2
NUHAS OMAN LLC P O Box 186, Postal Code 124, Rusayl Industrial Estate, Sultanate of Oman Tel : +968-24449007, 24449247, 24449249 Fax : +968 24446790 Email : [email protected] Website:www.nuhasoman.com (A Member of the Al Bahja Group) AN ISO 9001: 2008 COMPANY Fires can inflict widespread damage to life and property. The new Nuhas FRC 500 cables are designed to maintain Circuit Integrity during a fire and keep emergency systems working enabling evacuation, shutdown of critical operation, isolation of dangerous zones, etc. 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 12.1 7.41 4.61 3.08 1.83 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.0991 0.0754 0.0601 0.0470 15.4 9.45 5.88 3.93 2.33 1.47 0.927 0.668 0.494 0.342 0.247 0.197 0.16 0.128 0.0989 0.0802 0.0640 0.21 0.36 0.57 0.86 1.43 2.29 3.58 5.01 7.15 10.01 13.6 17.2 21.5 26.5 34.3 42.9 57.2 General Technical Data: Conductor CSA DC Resistance at 20°C, max AC Resistance at 90°C, approx "Short Circuit Rating for 1 sec" mm2 Ω/km Ω/km kA Installation Guide: Minimum Bending Radius 15 x O.D. Pulling Tension (pulling eye on conductor) 70 N/mm2

General Technical Data - · PDF file- HCL acid gas content as per BS EN 60754-1 (Max 0.5˝) ... 14460 4 Core Cables 5 Core Cables Conductor CSA mm Insulation Thickness, nom mm Bedding

Embed Size (px)

Citation preview

NUHAS OMAN LLCP O Box 186, Postal Code 124,

Rusayl Industrial Estate, Sultanate of OmanTel : +968-24449007, 24449247, 24449249 Fax : +968 24446790

Email : [email protected] Website:www.nuhasoman.com

(A Member of the Al Bahja Group)AN ISO 9001: 2008 COMPANY

Fires can in�ict widespread damage to life and property. The new Nuhas FRC 500 cables are designed to maintain Circuit Integrity during a �re and keep emergency systems working enabling evacuation, shutdown of critical operation, isolation of dangerous zones, etc.

1.52.546

10162535507095

120150185240300400

12.17.414.613.081.831.15

0.7270.5240.3870.2680.1930.1530.124

0.09910.07540.06010.0470

15.49.455.883.932.331.47

0.9270.6680.4940.3420.2470.1970.16

0.1280.09890.08020.0640

0.210.360.570.861.432.293.585.017.15

10.0113.617.221.526.534.342.957.2

General Technical Data:

Conductor CSA DC Resistance at 20°C, max AC Resistance at 90°C, approx

"Short Circuit Ratingfor 1 sec"

mm2 Ω/km Ω/km kA

Installation Guide:

Minimum Bending Radius 15 x O.D.

Pulling Tension (pulling eye on conductor) 70 N/mm2

FIRE RESISTANT CABLES - FRC 500

Fire resistant cables have the ability to maintain the circuit integrity under �re for a stated period of time and under de�ned condition. These are mica glass taped, armoured cables with low emission of smoke and corrosive gases when affected by �re and mainly used for �xed installations. Nuhas Oman offers these �re resistant cables under the series FRC 500.

Application: Industrial areas, buildings or similar application where maintenance of power supply during a �re is required for de�ned period of time.

Cable Characteristics: - Fire resistant to Category F2 of BS 7846 (BS 6387 Cat. CWZ, 950°C for 3 hours). BS 6387 Cat. CWZ test on cables is 'resistance to �re', 'resistance to �re with water spray' & 'resistance to �re with mechanical shock' - Flame retardant to BS EN 60332-3-24 (Cat.C) - Smoke density as per BS EN 61034-2 (Light transmittance of min 70%) - HCL acid gas content as per BS EN 60754-1 (Max 0.5%)

LPCB Product Approval: Nuhas Oman Fire Resistant Cables - FRC 500 are LPCB, UK approved (Certi�cate No. 1341a).

Construction:CU/MGT/XLPE/LSF/SWA/LSF

Operating / Short Circuit Temperature:90°C / 250°C

Voltage:U0/U (Um) : 0.6/1.0 (1.2) kV

Cable Standard:BS 7846:2015

2 Core Cables

3 Core Cables

Conductor CSA

mm

Insulation Thickness, nom

mm

Bedding Thickness, nom

mm

Armour Wire Diameter, nom

mm

Outer Sheath Thickness, nom

mm

Overall Diameter, approx

mm

Weight of cable, approx

kg/km

1.52.546

10162535507095

120150185240300400

0.60.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.0

0.80.80.80.80.80.80.81.01.01.01.21.21.21.41.41.61.6

0.90.90.90.90.9

1.251.251.61.61.62.02.02.02.52.52.52.5

1.31.41.41.41.51.51.61.71.81.92.02.12.22.42.52.62.8

13.014.515.516.518.521.024.027.530.534.539.042.547.052.558.063.069.5

320400460550710

1010135018302260292039604740569072208890

1066013060

Conductor CSA

mm

Insulation Thickness, nom

mm

Bedding Thickness, nom

mm

Armour Wire Diameter, nom

mm

Outer Sheath Thickness, nom

mm

Overall Diameter, approx

mm

Weight of cable, approx

kg/km

1.52.546

10162535507095

120150185240300400

0.60.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.0

0.80.80.80.80.80.81.01.01.01.01.21.21.41.41.41.61.6

0.90.90.90.9

1.251.251.61.61.61.62.02.02.52.52.52.52.5

1.31.41.41.41.51.61.71.81.81.92.12.22.32.42.62.72.9

13.515.016.017.520.522.524.027.029.533.037.541.546.549.055.061.065.5

330410480570850

1090154019302390313042905180660077609720

1184014460

4 Core Cables

5 Core Cables

Conductor CSA

mm

Insulation Thickness, nom

mm

Bedding Thickness, nom

mm

Armour Wire Diameter, nom

mm

Outer Sheath Thickness, nom

mm

Overall Diameter, approx

mm

Weight of cable, approx

kg/km

1.52.546

10162535507095

120150185240300400

0.60.70.70.70.70.70.90.91.01.11.11.21.41.61.71.82.0

0.80.80.80.80.80.81.01.01.01.21.21.41.41.41.61.61.8

0.90.90.9

1.251.251.251.601.61.62.02.02.52.52.52.52.53.2

1.31.41.41.51.51.61.71.81.92.12.22.32.42.62.72.93.2

14.516.017.520.022.024.027.530.032.538.542.048.552.056.563.569.579.0

380470560790

1020132019502420300042705420707083609970

125901523019840

Conductor CSA

mm

Insulation Thickness, nom

mm

Bedding Thickness, nom

mm

Armour Wire Diameter, nom

mm

Outer Sheath Thickness, nom

mm

Overall Diameter, approx

mm

Weight of cable, approx

kg/km

1.52.546

101625355070

0.60.70.70.70.70.70.90.91.01.1

0.80.80.80.80.81.01.01.01.21.2

0.90.90.9

1.251.251.601.61.62.02.0

1.41.41.51.51.61.71.81.92.02.2

15.517.519.021.023.527.532.035.040.045.5

440540650900

118017402390298040305310