2
ELEVATION DETAIL SECTION DETAIL
STRUCTURAL ENGINEER SHALL BENOTIFIED FOR REDESIGN
PIPE ON HANGER EXCEEDS 150 LBSNOTE: IF TOTAL LOAD OF FILLED
FOR ALL STEEL, PVC OR CAST IRON PIPE AND ROOF DRAIN SUPPORT TO BAR JOIST STRUCTURE
JOIST SPACING
TYP INTERIOR CMU WALL BRACING
TYP EXTERIOR CMU WALL BRACING
1
JOIST PARALLEL TO WALL
TYP CMU BRACE LOCATION - PLAN VIEW
TYP INTERIOR CMU WALL BRACINGJOIST PARALLEL TO WALL
HANGER SPACING SCHEDULEMAX HANGER SPACINGNOMINAL PIPE DIAM JOIST SPACING
HEADER ANGLE SCHEDULEANGLE SIZE
3
7 5/8"
TYP INTERIOR CMU WALL BRACINGTYP INTERIOR CMU WALL BRACINGJOIST PERPENDICULAR TO WALL
5
4
6
ADD L2x2x1/4WELD TO TOP& BUTT CHORP
GENERAL NOTES
CONCRETE:
ALL CONCRETE SHALL HAVE SAND AND GRAVEL AGGREGATE, TYPE I PORTLAND
CEMENT, AND SHALL HAVE A COMPRESSIVE STRENGTH (F'C) OF 3,000 PSI
AT 28 DAYS. DRILLED FOOTINGS MAY BE 2500 PSI AT 28 DAYS.
MINIMUM CEMENT RATIO TO BE: 5 SACKS PER CUBIC YARD FOR 3000 PSI
CONCRETE AND 4 - 1/2 SACKS PER CUBIC YARD FOR 2500 PSI CONCRETE.
MAXIMUM WATER CEMENT RATIO TO BE 0.50.
THE USE OF FLY ASH IS NOT PERMITTED ON THIS PROJECT.
ALL CONCRETE REINFORCEMENT BARS SHALL CONFORM TO ASTM A615, GRADE
60. NO.3 BARS MAY BE GRADE 40. DOWELS FROM FOUNDATION TO MASONRY
WALLS SHALL BE GRADE 40.
ALL WELDED WIRE FABRIC SHALL CONFORM TO ASTM 185.
DETAILING, FABRICATION AND PLACING OF CONCRETE REINFORCEMENT AND
ACCESSORIES SHALL BE IN ACCORDANCE WITH ACI SP-66, LATEST EDITION.
CONTINUOUS REINFORCEMENT FOR SLABS ON GRADE AND HORIZONTAL BARS IN
FOOTINGS SHALL HAVE MINIMUM LAP AT SPLICES AS FOLLOWS (UNLESS
OTHERWISE NOTED):
NO.3 BARS...16" NO.4 BARS...22" NO.5 BARS...27"
NO.6 BARS...32" NO.7 BARS...38" NO.8 BARS...43"
CONTINUOUS REINFORCEMENT FOR GRADE BEAMS SHALL HAVE MINIMUM LAP AT
SPLICES AS FOLLOWS (UNLESS OTHERWISE NOTED):
NO.3 BARS...21" NO.4 BARS...28" NO.5 BARS...35"
NO.6 BARS...42" NO.7 BARS...49" NO.8 BARS...59"
ALL OTHER CONTINUOUS REINFORCEMENT BEAMS SHALL HAVE MINIMUM LAP AT
SPLICES AS FOLLOWS (UNLESS OTHERWISE NOTED):
HORIZONTAL BARS:
NO.3 BARS...21" NO.4 BARS...28" NO.5 BARS...35"
NO.6 BARS...46" NO.7 BARS...63" NO.8 BARS...82"
NO.9 BARS..104" NO.10 BARS..132" NO.11 BARS..162"
VERTICAL BARS:
NO.3 BARS...16" NO.4 BARS...22" NO.5 BARS...27"
NO.6 BARS...36" NO.7 BARS...48" NO.8 BARS...63"
NO.9 BARS...80" NO.10 BARS..101" NO.11 BARS..125"
WELDED WIRE FABRIC SHALL LAP SO THAT THE OVERLAP MEASURED BETWEEN
OUTMOST CROSS WIRES OF EACH FABRIC SHEET IS NOT LESS THAN THE
SPACING OF CROSS WIRES PLUS 2".
PROVIDE CORNER BARS EQUAL IN SIZE AND NUMBER BY FIVE FEET WITH A
90 DEGREE BEND AT THE CORNER, IN EXTERIOR FACE OF BEAMS AND WALLS.
CORNER BARS NEED NOT BE LARGER THAN #5. SEE TYPICAL DETAIL FOR
CORNER BARS.
REINFORCING BARS MAY NOT BE WELDED WITHOUT APPROVAL OF THE
STRUCTURAL ENGINEER.
FOR CONTINUOUS GRADE BEAM REINFORCEMENT, TOP BARS SHALL BE SPLICED
AT THE CENTER OF A SPAN AND THE BOTTOM BARS SHALL BE SPLICED AT
THE CENTER OF A SUPPORT. SEE TYPICAL DETAIL.
CONCRETE PROTECTION FOR REINFORCEMENT SHALL BE AS FOLLOWS, (SEE
SECTION 7.7 ACI 318, LATEST EDITION, FOR CONDITIONS NOT NOTED):
ALL CONCRETE FORMED AGAINST THE GROUND...................3"
SIDES AND BOTTOMS OF GRADE BEAMS.........................3"
WALLS AND SIDES OF BEAMS ABOVE GRADE.....................1-1/2"
SLABS ABOVE GRADE.......................................3/4"
EXTERIOR FACE OF ALL GRADE BEAMS SHALL BE BOARD FORMED FOR FULL
DEPTH.
ALL MIXING, TRANSPORTING, PLACING AND CURING OF CONCRETE SHALL BE
DONE IN ACCORDANCE WITH THE RECOMMENDATION OF THE LATEST EDITIONS
OF THE AMERICAN CONCRETE INSTITUTE ACI 318, ACI 301, ACI 309,
ACI 305 AND ACI 306. MAXIMUM FREE FALL FOR CONCRETE TO BE 3'-0".
NO HORIZONTAL JOINTS WILL BE PERMITTED IN CONCRETE EXCEPT AT
CONSTRUCTION JOINTS EXCEPT WHERE THEY NORMALLY OCCUR OR WHERE
DETAILED.
HORIZONTAL REINFORCING SHALL BE CONTINUOUS THROUGH CONSTRUCTION
JOINTS.
FRESHLY DEPOSITED CONCRETE SHALL BE PROTECTED FROM PREMATURE
DRYING AND EXCESSIVE HOT OR COLD TEMPERATURES FOR THE PERIOD OF
TIME NECESSARY FOR THE HYDRATION OF THE CEMENT AND PROPER
HARDENING OF THE CONCRETE. THIS SHALL BE A MINIMUM OF SEVEN DAYS
AFTER THE CONCRETE IS POURED.
ALL CONCRETE, INCLUDING DRILLED FOOTINGS, SHALL BE CONSOLIDATED BY
VIBRATION, SPADING OR RODDING, SO THAT THE CONCRETE IS THOROUGHLY
WORKED AROUND THE REINFORCEMENT, EMBEDDED ITEMS, AND INTO CORNERS
OF FORMS, ELIMINATING ALL AIR OR STONE POCKETS WHICH MAY CAUSE
HONEYCOMBING. CARE SHALL BE TAKEN NOT TO OVER VIBRATE AND CAUSE
SEGREGATION.
