Upload
taylorbatey
View
231
Download
0
Embed Size (px)
Citation preview
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
1/82
818365A1.CDR
LISTED
52TL
IND.CONT. EQ.
E83849
GE Multilin
215 Anderson Avenue, Markham, Ontario
Canada L6E 1B3
Tel: (905) 294-6222, 1-800-547-8629 (North America)
Fax: (905) 201-2098
Internet: http://www.GEmultilin.com
REG
ISTERED
RRTD Remote RTD Module
Instruction Manual
RRTD Revision: 59CMB151.000
Manual P/N: 1601-0104-B7
Copyright 2008 GE Multilin
Manufactured under an
ISO9001 Registered system.
gGE Industrial Syste
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
2/82
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
3/82
GE Multilin RRTD Remote RTD Module i
TABLE OF CONTENTS
1. INTRODUCTION 1.1 OVERVIEW1.1.1 DESCRIPTION................................................................................................... 1-1
1.1.2 ORDERING........................................................................................................ 1-1
1.1.3 REVISION HISTORY ......................................................................................... 1-2
1.1.4 FUNCTIONAL SUMMARY................................................................................. 1-2
1.1.5 LABEL DEFINITION...........................................................................................1-3
1.2 GUIDEFORM SPECIFICATIONS1.2.1 DESCRIPTION................................................................................................... 1-41.2.2 PROTECTION FEATURES ............................................................................... 1-4
1.2.3 METERED QUANTITIES................................................................................... 1-4
1.2.4 ADDITIONAL FEATURES ................................................................................. 1-4
1.3 TECHNICAL SPECIFICATIONS1.3.1 INPUTS.............................................................................................................. 1-5
1.3.2 OUTPUTS.......................................................................................................... 1-5
1.3.3 COMMUNICATIONS.......................................................................................... 1-5
1.3.4 PROTECTION ELEMENTS ............................................................................... 1-6
1.3.5 ENVIRONMENTAL ............................................................................................ 1-6
1.3.6 APPROVALS / CERTIFICATION....................................................................... 1-6
1.3.7 TYPE TESTING ................................................................................................. 1-6
1.3.8 PRODUCTION TESTING .................................................................................. 1-6
2. INSTALLATION 2.1 MECHANICAL INSTALLATION2.1.1 DESCRIPTION................................................................................................... 2-1
2.2 TERMINAL IDENTIFICATION2.2.1 TERMINAL LIST ................................................................................................ 2-2
2.3 ELECTRICAL INSTALLATION2.3.1 TYPICAL WIRING..............................................................................................2-3
2.3.2 CONTROL POWER........................................................................................... 2-4
2.3.3 RTD INPUTS...................................................................................................... 2-4
2.3.4 DIGITAL INPUTS............................................................................................... 2-5
2.3.5 ANALOG OUTPUTS .......................................................................................... 2-5
2.3.6 DISPLAY............................................................................................................ 2-5
2.3.7 OUTPUT RELAYS ............................................................................................. 2-6
2.3.8 RS485 COMMUNICATIONS.............................................................................. 2-6
3. RTDPC INTERFACE 3.1 INTRODUCTION3.1.1 REQUIREMENTS .............................................................................................. 3-1
3.1.2 INSTALLING RTDPC......................................................................................... 3-1
3.1.3 UPGRADING RTDPC........................................................................................ 3-1
3.2 USING RTDPC3.2.1 CONFIGURATION ............................................................................................. 3-2
3.2.2 UPGRADING FIRMWARE................................................................................. 3-2
3.2.3 CREATING A NEW SETPOINT FILE ................................................................3-3
3.2.4 EDITING A SETPOINT FILE..............................................................................3-4
3.2.5 DOWNLOADING A SETPOINT FILE................................................................. 3-4
3.2.6 UPGRADING SETPOINT FILE TO NEW REVISION ........................................3-5
3.2.7 PRINTING.......................................................................................................... 3-6
3.2.8 TROUBLESHOOTING....................................................................................... 3-6
4. SETPOINTS 4.1 S1 SETUP4.1.1 SETPOINT ACCESS ......................................................................................... 4-1
4.1.2 PREFERENCES................................................................................................ 4-1
4.1.3 RRTD COMMUNICATIONS............................................................................... 4-2
4.1.4 REAL TIME CLOCK...........................................................................................4-2
4.1.5 CLEAR/PRESET DATA ..................................................................................... 4-3
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
4/82
ii RRTD Remote RTD Module GE Multilin
TABLE OF CONTENTS
4.1.6 OPTIONS............................................................................................................4-3
4.2 S2 SYSTEM SETUP4.2.1 DESCRIPTION ...................................................................................................4-4
4.2.2 MONITORING SETUP .......................................................................................4-4
4.2.3 OUTPUT RELAY SETUP ...................................................................................4-4
4.2.4 CONTROL FUNCTIONS ....................................................................................4-5
4.3 S3 RTD TEMPERATURE
4.3.1 DESCRIPTION ...................................................................................................4-64.3.2 LOCAL RTD PROTECTION...............................................................................4-6
4.3.3 OPEN RTD ALARM............................................................................................4-7
4.3.4 SHORT/LOW TEMP RTD ALARM.....................................................................4-8
4.4 S4 DIGITAL INPUTS4.4.1 DIGITAL INPUT FUNCTIONS............................................................................4-9
4.5 S5 ANALOG OUTPUTS4.5.1 ANALOG OUTPUT PARAMETER SELECTION ..............................................4-10
4.6 S6 TESTING4.6.1 FORCE OUTPUT RELAYS ..............................................................................4-11
4.6.2 FORCE ANALOG OUTPUTS ...........................................................................4-11
5. ACTUAL VALUES 5.1 A1 STATUS5.1.1 LAST TRIP DATA...............................................................................................5-1
5.1.2 ALARM STATUS ................................................................................................5-1
5.1.3 DIGITAL INPUT STATUS...................................................................................5-2
5.1.4 OUTPUT RELAY STATUS .................................................................................5-2
5.1.5 REAL TIME CLOCK ...........................................................................................5-2
5.2 A2 TEMPERATURE DATA5.2.1 LOCAL RTD........................................................................................................5-3
5.2.2 LOCAL RTD MAXIMUMS...................................................................................5-3
5.3 A3 STATISTICAL DATA5.3.1 TRIP COUNTERS ..............................................................................................5-4
5.3.2 STATISTICS.......................................................................................................5-4
5.4 A4 EVENT RECORDER5.4.1 EVENT RECORDER ..........................................................................................5-5
5.5 RELAY INFORMATION AND COMMMANDS5.5.1 A5 RELAY INFORMATION ................................................................................5-6
5.5.2 COMMANDS ......................................................................................................5-6
6. APPLICATIONS 6.1 RTD CIRCUITRY6.1.1 RTD CIRCUIT OPERATION...............................................................................6-1
6.1.2 TWO WIRE RTD LEAD COMPENSATION........................................................6-1
6.1.3 REDUCED RTD LEAD NUMBER APPLICATION..............................................6-2
6.1.4 MONITORING OF UP TO 60 RTDS...................................................................6-3
6.2 USING THE RRTD WITH THE 469 RELAY6.2.1 INTRODUCTION ................................................................................................6-5
6.2.2 CONTROL VIA THE 469 ....................................................................................6-5
6.2.3 MONITORING VIA THE 469 ..............................................................................6-56.2.4 MONITORING AND CONTROL VIA THE 469 ...................................................6-5
7. TESTING 7.1 TEST SETUP7.1.1 INTRODUCTION ................................................................................................7-1
7.1.2 TEST SETUP......................................................................................................7-1
7.2 HARDWARE FUNCTIONAL TESTING7.2.1 RTD ACCURACY TEST.....................................................................................7-2
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
5/82
GE Multilin RRTD Remote RTD Module iii
TABLE OF CONTENTS
7.2.2 DIGITAL INPUTS...............................................................................................7-3
7.2.3 ANALOG OUTPUTS .......................................................................................... 7-3
7.2.4 OUTPUT RELAYS ............................................................................................. 7-4
8. COMMUNICATIONS 8.1 OVERVIEW8.1.1 ELECTRICAL INTERFACE................................................................................9-1
8.1.2 MODBUS COMMUNICATIONS......................................................................... 9-1
8.1.3 DATA FRAME FORMAT AND DATA RATE...................................................... 9-1
8.1.4 DATA PACKET FORMAT.................................................................................. 9-1
8.1.5 ERROR CHECKING .......................................................................................... 9-2
8.1.6 CRC-16 ALGORITHM........................................................................................ 9-2
8.1.7 TIMING............................................................................................................... 9-2
8.2 SUPPORTED MODBUS FUNCTIONS8.2.1 DESCRIPTION................................................................................................... 9-3
8.2.2 FUNCTION CODES 03 & 04: READ SETPOINTS & ACTUAL VALUES .......... 9-3
8.2.3 FUNCTION CODE 05: EXECUTE OPERATION ............................................... 9-4
8.2.4 FUNCTION CODE 06 - STORE SINGLE SETPOINT ....................................... 9-4
8.2.5 FUNCTION CODE 07: READ DEVICE STATUS............................................... 9-5
8.2.6 FUNCTION CODE 08: LOOPBACK TEST ........................................................ 9-5
8.2.7 FUNCTION CODE 16: STORE MULTIPLE SETPOINTS.................................. 9-6
8.2.8 FUNCTION CODE 16: PERFORMING COMMANDS ....................................... 9-7
8.2.9 ERROR RESPONSES....................................................................................... 9-7
8.3 MEMORY MAP8.3.1 DESCRIPTION................................................................................................... 9-8
8.3.2 USER DEFINABLE MEMORY MAP AREA ....................................................... 9-8
8.3.3 MEMORY MAP .................................................................................................. 9-9
8.3.4 MEMORY MAP DATA FORMATS ................................................................... 9-20
A. WARRANTY A.1 WARRANTY INFORMATION
INDEX
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
6/82
iv RRTD Remote RTD Module GE Multilin
TABLE OF CONTENTS
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
7/82
GE Multilin RRTD Remote RTD Module 1-1
1 INTRODUCTION 1.1 OVERVIEW
1 INTRODUCTION 1.1 OVERVIEW 1.1.1 DESCRIPTION
The Remote RTD Module (RRTD) provides additional RTD temperature metering capabilities for GE Multilin relays such as
the 369 Motor Management Relay.
