ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLYRESERVES THE COMMON LAW COPYRIGHT ASSOCIATEDWITH THESE DRAWINGS, AND THESE DOCUMENTS MAYNOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RDPARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC,INC.
THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ANDARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL ORCOMPONENT REQUIRED FOR A COMPLETE, FULLYOPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S).
ANY CONTRACTOR RELYING ON THESE DOCUMENTSSHALL DO SO ONLY IN CONCERT WITH CURRENT CODECONSIDERATION, FIELD INVESTIGATION/VERIFICATIONAND UTILITY COORDINATION IN ORDER TO PROVIDE ACOMPREHENSIVE INSTALLATION.
PO BOX 93024Albuquerque, NM 87199
505-856-3419
INC.E N G I N E E R S
C O N S U L T I N G
Project #:
Date:
PROJECT ARCHITECT:
By:
File:Sheet of
Plot Date:
AEC-E-1.0-POWER RISER.DWG
2/12/2015 4:16:17 PM
Housing and Economic Rural OpportunityPase Del Oro ApartmentsLas Cruces, New Mexico
BOB HALL, AIA
IDA-14-01-P
DECEMBER 22, 2014
AEC
101/30/15 REVISION #1.
PANEL
1-PHASE
125A MCB
"A1-1"
120/240V
PANEL
1-PHASE
125A MCB
"A1-2"
120/240V
PANEL
1-PHASE
125A MCB
"A1-3"
120/240V
PANEL
1-PHASE
125A MCB
"A1-4"
120/240V
PANEL
"MA1"
400A MCB
120/240V
1-PHASE
UTILITY-OWNED
SERVICE TRANSFORMERS
ST-1, ST-2, AND ST-3
AC
AC
PV
INV.
PANEL
1-PHASE
125A MCB
"A2-1"
120/240V
PANEL
1-PHASE
125A MCB
"A2-2"
120/240V
PANEL
1-PHASE
125A MCB
"A2-3"
120/240V
PANEL
1-PHASE
125A MCB
"A2-4"
120/240V
PANEL
"MA2"
400A MCB
120/240V
1-PHASE
AC
DISC.
SW.
AC
PV
INV.
PANEL
1-PHASE
125A MCB
"A3-1"
120/240V
PANEL
1-PHASE
125A MCB
"A3-2"
120/240V
PANEL
1-PHASE
125A MCB
"A3-3"
120/240V
PANEL
1-PHASE
125A MCB
"A3-4"
120/240V
PANEL
"MA3"
400A MCB
120/240V
1-PHASE
AC
AC
PV
INV.
1 UTILITY-OWNED SERVICE TRANSFORMER WITH 120/240V, 1-PHASE SECONDARY.
REFER TO ELECTRICAL SITE PLAN FOR LOCATION.
2 PRIMARY ELECTRICAL FEEDER TO UTILITY SERVICE POINT (BY EL PASO
ELECTRIC (EPE), THE ELECTRIC UTILITY COMPANY).
3 PHOTOVOLTAIC (PV) EQUIPMENT PROVIDED AND INSTALLED BY OTHERS UNDER
SEPARATE PERMIT AS PART OF THIS PROJECT. REFER TO PV-100 DRAWING BY
AFFORDABLE SOLAR INCLUDED FOR REFERENCE. PROVIDE ONE 3/4" CONDUIT
STUB-UP FROM METER / PANEL LOCATION TO ROOF FOR PV SYSTEM,
COORDINATE EXACT LOCATION WITH PV SYSTEM INSTALLER.
4 METERING EQUIPMENT PER EPE REQUIREMENTS. VERIFY ALL METERING AND
SERVICE REQUIREMENTS WITH EPE BLUE BOOK AND EPE REPRESENTATIVE
PRIOR TO BEGINNING ANY ELECTRICAL WORK. CONTACT JERRY ORTEGA, PH.
(575) 523-3614.
5 LANDLORD METERING UNIT TO READ INDIVIDUAL APARTMENT PANEL USAGE.
INSTALL REQUIRED CT'S IN MAIN PANEL AND MAKE ALL FINAL CONNECTIONS
PER MANUFACTURER'S RECOMMENDATIONS. LEVITON VERIFYE MINI-METER
MULTIPLE UNIT (MMU) WITH MODHOPPER MODBUS/PULSE TRANSCEIVER, PULSE
MODULE, EMB HUB, CT'S AND ALL FINAL CONNECTIONS REQUIRED FOR A
COMPLETELY OPERATIONAL SYSTEM.
6 ONE #1/0 BSD COPPER SERVICE GROUND IN 1/2" CONDUIT. REFER TO SERVICE
GROUNDING DETAIL.
7 400A SERVICE FEEDER. 3 #500KCMIL CU IN 3" CONDUIT.
8 125A FEEDER. 3 #1 CU AND 1 #6 CU E.GR. IN 1.5" CONDUIT.
9 300A SERVICE FEEDER. 3 #350KCMIL CU IN 2.5" CONDUIT.
10 TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) DEVICE. LEVITON
#52120-CM2. CONNECT TO PANEL PER MANUFACTURER'S RECOMMENDATIONS.
ELECTRICAL KEYED NOTES:
1
2
3
REC
METER
4
6
3 3
REC
METER
4
6
4
6
REC
METER
2
UTILITY-OWNED
SERVICE
TRANSFORMER ST-4
1
PANEL
"MM"
300A MCB
120/240V
1-PHASE
AC
AC
PV
INV.
ON BUILDING "M" ROOF
3
REC
METER
4
POWER RISER DIAGRAM - BUILDINGS A1, A2, & A3
SCALE: NONE
PANEL
1-PHASE
125A MCB
"B-1"
120/240V
PANEL
1-PHASE
125A MCB
"B-2"
120/240V
PANEL
"MB"
300A MCB
120/240V
1-PHASE
AC
AC
PV
INV.
PANEL
1-PHASE
125A MCB
"C-1
120/240V
PANEL
1-PHASE
125A MCB
"C-2"
120/240V
PANEL
1-PHASE
125A MCB
"C-3"
120/240V
PANEL
"MC"
400A MCB
120/240V
1-PHASE
AC
AC
PV
INV.
PANEL
1-PHASE
125A MCB
"D-1"
120/240V
PANEL
1-PHASE
125A MCB
"D-2"
120/240V
PANEL
1-PHASE
125A MCB
"D-3"
120/240V
PANEL
1-PHASE
125A MCB
"D-4"
120/240V
PANEL
"MD"
400A MCB
120/240V
1-PHASE
AC
AC
PV
INV.
3
REC
METER
4
5
6
3 3
REC
METER
4
6
4
6
REC
METER
POWER RISER DIAGRAM - BUILDINGS B, C, & D
SCALE: NONE
PANEL
1-PHASE
125A MCB
"C-5"
120/240V
PANEL
1-PHASE
125A MCB
"C-4"
120/240V
PANEL
1-PHASE
125A MCB
"C-6"
120/240V
POWER RISER DIAGRAM - BUILDING M
SCALE: NONE
POWER RISER DIAGRAMS
E-1.0
9
9
7
7
7
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
8
6
7
7
2-METER UNIT
LEVITON #6M202-CFG
5
6-METER UNIT
LEVITON #6L206-CFG
5
4-METER UNIT
LEVITON #6M204-CFG
5
4-METER UNIT
LEVITON #6M204-CFG
5
4-METER UNIT
LEVITON #6M204-CFG
5
4-METER UNIT
LEVITON #6M204-CFG
C
I
E
X
W
M
N
E
0
A
L
O
M
É
ARC
I
N
I
E
G
A
S
18711
N
SERVICE FEEDER
NEUTRAL BUS
GROUND BUS
GROUNDING ELECTRODE CONDUCTOR SCHEDULE
A. ALL CONDUCTORS USED FOR THE GROUNDING SYSTEM SHALL BE COPPER.
B. CONNECT THE GROUNDING SYSTEM TO THE FOUR FOLLOWING COMPONENTS:
1. BUILDING STEEL.
2. METAL U.G. COLD WATER PIPE.
3. CONCRETE ENCASED REBAR OR #4 COPPER UFER.
4. 10' GROUND RODS.
C. ANY SPLICING SHALL BE VIA CAD-WELD TYPE PROCESS.
D. THE GROUNDING SYSTEM SHALL COMPLY WITH ALL REQUIREMENTS OF ARTICLE 250 OF THE 2011 NEC,
AND SHALL PROVIDE 5 OHMS OR LESS RESISTANCE TO GROUND. PROVIDE TEST REPORT VERIFYING
RESISTANCE LEVEL IS IN COMPLIANCE WITH 5 OHM MAXIMUM.