SEE ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS FOR
SLEEVES, CURBS, DEPRESSIONS, INSERTS, ETC. THAT ARE NOT SHOWN.
STRUCTURAL STEEL:
ALL STRUCTURAL STEEL BEAMS AND COLUMNS SHALL BE GRADE CONFORM
TO ASTM A572 WITH Fy = 50 KSI.
ALL STRUCTURAL STEEL ROLLED SHAPES AND PLATES SHALL CONFORM TO
ASTM A572 UNLESS NOTED OTHERWISE.
ALL PIPE SHALL CONFORM TO ASTM A501 OR ASTM A53, TYPE E OR S. ALL
TUBING SHALL CONFORM TO ASTM A500, GRADE B.
ALL CONNECTION BOLTS FOR STRUCTURAL STEEL MEMBERS SHALL CONFORM TO
ASTM A325 AND SHALL BE DESIGNED AS BEARING-TYPE
CONNECTIONS TIGHTENED TO A SNUG TIGHT CONDITION AS PER THE
REQUIREMENT OF THE AISC MANUAL OF STEEL CONSTRUCTION. WASHERS OF
A325 MATERIAL SHALL BE USED ON ALL A325 CONNECTIONS. THE USE OF
SHIM PLATES IS NOT ALLOWED WITHOUT APPROVAL OF THE STRUCTURAL ENGINEER.
GROUT UNDER COLUMN BASE PLATES SHALL BE OF A NON-SHRINK VARIETY
WITH A MINIMUM COMPRESSIVE STRENGTH OF 7,000 PSI AT 28 DAYS. 100%
OF VOID UNDER ALL BASE PLATES IS TO BE GROUTED. ALL BASE PLATES
WITH A DIMENSION GREATER THAN 24" ARE TO HAVE TWO 1" DIAMETER
GROUT HOLES. IF THE SPACE UNDER A COLUMN BASE PLATE IS LESS THAN
1/4", THEN A PRESSURE INJECTION SYSTEM SHALL BE USED.
ALL STRUCTURAL STEEL DETAILS AND CONNECTIONS SHALL CONFORM TO THE
STANDARDS OF AISC.
ALL WELDING SHALL CONFORM TO THE STANDARDS OF THE AMERICAN WELDING
SOCIETY AND SHALL BE PERFORMED BY CERTIFIED WELDERS WHO ARE
CERTIFIED FOR THE POSITION OF WELD WHICH THEY ARE PERFORMING.
ALL FILLET WELDS SHALL BE MINIMUM AS REQUIRED BY AISC TABLE J2.4
BUT NOT LESS THAN 3/16". UNLESS OTHERWISE NOTED, WELDS SHALL BE
WELDED ALL AROUND ON ALL ACCESSIBLE SIDES.
ALL GROOVE WELDS TO BE FULL PENETRATION, UNLESS OTHERWISE NOTED.
ALL FULL PENETRATION WELDS AT MOMENT CONNECTIONS SHALL BE TESTED
AND CERTIFIED BY AN INDEPENDENT TESTING LAB USING NON DESTRUCTIVE
TESTING METHOD. FOR SHOP WELDS, CERTIFICATION SHALL BE SUBMITTED
PRIOR TO SHIPPING TO JOB SITE. FOR FIELD WELDS, CERTIFICATION
SHALL BE SUBMITTED PRIOR TO COVERING CONNECTIONS WITH
ARCHITECTURAL FINISHES.
ALL SHOP CONNECTIONS ARE TO BE WELDED AND ALL FIELD CONNECTIONS
ARE TO BE BOLTED EXCEPT WHERE OTHERWISE NOTED.
SPLICING OF STRUCTURAL STEEL MEMBERS WHERE NOT DETAILED IS
PROHIBITED WITHOUT PRIOR APPROVAL OF THE STRUCTURAL ENGINEER.
ALL STRUCTURAL STEEL CONNECTIONS SHALL DEVELOP THE FULL UNIFORM
LOAD CAPACITY AS TABULATED BY AISC TABLES FOR UNIFORM LOAD
CONSTANTS ON BEAM UNLESS OTHERWISE NOTED. ALL STRUCTURAL STEEL
CONNECTIONS SHALL BE DESIGNED BY THE STEEL FABRICATOR TO SUPPORT
THESE LOADS OR OTHER LOADS AS NOTED ON THE STRUCTURAL DRAWINGS.
(FOR BEAMS WITH COMPOSITE DESIGN, STANDARD AISC CAPACITY SHALL BE
INCREASED BY 35 PERCENT).
FOR STEEL BEAMS SHOWN ON THE DRAWINGS THAT DO NOT MEET THE MINIMUM
SIZE REQUIRED BY THE U.L. DESIGN NUMBER, WHICH IS SELECTED BY THE
ARCHITECT, THE THICKNESS OF THE SPRAYED PROTECTION MATERIAL SHALL
BE INCREASED. INCREASED THICKNESS OF SPRAYED PROTECTION MATERIAL
SHALL BE AS REQUIRED BY THE FORMULA SHOWN ON PAGE 18 OF THE U.L.
FIRE RESISTANCE DIRECTORY 1993 (OR LATEST EDITION) UNDER
ADJUSTMENT OF SPRAYED PROTECTION MATERIAL THICKNESS FOR RESTRAINED
BEAM RATINGS FOR VARIOUS BEAM SIZES.
FOR STEEL COLUMNS SHOWN ON THE DRAWINGS THAT DO NOT MEET THE
MINIMUM SIZE REQUIRED BY THE U.L. DESIGN NUMBER, WHICH IS SELECTED
BY THE ARCHITECT, INCREASE OF THICKNESS FOR THE SPRAYED
PROTECTION MATERIAL SHALL BE AS REQUIRED BY THE FORMULA SHOWN ON
PAGE 19 OF THE U.L. FIRE RESISTANCE DIRECTORY 1993 (OR LATEST
EDITION).
ALL OPEN-WEB STEEL JOIST AND BRIDGING SHALL CONFORM TO THE
STANDARDS OF THE STEEL JOIST INSTITUTE. BRIDGING SHALL CONFORM TO
THE SJI STANDARDS AND SHALL BE WELDED TO THE TOP AND BOTTOM CHORDS
AND TO THE BEAMS AT THE END. ONE JOIST NEAREST COLUMN LINE SHALL
BE FIELD BOLTED, AS PER OSHA STANDARDS, TO PROVIDE LATERAL
STABILITY DURING CONSTRUCTION. THE JOIST MANUFACTURER IS
RESPONSIBLE FOR REVIEWING THE CONSTRUCTION DOCUMENTS TO DETERMINE
IF THERE ARE ANY SPECIAL U.L. REQUIREMENTS WHICH MAY AFFECT THE
JOIST DESIGN AND INCORPORATE THOSE U.L. REQUIREMENTS INTO THEIR
DESIGN.
WHERE LONGSPAN JOISTS OR TRUSSES 40 FEET OR LONGER ARE USED, A
CENTER ROW OF BOLTED BRIDGING SHALL BE INSTALLED TO PROVIDE
LATERAL STABILITY DURING CONSTRUCTION PRIOR TO SLACKING OF
HOISTING LINE. (OSHA 1926.751 (2)).
