Upload
chudyace
View
461
Download
11
Embed Size (px)
Citation preview
7/22/2019 GE MARK VI
1/22
GE Energy
Mark VI for Gas Turbine Control Retrofits
Application OverviewThis document is distributed for informational purposes only.It is not to be construed as creating or becoming part of anyGeneral Electric Company contractual or warranty obligationunless expressly stated in a written sales contract.
!2002 - 2005 by General Electric Company, USA. All rights reserved.
GEI-100538A
7/22/2019 GE MARK VI
2/22
Section Page
Introduction .................................................................................................................3Acronyms and Abbreviations ......................................................................................3Product Options...........................................................................................................4Architecture.................................................................................................................6I/O Interface.................................................................................................................8
Diagnostics ................................................................................................................10Communication .........................................................................................................10Control Functions ......................................................................................................12HMI ...........................................................................................................................16Typical Turbine Instrumentation...............................................................................18Packaging ..................................................................................................................19Typical Power Requirements.....................................................................................20
Ethernet is a registered trademark of Xerox Corporation.CIMPLICITY is a registered trademark of GE Fanuc Automation North America, Inc.Microsoft and Windows are registered trademarks of Microsoft Corporation.
Modbus is a registered trademark of Schneider Automation.Proximitor is a registered trademark of Bently Nevada.
7/22/2019 GE MARK VI
3/22
IntroductionMost existing transmitters,
sensors, and switches arecompatible with the Mark
VI I/O, and, in some cases,
the I/O is totallycompatible.
The Mark VI is a fully programmable gas turbine controller with its own power
supply, processor, communications, and I/O for turbine control, and protection.
Critical functions, such as emergency overspeed, redundant exhaust over-temperature protection, and backup synchronous check protection are provided by
the backup protection module.
Application software is derived from current control and protection algorithms,
originally designed for new gas turbines, and modified only where it is necessary for
compatibility with the existing site conditions. In addition, the controller has thespeed and capacity to implement many new advanced features such as Dry Low
NOx technology. All Mark VI controllers are shipped with application software and
display software.
Acronyms and Abbreviations
ADL Asynchronous Drives Language
DCS Distributed Control System
EGD EthernetGlobal Data
FSR Fuel Stroke Reference
GSM GE Standard Messages
GUI Graphical User Interface
HMI Human-Machine Interface
LVDT Linear Variable Differential Transformer
PDH Plant Data Highway
rms root mean square
RTD Resistance Temperature Detector
TMR Triple Modular Redundant
UDH Unit Data Highway
UPS uninterruptible power supply
VME VERSA module Eurocard
GEI-100538A Mark VI for Gas Turbine Control Retrofits 3
7/22/2019 GE MARK VI
4/22
Product OptionsThe Mark VI controller is available in two state-of-the-art types: simplexand Triple
Modular Redundant (TMR). These vary in cabinet size and I/O configuration
based on the turbine type, application (generator or mechanical drive), and I/Orequired at a particular site.
A simplex controller is available in two sizes:
36x 36 (900 mm x 900 mm), which fits into the standard Mark I or Mark IIcontroller footprint
54x 36 (1350 mm x 900 mm), which fits into the standard Mark II with ITS
controller footprint. This version also provides increased I/O capacity, as well asa redundant VME rack-power supply.
The standard size of the TMR unit is 54x 36 (1350 mm x 900 mm), which fits intothe standard Mark IV controller footprint (refer to the following diagram).
4 Mark VI for Gas Turbine Control Retrofits GEI-100538A Application Overview
7/22/2019 GE MARK VI
5/22
P
S
Control Module
X
P
S
Y
P
S
Control Module
Z
Control Module
Protection Module
Emergency Overspeed
Emergency Overtemp
Backup Synch Check
Control
Protection
Monitoring
Communication from Control Module:
Serial Modbus Slave
Serial Modbus Master
Ethernet TCP-IP Modbus Slave
Ethernet UDP-IP (UDH)
Additional
Communications(if required)
Devices on UDH:HMI, EX2000, Mark VI
P.S.
CPU
I/O
P.S.
CPU
I/O
P.S.