NEC 250.52(1)
COLD WATER PIPE,
BUILDING STEEL,
NEC 250.52(2)
SERVICE GROUNDING SYSTEM DIAGRAM
SCALE: NONE
SERVICE
ENTRANCE
EQUIPMENT
MAIN
DRIVEN
COPPER CLAD
5/8" X 10'
GROUND ROD
(SPACED 15' APART)
#4 UFER GROUND,
SLAB REBAR OR
NEC 250.52(3)
AS SHOWN ON GROUNDING
CONDUCTOR, MINIMUM SIZE
GROUNDING ELECTRODE
COPPER SERVICE
PANELBOARD
SERVICE GROUNDING SYSTEM GENERAL NOTES
200A
225A
400A
600A
800A
1000A
1200A
150A
100A
SERVICE
AMPACITY
METALLIC
PIPE
CONDUCTOR
BUILDING
STEEL
CONDUCTOR
#4
#2
#1/0
#2/0
#3/0
#3/0
250KCMIL
#6
#8
#4
#2
#1/0
#2/0
#3/0
#3/0
250KCMIL
#6
#8
#4
#2
#1/0
#2/0
#2/0
#3/0
#3/0
#6
#8
#4
#2
#1/0
#2/0
#2/0
#3/0
#6
#8
#3/0
G
N
ELECTRODE CONDUCTOR
SCHEDULE
NEC 250.28
MAIN BONDING JUMPER,
NEC 250.102(C)
EQUIP. BONDING JUMPER,
REBAR OR
UFER
CONDUCTOR
#4
#2
#1/0
#2/0
#2/0
#3/0
#6
#8
#3/0
GROUND
ROD
CONDUCTOR
#4
#2
#1/0
#2/0
#2/0
#3/0
#6
#8
#3/0
PHASE
BUSES
NEUTRAL
BUS
GROUND
BUS
EQUIV.
CU WIRE
SIZE
#3/0
#4/0
500
700
1000
1200
1400
#1/0
#2
MAIN
BONDING
JUMPER
EQUIPMENT
BONDING
JUMPER
INTERSYSTEM BONDING
TERMINATION (IBT),
NEC 250.94
#6 CU
2
TO ST-1
TO ST-2
TO ST-3
TO ST-4
TO ST-5
TO ST-5
UTILITY-OWNED
SERVICE TRANSFORMERS
ST-4 AND ST-5
1
TVSS TVSS
TVSS TVSS TVSS
TVSS
TVSS
10
10
10
10
10 1010
DISC.
SW.
DISC.
SW.
DISC.
SW.
DISC.
SW.
DISC.
SW.
DISC.
SW.
PV ARRAY
ON BUILDING "B" ROOF
PV ARRAY
ON BUILDING "C" ROOF
PV ARRAY
ON BUILDING "D" ROOF
PV ARRAY
ON BUILDING "A1" ROOF
PV ARRAY
ON BUILDING "A2" ROOF
PV ARRAY
ON BUILDING "A3" ROOF
PV ARRAY
A ALL PHOTOVOLTAIC (PV) SYSTEM COMPONENTS AND WIRING FOR EACH OF THE (7)
BUILDINGS SHALL BE PROVIDED AND INSTALLED BY THE PV SYSTEM
CONTRACTOR. NOTE: * PV SYSTEM CONTRACTOR IS REQUIRED TO OBTAIN
INDEPENDENT PERMIT FROM THE AHJ PRIOR TO STARTING THEIR WORK.
B THE PV SYSTEM CONTRACTOR SHALL REFER TO PV SERIES DRAWINGS FOR PV
WORK REQUIRED. THE PV SERIES DRAWINGS SHALL BE ENGINEERED AND
STAMPED BY A PROFESSIONAL PV SYSTEM DESIGN ENGINEER. COORDINATE ALL
PV WORK WITH AFFORDABLE SOLAR, PH. (505) 944-4220).
C ELECTRICAL CONTRACTOR SHALL PROVIDE A CONCEALED 3/4" CONDUIT WITH
PULL WIRE FROM THE ROOF OF EACH BUILDING TO THE LOCATION OF THE
ASSOCIATED BUILDING WALL MOUNTED PV EQUIPMENT. COORDINATE EXACT
LOCATION WITH PV SYSTEM INSTALLER.
PHOTOVOLTAIC SYSTEM GENERAL NOTES:
ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLYRESERVES THE COMMON LAW COPYRIGHT ASSOCIATEDWITH THESE DRAWINGS, AND THESE DOCUMENTS MAYNOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RDPARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC,INC.
THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ANDARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL ORCOMPONENT REQUIRED FOR A COMPLETE, FULLYOPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S).
ANY CONTRACTOR RELYING ON THESE DOCUMENTSSHALL DO SO ONLY IN CONCERT WITH CURRENT CODECONSIDERATION, FIELD INVESTIGATION/VERIFICATIONAND UTILITY COORDINATION IN ORDER TO PROVIDE ACOMPREHENSIVE INSTALLATION.
PO BOX 93024Albuquerque, NM 87199
505-856-3419
INC.E N G I N E E R S
C O N S U L T I N G
Project #:
Date:
PROJECT ARCHITECT:
By:
File:Sheet of
Plot Date:
AEC-E-2.0-SYMBOL LEGEND.DWG
2/12/2015 4:18:04 PM
Housing and Economic Rural OpportunityPase Del Oro ApartmentsLas Cruces, New Mexico
BOB HALL, AIA
IDA-14-01-P
DECEMBER 22, 2014
AEC
101/30/15 REVISION #1.
ELECTRICAL SYMBOL LEGEND
E-2.0
ABOVE FINISH FLOOR.
SPLIT-WIRED DUPLEX RECEPTACLE
PHOTOCELL.
THREE-WAY SWITCH
FOUR-WAY SWITCH
WEATHER-RESISTANT SWITCH
KEY-OPERATED SWITCH
DIMMER SWITCH, 1200W MINIMUM WATTAGE.
SINGLE-POLE WALL SWITCH. SUBSCRIPT, IF USED, DESIGNATES
AFF
DUPLEX RECEPTACLE OUTLET, 18"AFF. # INDICATES CIRCUIT.
QUADPLEX RECEPTACLE, 18" AFF TO CENTER.
GROUND FAULT CIRCUIT INTERRUPTER (GFCI) DUPLEX
CEILING JUNCTION BOX
WALL JUNCTION BOX
CONDUIT CAP/STUB-OUT.
CONDUIT TURNING DOWN.
CONDUIT TURNING UP.
FLEXIBLE CONDUIT.
HIDDEN OR BURIED.
HOME-RUN CONDUIT.
CONDUIT, NEW WORK.
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
ELECTRICAL SYMBOL LEGEND
(ALL SYMBOLS SHOWN ARE NOT NECESSARILY USED ON THE DRAWINGS)
THERMOSTAT
EXISTING CONDUIT.EX
ABOVE COUNTER.AC
OCCUPANCY SENSOR SWITCH.
CATV OUTLET
SURVEILLANCE CAMERA, PTZ = PAN, TILT, ZOOM, WEATHER-
1'X4' SURFACE MOUNTED LIGHTING FIXTURE.
SHADING AND "EM" INDICATES LIGHTING FIXTURE SUPPLIED WITH
2'X4' LAY-IN LIGHTING FIXTURE (TROFFER), TYPE INDICATED BY
RECESSED DOWNLIGHT FIXTURE.
A
1'X4' RECESSED (FLANGED) MOUNTED LIGHTING FIXTURE.
POLE MOUNTED AREA LIGHTING FIXTURE, SINGLE-HEAD.
2'X2' LAY-IN LIGHTING FIXTURE (TROFFER).
SURFACE MOUNTED DRUM TYPE LIGHTING FIXTURE.
WALL BRACKET LIGHTING FIXTURE.
EXTERIOR WALL SCONCE LIGHTING FIXTURE.
BOLLARD LIGHTING FIXTURE.
PENDANT HUNG CYLINDER-TYPE LIGHTING FIXTURE.
LINEAR PENDANT MOUNTED LIGHTING FIXTURE, LENGTH AS
EXTERIOR WALLPACK LIGHTING FIXTURE.
STEP LIGHT LIGHTING FIXTURE.
CONDUCTOR TICK MARKS: GROUND, NEUTRAL, PHASE,
RECEPTACLE WITH WEATHER-RESISTANT COVER.
CEILING MOUNTED DUPLEX RECEPTACLE.
SPECIAL RECEPTACLE, TYPE AS NOTED.
FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE.
CONTROL OF PARTICULAR LIGHTING FIXTURES.
MECHANICALLY WOUND TWIST-TIMER SWITCH OR ELECTRONIC
TIME SWITCH.
THERMAL SWITCH.
EVAPORATIVE COOLER SWITCH.
TWIN-EYE EMERGENCY LIGHTING UNIT WITH BATTERY BACK-UP.
EXIT SIGN, SINGLE FACE INDICATED BY SHADED QUADRANT.
EXIT SIGN, DOUBLE-FACED, DIRECTIONAL ARROWS INDICATED.
STANCHION MOUNTED SIGN-LIGHTER FIXTURE.
EXTERIOR WALL MOUNTED EMERGENCY LIGHTING UNIT WITH
MOTOR, HP SIZE AS INDICATED, "F" = FRACTIONAL HORSEPOWER.
FLUSH MOUNTED PANELBOARD, REFER TO ASSOCIATED
FUSED DISCONNECT SWITCH, NEMA 3R IF OUTSIDE, AMPS/
SURFACE MOUNTED PANELBOARD, REFER TO ASSOCIATED
POWER TRANSFORMER.
60/3/45
NON-FUSED DISCONNECT SWITCH, NEMA 3R IF OUTSIDE,60/3
POLES / FUSE SIZE INDICATED.
AMPS / POLES INDICATED.
GROUND FAULT CIRCUIT INTERRUPTER.GFCI
COMBINATION VOICE/DATA OUTLET, UP 18" U.N.O. EXTEND
U.N.O.UNLESS NOTED OTHERWISE.