The RRTD module is a black box which monitors up to 12 RTDs and can be polled for information. All RRTD setpoint pro-
gramming is accomplished via the 369 over the serial communication link or by other devices using the Modbus RTU proto-
col. Communications connections are over a shielded twisted pair RS485 connection or via the fiber optic port.The RRTD module has been designed to be mounted close the motor to facilitate reduced length of RTD wiring. A 369
Motor Management Relay can then monitor the RTDs from a remote location and use this temperature information for pro-
tection/metering purposes.
The RRTD has three RS485 ports. The Modbus RTU protocol is standard to all ports. The Fiber Optic port is an optional
feature of the RRTD.
Optional output relays, digital inputs, and analog outputs are also provided (see pages 25 to 26 for additional details).
These features allow for addition control and provide stand alone overtemperature protection. The RTDPC program is used
to program setpoints and monitor actual values if the RRTD is operated as stand alone. A Quick Panel display may be used
to monitor temperatures.
RRTD options are available when ordering the relay or as upgrades to the relay in the field. Field upgrades are via an
option enabling passcode available from GE Multilin, which is unique to each relay and option.
1.1.2 ORDERING
Select the basic model and the desired features from the selection guide below:
Notes: The control power (HI or LO) must be specified with all orders. If a feature is not required, a 0 must be
placed in the order code. All order codes have 9 or 10 digits.
Examples: RRTD-HI-IO-0 RRTD with HI voltage control power and IO option
RRTD-LO-0-F RRTD with LO voltage control power and fiber optic port
Location: GE Multilin
215 Anderson Avenue
Markham, Ontario
Canada L6E 1B3
Tel: (905) 294-6222, 1-800-547-8629 (North America)
Fax: (905) 201-2098
Web Page: http://www.GEindustrial.com/multilin; e-mail: [email protected]
RRTD RRTD | | | Base unit
HI | | 50 to 300 V DC / 40 to 265 V AC control power
LO | | 20 to 60 V DC / 20 to 48 VAC control power
IO | Optional Input and Output
0 | No optional Input and Output
F Optional Fiber Optic port
0 No optional Fiber Optic port
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
8/82
1-2 RRTD Remote RTD Module GE Multilin
1.1 OVERVIEW 1 INTRODUCTION
1
1.1.3 REVISION HISTORY
1.1.4 FUNCTIONAL SUMMARY
Figure 11: FUNCTIONAL VIEW
Table 11: FIRMWARE REVISION HISTORY
REVISION DESCRIPTION OF CHANGES RELEASE DATE
59CMB110.000 Production Release October 15, 1999
59CMB120.000 Improvements to Channel 3 communications January 3, 2000
59CMB140.000 Improved method of downloading setpoint files February 16, 2000
59CMB151.000 Changes to communications October 18, 2002
Table 12: SOFTWARE REVISION HISTORY
REVISION DESCRIPTION OF CHANGES RELEASE DATE
1.10 Production Release October 15, 1999
1.20 PC software for new firmware January 3, 2000
1.40 Implemented refresh RRTD setpoints command February 16, 2000
1.51 Changes to Channel communications October 18, 2002
FIBER OPTIC DATA LINK (F)For harsh environments
DIGITAL INPUTS
(IO)
Communications(3)-RS485 Com Ports
ANALOG OUTPUT(IO)
813701A5.CDR
CONTROL POWERHI: 50-300VDC/40-265VACLO: 20-60VDC/20-48VAC
Customer Accessiblefuse
12 RTD INPUTS
field selectable type
4 OUTPUT RELAYS (IO)Programmable alarm andtrip conditions activatedby programmable setpoints,digital inputs and remotecommunication control.
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
9/82
GE Multilin RRTD Remote RTD Module 1-3
1 INTRODUCTION 1.1 OVERVIEW
1.1.5 LABEL DEFINITION
1. The RRTD order code at the time of leaving the factory.
2. The serial number of the RRTD.
3. The firmware that was installed in the RRTD when it left the factory. Note that this may no longer be the current firm-
ware as firmware may be upgraded in the field. The current firmware revision may be checked via the RTDPC pro-
gram.
4. Specifications for the output relay contacts.
5. Certifications the RRTD conforms with or has been approved to.
6. Factory installed options. These are based on the order code. Note that the RRTD may have had options upgraded in
the field. The Actual Values section of the RTDPC may be checked to verify this.
7. Control power ratings for the RRTD as ordered. Based on the HI/LO rating from the order code.
8. Pollution degree.
9. Overvoltage Category.
10. IP code.
11. Modification number for any factory ordered mods. Note that the RRTD may have had modifications added in the field.
The Actual Values section of the RTD PC may be checked to verify this.
12. Insulative voltage rating.
CEg
INPUT POWER:
MODEL: RRTD-HI-IO-F-0
MAXIMUM CONTACTRATING2 50 VA C 8 A R ES IS TI VE1/4 HP 125 VAC 1/2 HP 250 VAC
SERIAL No: M59B01000745
FIRMWARE: 59CMB140.000
POLLUTION DEGREE: 2 IP CODE: 5OX
50-300 VDC40-265 VAC485mA MAX.50/60Hz or DC
MOD:
INPUT & OUTPUT
FIBER OPTIC PORT
OPTIONS
INSULATIVE VOLTAGE: 2
NONEOVERVOLTAGE CATEGORY: II
1
7
2
8
3
9
4
10 11
5 6
12
UL
813350A3.CDR
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
10/82
1-4 RRTD Remote RTD Module GE Multilin
1.2 GUIDEFORM SPECIFICATIONS 1 INTRODUCTION
1
1.2 GUIDEFORM SPECIFICATIONS 1.2.1 DESCRIPTION
The Remote RTD module shall be capable of monitoring up to 12 three wire shielded RTDs. Each RTD input is to be indi-
vidually field programmable to type (that is, 100P, 100N, 120N, or 10C). The Remote RTD shall be capable of being daisy-
chained with 4 other RRTD modules to provide monitoring and protection of up to 60 RTDs.
The communication interface includes 3 independent RS485 ports and a fiber optic port. Modbus RTU is to be the standard
protocol.The module shall be accompanied by supporting PC software, thus allowing easy programming and monitoring. The mod-
ule shall be capable of automatically communicating the RTD information to the 369 Motor Management Relay.
1.2.2 PROTECTION FEATURES
1.2.3 METERED QUANTITIES
1.2.4 ADDITIONAL FEATURES
ANSI/IEEEDEVICE
PROTECTION FEATURES TRIP ALARM
38 Bearing RTD 49 Stator RTD
Ambient RTD Short/Low Temperature RTD Broken/Open RTD Loss of RRTD Communications Self-Test/Service
METERED QUANTITY UNITS OPTION
Input Switch Status Open / Closed IO
Relay Output Status (De) Energized IO
RTD Temperature C or F
FEATURE OPTION
Modbus RTU Communications Protocol
User Definable Baud Rate (1200 to 19200)
Flash Memory for easy firmware updates
Rear RS485 communication port
Rear fiber optic port F
RTD type is user definable
4 User Definable Analog Outputs (0 to 1 mA, 0 to 20 mA, 4 to 20 mA) IO
Windows based PC software for setup and monitoring
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
11/82
GE Multilin RRTD Remote RTD Module 1-5
1 INTRODUCTION 1.3 TECHNICAL SPECIFICATIONS
1.3 TECHNICAL SPECIFICATIONSSpecifications are subject to change without notice.
1.3.1 INPUTS
CONTROL POWERLO range: DC: 20 to 60 V DC
AC: 20 to 48 V AC at 50/60 Hz
HI range: DC: 50 to 300 V DCAC: 40 to 265 V AC at 50/60 Hz
Power: nominal: 20 VA; maximum: 65 VA
Holdup: non-failsafe trip: 200 ms; failsafe trip: 100 ms
FUSET 3.15 A H 250 V (5 20 mm); Timelag high breaking capacity
DIGITAL / SWITCH INPUTS (IO option)Inputs: 6 optically isolated
Input type: Dry Contact (< 800 )
Function: Programmable
RTD INPUTSWire Type: 3 wire
Sensor Type: 100 platinum (DIN 43760), 100 nickel,
120 nickel, 10 copperRTD sensing current: 3 mA
Range: 40 to 200C or 40 to 392F
Accuracy: 2C or4F
Lead Resistance: 25 max. for Pt and Ni type;3 max. for Cu type
Isolation: 36 Vpk
1.3.2 OUTPUTS
ANALOG OUTPUTS (IO option)
Accuracy: 1% of full scale
Isolation: 50 V isolated active source
OUTPUT RELAYS (IO option)
1.3.3 COMMUNICATIONS
BACK PORTS (3)Type: RS485
Baud Rate: 1200 to 19200 baud
Protocol: Modbus RTU
Isolation: 36 V (together)
FIBER OPTIC PORT (Option F)Optional Use: RTD remote module hookup
Baud Rate: 1200 to 19200
Protocol: Modbus RTU
Fiber Sizes: 50/125, 62.5/125, 100/140, and 200 m
Emitter Fiber Type: 820 nm LED, multimode
Link Power Budget:
Transmit Power: 20 dBm
Received Sensitivity: 30 dBm
Power Budget: 10 dB
Maximum Optical Input Power: 7.6 dBm
Typical Link Distance: 1.65 kmTypical link distance is based upon the following assump-
tions for system loss. As actual losses vary from one
installation to another, the distance covered by your sys-
tem will vary.
