil compared with the 3-row coil Pa -4 -7 -12 -17 -23 -29 -37

6-row coil compared with the 3-row coil Pa -6 -12 -19 -27 -36 -47 -59

2-row post-heating water coil - B2RxF Pa -6 -12 -19 -27 -36 -46 -58

1-row post-heating water coil - B1RxF Pa -3 -6 -9 -13 -17 -22 -28

Electric post-heating coil - PBExF Pa -1 -2 -3 -4 -6 -8 -10

Silencers - SSLxF Pa -3 -6 -10 -14 -19 -25 -31

Soft pocket filters - FTFxF Pa -9 -16 -25 -37 -49 -64 -80

Closed supply plenum - PMCxF Pa 0 0 0 0 0 0 0

Supply plenum with circular vents - PMMxF Pa 0 0 -1 -1 -1 -2 -2

Supply damper - SAPxF Pa -1 -2 -3 -4 -5 -7 -9

Supply grille - GMDxF Pa -1 -2 -3 -4 -5 -7 -9

X version (without coils) Pa 6 12 19 27 36 47 59

� �

�    � ¡  ¢    ¢ ¡  £    £ ¡  ¡    ¤¥ ¦§ ¨ ©ª «¬ª ­®̄°¦¬¬ «± ² ­³

 ¡  ´    ´ ¡  µ     ´       ´ ¢     ´ ¶     ´ ·     � �    ² ° «¬ª ­®­̧ª

¹ º » ¼ ½ ¼ ½ ¾ ¿ À » Á º Â Ã Ä Å ¾ Æ ÇFLOW RATE m³/h 700 1000 1300 1600 1900 2200

Suction grille - GAPxF Pa -5 -9 -15 -22 -30 -39

Anti-freeze damper - SAPxF Pa -1 -2 -3 -5 -6 -8

Intake silencers - SSLxF Pa -4 -7 -11 -16 -22 -28

Intake fan - VRFxF Pa 374 355 332 308 277 226

3-damper mixing chamber - M3SxF Pa -1 -2 -3 -4 -5 -7

2-damper mixing chamber - M2SxF Pa -1 -2 -3 -5 -6 -8

Mixing chamber with 2 front dampers - S2ZxF Pa -3 -5 -8 -11 -15 -20

Soft pocket filters - FTFxF Pa -16 -31 -49 -72 -98 -127

4-row coil compared with the 3-row coil Pa -4 -8 -14 -20 -27 -35

6-row coil compared with the 3-row coil Pa -7 -13 -22 -31 -43 -56

2-row post-heating water coil - B2RxF Pa -8 -15 -24 -35 -48 -62

1-row post-heating water coil - B1RxF Pa -4 -7 -11 -17 -23 -29

Electric post-heating coil - PBExF Pa -1 -2 -4 -5 -7 -9

Silencers - SSLxF Pa -4 -7 -11 -16 -22 -28

Soft pocket filters - FTFxF Pa -16 -31 -49 -72 -98 -127

Closed Supply plenum - PMCxF Pa 0 0 0 0 0 0

Supply plenum with circular vents - PMMxF Pa -1 -1 -2 -2 -3 -4

Supply damper - SAPxF Pa -1 -2 -3 -5 -6 -8

Supply grille - GMDxF Pa -1 -2 -3 -5 -6 -8

X version (without coils) Pa 7 13 22 31 43 56

Air conditioning units - FTA range

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

FTA 19-3R

� �

FLOW RATE m³/h 800 1200 1600 2000 2400 2800

Suction grille - GAPxF Pa -3 -7 -11 -17 -24 -31

Anti-freeze damper - SAPxF Pa -1 -1 -2 -4 -5 -7

Intake silencers - SSLxF Pa -3 -6 -10 -16 -22 -28

Intake fan - VRFxF Pa 387 371 350 326 291 106

3-damper mixing chamber - M3SxF Pa -1 -2 -4 -6 -8 -10

2-damper mixing chamber - M2SxF Pa -1 -1 -2 -4 -5 -7

Mixing chamber with 2 front dampers - S2ZxF Pa -2 -3 -6 -9 -12 -16

Soft pocket filters - FTFxF Pa -6 -12 -21 -31 -43 -56

4-row coil compared with the 3-row coil Pa -3 -6 -10 -14 -20 -26

6-row coil compared with the 3-row coil Pa -4 -9 -15 -23 -32 -42

2-row post-heating water coil - B2RxF Pa -5 -10 -17 -25 -35 -47

1-row post-heating water coil - B1RxF Pa -2 -5 -8 -12 -17 -22

Electric post-heating coil - PBExF Pa -1 -2 -3 -4 -5 -7

Silencers - SSLxF Pa -3 -6 -10 -16 -22 -28

Soft pocket filters - FTFxF Pa -6 -12 -21 -31 -43 -56

Closed Supply plenum - PMCxF Pa 0 0 0 0 0 0

Supply plenum with circular vents - PMMxF Pa 0 -1 -2 -2 -3 -4

Supply damper - SAPxF Pa -1 -1 -2 -4 -5 -7

Supply grille - GMDxF Pa -1 -1 -2 -4 -5 -7

X version (without coils) Pa 4 9 15 23 32 42

È É ÉÈ Ê ÉË É ÉË Ê ÉÌ É ÉÌ Ê ÉÊ É ÉÍÎ ÏÐ Ñ ÒÓ ÔÕÓ Ö×ØÙÏÕÕ ÔÚ Û ÖÜ

ÉÊ ÉÝ É ÉÝ Ê ÉÞ É É Ý É É É Ý È É É Ý Ì É É Ý ß É É Ý Þ É É È É É É È È É É È Ì É É È ß É É È Þ É ÉÛ Ù ÔÕÓ Ö×ÖàÓ

á â ã ä å ä å æ ç è ã é â ê ë ì í æ î ï

Air conditioning units - FTA range

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

FTA 24-3R

� �

ð ñ ñð ò ñó ñ ñó ò ñô ñ ñô ò ñõö ÷ø ù úû üýû þÿ��÷ýý ü� � þ�

ñò ñ� ñ ñ� ò ñ� ó ñ ñ � ò ñ ñ � � ñ ñ � � ñ ñ ð � ñ ñ ð ó ñ ñ ð ò ñ ñ ð � ñ ñ ð � ñ ñ ó � ñ ñ ó ó ñ ñ ó ò ñ ñ ó � ñ ñ� � üýû þÿþ�û

� � � � � � � � � � � � � � �

FTA 33-3R

FLOW RATE m³/h 1300 1700 2100 2500 2900 3300 3700

Suction grille - GAPxF Pa -8 -13 -19 -26 -33 -42 -52

Anti-freeze damper - SAPxF Pa 0 -1 -1 -1 -1 -2 -2

Intake silencers - SSLxF Pa -8 -12 -18 -25 -32 -41 -50

Intake fan - VRFxF Pa 369 358 343 327 314 296 275

3-damper mixing chamber - M3SxF Pa -3 -4 -6 -8 -11 -14 -17

2-damper mixing chamber - M2SxF Pa 0 -1 -1 -1 -1 -2 -2

Mixing chamber with 2 front dampers - S2ZxF Pa -4 -7 -10 -13 -17 -21 -26

Soft pocket filters - FTFxF Pa -14 -23 -34 -46 -60 -76 -93

4-row coil compared with the 3-row coil Pa -7 -11 -16 -22 -28 -35 -44

6-row coil compared with the 3-row coil Pa -11 -17 -25 -34 -45 -56 -69

2-row post-heating water coil - B2RxF Pa -12 -19 -28 -38 -50 -63 -77

1-row post-heating water coil - B1RxF Pa -6 -9 -13 -18 -24 -30 -37

Electric post-heating coil - PBExF Pa -2 -3 -4 -6 -7 -9 -12

Silencers - SSLxF Pa -8 -12 -18 -25 -32 -41 -50

Soft pocket filters - FTFxF Pa -14 -23 -34 -46 -60 -76 -93

Closed Supply plenum - PMCxF Pa 0 0 0 0 0 0 0

Supply plenum with circular vents - PMMxF Pa -1 -2 -3 -4 -5 -6 -8

Supply damper - SAPxF Pa 0 -1 -1 -1 -1 -2 -2

Supply grille - GMDxF Pa -2 -3 -4 -5 -7 -9 -11

X version (without coils) Pa 11 17 25 34 45 56 69

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

& '

( ) )( * )+ ) )+ * ), ) ), * )* ) )-. /0 1 23 453 6789/55 4: ; 6<

)* )= ) )= * )= * ) ) = > * ) ( ) ) ) ( ( * ) ( * ) ) ( > * ) + ) ) ) + ( * ) + * ) ) + > * ) , ) ) ) , ( * ) , * ) ); 9 453 676?3

@ A B C D C D E F G B H A I J K L E M N

FTA 40-3R

FLOW RATE m³/h 1500 2000 2500 3000 3500 4000 4500

Suction grille - GAPxF Pa -5 -9 -13 -18 -24 -31 -38

Anti-freeze damper - SAPxF Pa 0 0 -1 -1 -1 -1 -2

Intake silencers - SSLxF Pa -5 -8 -12 -17 -22 -28 -35

Intake fan - VRFxF Pa 370 353 333 314 292 261 206

3-damper mixing chamber - M3SxF Pa -2 -3 -4 -5 -7 -9 -11

2-damper mixing chamber - M2SxF Pa 0 0 -1 -1 -1 -1 -2

Mixing chamber with 2 front dampers - S2ZxF Pa -3 -4 -6 -9 -12 -15 -18

Soft pocket filters - FTFxF Pa -9 -15 -22 -31 -41 -52 -64

4-row coil compared with the 3-row coil Pa -4 -7 -11 -15 -19 -25 -31

6-row coil compared with the 3-row coil Pa -7 -11 -17 -23 -31 -39 -48

2-row post-heating water coil - B2RxF Pa -7 -13 -19 -26 -34 -44 -54

1-row post-heating water coil - B1RxF Pa -4 -6 -9 -12 -16 -21 -26

Electric post-heating coil - PBExF Pa -1 -2 -3 -4 -5 -7 -8

Silencers - SSLxF Pa -5 -8 -12 -17 -22 -28 -35

Soft pocket filters - FTFxF Pa -9 -15 -22 -31 -41 -52 -64

Closed Supply plenum - PMCxF Pa 0 0 0 0 0 0 0

Supply plenum with circular vents - PMMxF Pa -2 -3 -4 -6 -8 -10 -12

Supply damper - SAPxF Pa 0 0 -1 -1 -1 -1 -2

Supply grille - GMDxF Pa -1 -2 -3 -4 -5 -7 -8

X version (without coils) Pa 7 11 17 23 31 39 48

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

& O

� ò ñð ñ ñð ò ñó ñ ñó ò ñô ñ ñõö ÷ø ù úû üýû þÿ��÷ýý ü� � þ�

ñò ñ� ñ ñð ò ñ ñ ð � ò ñ ó ñ ñ ñ ó ð ò ñ ó ò ñ ñ ó � ò ñ ô ñ ñ ñ ô ð ò ñ ô ò ñ ñ ô � ò ñ ò ñ ñ ñ ò ð ò ñ ò ò ñ ñ� � üýû þÿþ�û

� � � � � � � � � � � � � � �

FTA 50-3R

FLOW RATE m³/h 2500 3000 3500 4000 4500 5000 5500

Suction grille - GAPxF Pa -13 -18 -24 -31 -38 -46 -55

Anti-freeze damper - SAPxF Pa -1 -1 -1 -1 -2 -2 -2

Intake silencers - SSLxF Pa -13 -17 -23 -29 -36 -44 -52

Intake fan - VRFxF Pa 332 322 308 295 281 259 232

3-damper mixing chamber - M3SxF Pa -4 -5 -7 -9 -11 -13 -16

2-damper mixing chamber - M2SxF Pa -1 -1 -1 -1 -2 -2 -2

Mixing chamber with 2 front dampers - S2ZxF Pa -6 -9 -12 -15 -18 -22 -27

Soft pocket filters - FTFxF Pa -22 -31 -41 -52 -64 -77 -92

4-row coil compared with the 3-row coil Pa -11 -15 -19 -25 -31 -37 -44

6-row coil compared with the 3-row coil Pa -17 -23 -31 -39 -48 -59 -69

2-row post-heating water coil - B2RxF Pa -19 -26 -34 -44 -54 -65 -78

1-row post-heating water coil - B1RxF Pa -9 -12 -16 -21 -26 -31 -37

Electric post-heating coil - PBExF Pa -3 -4 -5 -7 -8 -10 -12

Silencers - SSLxF Pa -13 -17 -23 -29 -36 -44 -52

Soft pocket filters - FTFxF Pa -22 -31 -41 -52 -64 -77 -92

Closed Supply plenum - PMCxF Pa 0 0 0 0 0 0 0

Supply plenum with circular vents - PMMxF Pa -4 -6 -8 -10 -13 -15 -18

Supply damper - SAPxF Pa -1 -1 -1 -1 -2 -2 -2

Supply grille - GMDxF Pa -3 -4 -5 -7 -8 -10 -12

X version (without coils) Pa 17 23 31 39 48 59 69

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

P Q

PRESSURE DROP DUE TO DIRT ON THE FLAT FILTERS:

PRESSURE DROP DUE TO DIRT ON THE POCKET FILTERS:

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

Pressure drops in the filters, due to dirt

The charts to determine the pressure

drops with different filter dirt levels are

shown below. From the left-hand chart

(showing the air flow rate - m³/h - on

the x co-ordinate), locate the flow rate

in question then go up until you intersect

the straight line corresponding to the

unit size. At this point, by tracing a

straight line parallel to the x co-ordinate

axis, you will intersect one of the three

curves on the right-hand chart, each

showing the degree of obstruction of the

filter, as below:

curve 1: clean filter

curve 2: filter 25% clogged

curve 3: filter 50% clogged

To determine the corresponding value of

the filter pressure drop, trace a straight

line as far as the x co-ordinate axis.

R S R RR S T RU S R RU S T RV S R RV S T RW S R RW S T RX S R RR U R R R V R R R W R R R X R R R T R R R Y R R R R S R RR S T RU S R RU S T RV S R RV S T RW S R RW S T RX S R R

R S R T R S R U R R S R U T R S R V R R S RZ [ \ ] ^ _ [ ] ^ ` a \ ^ b c d a _ c a \ ^ a e [ df ^ d _ \ c a g a h b i [ j a k f ^ d _ [ \ a ^ \l \ [ h h m \ [ ] \ c l U V W

n o p q r s

P &

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

Tables showing heat exchange coil output

On the following pages you will find the

tables concerning the performance of

the heat exchange coils for the typical

combinations of heat vector fluid

temperature and hygrothermometric

characteristics of the incoming air.

The values for the direct expansion coils

refer to operation with R407C and R410A

refrigerant.

Table showing operating limits

Temperature of coil inlet air (summer)min 21°C

max 34°C

Temperature of coil inlet air (winter) min -5°C (*)

max 24°C

Relative humidity (summer-winter)min 20%

max 90%

Temperature of coil inlet water (H2O Cold)

min 4°C

max 12°C

Thermal head H2O

min 5°C

max 8°C

Temperature of coil inlet water (H2O Hot)

min 40°C

max 80°C

Thermal head H2O

min 5°C

max 25°C

Evaporation temperaturemin 2°C

max 12°C

Key:

P Air flow rate [m³/h]

Tia Temperature of incoming air [°C]

UmRel Relative humidity (%)

Qtot Total heating capacity [kW]

Qsen Sensible heating capacity [kW]

WtrFlow Water flow rate [l/h]

WtrDP Water side pressure drops [kPa]

RefrDP Refrigerant side pressure drops [kPa]

(*) envisage anti-freeze protection

P P

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

AIR

CO

ND

ITIO

NIN

GFTA 09

Temp. inlet water: 7°C

Temp. outlet water: 12 °C

3-row coil 4-row coil 6-row coil

P (m³/h) Tia (°C) UmRel (%) Qtot (kW) Qsen (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) Qsen (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) Qsen (kW) WtrFlow (l/h) WtrDP (kPa)

400 24 50 1.4 1.3 245 3 1.7 1.5 300 1 2.1 1.6 367 1

400 27 50 2.8 1.7 490 9 2.5 1.7 437 2 3.1 2.0 534 2

400 30 50 3.9 2.1 677 16 3.9 2.2 671 3 4.1 2.3 710 3

400 33 50 5.1 2.4 879 25 5.6 2.6 956 6 5.9 2.8 1022 5

500 24 50 1.8 1.6 316 4 1.9 1.7 327 1 2.4 1.9 415 1

500 27 50 3.4 2.1 589 12 2.8 2.0 487 2 3.5 2.3 607 2

500 30 50 4.7 2.5 801 21 5.0 2.7 851 5 5.4 2.9 925 4

500 33 50 6.1 2.8 1042 34 6.8 3.2 1169 8 7.4 3.5 1266 7

600 24 50 2.3 1.9 395 6 2.2 2.0 386 2 2.7 2.2 462 2

600 27 50 3.9 2.4 667 15 3.1 2.3 530 2 3.9 2.6 671 2

600 30 50 5.3 2.8 916 27 5.9 3.2 1010 7 6.5 3.5 1113 5

600 33 50 6.9 3.2 1194 43 7.8 3.7 1343 11 8.7 4.1 1497 9

700 24 50 2.7 2.1 457 8 2.5 2.2 424 2 2.9 2.5 491 2

700 27 50 4.3 2.7 739 18 4.1 2.8 713 4 4.5 3.1 779 3

700 30 50 5.9 3.1 1015 32 6.7 3.6 1157 8 7.5 4.0 1288 7

700 33 50 7.7 3.6 1320 51 8.8 4.2 1517 13 9.9 4.7 1705 11

800 24 50 3.0 2.3 512 10 2.7 2.4 457 2 3.0 2.7 521 2

800 27 50 4.7 2.9 806 21 4.8 3.2 827 5 5.4 3.5 933 4

800 30 50 6.5 3.4 1112 38 7.4 4.0 1278 10 8.5 4.5 1454 8

800 33 50 8.4 3.9 1449 60 9.8 4.7 1682 16 11.0 5.2 1893 13

900 24 50 3.2 2.5 548 11 2.8 2.6 486 2 3.4 3.1 593 2

900 27 50 5.1 3.2 872 25 5.4 3.6 930 6 6.2 4.0 1069 5

900 30 50 7.0 3.7 1203 43 8.1 4.4 1392 11 9.2 5.0 1590 10

900 33 50 9.1 4.2 1570 70 10.7 5.1 1838 18 12.1 5.7 2082 16

1000 24 50 3.5 2.8 605 13 3.0 2.7 514 2 3.7 3.3 633 2

1000 27 50 5.4 3.4 932 28 6.0 3.9 1030 7 6.9 4.4 1188 6

1000 30 50 7.5 4.0 1290 49 8.7 4.8 1498 13 10.1 5.4 1740 11

1000 33 50 – – – – 11.5 5.5 1982 21 13.2 6.2 2265 18

AIR

CO

ND

ITIO

NIN

G

FTA 11

Temp. inlet water: 7°C

Temp. outlet water: 12 °C

3-row coil 4-row coil 6-row coil

P (m³/h) Tia (°C) UmRel (%) Qtot (kW) Qsen (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) Qsen (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) Qsen (kW) WtrFlow (l/h) WtrDP (kPa)

500 24 50 1.8 1.6 316 4 1.9 1.7 327 1 2.4 1.9 415 1

500 27 50 3.4 2.1 589 12 2.8 2.0 487 2 3.5 2.3 607 2

500 30 50 4.7 2.5 801 21 5.0 2.7 851 5 5.4 2.9 925 4

500 33 50 6.1 2.8 1042 34 6.8 3.2 1169 8 7.4 3.5 1266 7

600 24 50 2.3 1.9 395 6 2.2 2.0 386 2 2.7 2.2 462 2

600 27 50 3.9 2.4 667 15 3.1 2.3 530 2 3.9 2.6 671 2

600 30 50 5.3 2.8 916 27 5.9 3.2 1010 7 6.5 3.5 1113 5

600 33 50 6.9 3.2 1194 43 7.8 3.7 1343 11 8.7 4.1 1497 9

700 24 50 2.7 2.1 457 8 2.5 2.2 424 2 2.9 2.5 491 2

700 27 50 4.3 2.7 739 18 4.1 2.8 713 4 4.5 3.1 779 3

700 30 50 5.9 3.1 1015 32 6.7 3.6 1157 8 7.5 4.0 1288 7

700 33 50 7.7 3.6 1320 51 8.8 4.2 1517 13 9.9 4.7 1705 11

800 24 50 3.0 2.3 512 10 2.7 2.4 457 2 3.0 2.7 521 2

800 27 50 4.7 2.9 806 21 4.8 3.2 827 5 5.4 3.5 933 4

800 30 50 6.5 3.4 1112 38 7.4 4.0 1278 10 8.5 4.5 1454 8

800 33 50 8.4 3.9 1449 60 9.8 4.7 1682 16 11.0 5.2 1893 13

900 24 50 3.2 2.5 548 11 2.8 2.6 486 2 3.4 3.1 593 2

900 27 50 5.1 3.2 872 25 5.4 3.6 930 6 6.2 4.0 1069 5

900 30 50 7.0 3.7 1203 43 8.1 4.4 1392 11 9.2 5.0 1590 10

900 33 50 9.1 4.2 1570 70 10.7 5.1 1838 18 12.1 5.7 2082 16

1000 24 50 3.5 2.8 605 13 3.0 2.7 514 2 3.7 3.3 633 2

1000 27 50 5.4 3.4 932 28 6.0 3.9 1030 7 6.9 4.4 1188 6

1000 30 50 7.5 4.0 1290 49 8.7 4.8 1498 13 10.1 5.4 1740 11

1000 33 50 – – – – 11.5 5.5 1982 21 13.2 6.2 2265 18

1100 24 50 3.7 2.9 640 14 3.2 2.9 550 3 3.9 3.5 668 2

1100 27 50 5.8 3.6 989 31 6.4 4.3 1109 8 7.5 4.8 1287 7

1100 30 50 8.0 4.2 1373 55 9.3 5.1 1602 15 10.9 5.8 1869 13

1100 33 50 – – – – 12.3 5.9 2123 24 14.2 6.7 2442 20

1200 24 50 3.9 3.1 674 16 3.6 3.3 624 3 4.1 3.7 702 3

1200 27 50 6.1 3.8 1044 34 7.0 4.6 1199 9 8.2 5.2 1408 8

1200 30 50 8.4 4.5 1452 61 9.9 5.4 1704 16 11.6 6.2 1989 14

1200 33 50 – – – – 13.1 6.3 2258 27 15.2 7.2 2614 23

P t

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

AIR

CO

ND

ITIO

NIN

GFTA 15

Temp. inlet water: 7°C

Temp. outlet water: 12 °C

3-row coil 4-row coil 6-row coil

P (m³/h) Tia (°C) UmRel (%) Qtot (kW) Qsen (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) Qsen (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) Qsen (kW) WtrFlow (l/h) WtrDP (kPa)