CPU
I/O
Ethernet - IONet
Ethernet - IONet
Ethernet - IONet
AdditionalCommunications
(if required)
TMR only
System Architecture
GEI-100538A Mark VI for Gas Turbine Control Retrofits 5
7/22/2019 GE MARK VI
6/22
ArchitectureScalable hardware and software make the Mark VI architecture well-suited for gas
turbine control retrofits.
A TMR system is generally
recommended for base load,DLN, and cogen
applications.
The TMR and simplex versions of the Mark VI controller have equivalent control
and turbine protection capabilities. The primary difference is running reliability.Running reliability is based on the percent of I/O used in the system, the percent of
I/O classified as critical, and the amount of redundancy.
TMR systems have the highest running reliability, represented by a longer Mean
Time Between Forced Outage (MTBFO) than other types of controllers.
Select a TMR system when:
Co-generation (cogen) plants where the gas turbine exhaust is the only source of
heat to generate steam for the production process and steam turbines
Turbines are equipped with triplicated field devices, for maximized runningreliability
Dry Low NOx (DLN) combustion system upgrades, where instrumentationstandards often require more replicated field devices than standard combustion
systems
Generator drive applications that require continuous base-load operation
Mechanical drive applications where compressors or pumps are critical to theproduction process
Select a simplex system when:
Using non-base load applications that are not critical to other plant processes
Customer operating experience indicates this system is adequate
6 Mark VI for Gas Turbine Control Retrofits GEI-100538A Application Overview
7/22/2019 GE MARK VI
7/22
s
Mark VI Simplex 36" by 36" Cabinet
GEI-100538A Mark VI for Gas Turbine Control Retrofits 7
7/22/2019 GE MARK VI
8/22
I/O InterfaceTerminations support the
existing #12 AWG (3.0mm2) wires at site with
barrier type terminal blocks
or ease ofmaintenance.
The Mark VI is designed for direct interface to turbine and generator devices such as
vibration sensors, flame scanners, linear variable differential transformers (LVDT),
magnetic speed pickups, thermocouples, and resistance temperature detectors(RTD). Direct monitoring of these sensors reduces the need for interposing devices
with their associated single-point failures. Direct connection to a field device reduceslong-term maintenance, and enables diagnostics to directly monitor the health of
devices mounted on the machinery.
Contact inputsare normally powered from the 125 V dc battery bus (optional 24and 48 V dc) through the Mark VI termination boards. Each contact input is optically
isolated and has a 1ms time stamp for Sequence of Events (SOE) monitoring.
Terminations for existing contact inputs can be replaced 1-for-1 or split up for
greater alarm resolution. For example, instead of having several field contacts wired
to a single contact input for theLube System Troublealarm on the enunciatorwindow, they can be separated into multiple contact inputs to provide a separate
alarm message for each problem in the lube oil system.
Diagnostics monitor the
secondary side of each fuse.Contact outputsare from plug-in, magnetic relays with dry, Form-C, contact
outputs. Turbine solenoids are normally powered from the 125 V dc battery bus with
suppression for each solenoid with a 3.2 A slow-blow fuse on each side of the feeder
circuit.
Analog inputsmonitor 4 20 mA (250 ), which can be configured for self-powered, differential inputs, or as sensors that use a +24 V dc supply from the Mark
VI. Selected inputs can be configured for 0 1mA inputs (5,000 ) or 5, 10 V dc
inputs. This interfaces to
existing 0 1mA generator MW and MVAR transducers
existing Dynesco-type gas fuel pressure and compressor discharge pressure
transducers with 12 V dc supply and 0 5 V dc inputs
Most Mark II generator drive systems already have these transducers; however,
Mark I systems do not. Compressor discharge pressure biases the temperaturecontrol system to improve turbine operation.
Analog outputscan be configured for 4 20 mA output (500 maximum) or 0
200 mA output (50 maximum).
Thermocouple inputscan be grounded or ungrounded. Software linearization is
provided for type J and K thermocouples used on GE gas turbines plus types E, S, orT thermocouples. Existing control and overtemperature thermocouples are retained
and divided between the Mark VI controller and the backup protection module for
temperature control and overtemperature protection, respectively.
RTD inputs can be grounded or ungrounded. Software linearization is provided for
10 copper, 100/200 platinum, or 120 nickel RTDs. The generator or load
compressor RTDs can be monitored directly by the Mark VI with all turbine anddriven-load temperatures being collected in a common database with other turbine-generator parameters.
