GPSA Control_Valve_Sizing(1).xls

Embed Size (px)

Citation preview

  • 8/12/2019 GPSA Control_Valve_Sizing(1).xls

    1/10

    CONTROL VALVE SIZING

    (GAS AND LIQUID SERVICE)

    Reference: GPSA Engineering Databook, 11th Edition

    Gas Service (Volumetric Flow):

    Qg= Cg* ((520 / G*T)0.5

    )*P1*Sin [(3417 / C1)*((P / P1)0.5)]DEGAlternativelyCg= Qg/ ((520 / G*T)

    0.5)*P1*Sin [(3417 / C1)*((P / P1)0.5)]DEG

    Gas Service (Mass Flow):

    Wg= 1.1*Cg*((1*P1)0.5)*Sin [(3417 / C1)*((P / P1)0.5)]DEGAlternatively

    Cg= Wg/ 1.1*Cg*((1*P1)0.5)*Sin [(3417 / C1)*((P / P1)0.5)]DEGwhere

    Qg= Volumetric Gas Flow Rate, ft / hr@ 14.7 psia, 60F (SCFH)Wg= Mass Flow Rate, lb/hr.

    Cg= Gas Sizing Coefficient

    G = specific gravity of gas (air = 1.0)

    T = absolute temperature of gas at inlet, R

    P1= absolute pressure of gas at inlet of valve, psia

    C1 = Cg/Cv Ratio of Gas Sizing Coefficient to Liquid Sizing Coefficient.

    DP = required pressure drop across control valve, psi

    r1= density at valve inlet pressure & temperature, lb/ft

    Page 1 of 10

  • 8/12/2019 GPSA Control_Valve_Sizing(1).xls

    2/10

    CONTROL VALVE SIZING

    (GAS AND LIQUID SERVICE)

    Typical C1& Cgvalues for valves in gas service:

    C1 Cg1

    C1 Cg1

    1 32.7 270 31.9 528 Notes:

    1 1/2 33.0 578 32.4 10202 33.2 851 32.0 2050

    2 1/2 32.5 1600 32.0 2830

    3 32.9 2150 31.5 3970

    4 33.8 4100 33.2 6260

    6 35.3 8200 34.4 13000

    8 34.0 8300 36.6 18100

    1 31.3 363 - -

    1 1/2 28.9 1050 - -

    2 30.3 1620 - -

    3 27.9 3180 - -

    4 28.1 5010 - -

    6 28.4 8960 - -8 29.5 15100 - -

    10 27.8 26900 - -

    12 28.2 46300 - -

    2 25.2 965 - -

    2 1/2 25.2 1770 - -

    3 25.2 3120 - -

    4 25.2 6400 - -

    5 25.2 10800 - -

    6 24.5 17500 - -

    8 24.5 31100 - -

    10 24.5 48500 - -

    12 24.5 75300 - -14 24.5 89000 - -

    16 24.5 124000 - -

    Linear Flow Characteristic:

    Applications of Linear Flow Characteristic Control Valves:

    Liquid level control & for certain flow control applications requiring constant gain.

    Ball

    Butterfly

    1. At approximately 70% of valvetravel.

    2. C1& Cgvalues vary with

    percentage of valve travel.

    3. For a more detailed analysis

    of capacity of a given valve at

    other percentages of travel

    consult manufacturer's data.

    The linear flow characteristic implies that the flow rate is directly proportional to the valve travel or opening.

    This proportional relationship produces a characteristic with a constant slope so that with constant

    pressure drop (delta P), the valve gain will be the same at all flows. Valve gain is the ratio of an

    incremental change in flow rate to an incremental change in valve plug position. Gain is a function of

    valve size & configuration, system operating conditions & valve plug characteristic).

    Valve Style

    Valve

    Body

    Size,

    inches

    Flow Characteristic

    Equal Percentage Linear

    Globe

    Page 2 of 10

  • 8/12/2019 GPSA Control_Valve_Sizing(1).xls

    3/10

    CONTROL VALVE SIZING

    (GAS AND LIQUID SERVICE)

    Selection Criteria for Linear Flow Characteristic Control Valve:

    3. When 2 control valves are used in pairs as a 3-way valve.4. For compressor recycle (spill-back) applications.

    5. For compressor anti-surge control valves.

    6. For pump minimum safe continuous recirculation flow applications.

    Equal-Percentage Flow Characteristic:

    Applications of Equal-Percentage Flow Characteristic Control Valves:

    Calculation steps for specifying gas service control valves:

    1. Calculate the required Cgby using the sizing equation given above.

    In this flow characteristic, equal increments of valve travel (opening) produce equal percentage changes in

    the existing flow. The change in flow rate is always proportional to the flow rate just before the change in

    position is made for a valve plug, disc or ball position. When the valve plug, disc or ball is near its seat &

    the flow is small, the change in flow rate will be small; with a large flow, the change in flow rate will be

    large.

    These are generally used for pressure control applications. They are also used where a large percentage

    of the total system pressure drop is normally absorbed by the system itself, with only a relatively small

    percentage by the control valve. These are also recommended for applications where highly varying

    pressure conditions can be expected.

