Introduction Ps. 1-6
Citation preview
For product Data Sheets, visit www.cooperbussmann.com/products/datasheet.asp 1
Table of contents
Disconnects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303Safety Module™ fused disconnect switch . . . . . . . . . . . . . . . . . . . . . . . 304Coordination Module™ fused panelboard . . . . . . . . . . . . . . . . . . . . . . . 305Power Module™ elevator disconnects . . . . . . . . . . . . . . . . . . . . . . . . . 306Overview for fusible disconnects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30730A Base & rail mount fusible disconnects . . . . . . . . . . . . . . . . . . 308-30960-100A Base & rail mount fusible disconnects . . . . . . . . . . . . . . 310-311200-800A Base & rail mount fusible disconnects . . . . . . . . . . . . . 312-31330-800A 2-, 3-, 4- & 6-Pole enclosed fusible disconnects . . . . . . . 314-317Overview for non-fusible disconnects . . . . . . . . . . . . . . . . . . . . . . 318-31916-100A Base & rail mount non-fusible disconnects . . . . . . . . . . . 320-32116-100A door mounted non-fusible disconnects . . . . . . . . . . . . . . . . . . 322400-800A Non-fusible disconnects & accessories . . . . . . . . . . . . . 323-32416-80A 3-Pole enclosed non-fusible disconnects . . . . . . . . . . . . . . . . . 32516-3150A 3-Pole enclosed non-fusible disconnects . . . . . . . . . . . . . . . 32616-400A 2-, 4- & 6-Pole enclosed non-fusible disconnects . . . . . . 327-328A/C disconnects - fused and non-fused . . . . . . . . . . . . . . . . . . . . . . . . 329Fused, dead front disconnect switches . . . . . . . . . . . . . . . . . . . . . . . . . 330
Telecom Protection Devices . . . . . . . . . . . . . . . . . . 331Telpower TPC & TPCDS compact fused disconnect switches . . . . . . . . 332Telpower TPM & TPMDS miniature fused disconnect switches . . . . . . . 333Fused disconnect switches for TPA fuses . . . . . . . . . . . . . . . . . . . 334-335Fused disconnect switches for TPS fuses . . . . . . . . . . . . . . . . . . . . . . 336Fused disconnect switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 337-338Telpower high-current switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 339Telpower 70-600A: 170Vdc fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . 340Telpower 1-600A: 170Vdc fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 341Indicating fuses & holders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 342-343Telpower specialty fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 344-345F38, FE2475 & F7036 Series filtered terminal blocks . . . . . . . . . . . 346-348Series C7021 & C7024 power feed thru terminal blocks . . . . . . . . 349-350
Surge Suppression Devices . . . . . . . . . . . . . . . . . . . . 351TVS transient voltage surge suppressors . . . . . . . . . . . . . . . . . . . . . . . 352TVSS transient surge suppression limiters . . . . . . . . . . . . . . . . . . . . . 353
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .255Fuse service kits & assortments . . . . . . . . . . . . . . . . . . . . . . . . . . 255-257Clip clamps & rail adapters (DIN & American) . . . . . . . . . . . . . . . . . . 258Spare fuse holders, pullers, testers & cabinets . . . . . . . . . . . . . . . . . . 259Fuse reducers & dummy "neutrals" . . . . . . . . . . . . . . . . . . . . . . . . . . . 260
Application Guide . . . . . . . . . . . . . . . . . . . . . . . . . . 361Cooper Bussmann Electrical Safety Services . . . . . . . . . . . . . . . . . . . . . 262Fuse technology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 363-369Motor circuit branch circuit protection . . . . . . . . . . . . . . . . . . . . . . . . . 370Conductor & termination considerations . . . . . . . . . . . . . . . . . . . . 371-373Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 374-376Out-of-stock substitution/upgrades . . . . . . . . . . . . . . . . . . . . . . . . . . . . 376Cooper Bussmann electrical trademarks . . . . . . . . . . . . . . . . . . . . . . . . 376Industrial & commercial fuse applications . . . . . . . . . . . . . . . . . . .377-378
Catalog Number Index . . . . . . . . . . . . . . . . . . . . 379-383
Sales support & manufacturing facilities . . . . . . . . . . . 384
Cross reference and Low-Peak® Fuse Stock ConsolidationInside back cover
Low Voltage
BranchCircuit
Low Voltage
Supplementary
Fuses
ElectronicFuses
Medium
VoltageFuses
High SpeedFuses
IEC&
BritishFuses
FuseHolders
& Blocks
Power
DistributionBlocks
Wire
ConnectionProducts
DisconnectsTelcom
ProtectionDevices
SurgeSuppression
DevicesAccessories
ApplicationGuide
Index
Catalog Sections Page
Low Voltage, Branch Circuit Rated Fuses . . . . . 7
Low Voltage Supplementary Fuses . . . . . . . . . . 39
Electronic - PC Board and Small . . . . . . . . . . . 53
Medium Voltage Fuses and Fuse Links . . . . . . . 67
High Speed Fuses . . . . . . . . . . . . . . . . . . . . . 87
IEC & British Standard Fuses . . . . . . . . . . . . . 213
Fuse Holders and Blocks . . . . . . . . . . . . . . . . 231
Power Distribution Blocks . . . . . . . . . . . . . . . 275
Wire Connection Products . . . . . . . . . . . . . . . 281
Disconnects . . . . . . . . . . . . . . . . . . . . . . . . 303
Telecom Protection Devices . . . . . . . . . . . . . 331
Surge Suppression Devices . . . . . . . . . . . . . . 351
Accessories . . . . . . . . . . . . . . . . . . . . . . . . 255
Application Guide . . . . . . . . . . . . . . . . . . . . . 361
Index by Part Number . . . . . . . . . . . . . . . . . .379
RED indicates NEW information
Electronic - PC Board andSmall Dimension Fuses . . . . . . . . . . . . . . . . .
