Features• Displays actual temperature and alarm values.• 4 alarm values can be entered: low-low, low,
high and high-high temperature alarm.• Large 17mm (0.67") digits.• Selectable on-screen engineering units
°C - °F - K• Operational temperature -30°C up to +80°C
(-22°F up to 178°F).• Very compact design for panel mount, wall
mount or field mount applications.• Rugged aluminum field mount enclosure
IP67 / NEMA4X.• Intrinsically Safe
II 1 GD EEx ia IIB/IIC T4 T100°C.• Explosion/flame proof II 2 GD EEx d IIB T5.• Alarm and analog signal outputs.• Full Modbus communication RS232/485/TTL.• Loop or battery powered, 8 - 24V AC/DC or
115 - 230V AC power supply.• Sensor supply 3.2 - 8.2 - 12 - 24V DC.
Signal output• Up to 4 free configurable alarm outputs.• (0)4 - 20mA / 0 - 10V DC according to the
temperature.
Signal inputTemperature• PT100 - 2 or 3 wire.• (0)4 - 20mA.• 0 - 10V DC.
Applications• For applications where continous temperature
measurement and monitoring is important.Also re-transmission of the actual temperatureor serial communication is required.Alternative basic model: F040 - F043.
TEMPERATURE MONITOR WITH ANALOG AND HIGH / LOW
ALARMS OUTPUTS
DA
TAS
HE
ET
F14
3 -
TE
MP
ER
ATU
RE
MO
NIT
OR
1
General informationIntroductionThe F143 is a versatile temperature indicatorwith continous temperature monitoring feature.It offers the facility to set two low temperatureand two high temperature alarm values. If desired, an ignore function can be set up toallow for an incorrect temperature for a certainperiod of time. Up to four outputs are availableto transmit the alarm condition. A wide selection of options further enhance thismodels capabilities, including Intrinsic Safetyand full Modbus communication.
DisplayThe display has large 17mm (0.67”) and 8mm(0.31”) digits which displays the temperature,measuring unit and alarm values. The alarmvalues can be password protected. On-screenengineering units are easily configured from acomprehensive selection.
ConfigurationAll configuration settings are accessed via asimple operator menu which can be pass-codeprotected. Each setting is clearly indicated withan alphanumerical description, thereforeavoiding confusing abbreviations. All settingsare safely stored in EEPROM memory in theevent of sudden power failure.
Analog output signalThe actual temperature is re-transmitted withthe (0)4 - 20mA or 0 - 10V DC output signal.The output signal is updated ten times persecond with a filter function being available tosmoothen out the signal if desired. The outputvalue is user defined in relation to thetemperature, e.g. 4mA equals to -20°C and20mA equals to 250 °C. The output signal canbe passive, active or isolated where the passiveoutput type will loop power the F143 as well.
Alarm outputUp to four configurable outputs are available totransmit the alarm condition. You can have e.g.two the same low alarm outputs, one highalarm output and one "all alarms" output. Type OS offers four mechanical relay outputs.However, only two outputs are available inIntrinsically Safe aplications. Three outputs are
available in all other configurations. The outputsignals can be a passive NPN, active PNP or anisolated electro-mechanical relay.
Signal inputThe F143 does accept (0)4 - 20mA and 0 - 10Vinput signals from any type of temperaturemeasurement device. Also a two or three wirePT100 sensor can be used.
CommunicationAll process data and settings can be read andmodified manually or through the Modbuscommunication link (RS232 / RS485). Full Modbus functionality remains available forthe Intrinsically Safe version (TTL).
Hazardous areasFor hazardous area applications, this model hasbeen ATEX certified Intrinsically Safe II 1GD EEx ia IIB / IIC T4 T100°C with an allowedoperational temperature of -30°C to +70°C (-22°F to +158°F). A flame proof enclosure is alsoavailable with the rating II 2 GD EEx d IIB T5.