FLUORESCENT STRIP FIXTURE.
PTZ
OC
S
EC
S
T
S
T
S
D
S
K
S
WR
S
4
S
3
S
aS
#
SWITCHED, AND ISOLATED GROUND RESPECTIVELY.
E.GR.EQUIPMENT GROUND.
WEATHER-RESITANT.WR
AE
FLUSH IN-GROUND LIGHTING FIXTURE.
T
EPRIMARY ELECTRICAL UNDERGROUND FEEDER.
UG
EOVERHEAD PRIMARY ELECTRICAL LINE.
OH
STA
DOORBELL SYSTEM PUSHBUTTON.
DUPLEX RECEPTACLE WITH BUILT-IN USB CHARGER OUTLET.
DOORBELL/CHIME.
MECHANICAL UNIT TAG (EXAMPLE: BOILER B-2 INDICATED),
B-2
PADDLE FAN, WITH OR WITHOUT LIGHT PER LUMINAIRE
SEE MECHANICAL EQUIPMENT SCHEDULE.
RESISTANT AT EXTERIOR; STA = STATIONARY.
COMBO EXIT SIGN/EMERGENCY TWIN-EYE UNIT.
DOOR OPERATOR PUSH-PAD UNIT (ADA COMPLIANT).
FLUSH CEILING VOICE/DATA OUTLET. EXTEND 3/4"C. WITH
PULL STRING TO CEILING.
3/4" CONDUIT WITH PULL STRING TO ACCESSIBLE CEILING.
J-BOX WITH FLEXIBLE CONDUIT CONNECTION TO LAY-IN
TRACK MOUNTED LIGHTING ASSEMBLY, ONE FIXTURE HEAD
PANEL SCHEDULE.
PANEL SCHEDULE.
LETTER.
EMERGENCY BATTERY PACK.
INDICATED.
OWNER FURNISHED, CONTRACTOR INSTALLED.O.F.C.I.
BATTERY BACK-UP.
INDICATED.
SCHEDULE.
LIGHTING FIXTURES.
B
2
T
J
J
T
V
T
BARE SOFT-DRAWN.BSD
J
FLUSH FLOOR VOICE/DATA OUTLET. EXTEND 3/4"C. WITH
PULL STRING TO CEILING.
CONTROL / LOW VOLTAGE TRANSFORMER.T
PROJECT GENERAL ELECTRICAL NOTES:
A ALL DEVICES SHALL BE IVORY WITH COMPATIBLE PLASTIC PLATES, INSTALLED
FOR ADA COMPLIANCE U.N.O.
B ALL TELEPHONE, DATA, SECURITY, CATV, SOUND AND INTERCOM LOW VOLTAGE
SYSTEM ARE PROVIDED BY OTHERS. NOTE: * LOW VOLTAGE CONTRACTORS
ARE REQUIRED TO OBTAIN INDEPENDENT PERMITS FROM THE AHJ PRIOR TO
STARTING THEIR WORK
C UTILIZE "DEEP" 4-SQUARES WHERE REQUIRED TO COMPLY WITH NEC 314.6
EXTRA CONSIDERATION SHALL BE GIVEN TO BOXES SUPPLYING HOME-RUNS
D CONFIRM EXACT ROUGH-IN DIMENSIONS WITH ARCHITECTURAL DRAWINGS,
KITCHEN EQUIPMENT, FURNITURE PLAN (IF AVAILABLE) AND SPECIALTY
EQUIPMENT
E GENERAL CONTRACTOR TO SAW-CUT/REMOVE/PATCH EXISTING
ARCHITECTURAL SURFACES INCLUDING BUT NOT LIMITED TO SLABS, WALLS AND
ROOFS.
F SHARED NEUTRALS ARE NOT PERMISSIBLE U.N.O.
G CONDUCTOR TICK MARKS ARE SHOWN FOR CONVENIENCE ONLY, THE
CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL CONDUCTORS WHETHER
SHOWN OR NOT INCLUDING "TRAVELERS" AS NECESSARY FOR COMPLETELY
OPERATIONAL SYSTEMS.
H PROVIDE GFCI-TYPE RECEPTACLES WITHIN 6' OF ANY SINK, IN KITCHENS,
BATHROOMS, LAUNDRY AREAS AND OUTDOORS PER NEC 210.8.
I PROVIDE AFCI PROTECTION IN DWELLING UNITS PER NEC 210.12.
J ELECTRICAL DEVICE INSTALLATION SHALL COMPLY WITH ACCESSIBILITY CODES
ADOPTED FOR NEW MEXICO. SPECIFICALLY; MOUNT APPLICABLE SWITCHES,
RECEPTACLES, AND ENVIRONMENTAL CONTROLS SO THAT THEY ARE MOUNTED
WITH THE TOP OF THE DEVICE NO HIGHER THAN 48 INCHES ABOVE FINISHED
FLOOR (AFF) AND THE BOTTOM OF THE DEVICE NO LOWER THAN 15 INCHES AFF.
ELECTRICAL DEVICES ABOVE COUNTERTOP (AC) OR OTHER OBSTRUCTION
SHOULD COMPLY WITH ICC/ANSI 117.1-2003 SECTION 308.
K EXTERIOR LIGHTING SHALL COMPLY WITH THE LAS CRUCES OUTDOOR LIGHTING
ORDINANCE AND THE NEW MEXICO NIGHT SKY PROTECTION ACT.
L ALL ELECTRICAL WORK SHALL COMPLY WITH THE 2011 NEC, 2011 NMEC, AND
APPLICABLE CODES AND ORDINANCES ADOPTED BY THE CITY OF LAS CRUCES.
REFERENCE WEB SITE:
TOTAL CONNECTED LOAD ON "MA1" (SAME FOR "MA2") 110.7 KVA
CODE DEMAND LOAD PER NEC 220.84: MULTIFAMILY DWELLING - (4) UNITS:
17.57 KVA X 4 X .45 DEMAND FACTOR = 31.63 KVA
DESIGN LOAD = DEMAND LOAD + FUTURE 20%: 38.0 KVA (158A).
RECOMMEND SERVICE TRANSFORMER BE SIZED AT 75 KVA.
SINGLE-PHASE FAULT CURRENT CALCULATIONS ARE BASED ON STANDARD
TRANSFORMER IMPEDANCES AND AN INFINITE PRIMARY CURRENT.
ASSUME SERVICE TRANSFORMER SIZE = 75 KVA
STANDARD TRANSFORMER IMPEDANCE (%Z) = 1.5%
MAXIMUM FAULT CURRENT AT TRANSFORMER SECONDARY = 34,639A
(USE RATING PER UTILITY STANDARDS: PADMOUNTED, UNDER 100 KVA,
RESIDENTIAL, MAXIMUM FAULT CURRENT AT SERVICE ENTRANCE = 10,000A.
ALL PANELS SHALL HAVE A.I.C. AS SCHEDULED.
SERVICE SIZING CALCULATIONS - LOAD RECAP
TOTAL CONNECTED LOAD ON "MA3": 111.2 KVA
CODE DEMAND LOAD PER NEC 220.84: MULTIFAMILY DWELLING - (4) UNITS:
17.57 KVA X 4 X .45 DEMAND FACTOR = 31.63 KVA
DESIGN LOAD = DEMAND LOAD + HOUSE LOAD + FUTURE 20%: 38.5 KVA (160A).
RECOMMEND SERVICE TRANSFORMER BE SIZED AT 75 KVA.
SINGLE-PHASE FAULT CURRENT CALCULATIONS ARE BASED ON STANDARD
TRANSFORMER IMPEDANCES AND AN INFINITE PRIMARY CURRENT.
ASSUME SERVICE TRANSFORMER SIZE = 75 KVA
STANDARD TRANSFORMER IMPEDANCE (%Z) = 1.5%
MAXIMUM FAULT CURRENT AT TRANSFORMER SECONDARY = 34,639A
(USE RATING PER UTILITY STANDARDS: PADMOUNTED, UNDER 100 KVA,
RESIDENTIAL, MAXIMUM FAULT CURRENT AT SERVICE ENTRANCE = 10,000A.
ALL PANELS SHALL HAVE A.I.C. AS SCHEDULED.
SERVICE SIZING CALCULATIONS - LOAD RECAP
TOTAL CONNECTED LOAD ON "MB": 56.7 KVA
CODE DEMAND LOAD PER NEC 220.84: MULTIFAMILY DWELLING - (2) UNITS:
17.57 KVA X 2 X 1.0 DEMAND FACTOR = 35.14 KVA
DESIGN LOAD = DEMAND LOAD + FUTURE 20%: 42.17 KVA (176A).
RECOMMEND SERVICE TRANSFORMER BE SIZED AT 75 KVA.
SINGLE-PHASE FAULT CURRENT CALCULATIONS ARE BASED ON STANDARD
TRANSFORMER IMPEDANCES AND AN INFINITE PRIMARY CURRENT.
ASSUME SERVICE TRANSFORMER SIZE = 75 KVA
STANDARD TRANSFORMER IMPEDANCE (%Z) = 1.5%
MAXIMUM FAULT CURRENT AT TRANSFORMER SECONDARY = 34,639A
(USE RATING PER UTILITY STANDARDS: PADMOUNTED, UNDER 100 KVA,
RESIDENTIAL, MAXIMUM FAULT CURRENT AT SERVICE ENTRANCE = 10,000A.