For product Data Sheets, visit www.cooperbussmann.com/products/datasheet.asp2
Selecting circuit protection
Low Voltage, Branch Circuit Rated Fuses
The following fuse selection guides are based on the 2005NEC® and provided fuse recommendations for the variousapplications listed.
These are only suggestions. Final fuse selection should beperformed only by a qualified personnel able to fully assesan application’s circuit protection requirements. If you needassistance in selecting a fuse for a particular application, callthe Cooper Bussmann Application Engineering team. This
team is staffed by degreed electrical engineers and availableby phone for technical and application support Monday –Friday, 8:00 a.m. – 5:00 p.m. Central Time.
Application Engineering can be reached via phone, fax or e-mail:
• Phone: 636-527-1270• Fax: 636-527-1607• E-mail: [email protected]
Fuse & Holder RecommendationsFuse Holder(s) Fuse Holder(s)BAF HEB KTK-R HEYBAN HEX FNQ-RKTK HPC-D LP-CCFNMFNQFNW
Mercury, Sodium, etc.
Fluorescent
All Other (Mercury,Sodium, etc.)
Indoor
Outdoor
Consult fixture manufacturer for size and type.
Consult fixture manufacturer for size and type.
Consult fixture manufacturer for size and type.
Fuse & Holder RecommendationsFuse Holder(s) Fuse Holder(s)GLR HLR GLQ HLQGMF GMQGRF
Ballasts
Fuse & Holder RecommendationsFuse Holder(s) Fuse Holder(s) Fuse Holder(s)BAF HPF KTK-R HPS-RR SC 0-15 HPF-EEBAN HPS FNQ-R HPF-RR HPS-EEKTK LP-CC SC 20 HPF-JJFNM HPS-JJFNQ KTQ HPS-L SC 25-30 HPF-FFFNW BBS HPF-L HPS-FF
Capacitors (NEC® 460)
Protected byTime-Delay Fuses.
150% to 175% of Full Load Current
On Load Side of Motor RunningOvercurrent Device.
Protection recommended as shown, but not required.
Protected byNon-Time-Delay Fuses.
250% to 300% of Full Load Current.
Fuse RecommendationsVolts Fuse(s)0-250 LPN-RK_SP, FRN-R0-600 LPS-RK_SP, FRS-R0-600 LPJ_SP, LP-CC,
FNQ-R, TCF
Fuse RecommendationsVolts Fuse(s)0-250 KTN-R, NON0-300 JJN0-600 KTS-R, NOS0-600 JKS, KTK-R0-600 JJS
For product Data Sheets, visit www.bussmann.com/products/datasheet.asp 3
Selecting circuit protection
Low Voltage, Branch Circuit Rated Fuses
Mains, Feeders, Branches
Feeder Circuits(600A & Less)
Fuse RecommendationsVolts Fuse(s)0-25O LPN-RK_SP, FRN-R0-600 LPS-RK_SP, FRS-R0-600 LPJ- SP, LP-CCMotor Loads
No Motor Load
Combination MotorLoads and Other Loads
100% of non-continuous load plus 125% of continuous load.
150%* of the FLA of largest motor (if there are two or moremotors of same size, one is considered to be the largest) plusthe sum of ail the FLA for all other motors plus 100% of non-continuous, non-motor load plus 125% of continuous, non-motor load.