EnclosuresVarious types of enclosures can be selected, allATEX approved. As standard the F143 issupplied in an GRP panel mount enclosure,which can be converted to an IP67 / NEMA 4XGRP field mount enclosure by the addition of aback case. Most popular is our ruggedaluminum field mount enclosure with IP67 /NEMA 4X rating. Both European or U.S. cablegland entry threads are available.
Overview application F143
Alarmoutput 4
Analogoutput
Communicationlink
Temperatureinput
Alarmoutput 3
Alarmoutput 2
Alarmoutput 1
F1432
Dimensions enclosuresAluminum & GRP panel mount enclosure
Aluminum & GRP field / wall mount enclosures
Terminal connections
CB:
RS2
32
CH
: RS4
85 -
2 w
ire
AB
YZ
RX
DT
XD
CT:
TTL
Intri
nsic
ally
Saf
e
A: (0
)4 -
20m
A
U: 0
- 10
V
+
==
56
ALAR
M O
UTP
UT
12
POW
ER S
UPP
LY
GN
D
-+
PD: 8
- 24
V AC
PD: 8
- 24
V D
C
-+
PF: 2
4V A
C
PM: 1
15 -
230V
AC
PF: 2
4V D
C
PD -
XI: 1
6 - 3
0V D
C +-
+
OT:
pas
sive
tran
s.
OA:
act
ive
24V
DC
OR
: mec
h. re
lay
+
==
34
ALAR
M O
UTP
UT
1011
TEM
PER
ATU
RE
INPU
T
9
+ +
AP: 4
- 20
mA
AA: 4
- 20
mA
AF: 4
- 20
mA
AU: 0
- 10
V
AI: 4
- 20
mA
AB: 0
- 20
mA
78
ANAL
OG
OU
TPU
T
+II-
+I +U
I U
+II
+II-
+II
OT:
pas
sive
tran
s.
OA:
act
ive
24V
DC
OR
: mec
h. re
lay
+
+
+I +U
1314
1218
1917
1516
ALAR
M O
UTP
UT
+
OT:
pas
sive
tran
s.
OA:
act
ive
24V
DC
+
2728
CO
MM
UN
ICAT
ION
/ BA
CKL
IGH
T
2623
2425
TP: P
T100
2-w
ire
2122
TEM
PER
ATU
RE
INPU
T
20 +
TP: P
T100
3-w
ire
+
2930
31
DT
R+
12V
CI:
RS4
85 -
4 w
ire
AB
RX
DT
XD
DT
R+
12V
Plea
se n
ote:
Term
inal
con
nect
ions
for t
he F
143
with
four
ala
rm
outp
uts
(type
OS)
is s
how
n on
one
of t
he n
ext p
ages
.
PX: 8
- 30
V D
CO
utpu
t loo
p po
wer
ed u
nit w
ith ty
pe A
P(te
rmin
als
GN
D -
1 - 2
are
not
ava
ilabl
e)
A - P
L: 4
- 20
mA
+I
ZB: B
ackl
ight
opt
ion
++
+
PB /
PC: b
atte
ry p
ower
edIn
tern
al lo
ng li
fe L
ithiu
m b
atte
ry(te
rmin
als
GN
D -
1 - 2
are
not
ava
ilabl
e)
PL: i
nput
loop
pow
ered
(term
inal
s G
ND
- 1
- 2 a
re n
ot a
vaila
ble)
(With
PD
/ PF
/ PM
term
inal
s 26
/ 31
are
not
ava
ilabl
e,
bac
klig
ht p
ower
sup
ply
is in
tegr
ated
.)