ALL PANELS SHALL HAVE A.I.C. AS SCHEDULED.
SERVICE SIZING CALCULATIONS - LOAD RECAP
TOTAL CONNECTED LOAD ON "MC": 155.0 KVA
CODE DEMAND LOAD PER NEC 220.84: MULTIFAMILY DWELLING - (6) UNITS:
17.57 KVA X 6 X .44 DEMAND FACTOR = 46.38 KVA
DESIGN LOAD = DEMAND LOAD + FUTURE 20%: 55.66 KVA (232A).
RECOMMEND SERVICE TRANSFORMER BE SIZED AT 75 KVA.
SINGLE-PHASE FAULT CURRENT CALCULATIONS ARE BASED ON STANDARD
TRANSFORMER IMPEDANCES AND AN INFINITE PRIMARY CURRENT.
ASSUME SERVICE TRANSFORMER SIZE = 75 KVA
STANDARD TRANSFORMER IMPEDANCE (%Z) = 1.5%
MAXIMUM FAULT CURRENT AT TRANSFORMER SECONDARY = 34,639A
(USE RATING PER UTILITY STANDARDS: PADMOUNTED, UNDER 100 KVA,
RESIDENTIAL, MAXIMUM FAULT CURRENT AT SERVICE ENTRANCE = 10,000A.
ALL PANELS SHALL HAVE A.I.C. AS SCHEDULED.
SERVICE SIZING CALCULATIONS - LOAD RECAP
TOTAL CONNECTED LOAD ON "MD": 111.6 KVA
CODE DEMAND LOAD PER NEC 220.84: MULTIFAMILY DWELLING - (4) UNITS:
17.57 KVA X 4 X 0.45 DEMAND FACTOR = 31.63 KVA
DESIGN LOAD = DEMAND LOAD + FUTURE 20%: 38.0 KVA (158A).
RECOMMEND SERVICE TRANSFORMER BE SIZED AT 75 KVA.
SINGLE-PHASE FAULT CURRENT CALCULATIONS ARE BASED ON STANDARD
TRANSFORMER IMPEDANCES AND AN INFINITE PRIMARY CURRENT.
ASSUME SERVICE TRANSFORMER SIZE = 75 KVA
STANDARD TRANSFORMER IMPEDANCE (%Z) = 1.5%
MAXIMUM FAULT CURRENT AT TRANSFORMER SECONDARY = 34,639A
(USE RATING PER UTILITY STANDARDS: PADMOUNTED, UNDER 100 KVA,
RESIDENTIAL, MAXIMUM FAULT CURRENT AT SERVICE ENTRANCE = 10,000A.
ALL PANELS SHALL HAVE A.I.C. AS SCHEDULED.
SERVICE SIZING CALCULATIONS - LOAD RECAP
TOTAL CONNECTED LOAD ON "MM": 45.6 KVA
CODE DEMAND LOAD PER NEC 220.40: SERVICE LOAD CALCULATION:
DEMAND LOAD = 44.7 KVA
DESIGN LOAD = DEMAND LOAD + FUTURE 20%: 53.6 KVA (224A).
RECOMMEND SERVICE TRANSFORMER BE SIZED AT 75 KVA.
SINGLE-PHASE FAULT CURRENT CALCULATIONS ARE BASED ON STANDARD
TRANSFORMER IMPEDANCES AND AN INFINITE PRIMARY CURRENT.
ASSUME SERVICE TRANSFORMER SIZE = 75 KVA
STANDARD TRANSFORMER IMPEDANCE (%Z) = 1.5%
MAXIMUM FAULT CURRENT AT TRANSFORMER SECONDARY = 34,639A
(USE RATING PER UTILITY STANDARDS: PADMOUNTED, UNDER 100 KVA,
RESIDENTIAL, MAXIMUM FAULT CURRENT AT SERVICE ENTRANCE = 10,000A.
ALL PANELS SHALL HAVE A.I.C. AS SCHEDULED.
SERVICE SIZING CALCULATIONS - LOAD RECAP
BLDGS A1 & A2 SERVICE CHARACTERISTICS: 120/240V, 1-PHASE, 3-WIRE BLDG A3 SERVICE CHARACTERISTICS: 120/240V, 1-PHASE, 3-WIRE
BLDG M SERVICE CHARACTERISTICS: 120/240V, 1-PHASE, 3-WIREBLDGS D SERVICE CHARACTERISTICS: 120/240V, 1-PHASE, 3-WIRE
BLDG B SERVICE CHARACTERISTICS: 120/240V, 1-PHASE, 3-WIRE BLDG C SERVICE CHARACTERISTICS: 120/240V, 1-PHASE, 3-WIRE
SHORT-CIRCUIT CALCULATIONS SHORT-CIRCUIT CALCULATIONS
SHORT-CIRCUIT CALCULATIONS SHORT-CIRCUIT CALCULATIONS
SHORT-CIRCUIT CALCULATIONS SHORT-CIRCUIT CALCULATIONS
SYMBOL DESCRIPTION
FIRE ALARM SYMBOL LEGEND
FIRE ALARM MANUAL PULL STATION.
FIRE ALARM AUDIO/STROBE UNIT.
FIRE ALARM DUCT SMOKE DETECTOR.
FIRE ALARM TAMPER SWITCH.
FIRE ALARM STROBE UNIT.
FIRE ALARM SMOKE DETECTOR.
FIRE ALARM HEAT DETECTOR.
FIRE ALARM FLOW SWITCH.
FIRE ALARM CONTROL PANEL (FACP).
FIRE PROTECTION SPRINKLER SYSTEM POST INDICATOR VALVE (PIV).
(ALL SYMBOLS SHOWN ARE NOT NECESSARILY USED ON THE DRAWINGS)
AUTHORITY HAVING JURISDICTION.AHJ
SLAVE GFCI-PROTECTED RECEPTACLE (NEC 422.52) FOR EDF
ELECTRIC DRINKING FOUNTAIN (EDF) CONCEALED WITHIN CASE.
GFCI PROTECTED DUPLEX RECEPTACLE. RECEPTACLES WITHGFCI
TRIP RESET SHALL BE IN READILY ACCESSIBLE LOCATION.
ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLYRESERVES THE COMMON LAW COPYRIGHT ASSOCIATEDWITH THESE DRAWINGS, AND THESE DOCUMENTS MAYNOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RDPARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC,INC.
THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ANDARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL ORCOMPONENT REQUIRED FOR A COMPLETE, FULLYOPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S).
ANY CONTRACTOR RELYING ON THESE DOCUMENTSSHALL DO SO ONLY IN CONCERT WITH CURRENT CODECONSIDERATION, FIELD INVESTIGATION/VERIFICATIONAND UTILITY COORDINATION IN ORDER TO PROVIDE ACOMPREHENSIVE INSTALLATION.
PO BOX 93024Albuquerque, NM 87199
505-856-3419
INC.E N G I N E E R S
C O N S U L T I N G
Project #:
Date:
PROJECT ARCHITECT:
By:
File:Sheet of
Plot Date:
AEC-E-3.0-PANEL SCHEDULES.DWG
2/12/2015 4:19:37 PM
Housing and Economic Rural OpportunityPase Del Oro ApartmentsLas Cruces, New Mexico
BOB HALL, AIA
IDA-14-01-P
DECEMBER 22, 2014
AEC
101/30/15 REVISION #1.
PANEL SCHEDULES
E-3.0
BUILDING A1
BUILDING A3
BUILDING A2
BUILDING M
BUILDING B
BUILDING C
BUILDING D
2-STORY
2-STORY
2-STORY
(OFFICE / LAUNDRY)
2-STORY
2-STORY
2-STORY
T
1
1
1
2
ELKS DRIVE
E
N
G
L
E
R
D
R
IV
E
G
O
L
D
C
O
U
R
T
PASEO DEL ORO CR
7
12
9
5
12
PP PP
10
11
11
10 10
4
T
EXISTING TRANSFORMER
EXISTING TELE. PED.
T
T
EXISTING TELE. PED.
4
5
5
8
5
5
9
3
5
CATV
13
14
12
9
12
12
9
9
T
T
15TYP
15TYP
15TYP
15TYP
15TYP
4
12
1
4
1
4
5
9
12
4
4
"MA1"
"MA2"
"MA3"
"MB"
"MC" "MD"
"MM"
ST-1
ST-3
ST-2
ST-4
ST-5
(4 APTS)
(4 APTS)
(4 APTS)
(2 APTS)
(6 APTS)
(4 APTS)
1616
16
16
16
16
16
17
17
17
17
17
17
17
UNIT 107
UNIT 115
UNIT 106
UNIT 103
19 19
18
18
6
6
6
6
TS FS
20
TS FS
6
TS FS
6
TS
FS
6
ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLYRESERVES THE COMMON LAW COPYRIGHT ASSOCIATEDWITH THESE DRAWINGS, AND THESE DOCUMENTS MAYNOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RDPARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC,INC.
THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ANDARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL ORCOMPONENT REQUIRED FOR A COMPLETE, FULLYOPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S).