8 Mark VI for Gas Turbine Control Retrofits GEI-100538A Application Overview
7/22/2019 GE MARK VI
9/22
Speed inputs.Redundant, passive, magnetic speed sensors provide an input to the
control module(s) for speed control and overspeed protection. Emergency overspeed
protection is provided electronically; mechanically on older turbines. A separate
backup protection module is provided with separate power supplies, processors, and
I/O cards to provide enhanced machine protection. Overspeed detection by either theprimary or emergency electronic trip systems or the mechanical overspeed bolt
automatically de-energizes the hydraulic solenoids.
Flame inputs.A direct interface is provided for ultra-violet flame scanners that
produce a pulsed output. This eliminates any interposing transducers and enables the
diagnostics to monitor the actual light level. An alarm is initiated if the light leveldiminishes below an acceptable level due to carbon or other deposits on the scanner
window.
Integrating servo interface. The Mark VI provides a direct interface to the bipolar
servo actuator and LVDT valve position feedback. Bi-polar integrating servo current
outputs are provided in 10, 20, 40, 80, and 120 mA ranges for fuel valves and InletGuide Vane (IGV) control. Mark VI LVDT excitation is 7.0 Vrms at 3.2 kHz. Pulse
rate inputs are also provided for servo control loops using liquid fuel-flow, pulse-rate
feedback.
Vibration protection.A direct interface is provided for vibration protection sensors,which are required to trip the turbine. This includesseismic (velocity) type sensors
used on heavy-duty gas turbines and accelerometerson aircraft-derivative gasturbines. This eliminates the single-point failure of a separate monitoring system, and
allows Mark VI diagnostics to monitorseismic sensorswhen the turbine is runningor stopped. Aircraft derivative applications primarily use accelerometers,which
produce a velocity signal from external charge amplifiers. The Mark VI contains
speed-tracking filters to isolate the appropriate vibration frequencies of each shaft for
the display, alarm, and trip.
Proximitor
monitoring provides monitoring and protection for GE gas-turbine
applications. Mark VI provides a direct interface to the keyphasor, radial proximitor,
and axial proximitor inputs, which are collected in a common database with turbineparameters. The fundamental (1X), first harmonic (2X), and composite vibration
signals are collected by the Mark VI and displayed with both magnitude and phaseangle on the Human-Machine Interface (HMI). Active isolators provide buffered
outputs to BNC connectors on the Mark VI termination boards for temporary
connection to portable analysis equipment.
The PTs are paralleled to
the backup protectionmodule for redundant
backup synch check
rotection.
Synchronizing interfaceincludes one generator PT and one line PT to match the
generator frequency (turbine speed) to the line frequency and match the generator
voltage to the line voltage through commands to the generator excitation control.The Mark VI monitors actual breaker closure time and self-corrects each time the
breaker closes.
GEI-100538A Mark VI for Gas Turbine Control Retrofits 9
7/22/2019 GE MARK VI
10/22
DiagnosticsMark VI diagnostics include power-up, background, and manually initiated
diagnostic routines capable of identifying both control panel, sensor, and output
device faults. These faults are identified down to the VME board and terminal boardlevel for the panel, and to the circuit level for sensors and actuators.
CommunicationThe Mark VI uses the following communication networks.
I/O Netis an Ethernet-based network between a control module, the three
sections of the backup protection module, and expansion I/O modules (if
required). I/O Net uses Asynchronous Drives Language (ADL) topollthemodules for data instead of using the typical collision detectiontechniques used
in Ethernet LANs.
Unit Data Highwat (UDH) is an Ethernet-based network that provides peer-to-peer communication between the Mark VI and a GE generator excitation
control. The network uses Ethernet Global Data (EGD), a message-based
protocol with support for sharing information with multiple nodes based on theUDP/IP standard. Data can be transmitted unicast or broadcast to peer
controllers on a network with up to 10 network nodes at 25 Hz.
Refer to the section, HMI,
or information on the user
interface.