500 24 50 2.0 1.7 347 3 2.3 1.9 395 1 3.0 2.2 516 2

500 27 50 4.0 2.4 695 10 3.4 2.3 582 1 4.5 2.7 766 4

500 30 50 5.5 2.8 942 16 4.6 2.6 788 2 6.5 3.4 1118 7

500 33 50 7.0 3.2 1200 25 7.2 3.4 1233 4 8.3 3.9 1428 10

700 24 50 3.2 2.4 552 7 2.7 2.4 463 1 3.7 2.8 634 3

700 27 50 5.2 3.1 894 15 4.0 2.9 693 2 6.3 3.8 1091 6

700 30 50 7.1 3.7 1220 26 7.3 4.0 1258 4 9.0 4.6 1540 12

700 33 50 9.1 4.2 1557 40 10.0 4.7 1719 7 11.3 5.3 1938 17

900 24 50 4.2 3.1 718 10 3.4 3.0 576 1 4.7 3.6 807 4

900 27 50 6.3 3.8 1080 21 4.5 3.4 777 2 8.2 4.8 1406 10

900 30 50 8.6 4.5 1475 36 9.3 5.0 1606 6 11.1 5.8 1911 17

900 33 50 11.0 5.1 1900 56 12.2 5.8 2102 10 14.0 6.6 2416 25

1100 24 50 4.8 3.6 834 13 3.8 3.4 648 2 6.3 4.6 1085 6

1100 27 50 7.2 4.4 1241 26 7.2 4.7 1239 4 9.9 5.8 1702 14

1100 30 50 9.8 5.1 1685 45 11.0 5.9 1896 8 13.1 6.8 2261 22

1100 33 50 – – – – 14.4 6.8 2470 13 16.6 7.8 2863 34

1300 24 50 5.4 4.0 927 16 4.1 3.7 710 2 7.5 5.4 1287 8

1300 27 50 8.1 4.9 1389 32 8.6 5.5 1482 5 11.2 6.7 1932 17

1300 30 50 11.0 5.7 1892 56 12.5 6.7 2147 10 15.1 7.9 2599 29

1300 33 50 – – – – 16.4 7.8 2813 17 19.1 8.9 3291 44

1500 24 50 5.9 4.4 1015 19 4.4 4.0 763 2 8.5 6.1 1471 11

1500 27 50 8.9 5.4 1526 38 9.9 6.3 1695 7 12.6 7.5 2169 21

1500 30 50 12.1 6.3 2085 66 13.8 7.5 2382 12 17.0 8.8 2924 35

1500 33 50 – – – – 18.2 8.6 3124 20 21.7 10.1 3730 54

1700 24 50 6.4 4.8 1098 21 5.3 4.8 908 3 9.5 6.8 1629 13

1700 27 50 9.6 5.9 1656 44 10.8 6.9 1862 8 13.9 8.3 2398 25

1700 30 50 – – – – 15.2 8.2 2611 14 18.6 9.7 3204 41

1700 33 50 – – – – 19.9 9.5 3427 24 24.0 11.2 4134 65

AIR

CO

ND

ITIO

NIN

G

FTA 19

Temp. inlet water: 7°C

Temp. outlet water: 12 °C

3-row coil 4-row coil 6-row coil

P (m³/h) Tia (°C) UmRel (%) Qtot (kW) Qsen (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) Qsen (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) Qsen (kW) WtrFlow (l/h) WtrDP (kPa)

700 24 50 2.7 2.3 466 2 3.3 2.7 567 1 4.2 3.0 725 3

700 27 50 5.4 3.3 923 7 4.8 3.2 822 2 7.0 4.0 1200 7

700 30 50 7.5 3.9 1286 12 8.0 4.3 1383 5 9.3 4.8 1608 12

700 33 50 9.6 4.5 1642 19 10.7 5.0 1836 8 11.7 5.5 2014 18

1000 24 50 4.1 3.3 703 5 3.9 3.5 667 2 6.4 4.5 1095 6

1000 27 50 7.2 4.4 1241 12 7.5 4.7 1294 4 9.8 5.7 1686 13

1000 30 50 9.8 5.1 1681 20 11.3 5.9 1939 9 12.9 6.6 2212 21

1000 33 50 12.6 5.9 2173 31 14.4 6.8 2483 13 16.1 7.5 2775 31

1300 24 50 5.5 4.2 941 7 4.8 4.4 825 2 8.3 5.8 1434 10

1300 27 50 8.7 5.3 1491 16 10.0 6.1 1712 7 12.2 7.1 2104 19

1300 30 50 11.8 6.2 2030 28 13.8 7.3 2376 12 16.1 8.3 2775 31

1300 33 50 15.4 7.1 2648 44 17.9 8.4 3081 19 20.3 9.5 3488 46

1600 24 50 6.6 5.0 1128 10 6.0 5.4 1026 3 10.1 7.0 1736 14

1600 27 50 10.0 6.1 1719 21 11.9 7.3 2044 9 14.5 8.5 2489 25

1600 30 50 13.6 7.2 2345 36 16.3 8.6 2797 16 19.1 9.9 3291 42

1600 33 50 17.7 8.2 3039 56 21.1 9.9 3638 25 24.2 11.3 4161 63

1900 24 50 7.4 5.6 1267 12 7.3 6.2 1256 4 11.5 8.0 1980 17

1900 27 50 11.2 6.9 1922 25 13.4 8.3 2313 12 16.7 9.8 2869 33

1900 30 50 15.3 8.1 2637 44 18.5 9.8 3180 20 22.2 11.5 3824 54

1900 33 50 19.9 9.2 3425 70 24.0 11.3 4127 32 – – – –

2200 24 50 8.1 6.2 1387 14 8.8 7.2 1520 6 12.8 9.0 2207 21

2200 27 50 12.3 7.6 2112 30 14.9 9.3 2560 14 18.6 11.0 3196 39

2200 30 50 16.9 8.9 2907 52 20.6 11.0 3539 24 24.7 12.8 4255 65

2200 33 50 – – – – 26.8 12.6 4607 39 – – – –

P u

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

AIR

CO

ND

ITIO

NIN

GFTA 24

Temp. inlet water: 7°C

Temp. outlet water: 12 °C

3-row coil 4-row coil 6-row coil

P (m³/h) Tia (°C) UmRel (%) Qtot (kW) Qsen (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) Qsen (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) Qsen (kW) WtrFlow (l/h) WtrDP (kPa)

800 24 50 3.3 2.8 567 2 4.1 3.2 702 1 5.1 3.6 878 3

800 27 50 5.8 3.7 1001 4 5.9 3.8 1021 2 8.1 4.7 1398 6

800 30 50 8.9 4.7 1532 7 9.9 5.2 1707 5 10.9 5.6 1882 9

800 33 50 11.5 5.4 1979 11 12.9 6.0 2214 8 13.7 6.4 2358 13

1200 24 50 4.3 3.9 732 2 5.0 4.3 865 2 7.9 5.5 1351 5

1200 27 50 9.0 5.4 1548 7 10.4 6.2 1795 6 12.2 7.0 2098 11

1200 30 50 12.3 6.4 2118 12 14.5 7.5 2493 10 16.0 8.2 2746 17

1200 33 50 15.9 7.4 2734 19 18.4 8.6 3158 15 19.9 9.3 3427 26

1600 24 50 6.3 5.1 1076 4 6.3 5.7 1081 3 10.8 7.4 1861 9

1600 27 50 11.3 6.8 1942 11 13.4 8.1 2313 9 15.7 9.1 2706 17

1600 30 50 15.3 8.0 2638 18 18.3 9.6 3150 15 20.6 10.6 3538 27

1600 33 50 19.8 9.2 3414 29 23.4 10.9 4019 23 25.7 12.0 4430 40

2000 24 50 8.3 6.4 1420 6 10.0 7.6 1727 5 13.4 9.1 2297 13

2000 27 50 13.2 8.0 2265 14 16.3 9.8 2796 12 18.9 11.0 3255 23

2000 30 50 18.0 9.4 3089 24 22.0 11.5 3779 21 24.9 12.8 4276 38

2000 33 50 23.2 10.8 3991 38 28.2 13.2 4849 32 31.3 14.6 5378 56

2400 24 50 9.8 7.4 1678 8 11.9 8.9 2046 7 15.4 10.6 2654 16

2400 27 50 14.9 9.1 2567 17 18.6 11.2 3201 16 22.1 12.8 3797 31

2400 30 50 20.4 10.7 3506 30 25.2 13.2 4335 26 28.9 14.9 4978 49

2400 33 50 26.4 12.2 4544 48 32.7 15.3 5619 42 – – – –

2800 24 50 10.9 8.3 1870 10 14.0 10.3 2400 9 17.4 12.0 2984 20

2800 27 50 16.5 10.1 2837 21 20.9 12.7 3589 19 25.1 14.6 4315 38

2800 30 50 22.6 11.9 3893 36 28.3 14.9 4871 32 33.2 17.1 5716 63

2800 33 50 29.4 13.6 5058 58 36.5 17.1 6272 51 – – – –

AIR

CO

ND

ITIO

NIN

G

FTA 33

Temp. inlet water: 7°C

Temp. outlet water: 12 °C

3-row coil 4-row coil 6-row coil

P (m³/h) Tia (°C) UmRel (%) Qtot (kW) Qsen (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) Qsen (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) Qsen (kW) WtrFlow (l/h) WtrDP (kPa)

1300 24 50 4.5 4.0 766 2 5.2 4.6 895 2 8.7 6.0 1494 6

1300 27 50 9.6 5.8 1660 8 11.3 6.7 1943 7 13.1 7.6 2262 12

1300 30 50 13.1 6.9 2253 14 15.5 8.1 2663 11 17.1 8.8 2947 20

1300 33 50 16.9 7.9 2910 22 19.7 9.2 3383 17 21.4 10.0 3682 29

1700 24 50 6.9 5.5 1180 5 7.1 6.3 1229 3 11.5 7.8 1975 10

1700 27 50 11.8 7.1 2026 12 14.1 8.5 2432 10 16.6 9.6 2847 18

1700 30 50 16.1 8.4 2761 20 19.2 10.1 3311 16 21.6 11.1 3724 30

1700 33 50 20.8 9.6 3575 31 24.6 11.5 4224 25 27.2 12.7 4672 44

2100 24 50 8.7 6.6 1488 7 10.6 8.0 1827 6 13.9 9.5 2394 14

2100 27 50 13.6 8.3 2335 15 16.9 10.1 2902 13 19.7 11.5 3394 25

2100 30 50 18.6 9.7 3197 26 22.8 12.0 3929 22 25.9 13.4 4454 40

2100 33 50 24.0 11.1 4134 40 29.3 13.7 5046 35 32.6 15.2 5608 61

2500 24 50 10.1 7.7 1737 9 12.7 9.4 2179 8 15.9 10.9 2739 17

2500 27 50 15.3 9.4 2637 18 19.2 11.6 3302 16 22.8 13.3 3929 32

2500 30 50 21.0 11.0 3606 32 26.0 13.7 4473 28 29.9 15.5 5148 52

2500 33 50 27.2 12.6 4676 50 33.4 15.6 5746 44 – – – –

2900 24 50 11.1 8.5 1912 10 14.3 10.6 2460 10 17.8 12.3 3065 21

2900 27 50 16.9 10.4 2903 22 21.4 13.0 3682 20 25.5 14.9 4390 39

2900 30 50 23.2 12.2 3986 38 29.1 15.3 5001 34 34.2 17.6 5885 66

2900 33 50 30.1 13.9 5181 61 37.5 17.5 6443 53 – – – –

3300 24 50 12.0 9.3 2069 12 15.6 11.7 2684 11 19.6 13.7 3380 25

3300 27 50 18.3 11.3 3155 25 23.5 14.3 4037 23 28.2 16.6 4855 47

3300 30 50 25.3 13.3 4344 44 32.0 16.9 5502 40 – – – –

3300 33 50 – – – – 41.3 19.3 7105 64 – – – –

3700 24 50 12.8 9.9 2201 13 16.8 12.7 2897 13 21.3 14.9 3669 29

3700 27 50 19.7 12.2 3392 28 25.4 15.6 4376 27 30.8 18.1 5300 55

3700 30 50 27.2 14.3 4681 51 34.8 18.3 5980 47 – – – –

3700 33 50 – – – – – – – – – – – –

P v

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

AIR

CO

ND

ITIO

NIN

GFTA 40

Temp. inlet water: 7°C

Temp. outlet water: 12 °C

3-row coil 4-row coil 6-row coil

P (m³/h) Tia (°C) UmRel (%) Qtot (kW) Qsen (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) Qsen (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) Qsen (kW) WtrFlow (l/h) WtrDP (kPa)

1500 24 50 5.4 4.9 924 1 6.2 5.4 1060 1 7.9 6.1 1359 3

1500 27 50 9.5 6.3 1642 3 9.2 6.5 1580 2 15.3 8.8 2624 7

1500 30 50 15.5 8.2 2661 6 17.5 9.2 3011 5 20.3 10.4 3490 11

1500 33 50 20.3 9.5 3498 10 23.3 10.9 4006 8 25.3 11.8 4345 17

2000 24 50 6.3 5.7 1087 2 7.8 7.1 1345 1 13.1 9.1 2253 5

2000 27 50 13.8 8.6 2382 5 15.8 9.8 2718 4 20.1 11.6 3463 11

2000 30 50 19.5 10.3 3362 9 23.3 12.2 4012 8 26.2 13.5 4511 18

2000 33 50 25.4 11.9 4369 14 29.7 13.9 5107 11 32.8 15.3 5640 26

2500 24 50 7.1 6.4 1220 2 8.9 8.1 1535 2 16.7 11.4 2879 8

2500 27 50 16.9 10.4 2914 7 20.3 12.3 3485 6 24.3 14.1 4188 16

2500 30 50 23.1 12.2 3978 12 27.8 14.6 4781 10 31.8 16.4 5478 25

2500 33 50 30.1 14.0 5179 20 35.8 16.8 6158 16 40.0 18.6 6873 37

3000 24 50 9.5 8.7 1638 3 9.9 9.0 1696 2 19.9 13.5 3427 11

3000 27 50 19.2 11.8 3303 9 23.8 14.4 4089 8 28.3 16.4 4866 20

3000 30 50 26.4 13.9 4546 15 32.2 17.0 5540 13 37.2 19.2 6395 33

3000 33 50 34.2 15.9 5878 25 41.6 19.5 7149 21 46.8 21.8 8049 49

3500 24 50 12.0 10.1 2063 4 13.8 12.5 2365 3 22.5 15.4 3879 14

3500 27 50 21.3 13.2 3663 11 26.6 16.2 4584 10 32.2 18.8 5543 26

3500 30 50 29.3 15.5 5040 19 36.4 19.2 6258 16 42.3 21.8 7273 41

3500 33 50 38.1 17.7 6557 30 47.0 22.0 8091 26 53.3 24.9 9176 62

4000 24 50 14.0 11.4 2409 5 17.6 14.0 3031 5 25.0 17.2 4294 16

4000 27 50 23.2 14.4 3991 12 29.4 18.0 5050 11 36.0 21.0 6194 31

4000 30 50 32.1 17.0 5518 22 40.1 21.2 6896 20 47.7 24.6 8205 51

4000 33 50 41.8 19.4 7193 35 51.8 24.3 8908 31 – – – –

4500 24 50 16.0 12.6 2745 6 20.3 15.7 3491 6 27.3 18.9 4689 19

4500 27 50 25.1 15.6 4320 14 32.0 19.6 5498 13 39.2 23.0 6736 36

4500 30 50 34.7 18.4 5969 25 43.7 23.2 7524 23 52.6 27.1 9049 61

4500 33 50 45.3 21.0 7795 40 56.6 26.6 9743 36 – – – –

AIR

CO

ND

ITIO

NIN

G

FTA 50

Temp. inlet water: 7°C

Temp. outlet water: 12 °C

3-row coil 4-row coil 6-row coil

P (m³/h) Tia (°C) UmRel (%) Qtot (kW) Qsen (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) Qsen (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) Qsen (kW) WtrFlow (l/h) WtrDP (kPa)

2500 24 50 7.1 6.4 1220 2 8.9 8.1 1535 2 16.7 11.4 2879 8

2500 27 50 16.9 10.4 2914 7 20.3 12.3 3485 6 24.3 14.1 4188 16

2500 30 50 23.1 12.2 3978 12 27.8 14.6 4781 10 31.8 16.4 5478 25

2500 33 50 30.1 14.0 5179 20 35.8 16.8 6158 16 40.0 18.6 6873 37

3000 24 50 9.5 8.7 1638 3 9.9 9.0 1696 2 19.9 13.5 3427 11

3000 27 50 19.2 11.8 3303 9 23.8 14.4 4089 8 28.3 16.4 4866 20

3000 30 50 26.4 13.9 4546 15 32.2 17.0 5540 13 37.2 19.2 6395 33

3000 33 50 34.2 15.9 5878 25 41.6 19.5 7149 21 46.8 21.8 8049 49

3500 24 50 12.0 10.1 2063 4 13.8 12.5 2365 3 22.5 15.4 3879 14

3500 27 50 21.3 13.2 3663 11 26.6 16.2 4584 10 32.2 18.8 5543 26

3500 30 50 29.3 15.5 5040 19 36.4 19.2 6258 16 42.3 21.8 7273 41

3500 33 50 38.1 17.7 6557 30 47.0 22.0 8091 26 53.3 24.9 9176 62

4000 24 50 14.0 11.4 2409 5 17.6 14.0 3031 5 25.0 17.2 4294 16

4000 27 50 23.2 14.4 3991 12 29.4 18.0 5050 11 36.0 21.0 6194 31

4000 30 50 32.1 17.0 5518 22 40.1 21.2 6896 20 47.7 24.6 8205 51

4000 33 50 41.8 19.4 7193 35 51.8 24.3 8908 31 – – – –

4500 24 50 16.0 12.6 2745 6 20.3 15.7 3491 6 27.3 18.9 4689 19

4500 27 50 25.1 15.6 4320 14 32.0 19.6 5498 13 39.2 23.0 6736 36

4500 30 50 34.7 18.4 5969 25 43.7 23.2 7524 23 52.6 27.1 9049 61

4500 33 50 45.3 21.0 7795 40 56.6 26.6 9743 36 – – – –

5000 24 50 17.4 13.7 2988 8 22.5 17.3 3879 7 29.5 20.6 5082 22

5000 27 50 26.8 16.8 4613 16 34.5 21.3 5931 15 42.5 25.0 7308 42

5000 30 50 37.2 19.7 6397 28 47.2 25.1 8126 26 56.4 29.2 9708 69

5000 33 50 48.6 22.6 8366 46 61.3 28.8 10542 42 – – – –

5500 24 50 18.4 14.6 3163 8 24.1 18.5 4138 8 31.6 22.2 5438 25

5500 27 50 28.5 17.9 4898 18 36.8 22.8 6326 17 45.7 26.9 7861 47

5500 30 50 39.6 21.0 6805 32 50.6 26.9 8703 29 – – – –

5500 33 50 51.8 24.0 8912 52 65.7 30.8 11310 47 – – – –

P w

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

HEATIN

GFTA 09

Temp. inlet water: 70°C

Temp. outlet water: 60°C

3-row coil 4-row coil 6-row coil

P (m³/h) Tia (°C) UmRel (%) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa)