ANY CONTRACTOR RELYING ON THESE DOCUMENTSSHALL DO SO ONLY IN CONCERT WITH CURRENT CODECONSIDERATION, FIELD INVESTIGATION/VERIFICATIONAND UTILITY COORDINATION IN ORDER TO PROVIDE ACOMPREHENSIVE INSTALLATION.
PO BOX 93024Albuquerque, NM 87199
505-856-3419
INC.E N G I N E E R S
C O N S U L T I N G
Project #:
Date:
PROJECT ARCHITECT:
By:
File:Sheet of
Plot Date:
AEC-SITE-ES-1.0.DWG
3/4/2015 1:54:37 PM
Housing and Economic Rural OpportunityPaseo Del Oro ApartmentsLas Cruces, New Mexico
BOB HALL, AIA
IDA-14-01-P
DECEMBER 22, 2014
AEC
101/30/15 REVISION #1.
203/04/15 REVISION #2, RELOCATE ST-5.
ELECTRICAL KEYED NOTES:
1" = 20'-0"
ELECTRICAL SITE PLAN
NORTH
ELECTRICAL SITE PLAN
ES-1.0
1 ONE 2" PVC CONDUIT W/PULL STRING TO COMCAST PEDESTAL.
2 ONE BARE # 6 SOLID CU TO TO INTERSYSTEM BONDING TERMINAL (IBT).
3 COMCAST PROVIDED CABINET.
4 2" PVC CONDUIT WITH PULL STRING.
1
2
3
CATV RISER DIAGRAM
4
SCALE: NONE
CCTV
CAB.
PEDESTAL
CCTV
4
4
4
4
4
3
CCTV
CAB.
3
CCTV
CAB.
3
CCTV
CAB.
3
CCTV
CAB.
3
CCTV
CAB.
3
CCTV
CAB.
1 ONE 4" PVC CONDUIT W/PULL STRING TO CENTURYLINK PEDESTAL.
2 ONE BARE # 6 SOLID CU TO TO INTERSYSTEM BONDING TERMINAL (IBT).
3 CENTURYLINK DEMARK, E.C. TO PROVIDE CIRCLE AW #420 NEMA 3R
ENCLOSURE WITH BACKBOARD.
4 E.C. PROVIDED 24X24X12 NEMA 3R J-BOX WITH PLYWOOD BACKBOARD AND
LOCKING COVER.
5 DIRECT BURY TELEPHONE DISTRIBUTION CABLE.
6 LIGHTNING PROTECTION.
7 CAT 5E PVC COATED TELEPHONE CABLING AND SINGLE PORT TERMINATION
PLATE TO EACH PHONE OUTLET.
8 TYPICAL VOICE/DATA (PHONE) OUTLET, FURNISHED BY E.C.
1
2
3
4
TELEPHONE RISER DIAGRAM
6
5
SCALE: NONE
7
TEL.
CAB.
PEDESTAL
TELEPHONE
4
6
5
7
4
6
5
7
4
6
5
7
4
6
5
7
4
6
5
7
TTB
BLDG. M
2" C.
1 UTILITY-OWNED SERVICE TRANSFORMER (ST) WITH 120/240V, 1-PHASE
SECONDARY, REFER TO POWER RISER DIAGRAM. VERIFY ALL SERVICE
REQUIREMENTS WITH EL PASO ELECTRIC (EPE) PRIOR TO BEGINNING ANY
ELECTRICAL WORK.
2 TELEPHONE TERMINAL BACKBOARD (TTB).
3 EXTEND 4" PVC TELEPHONE SERVICE CONDUIT TO SERVICE PEDESTAL. VERIFY
SERVICE LOCATION AND REQUIREMENTS WITH CENTURYLINK PRIOR TO ANY
INSTALLATION OR TRENCHING WORK.
4 SECONDARY SERVICE FEEDER BY ELECTRICAL CONTRACTOR, REFER TO
POWER RISER DIAGRAM.
5 SERVICE ENTRANCE GEAR, REFER TO POWER RISER DIAGRAM.
6 CONNECT FIRE ALARM DEVICES AT FIRE RISER ROOM TO FIRE ALARM CONTROL
PANEL (FACP) IN BUILDING "M", SEE POWER PLAN FOR THIS BUILDING. REFER
TO FIRE ALARM SYSTEM DIAGRAM AND FIRE ALARM GENERAL NOTES ON SHEET
EM-1.0.
7 TELEPHONE SERVICE PEDESTAL.
8 MAIN TELEPHONE SERVICE DEMARC CABINET, REFER TO TELEPHONE RISER
DIAGRAM.
9 TELEPHONE CABINET, REFER TO TELEPHONE RISER DIAGRAM.
10 EXISTING EPE-OWNED OVERHEAD 3-PHASE PRIMARY POWER LINE TO REMAIN.
11 EXISTING EPE-OWNED POWER POLE TO REMAIN.
12 CATV TERMINAL CABINET, FURNISHED BY COMCAST, INSTALLED BY ELECTRICAL
CONTRACTOR.
13 2" PVC CATV SERVICE CONDUIT PER COMCAST REQUIREMENTS. VERIFY
SERVICE POINT AND CONDUIT ROUTING WITH COMCAST REPRESENTATIVE
PRIOR TO ANY INSTALLATION OR TRENCHING WORK.
14 CATV SERVICE PEDESTAL.
15 PRIMARY UNDERGROUND ELECTRICAL FEEDER BY EL PASO ELECTRIC.
16 PHOTOVOLTAIC (PV) REC METER AND INVERTER SHALL BE LOCATED ADJACENT
TO SERVICE ENTRANCE EQUIPMENT, REFER TO POWER RISER DIAGRAM ON
SHEET E1.0.
17 PV PANELS SHALL BE INSTALLED ON THE ROOF OF THIS BUILDING, REFER TO
SHEET PV-1.00 FOR QUANTITY, LOCATION, AND ELECTRICAL CHARACTERISTICS.
18 THIS APARTMENT UNIT IS FOR THE HEARING IMPAIRED.
19 THIS APARTMENT UNIT IS FULLY ACCESSIBLE FOR THE PHYSICALLY
CHALLENGED.
20 FIRE ALARM CONTROL PANEL, REFER TO SHEET EM-1.0.
C
I
E
X
W
M
N
E
0
A
L
O
M
É
AR
C
I
N
I
E
G
A
S
18711
2
BUILDING A1
BUILDING A3
BUILDING A2
BUILDING M
BUILDING B
BUILDING C
BUILDING D
(6 APTS)
(4 APTS)(2 APTS)
(OFFICE / LAUNDRY)
(4 APTS)
(4 APTS)
(4 APTS)
2
ELKS DRIVE
E
N
G
L
E
R
D
R
IV
E
G
O
L
D
C
O
U
R
T
PASEO DEL ORO CR
1
2
3TYP
3TYP
3TYP
2
2
ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLYRESERVES THE COMMON LAW COPYRIGHT ASSOCIATEDWITH THESE DRAWINGS, AND THESE DOCUMENTS MAYNOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RDPARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC,INC.
THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ANDARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL ORCOMPONENT REQUIRED FOR A COMPLETE, FULLYOPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S).
ANY CONTRACTOR RELYING ON THESE DOCUMENTSSHALL DO SO ONLY IN CONCERT WITH CURRENT CODECONSIDERATION, FIELD INVESTIGATION/VERIFICATIONAND UTILITY COORDINATION IN ORDER TO PROVIDE ACOMPREHENSIVE INSTALLATION.
PO BOX 93024Albuquerque, NM 87199
505-856-3419
INC.E N G I N E E R S
C O N S U L T I N G
Project #:
Date:
PROJECT ARCHITECT:
By:
File:Sheet of
Plot Date:
AEC-SITE-ES-1.1 SITE LIGHTING.DWG
2/12/2015 4:22:10 PM
Housing and Economic Rural OpportunityPaseo Del Oro ApartmentsLas Cruces, New Mexico
BOB HALL, AIA
IDA-14-01-P
DECEMBER 22, 2014
AEC
1 EXTEND TO CIRCUIT INDICATED THROUGH PHOTOCELL/TIMECLOCK CONTROLS.
USE #10 WIRING THROUGHOUT ENTIRE RUN.
2 PARKING LOT FIXTURE ON 12' POLE, REFER TO POLE BASE MOUNTING DETAIL.
3 REFER TO ASSOCIATED BUILDING ELECTRICAL PLAN FOR CIRCUITING TO THIS
LIGHTING FIXTURE.
ELECTRICAL KEYED NOTES:
1" = 20'-0"
ELECTRICAL SITE LIGHTING PLAN
NORTH
ELECTRICAL SITE LIGHTING PLAN
ES-1.1
FINISHED GRADE
POLE BASE MOUNTING DETAIL
SCALE: NONE
TO BRANCH
CIRCUIT PER
PLAN
TO
EXTERIOR
LIGHTS
LIGHTING CONTROL DIAGRAM
SCALE: NONE
IECC LIGHTING COMPLIANCE - SITE LIGHTING
THE SITE LIGHTING DESIGN SHOWN ON THESE PLANS IS IN COMPLIANCE WITH THE
2009 INTERNATIONAL ENERGY CONSERVATION CODE (IECC).
REFERENCE SECTION 505 - ELECTRICAL POWER AND LIGHTING SYSTEMS
505.6 - EXTERIOR LIGHTING
1. TABLE 505.6.2(1) - EXTERIOR LIGHTING ZONES: THIS PROJECT SITE IS
CLASSIFIED AS LIGHTING ZONE 2: PREDOMINANTLY RESIDENTIAL,
NEIGHBORHOOD BUSINESS DISTRICT.
