General Condition
Element Units Abu
Dhabi Al Ain
Maximum ambient outdoor air temperature (shade) °C 49 50
Maximum daily average ambient shade temperature °C 40 40
Maximum monthly average ambient shade temperature
°C 37 37
Maximum annual average ambient shade temperature: °C 30 30
Minimum ambient temperature: °C 7 6
Storage temperature of equipment °C -10 to +70
Minimum barometric pressure (at sea level): Hecto Pascal 990 992
Maximum barometric pressure (at sea level): Hecto Pascal 1030
1030
Maximum ambient relative humidity: % 100 100
Minimum ambient relative humidity: % 1 1
Average annual rainfall: mm 85 85
Maximum annual rainfall: mm 255 165
Maximum daily (24 h) rainfall: mm 34 40
Maximum hourly rainfall: mm 80 50
Maximum seawater temperature: °C 36 -
Minimum seawater temperature: °C 20 -
Maximum ground temperature at 1 m depth: °C 40 41
Design Wind Speed: Km/h 160 160
Seismic load acceleration factor (horizontal) g 0.2 0.2
Seismic coefficient / importance factor (according to Zone 1 of Uniform Building Code):
0.075 / 1
0.075 /
Solar Radiation: W/m2 973 876
Isokeraunic Level: 7 thunderstorms
per year
Electrical Design Fundamentals
Description 220 kV
Phase to Earth Clearance 1700 mm
Minimum Safety Clearance – Conductor/ Live parts
To Walkways 8000 mm
To Public Road/ Highway 9000/1000 mm
To building, roofs, structures, light poles 6000 mm
Over pipeline 9000 mm
Minimum horizontal clearance b/w live part
Solid panel wall with a min. height of 1800 mm 2100 mm
wire mesh 2200 mm
Rail, chain, rope with a min. height of 1100 mm 2400 mm
substation perimeter walls of min. 1800 mm height 3600 mm
Live Conductor Crossings
11kV/33kV 5000 mm
132 kV 5000 mm
220 kV 5000 mm
400 kV 5000 mm
Tele-Communication Line 5000 mm
Minimum Clearances of/to Underground Cables & Cables to
other Services
Horizontal Cable Centre Line to Cable Centre Line
Between circuits 150 cm
Between phases (SC) 45 cm
Vertical Ground Surface to Cable Bottom 110 cm (in trough)
Horizontal/Vertical from Cables to other Services >200*,>60**/>100 (cm)
Note:
For OHTLs conductor clearances the maximum swing at maximum conductor sag of the concerned
OHTL conductor shall be considered (refer to DIN VDE 0210).
* distance from piles (horizontal)
** at cable crossings the space between the cable circuits shall be filled with CBS compound