400 -5 50 8.4 739 16 9.7 849 5 10.3 899 3

400 2 50 7.5 655 13 8.6 750 4 9.1 795 3

400 10 50 6.4 562 10 7.3 642 3 7.8 680 2

400 18 50 5.4 473 8 6.1 538 2 6.5 571 2

500 -5 50 10.0 876 22 11.7 1025 6 12.5 1098 5

500 2 50 8.9 777 18 10.3 906 5 11.1 970 4

500 10 50 7.6 667 14 8.9 775 4 9.5 830 3

500 18 50 6.4 561 10 7.4 650 3 8.0 697 2

600 -5 50 11.4 1003 28 13.6 1192 8 14.7 1288 6

600 2 50 10.2 890 23 12.0 1054 6 13.0 1138 5

600 10 50 8.7 764 18 10.3 902 5 11.1 974 4

600 18 50 7.3 643 13 8.6 756 4 9.3 817 3

700 -5 50 12.8 1121 34 15.4 1349 10 16.8 1469 8

700 2 50 11.4 995 28 13.6 1193 8 14.8 1299 6

700 10 50 9.8 855 21 11.7 1021 6 12.7 1112 5

700 18 50 8.2 719 16 9.8 856 5 10.7 933 4

800 -5 50 14.1 1232 41 17.1 1500 12 18.8 1644 9

800 2 50 12.5 1094 33 15.1 1327 10 16.6 1454 8

800 10 50 10.7 941 25 13.0 1136 7 14.2 1245 6

800 18 50 9.0 791 19 10.9 951 5 11.9 1044 4

900 -5 50 15.3 1338 47 18.8 1644 14 20.7 1813 11

900 2 50 13.6 1189 38 16.6 1454 11 18.3 1604 9

900 10 50 11.7 1022 29 14.2 1245 9 15.7 1373 7

900 18 50 9.8 860 22 11.9 1043 6 13.1 1151 5

1000 -5 50 16.4 1438 54 20.3 1782 16 22.6 1976 13

1000 2 50 14.6 1278 43 18.0 1577 13 20.0 1748 10

1000 10 50 12.6 1099 33 15.4 1350 10 17.1 1497 8

1000 18 50 10.6 925 24 12.9 1131 7 14.3 1255 6

HEATIN

G

FTA 11

Temp. inlet water: 70°C

Temp. outlet water: 60°C

3-row coil 4-row coil 6-row coil

P (m³/h) Tia (°C) UmRel (%) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa)

500 -5 50 10.0 876 22 11.7 1025 6 12.5 1098 5

500 2 50 8.9 777 18 10.3 906 5 11.1 970 4

500 10 50 7.6 667 14 8.9 775 4 9.5 830 3

500 18 50 6.4 561 10 7.4 650 3 8.0 697 2

600 -5 50 11.4 1003 28 13.6 1192 8 14.7 1288 6

600 2 50 10.2 890 23 12.0 1054 6 13.0 1138 5

600 10 50 8.7 764 18 10.3 902 5 11.1 974 4

600 18 50 7.3 643 13 8.6 756 4 9.3 817 3

700 -5 50 12.8 1121 34 15.4 1349 10 16.8 1469 8

700 2 50 11.4 995 28 13.6 1193 8 14.8 1299 6

700 10 50 9.8 855 21 11.7 1021 6 12.7 1112 5

700 18 50 8.2 719 16 9.8 856 5 10.7 933 4

800 -5 50 14.1 1232 41 17.1 1500 12 18.8 1644 9

800 2 50 12.5 1094 33 15.1 1327 10 16.6 1454 8

800 10 50 10.7 941 25 13.0 1136 7 14.2 1245 6

800 18 50 9.0 791 19 10.9 951 5 11.9 1044 4

900 -5 50 15.3 1338 47 18.8 1644 14 20.7 1813 11

900 2 50 13.6 1189 38 16.6 1454 11 18.3 1604 9

900 10 50 11.7 1022 29 14.2 1245 9 15.7 1373 7

900 18 50 9.8 860 22 11.9 1043 6 13.1 1151 5

1000 -5 50 16.4 1438 54 20.3 1782 16 22.6 1976 13

1000 2 50 14.6 1278 43 18.0 1577 13 20.0 1748 10

1000 10 50 12.6 1099 33 15.4 1350 10 17.1 1497 8

1000 18 50 10.6 925 24 12.9 1131 7 14.3 1255 6

1100 -5 50 17.5 1535 60 21.9 1915 18 24.4 2134 15

1100 2 50 15.6 1364 49 19.4 1695 15 21.6 1888 12

1100 10 50 13.4 1173 37 16.6 1452 11 18.5 1617 9

1100 18 50 11.3 987 27 13.9 1216 8 15.5 1356 7

1200 -5 50 18.6 1627 67 23.3 2043 20 26.1 2287 17

1200 2 50 16.5 1446 54 20.7 1809 16 23.1 2024 13

1200 10 50 14.2 1244 41 17.7 1549 13 19.8 1734 10

1200 18 50 11.9 1047 30 14.8 1297 9 16.6 1453 8

P x

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

HEATIN

GFTA 15

Temp. inlet water: 70°C

Temp. outlet water: 60°C

3-row coil 4-row coil 6-row coil

P (m³/h) Tia (°C) UmRel (%) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa)

500 -5 50 11.3 987 16 12.6 1104 3 13.2 1160 6

500 2 50 10.0 875 13 11.1 976 3 11.7 1026 5

500 10 50 8.6 751 10 9.5 835 2 10.0 879 4

500 18 50 7.2 632 7 8.0 701 2 8.4 740 3

700 -5 50 14.7 1288 25 16.9 1481 5 18.1 1582 11

700 2 50 13.0 1143 21 14.9 1309 4 16.0 1399 9

700 10 50 11.2 982 16 12.8 1121 3 13.7 1199 7

700 18 50 9.4 826 12 10.7 940 2 11.5 1009 5

900 -5 50 17.8 1558 36 20.9 1830 7 22.6 1982 16

900 2 50 15.8 1383 29 18.5 1619 6 20.0 1753 13

900 10 50 13.6 1189 22 15.8 1386 5 17.2 1503 10

900 18 50 11.4 1001 16 13.3 1162 3 14.4 1264 7

1100 -5 50 20.6 1806 46 24.6 2156 10 27.0 2361 22

1100 2 50 18.3 1604 37 21.8 1908 8 23.9 2089 18

1100 10 50 15.8 1379 29 18.7 1634 6 20.5 1792 13

1100 18 50 13.3 1161 21 15.6 1370 4 17.2 1507 10

1300 -5 50 23.2 2035 57 28.1 2464 12 31.1 2723 28

1300 2 50 20.6 1809 46 24.9 2181 10 27.5 2411 23

1300 10 50 17.8 1556 35 21.3 1868 7 23.6 2068 17

1300 18 50 15.0 1310 26 17.9 1566 6 19.9 1739 13

1500 -5 50 25.7 2250 69 31.5 2755 15 35.1 3070 35

1500 2 50 22.8 2000 56 27.8 2439 12 31.0 2719 28

1500 10 50 19.7 1721 42 23.9 2090 9 26.6 2332 21

1500 18 50 16.6 1450 31 20.0 1752 7 22.4 1961 16

1700 -5 50 – – – 34.6 3033 17 38.9 3403 42

1700 2 50 24.9 2181 65 30.7 2686 14 34.4 3015 34

1700 10 50 21.4 1878 50 26.3 2301 11 29.5 2587 26

1700 18 50 18.1 1581 37 22.0 1929 8 24.8 2175 19

HEATIN

G

FTA 19

Temp. inlet water: 70°C

Temp. outlet water: 60°C

3-row coil 4-row coil 6-row coil

P (m³/h) Tia (°C) UmRel (%) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa)

700 -5 50 15.6 1365 12 17.6 1545 5 18.5 1622 11

700 2 50 13.8 1210 10 15.6 1366 4 16.4 1434 9

700 10 50 11.9 1039 8 13.4 1170 3 14.0 1230 7

700 18 50 10.0 874 6 11.2 982 3 11.8 1035 5

1000 -5 50 20.6 1805 20 24.0 2106 9 25.7 2251 19

1000 2 50 18.3 1601 16 21.3 1863 7 22.7 1991 15

1000 10 50 15.7 1375 13 18.2 1596 6 19.5 1707 12

1000 18 50 13.2 1157 9 15.3 1340 4 16.4 1437 9

1300 -5 50 25.1 2197 29 29.9 2623 13 32.5 2843 29

1300 2 50 22.3 1950 23 26.5 2321 11 28.7 2516 23

1300 10 50 19.1 1676 18 22.7 1989 8 24.6 2158 18

1300 18 50 16.1 1410 13 19.1 1670 6 20.7 1816 13

1600 -5 50 29.2 2554 38 35.4 3104 18 38.9 3403 39

1600 2 50 25.9 2268 30 31.4 2748 14 34.4 3013 32

1600 10 50 22.3 1950 23 26.9 2356 11 29.5 2585 24

1600 18 50 18.7 1641 17 22.6 1977 8 24.8 2175 18

1900 -5 50 32.9 2884 47 40.6 3556 22 44.9 3936 51

1900 2 50 29.3 2562 38 36.0 3149 18 39.8 3487 41

1900 10 50 25.2 2204 29 30.8 2700 14 34.2 2992 31

1900 18 50 21.2 1855 21 25.9 2267 10 28.7 2517 23

2200 -5 50 36.4 3191 56 45.5 3983 27 50.8 4446 63

2200 2 50 32.4 2837 45 40.3 3529 22 45.0 3939 51

2200 10 50 27.9 2441 35 34.6 3026 17 38.6 3381 39

2200 18 50 23.5 2054 25 29.0 2540 12 32.5 2845 29

P '

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

HEATIN

GFTA 24

Temp. inlet water: 70°C

Temp. outlet water: 60°C

3-row coil 4-row coil 6-row coil

P (m³/h) Tia (°C) UmRel (%) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa)

800 -5 50 18.7 1638 7 20.8 1820 5 21.5 1884 8

800 2 50 16.6 1451 6 18.4 1609 4 19.0 1665 7

800 10 50 14.2 1245 5 15.7 1379 3 16.3 1428 5

800 18 50 11.9 1047 4 13.2 1159 3 13.7 1202 4

1200 -5 50 26.0 2273 13 29.9 2616 10 31.5 2756 16

1200 2 50 23.0 2015 10 26.4 2314 8 27.8 2438 13

1200 10 50 19.8 1730 8 22.6 1984 6 23.9 2090 10

1200 18 50 16.6 1455 6 19.0 1667 5 20.1 1759 7

1600 -5 50 32.4 2837 19 38.3 3351 15 40.9 3581 25

1600 2 50 28.7 2517 15 33.9 2966 12 36.2 3168 20

1600 10 50 24.7 2163 12 29.0 2543 9 31.0 2718 15

1600 18 50 20.8 1819 9 24.4 2137 7 26.1 2287 11

2000 -5 50 38.2 3350 25 46.1 4036 21 49.8 4364 35

2000 2 50 33.9 2973 21 40.8 3574 17 44.1 3863 28

2000 10 50 29.2 2555 16 35.0 3065 13 37.8 3314 21

2000 18 50 24.5 2150 12 29.4 2576 10 31.8 2789 16

2400 -5 50 43.6 3822 32 53.4 4680 28 58.3 5109 46

2400 2 50 38.8 3394 26 47.3 4146 22 51.7 4525 37

2400 10 50 33.3 2918 20 40.6 3557 17 44.3 3883 28

2400 18 50 28.0 2455 15 34.1 2989 13 37.3 3268 21

2800 -5 50 48.7 4261 39 60.4 5289 34 66.5 5822 58

2800 2 50 43.2 3786 32 53.5 4688 28 58.9 5158 47

2800 10 50 37.2 3256 24 45.9 4023 21 50.6 4428 36

2800 18 50 31.3 2741 18 38.6 3380 16 42.5 3726 26

HEATIN

G

FTA 33

Temp. inlet water: 70°C

Temp. outlet water: 60°C

3-row coil 4-row coil 6-row coil

P (m³/h) Tia (°C) UmRel (%) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa)

1300 -5 50 27.6 2420 14 32.0 2805 11 33.9 2967 18

1300 2 50 24.5 2146 12 28.3 2482 9 30.0 2624 14

1300 10 50 21.0 1843 9 24.3 2127 7 25.7 2250 11

1300 18 50 17.7 1550 7 20.4 1788 5 21.6 1894 8

1700 -5 50 33.9 2969 21 40.3 3526 17 43.2 3780 27

1700 2 50 30.1 2635 17 35.6 3122 13 38.2 3345 22

1700 10 50 25.9 2264 13 30.6 2677 10 32.8 2869 17

1700 18 50 21.7 1905 9 25.7 2250 8 27.6 2415 12

2100 -5 50 39.6 3471 27 48.0 4200 23 52.0 4553 38

2100 2 50 35.2 3082 22 42.5 3720 18 46.0 4031 30

2100 10 50 30.2 2649 17 36.4 3191 14 39.5 3459 23

2100 18 50 25.4 2229 12 30.6 2682 10 33.2 2911 17

2500 -5 50 44.9 3934 34 55.2 4836 29 60.4 5290 49

2500 2 50 39.9 3495 27 48.9 4284 24 53.5 4685 40

2500 10 50 34.3 3005 21 42.0 3675 18 45.9 4021 30

2500 18 50 28.9 2529 15 35.3 3089 13 38.6 3384 22

2900 -5 50 49.9 4367 41 62.1 5437 36 68.5 5996 61

2900 2 50 44.3 3880 33 55.0 4819 29 60.7 5313 50

2900 10 50 38.1 3338 25 47.2 4135 22 52.1 4561 38

2900 18 50 32.1 2809 19 39.7 3475 16 43.8 3838 28

3300 -5 50 54.5 4774 48 68.6 6009 43 – – –

3300 2 50 48.5 4244 39 60.8 5328 35 67.5 5915 60

3300 10 50 41.7 3651 30 52.2 4573 27 58.0 5079 46

3300 18 50 35.1 3073 22 43.9 3844 19 48.8 4275 34

3700 -5 50 58.9 5160 55 74.9 6556 51 – – –

3700 2 50 52.4 4588 45 66.4 5814 41 – – –

3700 10 50 45.1 3948 34 57.0 4992 31 63.7 5579 54

3700 18 50 37.9 3323 25 47.9 4196 23 53.6 4696 40

P O

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

HEATIN

GFTA 40

Temp. inlet water: 70°C

Temp. outlet water: 60°C

3-row coil 4-row coil 6-row coil

P (m³/h) Tia (°C) UmRel (%) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa)

1500 -5 50 33.5 2933 7 38.0 3328 5 39.8 3487 10

1500 2 50 29.7 2599 5 33.6 2942 4 35.2 3083 8

1500 10 50 25.5 2230 4 28.8 2521 3 30.2 2643 6

1500 18 50 21.4 1874 3 24.2 2118 3 25.4 2225 5

2000 -5 50 42.0 3679 10 48.9 4282 8 51.9 4549 16

2000 2 50 37.2 3262 8 43.2 3788 6 45.9 4024 13

2000 10 50 32.0 2800 6 37.1 3246 5 39.4 3450 10

2000 18 50 26.9 2354 5 31.1 2727 4 33.2 2904 7

2500 -5 50 49.8 4360 13 59.1 5177 11 63.5 5564 23

2500 2 50 44.2 3867 11 52.3 4582 9 56.2 4923 19

2500 10 50 37.9 3322 8 44.8 3927 7 48.2 4222 14

2500 18 50 31.9 2792 6 37.7 3299 5 40.6 3553 11

3000 -5 50 57.0 4989 17 68.8 6022 14 74.6 6535 31

3000 2 50 50.6 4427 14 60.9 5331 11 66.0 5785 25

3000 10 50 43.4 3804 10 52.2 4571 9 56.7 4963 19

3000 18 50 36.5 3198 8 43.8 3839 6 47.7 4176 14

3500 -5 50 63.7 5577 21 77.9 6823 18 85.3 7467 39

3500 2 50 56.5 4951 17 69.0 6043 14 75.5 6612 31

3500 10 50 48.6 4254 13 59.2 5182 11 64.8 5674 24

3500 18 50 40.8 3578 9 49.7 4352 8 54.5 4775 18

4000 -5 50 70.0 6130 24 86.6 7588 21 95.5 8365 48

4000 2 50 62.2 5444 20 76.7 6722 17 84.6 7410 38

4000 10 50 53.4 4680 15 65.8 5765 13 72.6 6360 29

4000 18 50 44.9 3935 11 55.3 4843 10 61.1 5352 22

4500 -5 50 76.0 6654 28 95.0 8320 25 105.4 9232 57

4500 2 50 67.5 5911 23 84.2 7372 20 93.4 8180 46

4500 10 50 58.0 5082 17 72.2 6325 15 80.2 7023 35

4500 18 50 48.8 4274 13 60.6 5312 11 67.5 5910 26

HEATIN

G

FTA 50

Temp. inlet water: 70°C

Temp. outlet water: 60°C

3-row coil 4-row coil 6-row coil

P (m³/h) Tia (°C) UmRel (%) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa)

2500 -5 50 49.8 4360 13 59.1 5177 11 63.5 5564 23

2500 2 50 44.2 3867 11 52.3 4582 9 56.2 4923 19

2500 10 50 37.9 3322 8 44.8 3927 7 48.2 4222 14

2500 18 50 31.9 2792 6 37.7 3299 5 40.6 3553 11

3000 -5 50 57.0 4989 17 68.8 6022 14 74.6 6535 31

3000 2 50 50.6 4427 14 60.9 5331 11 66.0 5785 25

3000 10 50 43.4 3804 10 52.2 4571 9 56.7 4963 19

3000 18 50 36.5 3198 8 43.8 3839 6 47.7 4176 14

3500 -5 50 63.7 5577 21 77.9 6823 18 85.3 7467 39

3500 2 50 56.5 4951 17 69.0 6043 14 75.5 6612 31

3500 10 50 48.6 4254 13 59.2 5182 11 64.8 5674 24

3500 18 50 40.8 3578 9 49.7 4352 8 54.5 4775 18

4000 -5 50 70.0 6130 24 86.6 7588 21 95.5 8365 48

4000 2 50 62.2 5444 20 76.7 6722 17 84.6 7410 38

4000 10 50 53.4 4680 15 65.8 5765 13 72.6 6360 29

4000 18 50 44.9 3935 11 55.3 4843 10 61.1 5352 22

4500 -5 50 76.0 6654 28 95.0 8320 25 105.4 9232 57

4500 2 50 67.5 5911 23 84.2 7372 20 93.4 8180 46

4500 10 50 58.0 5082 17 72.2 6325 15 80.2 7023 35

4500 18 50 48.8 4274 13 60.6 5312 11 67.5 5910 26

5000 -5 50 81.7 7153 32 103.0 9023 29 115.0 10070 66

5000 2 50 72.6 6355 26 91.3 7997 24 101.9 8925 54

5000 10 50 62.4 5465 20 78.3 6862 18 87.5 7664 41

5000 18 50 52.5 4597 15 65.8 5763 13 73.6 6450 30

5500 -5 50 87.1 7629 36 110.7 9700 33 – – –

5500 2 50 77.4 6781 29 98.2 8599 27 110.2 9648 62

5500 10 50 66.6 5832 22 84.3 7379 20 94.6 8286 47

5500 18 50 56.0 4905 16 70.8 6198 15 79.6 6974 34

t Q

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

HEATIN

GFTA 09

Temp. inlet water: 45°C

Temp. outlet water: 40°C

3-row coil 4-row coil 6-row coil

P (m³/h) Tia (°C) UmRel (%) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa)

400 -5 50 5.7 984 30 6.9 1191 6 6.9 1191 6

400 2 50 4.8 825 22 5.8 997 4 5.8 997 4

400 10 50 3.7 650 15 4.5 784 3 4.5 784 3

400 18 50 2.8 480 9 3.3 579 2 3.3 579 2

500 -5 50 6.7 1167 41 8.4 1456 8 8.4 1456 8

500 2 50 5.7 979 30 7.0 1218 6 7.0 1218 6

500 10 50 4.5 771 20 5.5 957 4 5.5 957 4

500 18 50 3.3 570 12 4.1 708 3 4.1 708 3

600 -5 50 7.7 1336 52 9.9 1708 11 9.9 1708 11

600 2 50 6.5 1122 38 8.2 1429 8 8.2 1429 8

600 10 50 5.1 883 25 6.5 1123 5 6.5 1123 5

600 18 50 3.8 652 15 4.8 830 3 4.8 830 3

700 -5 50 8.6 1495 63 11.3 1951 14 11.3 1951 14

700 2 50 7.2 1255 47 9.4 1632 10 9.4 1632 10

700 10 50 5.7 989 30 7.4 1282 7 7.4 1282 7

700 18 50 4.2 730 18 5.5 946 4 5.5 946 4

800 -5 50 – – – 12.6 2184 17 12.6 2184 17

800 2 50 8.0 1381 55 10.5 1827 12 10.5 1827 12

800 10 50 6.3 1088 36 8.3 1435 8 8.3 1435 8

800 18 50 4.6 802 21 6.1 1058 5 6.1 1058 5

900 -5 50 – – – 13.9 2409 20 13.9 2409 20

900 2 50 8.7 1500 64 11.6 2016 15 11.6 2016 15

900 10 50 6.8 1182 42 9.1 1583 10 9.1 1583 10

900 18 50 5.0 871 24 6.7 1166 6 6.7 1166 6

1000 -5 50 – – – 15.2 2627 23 15.2 2627 23

1000 2 50 – – – 12.7 2198 17 12.7 2198 17

1000 10 50 7.3 1271 48 10.0 1726 11 10.0 1726 11

1000 18 50 5.4 937 28 7.3 1271 7 7.3 1271 7

HEATIN

G

FTA 11

Temp. inlet water: 45°C

Temp. outlet water: 40°C

3-row coil 4-row coil 6-row coil

P (m³/h) Tia (°C) UmRel (%) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa)