F143 3
130 mm (5.12")
120
mm
(4.7
2")
31 mm(1.22")
29 mm(1.14")
115 (4.53")
98
(3.8
6")
panel cut-outHB & HC enclosures
75 mm (2.95")
130 mm (5.12")
112 mm (4.40")
60 m
m (2
.36"
)
120
mm
(4.7
2")
M20 x 1,5PG9 PG9
30mm 30mm
22,5
0mm
M20 x 1,5M16 x 1,5 M16 x 1,5
30mm 30mm
22,5
0mm
M20 x 1,5
22,5
0mm
M20 x 1,5 M20 x 1,5
25mm 25mm
22,5
0mm
1/2"NPT
0.9"
1/2"NPT1/2"NPT 1/2"NPT
1.18" 1.18"
0.9"
HA
HM
HN
HO
HD
HP
HE
HT
HF
HU
HG
HZ
HH6 x M12
12mm 12mm
24mm24mm36mm36mm
14m
m17
mm
Ø12
12mm 12mm
24mm24mm36mm36mm
14m
m17
mm
22,5
0mm
30mm 30mm
Ø16 Ø16Ø20
0.9"
Ø22 (0.866")
22,5
0mm
25mm 25mm
Ø20 Ø20
Aluminum GRP
Typical wiring diagram F143-T-AP-CH-OT-PX Typical wiring diagram F143-A-AA-CB-OA-PD
01
29
1011
65
Common ground
Signal
Supply *
Common ground
TERMINAL CONNECTORSF100 - series
8 - 24V DC
+
-
78
Common ground
Common ground
Main supply
2827
2629
Common ground
*Supply voltage: 3.2 - 8.2 - 12 - 24V DC to sensor
RXD
TXD
DTR12V
8 - 24V AC
Switch output type OA:active 24V DC signal
Analog output type AA:active 4 - 20mA
Temperature sensor type A:(0)4 - 20mA
e.g. indicator
+
-
+
-
Earth
Modbus communication type CB: RS232
Power supply type PD: 8 - 24V AC / DC
24V AC / DC POWER SUPPLY
43Common ground
+
-
Switch output type OA:active 24V DC signal
65Common ground
+
-
Switch output type OA:active 24V DC signal
alarm output 3
alarm output 2
alarm output 1
65Common ground
TERMINAL CONNECTORSF100 - series
78
Common ground
2827
2629
8 - 30V DC
+
-
A
Common ground
B
e.g. indicator
Analog output type AP: passive 4 - 20mA (loop powered)
Modbus communication type CH: RS485 - 2 wire
Switch output type OT:passive transistor
OUTPUT LOOP POWERED4
3Common ground
1615Common ground
alarm output 3
Switch output type OT:passive transistor
alarm output 1
Switch output type OT:passive transistor
alarm output 2
2221
20
Supply
Signal
Signal
Temperature input type T:
PT100 3 - wire
F1434
Typical wiring diagram F143-A-AI-CI-OR-PM Typical wiring diagram F143-T-AP-CB-OS-PD
01
29
1011
65
TERMINAL CONNECTORSF100 - series
N
78
Common ground
Main supply
26
8 - 30V DC
+
-
Common ground
Common ground
Signal
Supply *
Earth
L1
Temperature sensor input type A:(0)4 - 20mA
Switch output type OR:mechanic relay
e.g. indicator
Power supply type PM:115 - 230V AC
Analog output type AI:passive isolated 4 - 20mA
2831
3029
Y
Z
A
B
Modbus communication type CI: RS485 - 4 wire
115 - 230V AC POWER SUPPLY
*Supply voltage: 3.2 - 8.2 - 12 - 24V DC to sensor
alarm output 1
43
alarm output 2
1615Common ground
Switch output type OT:passive transistor
8 - 24V DC+
-
alarm output 3
01
2
TERMINAL CONNECTORSF100 - series
24V DC
+
-
Common ground
Main supply
2827
2629
Common ground
*Supply voltage: 3.2 - 8.2 - 12 - 24V DC to sensor
RXD
TXD
DTR12V
24V AC
Earth
Modbus communication type CB: RS232
Power supply type PD: 24V AC / DC
24V AC / DC POWER SUPPLY
89
Common ground
8 - 30V DC
+
-
e.g. indicator
Analog output type AP: passive 4 - 20mA (loop powered)
1011
1514
N
L1
Switch output type OS:mechanic relay
1312
1716
alarm output 1 0 - 230V AC / DC
alarm output 2
alarm output 3
alarm output 4
2221
20
Temperature input type T:
PT100 3 - wire
F143 5
Hazardous area applicationsThe F143-XI has been ATEX approved byKEMA for use in Intrinsically Safeapplications. It is approved according to
II 1 GD EEx ia IIB/IIC T4 T100°C for gasand dust applications with an operationaltemperature range of -30°C to +70°C (-22°F to+158°F). Besides the I.S. power supplies forthe two alarm outputs, it is allowed toconnect up to three I.S. power supplies in IIBapplications or one in IIC applications. Full functionality of the F143 remainsavailable, including two alarm outputs and 4 - 20mA output and Modbus communication(type CT). Power supply type PD-XI offers asensor supply according to the connectedpower supply voltage at terminal 1. A flameproof enclosure with rating II 2 GD EEx dIIB T5 is available as well. Please contact yoursupplier for further details.