2. TABLE 505.6.2(2) - LIGHTING POWER ALLOWANCES FOR BUILDING
EXTERIORS:
BASE SITE ALLOWANCE: 600W
PARKING AREAS AND DRIVES: 0.06 W/SF
WALKWAYS LESS THAN 10' WIDE: 0.7 W/LF
SPECIAL FEATURE AREAS: 0.14 W/SF
STAIRWAYS: 1.0 W/SF
MAIN ENTRIES: 20W/LINEAR FOOT OF DOOR WIDTH
OTHER DOORS: 20W/LINEAR FOOT OF DOOR WIDTH
EXTERIOR AREA TOTAL ALLOWABLE WATTAGE FOR THE SITE: 2,140W.
ACTUAL EXTERIOR LIGHTING LOAD = 1,026W. THIS BUILDING COMPLIES WITH THE
MAXIMUM EXTERIOR LIGHTING POWER ALLOWANCE.
BUILDING A1
BUILDING A3
BUILDING A2
BUILDING M
BUILDING B
BUILDING C
BUILDING D
(6 APTS)
(4 APTS)(2 APTS)
(OFFICE / LAUNDRY)
(4 APTS)
(4 APTS)
(4 APTS)
2
ELKS DRIVE
E
N
G
L
E
R
D
R
IV
E
G
O
L
D
C
O
U
R
T
PASEO DEL ORO CR
6
16TYP
17
17
17
TYP
TYP
TYP
SA
SA
SASA
SA
SD
SD
SD
SE
SE
SE
SA
SA
SA
SA
SA
SA
SA
SB
SB
SC
SC
SB
SC
SC
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SA
SD
SD
SD
SA
MM-7
0.1
0.1
0.1
0.1
0.1
0.0
0.0
0.0
0.0
0.1
0.2
0.7
1.6
2.9
10.0
4.4
5.9
0.1
1.5
1.4
0.9
0.1 0.1 0.1 0.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
0.0
0.0
0.0
0.0
0.0
0.0
0.1
0.1
0.2
0.3
0.5
0.9
1.2
1.5
1.7
1.5
1.5
1.0
0.8
0.6
0.4
0.3
0.3
0.3
0.4
0.5
0.8
1.1
1.6
3.43.5
8.8
15.0
18.7
15.1
8.9
3.0
1.1
0.3
0.0
0.0
0.0
0.1
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.10.1
0.1 0.0 0.0 0.0 0.00.0 0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.00.0
0.1
0.1
0.2
0.3
0.4
0.5
0.5
0.8
1.0
0.6
0.3
0.2
0.2
0.2
0.3
0.5
2.73.7
8.2
10.3
9.4
3.9
2.41.40.7
0.10.00.10.20.20.20.10.00.00.00.00.00.00.00.00.00.0 0.0 0.0 0.00.8 0.6 0.2 0.9 2.3 6.9 10.9 11.5 7.7 4.1 1.1 0.3 0.2 0.1 0.1 0.1 0.0
2.5
6.5
9.6
8.8
6.6
0.4
0.4
1.0
1.3
0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.10.1
1.3
0.7
0.4
0.3
0.2
0.1
0.110.4
0.0
0.0
0.0
ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLYRESERVES THE COMMON LAW COPYRIGHT ASSOCIATEDWITH THESE DRAWINGS, AND THESE DOCUMENTS MAYNOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RDPARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC,INC.
THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ANDARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL ORCOMPONENT REQUIRED FOR A COMPLETE, FULLYOPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S).
ANY CONTRACTOR RELYING ON THESE DOCUMENTSSHALL DO SO ONLY IN CONCERT WITH CURRENT CODECONSIDERATION, FIELD INVESTIGATION/VERIFICATIONAND UTILITY COORDINATION IN ORDER TO PROVIDE ACOMPREHENSIVE INSTALLATION.
PO BOX 93024Albuquerque, NM 87199
505-856-3419
INC.E N G I N E E R S
C O N S U L T I N G
Project #:
Date:
PROJECT ARCHITECT:
By:
File:Sheet of
Plot Date:
AEC-SITE-ES-1.2 SITE LIGHTING LUMEN CALCS.DWG
2/12/2015 4:23:16 PM
Housing and Economic Rural OpportunityPaseo Del Oro ApartmentsLas Cruces, New Mexico
BOB HALL, AIA
IDA-14-01-P
DECEMBER 22, 2014
AEC
1" = 20'-0"
ELECTRICAL SITE LIGHTING LUMENS CALC
NORTH
ELECTRICAL SITE LIGHTING LUMENS CALC
ES-1.2
Luminaire Schedule
Symbol Qty Label Arrangement Total Lamp Lumens LLF Description
34 SA SINGLE N.A. 0.930 RAB # SLIM26YWPC
3 SB SINGLE N.A. 0.930 RAB # SLIM26YWPC-ON 12 FT POLE
4 SC SINGLE N.A. 0.930 BK LIGHTING # BQL-LED-E36A9-WHP
3 SD SINGLE 1200 0.930 VOLUME # V8853-6 WHITE
3 SE SINGLE 1200 0.930 VOLUME # V8853-6 WHITE
Calculation Summary: Lighting levels calculated by point-to-point method using AGi32 software
Label CalcType Units Avg Max Min Avg/Min Max/Min
PARKING_Top Illuminance Fc 0.38 7.0 0.0 N.A. N.A.
SIDEWALK AROUND SITE_Top Illuminance Fc 0.30 2.5 0.0 N.A. N.A.
SIDEWALK INTERIOR SITE_1_Top Illuminance Fc 1.96 13.0 0.0 N.A. N.A.
SIDEWALK INTERIOR SITE_Top Illuminance Fc 2.04 18.8 0.0 N.A. N.A.
2
2
2
2
APARTMENT 111
(UNIT STYLE "3")
APARTMENT 112
(UNIT STYLE "3")
APARTMENT 113
(UNIT STYLE "3")
APARTMENT 114
(UNIT STYLE "3")
STAIRS
101
BATH
112
MECH.
101
BEDROOM 2
111
BEDROOM 3
114
DECK
HALLWAY
113
STORAGE
109
STAIRS
101
BATH
112
MECH.
101
BEDROOM 2
111
BEDROOM 3
114
DECK
HALLWAY
113
STORAGE
109
STAIRS
101
BATH
112
MECH.
101
BEDROOM 2
111
BEDROOM 3
114
DECK
HALLWAY
113
STORAGE
109
1
1 1
1
PANEL "MA1"3
APARTMENT 111
(UNIT STYLE "3")
APARTMENT 112
(UNIT STYLE "3")
APARTMENT 113
(UNIT STYLE "3")
APARTMENT 114
(UNIT STYLE "3")
PANEL "A3"4
BEDROOM 1
106
BATH 1
105
LAUNDRY
104
DINING
103
LIVING
102
KITCHEN
107
STORAGE
108
BEDROOM 1
106
BATH 1
105
LAUNDRY
104
DINING
103
LIVING
102
KITCHEN
107
STORAGE
108
PORCH PORCH
BEDROOM 1
106
BATH 1
105
LAUNDRY
104
DINING
103
LIVING
102
KITCHEN
107
STORAGE
108
PORCH
BEDROOM 1
106
BATH 1
105
LAUNDRY
104
DINING
103
LIVING
102
KITCHEN
107
STORAGE
108
PORCH
PANEL "A3"4 PANEL "A3"4
PANEL "A3"4
7
8
(APARTMENTS 107, 115)
EUH-1
S
RISER
-
TSFS
9
TYP
10 TYP
10TYP
5
CU-3
TO APT. 111
6
5
CU-3
TO APT. 112
6
5
CU-3
TO APT. 113
6
ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLYRESERVES THE COMMON LAW COPYRIGHT ASSOCIATEDWITH THESE DRAWINGS, AND THESE DOCUMENTS MAYNOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RDPARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC,INC.
THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ANDARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL ORCOMPONENT REQUIRED FOR A COMPLETE, FULLYOPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S).
ANY CONTRACTOR RELYING ON THESE DOCUMENTSSHALL DO SO ONLY IN CONCERT WITH CURRENT CODECONSIDERATION, FIELD INVESTIGATION/VERIFICATIONAND UTILITY COORDINATION IN ORDER TO PROVIDE ACOMPREHENSIVE INSTALLATION.
PO BOX 93024Albuquerque, NM 87199
505-856-3419
INC.E N G I N E E R S
C O N S U L T I N G
Project #:
Date:
PROJECT ARCHITECT:
By:
File:Sheet of
Plot Date:
AEC-A-EA-1.0.DWG
2/12/2015 4:24:29 PM
Housing and Economic Rural OpportunityPase Del Oro ApartmentsLas Cruces, New Mexico
BOB HALL, AIA
IDA-14-01-P
DECEMBER 22, 2014
AEC
101/30/15 REVISION #1.
1/8"=1'-0"
SECOND FLOOR ELECTRICAL PLAN - BUILDINGS A1, A2, A3
NORTH
1/8"=1'-0"
GROUND FLOOR ELECTRICAL PLAN - BUILDINGS A1, A2, A3
NORTH
GENERAL NOTES:
ELECTRICAL KEYED NOTES:
A REFER TO ARCHITECTURAL ELEVATIONS FOR ADDITIONAL DETAILS.