ALL HANGER LOADS SUSPENDED FROM OPEN-WEB STEEL JOIST THAT ARE
HEAVIER THAN 50 POUNDS PER HANGER ARE TO BE ATTACHED TO THE TOPCHORD AT A JOIST TOP CHORD PANEL POINT.
PIPES SUSPENDED FROM OPEN-WEB JOIST TO BE SUPPORTED TO EACH JOISTCROSSED FOR ROOFS AND EVERY OTHER JOIST CROSSED FOR FLOORS. INADDITION, PIPES SHALL BE SUPPORTED TO EACH STEEL BEAM CROSSED.SEE TYPICAL DETAIL.
ALL STEEL DECK SHALL CONFORM TO THE STANDARDS AND BASIC DESIGNSPECIFICATIONS OF THE STEEL DECK INSTITUTE. STEEL DECK SHALL BEATTACHED TO SUPPORTING MEMBERS AND ADJOINING STEEL DECK SHEETS BYMEANS OF ELECTRIC ARC WELDING IN ACCORDANCE WITH MANUFACTURER'S
SPECIFICATIONS. MINIMUM WELDING SHALL BE WITH 5/8" DIAMETERPUDDLE WELDS TO ALL SUPPORTING MEMBERS, INCLUDING ALL PERIMETER
EDGES, SPACED AT 12" O.C. MAXIMUM. USE WELDING WASHERS FOR DECK
LIGHTER THAN 22 GAGE. FOR DECK SPAN GREATER THAN 5 FEET, THE SIDE
LAPS SHALL BE FASTENED TOGETHER AT A MAXIMUM SPACING OF 3 FEET
O.C. END JOINTS SHALL BE OF OVERLAPPING TYPE WITH A 2" MINIMUMLAP AND SHALL OCCUR OVER A SUPPORT.
MASONRY:
ALL MASONRY CONSTRUCTION SHALL CONFORM WITH THE REQUIREMENTS OF
ACI 530-88 AND ACI 530.1-88, LATEST EDITION.
ALL CONCRETE MASONRY UNITS SHALL HAVE A MINIMUM PRISM STRENGTH OFf'm = 1800 PSI. ALL MORTAR SHALL BE TYPE M OR S USING PORTLANDCEMENT AND HYDRATED LIME. MASONRY CEMENT MIX IS NOT TO BE USED.
FILL ALL REINFORCED CELLS, REINFORCED BOND BEAMS OR REINFORCED
CAVITIES WITH ASTM C476 GROUT HAVING A 28 DAY COMPRESSIVE STRENGTH
OF 3000 PSI. LAP MASONRY REINFORCING 48 BAR DIAMETERS. PLACE
GROUT IN LIFTS NOT EXCEEDING 5 FEET. SEE ACI 530.1 - 88 FORMAXIMUM POUR HEIGHTS.
STRUCTURAL DRAWINGS SHOW MASONRY WALL REINFORCING FOR SHEAR WALLSAND LOAD-BEARING WALLS ONLY. ALL OTHER MASONRY REINFORCING ISINDICATED ON THE ARCHITECTURAL DRAWINGS.
MASONRY COURSING SHOWN ON STRUCTURAL DRAWINGS IS TO INDICATEMATERIAL TYPE. SEE ARCHITECTURAL DRAWINGS FOR ACTUAL MASONRYCOURSING.
DOWELS FROM FOUNDATION TO MASONRY WALLS SHALL BE GRADE 40.
GENERAL:
CONSTRUCTION METHODS, ERECTION PROCEDURES, AND SAFETY PRECAUTIONSARE THE RESPONSIBILITY OF THE CONTRACTOR. STRUCTURAL DRAWINGSREPRESENT THE FINISHED STATE OF STRUCTURAL ELEMENTS. CONTRACTORTO PROVIDE TEMPORARY BRACING FOR ACCURATE PLUMBING AND TO RESISTALL WIND, SOIL BACKFILL, AND CONSTRUCTION LOADS. ENGINEEREDSTRUCTURAL DESIGN FOR TEMPORARY BRACING, FORMWORK, SOIL RETENTION,AND SHORING ARE TO BE PROVIDED BY THE CONTRACTOR.
CONTRACTOR TO VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS OF JOBSITE. ANY VARIATION FROM DIMENSIONS OR DETAILS AS SHOWN ON THESTRUCTURAL DRAWINGS SHALL BE REPORTED TO THE ARCHITECT ANDSTRUCTURAL ENGINEER.
EXTRA CARE SHALL BE TAKEN TO PREVENT CAVING AND SLOUGHING OF THESIDES OF THE GRADE BEAM EXCAVATION. THE GRADE BEAMS SHALL BE KEPTCLEAN OF ANY EARTH THAT MAY COME LOOSE FROM THE SIDES AND FALLINTO THE EXCAVATIONS.
ALL LOOSE SOIL, DEBRIS OR MUD SHALL BE REMOVED FROM THE BOTTOM OFGRADE BEAMS BEFORE POURING.
EXCAVATIONS FOR FOOTINGS SHALL BE NEAT AND CLEAN OF ALL LOOSE SOILOR MUD BEFORE POURING.
FOOTINGS SHALL BE POURED IMMEDIATELY UPON COMPLETION OF EXCAVATIONAND CLEANING OF FOOTING BEARING SURFACE.
CRANES, CONCRETE TRUCKS AND ALL OTHER HEAVILY LOADED VEHICLES ARENOT TO BE DRIVEN ACROSS GRADE BEAMS OR ON BUILDING SLABS.
ERECTION OF STRUCTURAL STEEL MAY NOT BEGIN UNTIL CONCRETEFOUNDATION HAS CURED FOR A MINIMUM OF THREE DAYS. STRUCTURALSTEEL OR OTHER HEAVY LOADS SHALL NOT BE STOCKPILED ON ANY SLABUNTIL IT HAS CURED FOR A MINIMUM OF THREE DAYS.
WHERE A DRILLED FOOTING IS SHOWN ON THE PLAN CLOSER THAN 6'-0"FROM ANOTHER FOOTING, DRILL ONE FOOTING, FILL WITH CONCRETE AND
LET CURE 24 HOURS BEFORE THE ADJACENT FOOTING IS DRILLED. (6'-0"DIMENSION IS MEASURED BETWEEN BELLS NOT CENTER TO CENTER.)
FOUNDATION DESIGN AND CONSTRUCTION REQUIREMENTS ARE BASED ON THE
HTS INC CONSULTANTS PROJECT NO.13-S-488. THE CONTRACTOR SHALL OBTAINA COPE OF THIS REPORT AND SHALL FAMILIARIZE HIMSELF WITH THE SOILSCONDITIONS AT THE SITE. IF ANY CONDITIONS DIFFER FROM THIS REPORTOR IF THERE IS A CONFLICT BETWEEN THE REPORT,THE CONTRACT DOCUMENTSTHE CONTRACTOR SHALL NOTIFY THE ARCHITECT AND ENGINEER FOR ACLARIFICATION. PRIOR TO BIDDING THE PROJECT, IF THE CONTRACTORDISCOVERS A CONFILICT BETWEEN THE EXISTING SITE CONDITIONS AND THEREPORT.DURING CONSTRUCTION THE CONTRACTOR SHALL NOTIFY THE ARCHITECTAND ENGINEER FOR ADDITIONAL INSTRUCTIONS PRIOR TO CONTINUATION OFCONSTRUCTION.