500 -5 50 6.7 1167 41 8.4 1456 8 8.4 1456 8

500 2 50 5.7 979 30 7.0 1218 6 7.0 1218 6

500 10 50 4.5 771 20 5.5 957 4 5.5 957 4

500 18 50 3.3 570 12 4.1 708 3 4.1 708 3

600 -5 50 7.7 1336 52 9.9 1708 11 9.9 1708 11

600 2 50 6.5 1122 38 8.2 1429 8 8.2 1429 8

600 10 50 5.1 883 25 6.5 1123 5 6.5 1123 5

600 18 50 3.8 652 15 4.8 830 3 4.8 830 3

700 -5 50 8.6 1495 63 11.3 1951 14 11.3 1951 14

700 2 50 7.2 1255 47 9.4 1632 10 9.4 1632 10

700 10 50 5.7 989 30 7.4 1282 7 7.4 1282 7

700 18 50 4.2 730 18 5.5 946 4 5.5 946 4

800 -5 50 – – – 12.6 2184 17 12.6 2184 17

800 2 50 8.0 1381 55 10.5 1827 12 10.5 1827 12

800 10 50 6.3 1088 36 8.3 1435 8 8.3 1435 8

800 18 50 4.6 802 21 6.1 1058 5 6.1 1058 5

900 -5 50 – – – 13.9 2409 20 13.9 2409 20

900 2 50 8.7 1500 64 11.6 2016 15 11.6 2016 15

900 10 50 6.8 1182 42 9.1 1583 10 9.1 1583 10

900 18 50 5.0 871 24 6.7 1166 6 6.7 1166 6

1000 -5 50 – – – 15.2 2627 23 15.2 2627 23

1000 2 50 – – – 12.7 2198 17 12.7 2198 17

1000 10 50 7.3 1271 48 10.0 1726 11 10.0 1726 11

1000 18 50 5.4 937 28 7.3 1271 7 7.3 1271 7

1100 -5 50 – – – 16.4 2838 27 16.4 2838 27

1100 2 50 – – – 13.7 2375 20 13.7 2375 20

1100 10 50 7.8 1356 53 10.8 1864 13 10.8 1864 13

1100 18 50 5.8 1000 31 7.9 1372 8 7.9 1372 8

1200 -5 50 – – – 17.6 3043 30 17.6 3043 30

1200 2 50 – – – 14.7 2546 22 14.7 2546 22

1200 10 50 8.3 1438 59 11.5 1998 14 11.5 1998 14

1200 18 50 6.1 1060 34 8.5 1470 8 8.5 1470 8

t &

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

HEATIN

GFTA 15

Temp. inlet water: 45°C

Temp. outlet water: 40°C

3-row coil 4-row coil 6-row coil

P (m³/h) Tia (°C) UmRel (%) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa)

500 -5 50 7.6 1313 29 8.9 1536 11 8.9 1536 11

500 2 50 6.4 1102 21 7.4 1286 8 7.4 1286 8

500 10 50 5.0 869 14 5.9 1015 6 5.9 1015 6

500 18 50 3.7 645 8 4.4 757 4 4.4 757 4

700 -5 50 9.9 1715 47 12.1 2096 20 12.1 2096 20

700 2 50 8.3 1440 34 10.1 1756 14 10.1 1756 14

700 10 50 6.6 1136 22 8.0 1385 10 8.0 1385 10

700 18 50 4.9 842 13 5.9 1031 6 5.9 1031 6

900 -5 50 12.0 2076 66 15.2 2628 29 15.2 2628 29

900 2 50 10.1 1744 48 12.7 2201 21 12.7 2201 21

900 10 50 7.9 1376 32 10.0 1736 14 10.0 1736 14

900 18 50 5.9 1019 19 7.4 1290 8 7.4 1290 8

1100 -5 50 – – – 18.1 3134 40 18.1 3134 40

1100 2 50 11.7 2024 63 15.2 2626 29 15.2 2626 29

1100 10 50 9.2 1596 41 11.9 2070 19 11.9 2070 19

1100 18 50 6.8 1181 24 8.9 1537 11 8.9 1537 11

1300 -5 50 – – – 20.9 3617 51 20.9 3617 51

1300 2 50 – – -- 17.5 3031 37 17.5 3031 37

1300 10 50 10.4 1801 51 13.8 2389 25 13.8 2389 25

1300 18 50 7.7 1332 30 10.2 1772 15 10.2 1772 15

1500 -5 50 – – – 23.5 4079 64 23.5 4079 64

1500 2 50 – – – 19.7 3420 46 19.7 3420 46

1500 10 50 11.5 1993 61 15.6 2695 30 15.6 2695 30

1500 18 50 8.5 1474 36 11.5 1998 18 11.5 1998 18

1700 -5 50 – – – – – – – – –

1700 2 50 – – – 21.9 3793 56 21.9 3793 56

1700 10 50 – – – 17.3 2989 37 17.3 2989 37

1700 18 50 9.3 1607 42 12.8 2215 22 12.8 2215 22

HEATIN

G

FTA 19

Temp. inlet water: 45°C

Temp. utlet water: 40°C

3-row coil 4-row coil 6-row coil

P (m³/h) Tia (°C) UmRel (%) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa)

700 -5 50 10.5 1816 23 12.4 2147 19 12.4 2147 19

700 2 50 8.8 1523 17 10.4 1799 14 10.4 1799 14

700 10 50 6.9 1201 11 8.2 1420 10 8.2 1420 10

700 18 50 5.1 889 7 6.1 1059 6 6.1 1059 6

1000 -5 50 13.9 2404 37 17.2 2983 35 17.2 2983 35

1000 2 50 11.6 2018 27 14.4 2500 25 14.4 2500 25

1000 10 50 9.2 1590 18 11.4 1973 17 11.4 1973 17

1000 18 50 6.8 1177 11 8.5 1469 10 8.5 1469 10

1300 -5 50 16.9 2929 53 21.8 3771 52 21.8 3771 52

1300 2 50 14.2 2459 39 18.2 3161 38 18.2 3161 38

1300 10 50 11.2 1938 25 14.4 2494 25 14.4 2494 25

1300 18 50 8.3 1433 15 10.7 1855 15 10.7 1855 15

1600 -5 50 19.7 3407 69 – – – – – –

1600 2 50 16.5 2862 51 21.9 3789 53 21.9 3789 53

1600 10 50 13.0 2256 33 17.2 2988 35 17.2 2988 35

1600 18 50 9.6 1667 19 12.8 2221 21 12.8 2221 21

1900 -5 50 – – – – – – – – –

1900 2 50 18.7 3234 63 25.3 4386 68 25.3 4386 68

1900 10 50 14.7 2550 41 20.0 3459 45 20.0 3459 45

1900 18 50 10.9 1883 24 14.8 2569 27 14.8 2569 27

2200 -5 50 – – – – – – – – –

2200 2 50 – – – – – – – – –

2200 10 50 16.3 2824 50 22.6 3909 56 22.6 3909 56

2200 18 50 12.0 2085 29 16.7 2901 33 16.7 2901 33

t P

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

HEATIN

GFTA 24

Temp. inlet water: 45°C

Temp. outlet water: 40°C

3-row coil 4-row coil 6-row coil

P (m³/h) Tia (°C) UmRel (%) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa)

800 -5 50 12.6 2177 13 14.4 2491 14 14.4 2491 14

800 2 50 10.5 1825 10 12.0 2087 11 12.0 2087 11

800 10 50 8.3 1438 6 9.5 1649 7 9.5 1649 7

800 18 50 6.2 1067 4 7.1 1231 4 7.1 1231 4

1200 -5 50 17.5 3025 23 21.1 3649 28 21.1 3649 28

1200 2 50 14.6 2538 17 17.6 3058 21 17.6 3058 21

1200 10 50 11.5 2000 11 13.9 2415 14 13.9 2415 14

1200 18 50 8.5 1481 7 10.4 1801 8 10.4 1801 8

1600 -5 50 21.8 3780 35 27.4 4746 45 27.4 4746 45

1600 2 50 18.3 3173 25 23.0 3979 33 23.0 3979 33

1600 10 50 14.4 2501 17 18.1 3140 22 18.1 3140 22

1600 18 50 10.7 1850 10 13.5 2339 13 13.5 2339 13

2000 -5 50 25.8 4466 47 33.4 5789 64 33.4 5789 64

2000 2 50 21.6 3750 34 28.0 4854 47 28.0 4854 47

2000 10 50 17.1 2955 22 22.1 3830 31 22.1 3830 31

2000 18 50 12.6 2185 13 16.4 2851 18 16.4 2851 18

2400 -5 50 29.4 5098 59 – – – – – –

2400 2 50 24.7 4283 43 32.8 5689 62 32.8 5689 62

2400 10 50 19.5 3376 28 25.9 4489 41 25.9 4489 41

2400 18 50 14.4 2493 17 19.3 3338 24 19.3 3338 24

2800 -5 50 – – – – – – – – –

2800 2 50 27.6 4779 53 – – – – – –

2800 10 50 21.7 3767 34 29.5 5120 51 29.5 5120 51

2800 18 50 16.1 2782 20 22.0 3805 30 22.0 3805 30

HEATIN

G

FTA 33

Temp. inlet water: 45°C

Temp. outlet water: 40°C

3-row coil 4-row coil 6-row coil

P (m³/h) Tia (°C) UmRel (%) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa)

1300 -5 50 18.6 3221 26 22.7 3928 32 22.7 3928 32

1300 2 50 15.6 2703 19 19.0 3293 24 19.0 3293 24

1300 10 50 12.3 2130 13 15.0 2600 16 15.0 2600 16

1300 18 50 9.1 1577 8 11.2 1938 9 11.2 1938 9

1700 -5 50 22.8 3957 38 28.9 5012 49 28.9 5012 49

1700 2 50 19.2 3322 28 24.2 4202 36 24.2 4202 36

1700 10 50 15.1 2618 18 19.1 3315 24 19.1 3315 24

1700 18 50 11.2 1937 11 14.2 2469 14 14.2 2469 14

2100 -5 50 26.7 4629 50 34.9 6042 69 34.9 6042 69

2100 2 50 22.4 3887 36 29.2 5066 50 29.2 5066 50

2100 10 50 17.7 3064 24 23.1 3998 33 23.1 3998 33

2100 18 50 13.1 2264 14 17.2 2975 20 17.2 2975 20

2500 -5 50 30.3 5249 62 – – – – – –

2500 2 50 25.4 4410 46 34.0 5892 66 34.0 5892 66

2500 10 50 20.1 3476 30 26.8 4649 43 26.8 4649 43

2500 18 50 14.8 2567 17 19.9 3457 26 19.9 3457 26

2900 -5 50 – – – – – – – – –

2900 2 50 28.3 4898 55 – – – – – –

2900 10 50 22.3 3861 36 30.4 5273 54 30.4 5273 54

2900 18 50 16.5 2851 21 22.6 3919 32 22.6 3919 32

3300 -5 50 – – – – – – – – –

3300 2 50 30.9 5358 65 – – – – – –

3300 10 50 24.4 4224 42 33.9 5873 66 33.9 5873 66

3300 18 50 18.0 3118 25 25.2 4363 39 25.2 4363 39

3700 -5 50 – – – – – – – – –

3700 2 50 – – – – – – – – –

3700 10 50 26.4 4568 49 – – – – – –

3700 18 50 19.5 3371 28 27.7 4791 46 27.7 4791 46

t t

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

HEATIN

GFTA 40

Temp. inlet water: 45°C

Temp. outlet water: 40°C

3-row coil 4-row coil 6-row coil

P (m³/h) Tia (°C) UmRel (%) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa)

1500 -5 50 22.5 3901 12 26.6 4613 18 26.6 4613 18

1500 2 50 18.9 3271 9 22.3 3866 14 22.3 3866 14

1500 10 50 14.9 2576 6 17.6 3052 9 17.6 3052 9

1500 18 50 11.0 1906 4 13.1 2278 6 13.1 2278 6

2000 -5 50 28.3 4899 18 34.8 6024 29 34.8 6024 29

2000 2 50 23.7 4109 13 29.1 5050 22 29.1 5050 22

2000 10 50 18.7 3236 9 23.0 3986 14 23.0 3986 14

2000 18 50 13.8 2392 5 17.1 2971 9 17.1 2971 9

2500 -5 50 33.5 5809 24 42.6 7375 42 42.6 7375 42

2500 2 50 28.1 4874 18 35.7 6183 31 35.7 6183 31

2500 10 50 22.2 3838 12 28.2 4879 20 28.2 4879 20

2500 18 50 16.4 2835 7 21.0 3633 12 21.0 3633 12

3000 -5 50 38.4 6651 31 50.0 8669 56 50.0 8669 56

3000 2 50 32.2 5582 23 42.0 7269 41 42.0 7269 41

3000 10 50 25.4 4396 15 33.1 5736 27 33.1 5736 27

3000 18 50 18.7 3245 9 24.6 4268 16 24.6 4268 16

3500 -5 50 42.9 7439 38 – – – – – –

3500 2 50 36.0 6246 28 48.0 8314 52 48.0 8314 52

3500 10 50 28.4 4918 18 37.9 6560 34 37.9 6560 34

3500 18 50 20.9 3629 11 28.2 4878 20 28.2 4878 20

4000 -5 50 47.2 8181 45 – – – – – –

4000 2 50 39.6 6869 33 53.8 9320 64 53.8 9320 64

4000 10 50 31.2 5410 21 42.4 7353 42 42.4 7353 42

4000 18 50 23.0 3989 12 31.5 5466 25 31.5 5466 25

4500 -5 50 51.3 8883 52 – – – – – –

4500 2 50 43.1 7461 38 – – – – – –

4500 10 50 33.9 5875 25 46.9 8120 50 46.9 8120 50

4500 18 50 25.0 4331 14 34.8 6033 29 34.8 6033 29

HEATIN

G

FTA 50

Temp. inlet water: 45°C

Temp. outlet water: 40°C

3-row coil 4-row coil 6-row coil

P (m³/h) Tia (°C) UmRel (%) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa)

2500 -5 50 33.5 5809 24 42.6 7375 42 42.6 7375 42

2500 2 50 28.1 4874 18 35.7 6183 31 35.7 6183 31

2500 10 50 22.2 3838 12 28.2 4879 20 28.2 4879 20

2500 18 50 16.4 2835 7 21.0 3633 12 21.0 3633 12

3000 -5 50 38.4 6651 31 50.0 8669 56 50.0 8669 56

3000 2 50 32.2 5582 23 42.0 7269 41 42.0 7269 41

3000 10 50 25.4 4396 15 33.1 5736 27 33.1 5736 27

3000 18 50 18.7 3245 9 24.6 4268 16 24.6 4268 16

3500 -5 50 42.9 7439 38 57.2 9913 71 – – –

3500 2 50 36.0 6246 28 48.0 8314 52 48.0 8314 52

3500 10 50 28.4 4918 18 37.9 6560 34 37.9 6560 34

3500 18 50 20.9 3629 11 28.2 4878 20 28.2 4878 20

4000 -5 50 47.2 8181 45 – – – – – –

4000 2 50 39.6 6869 33 53.8 9320 64 53.8 9320 64

4000 10 50 31.2 5410 21 42.4 7353 42 42.4 7353 42

4000 18 50 23.0 3989 12 31.5 5466 25 31.5 5466 25

4500 -5 50 51.3 8883 52 – – – – – –

4500 2 50 43.1 7461 38 – – – – – –

4500 10 50 33.9 5875 25 46.9 8120 50 46.9 8120 50

4500 18 50 25.0 4331 14 34.8 6033 29 34.8 6033 29

5000 -5 50 55.1 9551 59 – – – – – –

5000 2 50 46.3 8023 43 – – – – – –

5000 10 50 36.5 6319 28 51.2 8864 58 51.2 8864 58

5000 18 50 26.9 4656 16 38.0 6583 34 38.0 6583 34

5500 -5 50 58.8 10190 67 – – – – – –

5500 2 50 49.4 8561 49 – – – – – –

5500 10 50 38.9 6743 32 55.3 9585 67 55.3 9585 67

5500 18 50 28.7 4968 18 41.1 7116 39 41.1 7116 39

t u

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

EVAPO

RATIO

NFTA 09

Evaporation

temperature: 5°C

3-row coil

R407C

4-row coil

R407C

3-row coil

R410A

4-row coil

R410A

P (m³/h) Tia (°C) UmRel % Qtot (kW) Qsen (kW) RefrDp (kPa) Qtot (kW) Qsen (kW) RefrDp (kPa) Qtot (kW) Qsen (kW) RefrDp (kPa) Qtot (kW) Qsen (kW) RefrDp (kPa)

400 24 50 2.4 1.7 9 2.6 1.8 5 2.5 1.7 8 2.8 1.9 4

400 27 50 3.0 1.9 13 3.3 2.1 7 3.2 2.0 12 3.5 2.1 6

400 30 50 3.7 2.1 19 4.1 2.3 10 3.9 2.2 18 4.3 2.4 9

400 33 50 4.4 2.3 26 4.9 2.5 14 4.7 2.4 24 5.1 2.6 12

500 24 50 2.7 2.0 11 3.1 2.1 6 2.9 2.0 11 3.2 2.2 6

500 27 50 3.4 2.2 17 3.9 2.4 9 3.7 2.3 16 4.1 2.5 8

500 30 50 4.2 2.4 24 4.7 2.7 13 4.6 2.6 23 5.0 2.8 12

500 33 50 5.1 2.7 33 5.7 2.9 18 5.5 2.8 31 6.0 3.1 16

600 24 50 3.0 2.2 13 3.4 2.4 7 3.3 2.3 13 3.7 2.5 7

600 27 50 3.8 2.5 20 4.3 2.7 11 4.1 2.6 19 4.6 2.9 10

600 30 50 4.6 2.7 28 5.3 3.0 16 5.1 2.9 27 5.7 3.2 15

600 33 50 5.6 3.0 39 6.3 3.3 22 6.1 3.2 38 6.8 3.5 20

700 24 50 3.2 2.4 15 3.7 2.7 9 3.6 2.6 15 4.0 2.8 8

700 27 50 4.0 2.7 22 4.7 3.0 13 4.5 2.9 22 5.1 3.2 12

700 30 50 5.0 3.0 32 5.7 3.4 18 5.6 3.2 32 6.2 3.5 17

700 33 50 6.0 3.3 45 6.9 3.7 25 6.7 3.5 45 7.5 3.9 24

800 24 50 3.4 2.6 17 4.0 2.9 10 3.8 2.8 17 4.4 3.1 9

800 27 50 4.3 3.0 25 5.0 3.3 14 4.9 3.1 25 5.5 3.5 14

800 30 50 5.3 3.2 36 6.1 3.6 20 6.0 3.5 36 6.8 3.9 20

800 33 50 6.4 3.5 50 7.4 4.0 28 – – – 8.2 4.2 27

900 24 50 3.6 2.8 18 4.2 3.2 11 4.1 3.0 19 4.7 3.3 10

900 27 50 4.5 3.2 27 5.3 3.5 16 5.1 3.4 28 5.9 3.7 16

900 30 50 5.6 3.5 39 6.5 3.9 23 6.3 3.7 40 7.2 4.1 22

900 33 50 – – – 7.8 4.3 31 – – – 8.7 4.5 31

1000 24 50 3.7 3.0 19 4.4 3.4 11 4.3 3.2 20 4.9 3.6 12

1000 27 50 4.7 3.4 29 5.6 3.8 17 5.4 3.6 31 6.2 4.0 17

1000 30 50 5.8 3.7 42 6.8 4.2 25 6.7 3.9 44 7.7 4.4 25

1000 33 50 – – – 8.2 4.5 34 – – – 9.2 4.8 34

EVAPO

RATIO

N

FTA 11

Evaporation

temperature: 5°C

3-row coil

R407C

4-row coil

R407C

3-row coil

R410A

4-row coil

R410A

P (m³/h) Tia (°C) UmRel % Qtot (kW) Qsen (kW) RefrDp (kPa) Qtot (kW) Qsen (kW) RefrDp (kPa) Qtot (kW) Qsen (kW) RefrDp (kPa) Qtot (kW) Qsen (kW) RefrDp (kPa)