Connector Loss: 2 dB
Fiber Loss: 3 dB/km
Splice Loss: One splice every 2 km at 0.05 dB loss/splice
System Margin: 3 dB additional loss added to calculations to
compensate for all other losses
PROGRAMMABLE
OUTPUT 0 to 1 mA 0 to 20 mA 4 to 20 mA
MAX LOAD 2400 600 600
MAX OUTPUT 1.01 mA 20.2 mA 20.2 mA
RESISTIVE LOAD(pf = 1)
INDUCTIVE LOAD(pf = 0.4)(L/R - 7ms)
RATED LOAD 8 A at 250 V AC8 A at 30 V DC
3.5 A at 250 V AC3.5 A at 30 V DC
CARRY CURRENT 8A
MAX SWITCHINGCAPACITY
2000 VA240 W
875 VA170 W
MAX SWITCHING V 380 V AC 125 V DC
MAX SWITCHING I 8 A 3.5 A
OPERATE TIME
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
12/82
1-6 RRTD Remote RTD Module GE Multilin
1.3 TECHNICAL SPECIFICATIONS 1 INTRODUCTION
1
1.3.4 PROTECTION ELEMENTS
38/49 RTD and RRTD PROTECTIONPickup Level: 1 to 200C or 34 to 392F
Pickup Accuracy: 2C or4F
Dropout Level: 96 to 98% of pickup above 80C
Time Delay: 1000
Dropout Level: 96 to 98% of pickup
Time Delay:
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
13/82
GE Multilin RRTD Remote RTD Module 1-7
1 INTRODUCTION 1.3 TECHNICAL SPECIFICATIONS
CALIBRATION AND FUNCTIONALITY100% hardware functionality tested
100% calibration of all metered quantities
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
14/82
1-8 RRTD Remote RTD Module GE Multilin
1.3 TECHNICAL SPECIFICATIONS 1 INTRODUCTION
1
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
15/82
GE Multilin RRTD Remote RTD Module 2-1
2 INSTALLATION 2.1 MECHANICAL INSTALLATION
2 INSTALLATION 2.1 MECHANICAL INSTALLATION 2.1.1 DESCRIPTION
The RRTD is contained in a compact plastic housing with the keypad, display, communication port and all indicators/targets
on the front panel. The physical dimensions and mounting (drill diagram) are shown below. Mounting hardware consisting
of bolts and washers are provided with the module.
Although it is internally shielded to minimize noise pickup and interference, the RRTD should be mounted away from high
current conductors or sources of strong magnetic fields.
Figure 21: PHYSICAL DIMENSIONS
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
16/82
2-2 RRTD Remote RTD Module GE Multilin
2.2 TERMINAL IDENTIFICATION 2 INSTALLATION
2
2.2 TERMINAL IDENTIFICATION 2.2.1 TERMINAL LIST
Table 21: TERMINAL LIST
TERMINAL WIRING CONNECTION TERMINAL WIRING CONNECTION
1 RTD1 + 47 RTD12 COMPENSATION
2 RTD1 48 RTD12 SHIELD
3 RTD1 COMPENSATION 51 DIGITAL INPUT 6
4 RTD1 SHIELD 52 DIGITAL INPUT 6 COMMON
5 RTD2 + 53 DIGITAL INPUT 5
6 RTD2 54 DIGITAL INPUT 5 COMMON
7 RTD2 COMPENSATION 55 DIGITAL INPUT 4
8 RTD2 SHIELD 56 DIGITAL INPUT 4 COMMON
9 RTD3 + 57 DIGITAL INPUT 3
10 RTD3 58 DIGITAL INPUT 3 COMMON
11 RTD3 COMPENSATION 59 DIGITAL INPUT 2
12 RTD3 SHIELD 60 DIGITAL INPUT 2 COMMON
13 RTD4 + 61 DIGITAL INPUT 1
14 RTD4 62 DIGITAL INPUT 1 COMMON
15 RTD4 COMPENSATION 71 COMM1 RS485 +
16 RTD4 SHIELD 72 COMM1 RS485
17 RTD5 + 73 COMM1 SHIELD
18 RTD5 74 COMM2 RS485 +
19 RTD5 COMPENSATION 75 COMM2 RS485
20 RTD5 SHIELD 76 COMM2 SHIELD
21 RTD6 + 77 COMM3 RS485 +
22 RTD6 78 COMM3 RS485
23 RTD6 COMPENSATION 79 COMM3 SHIELD
24 RTD6 SHIELD 80 ANALOG OUT 1
25 RTD7 + 81 ANALOG OUT 2
26 RTD7 82 ANALOG OUT 3
27 RTD7 COMPENSATION 83 ANALOG OUT 428 RTD7 SHIELD 84 ANALOG COM
29 RTD8 + 85 ANALOG SHIELD
30 RTD8 111 TRIP NC
31 RTD8 COMPENSATION 112 TRIP COMMON
32 RTD8 SHIELD 113 TRIP NO
33 RTD9 + 114 ALARM NC
34 RTD9 115 ALARM COMMON
35 RTD9 COMPENSATION 116 ALARM NO
36 RTD9 SHIELD 117 AUX1 NC
37 RTD10 + 118 AUX1 COMMON
38 RTD10 119 AUX1 NO
39 RTD10 COMPENSATION 120 AUX2 NC40 RTD10 SHIELD 121 AUX2 COMMON
41 RTD11 + 122 AUX2 NO
42 RTD11 123 POWER FILTER GROUND
43 RTD11 COMPENSATION 124 POWER LINE
44 RTD11 SHIELD 125 POWER NEUTRAL
45 RTD12 + 126 POWER SAFETY
46 RTD12
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
17/82
GE Multilin RRTD Remote RTD Module 2-3
2 INSTALLATION 2.3 ELECTRICAL INSTALLATION
2.3 ELECTRICAL INSTALLATION 2.3.1 TYPICAL WIRING
Since the RRTD can cover a broad range of applications, wiring will be dependent upon the users protection and monitor-
ing scheme. This section covers most of the typical RRTD interconnections.
The terminals have been logically grouped together for explanation purposes. A typical wiring diagram for the RRTD is
shown below. For further information on specific wiring applications, please refer to Chapter 7: APPLICATIONS or contact
GE Multilin for further information.Hazard may result if the product is not used for intended purposes. This equipment can only be serviced by trained
personnel.
Figure 22: TYPICAL WIRING
WARNING
369
Motor Management Relay
g
g
813703A5.CDR
FIBER
RxTx
STATOR
WINDING 1
STATOR
WINDING 2
STATOR
WINDING 3
STATOR
WINDING 4
STATOR
WINDING 5
STATOR
WINDING 6
MOTOR
BEARING 1
MOTOR
BEARING 2
PUMP
BEARING 1
PUMP
BEARING 2
PUMP
CASE
AMBIENT
4
12
16
20
24
28
32
36
40
44
48
8
3
11
15
19
23
27
31
35
39
43
47
7
2
10
14
18
22
26
30
34
38
42
46
6
1
9
13
17
21
25
29
33
37
41
45
5
Com
Com
Com
Com
Com
Com
Com
Com
Com
Com
Com
Com
shld.
shld.shld.
shld.
shld.
shld.
shld.
shld.
shld.
shld.
shld.
shld.
shld.
RTD1
RTD3
RTD4
RTD5
RTD6
RTD7
RTD8
RTD9
RTD10
RTD11
RTD12
RTD2
GROUND
BUS
METER
HottestStator
RTD1
RTD2
PLC
SCADA
RS485
+
cpm-
ShieldShield
-
CONTROL
POWER
380VAC / 125VDC
L
N
CHANNEL 1 CHANNEL 2 CHANNEL 3
RS485 RS485 RS485FIBER
71 74 7773 76 7972 75 78
80
82
84
85
81
83
Com-
shld.
SHLD SHLD SHLD Tx Rx
1
2
3
4
ANALOG
OUTPUTS
OPTION(IO)
RTD HI
ALARM
SELF TEST
ALARM
ALARM
RTD trip
Flow
Value
PressureValue
111
126
125
124
123
112
113114
115
116
117
118
119
120
121
122OUTPUTRELAYSOPTION(IO)
TRIP
ALARM
AUX. 1
AUX. 2
FILTER GROUND
LINE +
NEUTRAL -
SAFTY GROUNDCONTROL
POWER
WITH OPTION(F)
INPUT 1
INPUT 3
INPUT 6
INPUT 2
INPUT 4
INPUT 5
DIGITALINPUTS
OPTION(
IO)
51
59
61
52
60
62
53
54
55
56
57
58
GE Power Management
GEPower Management
RRTD
Remote RTD Module
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
18/82
2-4 RRTD Remote RTD Module GE Multilin
2.3 ELECTRICAL INSTALLATION 2 INSTALLATION
2
2.3.2 CONTROL POWER
VERIFY THAT THE CONTROL POWER SUPPLIED TO THE RELAY IS WITHIN THE RANGE COVERED BY
THE ORDERED RRTD RELAYS CONTROL POWER.
The RRTD power supply is a switchmode supply. It can operate with either AC or DC voltage applied to it.
Extensive filtering and transient protection has been incorporated into the RRTD to ensure reliable operation in harsh
industrial environments. Transient energy is removed from the module and conducted to ground via the ground terminal.
This terminal must be connected to the cubicle ground bus using a 10AWG wire or a ground braid. Do not daisy chain
grounds with other devices. Each should have its own connection to the ground bus.