The Mark VI can communicate to a GE HMI or directly with a plant Distributed
Control System (DCS) network or Plant Data Highway (PDH) through Ethernet
serial Modbus
slave/master, Ethernet TCP/IP Modbus slave, or Ethernet TCP/IP
with GE Energy Standard Messages (GSM).
GSM is only available from a Mark VI HMI; its protocol provides
Administration messages
Spontaneous event-driven messages (with local time tags)
Periodic group data messages at rates to one second
Common request messages
10 Mark VI for Gas Turbine Control Retrofits GEI-100538A Application Overview
7/22/2019 GE MARK VI
11/22
EX2100
Unit Data Highway
Gas Turbine
Control
Mark VI
Generator
Excitation
Plant DCS
HMIOperatorStation
HMIOperatorStation
Ethernet TCP/IP GSMEthernet TCP/IP ModbusRS-232C/RS-485 Modbus
IRIG-B
Time Sync
Ethernet TCP/IPModbus
RS-232C/RS-485Modbus
Plant Data Highway
Ethernet UDP/IP
Typical Network for Mark VI and EX2100 with Direct Connect to DCS Option
GEI-100538A Mark VI for Gas Turbine Control Retrofits 11
7/22/2019 GE MARK VI
12/22
Control FunctionsThe control functions below are typical for a single-shaft generator drive application.
Nozzle control for two-shaft machines and load compressor controls are also
supported by Mark VI.
Startup controlis an open-loop system that increases the fuel stroke reference as theturbine startup sequence progresses to preassigned plateaus.
Acceleration controladjusts the fuel stroke reference according to the rate ofchange of the turbine speed to reduce the thermal shock to the hot gas path parts of
the turbine.
Speed controluses the median speed from three speed sensors for droop and
isochronous speed control with an automatic transfer to isochronous upon loss of the
tie-line breaker. Separate shaft speed-control algorithms are provided for each shaftin multi-shaft machine applications. The Mark VI varies shaft speed to control real
power (megawatt) output in a mechanical (compressor or pump) drive application. In
a generator drive application, the Mark VI maintains a constant generator shaft speedto meet the electrical power demand and also controls the generator field through the
use of VAR/Power Factor (PF) control algorithms to generate excitation raise and
lower commands.
Generator load controlcompares the load setpoint with the MW feedback from a
single-phase transducer and adjusts the speed setpoint to regulate the load. ASpinning Reserveselection allows the machine to start automatically and await an
operator input to synchronize to the grid. Selection ofFast Load StartorPre-
selected Loadraises the output to thePre-selected Loadsetpoint limit. Selection of
base or peak raises this setpoint to the maximum limit.
Exhaust temperature controlalgorithms sort the input from each thermocouple
from the highest to the lowest temperature. They automatically reject badthermocouple data, average the remaining data values, and execute the control
algorithm based upon the average calculated temperature. Redundant transducers
monitor the compressor discharge pressure and bias the temperature control to
correct for ambient conditions and the corresponding variations in mass flow.
Inlet guide vane controlmodulates the position of the compressor stator vanes toprovide optimum compressor and unit operation. During startup, the guide vanes
open as the turbine speed increases. When the unit is online, the guide vanes
modulate to control turbine airflow temperature to optimize combustion system and
combine-cycle performance.
Fuel control is a reference from the governor and feedback of the fuel controlvalves. The Fuel Stroke Reference (FSR) is determined by the turbine parameter
(speed, temperature, and so on) calling for the least fuel. FSR calculation occurs in
the main processor, then is transmitted to the servo valve cards on the backplane of
the control module(s). Liquid fuel control establishes the FSR of the bypass valve.
Fuel flow is proportional to the speed (Fuel Flow = Speed X FSR). Gas fuel control
uses a Gas Control Valve (GCV), where fuel flow is a function of pressure (FuelFlow = Fuel Pressure X FSR). An added Stop/speed Ratio Valve (SRV) opens as a
turbine speed function, so pressure becomes a function of speed and the liquid fuel
control system and the gas fuel control systems have the same characteristic.
12 Mark VI for Gas Turbine Control Retrofits GEI-100538A Application Overview
7/22/2019 GE MARK VI
13/22
Emissions controlis available with diluent (water or steam) injection through a
multi-nozzle quiet combustor to quench flame temperature and reduce thermal NOx
formation. Lean-burning, pre-mixed flame combustors are available for lower NOx
levels without the need for water or steam injection called Dry Low NOx (DLN).