    2. Select a valve from the manufacturers catalog (see table above). The valve selected should have a Cgwhich equals or exceeds the calculated value.. The assumed C1value for the Cgcalculation must match

    the C1value for the valve selected from the catalog.

    1. When the ratio of differential pressure across the control valve at minimum flow over the differential

    pressure across the control valve at maximum flow is equal to or less than 1.5.

    2. When the differential pressure conditions across the control valve under all specified flow conditions

    are more than two-third (2/3) of the differential pressure across the control valve in the closed condition.

    7. For pressure reducing service where pressure drop is constant within +/- 15% over all specified flow

    conditions.

    Page 3 of 10

  • 8/12/2019 GPSA Control_Valve_Sizing(1).xls

    4/10

    CONTROL VALVE SIZING

    (GAS AND LIQUID SERVICE)

    Liquid Service (Volumetric Flow):

    QL= Cv* (P / G)0.5Alternatively

    Cv= QL*(G / P)0.5

    whereQL= Volumetric Liquid Flow Rate, gpmat inlet pressure & temperature

    G = specific gravity of liquid (water = 1.0 @60F)

    DP =

    DPmax= Km( P1- rc*Pv)

    where

    Km = valve recovery coefficient (see table below for values)

    rc= Critical pressure ratio = 0.96 - (0.28*(Pv/ Pc)0.5

    )

    Pv= Vapor Pressure of liquid at valve inlet temperature,psia

    Pc= Absolute thermodynamic critical pressure, psia

    Note: For flashing liquids the following equation should be used to determine the maximum allowable

    pressure drop that is effective in producing flow.

    If actual delta P is less than DPa,then the actual DP should be used in the equation above for calculating

    flow or coefficient..

    less than the maximum allowable pressure drop (DPmax)across control valve for sizing or

    actual pressure drop, psi

    Page 4 of 10

  • 8/12/2019 GPSA Control_Valve_Sizing(1).xls

    5/10

    CONTROL VALVE SIZING

    (GAS AND LIQUID SERVICE)

    Typical Km& Cvvalues for valves in liquid service:

    Km Cv1

    Km Cv1

    1 0.77 7.83 0.87 8.31 Notes:1 1/2 0.7 17.4 0.82 11.7

    2 0.72 25.4 0.81 19.9

    2 1/2 0.71 49.2 0.88 32.6

    3 0.68 66 0.89 40.4

    4 0.68 125 0.8 73.5

    6 0.73 239 0.82 100

    1 0.74 11.6 - -

    1 1/2 0.72 36.3 - -

    2 0.6 53.4 - -

    3 0.67 114 - -

    4 0.68 178 - -

    6 0.68 316 0.73 2488 0.61 512 0.72 407

    10 0.66 967 0.72 691

    12 0.6 1640 0.71 1010

    2 0.55 38.3 - -

    2 1/2 0.55 70.4 - -

    3 0.55 124 - -

    4 0.55 254 - -

    5 0.55 428 - -

    6 0.55 713 - -

    8 0.55 1270 - -

    10 0.55 1980 - -

    12 0.55 3070 - -

    14 0.55 3630 - -

    16 0.55 5070 - -

    Calculation steps for specifying liquid service control valves:

    Prepared by: Ankur Srivastava

    Chemical Engineer

    e-mail: [email protected]

    Linear- Anti-

    cavitation Trim

    Globe

    1. At approximately 70% of valve

    travel.

    2. Select a valve from the manufacturer's catalog, with a Cvequal to or greater than the calculated value.

    1. Calculate the required Cvby using the sizing equation given above. The DP used in the equation must

    be the actual valve pressure drop or DPmax, whichever is smaller.

    Ball

    Butterfly

    Disclaimer : The information and methods included within this spreadsheet are presented for "cont

    calculations. It is intended to be used by technically skilled persons at their own discretion. I do no

    suitability or accuracy of these methods.

    Valve Style

    Valve

    Body

    Size,

    inches

    Flow CharacteristicEqual Percentage-

    Standard

    Page 5 of 10

    mailto:[email protected]:[email protected]
  • 8/12/2019 GPSA Control_Valve_Sizing(1).xls

    6/10

    CONTROL VALVE SIZING

    (GAS AND LIQUID SERVICE)

    Page 6 of 10

  • 8/12/2019 GPSA Control_Valve_Sizing(1).xls

    7/10

    CONTROL VALVE SIZING

    (GAS AND LIQUID SERVICE)

    Page 7 of 10

  • 8/12/2019 GPSA Control_Valve_Sizing(1).xls

    8/10

    CONTROL VALVE SIZING

    (GAS AND LIQUID SERVICE)

    Page 8 of 10

  • 8/12/2019 GPSA Control_Valve_Sizing(1).xls

    9/10

    CONTROL VALVE SIZING

    (GAS AND LIQUID SERVICE)

    Page 9 of 10

  • 8/12/2019 GPSA Control_Valve_Sizing(1).xls

    10/10

    CONTROL VALVE SIZING

    (GAS AND LIQUID SERVICE)

    ol valve sizing"

    warrant the

    Page 10 of 10