THE USE OF REPRODUCTIONS OF STRUCTURAL CONSTRUCTION DOCUMENTS INPLACE OF PREPARATION OF SHOP DRAWINGS IS NOT RECOMMENDED BY THISOFFICE. INDEPENDENT PREPARATION OF SHOP DRAWINGS PROVIDES ANADDITIONAL CHECK OF ACCURACY, FIT, AND DETAILS THAT IS BENEFICIALTO THE CONSTRUCTION PROCESS. BY USE OF REPRODUCTIONS OF THECONTRACT DOCUMENTS FOR SHOP DRAWINGS, THE CONTRACTOR SIGNIFIES HISACCEPTANCE OF ALL RESPONSIBILITY THAT INFORMATION ON THEREPRODUCED DRAWINGS IS CORRECT--AS IF THE DRAWINGS WERE PREPAREDBY THE CONTRACTOR. ADDITIONALLY, THE CONTRACTOR SHALL BE
OBLIGATED FOR ANY JOB EXPENSE AND LIABILITY TO THE ENGINEER AND/ORARCHITECT THAT MAY OCCUR DUE TO ANY ERRORS OR OMISSIONS ONREPRODUCTIONS OF STRUCTURAL DRAWINGS.
REPRODUCTIONS USED AS SHOP DRAWINGS SHALL HAVE TITLES AND SEALSREMOVED. ELECTRONIC FORMAT OF CADD FILES WILL NOT BE FURNISHED.
DESIGN LOADS:
ROOF LIVE LOAD............... 20 PSF (ROOF PITCH LESS THAN
4:12)
16 PSF (ROOF PITCH 4:12 TO
12:12)
12 PSF (ROOF PITCH 12:12 AND GREATER)
WIND LOAD.................... PER SECTION 1609 OF THE INTERNATIONAL BUILDING CODE,
110 M.P.H. BASIC WIND SPEED AND
1.15 IMPORTANCE FACTOR.
DescriptionDateNo.
1001 Fannin Street, Suite 300 | Houston, TX 77002 USAPhone 713.622.1180 | Fax 713.622.7021
www.morris-hz.com
INTERIM REVIEW DOCUMENTS
Interim review documents are incomplete and not to be used forregulatory approval, permit, or construction.
ALDINE INDEPENDENT SCHOOL DISTRICTCLIENT
MORRISARCHITECT
Project Team WONG AND ASSOCIATESLANDSCAPE ARCHITECTBROOKS AND SPARKSCIVIL ENGINEER
ISSUE FOR OWNER REVIEW1.31.201401
SCHMITZ/LAMB ENGINEERS, INCSTRUCTURAL ENGINEER
JSE CONSULTING ENGINEERSMEP ENGINEERFCA DESIGN, INCFOOD SERVICE CONSULTANTS
DescriptionDateNo.
ISSUE FOR COMPETITIVE SEALED PROPOSALS3.21.201402
©
©
A
A
A
A
E
H
E
EHI
F
AA
A
AA
A
AA
AA
AA
AAA
42"
A
A
A
A
A
A
A
A
A
A
A
A
E
A
AA
E
1/S
4-1
2/S
4-1
6/S4-1
12/S4-1
3/S4-1
4/S4-1
7/S4-1
12/S
4-1
8/S
4-1
6/S
4-1
9/S4-113/S4-2
9/S4-1
13/S
4-1
S/M
13/S4-114/S4-1
2A/S4-1
9/S4-1
7/S
4-18/S4-1
TYP
7/S4-1
7/S4-1
8/S
4-1
13/S4-2
A
A
A
A
72"
42"42"
42"
42"
42"
42"
42"
42"
42"
42"
42
48"42"48"42"
42"
48"42"
42"
48"
42"
42"
30"
42"
42"
42"36"
42"
42"48"42''
30"
48"
42"
30"
30"
30"
-2 1/2"
SEE SHT. S1-2 FORCOL. AND FTG. SIZES
1A/S4-1
A
2/S4-1
1/S4-1-9"
-9"
-2-1/2"
-2-1/2"
-2 1/2"
24/S4-1
A
48"30"
30"
42"
48"
42"
42"30"
30"
42"
48"
42"
48"30"
48"48"66"42"42"
30"
48"
42"
48"
30"
48"
30"
42"42"
48"
48"
42"
42"
42"48"
42"
54"
42"
42" 42"
30"
36"
48" 48"
48" 42" 42"
42"
42"
42"
48"
48"
42"
48"
48"
48"
42"48"
48"
48"
48"
54"
48"
66"42"
48"48"48"
42"
48"
42"
42"
48"
42"
42"
48"
42"
72"48"48"
72"72"
23'-11 3/4"
TYP
9/S4-1
TYP
48" 48"
54"
54"
54"
54"
36"
36"
36"
36"
1'-3 "
10"
-9"
13'-0"
E
8/S
4-1
36"
36"
48"
48"
66"
DescriptionDateNo.
1001 Fannin Street, Suite 300 | Houston, TX 77002 USAPhone 713.622.1180 | Fax 713.622.7021
www.morris-hz.com
INTERIM REVIEW DOCUMENTS
Interim review documents are incomplete and not to be used forregulatory approval, permit, or construction.
ALDINE INDEPENDENT SCHOOL DISTRICTCLIENT
MORRISARCHITECT
Project Team WONG AND ASSOCIATESLANDSCAPE ARCHITECTBROOKS AND SPARKSCIVIL ENGINEER
ISSUE FOR OWNER REVIEW1.31.201401
SCHMITZ/LAMB ENGINEERS, INCSTRUCTURAL ENGINEER
JSE CONSULTING ENGINEERSMEP ENGINEERFCA DESIGN, INCFOOD SERVICE CONSULTANTS
DescriptionDateNo.
ISSUE FOR COMPETITIVE SEALED PROPOSALS3.21.201402
©
©
A
A
66"42"
30"
48"
54" 54"
48"
72"
48"48"
66"54"
30"
42"
48"
42"48"
42"
42"
42"66"54"
42"54"
54"48"
30"
30"42"
54"
30"
54"
78"30"
42"
54"66"
30"
54"
72"
54"
72"
72"30"30"
42"
54"
42" 42"
42"
48"
30"
42" 48" 42" 48" 42" 48" 42" 48" 42"
42" 42"
42" 42"
48" 48"
42"
48"
42" 54"
30"
42"
48"
30"
42"
48"
48"
42"
30"
30"
42"
42"
42"
54"
54"
60"
30"
36"36"
48" 48"
1/S
4-2
42" 48" 48"
36"
36"
60"
36"
54" 42"
54"
48"
54"
54"
54"
48"
42"
66"
72"
54"
1'-3"
6"
33'-7"
30'-5 1/2"
30'-5 1/2"
32'-11 1/2"
10"
31'-4 1/2"
158'-7"
16'-6 1/2"
9" 13'-0 1/2" 9 1/2"
16'-5"
10"
28'-5 1
/2"
28'-6 1
/2"
13'-11 3/4" 16'-5 3/4"
6'-6" 10'-7 3/4"
1'-11"
7'-9"
7'-2 1/4"
33'-8"
7'-0"
14'-6"
9'-11"
6'-2"
10'-4"
12'-10 1
/2"
14'-7" 24'-0" 30'-0" 30'-0" 30'-0" 30'-0" 9"
12'-9 1/2" 12'-0" 15'-0" 15'-0" 15'-0" 15'-0" 15'-0" 15'-0" 15'-0" 15'-9"
17'-2 1
/2"
16'-5 1
/2"
24'-3"
54"9'-1 7
/8"
6'-0"
5'-1 1
/2"
11'-11 1
/2"
10"
10'-0"
13'-3"
1'-0 1
/2"
30"48"
8'-8 1
/2"
8'-8 1
/2"
6/S
4-1
12/S
4-1
8/S
4-1
42"
15'-6"15'-5"
30'-11"
DescriptionDateNo.