Load compressor controladjusts the turbine power output (speed) and providesvalve sequencing and surge control to optimize compressor operation.
Generator excitation controlfor voltage matching during synchronization andVAR/PF control after breaker closure can be integrated into the turbine control.
When a reference or setpoint is entered, feedback from a single-phase VAR
transducer regulates the setpoint in the Mark VI. Mark VI calculates PF from MWand MVAR inputs, or an external PF transducer can be connected to the Mark VI.
Setpoints are transmitted from the turbine control to the generator excitation control.
Gas Fuel
Servo
90SR
LVDT
96SR
TSVO
Stop/Speed
Ratio Valve
Termination
BoardVSVO Card
A/D
VCMICard
Main Processor
FPRG
TNH (Speed)
Constants
LogicSoftware
RegulatorD/A
96FG
Gas Fuel
PressureTBAIVAIC Card
D/A
+
-
Servo
65GC
LVDT96GC
TSVO
Gas Control
ValveVSVO Card
A/D
FSROUT
FSR2
LogicSoftware
RegulatorD/A
Combustion
Chamber
Servo65FP
TSVO
Stop/Speed
Ratio Valve
VSVO Card
A/D
SoftwareRegulator
Flow
Divider
Liquid Fuel
Pulse
77FD
D/A
FSROUT
Logic
TNH (Speed)
FSR1
FuelSplitterFSR
Logic
Control Module
Typical Dual Fuel Control System
GEI-100538A Mark VI for Gas Turbine Control Retrofits 13
7/22/2019 GE MARK VI
14/22
Sequencing
Turbine control can include automated startup and shutdown sequences customized
to meet operator requirements, as well as control and monitoring of all gas turbine
auxiliary and support systems. Operators can have the turbine automatically
sequence to intermediate hold points by selecting Crank,Fire, orAutowithout
enabling automatic synchronization. All ramp rates and time delays are pre-programmed for optimum performance. Timers and counters record long-term
turbine operating information that can include:
Total fired time
Separate DLN operating mode timers
Manually initiated starts
Total starts
Fast load starts
Fired starts
Emergency trips
This automation enables gas-turbine operation from a remote site with the assurancethat the turbine fully protected. Diagnostics capture a record of any abnormal
conditions.
Protection
Turbine control monitors all control and protection parameters and initiates an alarm
if an abnormal condition is detected. If the condition exceeds a predefined trip level,
the turbine control drives the gas/liquid control valves to a zero-flow position and de-
energizes the fuel shut-off solenoids. All control, protection, and monitoringalgorithms are contained in the control modules for efficiency in sharing common
data. The protection module includes standard backup turbine protection that meets
OEM tripping reliability requirements for turbine overspeed, overtemperature, andsync-check protection.
In a typical installation, a trip solenoid is powered from the 125 V dc floating batterybus with:
Contacts from the control module in series with the negative side of the bus
Contacts from the backup protection module in series with the positive side ofthe bus
Additionally, diagnostic and
trip data is communicated
between the control moduleand the backup protection
modules on the triple
redundant I/O Nets forcross-tripping.
Diagnostics monitor:
Contact from each relay
Voltage directly across the trip solenoid
Overspeed protection includes a primary overspeed monitoring system in the threecontrol modules and an emergency overspeed monitoring system in the backup
protection module that replaces the mechanical overspeed bolt used on older
turbines. The control module and each section of the backup protection module
monitors magnetic speed sensors from 2.0 rpm on a 60-tooth wheel. Diagnostics
monitor the speed and acceleration, then exchange the data between the controlmodule and the protection module on startup to verify that all sensors are active.