500 24 50 2.7 2.0 11 3.1 2.1 6 2.9 2.0 11 3.2 2.2 6

500 27 50 3.4 2.2 17 3.9 2.4 9 3.7 2.3 16 4.1 2.5 8

500 30 50 4.2 2.4 24 4.7 2.7 13 4.6 2.6 23 5.0 2.8 12

500 33 50 5.1 2.7 33 5.7 2.9 18 5.5 2.8 31 6.0 3.1 16

600 24 50 3.0 2.2 13 3.4 2.4 7 3.3 2.3 13 3.7 2.5 7

600 27 50 3.8 2.5 20 4.3 2.7 11 4.1 2.6 19 4.6 2.9 10

600 30 50 4.6 2.7 28 5.3 3.0 16 5.1 2.9 27 5.7 3.2 15

600 33 50 5.6 3.0 39 6.3 3.3 22 6.1 3.2 38 6.8 3.5 20

700 24 50 3.2 2.4 15 3.7 2.7 9 3.6 2.6 15 4.0 2.8 8

700 27 50 4.0 2.7 22 4.7 3.0 13 4.5 2.9 22 5.1 3.2 12

700 30 50 5.0 3.0 32 5.7 3.4 18 5.6 3.2 32 6.2 3.5 17

700 33 50 6.0 3.3 45 6.9 3.7 25 6.7 3.5 45 7.5 3.9 24

800 24 50 3.4 2.6 17 4.0 2.9 10 3.8 2.8 17 4.4 3.1 9

800 27 50 4.3 3.0 25 5.0 3.3 14 4.9 3.1 25 5.5 3.5 14

800 30 50 5.3 3.2 36 6.1 3.6 20 6.0 3.5 36 6.8 3.9 20

800 33 50 6.4 3.5 50 7.4 4.0 28 – – – 8.2 4.2 27

900 24 50 3.6 2.8 18 4.2 3.2 11 4.1 3.0 19 4.7 3.3 10

900 27 50 4.5 3.2 27 5.3 3.5 16 5.1 3.4 28 5.9 3.7 16

900 30 50 5.6 3.5 39 6.5 3.9 23 6.3 3.7 40 7.2 4.1 22

900 33 50 – – – 7.8 4.3 31 – – – 8.7 4.5 31

1000 24 50 3.7 3.0 19 4.4 3.4 11 4.3 3.2 20 4.9 3.6 12

1000 27 50 4.7 3.4 29 5.6 3.8 17 5.4 3.6 31 6.2 4.0 17

1000 30 50 5.8 3.7 42 6.8 4.2 25 6.7 3.9 44 7.7 4.4 25

1000 33 50 – – – 8.2 4.5 34 – – – 9.2 4.8 34

1100 24 50 3.9 3.2 21 4.6 3.6 12 4.5 3.4 22 5.2 3.8 13

1100 27 50 4.9 3.5 31 5.8 4.0 18 5.7 3.8 33 6.6 4.2 19

1100 30 50 6.0 3.9 45 7.1 4.4 26 7.0 4.2 48 8.1 4.7 27

1100 33 50 – – – 8.6 4.8 37 – – – 9.7 5.1 37

1200 24 50 4.0 3.3 22 4.8 3.8 13 4.7 3.6 24 5.4 4.0 14

1200 27 50 5.0 3.7 33 6.0 4.2 20 5.9 4.0 35 6.8 4.5 20

1200 30 50 6.2 4.1 48 7.4 4.6 28 – – – 8.4 4.9 29

1200 33 50 – – – 8.9 5.0 39 – – – 10.2 5.4 40

t v

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

EVAPO

RATIO

NFTA 15

Evaporation

temperature: 5°C

3-row coil

R407C

4-row coil

R407C

3-row coil

R410A

4-row coil

R410A

P (m³/h) Tia (°C) UmRel % Qtot (kW) Qsen (kW) RefrDp (kPa) Qtot (kW) Qsen (kW) RefrDp (kPa) Qtot (kW) Qsen (kW) RefrDp (kPa) Qtot (kW) Qsen (kW) RefrDp (kPa)

500 24 50 3.3 2.3 8 3.6 2.4 5 3.5 2.3 7 3.7 2.5 5

500 27 50 4.2 2.6 11 4.5 2.8 8 4.4 2.7 10 4.6 2.8 7

500 30 50 5.1 2.9 16 5.6 3.1 11 5.3 3.0 14 5.7 3.1 10

500 33 50 6.2 3.2 22 6.7 3.4 15 6.4 3.3 19 6.8 3.5 13

700 24 50 4.1 2.9 11 4.6 3.2 8 4.4 3.0 10 4.8 3.2 7

700 27 50 5.2 3.3 16 5.7 3.6 12 5.5 3.4 15 6.0 3.7 11

700 30 50 6.3 3.6 23 7.1 4.0 17 6.8 3.8 21 7.4 4.1 15

700 33 50 7.6 4.0 32 8.5 4.4 23 8.2 4.2 29 8.9 4.5 21

900 24 50 4.7 3.4 14 5.3 3.8 10 5.2 3.6 13 5.7 3.9 10

900 27 50 5.9 3.9 21 6.7 4.3 16 6.5 4.1 20 7.2 4.4 14

900 30 50 7.3 4.3 30 8.3 4.7 22 8.0 4.5 28 8.8 4.9 20

900 33 50 8.8 4.7 41 10.0 5.2 31 9.6 4.9 39 10.6 5.4 28

1100 24 50 5.2 3.9 16 6.0 4.3 13 5.8 4.1 16 6.5 4.5 12

1100 27 50 6.6 4.4 25 7.6 4.9 19 7.3 4.6 24 8.2 5.1 18

1100 30 50 8.1 4.8 35 9.3 5.4 27 9.0 5.1 35 10.0 5.7 26

1100 33 50 9.7 5.3 49 11.2 5.9 38 10.8 5.6 48 12.1 6.2 35

1300 24 50 5.6 4.3 19 6.5 4.8 15 6.3 4.6 19 7.2 5.1 14

1300 27 50 7.1 4.9 28 8.2 5.4 22 8.0 5.2 28 9.1 5.7 21

1300 30 50 8.7 5.3 40 10.1 6.0 32 9.8 5.7 41 11.1 6.3 31

1300 33 50 – – – 12.2 6.5 44 – – – 13.4 6.9 42

1500 24 50 6.0 4.7 21 7.0 5.3 17 6.8 5.0 21 7.8 5.6 16

1500 27 50 7.5 5.3 31 8.8 5.9 25 8.6 5.6 32 9.8 6.3 25

1500 30 50 9.3 5.8 45 10.9 6.5 36 10.6 6.2 46 12.1 6.9 35

1500 33 50 – – – 13.1 7.1 50 – – – – – –

1700 24 50 6.3 5.1 23 7.4 5.7 18 7.2 5.4 24 8.3 6.0 18

1700 27 50 7.9 5.7 34 9.4 6.4 28 9.1 6.1 36 10.5 6.8 28

1700 30 50 9.8 6.2 49 11.5 7.0 40 – – – 12.9 7.5 40

1700 33 50 – – – – – – – – – – – –

EVAPO

RATIO

N

FTA 19

Evaporation

temperature: 5°C

3-row coil

R407C

4-row coil

R407C

3-row coil

R410A

4-row coil

R410A

P (m³/h) Tia (°C) UmRel % Qtot (kW) Qsen (kW) RefrDp (kPa) Qtot (kW) Qsen (kW) RefrDp (kPa) Qtot (kW) Qsen (kW) RefrDp (kPa) Qtot (kW) Qsen (kW) RefrDp (kPa)

700 24 50 4.6 3.2 8 5.0 3.4 7 4.8 3.2 7 5.1 3.4 6

700 27 50 5.8 3.6 12 6.3 3.8 10 6.0 3.7 11 6.4 3.9 9

700 30 50 7.1 4.0 17 7.7 4.3 14 7.4 4.1 15 7.9 4.4 12

700 33 50 8.5 4.4 23 9.2 4.7 19 8.9 4.5 21 9.5 4.8 17

1000 24 50 5.7 4.1 12 6.4 4.4 10 6.1 4.2 11 6.7 4.5 9

1000 27 50 7.2 4.6 17 8.0 5.0 15 7.7 4.8 16 8.4 5.2 14

1000 30 50 8.8 5.1 25 9.8 5.6 22 9.5 5.3 23 10.3 5.8 19

1000 33 50 10.6 5.6 34 11.8 6.1 30 11.4 5.8 32 12.4 6.3 27

1300 24 50 6.5 4.8 15 7.5 5.3 13 7.2 5.1 14 8.0 5.5 12

1300 27 50 8.3 5.4 22 9.4 6.0 20 9.1 5.7 21 10.1 6.2 19

1300 30 50 10.2 6.0 32 11.6 6.7 29 11.2 6.3 31 12.4 7.0 27

1300 33 50 12.2 6.5 44 13.9 7.3 40 13.4 6.9 43 14.9 7.6 37

1600 24 50 7.2 5.5 18 8.4 6.1 16 8.1 5.8 18 9.1 6.4 16

1600 27 50 9.1 6.2 26 10.5 6.9 25 10.2 6.5 26 11.5 7.2 23

1600 30 50 11.2 6.8 38 13.0 7.6 35 12.5 7.2 38 14.1 8.0 34

1600 33 50 – – – – – – – – – – – –

1900 24 50 7.8 6.1 20 9.1 6.8 19 8.9 6.5 21 10.1 7.2 19

1900 27 50 9.8 6.8 30 11.5 7.6 29 11.2 7.3 31 12.7 8.1 28

1900 30 50 12.1 7.5 43 14.1 8.4 41 13.7 8.0 44 15.6 8.9 40

1900 33 50 – – – – – – – – – 18.9 9.8 56

2200 24 50 8.3 6.7 22 9.8 7.5 21 9.5 7.1 23 11.0 7.9 21

2200 27 50 10.5 7.4 33 12.3 8.4 32 12.0 7.9 35 13.8 8.9 32

2200 30 50 – – – – – – – – – – – –

2200 33 50 – – – – – – – – – – – –

t w

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

EVAPO

RATIO

NFTA 24

Evaporation

temperature: 5°C

3-row coil

R407C

4-row coil

R407C

3-row coil

R410A

4-row coil

R410A

P (m³/h) Tia (°C) UmRel % Qtot (kW) Qsen (kW) RefrDp (kPa) Qtot (kW) Qsen (kW) RefrDp (kPa) Qtot (kW) Qsen (kW) RefrDp (kPa) Qtot (kW) Qsen (kW) RefrDp (kPa)

800 24 50 5.7 3.9 5 6.1 4.1 4 5.8 3.9 5 6.1 4.1 3

800 27 50 7.1 4.4 8 7.6 4.6 5 7.3 4.4 7 7.7 4.6 5

800 30 50 8.7 4.9 11 9.3 5.2 8 9.0 5.0 10 9.4 5.2 6

800 33 50 10.5 5.4 15 11.2 5.7 10 10.8 5.5 13 11.3 5.8 9

1200 24 50 7.5 5.2 8 8.2 5.6 6 7.9 5.4 8 8.5 5.7 5

1200 27 50 9.4 5.9 12 10.3 6.4 9 9.9 6.1 11 10.7 6.5 8

1200 30 50 11.5 6.6 18 12.7 7.1 13 12.2 6.8 16 13.1 7.3 11

1200 33 50 13.9 7.2 25 15.2 7.8 18 14.6 7.5 22 15.7 8.0 15

1600 24 50 8.8 6.4 11 9.9 6.9 8 9.6 6.6 11 10.5 7.1 8

1600 27 50 11.1 7.2 17 12.5 7.8 12 12.0 7.5 16 13.2 8.1 11

1600 30 50 13.7 7.9 24 15.3 8.7 18 14.8 8.3 22 16.2 9.0 16

1600 33 50 16.5 8.7 33 18.5 9.6 24 17.8 9.1 31 19.5 9.9 22

2000 24 50 9.9 7.4 14 11.3 8.1 11 10.9 7.7 13 12.2 8.4 10

2000 27 50 12.5 8.3 21 14.3 9.1 16 13.8 8.7 20 15.4 9.5 15

2000 30 50 15.4 9.1 29 17.5 10.1 22 16.9 9.6 29 18.8 10.6 21

2000 33 50 18.5 9.9 41 21.1 11.1 31 20.4 10.5 40 22.7 11.6 29

2400 24 50 10.8 8.2 16 12.5 9.1 12 12.1 8.7 16 13.7 9.5 12

2400 27 50 13.6 9.2 24 15.8 10.3 19 15.3 9.8 24 17.2 10.8 18

2400 30 50 16.8 10.2 34 19.4 11.4 27 18.8 10.8 34 21.1 12.0 25

2400 33 50 20.2 11.0 48 23.3 12.4 37 22.6 11.8 48 25.5 13.1 35

2800 24 50 11.6 9.0 18 13.5 10.1 14 13.1 9.6 18 15.0 10.6 14

2800 27 50 14.6 10.1 27 17.0 11.3 21 16.6 10.7 27 18.9 11.9 21

2800 30 50 17.9 11.1 39 20.9 12.5 31 20.3 11.9 39 23.2 13.2 30

2800 33 50 21.7 12.1 54 25.3 13.6 43 24.5 12.9 55 27.9 14.4 42

EVAPO

RATIO

N

FTA 33

Evaporation

temperature: 5°C

3-row coil

R407C

4-row coil

R407C

3-row coil

R410A

4-row coil

R410A

P (m³/h) Tia (°C) UmRel % Qtot (kW) Qsen (kW) RefrDp (kPa) Qtot (kW) Qsen (kW) RefrDp (kPa) Qtot (kW) Qsen (kW) RefrDp (kPa) Qtot (kW) Qsen (kW) RefrDp (kPa)

1300 24 50 7.8 5.5 9 8.7 6.0 7 8.3 5.7 8 9.0 6.1 6

1300 27 50 9.9 6.2 14 10.9 6.8 10 10.5 6.5 12 11.4 6.9 9

1300 30 50 12.1 6.9 19 13.4 7.5 14 12.9 7.2 18 13.9 7.7 12

1300 33 50 14.6 7.6 27 16.1 8.3 19 15.5 7.9 24 16.7 8.5 17

1700 24 50 9.1 6.6 12 10.3 7.2 9 9.9 6.9 11 10.9 7.5 8

1700 27 50 11.5 7.4 18 13.0 8.2 13 12.5 7.8 17 13.8 8.5 12

1700 30 50 14.1 8.2 25 15.9 9.1 19 15.3 8.7 24 16.9 9.4 17

1700 33 50 17.0 9.0 35 19.2 9.9 26 18.5 9.5 33 20.3 10.4 24

2100 24 50 10.2 7.6 14 11.6 8.4 11 11.2 8.0 14 12.6 8.7 10

2100 27 50 12.8 8.5 21 14.7 9.4 16 14.2 9.0 21 15.9 9.8 15

2100 30 50 15.7 9.4 31 18.0 10.4 23 17.4 9.9 30 19.5 10.9 22

2100 33 50 19.0 10.2 43 21.7 11.4 33 21.0 10.9 42 23.4 12.0 30

2500 24 50 11.0 8.5 16 12.8 9.4 13 12.4 8.9 17 14.0 9.8 12

2500 27 50 13.9 9.5 25 16.1 10.5 19 15.6 10.0 25 17.7 11.1 19

2500 30 50 17.1 10.4 35 19.8 11.7 28 19.2 11.1 36 21.7 12.3 27

2500 33 50 20.6 11.3 49 23.8 12.7 38 23.1 12.1 49 26.1 13.4 37

2900 24 50 11.7 9.2 18 13.7 10.3 15 13.3 9.8 19 15.3 10.8 14

2900 27 50 14.8 10.3 28 17.3 11.6 22 16.8 11.0 28 19.2 12.2 22

2900 30 50 18.2 11.3 40 21.3 12.7 32 20.7 12.1 41 23.6 13.5 31

2900 33 50 – – – 25.7 13.9 44 – – – 28.5 14.8 43

3300 24 50 12.4 10.0 20 14.6 11.2 16 14.2 10.6 21 16.4 11.8 16

3300 27 50 15.6 11.1 30 18.4 12.5 24 17.9 11.9 32 20.6 13.2 24

3300 30 50 19.2 12.2 44 22.6 13.8 35 22.0 13.1 45 25.4 14.6 35

3300 33 50 – – – 27.3 14.9 49 – – – – – –

3700 24 50 12.9 10.6 22 15.3 12.0 18 15.0 11.3 23 17.4 12.6 18

3700 27 50 16.3 11.9 33 19.3 13.4 27 18.9 12.7 35 21.9 14.2 27

3700 30 50 20.0 13.0 47 23.8 14.7 38 23.2 13.9 50 26.9 15.7 39

3700 33 50 – – – – – – – – – – – –

t x

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

EVAPO

RATIO

NFTA 40

Evaporation

temperature: 5°C

3-row coil

R407C

4-row coil

R407C

3-row coil

R410A

4-row coil

R410A

P (m³/h) Tia (°C) UmRel % Qtot (kW) Qsen (kW) RefrDp (kPa) Qtot (kW) Qsen (kW) RefrDp (kPa) Qtot (kW) Qsen (kW) RefrDp (kPa) Qtot (kW) Qsen (kW) RefrDp (kPa)

1500 24 50 9.9 6.8 9 10.8 7.3 7 10.3 7.0 8 11.0 7.4 6

1500 27 50 12.5 7.7 13 13.5 8.3 11 13.0 7.9 11 13.9 8.4 9

1500 30 50 15.3 8.6 18 16.6 9.3 15 15.9 8.9 16 17.0 9.4 13

1500 33 50 18.4 9.5 25 19.9 10.2 21 19.2 9.8 22 20.4 10.4 18

2000 24 50 11.9 8.4 12 13.2 9.1 10 12.7 8.7 11 13.8 9.3 9

2000 27 50 15.0 9.5 18 16.6 10.3 15 16.0 9.8 16 17.3 10.6 14

2000 30 50 18.3 10.5 25 20.3 11.5 22 19.6 11.0 23 21.2 11.8 19

2000 33 50 22.1 11.5 35 24.5 12.6 30 23.6 12.0 32 25.5 13.0 27

2500 24 50 13.5 9.8 15 15.2 10.7 13 14.6 10.2 14 16.1 11.0 12

2500 27 50 17.0 11.0 22 19.1 12.1 20 18.4 11.5 21 20.3 12.5 18

2500 30 50 20.8 12.2 32 23.5 13.4 28 22.6 12.8 30 24.9 13.9 26

2500 33 50 25.1 13.3 44 28.3 14.7 39 27.3 14.0 42 30.0 15.3 35

3000 24 50 14.8 11.0 17 16.9 12.1 16 16.3 11.5 17 18.2 12.6 15

3000 27 50 18.6 12.3 26 21.3 13.6 24 20.6 13.0 25 23.0 14.2 22

3000 30 50 22.9 13.6 37 26.2 15.1 34 25.3 14.4 36 28.2 15.8 32

3000 33 50 – – – 31.5 16.5 47 – – – 33.9 17.3 44

3500 24 50 15.9 12.1 20 18.4 13.4 18 17.8 12.7 20 20.1 14.0 17

3500 27 50 20.1 13.5 30 23.2 15.1 27 22.4 14.3 29 25.3 15.8 26

3500 30 50 24.7 14.9 43 28.5 16.7 39 27.6 15.9 42 31.0 17.6 38

3500 33 50 – – – – – – – – – – – –

4000 24 50 16.9 13.1 22 19.7 14.6 21 19.1 13.9 22 21.7 15.3 20

4000 27 50 21.3 14.7 33 24.8 16.4 31 24.1 15.6 33 27.4 17.3 30

4000 30 50 26.2 16.1 47 30.5 18.1 44 29.6 17.2 48 33.6 19.1 43

4000 33 50 – – – – – – – – – – – –

4500 24 50 17.7 14.1 24 20.8 15.7 23 20.2 14.9 25 23.2 16.5 23

4500 27 50 22.4 15.7 36 26.3 17.6 34 25.5 16.7 37 29.3 18.6 34

4500 30 50 – – – 32.3 19.4 49 – – – – – –

4500 33 50 – – – – – – – – – – – –

EVAPO

RATIO

N

FTA 50

Evaporation

temperature: 5°C

3-row coil

R407C

4-row coil

R407C

3-row coil

R410A

4-row coil

R410A

P (m³/h) Tia (°C) UmRel % Qtot (kW) Qsen (kW) RefrDp (kPa) Qtot (kW) Qsen (kW) RefrDp (kPa) Qtot (kW) Qsen (kW) RefrDp (kPa) Qtot (kW) Qsen (kW) RefrDp (kPa)

2500 24 50 13.5 9.8 15 15.2 10.7 13 14.6 10.2 14 16.1 11.0 12

2500 27 50 17.0 11.0 22 19.1 12.1 20 18.4 11.5 21 20.3 12.5 18

2500 30 50 20.8 12.2 32 23.5 13.4 28 22.6 12.8 30 24.9 13.9 26

2500 33 50 25.1 13.3 44 28.3 14.7 39 27.3 14.0 42 30.0 15.3 35

3000 24 50 14.8 11.0 17 16.9 12.1 16 16.3 11.5 17 18.2 12.6 15

3000 27 50 18.6 12.3 26 21.3 13.6 24 20.6 13.0 25 23.0 14.2 22

3000 30 50 22.9 13.6 37 26.2 15.1 34 25.3 14.4 36 28.2 15.8 32

3000 33 50 – – – 31.5 16.5 47 – – – 33.9 17.3 44

3500 24 50 15.9 12.1 20 18.4 13.4 18 17.8 12.7 20 20.1 14.0 17

3500 27 50 20.1 13.5 30 23.2 15.1 27 22.4 14.3 29 25.3 15.8 26

3500 30 50 24.7 14.9 43 28.5 16.7 39 27.6 15.9 42 31.0 17.6 38

3500 33 50 – – – – – – – – – – – –

4000 24 50 16.9 13.1 22 19.7 14.6 21 19.1 13.9 22 21.7 15.3 20

4000 27 50 21.3 14.7 33 24.8 16.4 31 24.1 15.6 33 27.4 17.3 30

4000 30 50 26.2 16.1 47 30.5 18.1 44 29.6 17.2 48 33.6 19.1 43

4000 33 50 – – – – – – – – – – – –

4500 24 50 17.7 14.1 24 20.8 15.7 23 20.2 14.9 25 23.2 16.5 23

4500 27 50 22.4 15.7 36 26.3 17.6 34 25.5 16.7 37 29.3 18.6 34

4500 30 50 – – – 32.3 19.4 49 – – – – – –

4500 33 50 – – – – – – – – – – – –

5000 24 50 18.5 15.0 26 21.8 16.8 25 21.3 15.9 27 24.5 17.7 25

5000 27 50 23.3 16.7 39 27.6 18.8 37 26.9 17.8 40 31.0 19.9 37

5000 30 50 – – – – – – – – – – – –

5000 33 50 – – – – – – – – – – – –

5500 24 50 19.1 15.8 27 22.7 17.8 27 22.2 16.8 29 25.8 18.8 27

5500 27 50 24.2 17.6 41 28.7 19.9 40 28.1 18.8 44 32.5 21.1 41

5500 30 50 – – – – – – – – – – – –

5500 33 50 – – – – – – – – – – – –

t '