Certificate of conformity KEMA 03ATEX1074 X
TERMINAL CONNECTORSF100 - series
HAZARDOUS AREA SAFE AREA
Common ground 78
RXD
Common ground
TXD
2826
29
DTR+12V
27
Analog output type AP:passive 4 - 20mA
(not used in this example).
Modbus communication type CT: TTLPossible for battery powered applications
(not used in this example).
Please note: communciation type CT is not allowed in IIC applications.
Please note: type AP may be used in combination with the battery
(type PC), but only in IIB applications!
AP will power the unit (output loop powered);
the battery will be disabled automatically till power
is disconnected.
2221
20
Supply
Signal
Signal
Temperature input type T:
PT100 3 - wire
34
Common ground
56
Common ground Alarm output type OT:passive transistor
(not used in this example).
F143
Configuration example IIB and IIC F143-T-(AP)-(CT)-(OT)-PC-XI - Battery powered unit
6
Configuration example IIB - F143-A-AP-CT-OT-PX-XI - Output loop powered
TERMINAL CONNECTORSF100 - series
HAZARDOUS AREA SAFE AREA
34
910
11
Common ground
Common ground
Signal
Supply *
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
Analog output type AP:passive 4 - 20mA (output loop powered)
RXD
Common ground
TXD
2826
295
6
Common ground
Temperature input type A:(0)4 - 20mA
Ci = 17nF
78
Common ground
DTR+12V
27
+
-
ISOLATOR:I.S. Certified Isolator
TTL to RS232 / RS422 / TTL
For example: MTL5051
+
-
POWER SUPPLYe.g. MTL 5025
and / or REPEATER
e.g. MTL 5042
Uo=max 30V
Io=max 100mA
Po=max 750mW
Uo=max 30V
Io=max 250mA
Po=max 850mW
POWER SUPPLY
For example MTL5025
Uo=max 30V
Io=max 100mA
Po=max 750mW
+
e.g. indicator
e.g. PC
e.g. indicator
Modbus communication type CT: TTL
Ci is negligiblysmall
+
-
POWER SUPPLYe.g. MTL 5025
or SWITCH INTERFACE
e.g. MTL 5011B
Uo=max 30V
Io=max 100mA
Po=max 750mW
+
-
POWER SUPPLYe.g. MTL 5025
or SWITCH INTERFACE
e.g. MTL 5011B
Uo=max 30V
Io=max 100mA
Po=max 750mW
Ci is negligiblysmall
Ci is negligiblysmall
e.g. sounder
Switch output type OT:passive transistor
Switch output type OT:passive transistor Alarm output 2
Alarm output 1
e.g. sounder
* Note sensor supply voltage: 3.2V DC - not suitable to power analog sensors.
Note: above values are safety values.Consult the technical specification for operational values.