14 Mark VI for Gas Turbine Control Retrofits GEI-100538A Application Overview
7/22/2019 GE MARK VI
15/22
Typical gas turbine trip protection system
Trips Types
Pre-ignition Auxiliary check (Servos)
Seal oil dc motor undervoltage
dc lube oil pump undervoltageStartup fuel flow excessive
Failure to ignite
Post-ignition Loss of flame
High exhaust temperature
Exhaust thermocouples open
Compressor bleed valve position trouble
Load tunnel temperature high
Gas fuel hydraulic pressure low
Turbine lube oil header temperature high
Turbine electronic overspeed
Protective Status Starting device trouble
Inlet guide vane trouble
Manual trip
Control speed signal lost
Exhaust pressure high
Protective speed signal trouble
Control speed signal trouble
Breaker failure trip lockout
Vibration tripLoss of protection HP speed inputs
Customer trip
Control system fault
Low lube oil pressure
Fire indication
Generator lockout trip
GEI-100538A Mark VI for Gas Turbine Control Retrofits 15
7/22/2019 GE MARK VI
16/22
HMI
The HMI or user interface is provided through a GE CIMPLICITY
graphics
window with unit-specific screens, a Microsoft
Windows
operating system, and a
Control Systems Toolbox with editors for application software. It can be applied as:
Primary user interface for single or multiple units
Gateway for communication links to other controllers
Permanent or temporary maintenance station
Engineering workstation
All control and protection is resident in the Mark VI controller, which allows the
HMI to be a non-essential component. With the turbine running, it can be
reinitialized or replaced with no impact on the controller. The HMI communicateswith the processor in the controller through the UDH.
Gas turbine control screens show a diagram of the turbine with the primary controlparameters. The diagram is repeated on most of the screens to provide a visual image
of the turbines performance while changing screens.
Typical Gas Turbine Screens
ControlScreens
MonitorScreens Auxiliaries Tests
Startup Bearingtemperature
Flame Overspeedtest
Motors Exhausttemperature
Water wash
FSR control Generator RTDs Start checkGenerator/exciter Wheelspace
temperatureTrip diagram
Synchronizing Seismic vibration Timers
Buttons on the right side of
all screens produce sub-menus of category-specific
screens.
The main screen is the Startupscreen. Since the gas turbine control provides fully
automatic startup including all interfaces to auxiliary systems, all basic commandsand all primary control parameters and status conditions start from this screen.
For example, the Startcommand can be sent to the Mark VI whenReady to Startdisplays in the startup status field. A pop-up window displays above the Start-up
button for verification. Upon verification, the application software checks the startup
permissives and starts a sequence that displays Startingand Sequence in Progressmessages.
If startup permissives were not satisfied, the messageNot Ready to Startdisplays,
with a message in the alarm field that identifies the reason. Additionally, when the
Auxbutton is clicked and the Start Checkscreen is selected, it displays graphicalinformation for the Start Check/Ready to Startpermissives.
A message reminds you to
investigate the nature of thelatched trip prior to clicking
Master Reset.
Trip conditions that display in the alarm field and in the Trip Diagram are accessed
by clicking the Auxbutton and selecting the Trip Diagramscreen. A trip duringstartup causes the messageNot Ready to Start.
16 Mark VI for Gas Turbine Control Retrofits GEI-100538A Application Overview
7/22/2019 GE MARK VI
17/22
v o o
Mark VI also allows you to change a numeric setpoint, such asMegawatts (MW)fora generator drive or Speed Reference (TNPREF)for a mechanical drive, by entering
a setpoint value rather than issuing continuous discrete raise/lower commands. The
Mark VI application compares the requested setpoint with acceptable limits and the
present output to determine a suitable ramp rate to the new target.
The Mark VI supports trending displays for comparing operating parameters. A
startup trend can be set with pre-assigned parameters, such as meanExhaust GasTemperature (EGT),speed, maximum vibration, Compressor Discharge Pressure
(CPD), andFuel Stroke Reference (FSR). More detailed information and trending are
provided on supporting screens, along with the capability to create customizedtrends.
Typical Turbine Instrumentation
GEI-100538A Mark VI for Gas Turbine Control Retrofits 17
7/22/2019 GE MARK VI
18/22
Typical Turbine InstrumentationAnalog and digital devices found on a typical dual fuel gas turbine without emission
suppression are provided in the following tables.