1001 Fannin Street, Suite 300 | Houston, TX 77002 USAPhone 713.622.1180 | Fax 713.622.7021
www.morris-hz.com
INTERIM REVIEW DOCUMENTS
Interim review documents are incomplete and not to be used forregulatory approval, permit, or construction.
ALDINE INDEPENDENT SCHOOL DISTRICTCLIENT
MORRISARCHITECT
Project Team WONG AND ASSOCIATESLANDSCAPE ARCHITECTBROOKS AND SPARKSCIVIL ENGINEER
ISSUE FOR OWNER REVIEW1.31.201401
SCHMITZ/LAMB ENGINEERS, INCSTRUCTURAL ENGINEER
JSE CONSULTING ENGINEERSMEP ENGINEERFCA DESIGN, INCFOOD SERVICE CONSULTANTS
DescriptionDateNo.
ISSUE FOR COMPETITIVE SEALED PROPOSALS3.21.201402
©
©
A.1CD.7E.9
K.8
10.6
10.2
9.8
9.2
9.3
7.6
7.3
6.8
6.6
6.2
4.8
4
2.5
GHK JLMN
1
K.7
M.9
RD
RD
8
5
RD
RDRD
RD
RD
RD
RD
RD
18
/S6
-1
14
A/S
6-1
7/S
6-1
19
A/S
6-1
3 E
Q S
PA
3'-6
"
7/S6-1
14/S6-1
6"
2" E
J
4"
2" EJ
2" EJ
4"
14/S6-1
F
3'-3"
W1
6x2
6
4'-0" 4'-0" 4'-0"4'-0"
AD.3 B.8E A.7
9
11
10
8
7
6
5
4
3
2
1
B A.5
A
15'-6"7'-6"7'-5"
W1
6x2
6
W1
6x2
6
J G
DescriptionDateNo.
1001 Fannin Street, Suite 300 | Houston, TX 77002 USAPhone 713.622.1180 | Fax 713.622.7021
www.morris-hz.com
INTERIM REVIEW DOCUMENTS
Interim review documents are incomplete and not to be used forregulatory approval, permit, or construction.
ALDINE INDEPENDENT SCHOOL DISTRICTCLIENT
MORRISARCHITECT
Project Team WONG AND ASSOCIATESLANDSCAPE ARCHITECTBROOKS AND SPARKSCIVIL ENGINEER
ISSUE FOR OWNER REVIEW1.31.201401
SCHMITZ/LAMB ENGINEERS, INCSTRUCTURAL ENGINEER
JSE CONSULTING ENGINEERSMEP ENGINEERFCA DESIGN, INCFOOD SERVICE CONSULTANTS
DescriptionDateNo.
ISSUE FOR COMPETITIVE SEALED PROPOSALS3.21.201402
©
©
B
20
19
17
18
DEF
16
15
14
13
12
11
GHJK.9M.9
18.4
20
17
15.8
14
12.2
10.6
JK.8M.9
13.1
13.1
14K2
14K2
H D.3 B.8 B A.7 AE
7'-9
"
3'-1
0"
22
'-4
1/2
"
28
'-6
1/2
"
28
'-5
1/2
"
18.6
7'-0
"3
3'-7
"1
0"
16
'-9
1/2
"
30
'-7
1/2
"2
8'-4
1/2
"2
4'-3
"1
7'-2
1/2
"2
6'-8
"
8 EQ SPA
6 EQ SPA
8 E
Q S
PA
1'-3"
1'-3"K7
6"
DescriptionDateNo.
1001 Fannin Street, Suite 300 | Houston, TX 77002 USAPhone 713.622.1180 | Fax 713.622.7021
www.morris-hz.com
INTERIM REVIEW DOCUMENTS
Interim review documents are incomplete and not to be used forregulatory approval, permit, or construction.
ALDINE INDEPENDENT SCHOOL DISTRICTCLIENT
MORRISARCHITECT
Project Team WONG AND ASSOCIATESLANDSCAPE ARCHITECTBROOKS AND SPARKSCIVIL ENGINEER
ISSUE FOR OWNER REVIEW1.31.201401
SCHMITZ/LAMB ENGINEERS, INCSTRUCTURAL ENGINEER
JSE CONSULTING ENGINEERSMEP ENGINEERFCA DESIGN, INCFOOD SERVICE CONSULTANTS
DescriptionDateNo.
ISSUE FOR COMPETITIVE SEALED PROPOSALS3.21.201402
©
©
12"
1"
12"
ANCH BOLT ANCHOR BOLTS - SEE COLUMN SCHEDULE
BLDG LN BUILDING LINE. SEE ARCHITECTURAL DRAWINGS.
CL BM & FTG CENTER LINE OF GRADE BEAM AND FOOTING TO BE THE SAME AT FOOTINGS BETWEEN COLUMNS OR WHERE COLUMNS ARE NOT PRESENT.
CL COL & FTG CENTER LINE OF COLUMN AND FOOTING TO BE THE SAME AT FOOTINGS LOCATED AT COLUMNS.
CONC CVR CONCRETE COVER AROUND BASE PLATE POUR DOWN SLAB MINIMUM
3" ON ALL SIDES.
CONT KEY CONSTRUCTION KEYWAY FORMED 1 1/2" DEEP INTO CONCRETE.
DOWEL ACROSS THE JOINT WITH #3 x 3'-0" DOWEL SPACED AT
24" O.C.
EXT COL BLK OUT EXTERIOR COLUMN BLOCK OUT FOR BASE PLATE, FILL WITH CONCRETE AFTER GROUTING COLUMN.
FIN FST FLR FINISHED FIRST FLOOR SLAB. SEE ARCHITECTURAL DRAWINGS FOR ELEVATION.
FTG CAP CONCRETE FOOTING CAP. REINFORCE WITH 2 - #4 HOOPS EACH WAY.
HOOK STANDARD 90 DEGREE OR 180 DEGREE HOOK (AS SHOWN.)
INT COL BLK OUT INTERIOR COLUMN BLOCK OUT. IF A SLAB IS PLACED BEFORE THE COLUMN IS ERECTED, PROVIDE BLOCK OUT BY USING A METAL KEY JOINT FOR FORM. SEE TYPICAL DETAIL.
JNT MTL EXPANSION JOINT MATERIAL.
KEY 3 1/2 x 1 1/2 FORM CONTINUOUS 1 1/2" DEEP x 3 1/2" WIDE KEY.
MAS DWLS MASONRY DOWELS. PROVIDE DOWELS EQUAL IN SIZE AND SPACING AND AT THE SAME LOCATION AS VERTICAL MASONRY WALL REINFORCING, AS NOTED ON THE ARCHITECTURAL
DRAWINGS. DOWELS TO BE 4'-0" IN LENGTH, EXTENDING
2'-0" INTO CONCRETE AND 2'-0" INTO MASONRY WALL AND CENTERED ON MASONRY WALL.