ARCHITECTURAL ELEVATIONS (DEMO & NEW) SHOW EXTERIOR DUPLEX
RECEPTACLES, ALARM BELL, ALARM STROBE, CONDENSERS, ETC.
B BUILDING A1 WITH APARTMENTS 111, 112, 113, AND 114 IS SHOWN ON THIS
SHEET, BUILDINGS A2 AND A3 ARE SIMILAR BUILDINGS. APARTMENT NUMBERS
ARE 107, 108, 109, 110 FOR BUILDING A2, AND 115, 116, 117, 118 FOR BUILDING A3.
1 REFER TO ENLARGED UNIT STYLE "3" - FIRST FLOOR ELECTRICAL PLAN FOR
WORK REQUIRED IN THIS LEVEL OF THE DWELLING UNIT.
2 REFER TO ENLARGED UNIT STYLE "3" - SECOND FLOOR ELECTRICAL PLAN FOR
WORK REQUIRED IN THIS LEVEL OF THE DWELLING UNIT.
3 MAIN DISTRIBUTION / HOUSE PANEL FOR BUILDING A1, SIMILAR FOR PANELS
"MA2" AND "MA3" WHICH SERVE BUILDINGS A2 AND A3 RESPECTIVELY. REFER
TO POWER RISER DIAGRAM.
4 TYPICAL POWER PANEL FOR STYLE "3" APARTMENTS, REFER TO ASSOCIATED
PANEL SCHEDULE.
5 EXTEND TO CIRCUIT INDICATED IN ASSOCIATED APARTMENT PANEL.
6 INSTALL ROOFTOP GFCI, WR RECEPTACLE ADJACENT TO HVAC UNIT. EXTEND 3
#12 TO CIRCUIT BREAKER INDICATED IN PANEL "MA" AND MAKE ALL FINAL
POWER CONNECTIONS.
7 EXTEND TO CIRCUIT INDICATED THROUGH PHOTOCELL FOR DUSK-TO-DAWN
OPERATION.
8 NUMBER ADJACENT TO RECEPTACLE INDICATES CIRCUIT NUMBER. EXTEND 3
#12 TO CIRCUIT BREAKER IN PANEL "MA" AND MAKE ALL FINAL POWER
CONNECTIONS.
9 CONNECT FIRE SPRINKLER SYSTEM FLOW AND TAMPER SWITCHES TO FIRE
ALARM CONTROL PANEL IN BUILDING "M". PROVIDE FIRE ALARM STROBE ABOVE
DOOR (STROBE ACTIVATED BY LOCAL FLOW & TAMPER SWITCHES).
10 REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATION AND MOUNTING
HEIGHT OF EXTERIOR LIGHTING FIXTURE.
BUILDINGS A1, A2, & A3 ELECTRICAL PLAN
EA-1.0
NTS
KEY PLAN
NORTH
1/8"=1'-0"
ROOF ELECTRICAL PLAN - BUILDINGS A1, A2, A3
NORTH
IECC LIGHTING COMPLIANCE
THE LIGHTING DESIGN SHOWN ON THESE PLANS IS IN COMPLIANCE WITH THE 2009
INTERNATIONAL ENERGY CONSERVATION CODE (IECC) SECTION 505 - ELECTRICAL
POWER AND LIGHTING SYSTEMS AS FOLLOWS:
1. 505.2.2.2 - LIGHTING CONTROLS:
A. THIS PROJECT DOES NOT INCLUDES AREAS LARGER THAN 5,000 SQUARE
FEET.
2. TABLE 505.5.2 - INTERIOR LIGHTING POWER ALLOWANCES: THIS TABLE
LIMITS THE ALLOWABLE LIGHTING POWER DENSITY (LPD) WITHIN A
MULTI-FAMILY DWELLING TO 0.7 W/SF.
BUILDINGS "A1", "A2", AND "A3" AREA IS 5,368 SQ FT, TOTAL ALLOWABLE WATTAGE
IS 3,758W.
INTERIOR LIGHTING LOAD = 3,200W. THIS MULTIFAMILY DWELLING BUILDING HAS
AN LPD OF 0.60W/SF AND COMPLIES WITH MAXIMUM ALLOWABLE LPD.
3. TABLE 505.6.2(2) - INDIVIDUAL LIGHTING POWER ALLOWANCES FOR BUILDING
EXTERIORS: THIS TABLE LIMITS EXTERIOR LIGHTING BASED ON ZONE
CLASSIFICATION AND LOCATION OF LIGHTING. THIS BUILDING IS CLASSIFIED
AS ZONE 2: PREDOMINANTLY RESIDENTIAL, NEIGHBORHOOD BUSINESS
DISTRICT. THE EXTERIOR LIGHTING POWER ALLOWANCES ARE:
BASE SITE ALLOWANCE: 600W
PARKING AREAS AND DRIVES: 0.06 W/SF
WALKWAYS LESS THAN 10' WIDE: 0.7 W/LF
SPECIAL FEATURE AREAS: 0.14 W/SF
MAIN ENTRIES: 20W/LINEAR FOOT OF DOOR WIDTH
OTHER DOORS: 20W/LINEAR FOOT OF DOOR WIDTH
EXTERIOR AREA TOTAL ALLOWABLE WATTAGE FOR BLDGS "A1, "A2, & "A3": 240W.
ACTUAL EXTERIOR LIGHTING LOAD = 168W. THIS BUILDING COMPLIES WITH THE
MAXIMUM EXTERIOR LIGHTING POWER ALLOWANCE.
C
I
E
X
W
M
N
E
0
A
L
O
M
É
AR
C
I
N
I
E
G
A
S
18711
22
APARTMENT 206
(UNIT STYLE "3")
APARTMENT 205
(UNIT STYLE "3")
1
1
PANEL "MB"3
APARTMENT 106
(UNIT STYLE "3")
APARTMENT 105
(UNIT STYLE "3")
PORCH PORCH
7
TYP8
EUH-1
RISER
-
S
TSFS
TYP10
BUILDING B
ROOF
5
CU-3
TO APT. 106
6
5
CU-3
TO APT. 105
6
ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLYRESERVES THE COMMON LAW COPYRIGHT ASSOCIATEDWITH THESE DRAWINGS, AND THESE DOCUMENTS MAYNOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RDPARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC,INC.
THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ANDARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL ORCOMPONENT REQUIRED FOR A COMPLETE, FULLYOPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S).
ANY CONTRACTOR RELYING ON THESE DOCUMENTSSHALL DO SO ONLY IN CONCERT WITH CURRENT CODECONSIDERATION, FIELD INVESTIGATION/VERIFICATIONAND UTILITY COORDINATION IN ORDER TO PROVIDE ACOMPREHENSIVE INSTALLATION.
PO BOX 93024Albuquerque, NM 87199
505-856-3419
INC.E N G I N E E R S
C O N S U L T I N G
Project #:
Date:
PROJECT ARCHITECT:
By:
File:Sheet of
Plot Date:
AEC-B-EB-1.0.DWG
2/12/2015 4:25:13 PM
Housing and Economic Rural OpportunityPase Del Oro ApartmentsLas Cruces, New Mexico
BOB HALL, AIA
IDA-14-01-P
DECEMBER 22, 2014
AEC
101/30/15 REVISION #1.
GENERAL NOTES:
ELECTRICAL KEYED NOTES:
A REFER TO ARCHITECTURAL ELEVATIONS FOR ADDITIONAL DETAILS.
ARCHITECTURAL ELEVATIONS (DEMO & NEW) SHOW EXTERIOR DUPLEX
RECEPTACLES, ALARM BELL, ALARM STROBE, CONDENSERS, ETC.
1 REFER TO ENLARGED UNIT STYLE "3" - FIRST FLOOR ELECTRICAL PLAN FOR
WORK REQUIRED IN THIS LEVEL OF THE DWELLING UNIT.
2 REFER TO ENLARGED UNIT STYLE "3" - SECOND FLOOR ELECTRICAL PLAN FOR
WORK REQUIRED IN THIS LEVEL OF THE DWELLING UNIT.
3 MAIN DISTRIBUTION /HOUSE PANEL FOR THIS BUILDING, REFER TO POWER
RISER DIAGRAM.
4 TYPICAL POWER PANEL FOR STYLE "3" APARTMENTS, REFER TO ASSOCIATED
PANEL SCHEDULE.
5 EXTEND TO CIRCUIT INDICATED IN ASSOCIATED APARTMENT PANEL.
6 INSTALL ROOFTOP GFCI, WR RECEPTACLE ADJACENT TO HVAC UNIT. EXTEND 3
#12 TO CIRCUIT BREAKER INDICATED IN PANEL "MB" AND MAKE ALL FINAL
POWER CONNECTIONS.
7 EXTEND TO CIRCUIT INDICATED THROUGH PHOTOCELL FOR DUSK-TO-DAWN
OPERATION.
8 NUMBER ADJACENT TO RECEPTACLE INDICATES CIRCUIT NUMBER. EXTEND 3
#12 TO CIRCUIT BREAKER IN PANEL "MB" AND MAKE ALL FINAL POWER
CONNECTIONS.