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

4-P

IPE S

YSTEM

HEATIN

GFTA 09 2-row coil

Temp. of inlet water: 70°C

Temp. of outlet water: 60°C

1-row coil

Temp. of inlet water: 70°C

Temp. of outlet water: 60°C

2-row coil

Temp. of inlet water: 45°C

Temp. of outlet water: 40°C

1-row coil

Temp. of inlet water: 45°C

Temp. of outlet water: 40°C

P(m³/h) Tia (°C) UmRel % Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa)

400 -5 50 7.1 622 8 5.3 462 7 4.8 830 14 3.6 617 13

400 2 50 6.3 552 6 4.7 409 6 4.0 695 10 3.0 515 10

400 10 50 5.4 473 5 4.0 350 5 3.1 544 7 2.3 402 6

400 18 50 4.5 396 4 3.3 292 3 2.3 398 4 1.7 291 4

500 -5 50 8.3 727 10 5.9 516 9 5.6 971 18 4.0 690 16

500 2 50 7.4 645 8 5.2 457 7 4.7 813 14 3.3 576 12

500 10 50 6.3 553 6 4.5 391 6 3.7 637 9 2.6 449 8

500 18 50 5.3 463 5 3.7 327 4 2.7 465 5 1.9 325 4

600 -5 50 9.4 823 13 6.4 562 10 6.3 1099 23 4.3 752 19

600 2 50 8.3 730 10 5.7 499 8 5.3 920 17 3.6 629 14

600 10 50 7.1 626 8 4.9 427 6 4.2 721 11 2.8 490 9

600 18 50 6.0 524 6 4.1 356 5 3.0 526 6 2.0 354 5

700 -5 50 10.4 912 15 6.9 603 12 7.0 1218 28 4.7 807 22

700 2 50 9.2 809 12 6.1 535 10 5.9 1020 20 3.9 675 16

700 10 50 7.9 694 9 5.2 458 7 4.6 799 13 3.0 526 10

700 18 50 6.6 581 7 4.4 383 5 3.4 583 8 2.2 380 6

800 -5 50 11.4 995 18 7.3 640 13 7.7 1330 32 4.9 856 24

800 2 50 10.1 883 14 6.5 568 11 6.4 1114 24 4.1 716 17

800 10 50 8.6 757 11 5.6 486 8 5.0 872 15 3.2 558 11

800 18 50 7.2 634 8 4.6 406 6 3.7 636 9 2.3 403 6

900 -5 50 12.3 1073 20 7.7 673 14 8.3 1435 37 5.2 901 26

900 2 50 10.9 952 16 6.8 597 12 6.9 1201 27 4.3 753 19

900 10 50 9.3 817 12 5.8 511 9 5.4 941 17 3.4 587 12

900 18 50 7.8 684 9 4.9 427 6 4.0 686 10 2.4 423 7

1000 -5 50 13.1 1147 23 8.0 703 15 8.9 1534 42 5.4 942 28

1000 2 50 11.6 1018 18 7.1 624 13 7.4 1285 30 4.5 787 21

1000 10 50 10.0 874 14 6.1 535 10 5.8 1006 20 3.5 613 13

1000 18 50 8.4 732 10 5.1 446 7 4.2 733 11 2.6 442 7

4-P

IPE S

YSTEM

HEATIN

G

FTA 11 2-row coil

Temp. of inlet water: 70°C

Temp. of outlet water: 60°C

1-row coil

Temp. of inlet water: 70°C

Temp. of outlet water: 60°C

2-row coil

Temp. of inlet water: 45°C

Temp. of outlet water: 40°C

1-row coil

Temp. of inlet water: 45°C

Temp. of outlet water: 40°C

P(m³/h) Tia (°C) UmRel % Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa)

500 -5 50 8.3 727 10 5.9 516 9 5.6 971 18 4.0 690 16

500 2 50 7.4 645 8 5.2 457 7 4.7 813 14 3.3 576 12

500 10 50 6.3 553 6 4.5 391 6 3.7 637 9 2.6 449 8

500 18 50 5.3 463 5 3.7 327 4 2.7 465 5 1.9 325 4

600 -5 50 9.4 823 13 6.4 562 10 6.3 1099 23 4.3 752 19

600 2 50 8.3 730 10 5.7 499 8 5.3 920 17 3.6 629 14

600 10 50 7.1 626 8 4.9 427 6 4.2 721 11 2.8 490 9

600 18 50 6.0 524 6 4.1 356 5 3.0 526 6 2.0 354 5

700 -5 50 10.4 912 15 6.9 603 12 7.0 1218 28 4.7 807 22

700 2 50 9.2 809 12 6.1 535 10 5.9 1020 20 3.9 675 16

700 10 50 7.9 694 9 5.2 458 7 4.6 799 13 3.0 526 10

700 18 50 6.6 581 7 4.4 383 5 3.4 583 8 2.2 380 6

800 -5 50 11.4 995 18 7.3 640 13 7.7 1330 32 4.9 856 24

800 2 50 10.1 883 14 6.5 568 11 6.4 1114 24 4.1 716 17

800 10 50 8.6 757 11 5.6 486 8 5.0 872 15 3.2 558 11

800 18 50 7.2 634 8 4.6 406 6 3.7 636 9 2.3 403 6

900 -5 50 12.3 1073 20 7.7 673 14 8.3 1435 37 5.2 901 26

900 2 50 10.9 952 16 6.8 597 12 6.9 1201 27 4.3 753 19

900 10 50 9.3 817 12 5.8 511 9 5.4 941 17 3.4 587 12

900 18 50 7.8 684 9 4.9 427 6 4.0 686 10 2.4 423 7

1000 -5 50 13.1 1147 23 8.0 703 15 8.9 1534 42 5.4 942 28

1000 2 50 11.6 1018 18 7.1 624 13 7.4 1285 30 4.5 787 21

1000 10 50 10.0 874 14 6.1 535 10 5.8 1006 20 3.5 613 13

1000 18 50 8.4 732 10 5.1 446 7 4.2 733 11 2.6 442 7

1100 -5 50 13.9 1218 25 8.4 731 17 9.4 1629 47 5.7 980 31

1100 2 50 12.3 1081 20 7.4 649 13 7.9 1364 34 4.7 819 22

1100 10 50 10.6 927 16 6.3 556 10 6.2 1068 22 3.7 638 14

1100 18 50 8.9 777 11 5.3 464 7 4.5 777 13 2.7 460 8

1200 -5 50 14.7 1286 28 8.6 758 18 9.9 1719 52 5.9 1015 33

1200 2 50 13.0 1141 23 7.7 672 14 8.3 1440 37 4.9 848 24

1200 10 50 11.2 979 17 6.6 576 11 6.5 1127 24 3.8 661 15

1200 18 50 9.4 820 13 5.5 481 8 4.7 820 14 2.7 476 8

t O

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

4-P

IPE S

YSTEM

HEATIN

GFTA 15 2-row coil

Temp. of inlet water: 70°C

Temp. of outlet water: 60°C

1-row coil

Temp. of inlet water: 70°C

Temp. of outlet water: 60°C

2-row coil

Temp. of inlet water: 45°C

Temp. of outlet water: 40°C

1-row coil

Temp. of inlet water: 45°C

Temp. of outlet water: 40°C

P(m³/h) Tia (°C) UmRel % Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa)

500 -5 50 9.7 852 8 7.8 683 18 6.6 1136 14 5.3 912 33

500 2 50 8.6 755 6 6.9 606 14 5.5 952 10 4.4 765 24

500 10 50 7.4 648 5 5.9 521 11 4.3 748 7 3.5 601 16

500 18 50 6.2 544 4 5.0 437 8 3.2 550 4 2.5 441 9

700 -5 50 12.4 1087 12 9.3 817 25 8.4 1450 22 6.3 1093 46

700 2 50 11.0 965 10 8.3 727 20 7.0 1216 16 5.3 917 33

700 10 50 9.5 828 7 7.1 625 15 5.5 955 10 4.2 721 22

700 18 50 7.9 695 6 6.0 524 11 4.0 702 6 3.0 528 12

900 -5 50 14.8 1295 16 10.6 926 31 10.0 1729 30 7.2 1239 57

900 2 50 13.1 1149 13 9.4 824 25 8.4 1450 22 6.0 1040 42

900 10 50 11.3 987 10 8.1 708 19 6.6 1139 14 4.7 818 27

900 18 50 9.5 828 7 6.8 595 14 4.8 836 8 3.5 599 16

1100 -5 50 16.9 1483 21 11.6 1018 37 11.4 1980 38 7.9 1362 68

1100 2 50 15.0 1316 17 10.3 905 30 9.6 1661 28 6.6 1144 49

1100 10 50 12.9 1131 13 8.9 779 23 7.5 1305 18 5.2 899 32

1100 18 50 10.8 949 9 7.5 655 17 5.5 957 10 3.8 658 18

1300 -5 50 18.9 1655 25 12.5 1097 42 12.8 2212 47 – – –

1300 2 50 16.8 1470 20 11.1 976 34 10.7 1856 34 7.1 1234 57

1300 10 50 14.4 1263 16 9.6 840 26 8.4 1457 22 5.6 970 37

1300 18 50 12.1 1060 11 8.1 706 19 6.2 1068 13 4.1 710 21

1500 -5 50 20.7 1816 30 13.3 1167 47 14.0 2427 55 – – –

1500 2 50 18.4 1613 24 11.9 1039 38 11.8 2036 40 7.6 1314 64

1500 10 50 15.8 1386 18 10.2 895 29 9.2 1599 26 6.0 1033 41

1500 18 50 13.3 1163 13 8.6 752 21 6.8 1171 15 4.4 756 23

1700 -5 50 22.4 1966 34 14.1 1231 52 15.2 2629 64 – – –

1700 2 50 19.9 1747 28 12.5 1096 42 12.7 2206 46 8.0 1386 70

1700 10 50 17.1 1501 21 10.8 944 32 10.0 1732 30 6.3 1089 45

1700 18 50 14.4 1260 16 9.1 793 23 7.3 1268 17 4.6 797 26

4-P

IPE S

YSTEM

HEATIN

G

FTA 19 2-row coil

Temp. of inlet water: 70°C

Temp. of outlet water: 60°C

1-row coil

Temp. of inlet water: 70°C

Temp. of outlet water: 60°C

2-row coil

Temp. of inlet water: 45°C

Temp. of outlet water: 40°C

1-row coil

Temp. of inlet water: 45°C

Temp. of outlet water: 40°C

P(m³/h) Tia (°C) UmRel % Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa)

700 -5 50 13.2 1158 9 10.3 899 12 8.9 1544 16 6.9 1202 22

700 2 50 11.7 1027 7 9.1 798 10 7.5 1294 12 5.8 1007 16

700 10 50 10.1 881 6 7.8 685 8 5.9 1017 8 4.6 789 11

700 18 50 8.4 739 4 6.6 574 6 4.3 747 5 3.3 577 6

1000 -5 50 17.0 1493 14 12.3 1081 17 11.5 1992 26 8.3 1446 31

1000 2 50 15.1 1324 11 11.0 960 14 9.6 1670 19 7.0 1212 23

1000 10 50 13.0 1137 9 9.4 825 10 7.6 1312 12 5.5 950 15

1000 18 50 10.9 954 6 7.9 692 8 5.6 963 7 4.0 694 8

1300 -5 50 20.4 1785 19 14.0 1226 21 13.8 2384 36 9.5 1640 39

1300 2 50 18.1 1585 16 12.4 1089 17 11.5 2000 26 7.9 1376 29

1300 10 50 15.5 1361 12 10.7 936 13 9.1 1571 17 6.2 1078 18

1300 18 50 13.0 1143 9 9.0 785 10 6.6 1152 10 4.5 786 11

1600 -5 50 23.4 2048 25 15.4 1346 25 15.8 2737 46 10.4 1802 47

1600 2 50 20.8 1819 20 13.7 1197 20 13.3 2296 33 8.7 1512 34

1600 10 50 17.8 1563 15 11.7 1029 16 10.4 1803 22 6.8 1186 22

1600 18 50 15.0 1312 11 9.9 863 11 7.6 1321 12 5.0 864 12

1900 -5 50 26.1 2289 30 16.6 1451 29 17.7 3060 56 11.2 1942 53

1900 2 50 23.2 2033 24 14.7 1290 23 14.8 2567 41 9.4 1630 39

1900 10 50 19.9 1747 19 12.7 1109 18 11.6 2016 26 7.4 1278 25

1900 18 50 16.7 1467 14 10.6 930 13 8.5 1477 15 5.4 931 14

2200 -5 50 28.7 2512 36 17.6 1542 32 19.4 3359 66 11.9 2066 60

2200 2 50 25.5 2232 29 15.7 1372 26 16.3 2818 48 10.0 1734 43

2200 10 50 21.9 1918 22 13.5 1180 20 12.8 2213 31 7.8 1359 28

2200 18 50 18.4 1610 16 11.3 990 14 9.4 1620 18 5.7 990 16

u Q

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

4-P

IPE S

YSTEM

HEATIN

G

FTA 24 2-row coil

Temp. of inlet water: 70°C

Temp. of outlet water: 60°C

1-row coil

Temp. of inlet water: 70°C

Temp. of outlet water: 60°C

2-row coil

Temp. of inlet water: 45°C

Temp. of outlet water: 40°C

1-row coil

Temp. of inlet water: 45°C

Temp. of outlet water: 40°C

P(m³/h) Tia (°C) UmRel % Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa)

800 -5 50 16.3 1428 10 13.3 1161 11 11.0 1902 18 8.9 1550 20

800 2 50 14.5 1266 8 11.8 1030 9 9.2 1595 13 7.5 1299 15

800 10 50 12.4 1087 6 10.1 884 7 7.2 1256 9 5.9 1020 10

800 18 50 10.4 913 5 8.5 742 5 5.3 927 5 4.3 748 6

1200 -5 50 22.0 1926 17 16.6 1453 16 14.8 2568 31 11.2 1942 30

1200 2 50 19.5 1709 14 14.7 1290 13 12.4 2155 22 9.4 1629 22

1200 10 50 16.8 1468 10 12.7 1109 10 9.8 1697 15 7.4 1279 14

1200 18 50 14.1 1234 8 10.6 930 7 7.2 1251 9 5.4 936 8

1600 -5 50 26.9 2358 24 19.2 1679 21 18.2 3147 44 13.0 2246 39

1600 2 50 23.9 2094 19 17.0 1493 17 15.3 2643 32 10.9 1885 29

1600 10 50 20.5 1800 15 14.7 1283 13 12.0 2080 21 8.5 1480 19

1600 18 50 17.3 1513 11 12.3 1077 10 8.8 1532 12 6.2 1083 11

2000 -5 50 31.3 2744 32 21.3 1866 26 21.2 3665 58 14.4 2498 48

2000 2 50 27.8 2438 25 19.0 1660 21 17.8 3078 42 12.1 2097 35

2000 10 50 23.9 2097 19 16.3 1427 16 14.0 2423 28 9.5 1646 22

2000 18 50 20.1 1763 14 13.7 1198 12 10.3 1784 16 6.9 1204 13

2400 -5 50 35.3 3096 39 23.1 2026 30 – – – 15.7 2712 56

2400 2 50 31.4 2752 32 20.6 1803 24 20.1 3476 53 13.1 2278 40

2400 10 50 27.0 2367 24 17.7 1551 19 15.8 2736 34 10.3 1789 26

2400 18 50 22.7 1991 18 14.9 1302 14 11.6 2013 20 7.5 1307 15

2800 -5 50 39.1 3421 47 24.7 2166 34 – – – 16.7 2901 63

2800 2 50 34.7 3043 38 22.0 1928 28 22.2 3843 63 14.1 2437 46

2800 10 50 29.9 2618 29 18.9 1659 21 17.5 3025 41 11.0 1914 29

2800 18 50 25.1 2202 21 15.9 1393 15 12.8 2225 24 8.1 1398 17

4-P

IPE S

YSTEM

HEATIN

G

FTA 33 2-row coil

Temp. of inlet water: 70°C

Temp. of outlet water: 60°C

1-row coil

Temp. of inlet water: 70°C

Temp. of outlet water: 60°C

2-row coil

Temp. of inlet water: 45°C

Temp. of outlet water: 40°C

1-row coil

Temp. of inlet water: 45°C

Temp. of outlet water: 40°C

P(m³/h) Tia (°C) UmRel % Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa)

1300 -5 50 23.3 2039 19 17.3 1514 18 15.7 2720 34 11.7 2024 33

1300 2 50 20.7 1810 15 15.4 1345 14 13.2 2283 25 9.8 1698 24

1300 10 50 17.8 1555 11 13.2 1156 11 10.4 1797 16 7.7 1333 15

1300 18 50 14.9 1307 8 11.1 970 8 7.6 1325 10 5.6 976 9

1700 -5 50 28.1 2458 26 19.7 1729 23 18.9 3282 48 13.4 2313 42

1700 2 50 24.9 2183 21 17.6 1537 18 15.9 2756 35 11.2 1942 30

1700 10 50 21.4 1877 16 15.1 1321 14 12.5 2169 23 8.8 1524 20

1700 18 50 18.0 1578 12 12.7 1109 10 9.2 1597 13 6.4 1115 11

2100 -5 50 32.4 2835 33 21.8 1908 27 21.9 3787 62 14.7 2554 50

2100 2 50 28.8 2519 27 19.4 1697 22 18.4 3181 45 12.4 2145 36

2100 10 50 24.7 2166 21 16.7 1460 17 14.5 2504 29 9.7 1684 23

2100 18 50 20.8 1822 15 14.0 1226 12 10.6 1843 17 7.1 1231 13

2500 -5 50 36.3 3179 41 23.6 2063 31 – – – 15.9 2762 57

2500 2 50 32.3 2827 33 21.0 1835 25 20.6 3570 55 13.4 2319 42

2500 10 50 27.8 2432 25 18.0 1579 19 16.2 2810 36 10.5 1822 27

2500 18 50 23.3 2045 19 15.1 1326 14 11.9 2068 21 7.7 1331 15

2900 -5 50 40.0 3499 49 25.1 2199 35 – – – 17.0 2945 65

2900 2 50 35.5 3112 40 22.3 1957 28 22.7 3931 66 14.3 2474 47

2900 10 50 30.6 2678 30 19.2 1684 22 17.9 3095 43 11.2 1943 30

2900 18 50 25.7 2252 22 16.1 1414 16 13.1 2276 25 8.2 1419 17

3300 -5 50 43.4 3798 57 26.5 2321 39 – – – – – –

3300 2 50 38.6 3379 46 23.6 2066 31 – – – 15.1 2612 52

3300 10 50 33.2 2908 35 20.3 1778 24 19.4 3360 50 11.8 2052 33

3300 18 50 27.9 2446 26 17.1 1494 17 14.3 2471 29 8.6 1498 19

3700 -5 50 46.6 4080 65 27.8 2432 42 – – – – – –

3700 2 50 41.4 3630 52 24.7 2166 34 – – – 15.8 2738 57

3700 10 50 35.7 3125 40 21.3 1864 26 20.8 3612 57 12.4 2150 36

3700 18 50 30.0 2628 29 17.9 1566 19 15.3 2655 32 9.1 1570 21

u &

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

4-P

IPE S

YSTEM

HEATIN

GFTA 40 2-row coil

Temp. of inlet water: 70°C

Temp. of outlet water: 60°C

1-row coil

Temp. of inlet water: 70°C

Temp. of outlet water: 60°C

2-row coil

Temp. of inlet water: 45°C

Temp. of outlet water: 40°C

1-row coil

Temp. of inlet water: 45°C

Temp. of outlet water: 40°C

P(m³/h) Tia (°C) UmRel % Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa)

1500 -5 50 28.8 2521 12 22.6 1982 20 19.4 3361 21 15.3 2648 37

1500 2 50 25.5 2237 9 20.1 1761 16 16.3 2820 16 12.8 2223 27

1500 10 50 21.9 1921 7 17.3 1514 12 12.8 2220 10 10.1 1749 17

1500 18 50 18.4 1614 5 14.5 1272 9 9.4 1637 6 7.4 1285 10

2000 -5 50 35.4 3101 17 26.3 2307 26 23.9 4138 31 17.8 3085 48

2000 2 50 31.4 2753 14 23.4 2052 21 20.0 3474 23 15.0 2592 35

2000 10 50 27.0 2366 10 20.2 1765 16 15.8 2733 15 11.8 2039 23

2000 18 50 22.7 1989 8 16.9 1484 12 11.6 2015 9 8.6 1497 13

2500 -5 50 41.4 3622 22 29.4 2577 32 27.9 4836 41 19.9 3447 59

2500 2 50 36.7 3217 18 26.2 2292 26 23.4 4061 30 16.7 2897 43

2500 10 50 31.6 2766 14 22.5 1973 20 18.4 3196 19 13.2 2279 28

2500 18 50 26.5 2325 10 18.9 1659 15 13.6 2353 11 9.7 1673 16

3000 -5 50 46.8 4098 28 32.1 2807 38 31.6 5474 51 21.7 3757 69

3000 2 50 41.6 3641 23 28.5 2499 30 26.5 4597 37 18.2 3159 51

3000 10 50 35.7 3131 17 24.6 2151 23 20.9 3619 24 14.3 2486 33

3000 18 50 30.1 2633 13 20.7 1809 17 15.4 2663 14 10.5 1824 19

3500 -5 50 51.8 4538 34 34.4 3010 43 35.0 6064 62 – – –

3500 2 50 46.1 4034 27 30.6 2680 35 29.4 5094 45 19.6 3388 57

3500 10 50 39.6 3470 21 26.4 2308 26 23.1 4010 29 15.4 2667 37

3500 18 50 33.3 2917 15 22.2 1941 19 17.0 2950 17 11.3 1956 21

4000 -5 50 56.5 4950 39 36.4 3191 47 – – – – – –

4000 2 50 50.3 4401 32 32.4 2842 38 32.1 5559 53 20.7 3595 64

4000 10 50 43.2 3787 24 28.0 2448 29 25.3 4376 34 16.3 2829 41

4000 18 50 36.4 3184 18 23.5 2060 21 18.6 3218 20 12.0 2075 24

4500 -5 50 61.0 5338 45 38.3 3355 52 – – – – – –

4500 2 50 54.2 4748 36 34.1 2989 42 34.6 5997 61 21.8 3781 70

4500 10 50 46.6 4085 28 29.4 2575 32 27.2 4721 39 17.2 2976 45

4500 18 50 39.2 3435 20 24.7 2167 23 20.0 3471 23 12.6 2182 26

4-P

IPE S

YSTEM

HEATIN

G

FTA 50 2-row coil

Temp. of inlet water: 70°C

Temp. of outlet water: 60°C

1-row coil

Temp. of inlet water: 70°C

Temp. of outlet water: 60°C

2-row coil

Temp. of inlet water: 45°C

Temp. of outlet water: 40°C

1-row coil

Temp. of inlet water: 45°C

Temp. of outlet water: 40°C

P(m³/h) Tia (°C) UmRel % Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa) Qtot (kW) WtrFlow (l/h) WtrDP (kPa)

