Upload
neelakandan-masilamani
View
42
Download
3
Embed Size (px)
DESCRIPTION
Generator Tutorial
Citation preview
Copyright © of Alstom Grid UK Limited
1. For the system below, provide the following:
a. C.T. and V.T. ratios b. Single line connections for complete protection c. Relay ANSI numbers
140MVA132/13.8kV
140MVA13.8kV
40 Ohms
EXC
10MVA13.8/6.6kV
132kV
Copyright © of Alstom Grid UK Limited
2. Calculate the size and rating of transformer and loading resistor for
the distribution transformer earthing of the generator below.
The Generator is 75,000 kVA, 11.5kV at 60Hz having surge protective capacitors at its terminals. The distribution transformer is to have 110V secondary winding NOTE 1) The rated primary voltage of the distribution transformer should
be approximately √3 times the generator line-neutral voltage, in order to avoid excessive magnetizing inrush when an earth fault occurs.
2) Overvoltages due to field forcing are not considered. 3) Copper losses in the distribution transformer are not
considered. 4) The distribution transformer rating can be reduced by the
following factors depending on its required operational time.
0.25uF
0.25uF
0.25uF
R
0.32uF
0.32uF
0.32uF
0.06uF
0.004uF
0.06uF
0.004uF0.06uF
0.004uF
Copyright © of Alstom Grid UK Limited
1 Minute – 4.7 5 Minutes – 2.8 30 Minutes – 1.8 1 Hour – 1.6 2 Hours – 1.4 For this example a 1 minute rating has been considered. Note It is preferable to disconnect the generator from the system and remove excitation immediately upon the occurrence of a fault in order to confine the damage as much as possible. On small systems, some operators prefer to have the earth fault relay sound an alarm, giving the system operator a chance to make provision for the loss of the generator.
Copyright © of Alstom Grid UK Limited
3. If the generator shown in question 2 is Resistance earthed,
calculate the ohmic size of resistor to limit the earth fault current to 200A and the percentage of stator winding protected by an overcurrent relay in the generator neutral.
Effective primary setting of relay = 15% Current Transformer ratio = 250/1
Copyright © of Alstom Grid UK Limited
Solutions
1.
For Faults here BusBar Protection operates and initiates relay which trips generator
132kV
625/0.58
6000/20
1000/1
20/1
6000/20
6000/20
6000/20
6000/20
200/1
64A
EXC
32
50N
20/1
87G-T
87G
20/1
4646
20/1
40
U.T.
87
625/1
625/1
625/1
140MVA132/13.8kV
6000/20
13.8kV/110V
20/1REF
450/120/1
51
625/1
450/1
50N
B.B.
87
51 50i
950/0.851000/1
1000/1
51S
50N
10MVA13.8/6.6kV
Copyright © of Alstom Grid UK Limited
Relay References: 40 Field Failure 46 Negative Phase Sequence 51 IDMT O/C 51I Interlocked O/C 64A Negative Biased Earth Fault 50N Instantaneous Earth Fault 50Nref Restricted Earth Fault
87UT Unit Transformer Differential 87BB Busbar Protection 87GT Overall Differential 32 Reverse Power Protection 51S Standby Earth Fault
Generator – Transformer Overall differential Connections
Considering the fault shown above. If the infeed from the external system is very small the maximum bias will be obtained by connecting the overall differential between the generator and unit transformer C.T.s
Op
87GT
BiasBias
Copyright © of Alstom Grid UK Limited
Connections as shown above are used where infeed from the system is large in comparison with the generator contribution.
Op
87GT
Bias Bias
Copyright © of Alstom Grid UK Limited
2. The zero-sequence capacitance per phase of each circuit
component is listed below and totaled:
Generator winding 0.32 µF Generator Surge capacitor 0.25 µF Generator Leads 0.06 µF Power Transformer 0.004 µF Total 0.634 µF The capacitive reactance can be found by
fCπ21
Therefore, 610634.06021
−××××π
= 4184 Ohms
The per phase charging current is as follows :-
So, 41846620 = 1.58A
The steady state 3∅ capacitive kVA developed is
358.135.11
×× =31.5kVA
NOTE: During a phase to earth fault on a high impedance earthed system the fault current is approximately 3x steady state the capacitive charging current (i.e. 4.74A) To keep transient overvoltages to a minimum the loading resistor should also dissipate 31.5kVA i.e. equal to the charging kVA as shown below:-
Copyright © of Alstom Grid UK Limited
Choosing a transformer of 11.5kV primary and 110V secondary the open circuit secondary voltage will be 110/√3 = 63.5V The current rating of the resistor will be
5.6331500 = 496A and the
resistance 496
5.63 = 0.128 Ohms
During an earth fault the transformer dissipates:- AkV 74.4
35.11
× =31.5kVA
However, the transformer rating is a function of its rated voltage and rated current, which are 11.5kV and 4.74A respectively. Therefore:- Transformer continuous rating = AkV 74.45.11 × = 54.5kVA In this example the transformer need only be rated for 1 minute and hence it can be de-rated accordingly:- Actual transformer rating =
7.45.54 kVA = 11.6kVA
VTRANSIENT
Neutral to Earth
Faulted Phase
Resistor kW Charging kVA
(% EØ/N PEAK)
Unfaulted Phase
400
.2 .4 .6 .8 1.0 2.0
300
200
100
Copyright © of Alstom Grid UK Limited
3. The degree of the generator winding protected may be
determined as follows:
If V = normal phase-neutral voltage. R = Ohmic value of earthing resistance = Ω==
− 332006.6 kV
IenVp
IA = Primary fault setting of relay in amps. IG = Generator full load current IP = Primary fault setting of relay in percent of generator full
load current. IR = Rating of earthing resistance in percent of generator full
load current. Then percentage of winding unprotected = 100×
×V
RIA
= %5.18100
660033)25015.0(
=×××
and percentage of winding protected = 1001 ×⎟⎠
⎞⎜⎝
⎛ ×−
VRIA
= 100)1875.01( ×− = 81.25%
or using ratings in terms of generator full load current
= 100×=G
R IR
VI
= 100
5.113100075
336600
×
××
= 1003756200
×
= 5.3%
Copyright © of Alstom Grid UK Limited
And percentage of winding protected = 1001 ×−R
P
II
= 1003.53756
5.371 ×−
= 100
3.5995.01 ×−
= 1001875.01 ×− = 81.25%