The internal supply is protected via a 3.15 A slo-blo fuse that is accessible for replacement. If it must be replaced ensure
that it is replaced with a fuse of equal size (see Fuse Specifications in Technical Specifications - section 2)
2.3.3 RTD INPUTS
The RRTD can monitor up to 12 RTD inputs for Stator, Bearing, Ambient, or Other temperature applications. The type of
each RTD is field programmable as: 100 Platinum (DIN.43760), 100 Nickel, 120 Nickel, or 10 Copper. RTDs mustbe the three wire type. There are no provisions for the connection of thermistors.
The RTD circuitry compensates for lead resistance, provided that each of the three leads is the same length. Lead resis-
tance should not exceed 25 per lead for platinum and nickel type RTDs or 3 per lead for Copper type RTDs.
Shielded cable should be used to prevent noise pickup in industrial environments. RTD cables should be kept close to
grounded metal casings and avoid areas of high electromagnetic or radio interference. RTD leads should not be run adja-
cent to or in the same conduit as high current carrying wires.
The shield connection terminal of the RTD is grounded in the RRTD and should not be connected to ground at the motor or
anywhere else to prevent noise pickup from circulating currents.
If 10 Copper RTDs are used, special care should be taken to keep the lead resistance as low as possible to maintainaccurate readings.
Figure 23: RTD INPUTS
Table 22: RRTD POWER SUPPLY RANGES
RRTD POWER SUPPLY AC RANGE DC RANGE
HI 40 to 265 V 50 to 300 V
LO 20 to 48 V 20 to 60 V
CAUTION
4
Com
ShieldShield
Hot
Compensation
Return
12
1
2
3
SAFETY GROUND
RTD
SENSING
RTD
#1
RRTD RELAYMOTOR
STARTER
MOTOR3 WIRE SHIELDED CABLE
RTD
TERMINALSIN MOTORSTARTER
RTD TERMINALS AT MOTOR
Maximum total lead resistance25 ohms ( Platinum & Nickel RTDs)3 ohms (Copper RTDs)
Route cable in separate conduit fromcurrent carrying conductors
RTD INMOTOR
STATOR
OR
BEARING
813704A2.CDR
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
19/82
GE Multilin RRTD Remote RTD Module 2-5
2 INSTALLATION 2.3 ELECTRICAL INSTALLATION
2.3.4 DIGITAL INPUTS
DO NOT CONNECT LIVE CIRCUITS TO THE RRTD DIGITAL INPUTS. THEY ARE DESIGNED FOR DRY CON-
TACT CONNECTIONS ONLY.
The RRTD provides 6 programmable digital inputs with the Input/Output option (IO). They can also be programmed for use
as generic inputs to set up trips and alarms or for monitoring purposes based on external contact inputs.A twisted pair of wires should be used for digital input connections.
2.3.5 ANALOG OUTPUTS
The RRTD provides 4 analog current output channels with the Input/Output option (IO). These outputs are field program-
mable to a full-scale range of either 0 to 1 mA (into a maximum 2.4 k impedance) and 4 to 20 or 0 to 20 mA (into a maxi-mum 600 impedance).
As shown in Figure 22: TYPICAL WIRING on page 23, these outputs share one common return. Polarity of these outputs
must be observed for proper operation.
Shielded cable should be used for connections, with only one end of the shield grounded, to minimize noise effects. The
analog output circuitry is isolated. Transorbs limit this isolation to 36 V with respect to the RRTD safety ground.
If an analog voltage output is required, a burden resistor must be connected across the input of the SCADA or measuringdevice (see the figure below). Ignoring the input impedance of the input,
For 0 to 1 mA, for example, if 5 V full scale is required to correspond to 1 mA,
For 4 to 20 mA, this resistor would be
Figure 24: ANALOG OUTPUT VOLTAGE CONNECTION
2.3.6 DISPLAY
Monitoring and setting of the RRTD module can be performed via the 369 Motor Management Relay through a communica-
tion link to the RRTD. If a stand alone RRTD is required, a Quick Panel display can be configured to monitor actual values.
The RTDPC program is used to program the module when it is configured as a stand alone.
CAUTION
RLOADVFULL SCALE
IMAX----------------------------------=
RLOADVFULL SCALE
IMAX----------------------------------
5 V
0.001 A--------------------- 5000 = = =
RLOADVFULL SCALE
IMAX----------------------------------
5 V
0.020 A--------------------- 250 = = =
840714A3.CDR
80
SCADA
OR
PLC
OR
METERING
DEVICE
V +
V -
R
Com-
Shield
Analog
Outputs
82
84
81
83
85
1
2
3
4
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
20/82
2-6 RRTD Remote RTD Module GE Multilin
2.3 ELECTRICAL INSTALLATION 2 INSTALLATION
2
2.3.7 OUTPUT RELAYS
The RRTD provides four form C output relays. They have been labeled Trip, Aux 1, Aux 2 and Alarm. Each relay has nor-
mally open (NO) and normally closed (NC) contacts and can switch up to 8 A at either 250 V AC or 30 V DC with a resistive
load. The NO or NC state is determined by the no power state of the relay outputs.
All four output relays may be programmed for fail-safe or non-fail-safe operation. When in fail-safe mode, output relay acti-
vation or a loss of control power will cause the contacts to go to their power down state.For example:
A fail-safe NO contactwill close when the RRTD is powered up (if no prior unreset trip conditions) and will open when
activated (tripped) or when the RRTD loses control power.
A non-fail-safe NO contactwill remain open when the RRTD is powered up (unless a prior unreset trip condition) and
will close only when activated (tripped). If control power is lost while the output relay is activated (NO contacts closed)
the NO contacts will open.
Thus, in order to cause a trip on loss of control power to the RRTD, the Trip relay should be programmed as fail-safe. See
Figure 22: TYPICAL WIRING for typical wiring of contactors and breakers for fail-safe and non-fail-safe operation.
Output relays will remain latched after activation if the fault condition persists or the protection element has been pro-
grammed as latched. This means that once this relay has been activated it will remain in the active state until the RRTD is
manually reset. The Trip relay cannot be reset if a timed lockout is in effect. Lockout time will be adhered to regardless of
whether control power is present or not.
The relay contacts may be reset if motor conditions allow, by pressing the RESET key, using the REMOTE RESET switch
or via communications. The Emergency Restart feature overrides allfeatures to reset the RRTD.
The rear of the RRTD relay shows output relay contacts in their power down state.
2.3.8 RS485 COMMUNICATIONS
Three independent two-wire RS485 ports are provided. If option (F), the fiber optic port, is installed and used the Comm 3
RS485 port, may not be used. The RS485 ports are isolated as a group.
Up to 32 devices can be daisy-chained together on a single serial communication channel without exceeding the driver
capability. For larger systems, additional serial channels must be added. Commercially available repeaters may also be
used to increase the number of relays on a single channel to a maximum of 254. Note that there may only be one masterdevice per serial communication link.
Connections should be made using shielded twisted pair cables (typically 24AWG). Suitable cables should have a charac-
teristic impedance of 120 (e.g. Belden #9841) and total wire length should not exceed 4000 feet. Commercially availablerepeaters can be used to extend transmission distances.
Voltage differences between remote ends of the communication link are not uncommon. For this reason, surge protection
devices are internally installed across all RS485 terminals. Internally, an isolated power supply with an optocoupled data
interface is used to prevent noise coupling. The source computer/PLC/SCADA system should have similar transient protec-
tion devices installed, either internally or externally, to ensure maximum reliability.
To ensure that all devices in a daisy-chain are at the same potential, it is imperative that the common termi-
nals of each RS485 port are tied together and grounded in one location only, at the master. Failure to do so
may result in intermittent or failed communications.
Correct polarity is also essential. RRTDs must be wired with all positive (+) terminals connected together and all negative() terminals connected together. Each relay must be daisy-chained to the next one. Avoid star or stub connected configu-
rations. The last device at each end of the daisy chain should be terminated with a 120 1/4 W resistor in series with a 1nFcapacitor across the + and terminals. Observing these guidelines will result in a reliable communication system that is
immune to system transients.
CAUTION
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
21/82
GE Multilin RRTD Remote RTD Module 3-1
3 RTDPC INTERFACE 3.1 INTRODUCTION
3 RTDPC INTERFACE 3.1 INTRODUCTION 3.1.1 REQUIREMENTS
The following minimum requirements must be met for the RTDPC software to operate properly.
Processor: Minimum 486, Pentium or higher recommended.
Memory: Minimum 4 MB RAM, 16 MB recommended. Minimum 540 K of conventional memory.
Hard Drive: 20 MB free space required before installation of software.O/S: Minimum Windows 3.1/3.11, Windows NT, or Windows 95/98 (recommended).
Windows 3.1 Users must ensure that SHARE.EXE is installed.
Other: CD-ROM or internet capability to install RTDPC
(if neither is available, 3.5" floppy disks can be ordered from the factory)
If RTDPC is currently installed, note the path and directory name. This information is required when upgrading.
The RTDPC software is included on the GE Multilin Products CD included with the RRTD. If your PC does not have CD-
ROM capability, the software may be downloaded from the GE Multilin website at www.GEindustrial.com/multilin or ordered
on 3.5" floppy disks from the nearest GE Multilin office.
All products include the GE Multilin Products CD. Since this CD is essentially a snapshot of the GE Multilin web-
site, the procedures for installation from the CD and the Web are identical. However, the website will always contain
the newest versions and is recommended for upgrading the software.
3.1.2 INSTALLING RTDPC
Installation of the RTDPC software is accomplished as follows.
1. Ensure that Windows is running and functional on the local PC
2. Insert the GE Multilin Products CD into your CD-ROM drive orpoint your web browser to the GE Multilin website at
www.GEindustrial.com/multilin. With Windows 95/98, the Products CD will launch the welcome screen automatically
(alternately, you may open the index.htm file in the Products CD root directory). Since the Products CD is essentially
a snapshot of the GE Multilin website, the procedures for installation from the CD and the Web are identical from this
point forward.