Analog Turbine Devices
Device Parameter Device Type
28FD Flame detector Flame scanner
39V-x Vibration sensor Velocity pickup
65FP Liquid fuel pump servo Torque motor
65GC Gas control valve servo Torque motor
65NZ Nozzle control servo (2-shaft only) Torque motor
77FD Liquid fuel flow Magnetic pickup
77NH High Pressure shaft speed Magnetic pickup
77NL Low Pressure shaft speed (2-shaft) Magnetic pickup
90SR Gas ratio valve servo Torque motor90TV Inlet guide vane servo Torque motor
96FG-2 Gas fuel control pressure Transducer
96GC Gas control valve LVDT
96NC Nozzle control (2-shaft only) LVDT
96SR Gas ratio valve LVDT
96TV Inlet guide vane LVDT
CTDA Compressor discharge temperature Thermocouple
CTIF Compressor inlet temperature Thermocouple
TTWS-x GT wheelspace temperature Thermocouple
TTXD-x GT exhaust temperature Thermocouple
18 Mark VI for Gas Turbine Control Retrofits GEI-100538A Application Overview
7/22/2019 GE MARK VI
19/22
Digital Turbine Devices
Device Parameter Device Type
12HA Mechanical overspeed bolt sensor Limit switch
20FG Gas fuel trip oil Solenoid valve
20FL Liquid fuel trip oil Solenoid valve
26FD Liquid fuel temperature Temperature switch
26QA/T Lube oil temperature high alarm / trip Temperature switch
26QL/M Lube oil temperature low / moderate Temperature switch
26QN Lube oil temperature normal Temperature switch
33CS Starting clutch Limit switch
33FL Liquid fuel stop valve position Limit switch
33HR Ratchet position Limit switch
45F-x Fire detector Temperature switch
63AD Atomizing air differential pressure Pressure switch
63FD Liquid fuel pressure Pressure switch
63FG Gas fuel pressure Pressure switch
63HG Gas fuel trip oil pressure Pressure switch
63HL Liquid fuel trip oil pressure Pressure switch
63LF1 Liquid fuel filter pressure Pressure switch
63LF2 Liquid fuel forwarding filter pressure Pressure switch
63QA/T Lube oil header / bearing pressure Pressure switch
63QL Lube oil pressure Pressure switch
63TF Inlet filter pressure Pressure switch
71QH Lube tank high level Pressure switch
71QL Lube tank low level Level switch
71WL Water tank low level Level switch
GEI-100538A Mark VI for Gas Turbine Control Retrofits 19
7/22/2019 GE MARK VI
20/22
Packaging
Mark VI packages can be customized to meet any site requirement. Package options
that fit into the Mark I, Mark II and Mark IV footprints are shown below.
Component Description
Card Backplane VME type (VERSA module Eurocard)
Cabinet NEMA 1 convection cooled, similar to IP-20
Cable Entrance Top and/or bottom
Material Sheet steel
Terminal Blocks 24-point, barrier type terminal blocks that can be unplugged formaintenance. Each screw can terminate two #12 AWG (3.0mm
2), 300-volt insulated wires.
Width Depth Height Weight
36" (900 mm) 36" (900 mm) 91.5" (2,324 mm) 1300 lbs(590 Kg)
Dimensions- Cabinet Option #1
- Cabinet Option #2
54" (1350 mm) 36" (900 mm) 91.5" (2,324 mm) 1600 lbs(725 Kg)
GEI-100538A Mark VI for Gas Turbine Control Retrofits 19
7/22/2019 GE MARK VI
21/22
Typical Power Requirements
The control cabinet is powered from a 125 V dc battery bus that is normally short-
circuit protected in the motor control center. Both sides of the floating 125 V dc busare continuously monitored for grounding. A floating bus eliminates the need for the
dc ground relay and dc under-voltage relay present in older controllers. The 125 V dc
bus is fuse-isolated in the Mark VI power distribution module and sent to:
VME rack power supply for each control module
Termination boards for the field contact inputs and the turbine solenoids
A separateuninterruptible power
supply (UPS) is required
to power the HMI and
network equipment.
Additional 3.2 A fuse protection is provided on the termination board for each
solenoid. A 120 V ac feed is provided for ignition transformers. Control cabinetpower specifications are shown below.
Steady-state Voltage Frequency Load Comments
125 V dc (100 to 145 V dc) 10 A dc Ripple
7/22/2019 GE MARK VI
22/22
g GE Energy1502 Roanoke Blvd.Salem, VA 24153-6492 USA GEI-100538ARevised 051109Issued 020525