F143 7
Configuration example IIB - F143-A-AF-CT-OT-PL-XI - Input loop powered
TERMINAL CONNECTORSF100 - series
HAZARDOUS AREA SAFE AREA
RXD
Common ground
TXD
2826
29
DTR+12V
27
ISOLATOR:I.S. Certified Isolator
TTL to RS232 / RS422 / TTL
For example: MTL5051
Uo=max 30V
Io=max 250mA
Po=max 850mW
+
-
e.g. PC
Modbus communication type CT: TTL
Ci = 17nF
34
910
Common ground
Common ground
Signal
Ci is negligiblysmall
Analog output type AF:passive floating 4 - 20mA
56
Common ground
78
Temperature sensor input type: A - PLinput loop powered 4 - 20mA
+
-
+
-
POWER SUPPLYe.g. MTL 5025
and / or REPEATER
e.g. MTL 5042
Uo=max 30V
Io=max 100mA
Po=max 750mW
POWER SUPPLY
For example MTL5025
Uo=max 30V
Io=max 100mA
Po=max 750mW
e.g. indicator
e.g. indicator
+
-
POWER SUPPLYe.g. MTL 5025
or SWITCH INTERFACE
e.g. MTL 5011B
Uo=max 30V
Io=max 100mA
Po=max 750mW
+
-
POWER SUPPLYe.g. MTL 5025
or SWITCH INTERFACE
e.g. MTL 5011B
Uo=max 30V
Io=max 100mA
Po=max 750mW
Ci is negligiblysmall
Ci is negligiblysmall
e.g. sounder
Switch output type OT:passive transistor
Switch output type OT:passive transistor Alarm output 2
Alarm output 1
e.g. sounder
Note: above values are safety values.Consult the technical specification for operational values.
F1438
Configuration example IIB and IIC - F143-A-AP-(CT)-OT-PD-XI - Power supply 16 - 30V DC
TERMINAL CONNECTORSF100 - series
HAZARDOUS AREA SAFE AREA
Ci = 17nF
34
910
11
Common ground
Common ground
Common ground
Signal
TOTAL Co OF ALL CONNECTEDANALOG APPARATUS IN IICAPPLICATIONS MAY NOT EXCEED 66nF MINUS 17nF
(17nF IS USED BY THE ANALOG OUTPUT SIGNAL TERMINAL 7 + 8).
Supply *
Main supply
Circ
uit d
epen
ds o
n ty
pe o
f sig
nal
Power supply type PD: 16 - 30V DC (please note: PD and battery supply (type PC) is NOT allowed in IIC applications).
Analog output type AP:passive 4 - 20mA
RXD
Common ground
TXD
2826
295
6
Common ground
01
2
Temperature input type: A(0)4 - 20mA
DTR+12V
27
ISOLATOR:I.S. Certified Isolator
TTL to RS232 / RS422 / TTL
For example: MTL5051
Uo=max 30V
Io=max 250mA
Po=max 850mW
+
-
POWER SUPPLY
For example MTL5025
Uo=max 30V
Io=max 100mA
Po=max 750mW
+
-
+
-
POWER SUPPLYe.g. MTL 5025
or SWITCH INTERFACE
e.g. MTL 5011B
Uo=max 30V
Io=max 100mA
Po=max 750mW
+
-
POWER SUPPLYe.g. MTL 5025
or SWITCH INTERFACE
e.g. MTL 5011B
Uo=max 30V
Io=max 100mA
Po=max 750mW
e.g. PC
e.g. indicator
Modbus communication type CT: TTLPlease note: communciation type CT is not allowed in IIC applications.
Ci is negligiblysmall
Ci is negligiblysmall
Ci is negligiblysmall
e.g. sounder
Switch output type OT:passive transistor
Switch output type OT:passive transistor Alarm output 2
* Note power supply type PD: the supply voltage to sensors is as connected to terminal 1 (internally linked).