3. Click the Index By Product Name item from the main page menu and select the RRTD Remote RTD Module from the
product list to open the RRTD product page.
4. Click the Software menu item from the Product Resources list to proceed to the RRTD software page.
5. The latest version of the RTDPC software will be shown. Select the RTDPC Program item to download the installation
program to your local PC. Run the installation program and follow the prompts to install the software to the desired
directory. When complete, a new GE Multilin group window will appear containing the RTDPC icon.
3.1.3 UPGRADING RTDPC
The following procedure determines if the currently installed version of RTDPC requires upgrading:
1. Run the RTDPC software.
2. Select the Help > About RTDPC menu item.
3. Compare the version shown in this window with the version on the Products CD or website. If the installed version is
lower than the version on the CD or web, then RTDPC needs to be upgraded.
4. To upgrade the RTDPC software, follow the installation instructions shown in the previous section. The installation pro-
gram will automatically upgrade the RTDPC software.
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
22/82
3-2 RRTD Remote RTD Module GE Multilin
3.2 USING RTDPC 3 RTDPC INTERFACE
3
3.2 USING RTDPC 3.2.1 CONFIGURATION
1. Connect the computer containing the RTDPC software to the relay via the Channel 1 or 2 RS485 port. Channel 3 is
designated for communication to the 369 relay for remote RTD monitoring and is not meant for use with the RTDPC
software.
2. Run the RTDPC software. Once the program starts to operate, it will not automatically communicate with the relay
unless enabled to do so (see the Startup Mode option below). The LED status and display message shown will matchactual relay state if communications is established.
3. To setup communications, select Communication > Computermenu item.
Figure 31: COMMUNICATION / COMPUTER WINDOW
4. Set Slave Address to match that programmed into relay.
5. Set Communication Port# to the computer port connected to the relay.
6. Set Baud Rate and Parity to match that programmed into relay.
7. Set Control Type to type used.
8. Set Startup Mode to the desired startup (communicate or file)
9. Select ON to enable communications with new settings.
3.2.2 UPGRADING FIRMWARE
1. To upgrade the relay firmware, connect a computer to the Channel 1 RS485 Port of the RRTD. Channels 2 and 3 can-
not be used to upgrade the relay firmware.
2. Run RTDPC and establish communications with the relay.
3. Select the Communication > Upgrade Firmware menu item. The following window will appear:
4. SelectYes to proceed orNo to abort. Remember, all previously programmed setpoints will be erased! If you have not
already created a setpoint file, it is highly recommended that the current setpoints be saved to disk by following the
procedure in Section 3.2.3: CREATING A NEW SETPOINT FILE on page 33 before continuing with the firmware
upgrade.
5. The Load Firmware window will appear. Locate the firmware file to load into the relay and select OK to proceed or
Cancel to quit the firmware upgrade.
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
23/82
GE Multilin RRTD Remote RTD Module 3-3
3 RTDPC INTERFACE 3.2 USING RTDPC
6. The Upload Firmware dialog box shown below will appear. This provides one last chance to cancel the firmware
upgrade. SelectYes to proceed, No to load a different firmware file, orCancel to end the firmware upgrade. This will
be the last chance to cancel the firmware upgrade all previously programmed setpoints will be erased!
7. The RTDPC software automatically puts the relay into upload mode and then begin loading the file selected.
8. When loading is complete, the relay will require programming. To reload the previously programmed setpoints, see the
procedure in Section 3.2.5: DOWNLOADING A SETPOINT FILE on page 34.
3.2.3 CREATING A NEW SETPOINT FILE
1. To create a new setpoint file, run RTDPC. It is not necessary to have an RRTD unit connected to the computer to cre-
ate the file; however, some setpoint sections are only active if there is communication with an RRTD. The RTDPC sta-
tus bar will indicate that the program is in Editing File mode and Not Communicating.2. From the Setpoint menu, choose the appropriate setpoints section to program, for example, S3 RTD Temperature >
RTD Protection to enter output relay setup setpoints.
Figure 32: RTD PROTECTION WINDOW
3. When you are finished programming a page, select OK to store the information to the RTDPC scratchpad memory
(note: this action does not store the information as a file on a disk).
4. Repeat steps 2 to 3 until all the desired setpoints are programmed.
5. Select the File > Save As menu item to store these setpoints to the disk. Enter the location and file name of the set-
point file with a file extension of .RTD and select OK.
6. The file is now saved. See Section 3.2.5: DOWNLOADING A SETPOINT FILE on page 34 for instructions on reload-ing this file to the RRTD.
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
24/82
3-4 RRTD Remote RTD Module GE Multilin
3.2 USING RTDPC 3 RTDPC INTERFACE
3
3.2.4 EDITING A SETPOINT FILE
The following procedure describes how to edit setpoint files.
1. Run the RTDPC software. It is not necessary to have an RRTD unit connected to the computer. The status bar will indi-
cate that the program is in Polling Relay mode and Not Communicating.
2. If the RTDPC is communicating, select the Communication > Computermenu item to launch the COMMUNICA-
TION/COMPUTER window (see Figure 31: COMMUNICATION / COMPUTER WINDOW on page 32) and set Com-municate to "Off". Click OK to turn off communications to the relay and place RTDPC in Editing File mode.
3. Open a setpoint file by selecting the File > Open menu item. Locate the appropriate RRTD setpoint files (ending with
the extension .RTD) and select OK.
4. From the Setpoints menu item, choose the appropriate setpoints section to program; for example, System Setup >
Output Relay Setup to edit the output relay setup setpoints. When you have finished editing a page, select OK to
store the information to the RRTD scratchpad memory (NOTE: this action does not store the information as a file on a
disk).
5. Repeat Step 4 until all the desired setpoints are edited. Select the File > Save As menu item to store this file to disk.
Enter the location and file name of the setpoint file with a file extension of .RTD.
6. The file is now saved to disk. See Section 3.2.5: DOWNLOADING A SETPOINT FILE on page 34 for instructions on
downloading this file to the RRTD.
3.2.5 DOWNLOADING A SETPOINT FILE
The following procedure describes how to download setpoint files to the RRTD.
1. To download a pre-programmed setpoint file to the RRTD, run RTDPC and establish communications with the con-
nected relay via the RS485 connector.
2. Select the File > Open menu item to locate the setpoint file to be loaded into the relay. Click OK to load.
3. When the file is completely loaded, the RTDPC software will break communications with the connected relay and the
status bar changes to indicate Editing File, Not Communicating.
4. Select the File > Send Info To Relay menu item to download the setpoint file to the connected relay.
5. When the file is completely downloaded, the status bar will revert back to Communicating. The RRTD now contains
all the setpoints as programmed in the setpoint file.If an attempt is made to download a setpoint file with a revision number that does not match the relay firmware revi-
sion, the following message type will appear:
See Section 3.2.6: UPGRADING SETPOINT FILE TO NEW REVISION on page 35 for instructions on upgrading
the setpoint file.
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
25/82
GE Multilin RRTD Remote RTD Module 3-5
3 RTDPC INTERFACE 3.2 USING RTDPC
3.2.6 UPGRADING SETPOINT FILE TO NEW REVISION
The following procedure describes how to upgrade setpoint file revisions. It may be necessary to upgrade the revision code
for a previously saved setpoint file when the RRTD firmware is upgraded.
1. To upgrade the revision of a previously saved setpoint file, run the 369PC software and establish communications with
the RRTD through the RS485 connector.
2. Select the Actual > A5 Relay Information menu item and record the Main Software revision number (for example,59CMB115.000, where 115 is the main revision identifier and refers to firmware version 1.15).
Figure 33: RELAY INFORMATION WINDOW
3. Select the File > Open menu item and select the setpoint file to be downloaded to the connected relay. When the file is
open, the RTDPC software will be in File Editing mode and Not Communicating.
4. Select the File > Properties menu item and note the version code of the setpoint file.
Figure 34: SETPOINT FILE PROPERTIES
5. If the Version code (e.g. 1.4X above) differs the firmware revision (noted in step 2 as 115), select the revision code that
matches the firmware from the pull-down tab. For example: for firmware revision 59CMB140.000 and current setpoint
revision as 1.15; change the Version code to 1.4X to upgrade.
6. Select the File > Save menu item to save the setpoint file.
7. To download the upgraded setpoint file to the RRTD, see Section 3.2.5: DOWNLOADING A SETPOINT FILE on page
34.
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
26/82
3-6 RRTD Remote RTD Module GE Multilin
3.2 USING RTDPC 3 RTDPC INTERFACE
3
3.2.7 PRINTING
This procedure describes how to print a list of the RRTD setpoints and/or actual values.
1. Start RTDPC. It is not necessary to establish communications.
2. Select the File > Open menu item to open a previously saved setpoint file, or
establish communications with a connected RRTD unit.
3. Select the File > Print Setup menu item. The following window will appear.
Select Actual Values to print a list of actual values.
Select Setpoints (All) or Setpoints (Enabled Features) to print a list of setpoints.
Select User Definable Memory Map to print the user-definable memory map.
4. Click OK to close the Window.
5. Select the File > Print menu item to send the setpoint/actual values file to the connected printer.
3.2.8 TROUBLESHOOTING
This section provides some tips for troubleshooting RTDPC when troubles are encountered within the Windows environ-
ment, e.g. General Protection Fault (GPF), Missing Window, Problems in Opening/Saving Files, and Application
Error.
If the RRTD program causes Windowssystem errors:
Ensure the RTDPC software is correctly installed and the PC being used meets the minimum requirements.
Ensure that only one copy of RTDPC is running at a given time: the RTDPC software cannot multi-task.