MAS REINF CONTINUOUS MASONRY REINFORCING. LAP BARS 48 TIMES BAR DIAMETERS. FILL ALL REINFORCED CELLS, BOND BEAMS OR
CAVITIES WITH ASTM C476 (2,500 PSI) GROUT. EXCEPT AS NOTED ON STRUCTURAL DRAWINGS, SEE ARCHITECTURAL DRAWINGS FOR SIZE AND SPACING OF WALL REINFORCING.
MTL C J METAL CONSTRUCTION JOINT FORMED WITH A METAL KEY JOINT
WITH #4 DOWELS x 3'-0" AT 18" O.C. AT COLD JOINTS OF POUR BREAKS, REMOVE THE METAL JOINT FROM THE FIRST SIDE OF THE SLAB POUR BEFORE SECOND SIDE IS POURED. PLACE THE METAL CONSTRUCTION JOINTS AS NOTED BY TYPICAL DETAIL
AT A MAXIMUM 40'-0" O.C. EACH WAY UNLESS NOTED OTHERWISE ON THE PLAN. SUBMIT LOCATIONS TO THE ARCHITECT AND THE ENGINEER FOR REVIEW.
NOSE BAR #4 CONTINUOUS AT THE NOSE OF ALL STAIR TREADS WITH #3 DOWELS AS SHOWN AT 15" O.C.
OPNG THRU BEAM OPENING THROUGH BEAM FOR PIPING. SEE ARCHITECTURAL OR MECHANICAL DRAWINGS FOR SIZE AND LOCATION. PREFERABLY PLACE THE OPENING SO THAT A CONTINUOUS BEAM REINFORCING IS NOT CUT. IF IT IS NECESSARY THAT ANY CONTINUOUS BEAM REINFORCING BE CUT, THEN CONSULT THE STRUCTURAL ENGINEER FOR REDESIGN. FOR PIPES EMBEDDED IN BEAM, WRAP
WITH 1/2" SPONGE RUBBER.
PVMT PAVEMENT. SEE ARCHITECTURAL DRAWINGS FOR DETAILS AND REINFORCING.
PVMT DWLS 3/4" ROUND x 18", SMOOTH DOWELS WITH AN EXPANSION CAP TO
THE PAVEMENT AT 15" O.C.
SCHD COL & B PLT SCHEDULED COLUMN AND BASE PLATE ON 1 1/2" NON-SHRINK GROUT WITH SCHEDULED ANCHOR BOLTS. ANCHOR BOLTS MAY NOT BE SHOWN FOR CLARITY.
SCHD FTG REINF SCHEDULED FOOTING REINFORCING. EXTEND THE VERTICAL
REINFORCING 1'-9" INTO THE GRADE BEAM OR CONCRETE HAUNCH.
SCHD FTG SIZE SCHEDULED FOOTING SIZE. SEE PLAN FOR SIZES.
SEL COMP FILL SELECT COMPACTED FILL UNDER STRUCTURE. SEE SPECIFICATIONS AND SEE SOILS REPORT.
SHAFT DIAM SCHEDULED SHAFT DIAMETER.
TO APPR SOIL BRG TO APPROVED SOIL BEARING AS NOTED. ANY REFERENCES TO
EXISTING GRADE ARE TO NATURAL (PRIOR TO SITE FILL) GRADE. SEE SOILS REPORT FOR OTHER INFORMATION.
TURN DWN REINF TYPICAL TURN DOWN REINFORCING 2-#4 CONTINUOUS WITH #3
TIES AT 15" O.C. 1'-3" LONG. BEND AT THE CENTER AS
SHOWN. DOWEL CONTINUOUS 2-#4 TO BEAMS OR WALLS AT ENDS
WITH 2-#4 DOWELS.
TYP EXT G B REINF TYPICAL EXTERIOR GRADE BEAM REINFORCING 2-#6 CONTINUOUS TOP AND BOTTOM. SEE TYPICAL GRADE BEAM DETAIL FOR BAR SPLICE. SEE THE PLAN FOR ADDED REINFORCING. FOR ADDED REINFORCING NOTED ON PLAN, ADD THE TOP BARS CENTERED OVER FOOTINGS AND THE BOTTOM BARS CENTERED BETWEEN FOOTINGS.
TYPICAL STIRRUPS TO BE NO. 3 CLOSED TIES SPACED AS SHOWN ON TYPICAL GRADE BEAM DETAIL. SEE PLAN NOTES OR DETAILS FOR OTHER STIRRUP SPACING THAT TAKES PRECEDENCE OVER TYPICAL STIRRUPS.
TYP INT G B REINF TYPICAL INTERIOR GRADE BEAM REINFORCING 2-#6 CONTINUOUS TOP AND BOTTOM. SEE TYPICAL GRADE BEAM DETAIL FOR BAR SPLICE. SEE THE PLAN FOR ADDED REINFORCING. FOR ADDED REINFORCING NOTED ON PLAN, ADD THE TOP BARS CENTERED OVER THE FOOTINGS AND THE BOTTOM BARS CENTERED BETWEEN THE FOOTINGS.
TYPICAL STIRRUPS TO BE NO. 3 CLOSED TIES SPACED AS SHOWN ON TYPICAL GRADE BEAM DETAIL. SEE PLAN NOTES OR DETAILS FOR OTHER STIRRUP SPACING THAT TAKES PRECEDENCE OVER TYPICAL STIRRUPS.
TYP FTG TYPICAL FOOTING. SEE TYPICAL FOOTING DETAIL AND SCHEDULE.
TYP SLB DWL TYPICAL SLAB DOWEL #3 AT 24" O.C. 3'-0" LONG. BEND AT THE CENTER AS SHOWN.
TYP SLB REINF TYPICAL SLAB REINFORCING. SEE FOUNDATION PLAN.
UNDIST SOIL UNDISTURBED SOIL. PLACE THE FOOTING ON UNDISTURBED SOIL WITHOUT ANY LOOSE, UNCOMPACTED SOIL, FOREIGN DEBRIS, OR STANDING WATER.
VAP BAR VAPOR BARRIER. SEE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS.
VERIFY VERIFY DIMENSIONS OR DETAIL WITH THE MANUFACTURER'S DRAWINGS.
WDN BM WIDEN GRADE BEAM AT COLUMNS (INCLUDING CORNER COLUMNS)
AND REINFORCE WITH 2 - #4 HORIZONTAL HOOPS TIED TO THE GRADE BEAM REINFORCING.
WLK DWLS SIDEWALK DOWELS. #3 x 2'-0" DOWELS TO SIDEWALK SLAB AT
15" O.C.
WLK SIDEWALK. SEE ARCHITECTURAL DRAWINGS FOR DETAILS AND REINFORCING.
WS CONTINUOUS WATER STOP. TO BE SYNKOFLEX UNLESS OTHERWISE NOTED.
CART FORM CARDBOARD CARTON VOID FORMS THAT ARE PLACED 1/2" MINIMUM AND 1" MAXIMUM CLEAR FROM SIDES OF GRADE BEAMS. STAKE CARTON FORM TO GRADE BY DRIVING #3 x 2'-0" DOWEL THROUGH TOP OF FORM AT 1'-0" FROM ENDS (OR JOINTS) AND AT MAXIMUM OF 10'-0" O.C. CARTON FORM TO BE DISCONTINUOUS OVER FOOTINGS.
DescriptionDateNo.