Alarm output 1
e.g. sounder
78
Common ground
Note: above values are safety values.Consult the technical specification for operational values.
F143 9
F143
Technical specificationGeneral
DisplayType High intensity reflective numeric and
alphanumeric LCD, UV-resistant.Dimensions 90 x 40mm (3.5” x 1.6”).Digits Seven 17mm (0.67") and eleven 8mm (0.31") digits.
Various symbols and measuring units.Refresh rate User definable: 8 times/sec. - 30 secs.Option ZB Transflective LCD with green LED backlight.
Good readings in full sunlight and darkness. Note Only available for safe area applications.
Operating temperatureOperational -30°C to +80°C (-22°F to +178°F).Intrinsically Safe -30°C to +70°C (-22°F to +158°F).
Power requirementsType PB Long life Lithium battery - life-time depends upon
settings and configuration - up to 5 years.Type PC Intrinsically Safe long life lithium battery - life-time
depends upon settings and configuration - up to 5 years.
Type PD 8 - 24V AC / DC ± 10%. Power consumption max. 10 Watt. Intrinsically Safe: 16 - 30V DC; power consumption max. 0.75 Watt.
Type PF 24V AC / DC ± 10%. Power consumption max. 15 Watt.Type PL Input loop powered from sensor signal 4 - 20mA
(type “A”) - requires types AI or AF and OT.Type PM 115 - 230V AC ± 10%. Power consumption max. 15 Watt.Type PX 8 - 30V DC. Power consumption max. 0.5 Watt. Type ZB 12 - 24V DC ± 10% or type PD / PF / PM.
Power consumption max. 1 Watt.Note PB/PF/PM Not availble Intrinsically Safe.Note PF/PM The total consumption of the sensors and outputs
may not exceed 400mA @ 24V.Note For Intrinsically Safe applications, consult the safety
values in the certificate.
Sensor excitationType PB/PC/PX 3.2V DC.
Note This is not a real sensor supply. Only suitable for sensors with a very low power consumption.
Type PD 3.2 - 8.2 - 12 and 24V DC - max. 50mA @ 24V DC.Type PD-XI The sensor supply voltage will be according to power
supply as connected to terminal 1.Type PF / PM 3.2 - 8.2 - 12 and 24V DC - max. 400mA @ 24V DC.
Terminal connectionsType Removable plug-in terminal strip.
Wire max. 1.5mm2 and 2.5mm2.
Data protectionType EEPROM backup of all settings. Data retention at
least 10 years.Pass-code Configuration settings can be pass-code protected.
Hazardous areaIntrinsically Safe ATEX approval ref.: II 1 GD EEx ia IIB/IIC T4 T100°C.Type XI Maximum ambient +70°C (158°F).Explosion proof ATEX approval ref.: II 2 GD EEx d IIB T5.Type XF Dimensions of enclosure: 300 x 250 x 200mm
(11.8” x 9.9” x 7.9”) L x H x D.Weight appr. 15 Kg.
EnvironmentElectromagnetic Compliant ref: EN 61326 (1997), EN 61010-1 (1993).compatibility
CasingGeneralWindow Polycarbonate window.Sealing Silicone.Control keys Three industrial micro-switch keys. UV-resistant
silicone keypad. Option ZS Silicone free ABS enclosure with EPDM and PE
sealings. UV-resisitant polyester keypad. Note This option comes with type HD only.
Aluminum wall / field mount enclosuresGeneral Die-cast aluminum wall/field mount enclosure IP67 /
NEMA 4X with 2-component UV-resistant coating.Dimensions 130 x 120 x 75mm (5.12" x 4.72" x 2.95") - W x H x D.Weight 1064 gr.
Type HA Cable entry: 2 x PG9 and 1 x M20. Type HM Cable entry: 2 x M16 and 1 x M20. Type HN Cable entry: 1 x M20. Type HO Cable entry: 2 x M20. Type HP Cable entry: 6 x M12. Type HT Cable entry: 1 x 1/2" NPT.Type HU Cable entry: 3 x 1/2" NPT.Type HZ Cable entry: no holes.