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
27/82
GE Multilin RRTD Remote RTD Module 4-1
4 SETPOINTS 4.1 S1 SETUP
4 SETPOINTS 4.1 S1 SETUP 4.1.1 SETPOINT ACCESS
The communication access may be changed through the RTDPC software. Setpoint access is changed in the Setpoint >
S1 Setup menu item. An access tab is shown only when communicating with a relay. To set a passcode, click the Change
Passcode button. Enter and verify a new passcode; after a passcode is entered, the Setpoint Access changes to "Read
Only". When setpoints are changed through the PC program during Read Only access, the user is prompted to enter the
passcode before the new setpoint is stored. To allow extended write access, click on Allow Write Access and enter the
passcode. To change the access level back to "Read Only", click Restrict Write Access. If 30 minutes elapses without set-point changes, or if control power is cycled, access automatically reverts to "Read Only".
If the access level is "Read and Write", write access to setpoints is automatic and a 0 passcode need not be entered. If the
programmed passcode is not known, consult the factory service department with the Encrypted Passcode to be decoded.
4.1.2 PREFERENCES
The Preferences section of the Setpoint > S1 Setup menu item allows the user to set the temperature display units to
either Celsius or Fahrenheit. The value chosen here will be reflected in all temperature actual values. RTD setpoints are
programmed in Celsius only.
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
28/82
4-2 RRTD Remote RTD Module GE Multilin
4.1 S1 SETUP 4 SETPOINTS
4
4.1.3 RRTD COMMUNICATIONS
The RRTD is equipped with three independent RS485 serial ports. The RRTD can act as a stand-alone unit or can be con-
nected along with a maximum of three (3) other RRTDs to the 369 Motor Management Relay. In this case, Channel 3
must be used for communication between the devices (see Section 6.1.4: MONITORING OF UP TO 60 RTDs on
page 63 for additional details). Communications Channels 1 and 2 may be used by other devices (for example, comput-
ers or PLCs). Only Channel 1 may be used to upgrade firmware on the RRTD.
The CHANNEL 3 APPLICATION setpoint of the 369 must be set to "RRTD" and each Remote RTD must have its application
set to "Modbus" and assigned a unique address. Each RRTD slave address must be set prior to connecting it to the
network. Establish communication with only one RRTD by using the default slave address of 254. Then change the Slave
Address in the S1 Setpoints > Setup window. When this new Slave Address is stored, the RRTD will lose communications
with RTDPC. At this point, the new address must then be stored in Communications Setup and communications re-estab-
lished with the relay.
Option F, a fiber optic port, may be ordered and used for Channel 3 communications. If the Channel 3 fiber optic port is
used, the Channel 3 RS485 connection is disabled.
RS485 communications support a subset of RTU protocol. Each must have a unique address from 1 to 254. Address 0 is
the broadcast address which all relays listen to. Addresses do not have to be sequential but no two devices can have the
same address or conflicts resulting in errors will occur. Generally each added to the link will use the next higher address
starting at 1. A maximum of 32 devices can be daisy chained and connected to a DCS, PLC or PC using the RS485 ports.
A repeater may be used to increase the number of relays on a single link to greater than 32.
4.1.4 REAL TIME CLOCK
The time/date stamp is used to track events for diagnostic purposes. The date and time are preset but may be entered
manually. A battery allows the internal clock to run continuously even when power is off. It has the same accuracy as an
electronic watch, approximately 1 minute per month. It may be periodically corrected via the clock update command over
the serial link using the PC program.
Enter the current date using two digits for the month, two digits for the day, and four digits for the year. For example, July
15, 2001 would be entered as "07 15 2001". If entered from the keypad, the new date will take effect the moment the [Store
Relay Time and Date] button is clicked. Enter the current time, by using two digits for the hour in 24 hour time, two digits for
the minutes, and two digits for the seconds. If entered from the keypad, the new time will take effect the moment the [StoreRelay Time and Date] button is clicked.
If the serial communication link is used, then all the relays can keep time in synchronization with each other. A new clock
time is pre-loaded into the memory map via the communications port by a remote computer to each relay connected on the
communications channel. The computer broadcasts (address 0) a set clock command to all relays. Then all relays in the
system begin timing at the exact same instant. There can be up to 100 ms of delay in receiving serial commands so the
clock time in each relay is 100 ms, the absolute clock accuracy in the PLC or PC (see Chapter8: COMMUNICATIONS
for information on programming the time and synchronizing commands).
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
29/82
GE Multilin RRTD Remote RTD Module 4-3
4 SETPOINTS 4.1 S1 SETUP
4.1.5 CLEAR/PRESET DATA
These commands may be used to clear various historical data. This is useful on new installations or to preset information
on existing installations where new equipment has been installed. The PRESET DIGITAL COUNTER message will only be
seen if one of the digital inputs has been configured as a digital input counter.
4.1.6 OPTIONS
The currently installed RRTD options, order code, and serial number are displayed in this window. If new options are
installed after ordering, select the relevant option ("Input/Output" and/or "Fiber Optic"), enter the passcode, and click the
Update Options Now button to update the RTDPC software to recognize them.
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
30/82
4-4 RRTD Remote RTD Module GE Multilin
4.2 S2 SYSTEM SETUP 4 SETPOINTS
4
4.2 S2 SYSTEM SETUP 4.2.1 DESCRIPTION
These setpoints are critical to the operation of the RRTD protective elements and control features. The output relay setup
and Control Functions are not shown if the IO option is not installed.
4.2.2 MONITORING SETUP
When the Trip Counter is enabled and the alarm pickup level is reached, an alarm will occur. To reset the alarm, the trip
counter must be cleared (see Section 4.1.5: CLEAR/PRESET DATA on page 43) or the pickup level increased and a reset
command issued. The trip counter alarm can be used to monitor and alarm when a predefined number of trips occur. This
would then prompt the operator or supervisor to investigate the causes of the trips that have occurred. See Section 5.3.1:
TRIP COUNTERS on page 54 for details of the individual trip counters.
4.2.3 OUTPUT RELAY SETUP
A latched relay (caused by a protective elements alarm or trip) may be reset at any time, providing that the condition that
caused operation is no longer present. Unlatched elements automatically reset when the condition has cleared.
These setpoints allow the relay output operation to be fail-safe or non-failsafe. The latchcode however, is defined individu-
ally for each protective element. Failsafe operation causes the output relay to energize in its normal state and de-energize
when activated by a protection element. A failsafe relay also changes state (if not already activated by a protection ele-ment) when control power is removed from the RRTD. Conversely a non-failsafe relay de-energizes in its normal non-acti-
vated state and does not change state when control power is removed (if not already activated by a protection element).
The choice of failsafe or non-failsafe operation is usually determined by the application. In situations where the process is
more critical than the protected equipment, non-failsafe operation is typically programmed. In situations where the equip-
ment is more critical than the process, failsafe operation is programmed.
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
31/82
GE Multilin RRTD Remote RTD Module 4-5
4 SETPOINTS 4.2 S2 SYSTEM SETUP
4.2.4 CONTROL FUNCTIONS
If enabled the motor may be remotely started and stopped via Modbus communications to the RRTD. Refer to Section
8.2.8: FUNCTION CODE 16: PERFORMING COMMANDS on page 87 for details on how to send commands. When a
Stop command is sent the Trip relay will activate for 1 second to complete the trip coil circuit for a breaker application or
break the coil circuit for a contactor application. When a Start command is issued the relay assigned for starting control will
activate for 1 second to complete the close coil circuit for a breaker application or complete the coil circuit for a contactor
application.
The Serial Communication Control functions may also be used to reset the unit. Refer to 8.2.3: FUNCTION CODE 05:
EXECUTE OPERATION on page 84 for more information.
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
32/82
4-6 RRTD Remote RTD Module GE Multilin
4.3 S3 RTD TEMPERATURE 4 SETPOINTS
4
4.3 S3 RTD TEMPERATURE 4.3.1 DESCRIPTION
These setpoints deal with the RTD overtemperature elements of the RRTD.
4.3.2 LOCAL RTD PROTECTION
Application: Each individual RTD may be assigned an application. A setting of None effectively turns that individualRTD off. Only RTDs with the application set to Stator are used for RTD biasing of the thermal model.
Type: Each RTD is individually assigned the RTD type connected to it. Multiple types may be used with a single RRTD.
Name: Each RTD may be assigned an 8 character (maximum) name. This name is used in alarm and trip messages.
Alarm/Hi Alarm/Trip: Each RTD can be programmed for separate Alarm, Hi Alarm and Trip levels and relays. Trips
are automatically stored as events. Alarms and Hi Alarms are stored as events only if the Record Alarms as Events
setpoint for that RTD is set to Yes.
Trip Voting: This feature has been included for added RTD trip reliability in situations where RTD malfunction and nui-
sance tripping is common. If enabled that RTD will only trip if the RTD or RTDs listed to be voted with are also above
their trip level. For example, if RTD 1 is set to vote with All Stator RTDs, the RRTD will only trip if RTD 1 is above its trip
level and any one of the other stator RTDs is also above its own trip level. RTD voting is typically only used on Stator
RTDs and typically done between adjacent RTDs to detect hot spots.
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
33/82
GE Multilin RRTD Remote RTD Module 4-7
4 SETPOINTS 4.3 S3 RTD TEMPERATURE
4.3.3 OPEN RTD ALARM
The RRTD has an Open RTD Sensor Alarm. This alarm will look at all RTDs that have been assigned an application other
than None and determine if an RTD connection has been broken. When a broken sensor is detected, the assigned output
relay will operate and the RTDPC program will identify the RTD that is broken. It is recommended that if this feature is used,
the alarm be programmed as latched so that intermittent RTDs are detected and corrective action may be taken.