150%* of the FLA of largest motor (if there are two or moremotors of same size, one is considered to be the largest) plusthe sum of ail the FLA for ail other motors.
*A max. of 175% (or the next standard size if 175% does notcorrespond to a standard size) is allowed for all but woundrotor and all dc motors.
Fuse RecommendationsVolts Fuse(s)0-250 LPN-RK_SP, FRN-R0-300 JJN0-600 LPS-RK_SP, FRS-R0-600 JJS0-600 LPJ_SP, LP-CC
JKS, KTK-R, LPT
Main, Branch &Feeder Circuits
(601-6000A)
150% to 225% of full load current of largest motor plus 100%of full load current of all other motors plus 125% of continuousnon-motor load plus 100% of non-continuous non-motor load.
Fuse RecommendationVolts Fuse(s)0-600 KRP-C_SP
Electric Heat (NEC® 424)
Electric Space Heating Size at 125% or next size larger but in no case larger than60 amps for each subdivided load.
Electric Boilers withResistance Type Immersion
Heating Elements in an ASMERated and Stamped Vessel
Size at 125% or next size larger but in no case larger than150 amps for each subdivided load.
Fuse RecommendationVolts Fuse(s)0-250 LPN-RK_SP
FRN-R, NON0-300 JJN0-480 SC 25 to SC 600-600 LPS-RK_SP
FRS-R, NOS0-600 JJS0-600 LPJ_SP, LP-CC
FNQ-R, JKS, KTK-R,TCF, SC 1⁄2 to SC 20
For product Data Sheets, visit www.cooperbussmann.com/products/datasheet.asp4
Selecting circuit protection
Low Voltage, Branch Circuit Rated Fuses
Above 600V
600V & Less
Fuse RecommendationsVolts Fuse(s)0-250 LPN-RK_SP, FRN-R0-600 LPS-RK_SP, FRS-R0-600 LPJ_SP, TCF
Fuse RecommendationsVolts Fuse(s)0-250 KTN-R, NON0-300 JJN0-600 KTS-R, NOS0-600 JJS0-600 LP-CC, JKS, KTK-R,
LPT
Short-Circuit Only
Backup Overload w/Motor Starter & Short-Circuit Protection
Short-Circuit Only
Protected by Time-Delay Fuses
Protected by Non-Time Delay Fuses &all Class CC Fuses
Compare the min. melting time-current characteristics of the fuses with the time-current characteristics of the overload relaycurve. The size fuse which is selected should be such that short.circuit protection is provided by the fuse and overload pro-tection is provided by the controller overload relays.
Fuse RecommendationsVolts Fuse(s)2400 JCK, JCK-A, JCH4800 JCL, JCL-A, JCG7200 JCR, 7.2 WKMSJ
Motor Loads (NEC® 430)
125% of motor FLA or next size larger.
130% of motor FLA or next size larger.
175%* of motor FLA or next size larger. (If 175% does not cor-respond to a standard size). If this will not allow motor to start,due to higher than normal inrush currents or longer than nor-mal acceleration times (5 sec. or greater), fuse may be sized upto 225% or next size smaller.
Max. of 300%* of motor FLA or next size larger (if 300% doesnot ocrrespond to a standard size). If this will not allow motorto start due to higher than normal inrush currents or longerthan normal acceleration times (5 sec. or greater), fusesthrough 600 amps may be sized up to 400% or next sizesmaller.
Fuse Sized For:
*150% for wound rotor and all DC motors.
Fuse RecommendationsVolts Fuse(s)0-250 FRN-R0-600 FRS-R
Fuse RecommendationsVolts Fuse(s)0-250 LPN-RK_SP0-600 LPS-RK_SP
Solenoids (Coils)Branch Circuit
FusesSize at 125% or next size smaller.
Fuse RecommendationVolts Fuse(s)0-250 Best: LPN-RK_SP
FRN-R0-600 LPS-RK_SP
FRS-R0-600 LPJ_SP, LP-CC
FNQ-R, TCF
SupplementaryFuses
Size at 125% or next size larger.Fuse RecommendationVolts Fuse(s)0-32 MDL 9-30A,
FNM 20-30A0-125 MDA 25-30A,
FNM 12-15A0-250 MDL 1⁄16-8A,
MDA 2⁄10-20A,FNM 1⁄10-10A,FNW 12-30A,MDQ 1⁄100-7A
0-500 FNQ 1⁄10-30A
For product Data Sheets, visit www.bussmann.com/products/datasheet.asp 5
Selecting circuit protection
Low Voltage, Branch Circuit Rated Fuses
PrimaryProtection
Only
*When 125% of FLA corresponds toa standard rating, the next larger sizeis not permitted.