GRP wall / field mount enclosuresGeneral GRP wall/field mount enclosure IP67 / NEMA 4X,
UV-resistant and flame retardant. Dimensions 130 x 120 x 75mm (5.12" x 4.72" x 2.95") - W x H x D.Weight 566 gr.
Type HD Cable entry: no holes.Type HE Cable entry: 2 x Ø 16mm and 1 x Ø 20mm.Type HF Cable entry: 1 x Ø 22mm (0.866").Type HG Cable entry: 2 x Ø 20mm. Type HH Cable entry: 6 x Ø 12mm.
Panel mount enclosuresDimensions 130 x 120 x 60mm (5.12" x 4.72" x 2.36") - W x H x D.Panel cut-out 115 x 98mm (4.53" x 3.86") L x H.
Type HB Die-cast aluminum panel mount enclosure IP65 / NEMA 4.
Weight 570 gr.Type HC GRP panel mount enclosure IP65 / NEMA 4,
UV-resistant and flame retardant.Weight 422 gr.
10
F143
Signal inputsTemperatureAccuracy Resolution: 14 bit. Error < 0.025mA / ± 0.125% FS.
Low level cut-off programmable.Update time Four times per second.Type A (0)4 - 20mA. Analog input signal can be scaled to
any desired range within 0 - 20mA.Span 0.000010 - 9,999,999 with variable decimal position.Offset 0.00 - 99,999.99 K.Voltage drop 2.5V @ 20mA.
Type T 2 or 3 wire PT100.Range -100°C to +200°C (-148°F to 392°F).
Accuracy 0.1°C (0.18°F).Option ZV Range: -200°C to +800°C (-328°F to 1472°F).
Accuracy 0.5°C (0.9°F).Type U 0 - 10V DC. Analog input signal can be scaled to
any desired range within 0 - 10V DC.Span 0.000010 - 9,999,999 with variable decimal position.Offset 0.00 - 99,999.99 K.Load impedance 3kΩ.Note For signal A and U: power supply to temperature
sensor is required; e.g. PD.
Signal outputsAnalog outputFunction Transmitting actual temperature.Accuracy 10 bit. Error < 0.05%. Analog output signal can be
scaled to any desired range.Update time Ten times per second.Type AA Active 4 - 20mA output (requires OA + PD, PF or PM).Type AB Active 0 - 20mA output (requires OA + PD, PF or PM).Type AF Passive floating 4 - 20mA output for Intrinsically
Safe applications (requires PC, PD or PL).Type AI Passive galvanically isolated 4 - 20mA output - also
available for battery powered models (requires PB, PD, PF, PL or PM).
Type AP passive 4 - 20mA output - not isolated. Unit will beloop powered.
Type AU Active 0 - 10V DC output (requires OA + PD, PF or PM).
Alarm outputFunction User defined: low, low-low, high, high-high or all
alarms output.Type OA Three active 24V DC transistor outputs (PNP);
max. 50mA per output (requires AA + PD, PF or PM).Type OR Two electro-mechanical relay outputs isolated (N.O.) -
max. switch power 230V AC - 0.5A (requires PFor PM) and one transistor output OT or OA (OA in combination with AA only).
Type OS Four electro-mechanical relay outputs - isolated; max. switch power 230V AC - 0.5A per relay (requires AP and PD with 24V AC / DC).
Type OT Three passive transistor outputs (NPN) - not isolated. Load Max. 50V DC - 300mA per output.Note Intrinsically Safe applications: only two transistor
outputs type OT available.
Communication optionFunction Reading display information, reading / writing all
configuration settings.Protocol Modbus ASCII / RTU.Speed 1200 - 2400 - 4800 - 9600 baud.Addressing Maximum 255 addresses.Type CB RS232Type CH RS485 2-wire Type CI RS485 4-wireType CT TTL Intrinsically Safe.