Table 41: RTD RESISTANCE TO TEMPERATURE
TEMPERATURE RTD RESISTANCE (IN OHMS)
C F 100 Pt(DIN43760)
120 Ni 100 Ni 10 Cu
40 40 84.27 92.76 79.13 7.49
30 22 88.22 99.41 84.15 7.88
20 4 92.16 106.15 89.23 8.26
10 14 96.09 113.00 94.58 8.65
0 32 100.00 120.00 100.0 9.04
10 50 103.90 127.17 105.6 9.42
20 68 107.79 134.52 111.2 9.81
30 86 111.67 142.06 117.1 10.19
40 104 115.54 149.79 123.0 10.58
50 122 119.39 157.74 129.1 10.97
60 140 123.24 165.90 135.3 11.35
70 158 127.07 174.25 141.7 11.74
80 176 130.89 182.84 148.3 12.12
90 194 134.70 191.64 154.9 12.51100 212 138.50 200.64 161.8 12.90
110 230 142.29 209.85 168.8 13.28
120 248 146.06 219.29 176.0 13.67
130 266 149.82 228.96 183.3 14.06
140 284 153.58 238.85 190.9 14.44
150 302 157.32 248.95 198.7 14.83
160 320 161.04 259.30 206.6 15.22
170 338 164.76 269.91 214.8 15.61
180 356 168.47 280.77 223.2 16.00
190 374 172.46 291.96 231.6 16.39
200 392 175.84 303.46 240.0 16.78
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
34/82
4-8 RRTD Remote RTD Module GE Multilin
4.3 S3 RTD TEMPERATURE 4 SETPOINTS
4
4.3.4 SHORT/LOW TEMP RTD ALARM
The RRTD has an RTD Short/Low Temperature alarm. This alarm will look at all RTDs that have an application other than
None and determine if an RTD has either a short or a very low temperature (less than 40C). When a short/low tempera-
ture is detected, the assigned output relay will operate and a message will appear on the display identifying the RTD that
caused the alarm. It is recommended that if this feature is used, the alarm be programmed as latched so that intermittent
RTDs are detected and corrective action may be taken.
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
35/82
GE Multilin RRTD Remote RTD Module 4-9
4 SETPOINTS 4.4 S4 DIGITAL INPUTS
4.4 S4 DIGITAL INPUTS 4.4.1 DIGITAL INPUT FUNCTIONS
Any of the programmable digital inputs may be programmed as a General Switch Input or Digital Counter.
Digital input alarms and trips (both General or Digital Counter) are activated at the local module, the mas-
ters output relays DO NOT activate.
Only one digital input may be selected as a digital counter at a time. User defined units and counter name may be defined
and these will appear on all counter related actual value and alarm messages. To clear a digital counter alarm, the alarm
level must be increased or the counter must be cleared or preset to a lower value.
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
36/82
4-10 RRTD Remote RTD Module GE Multilin
4.5 S5 ANALOG OUTPUTS 4 SETPOINTS
4
4.5 S5 ANALOG OUTPUTS 4.5.1 ANALOG OUTPUT PARAMETER SELECTION
The analog outputs are only configurable for the local RTDs.
Table 42: ANALOG OUTPUT PARAMETERS
PARAMETER NAME RANGE /UNITS STEP DEFAULT
MINIMUM MAXIMUM
Hottest Stator RTD 40 to +200C or 40 to +392F 1 0 200
RTD #1 to 12 40 to +200C or 40 to +392F 1 40 200
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
37/82
GE Multilin RRTD Remote RTD Module 4-11
4 SETPOINTS 4.6 S6 TESTING
4.6 S6 TESTING 4.6.1 FORCE OUTPUT RELAYS
The Force Output Relay feature provides a method of performing checks on all relay contact outputs. The feature can also
be used for control purposes while the equipment is operating. The forced state overrides the normal operation of the relay
output.
The forced state, if enabled (energized or de-energized), will force the selected relay into the programmed state for as long
as the programmed duration. After the programmed duration expires the forced state will return to disabled and relay oper-ation will return to normal. If the duration is programmed as Static, the forced state will remain in effect until changed or dis-
abled. If control power to the RRTD is interrupted, any forced relay condition will be removed.
4.6.2 FORCE ANALOG OUTPUTS
The Force Analog Output setpoints may be used during startup or testing to verify that the analog outputs are functioning
correctly. It may also be used when the motor is running to give manual or communication control of an analog output.
Forcing an analog output overrides its normal functionality.
When the Force Analog Outputs Function is enabled, the output will reflect the forced value as a percentage of the range 4
to 20 mA, 0 to 20 mA, or 0 to 1 mA. Selecting Off will place the analog output channels back in service, reflecting the
parameters programmed to each.
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
38/82
4-12 RRTD Remote RTD Module GE Multilin
4.6 S6 TESTING 4 SETPOINTS
4
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
39/82
GE Multilin RRTD Remote RTD Module 5-1
5 ACTUAL VALUES 5.1 A1 STATUS
5 ACTUAL VALUES 5.1 A1 STATUS 5.1.1 LAST TRIP DATA
Immediately prior to a trip, the RRTD records the cause of trip, the date and time and stores this as pre-trip value. This
allows for ease of troubleshooting when a trip occurs. These values are overwritten when the next trip occurs.
The resetting of any latched trip or alarm is done here. All RTD trips and alarms are activated at the master only; thus any
latched RTD trip or alarm is resettable at the master by clicking on the Reset button. On the other hand, digital trips or
alarms are activated at the slave only; thus any latched digital trip or alarm is resettable by clicking on the related RRTDreset button.
5.1.2 ALARM STATUS
Any active alarm may be viewed here. If the Line Up and Down keys are not pressed, the active messages will automati-
cally cycle. The current level causing the alarm is displayed along with the alarm name.
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
40/82
5-2 RRTD Remote RTD Module GE Multilin
5.1 A1 STATUS 5 ACTUAL VALUES
5
5.1.3 DIGITAL INPUT STATUS
The present state of the digital inputs will be displayed here.
5.1.4 OUTPUT RELAY STATUS
The present state of the output relays will be displayed here. Energized indicates that the NO contacts are now closed and
the NC contacts are now open. De-energized indicates that the NO contacts are now open and the NC contacts are now
closed. Forced indicates that the output relay has been commanded into a certain state.
5.1.5 REAL TIME CLOCK
The date and time from the RRTD real time clock may be viewed here.
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
41/82
GE Multilin RRTD Remote RTD Module 5-3
5 ACTUAL VALUES 5.2 A2 TEMPERATURE DATA
5.2 A2 TEMPERATURE DATA 5.2.1 LOCAL RTD
LOCAL RTD: The temperature level of all 12 internal RTDs will be displayed here. The programmed name of each
RTD (if changed from the default) will appear as the first line of each message.
5.2.2 LOCAL RTD MAXIMUMS
LOCAL RTD MAXIMUMS: The maximum temperature level of all 12 internal RTDs will be displayed. The programmed
name of each RTD (if changed from the default) will appear as the first line of each message.
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
42/82
5-4 RRTD Remote RTD Module GE Multilin
5.3 A3 STATISTICAL DATA 5 ACTUAL VALUES
5
5.3 A3 STATISTICAL DATA 5.3.1 TRIP COUNTERS
A breakdown of the number of trips by type is displayed here. When the total reaches 50000, the counter resets to 0 on the
next trip and continues counting. This information can be cleared in the Setpoints > S1 Setup menu item (see Clear/Pre-
set tab). The date the counters are cleared is recorded.
5.3.2 STATISTICS
The digital counter is displayed when one of the digital inputs is set as a digital counter. The digital counter can be cleared
in the Setpoints > S1 Setup menu item (see Clear/Presets tab). When the digital counter reaches 65535, it is automati-
cally reset to 0.
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
43/82
GE Multilin RRTD Remote RTD Module 5-5
5 ACTUAL VALUES 5.4 A4 EVENT RECORDER
5.4 A4 EVENT RECORDER 5.4.1 EVENT RECORDER
The event recorder stores system information each time an event occurs (for example, a motor trip). A maximum of 40
events are stored, with Event 1 representing the oldest event. When the number of events exceeds 40, Event 1 is deleted
from the event recorder.
Details of selected events can be viewed by clicking the View Data button. Select events by clicking the checkboxes in the
Select column. This data can be stored and/or printed for future reference.
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
44/82
5-6 RRTD Remote RTD Module GE Multilin
5.5 RELAY INFORMATION AND COMMMANDS 5 ACTUAL VALUES
5
5.5 RELAY INFORMATION AND COMMMANDS 5.5.1 A5 RELAY INFORMATION
RRTD model and manufacture information may be viewed here. The last calibration date is the date the relay was last cali-
brated at GE Multilin. This information reflects the revisions of the software currently running in the RRTD. This information
should be noted and recorded before calling for technical support or service.
5.5.2 COMMANDS
RRTD commands are performed through the Commands menu, allowing for the refreshing and resetting of local RRTDs.
a) RESET RRTD
Each individual RRTD can be reset through the commands menu. This is used to reset RRTD units that have the IO option
and have a latched trip or alarm active.
b) REFRESH RRTD
The refresh command sends the setpoints that are saved in the master RRTD to the slave. This command is used when
replacing a RRTD unit.
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
45/82
GE Multilin RRTD Remote RTD Module 6-1
6 APPLICATIONS 6.1 RTD CIRCUITRY
6 APPLICATIONS 6.1 RTD CIRCUITRY 6.1.1 RTD CIRCUIT OPERATION
The following is an explanation of how the RTD circuitry works in the RRTD.
Figure 61: RTD CIRCUITRY
A constant current source sends 3 mA DC down legs A and C. A 6 mA DC current returns down leg B. It may be seen that:
or
The above holds true providing that all three leads are the same length, gauge, and material, hence the same resistance.
or
Electronically, subtracting VAB from VBC leaves only the voltage across the RTD. In this manner lead length is effectively
negated:
6.1.2 TWO WIRE RTD LEAD COMPENSATION
An example of how to add lead compensation to a two wire RTD is shown below.