2500 -5 50 41.4 3622 22 29.4 2577 32 27.9 4836 41 19.9 3447 59

2500 2 50 36.7 3217 18 26.2 2292 26 23.4 4061 30 16.7 2897 43

2500 10 50 31.6 2766 14 22.5 1973 20 18.4 3196 19 13.2 2279 28

2500 18 50 26.5 2325 10 18.9 1659 15 13.6 2353 11 9.7 1673 16

3000 -5 50 46.8 4098 28 32.1 2807 38 31.6 5474 51 21.7 3757 69

3000 2 50 41.6 3641 23 28.5 2499 30 26.5 4597 37 18.2 3159 51

3000 10 50 35.7 3131 17 24.6 2151 23 20.9 3619 24 14.3 2486 33

3000 18 50 30.1 2633 13 20.7 1809 17 15.4 2663 14 10.5 1824 19

3500 -5 50 51.8 4538 34 34.4 3010 43 35.0 6064 62 – – –

3500 2 50 46.1 4034 27 30.6 2680 35 29.4 5094 45 19.6 3388 57

3500 10 50 39.6 3470 21 26.4 2308 26 23.1 4010 29 15.4 2667 37

3500 18 50 33.3 2917 15 22.2 1941 19 17.0 2950 17 11.3 1956 21

4000 -5 50 56.5 4950 39 36.4 3191 47 – – – – – –

4000 2 50 50.3 4401 32 32.4 2842 38 32.1 5559 53 20.7 3595 64

4000 10 50 43.2 3787 24 28.0 2448 29 25.3 4376 34 16.3 2829 41

4000 18 50 36.4 3184 18 23.5 2060 21 18.6 3218 20 12.0 2075 24

4500 -5 50 61.0 5338 45 38.3 3355 52 – – – – – –

4500 2 50 54.2 4748 36 34.1 2989 42 34.6 5997 61 21.8 3781 70

4500 10 50 46.6 4085 28 29.4 2575 32 27.2 4721 39 17.2 2976 45

4500 18 50 39.2 3435 20 24.7 2167 23 20.0 3471 23 12.6 2182 26

5000 -5 50 65.1 5706 51 40.0 3506 56 – – – – – –

5000 2 50 57.9 5076 41 35.7 3124 46 37.0 6413 69 – – –

5000 10 50 49.9 4368 31 30.7 2692 35 29.1 5047 44 18.0 3111 49

5000 18 50 41.9 3673 23 25.9 2265 25 21.4 3710 25 13.2 2281 28

5500 -5 50 69.1 6056 57 41.6 3645 61 – – – – – –

5500 2 50 61.5 5388 46 37.1 3248 49 – – – – – –

5500 10 50 52.9 4637 35 32.0 2799 37 30.9 5360 49 18.7 3235 53

5500 18 50 44.5 3900 26 26.9 2356 27 22.7 3938 28 13.7 2371 30

u P

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

INSTALLATION, USE AND MAINTENANCE MANUAL

WARNING!

The units of the FTA range are

designed for the public and

service sectors: any other use

(in highly corrosive environments, in the

presence of potentially explosive sur-

roundings, etc.) is not permitted.

Installation and maintenanceBefore installation, make sure that the

unit has not been damaged during tran-

sportation: the use of a damaged machi-

ne may be hazardous.

Installation and supplementary main-

tenance must be carried out by trained

personnel in accordance with the present

laws.

The unit must not be used as recovery of

equipment or spare parts. Any other use

other than that indicated in the present

manual may be hazardous and is therefo-

re prohibited.

Before starting any maintenance or cle-

aning operations, make sure the units is

disconnected from the power supply and

that it cannot be reconnected without

the knowledge of the maintenance engi-

neer.

During maintenance and cleaning, take

care of possible scalding from heating

coils.

Before starting the unit, make sure that

the electrical parts have been connected

to the building's earth system.

During installation, maintenance and

cleaning, Personal Protective Equipment

(PPE) must be worn and the correct tools

used.

Access to the unitAccess to the unit once it has been instal-

led must only be permitted to qualifi ed

operators and technicians. The operator

is a person who has been authorised by

the owner of the machine to carry out

operations on the said machine (accor-

ding to the indications given in this ma-

nual). The technician is a person autho-

rised by FAST, or subordinate under their

own responsibility by a FAST distributor,

to carry out operations on the machine.

The owner of the machine is the legal

representative of the company, entity or

individual owner of the system in which

the FAST machine is installed. These per-

sons are responsible for the observance

of all safety standards indicated in this

manual and the existing law. As these

units are usually installed in suspended

ceilings,

it is important to ensure the lower panel-

ling can be accessed in order to inspect

the fi lters and fans.

Residual risksThe installation, start-up, shutdown and

maintenance of the machine must be car-

ried out in accordance with that stipu-

lated in the technical documentation of

the product and in such a manner that

no hazardous situations are generated.

The machine has been designed so as to

reduce to a minimum the risks for the sa-

fety of those persons interacting with it.

During the design phase, it was not tech-

nically possible to completely eliminate

the risk causes. Therefore it is imperative

to refer to the following instructions.

General safety requirements

CONSIDERED PART RESIDUAL RISK METHOD PRECAUTION

Inside the unit: fi nned heat

exchanger coilsmall cuts contact

avoid contact, use protective

gloves

Electric heating coil burns, injuries contact avoid contact

Inside the unit: metal parts

and electrical cables

intoxication, electrocution,

severe burns

insulation defect of the power

supply cables upstream of the

unit's electric panel; live metal

parts

suitable electrical protection of

the power supply line; maximum

care when earthing the metal

parts

Outside the unit: area

around the unitserious burns

fi re due to short circuit or

overheating of the power supply

line upstream of the unit's elec-

tric panel

cable section and power supply

line safety system conforming

with existing laws

u t

All the necessary operating spaces

must be checked before beginning the

installation:

• the positioning of the canalisation of

the intake and expulsion air;

• the passage of the electrical power sup-

ply cables;

• the correct maintenance and cleaning

operations.

In particular:

• there must be a space of at least 200

mm in correspondence with the conden-

sate discharge point, for the drain-trap

(more detailed instructions can be found

on the label attached to the discharge

point itself);

• a space of at least 400 mm is required in

correspondence with the water coil col-

lectors, to install the valve;

• for routine maintenance operations (vi-

sual inspections, fi lter replacement and

cleaning), there must be a space of at

least 1000 mm.

PACKAGING

The air conditioning units of the FTA ran-

ge are supplied on pallets and packaged

in cardboard boxes.

ON-SITE STORAGE

The units of the FTA range must be stored

under cover.

TRANSPORT

Transportation must be carried out with

the following precautions:

• the load must be well blocked on the

lorry;

• the load must be suitably protected.

CHECKS UPON RECEIPT

Upon receipt of the unit, an initial visual

check must be made for any damage re-

sulting from transportation. If damage is

discovered, this must be highlighted on

the accompanying travel document.

The essential indications for the correct

installation of the equipment are given

below.

The fi ne details of all the operations de-

pend on the specifi c requirements howe-

ver, and are therefore left to the instal-

ler's experience.

The unit is supplied complete with sup-

port brackets for wall or ceiling assembly.

The brackets can be assembled with the

bend pointing inwards or outwards.

For other types of assembly, the indica-

tions below should be modifi ed according

to the specifi c on-site requirements.

In any case, you are advised to fi x the

brackets to the ceiling fi rst of all (using

wall plugs or threaded tie-rods), then fi x

the units to the brackets.

In the case of vertical installation, the

screws for fi xing the unit to the brackets

will rest in the shorter part of the slots.

To fi x the unit to the wall, proceed as fol-

lows:

- mark the four holes for the wall plugs;

- prepare the fi xing means (wall plugs or

tie-rods);

- fi x the brackets to the wall or ceiling,

using nuts, washers and locknuts;

- attach the unit to the brackets, using

the 4 side screws;

- in the case of horizontal installation,

before tightening the screws, nuts and

locknuts check the condensate is correct-

ly discharged.

Finally, you are advised to apply a slight

inclination towards the discharge point,

to aid the fl ow.

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

Minimum operating spaces

Handling

Unit installation

u u

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

Installation - Connections

Aeraulic connections

WARNING!

It is prohibited to start the

machine if the fan inlets are

not ducted or are not protec-

ted by an accident-prevention system

For installation, proceed as follows:

• arrange suitable brackets to support

the channelling, so it does not weigh

on the recovery unit;

• connect the supply and intake ports

to the channels with vibration-dam-

ping joints in between (canvas). The

vibration-damping joint must be se-

cured to the panel with self-tapping

screws making sure that the canvas

joints are taught when running;

• arrange an earth cable that acts as

a bridge on the anti-vibration joint to

guarantee the equipotential connec-

tion between the channels and the re-

covery unit;

• before connecting any bends or bran-

ches, etc., set out the supply channel

with a straight section with a length of

at least 2.5 times the shorter side of

the channel A, avoiding an inclination

of more than 7° for the channelling

(to avoid any possible reduction in fan

performance levels).

Hydraulic connections: con-densate discharge

The condensate drip tray has a threa-

ded outlet with a diameter of 1/2” -G

UNI 338.

A discharge system must foresee a sui-

table drain-trap to:

• allow the free discharge of the con-

densate;

• prevent the undesired entry of air in

vacuum systems;

• prevent the infi ltration of odours or

insects.

The lower part of the trap should have

a discharge plug or should in any case

allow easy dismantling for cleaning.

The instructions for the dimensioning

and execution of the trap are as fol-

lows (see fi gure 21):

H1 = 2P

H2= H1 / 2

where P is the pressure of the water

column expressed in mm (1mm w.c. =

9.81 Pa).

Drain-trap measurements diagram

P

POS

u v

Water coil connection

All water coil manifolds have threaded

male connectors for the entrance and

exit of water.

For correct installation follow the simple

indications below:

• anti-freeze devices should be present

in the event of adverse weather condi-

tions;

• the course of the piping must be such

so as not to create obstacles in the event

the coil must be removed and so as not to

compromise inspection and maintenance

of the unit and possible accessories;

• when screwing together the manifolds

and hydraulic circuit, avoid stresses that

could damage the coil manifolds;

• provide a stop valve to isolate the coil

from the rest of the circuit in the even it

must be disconnected from the hydraulic

circuit;

• fi rmly clamp the pipes outside the unit,

to prevent them weighing on the coil;

• for the connection of water feed pipes,

follow the indications on the "WATER IN-

LET" and "WATER OUTLET" plate on the

outside panelling ;

• fi t an air bleed valve on the highest sec-

tion of the circuit and a water discharge

valve on the lowest section of the circuit;

• once the connections have been made,

position the external rubber seal fl ush

with the panelling to avoid air

seepage.

WARNING!

To avoid burns during the heating fun-

ction, the piping must be carefully insu-

lated with suitable material as far as the

panelling.

Connection of the direct ex-pansion coils

The coils are supplied with connections

hermetically sealed and pressurised with

inert gas.

For correct installation follow the simple

indications below:

• the course of the piping must be

such so as not to create obstacles if the

coil needs to be removed, and not to

compromise the inspection and mainte-

nance of the unit and any accessories;

• arrange suitable brackets to support

the piping so as to avoid that their weight

overloads the recovery unit;

• once the connections have been made,

position the external rubber seal fl ush

with the panelling to avoid air seepage;

• the performance of the coil declared

in the present manual could undergo

changes in the event that the connection

pipes to a condensing only unit cause ex-

cessive pressure drops of the refrigerant.

WARNING!

To avoid burns, the piping must be suita-

bly insulated with suitable material up to

the panelling.

Electrical connec-tions: earth system

WARNING!

The electrical connections and wiring

must be carried out by qualifi ed person-

nel in accordance with the

present laws.

WARNING!

Each electrical appliance must be con-

nected to the earth of the system.

Use the connectors with the earth symbol

to connect the earth of the unit and pos-

sible accessories to the earth of the bu-

ilding.

Mains power supply connection

WARNING!

Make sure that the characteristics of the

mains power supply are compatible with

the electrical characteristics indicated

on the machine's rating plate.

Electrical connec-tions: electric coils

WARNING!Make sure that the characteristics of the

mains power supply are compatible with

the electrical characteristics indicated

on the part's rating plates.

Carry out the following instructions for

the connection of the electric coil:

• prepare suitable protection upstream,

with a residual current circuit breaker

with overcurrent protection;

• always connect a safety thermostat

to guarantee the disconnection of the

electric coil power supply in the event of

overheating;

• the safety thermostat must be in se-

ries with the regulating thermostat (not

supplied);

• the power supply of the coil must be

slaved to the function of the fans;

• always connect the earth wire of the

electric heating coil to the terminal insi-

de the electric box.

The wiring diagrams are supplied along

with the machine.

Electrical connections: elec-tric motors

The correct connection of the electric

motors is made on the control boards

assembled inside the unit (for FTA sizes

09-11-15), or on the Archimedean screw

of one of the fans (for FTA units 19-24-

33-40-50).

For units with two motors, the power

supply and earth cables are on one con-

trol board for each fan.

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

u w

Repositioning the internal components

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

All FTA units have been designed to faci-

litate both the set-up and the personali-

sation requested by the customer.

In particular, it is possible to invert the

position of the water coil connections.

Heating or cooling water coil

If the position of the water coil connec-

tions is not as you require, follow the

indications below:

• disassemble the upper panel and the

air delivery panel (coil side);

First start-up

WARNING!

Make sure that all the indi-

cations in the present

manual have been carried

out before carrying out the controls on

the first start-up.

Before starting up the unit, check:

• with a tester that the voltage on the

PCT2 control panel

Description

Main characteristics of the control panel:

• electronic room thermostat with knob

for setting the set-point;

• manual selection of the operating

mode;

• 3 fan speeds;

• Hot Start function with digital input or

temperature probe;

• limitation of set-point by means of

special pegs;

• room air temperature probe.

Technical data

• Power supply: 230V - 50 Hz;

• Maximum input power: 12W;

• Maximum allowed current: 1A;

• Electrical data of the 230C output:

max 0.5A for the valve output and max 1

for the fan outputs;

• Insulation class: II;

• Degree of protection: IP30;

• Analogue inputs:

- 1 (+1) NTC probes 103 AT-2

- air probe (see connection diagram)

- water probe (see connection diagram)

• presence of built-in air temperature probe;

•Outputs: 2 outputs on relay;

•Unit dimensions: 120 x 80 x 40mm;

•Assembly: wall;

•Connections of screwed control board

for wires:

- max diameter 2.5mm² for rigid cable;

- max diameter 1.5mm² for flexible cable;

• Room temperature: 0...55°C;

• Storage temperature: -20...85°C;

• Storage humidity: 10...90°C.

User instructions

SLIDER 1 (at the bottom) allows you to

vary the required fan speed settings

(max-av-min).

SLIDER 2 (in the middle) allows you to

vary the unit operating mode (OFF-Heat-

Cool).

The knob is used to set the required

room temperature.

80

SLIDER 1

SLIDER 2

120

• disassemble the closure panel;

• take out the coil;

• rotate the coil by 180°;

• insert the coil again, and fix it in

place;

• reassemble the closure panel;

• reassemble the panels.

With regards the water connections,

proceed as follows:

• connect the discharge conduit to the

threaded stump of the tray, and plug the

other stump (not used);

• cut the two plastic plugs;

• tighten the threaded pipe couplings on

the coil collectors;

• tighten the air drain point on the pipe

coupling; this must be positioned higher

than the other, and the drain point must

be near the top.

Make the connections to the system,

then insulate the piping and check the

condensate is correctly discharged.

If water is used as a heat vector fluid,

any risk of freezing must be avoided at

all costs.

terminals is 230V ± 5%: if the voltage is

subject to frequent changes, contact our

Technical department for the choice of

suitable protections;

• that the unit is correctly secured;

• the connection of the unit to the buil-

ding's earth;

• the channel connections;

• the connection of the condensate

discharge with the trap;

• the insulation of the coil's supply

pipes;

• the absence of air in the water and

direct expansion coils;

• the closure of the examinable panels;

• the presence of voltage.

u x

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

Union base unit with accessories

All base units are designed to provide

easy confi guration and customization

through modular accessories to meet fully

the needs of the customer.To ensure this,

have been developed of how to merge

standard to simplify the connection

between the base unit and accessories

or even across multiple accessories

and the unit itself. It comes complete

with all the accessories provided, a kit

assembly composed of screws and fl at

sealing adhesive to be applied on the

walls in contact in order to prevent air

leakage between one or more modules.

The mounting of accessories may be

executed either when the machine to

the ground (in the case where this is a

new installation) of that machine already

installed.

We will hereafter consider the case of

union of units on the ground:

1a) remove the inspection panel on the

bottom of the accessory in order to allow

access to the inside of the assembly

accessory - base unit or accessory -

accessory.

2a) apply the self-adhesive gasket,

supplied with, on the edges of the

accessory that will be connected in order

to prevent air leakage during operation.

3a) to bring the two modules and

screwing together the brackets (top,

bottom and sides) of the two modules

using the screws metric supplied.

4a) close the panel inspection accessory.

In the case in which the base unit is

already installed and it should proceed

with the installation of an accessory

in a second moment, it can act in the

following way:

1b) remove the inspection panel on the

bottom of the accessory in order to allow

access to the inside of the assembly

accessory - base unit or accessory -

accessory.

2b) apply the self-adhesive gasket,

supplied with, on the edges of the

accessory that will be connected in order

to prevent air leakage during operation.

3b) remove the bracket on the inside of

the upper long side of the accessory and

reinstall it from the outside of the same

side: fi xing is fi xing the screws from the

inside. Bring the two modules together

and screw the brackets top and sides of

the two modules using the metric screws

supplied.

4b) close the inspection of the accessory

panel and secure the lower bracket from

the outside.

1a

2a

1b

3b

Il metodo esposto si riferisce a tutte le tipologie di accessori anche se lo schema raffigura

il montaggio di un silenziatore SSL

3a

2b

u '

WARNING!

Use suitable personal protective equi-

pment (PPE) during maintenance ope-

rations

WARNING!

Before accessing the unit

for maintenance or clea-

ning operations, make sure the unit is

disconnected from the power supply,

that the supply can not be switched

on again without the maintenance

engineer's knowledge and that the

heat exchange coils are off.

WARNING!

Take particular care when

working close to finned

coils because the fins are particularly

sharp.

WARNING!

After finishing the main-

tenance operations, make

sure that the panelling is correctly

closed by means of fixing screws.

The units of the FTA range have been

designed to require less maintenance,

and to make each operation easier.

Below are some simple instructions

for correct maintenance of the unit.

The maintenance program must in

any case be carried out by a qualified

technician.

Routine maintenanceRoutine maintenance consists of sim-

ple operations that should be carried

out monthly, as follows:

- check the tightness of the fans fi xing

screws to the panels;

- check that the machine's power sup-

ply cable has not undergone any al-

terations that could compromise its

insulation;

- make sure that the screws that fi x

the wires to the electrical components

inside the electric panel are tight so

as to guarantee an electrical connec-

tion; the same also goes for the earth

connections.

Maintenance of the filters (if present)The cleaning of the filters is funda-

mental in order to maintain a high

qualitative standard of air in the

room. The synthetic filters fitted to

the FTA unit can be regenerated using

compressed air or by washing them

in cold water. To disassemble the fil-

ters, observe the following indica-

tions (see the figure below):

• remove the inspection panel with

knobs;

• remove the filters;

• clean the filters;

• reassemble all the components in

the reverse order.

Fan maintenance

It is essential to check and clean the

fans, to maintain the low noise level

of the unit. Check annually:

- the clean state of the impeller;

- the noise level of the bearings.

Coil maintenance

It is essential to check and clean the

coils, to maintain the high standard

of quality and renewal of fresh air in

the room.

Check annually:

- the clean state of the finned unit.

Unit maintenance

FTA

FLAT

FILTER

665 x 265

FLAT

FILTER

1015 x 265

FLAT

FILTER

1440 x 355

FLAT

FILTER

2065 x 355

09 1

11 1

15 1

19 1

24 1

33 1

40 1

50 1

FTA

POCKET

FILTER

287 x 592

09 1

11 1

15 1

19 1

24 2

33 2

40 3

50 3

Dimensional table of filters used in the FTA units

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

u O

Unit disposal

The components of the FTA range have

been designed to guarantee continual ope-

rations. The duration of some main parts

depends on the maintenance to which it

has undergone.