OperationalOperator functionsDisplayed • Actual temperature.functions • Low - low alarm value.
• Low alarm value.• High alarm value.• High - high alarm value.• Alarm values can be set (or only displayed).
TemperatureDigits 6 digits.Units °C, °F or K.Decimals Type T: 1.
Type A / U: 3.
Alarm valuesDigits 7 digits.Units According to the settings for temperature.Decimals According to the settings for temperature.Time units According to the settings for temperature.Type of alarm Low, high, low-low or high-high temperature alarm.
Includes alarm delay time and configurable alarm outputs.
Display example - 90 x 40mm (3.5” x 1.6”)
11
Specifications are subject to change without notice.
Ordering information Standard configuration: F143-A-AP-CX-HC-OT-PX-XX-ZX.Ordering information: F143 -_ -A _ -C _ -H _ -O _ -P _ -X _ -Z _Temperature signalA (0)4 - 20mA input.T PT100 input.U 0 - 10V DC input.Analog output signalAA Active 4 - 20mA output - requires OA + PD, PF or PM.AB Active 0 - 20mA output - requires OA + PD, PF or PM.AF I.S. floating 4 - 20mA output - requires PC, PD or PL.AI Isolated 4 - 20mA output - requires PB, PD, PF, PL or PM.AP Passive 4 - 20mA output, loop powered unit.AU Active 0 - 10V DC output - requires OA + PD, PF or PM.CommunicationCB Communication RS232 - Modbus ASCII / RTU.CH Communication RS485 - 2-wire - Modbus ASCII / RTU.CI Communication RS485 - 4-wire - Modbus ASCII / RTU.CT Intrinsically Safe TTL - Modbus ASCII / RTU.CX No communication.Panel mount enclosures - IP65 / NEMA4HB Aluminum enclosure.HC GRP enclosure.GRP field / wall mount enclosures - IP67 / NEMA4XHD Cable entry: no holes.HE Cable entry: 2 x 16mm + 1 x 20mm.HF Cable entry: 1 x 22mm (0.866”).HG Cable entry: 2 x 20mm.HH Cable entry: 6 x 12mm.Aluminum field / wall mount enclosures - IP67 / NEMA4XHA Cable entry: 2 x PG9 + 1 x M20.HM Cable entry: 2 x M16 + 1 x M20.HN Cable entry: 1 x M20.HO Cable entry: 2 x M20.HP Cable entry: 6 x M12.HT Cable entry: 1 x 1/2”NPT.HU Cable entry: 3 x 1/2”NPT.HZ Cable entry: no holes.OutputsOA Three active transistor outputs - requires AA, AB or AU and PD, PF or PM.OR Two mechanical relay outputs + one OT or OA - requires PF or PM.OS Four mechanical relay outputs - requires AP and PD.OT Three passive transistor outputs - standard configuration.Power supplyPB Lithium battery powered.PC Lithium battery powered - Intrinsically Safe.PD 8 - 24V AC / DC + sensor supply - with XI: 16 - 30V DC.PF 24V AC / DC + sensor supply.PL Input loop powered from sensor signal type “A” - requires AI or AF and OT.PM 115 - 230V AC + sensor supply.PX Basic power supply 8 - 30V DC (no real sensor supply). Unit requires external loop AP.Hazardous areaXI Intrinsically Safe.XF EExd enclosure - 3 keys.XX Safe area only.Other optionsZB Backlight. ZS Silicone free ABS enclosure with EPDM and PE sealings (type HD only).ZV PRTD-range -200°C / +800°C.ZX No options.
The bold marked text contains the standard configuration.
Available Intrinsically Safe.
FLUIDWELL bvP.O. Box 65460 AA - Veghel - The NetherlandsTel.: +31 (0)413 343786Fax.: +31 (0)413 [email protected] Internet: www.fluidwell.com C