1001 Fannin Street, Suite 300 | Houston, TX 77002 USAPhone 713.622.1180 | Fax 713.622.7021
www.morris-hz.com
INTERIM REVIEW DOCUMENTS
Interim review documents are incomplete and not to be used forregulatory approval, permit, or construction.
ALDINE INDEPENDENT SCHOOL DISTRICTCLIENT
MORRISARCHITECT
Project Team WONG AND ASSOCIATESLANDSCAPE ARCHITECTBROOKS AND SPARKSCIVIL ENGINEER
ISSUE FOR OWNER REVIEW1.31.201401
SCHMITZ/LAMB ENGINEERS, INCSTRUCTURAL ENGINEER
JSE CONSULTING ENGINEERSMEP ENGINEERFCA DESIGN, INCFOOD SERVICE CONSULTANTS
DescriptionDateNo.
ISSUE FOR COMPETITIVE SEALED PROPOSALS3.21.201402
©
©
10
25TYPICAL FOOTING DETAIL
9
6" MIN
8
SEE
PLA
N/A
RCH
2 43
1'6
"
1
14TYPICAL SLAB DROP DETAIL
NO SCALEBEAMS & WALLS
EQEQ
PLAN VIEW
CONST JOINT LOCATION CRITERIA:
TYPICAL CORNER BAR (PLAN DETAIL)
TYPICAL SPANS
12
CANTILEVER
TO BE USED IF SLAB IS POURED PRIOR TO STEEL ERECTION
TYPICAL INTERIOR COLUMN BLOCKOUT
EQUAL EQUAL
SEE PLANS FOR ADDITIONAL REINFORCEMENT NOTED
TYPICAL BAR PLACEMENT (ELEVATION VIEW)18
13
24
1-1/2"
NO SCALE
EQ
ELEVATION VIEWTYPICAL GRADE BEAM CONST JOINT22 NO SCALE
TYPICAL STIRRUP PLACEMENT (ELEVATION VIEW)SEE PLANS FOR ANY ADDITIONAL OR SPECIFIC STIRRUP SPACING
TYPICAL GRADE BEAM REINF. DETAIL 23
2'6"
3"3" 3" STD TIE SPACING
1'6"
STD TIE SPACING
11
3"
TO BE USED IF SLAB IS POURED PRIOR TO STEEL ERECTION
TYPICAL EXTERIOR COLUMN BLOCKOUT
2'0" MIN.
3" 3" 3" STD TIE SPACING
2'0" MIN.
STD TIE SPACING
16
3"
GRADE BEAM LARGER THAN 3" DIAMTYPICAL HORIZONTAL HOLE THRU ELEVATION VIEW -
2'0" MIN.2'0" MIN.
21
PLAN VIEW -
GRADE BEAM LARGER THAN 3" DIAMTYPICAL VERTICAL HOLE THRU
1'-2"
4 1/2"
2'-0"
6"
9"
1'-2"
12'-0"
2'-6"
8'-0"
6" M
IN
2'-6" M
IN
4'-0" F
OR
6'-0" &
8'-0" H
IGH
FE
NC
E
1'-0"
6"
15
4 1/2"
1'-7"
2'-0"
6"
1'-2"
10"
4" 11"
1'-3"10" 8"
1'-0"
9"
8"
7"
2"
4" 11" 8"
1'-3"
DescriptionDateNo.
1001 Fannin Street, Suite 300 | Houston, TX 77002 USAPhone 713.622.1180 | Fax 713.622.7021
www.morris-hz.com
INTERIM REVIEW DOCUMENTS
Interim review documents are incomplete and not to be used forregulatory approval, permit, or construction.
ALDINE INDEPENDENT SCHOOL DISTRICTCLIENT
MORRISARCHITECT
Project Team WONG AND ASSOCIATESLANDSCAPE ARCHITECTBROOKS AND SPARKSCIVIL ENGINEER
ISSUE FOR OWNER REVIEW1.31.201401
SCHMITZ/LAMB ENGINEERS, INCSTRUCTURAL ENGINEER
JSE CONSULTING ENGINEERSMEP ENGINEERFCA DESIGN, INCFOOD SERVICE CONSULTANTS
DescriptionDateNo.
ISSUE FOR COMPETITIVE SEALED PROPOSALS3.21.201402
©
©
21
11 12
6
1
7
2
23 24
19
8
3
9
4
6" TYP
13 14
17 18
23 24
FOR CLARITYOTHER FRAMING OMITTED
PLT 8"X6"X3/8"
7/8" DIAM HOLEFOR GUYING
DEAD LOAD IS ROOF OR FLOORWELD AFTER
3/16
3"
6"
TYPICAL AT EACH JOIST AT COLUMNS
JST
SCHD COL
IN PLACE
CONTRACTOR IS RESPONSIBLEFOR FABRICATION AND ERECTIONPROCEDURES TO COMPLY W/ ALLOSHA REQUIREMENTS
TYPICAL AT EACH JOIST AT COLUMNS
OTHER FRAMING OMITTEDFOR CLARITY
3/16
7/8" DIAM HOLEFOR GUYING
CONTRACTOR IS RESPONSIBLEFOR FABRICATION AND ERECTIONPROCEDURES TO COMPLY W/ ALLOSHA REQUIREMENTS
IN PLACE
WELD AFTERROOF OR FLOORDEAD LOAD IS
SCHD COL
3" MIN.
JST1" M
IN.
3" M
IN.
PLT 3/8" THK
9"
3 1/2"
1'-3"
1'-1"
6" TYP
6 3/8"
CLG LNCLG LN
AT 14A JOIST & DECKROTATE 90°, AND BEAMMOVE UP TO BOTTOM OF DECK
8"
4"
1'-1"
DescriptionDateNo.
1001 Fannin Street, Suite 300 | Houston, TX 77002 USAPhone 713.622.1180 | Fax 713.622.7021
www.morris-hz.com
INTERIM REVIEW DOCUMENTS
Interim review documents are incomplete and not to be used forregulatory approval, permit, or construction.
ALDINE INDEPENDENT SCHOOL DISTRICTCLIENT
MORRISARCHITECT
Project Team WONG AND ASSOCIATESLANDSCAPE ARCHITECTBROOKS AND SPARKSCIVIL ENGINEER
ISSUE FOR OWNER REVIEW1.31.201401
SCHMITZ/LAMB ENGINEERS, INCSTRUCTURAL ENGINEER
JSE CONSULTING ENGINEERSMEP ENGINEERFCA DESIGN, INCFOOD SERVICE CONSULTANTS
DescriptionDateNo.
ISSUE FOR COMPETITIVE SEALED PROPOSALS3.21.201402
©
©
INJECTION SYSTEMUSING HILTI HIT HY150EMBED 8" INTO BEAM
10" OF 1/4" WELD
6 3
/8"SEE 14/S6-2
DIAG STRAP @FACE OF STUD
L5x3x3/8"
WING PLT (1/4" THICK)
FACE OF STUD
2 - 3/4" Ø ALL THREADS
GRADE BEAMTOP OF
PLAN @ XB EMBED
LOCATE AT EXTERIORDIAG STRAP
6'-6"3'-0"
E F
20/S6-2
TS COL.