At the end of their useful life, the FTA

range units must be disposed of in accor-

dance with the current laws in force.

If the unit is to be disposed of, the opera-

tion must be carried out by speciali-

sed personnel.

The main materials that make up the

units of the FTA range are:

• galvanised steel (panels, fans, con-

densate drip tray);

• aluminium sheet or aluminium

alloy (coil fins, grilles, electric motor

frame);

• copper (coil pipes, winding of the

electric motors);

• polyurethane foam (sandwich panels

insulation).

PROBLEM CAUSE REMEDY

1. INSUFFICIENT

AIR FLOW RATE

1. Blocked filters - Clean the filters

2. Blocked coils - Clean the coils

3. NO AIR FLOW

RATE

1. Power supply off - Check the presence of power

2. Electric motor burnt out - Replace the electric motor

4. ABNORMAL

NOISE

1. Excessive flow rate - Reduce the flow rate

2. Fan bearings worn or defective - Replace bearings

3. Foreign bodies on the fans' impellers - Clean the impellers

4. MOISTURE

CARRYOVER

1. Drain-trap blocked - Clean drain-trap

2. No drain-trap or incorrectly made - Correctly prepare a drain-trap as

indicated in this manual

5. REQUIRED

TEMPERATURE NOT

ACHIEVED

1. Temperature of the inlet air on coil out-

side the envisaged limits - Check the water temperature

2. Air in the water coils - Bleed the coils

3. Insufficient water flow rate in the water

coils - Increase the water flow rate

4. Insufficient coil inlet water temperature - Check the water temperature

5. Dirty coil unit surface - Clean the surface of the pack

Diagnosis and fault solving

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

v Q

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

Wiring diagrams

KEY TO PCT 2 DIAGRAMS

VC: HOT VALVE VF: COLD VALVE CR: ELECTRIC HEATER COUNTER KA1: MINIMUM SPEED RELAY KA2: AVERAGE SPEED RELAY KA3: MAXIMUM SPEED RELAY

• CONNECTION DIAGRAM FOR THE PCT2 REMOTE PANEL

M

1

230V-1-50Hz

ON/OFF

Heating valve

Sonda Acqua

Cooling valve

N

L

MAX

MED

PROBE

WATER TEMPERATURE

COM

PE

MIN

MAX

MED230Vacmax 1A

max 0,5A

MIN

230Vac

230V - 1 - 50Hz

VC

KA2

KA3

KA1

KA1

KA3

KA2

VFCR

C1

4

5

6

7

8

10

19

20

9

LN

5

1

2

3

4

N

BI

RO

NE

BL

GR

FTA 09THE CALCULATION OF THE ELECTRIC DIMENSIONS IS THE RESPONSIBILITY

OF THE CUSTOMER NOT SUPPLIED

POWER SUPPLY LINE

PREPARE SUITABLE

PROTECTION UPSTREAM,

WITH A RESIDUAL CURRENT

CIRCUIT BREAKER WITH

OVERCURRENT PROTECTION

BI: WHITE

RO: RED

GR: GREY

NE: BLACK

BL: BLUE

NCT 10K

PCT 2

v &

Air conditioning units - FTA range

� � � � � � � � � � � ! � " � � " � � � � # ! � " � $ % " � � � � � " � � � % " � # " �

M

1

M

1

MIN

MAX

MED

230Vacmax 1A

max 0,5A

MIN

230V-1-50Hz

ON/OFF

COM

PE

MIN

MAX

MED

230Vac

230V - 1 - 50Hz

PE

COM

PROBE

WATER TEMPERATURE

MED

MAX

L

N

Cooling valve

Heating valve

Sonda Acqua

KA1

KA3

KA2

VC

KA2

KA3

KA1

KA1

KA3

KA2

VFCR

C1

C1

8

10

19

20

9

LN

7

6

5

4

5

1

2

3

4

N

BI

RO

NE

BL

GR

5

1

2

3

4

N

BI

RO

NE

BL

GR

FTA 11-15THE CALCULATION OF THE ELECTRIC DIMENSIONS IS THE RESPONSIBILITY

OF THE CUSTOMER NOT SUPPLIED

BI: WHITE

RO: RED

GR: GREY

NE: BLACK

BL: BLUE

POWER SUPPLY LINE

PREPARE SUITABLE

PROTECTION UPSTREAM,

WITH A RESIDUAL CURRENT

CIRCUIT BREAKER WITH

OVERCURRENT PROTECTION

PCT 2

NCT 10K

M

1

COM

PE

ON/OFF

230V-1-50Hz

MED

MAX

MIN

PROBE

WATER TEMPERATURE

MED

MAX

L

N

Cooling valve

Heating valve

Sonda Acqua

230V - 1 - 50Hz

230Vacmax 1A

max 0,5A

MIN

230Vac

C1

CRVF

KA2

KA3

KA1

KA2

KA3

KA1

VC

MA

BL

NE

RO

BI

1

2

3

4

5

4

5

6

7

8

10

19

20

9

LN

THE CALCULATION OF THE ELECTRIC DIMENSIONS IS THE RESPONSIBILITY

OF THE CUSTOMERNOT SUPPLIED

FTA 19-24

POWER SUPPLY LINE

PREPARE SUITABLE

PROTECTION UPSTREAM,

WITH A RESIDUAL CURRENT

CIRCUIT BREAKER WITH

OVERCURRENT PROTECTION

BI: WHITE

RO: RED

GR: GREY

NE: BLACK

BL: BLUE

MA: BROWN

PCT 2

NCT 10K

y z

Air conditioning units - FTA range

{ | } | ~ � � � � � � � � � � } } � � � � � � � � | � � � � � � � � | � � � ~ | � � � � � }

M

1

M

1

PE

COM

MIN

MAX

MED

COM

PE

MED

MAX

MIN

ON/OFF

230V-1-50Hz

230V - 1 - 50Hz

PROBE

WATER TEMPERATURE

MED

MAX

L

N

Cooling valve

Heating valve

Sonda Acqua

230Vac

MIN

max 0,5A

max 1A230Vac

C1

KA1

KA3

KA2

C1

CRVF

KA2

KA3

KA1

KA2

KA3

KA1

VC

MA

BL

NE

RO

BI8

1

2

3

4

5

10

BI

RO

NE

BL

MA

1

2

3

4

5

4

5

6

7

N L

9

20

19

THE CALCULATION OF THE ELECTRIC DIMENSIONS IS THE RESPONSIBILITY

OF THE CUSTOMER

FTA 33-40

BI: WHITE

RO: RED

GR: GREY

NE: BLACK

BL: BLUE

MA: BROWN

NOT SUPPLIED

POWER SUPPLY LINE

PREPARE SUITABLE

PROTECTION UPSTREAM,

WITH A RESIDUAL CURRENT

CIRCUIT BREAKER WITH

OVERCURRENT PROTECTION

PCT 2

NCT 10K

M

1

M

1

PE

COM

MIN

MAX

MED

COM

PE

MINMED

MAX

230VacMIN

max 1A

max 0,5AON/OFF

230V-1-50Hz

230V - 1 - 50Hz

PROBE

WATER TEMPERATURE

MED

MAX

L

N

Cooling valve

Heating valve

Sonda Acqua

230Vac

C1

KA1

KA3

KA2

VC

KA1

KA3

CRVF

KA2

KA3

KA1 KA2

C1

MA

BL

NE

RO

BI

8

6

19

20

10

9

LN

1

2

3

4

5

4

5

6

7

MA

BL

NE

RO

BI

6

1

2

3

4

5

NCT 10K

PCT 2

THE CALCULATION OF THE ELECTRIC DIMENSIONS IS THE RESPONSIBILITY

OF THE CUSTOMER NOT SUPPLIED

BI: WHITE

RO: RED

GR: GREY

NE: BLACK

BL: BLUE

MA: BROWN

POWER SUPPLY LINE

PREPARE SUITABLE

PROTECTION UPSTREAM,

WITH A RESIDUAL CURRENT

CIRCUIT BREAKER WITH

OVERCURRENT PROTECTION

FTA 50

y �

KEY:

CR: ELECTRIC HEATER COUNTERRE: ELECTRIC HEATERSTS: AUTOMATIC THERMOSTATTSM: MANUAL THERMOSTAT

Air conditioning units - FTA range

{ | } | ~ � � � � � � � � � � } } � � � � � � � � | � � � � � � � � | � � � ~ | � � � � � }

TMIN

230Vacmax 0,5A

NOT SUPPLIEDNON FORNITA

max 1A230Vac

Sonda Acqua

Heating valve

Cooling valve

N

L

MAX

MED

PROBE

WATER TEMPERATURE

230V-1-50Hz

ON/OFF

Sonda Acqua

Heating valve

Cooling valve

N

L

MAX

MED

PROBE

WATER TEMPERATURE

230V-1-50Hz

ON/OFF

230Vacmax 1A

max 0,5A230Vac

MIN

BRIDGEPONTE

6

5

7

9

20

19

10

8

7

6

5

4 4

8

10

H2

O19

20

9

WITH WATER PROBE WITHOUT WATER PROBE

PCT 2 PCT 2

NCT 10K NCT 10K

ΘΘ

C° 001C° 09

40

0V

- 3

- 5

0H

z4

00

V -

3 -

50

Hz

NON FORNITI

TSMTS

RE

CR

A2 A1

RE

CR

A2 A1

W1

V1

U1

1N

W2

V2

U2

2

N

4

POWER SUPPLY LINE

PREPARE SUITABLE

PROTECTION UPSTREAM,

WITH A RESIDUAL CURRENT

CIRCUIT BREAKER WITH

OVERCURRENT PROTECTION

FSS 210

FSS 210

• CONNECTION DIAGRAM FOR THE ELECTRIC COILS

y �

• CONNECTION DIAGRAM FOR THE PX REMOTE PANEL

M

1

4 3 2 1

cd

MAX

MIN

PE

230V - 1 - 50Hz

MED

COM

C1

L

N

5

1

2

3

4

N

BI

RO

NE

BL

GR

Air conditioning units - FTA range

{ | } | ~ � � � � � � � � � � } } � � � � � � � � | � � � � � � � � | � � � ~ | � � � � � }

POWER SUPPLY LINE

PREPARE SUITABLE

PROTECTION UPSTREAM,

WITH A RESIDUAL CURRENT

CIRCUIT BREAKER WITH

OVERCURRENT PROTECTION

FTA 09

PXBI: WHITE

RO: RED

GR: GREY

NE: BLACK

BL: BLUE

M

1

M

1

1234

230V - 1 - 50Hz

cd

MIN

MAX

MED

COM

PE

MIN

MAX

MED

PE

COM

KA3

KA1

KA2

KA1

KA3

KA2

KA2

KA3

KA1

C1

C1

N

L

GR

5

1

2

3

4

N

BI

RO

NE

BL

GR

5

1

2

3

4

N

BI

RO

NE

BLPX

POWER SUPPLY LINE

PREPARE SUITABLE

PROTECTION UPSTREAM,

WITH A RESIDUAL CURRENT

CIRCUIT BREAKER WITH

OVERCURRENT PROTECTION

FTA 11-15 BI: WHITE

RO: RED

GR: GREY

NE: BLACK

BL: BLUE

THE CALCULATION OF THE ELECTRIC DIMENSIONS IS THE RESPONSIBILITY OF THE CUSTOMER

NOT SUPPLIED

THE CALCULATION OF THE ELECTRIC DIMENSIONS IS THE RESPONSIBILITY OF THE CUSTOMER

� �

Air conditioning units - FTA range

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

M

1MAX

MIN

PE

COM

4 3 2 1

cd

230V - 1 - 50Hz

MED

C1

MA

BL

NE

RO

BI

1

2

3

4

5

L

N

FTA 19-24

POWER SUPPLY LINE

PREPARE SUITABLE

PROTECTION UPSTREAM,

WITH A RESIDUAL CURRENT

CIRCUIT BREAKER WITH

OVERCURRENT PROTECTION

BI: WHITE

RO: RED

GR: GREY

NE: BLACK

BL: BLUE

MA: BROWN

PX

NOT SUPPLIED

THE CALCULATION OF THE ELECTRIC DIMENSIONS IS THE RESPONSIBILITY OF THE CUSTOMER

M

1

M

1

MIN

MAX

MED

COM

PE

MIN

MAX

MED

d c

230V - 1 - 50Hz

PE

COM

4 3 2 1

C1

C1KA1

KA3

KA2

KA2

KA3

KA1

KA2

KA1

KA3

MA

BL

NE

RO

BI

5

4

3

2

1

MA

1

2

3

BL

NE

4

5

RO

BI

N

L

FTA 33-40 BI: WHITE

RO: RED

GR: GREY

NE: BLACK

BL: BLUE

MA: BROWN

PX

POWER SUPPLY LINE

PREPARE SUITABLE

PROTECTION UPSTREAM,

WITH A RESIDUAL CURRENT

CIRCUIT BREAKER WITH

OVERCURRENT PROTECTION

NOT SUPPLIED

THE CALCULATION OF THE ELECTRIC DIMENSIONS IS THE RESPONSIBILITY OF THE CUSTOMER

� �

M

1

M

1

1234

COM

PE

230V - 1 - 50Hz

cd

MIN

MAX

MED

COM

PE

MIN

MAX

MED

KA3

KA1

KA2

KA1

KA3

KA2

KA2

KA3

KA1

C1

C1

L

N

MA

BL

NE

RO

BI

6

1

2

3

4

5

MA

BL

NE

RO

BI

6

1

2

3

4

5

Air conditioning units - FTA range

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

PX

FTA 50POWER SUPPLY LINE

PREPARE SUITABLE

PROTECTION UPSTREAM,

WITH A RESIDUAL CURRENT

CIRCUIT BREAKER WITH

OVERCURRENT PROTECTION

BI: WHITE

RO: RED

GR: GREY

NE: BLACK

BL: BLUE

MA: BROWN

NOT SUPPLIED

THE CALCULATION OF THE ELECTRIC DIMENSIONS IS THE RESPONSIBILITY

OF THE CUSTOMER

KEY TO PX DIAGRAMS

KA1: MINIMUM SPEED RELAY KA2: AVERAGE SPEED RELAY KA3: MAXIMUM SPEED RELAY

� �

Size data

Unit dimensions (mm)

A

B

C

Mod. A B C D

FTA 09 - FTA 11 700 300 700 82

FTA 15 700 300 1050 82

FTA 19 850 390 1050 82

FTA 24 - FTA 33 850 390 1475 82

FTA 40 - FTA 50 1000 390 2100 82

D

Mod. A B C D E G N. Ventilator

FTA 09 700 840 300 732 655 70 1

FTA 11 700 840 300 732 655 70 2

FTA 15 1050 840 300 1082 655 70 2

FTA 19 1050 1090 390 1082 905 70 1

FTA 24 1475 1090 390 1507 905 70 1

FTA 33 1475 1090 390 1507 905 70 2

FTA 40 2099 1090 390 2131 905 70 2

FTA 50 2099 1090 390 2131 905 70 2

A

36,5°

C

B

D

GE

G

Air conditioning units - FTA range

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

Orizzontal version

Vertical version

� �

Plenum with 2-stage post-heating electric coil « PBExF »

Mod. A B C

PBE1F for FTA 09 250 300 700

PBE2F for FTA 11 250 300 700

PBE3F for FTA 15 250 300 1050

PBE4F for FTA 19 250 390 1050

PBE5F for FTA 24 250 390 1475

PBE6F for FTA 33 250 390 1475

PBE7F for FTA 40 250 390 2100

PBE8F for FTA 50 250 390 2100

A

B

C

Section of soft pocket filters « FTFxF »

Mod. A B C

FTF1F for FTA 09 - FTA 11 700 300 700

FTF2F for FTA 15 700 300 1050

FTF3F for FTA 19 700 390 1050

FTF4F for FTA 24 - FTA 33 700 390 1475

FTF5F for FTA 40 - FTA 50 700 390 2100

A

B

C

Air conditioning units - FTA range

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� �

Supply grille « GMDxF »

A

B

CD

E

Mod. A B C D E

GMD1F for FTA 09 - FTA 11 700 640 300 240 45

GMD2F for FTA 15 1050 990 300 240 45

GMD3F for FTA 19 1050 990 390 330 45

GMD4F for FTA 24 - FTA 33 1475 1415 390 330 45

GMD5F for FTA 40 - FTA 50 2100 2040 390 330 45

Mod. A B C D E

GAP1F for FTA 09 - FTA 11 700 640 293 240 48

GAP2F for FTA 15 1050 990 300 240 45

GAP3F for FTA 19 1050 990 390 330 45

GAP4F for FTA 24 - FTA 33 1475 1415 390 330 45

GAP5F for FTA 40 - FTA 50 2100 2040 390 330 45

Intake grille « GAPxF »

A

B

C D

E

Air conditioning units - FTA range

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� �

2-damper mixing chamber « M2SxF »

Mod. A B C D E F G

M2S1F for FTA 09 - FTA 11 242 242 400 300 700 521 620

M2S2F for FTA 15 242 242 400 300 1050 501 600

M2S3F for FTA 19 332 332 490 390 1050 591 690

M2S4F for FTA 24 - FTA 33 332 332 490 390 1475 591 690

M2S5F for FTA 40 - FTA 50 332 332 490 390 2100 591 690

G

E

F

A

D

C

B

Air conditioning units - FTA range

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� �

3-damper mixing chamber « M3SxF »

AB

C D

E

Mod. A B C D E

M3S1F for FTA 09 - FTA 11 700 400 300 200 700

M3S2F for FTA 15 700 400 300 200 1050

M3S3F for FTA 19 850 500 390 300 1050

M3S4F for FTA 24 - FTA 33 1142 770 390 300 2100

M3S5F for FTA 40 - FTA 50 1142 770 390 300 2100

Air conditioning units - FTA range

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

�  

Plenum with multiple circular delivery points « PMMxF »

D2Mod. A B C E D1 D2 D3 No.of flanges

PMM1F for FTA 09 - FTA 11 607 500 300 700 200 180 150 3

PMM2F for FTA 15 607 500 300 1050 200 180 150 4

PMM3F for FTA 19 697,5 590 390 1050 200 180 150 4

PMM4F for FTA 24 - FTA 33 697,5 590 390 1475 200 180 150 5

PMM5F for FTA 40 - FTA 50 697,5 590 390 2100 200 180 150 5

A

B

C

E

D2

D3

D1

Closed supply plenum « PMCxF »

Mod. A B C

PMC1F for FTA 09 - FTA 11 500 300 700

PMC2F for FTA 15 500 300 1050

PMC3F for FTA 19 590 390 1050

PMC4F for FTA 24 - FTA 33 590 390 1475

PMC5F for FTA 40 - FTA 50 590 390 2100

A

B

C

Air conditioning units - FTA range

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� ¡

Suction damper « SAPxF »

A B

C

Mod. A B C

SAP1F for FTA 09 - FTA 11 100 700 300

SAP2F for FTA 15 100 1050 300

SAP3F for FTA 19 100 1050 390

SAP4F for FTA 24 - FTA 33 100 1475 390

SAP5F for FTA 40 - FTA 50 100 2100 390

2-area damper « S2ZxF »

Mod. A B C D E F

S2Z1F for FTA 09 - FTA 11 100 700 400 180 240 300

S2Z2F for FTA 15 100 1050 650 280 240 300

S2Z3F for FTA 19 100 1050 650 280 300 390

S2Z4F for FTA 24 - FTA 33 100 1475 950 405 300 390

S2Z5F for FTA 40 - FTA 50 100 2100 1380 600 330 390

A

B

C D

E F

Air conditioning units - FTA range

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� ¢

Silencers « SSLxF »

Mod. A B C No. of Silencers

SSL1F for FTA 09 - FTA 11 700 300 700 3

SSL2F for FTA 15 700 300 1050 4

SSL3F for FTA 19 700 390 1050 4

SSL4F for FTA 24 - FTA 33 700 390 1475 5

SSL5F for FTA 40 - FTA 50 700 390 2100 7

A

B

C

Fan intake section « VRFxF »

A

B

C

Mod. A B C No. of Fans

VRF1F for FTA 09 500 300 700 1

VRF2F for FTA 11 500 300 700 2

VRF3F for FTA 15 500 300 1050 2

VRF4F for FTA 19 590 390 1050 1

VRF5F for FTA 24 590 390 1475 1

VRF6F for FTA 33 590 390 1475 2

VRF7F for FTA 40 720 390 2100 2

VRF8F for FTA 50 720 390 2100 2

Air conditioning units - FTA range

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

� �

PCT2 (mm)

Air conditioning units - FTA range

� � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �

SLIDER 1

SLIDER 2

STO

MAX

MED

MIN

82

82 38

PX (mm)

120

80

The technical data given in this booklet are not binding. FAST S.p.A. reserves the right to introduce at any time whatever modifications are deemed necessary for product improvement.

£ ¤ ¥ ¦ ¤ § ¨ © ª ¥ « ¬ ­ ® ¥ © ¬ ¯ ° ¯ § ¬ ­ ¨ ¤ ¨ ¬ © ±

FAST S.p.A. AIR TREATMENT35044 Montagnana (PD) - ItalyVia Luppia Alberi, 170Tel. (+39) 0429 806311 - Fax 0429 806340E-mail: [email protected]://www.fastaer.com

²³́µ ¶³́·² ¸·́ ¶¹º» ¼²³