Primary AndSecondaryProtection
Optimum Protection
125% or next size larger
125% or next size larger
125% or next size larger Max. of 125% or next larger*
NEC® MaximumsMax. 300% or next size smaller (SeeNEC® 430.72(C) for control circuittransformer maximum of 500%
Max. 167% or next size smaller
Maximum Fuse Size
% of Primary FLA(or next FLA size smaller)
A = 250%B = 250%C = 600%D = 600%E = 400%F = 400%
% of Secondary FLAA = 167% or next size smallerB = 125% or next size larger*C = 167% or next size smallerD = 125% or next size larger*E = 167% or next size smallerF = 125% or next size larger*
Rated secondary current 9amps or greater
Rated secondary currentless than 9 amps
TransformerImpedance of 6%or Less
Rated secondary current 9amps or greater
Rated secondary currentless than 9 amps
TransformerImpedance ofMore Than 6%But Less Than10%
Rated secondary currentless than 9 amps
Rated secondary current 9amps or greater
Without ThermalOverloadProtection
With ThermalOverloadProtection
Note: Components on the secondary stillneed overcurrent protection Rated primary current less
than 2 amps
Rated primary currentgreater than or equal to 9amps
Rated primary currentgreater than or equal to 2amps but less than 9 amps
Transformers 600V Nominal or Less (NEC® 450.3)
Fuse RecommendationsVolts Fuse(s)250V LPN-RK_SP, FRN-R600V KRP-C_SP, LPJ_SP, LPS-RK_SP, FNQ-R, FRS-R, TCF
A A
B
C
D
E
F
B
C
D
E
F
Primary and secondaryfuses at 125% of prima-ry and secondary FLA ornext size larger
Maximum Fuse Size
For product Data Sheets, visit www.cooperbussmann.com/products/datasheet.asp6
Selecting circuit protection
Low Voltage, Branch Circuit Rated Fuses
Solid State Devices (Diodes, SCRs, Triacs, Transistors)
Short-CircuitProtection
Only
“F,” “S,” “K,” & 170M Series fuses sized up to several sizeslarger than full load RMS or dc rating of device.
Fuse RecommendationsVolts Fuse(s)0-130 FWA0-250 FWX0-500 FWH0-600 FWC, KAC, KBC0-700 FWP, 170M Series,
SPP0-1000 FWJ, 170M Series,
SPJ
SupervisedInstallations
UnsupervisedInstallations
Transformers Over 600V Nominal (NEC® 450.3)
Fuse RecommendationsVolts Fuse(s)250V LPN-RK_SP, FRN-R600V LPS-RK_SP, LPJ-_SP,
KRP-C_SP, FRS-R, FNQ-R,TCF
2475V JCD2750V JCX2750/5500V JCW5500V JCE, JCQ, JCY, JCU,
5.5 ABWNA, 5.5 AMWNA,5.5 FFN
7200V 7.2 ABWNA, 7.2 SDLSJ, 7.2 SFLSJ
8300V JCZ, JDZ, 8.25 FFN15500V JCN, JDN, JDM, 15.5 CAVH17500V 17.5 CAV, 17.5 SDM24000V 24 SDM, 24 SFM, 24 FFM36000V 36 CAV, 36 SDQ, 36 SFQ38000V 38 CAV
Note: Components on the secondary still needovercurrent protectionPrimary at code max. of 250% or
next standard size if 250% does notcorrespond to a standard rating
PrimaryProtectionOnly
TransformerImpedance LessThan or Equal to 6%
Primaryat codemax. of300%
SecondaryOver 600V
Secondary atcode max. of250%
Secondary atcode max. of250%
Secondary atcode max. of225%
SecondaryOver 600V
Primaryat codemax. of300%
Secondary atcode max. of250%
SecondaryOver 600V
Primary at code max. of300% or next standard sizeif 300% does not corre-spond to a standard rating
TransformerImpedance LessThan or Equal to 6%
Primary at code max. of300% or next standard sizeif 300% does not corre-spond to a standard rating
SecondaryOver 600V
Secondary at code max. of125% or next standard sizeif 125% does not corre-spond to a standard rating
Secondary at code max. of225% or next standard sizeif 225% does not corre-spond to a standard rating
Secondary at code max. of125% or next standard sizeif 125% does not corre-spond to a standard rating
Secondary at code max. of250% or next standard sizeif 250% does not corre-spond to a standard rating
TransformerImpedance GreaterThan 6% But LessThan 10%
Secondary600V orBelow
Secondary600V orBelow
PrimaryandSecondaryProtection
TransformerImpedance GreaterThan 6% But LessThan 10%
Secondary600V orBelow
Secondary600V orBelow