Figure 62: 2 WIRE RTD LEAD COMPENSATION
The compensation lead would be added and it would compensate for the Hot and the Return assuming they are all of equal
length and gauge. To compensate for resistance of the Hot and Compensation leads, a resistor equal to the resistance of
the Hot lead could be added to the compensation lead, though in many cases this is unnecessary.
RTD
COMPENSATION3 mA
RETURN6 mA
HOT
840733A1.CDRC
B
A
3 mA
VAB VLeadA VLeadB+= and VCB VLeadC VRT D VLeadB+ +=
VAB Vcomp Vreturn+= and VCB Vho t VRT D Vreturn+ +=
RLeadA RLeadB RLeadC RLead= = =
Rcomp Rreturn Rho t RLead= = =
VCB VAB VLead VRT D VLead+ +( ) VLead VLead+( )=
VCB VAB VRT D=
RTD #6
COMPENSATION
RETURN
TERMINAL
RRTDCOMPENSATION
RESISTOR
MOTORRETURN
HOTHOT
813711A1.CDR
22
24
21
23
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
46/82
6-2 RRTD Remote RTD Module GE Multilin
6.1 RTD CIRCUITRY 6 APPLICATIONS
6
6.1.3 REDUCED RTD LEAD NUMBER APPLICATION
The RRTD requires three leads to be brought back from each RTD: Hot, Return, and Compensation. In certain situations
this can be quite expensive. However, it is possible to reduce the number of leads so that three are required for the first
RTD and only one for each successive RTD. Refer to the following diagram for wiring configuration.
Figure 63: REDUCED WIRING RTDs
The Hot line is run as usual for each RTD. However, the Compensation and Return leads need only be run for the first RTD.
At the motor RTD terminal box, connect the RTD Return leads together with as short as possible jumpers. At the RRTD
unit, the Compensation leads must be jumpered together.
Note that an error is produced on each RTD equal to the voltage drop across the RTD return jumper. This error increases
for each successive RTD added as:
VRTD1 = VRTD1
VRTD2 = VRTD2 + VJ3
VRTD3 = VRTD3 + VJ3 + VJ4
VRTD4 = VRTD4 + VJ3+ VJ4 + VJ5, etc....
This error is directly dependent on the length and gauge of the jumper wires and any error introduced by a poor connection.For RTD types other than 10C, the error introduced by the jumpers is negligible.
Although this RTD wiring technique reduces the cost of wiring, the following disadvantages must be noted:
1. There is an error in temperature readings due to lead and connection resistances. Not recommended for 10C RTDs.
2. If the RTD Return lead to the RRTD or one of the jumpers breaks, all RTDs from the point of the break onwards will
read open.
3. If the Compensation lead breaks or one of the jumpers breaks, all RTDs from the point of the break onwards will func-
tion without any lead compensation.
RTD #1RTD #1
RRTD
RTD #2RTD #2
RTD #3RTD #3
RTD #4RTD #4
RTD #5RTD #5
RTD #6RTD #6
HOT
HOT
HOT
HOT
HOT
HOT
RETURN
RETURN
RETURN
RETURN
RETURN
RETURN
COMPENSATION
COMPENSATION
COMPENSATION
COMPENSATION
COMPENSATION
COMPENSATION
SHIELD
MOTORSHIELD
813710A1.CDR
1
5
9
13
17
21
2
6
10
14
18
22
3
7
11
15
19
23
24
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
47/82
GE Multilin RRTD Remote RTD Module 6-3
6 APPLICATIONS 6.1 RTD CIRCUITRY
6.1.4 MONITORING OF UP TO 60 RTDs
A maximum of four (4) RRTD modules with a 369 can be daisy-chained together as illustrated in Figure 65: DAISY
CHAINING RRTD MODULES on page 64. This provides the capability of monitoring up to 60 RTDs.
The 369 Motor Management Relay is designated as the master and the other RRTDs as the slaves. Each of the RRTD
slave modules must be programmed with a unique SLAVE ADDRESS before they can be daisy-chained together. Program-
ming is accomplished via RTDPC by connecting to either the Channel 1 or Channel 1 RS485 port. When all devices con-nected to the 369 are communicating properly, the 369PC software can also be used to program individual RRTD modules.
Figure 64: RTDPC SCREEN
Since the RRTD does not have a display, a HMI, such as the Quick Panel Jr., can be connected to one of the communica-
tion ports. The HMI can be configured to display the information of choice. Visit the GE Multilin Web site to obtain a Quick
Panel configuration template.
Please note that RRTD can be connected to only one 369 at a time.
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
48/82
6-4 RRTD Remote RTD Module GE Multilin
6.1 RTD CIRCUITRY 6 APPLICATIONS
6
Figure 65: DAISY CHAINING RRTD MODULES
813708A3.C
DR
COMPUTER
or
PLC
QUICKPANELJr.
369
M
OTORMANAGEMENT
RELAY
MASTER
CHANNE
L1
CHANNEL2
CHANNEL3
RS485
RS485
RS485
FIBER
S
HLD
SHLD
SHLD
Tx
Rx
R
RTD
REMO
TERTD
Mod
ule#1
RRTD
REMOTERTD
Module#2
RRTD
REMOTERTD
Module#3
RRTD
REMOTERTD
Module#4
SL
AVE
HMI
SLAVE
SLAVE
SLAVE
CHANNEL1
CHANNEL1
CHANNEL1
CHANNEL1
CHANNEL
2
CHANNEL2
CHANNEL2
CHANNEL2
CHANNEL3
CHANNEL3
CHANNEL3
CHANNEL3
RS485
RS485
RS485
RS485
RS485
RS485
RS485
RS485
RS485
RS485
RS485
RS485
FIBER
FIBER
FIBER
FIBER
SHLD
SHLD
SHLD
SHLD
SHLD
SHLD
SHLD
SHLD
SHLD
SHLD
SHLD
SHLD
Tx
Tx
Tx
Tx
Rx
Rx
Rx
Rx
COMPUTER
or
PLC
369
M
OTORMANAGEMENT
RELAY
MASTER
CHANNE
L1
CHANNEL2
CHANNEL3
RS485
RS485
RS485
FIBER
71
74
77
73
76
79
72
75
78
71
74
77
73
76
79
72
75
78
71
74
77
73
7
6
79
72
75
78
71
74
77
73
76
79
72
75
78
71
74
77
73
76
79
72
75
78
71
74
77
73
76
79
72
75
78
71
74
77
73
76
79
72
75
78
71
74
77
73
76
79
72
75
78
71
74
77
73
76
79
72
75
78
71
74
77
73
76
79
72
75
78
SHLD
SHLD
SHLD
Tx
Rx
R
RTD
REMOTERTD
Module#1
RRTD
REMOTERTD
Module#2
RRTD
REMOTERTD
Module#3
RRTD
REMOTERTD
Module#4
SL
AVE
F485
SLAVE
SLAVE
SLAVE
CHANNEL1
CHANNEL1
CHANNEL1
CHANNEL1
CHANNEL2
CHANNEL2
CHANNEL2
CHANNEL2
CHANNEL3
CHANNEL3
CHANNEL3
CHANNEL3
RS485
RS485
RS485
RS485
RS485
RS485
RS485
RS485
RS485
RS485
RS485
RS485
FIBER
FIBER
FIBER
FIBER
SHLD
SHLD
SHLD
SHLD
S
HLD
SHLD
SHLD
SHLD
SHLD
SHLD
SHLD
SHLD
Tx
Tx
Tx
Tx
Rx
Rx
Rx
Rx
GEPowerManagement
g
GEPowerManagement
g
G
EPowerManagement
g
G
EPowerManagement
g
GEPowerManagement
g
GEPowerManagement
g
GEPowerManagement
g
GEPowerManagement
g
GEPowerManagement
g
GEPowerManagement
g
8/3/2019 Ge Rrtd Manual Pn 1601-0104-b7
49/82
GE Multilin RRTD Remote RTD Module 6-5
6 APPLICATIONS 6.2 USING THE RRTD WITH THE 469 RELAY
6.2 USING THE RRTD WITH THE 469 RELAY 6.2.1 INTRODUCTION
Using the RRTD with the 469 eliminates the necessity of wiring RTDs back to the 469 for monitoring and/or control func-
tions.
Any RRTDs used with the 469 MUST have the IO option.
The following three scenarios are addressed in this section: control via the 469, monitoring via the 469, and monitoring and
control via the 469. Although only three specific scenarios are described, it is possible to use combinations of them. It is up
to the customer's discretion to apply them according to their needs.
6.2.2 CONTROL VIA THE 469
Use this setup if the application requires the 469 to control RTD trips and no monitoring by the 469 is required.
1. Wire the RTDs to the RRTD and program the RRTD with trip and alarm levels as described in the RRTD instruction
manual. Program all RRTD trips and alarms as unlatched.
2. Wire trip and alarm output relays from the RRTD to the 469 digital input(s). Program the 469 digital input(s) (one or
more of the General Switch A-D) and assign the appropriate output relay. The General Switch inputs can be renamed
to indicate that it is an RRTD trip or alarm (i.e. RRTD Trip).
3. A trip or alarm from the RRTD will now cause the 469 to issue the trip or alarm to the control scheme. The output relay
of the RRTD will reset as soon as the condition is cleared. The 469 output relay will reset according to whether it is pro-
grammed as latched or unlatched.
4. If monitoring of the RTD temperatures is required, the data can be read from the RRTD through communications.
6.2.3 MONITORING VIA THE 469
Use this setup if the application requires the RRTD to control tripping and/or alarms and it is desirable to have the 469 mon-
itor RTD temperatures.
1. Wire the RTDs to the RRTD as described in the RRTD instruction manual. If tripping and/or alarms are required, pro-
gram the RRTD accordingly and wire the RRTD output relays into the control scheme.
2. The RRTD has 4 Analog Outputs that can be wired to the 469 Analog Inputs. They can be programmed to representindividual RTDs or the Hottest Stator RTD.
3. Prog