TENS L - ONE WELDEDTO WING PLT & ONE WELDEDTO DAIG STRP - USED TOPRETENSION THE DIAGSTRAP BEFORE WELDINGTHE DIAG STRP TO THEWING PLATE
DIAG STRP
LAP AS REQ'-D TO PROVIDEMIN WELD AS NOTEDON X-BRACE DIAGRAMS
AFTERTENSIONING
WING PLTSHOP WELDED TOCOLUMN
PLAN OF TOP WIND BRACE CONNECTIONBOTTOM SIMILAR WITHOUT TENS L's
X-BRACING STRAP
SECT "B"SECT "B"
3/4
"
1 1
/2"
L2x2x14 GAx3 3/8" LONGSCREW TO STUD ANDWELD TO X-BRACINGSTRAP@ 48" O.C.
3/4
"
X-BRACING STRAP
2 1/2" X 20 GA CEESTUDS CUT STUD ATSTRAP X-BRACING
6" STUD
SECT "A"WALL FINISH
SECT "A"
SE
E S
CH
ED
ULE
MARK
XB-3
XB-3C
XB-3D
XB-3F
XB-3B
XB-3E
STRAP LOCATION SEE PLAN DETAIL
DIAG STRAP SCHEDULESIZE
1/4" x 4" PL 1/2" NORTH OF GRID 13.1
1/4" x 4" PL
1/4" x 4" PL
1/4" x 4" PL
1/4" x 4" PL 2 1/8" NORTH OF GRID 9.3
3 3/4" NORTH OF GRID 4, GRID 7
1/4" x 4" PL 1 1/2" WEST OF GRID H
SEE DET. 8/S6-2
SE
E S
CH
ED
ULE
PLAN OF INTERIOR WIND BRACE
INTERIOR WIND BRACE
2 1/2" SOUTH OF GRID 13
XB-1, XB-2 1/4" x 4" PL
1/4" x 4" PLXB-1A, XB-2A 1 5/8" SOUTH OF GRID 2, GRID 5
1 5/8" NORTH OF GRID 61/4" x 4" PLXB-1B, XB-2B
XB-4, XB-5 1/4" x 4" PL SEE DET. 8/S6-2
XB-6 1/4" x 4" PL SEE DET. 8/S6-2
1" M
AX
CLE
AR
5'-
0" M
AX.
CONSULT E
NGIN
EER
IF L
ARGER
7/S6-2 OR 12/S6-27/S6-2 OR 12/S6-2
SEE DET. 8/S6-2
XB-1C, XB-2C 1/4" x 4" PL 1 5/8" EAST OF GRID F
FLG BRACE L AS NOTED BY ON PLAN(SEE PLAN FOR LOCATION)
REPEAT DETAIL ANDNOTES AT OTHERSIDE IF FLANGEBRACE L IS TO BEON BOTH SIDES OFBEAM. 1 1/2x1 1/2x1/4"
LARGER OF L OR L1
3/16
4'-1" TO 6'-0"0'-0" TO 4'-0"
2 FLG BRACE L
TYP
2 1/2x2 1/2x1/4"
LL 21
IF LENGTH EXCEEDS THOSE SHOWN IN TABLESTRUCTURAL ENGINEER SHALL BE CONTACTEDFOR DESIGN OF ANGLE
DescriptionDateNo.
1001 Fannin Street, Suite 300 | Houston, TX 77002 USAPhone 713.622.1180 | Fax 713.622.7021
www.morris-hz.com
INTERIM REVIEW DOCUMENTS
Interim review documents are incomplete and not to be used forregulatory approval, permit, or construction.
ALDINE INDEPENDENT SCHOOL DISTRICTCLIENT
MORRISARCHITECT
Project Team WONG AND ASSOCIATESLANDSCAPE ARCHITECTBROOKS AND SPARKSCIVIL ENGINEER
ISSUE FOR OWNER REVIEW1.31.201401
SCHMITZ/LAMB ENGINEERS, INCSTRUCTURAL ENGINEER
JSE CONSULTING ENGINEERSMEP ENGINEERFCA DESIGN, INCFOOD SERVICE CONSULTANTS
DescriptionDateNo.
ISSUE FOR COMPETITIVE SEALED PROPOSALS3.21.201402
©
©
21 22 23 24 25
2019181716
1514131211
109876
54321
SE
E P
LAN
5" L
H J
OIS
T
BOND BM
SCHD COL
BRACEVA
RIE
S 7"
TO
13"
EL 24'-7"
VA
RIE
S 4
" TO
10
"
WD BLK
SCHD COL
WD BLK
FIB JNTRF DK
BLDG LN
2"
PC W18x35
SEE 2/S6-2 FOR SLIP CONN
8"
4"
CONT L(5x3x1/4 LLV) W/ 3/8"ØLAG SCREWS @ 24"o.c.
SEE
PLAN
3 1/
2"
9"
7"
MAS ANCH
MAS DWLANCH
BENT PLT 4" (H) xAS REQ'D (V) x1/4" x0'-4" @36" O.C.
CONT L (4 x3 x1/4 LLV)
RF DK
FIB JNT
SCHD COL
WD BLK
FIB JNTRF DK
BLDG LN
2"
PC W18x35
4"
CONT L(5x3x1/4 LLV) W/ 3/8"ØLAG SCREWS @ 24"o.c.
SEE
PLAN
3 1/
2"
9"
7"
SCHD COL
1'-3"
1'-1
"
PLAN VIEW @ ELEV. 14'-0" ±
BEAM TOCANTILEVER OVERSEAT
2" E.J.
W14X43 SEATBEAM WELDED TOCOL
BEAM TOCANTILEVER OVERSEAT
2/S6-3 OH
2" E
J
PLAN VIEW @ ELEV. 14'-0" ±
BEAM TOCANTILEVER OVERSEAT
W14X43 SEATBEAM WELDED TOCOL
BEAM TOCANTILEVER OVERSEAT
2" E.J.
OUTLK L WELDED TOBEAM AT 48" O.C. & 6"FROM ENDS TOSUPPORT EDGE ANGLE
1'-1
"
1'-3"
7"
W14
W12
W14
W18
2/S6-3 OH
PLAN VIEW @ ELEV. 14'-0" ±
W14X43 SEATBEAM WELDED TOCOL
1'-3"
7"
W14
W12
W14
W12
W16
2" E.J.
2" E.J.
CAP PLT
SCHD COL
BRACE
RF DK
SE
E P
LAN
5"
MAS DWLANCH
BOND BM
3/4"Ø NUTS WELDEDTO BM FLANGE ATEA MAS. DWL ANCH
OUTLK L WELDED TOBEAM AT 48" O.C. & 6"FROM ENDS TOSUPPORT EDGE ANGLE
2" E.J.
7"
1'-3"
W12
W12
W16
DescriptionDateNo.
1001 Fannin Street, Suite 300 | Houston, TX 77002 USAPhone 713.622.1180 | Fax 713.622.7021
www.morris-hz.com
INTERIM REVIEW DOCUMENTS
Interim review documents are incomplete and not to be used forregulatory approval, permit, or construction.
ALDINE INDEPENDENT SCHOOL DISTRICTCLIENT
MORRISARCHITECT
Project Team WONG AND ASSOCIATESLANDSCAPE ARCHITECTBROOKS AND SPARKSCIVIL ENGINEER
ISSUE FOR OWNER REVIEW1.31.201401
SCHMITZ/LAMB ENGINEERS, INCSTRUCTURAL ENGINEER
JSE CONSULTING ENGINEERSMEP ENGINEERFCA DESIGN, INCFOOD SERVICE CONSULTANTS
DescriptionDateNo.
ISSUE FOR COMPETITIVE SEALED PROPOSALS3.21.201402
©
©