9 CONNECT FIRE SPRINKLER SYSTEM FLOW AND TAMPER SWITCHES TO FIRE
ALARM CONTROL PANEL IN BUILDING "M". PROVIDE FIRE ALARM STROBE ABOVE
DOOR (STROBE ACTIVATED BY LOCAL FLOW & TAMPER SWITCHES).
10 REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATION AND MOUNTING
HEIGHT OF EXTERIOR LIGHTING FIXTURE.
BUILDING B ELECTRICAL PLAN
EB-1.0
1/8"=1'-0"
SECOND FLOOR ELECTRICAL PLAN - BUILDING B
NORTH
1/8"=1'-0"
FIRST FLOOR ELECTRICAL PLAN - BUILDING B
NORTH
NTS
KEY PLAN
NORTH
1/8"=1'-0"
ROOF ELECTRICAL PLAN - BUILDING B
NORTH
IECC LIGHTING COMPLIANCE
THE LIGHTING DESIGN SHOWN ON THESE PLANS IS IN COMPLIANCE WITH THE 2009
INTERNATIONAL ENERGY CONSERVATION CODE (IECC) SECTION 505 - ELECTRICAL
POWER AND LIGHTING SYSTEMS AS FOLLOWS:
1. 505.2.2.2 - LIGHTING CONTROLS:
A. THIS PROJECT DOES NOT INCLUDES AREAS LARGER THAN 5,000 SQUARE
FEET.
2. TABLE 505.5.2 - INTERIOR LIGHTING POWER ALLOWANCES: THIS TABLE
LIMITS THE ALLOWABLE LIGHTING POWER DENSITY (LPD) WITHIN A
MULTIFAMILY DWELLING TO 0.7 W/SF.
BUILDING "B" AREA IS 2,684 SQ FT, TOTAL ALLOWABLE WATTAGE IS 1,879W.
INTERIOR LIGHTING LOAD = 1600W. THIS MULTIFAMILY DWELLING BUILDING HAS
AN LPD OF 0.60W/SF AND COMPLIES WITH MAXIMUM ALLOWABLE LPD.
3. TABLE 505.6.2(2) - INDIVIDUAL LIGHTING POWER ALLOWANCES FOR BUILDING
EXTERIORS: THIS TABLE LIMITS EXTERIOR LIGHTING BASED ON ZONE
CLASSIFICATION AND LOCATION OF LIGHTING. THIS BUILDING IS CLASSIFIED
AS ZONE 2: PREDOMINANTLY RESIDENTIAL, NEIGHBORHOOD BUSINESS
DISTRICT. THE EXTERIOR LIGHTING POWER ALLOWANCES ARE:
BASE SITE ALLOWANCE: 600W
PARKING AREAS AND DRIVES: 0.06 W/SF
WALKWAYS LESS THAN 10' WIDE: 0.7 W/LF
SPECIAL FEATURE AREAS: 0.14 W/SF
MAIN ENTRIES: 20W/LINEAR FOOT OF DOOR WIDTH
OTHER DOORS: 20W/LINEAR FOOT OF DOOR WIDTH
EXTERIOR AREA TOTAL ALLOWABLE WATTAGE FOR BLDG "B": 240W.
ACTUAL EXTERIOR LIGHTING LOAD = 168W. THIS BUILDING COMPLIES WITH THE
MAXIMUM EXTERIOR LIGHTING POWER ALLOWANCE.
C
I
E
X
W
M
N
E
0
A
L
O
M
É
AR
C
I
N
I
E
G
A
S
18711
DNDN
2
22
APARTMENT 203
(UNIT STYLE "2")
APARTMENT 204
(UNIT STYLE "2")
APARTMENT 202
(UNIT STYLE "2")
LIVING
ROOM
102
PANEL "A2"4
DECK
KITCHEN
109
BATH
104
BEDROOM 1
105
BEDROOM 2
106
BEDROOM 2
106
BEDROOM 1
105
BATH
104
KITCHEN
109
LIVING
ROOM
102
DECK DECK
BEDROOM 2
106
BEDROOM 1
105
KITCHEN
109
BATH
104
LIVING
ROOM
102
MECH.
101
MECH.
101
MECH.
101
PANEL "A2" 4
PANEL "A2"4
LINEN
108
PANTRY
107
LINEN
108
PANTRY
107
LINEN
108
PANTRY
107
PANEL "MC"
UPUP
1
1
1
3
APARTMENT 103
(UNIT STYLE "1")
APARTMENT 104
(UNIT STYLE "1")
APARTMENT 102
(UNIT STYLE "1")
BEDROOM 2
106
BATH
104
BEDROOM 1
102
LIVING
109
PORCH
LINEN
103
DINING
108
KITCHEN
107
LAUNDRY
105
MECH.
101
STORAGE
111
STORAGE
110
BEDROOM 2
106
LAUNDRY
105
BATH
104
KITCHEN
107
DINING
108
BEDROOM 1
102
STORAGE
110
STORAGE
110
STORAGE
111
STORAGE
111
KITCHEN
107
BEDROOM 2
106
LAUNDRY
105
BATH
104
DINING
108
BEDROOM 1
102
LIVING
109
LIVING
109
MECH.
101
MECH.
101
PORCH PORCH
PANEL "A1"9 PANEL "A1"9PANEL "A1" 9
7
EUH-1
RISER
-
S
7
8
TYP
7
S
TS
FS
10
11
TYP
CU-4
5
5
CU-4
TO APT. 102
TO APT. 202
6
CU-4
5
5
CU-4
TO APT. 103
TO APT. 203
6
CU-4
5
5
CU-4
TO APT. 104
TO APT. 204
6
BUILDING C
ROOF
ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLYRESERVES THE COMMON LAW COPYRIGHT ASSOCIATEDWITH THESE DRAWINGS, AND THESE DOCUMENTS MAYNOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RDPARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC,INC.
THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ANDARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL ORCOMPONENT REQUIRED FOR A COMPLETE, FULLYOPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S).
ANY CONTRACTOR RELYING ON THESE DOCUMENTSSHALL DO SO ONLY IN CONCERT WITH CURRENT CODECONSIDERATION, FIELD INVESTIGATION/VERIFICATIONAND UTILITY COORDINATION IN ORDER TO PROVIDE ACOMPREHENSIVE INSTALLATION.
PO BOX 93024Albuquerque, NM 87199
505-856-3419
INC.E N G I N E E R S
C O N S U L T I N G
Project #:
Date:
PROJECT ARCHITECT:
By:
File:Sheet of
Plot Date:
AEC-C-EC-1.0.DWG
2/12/2015 4:26:17 PM
Housing and Economic Rural OpportunityPase Del Oro ApartmentsLas Cruces, New Mexico
BOB HALL, AIA
IDA-14-01-P
DECEMBER 22, 2014
AEC
101/30/15 REVISION #1.
BUILDING C ELECTRICAL PLAN
EC1.0
1/8"=1'-0"
SECOND FLOOR ELECTRICAL PLAN - BUILDING C
NORTH
1/8"=1'-0"
GROUND FLOOR ELECTRICAL PLAN - BUILDING C
NORTH
NTS
KEY PLAN
NORTH
GENERAL NOTES:
ELECTRICAL KEYED NOTES:
A REFER TO ARCHITECTURAL ELEVATIONS FOR ADDITIONAL DETAILS.
ARCHITECTURAL ELEVATIONS (DEMO & NEW) SHOW EXTERIOR DUPLEX
RECEPTACLES, ALARM BELL, ALARM STROBE, CONDENSERS, ETC.
1 REFER TO ENLARGED UNIT STYLE "1" - ELECTRICAL PLAN FOR WORK REQUIRED
IN THIS DWELLING UNIT.
2 REFER TO ENLARGED UNIT STYLE "2" - ELECTRICAL PLAN FOR WORK REQUIRED
IN THIS DWELLING UNIT.
3 MAIN DISTRIBUTION / HOUSE PANEL FOR THIS BUILDING, REFER TO POWER
RISER DIAGRAM.
4 TYPICAL POWER PANEL FOR STYLE "2" APARTMENTS, REFER TO ASSOCIATED
PANEL SCHEDULE.
5 EXTEND TO CIRCUIT INDICATED IN ASSOCIATED APARTMENT PANEL.
6 INSTALL ROOFTOP GFCI, WR RECEPTACLE ADJACENT TO HVAC UNIT. EXTEND 3
#12 TO CIRCUIT BREAKER INDICATED IN HOUSE PANEL "MC" AND MAKE ALL FINAL
POWER CONNECTIONS.
7 EXTEND TO CIRCUIT INDICATED THROUGH PHOTOCELL FOR DUSK-TO-DAWN
OPERATION.
8 NUMBER ADJACENT TO RECEPTACLE INDICATES CIRCUIT NUMBER. EXTEND 3
#12 TO CIRCUIT BREAKER IN HOUSE PANEL "MC" AND MAKE ALL FINAL POWER
CONNECTIONS.
9 TYPICAL POWER PANEL FOR STYLE "1" APARTMENTS, REFER TO ASSOCIATED
PANEL SCHEDULE.
10 CONNECT FIRE SPRINKLER SYSTEM FLOW AND TAMPER SWITCHES TO FIRE
ALARM CONTROL PANEL IN BUILDING "M". PROVIDE FIRE ALARM STROBE ABOVE
DOOR (STROBE ACTIVATED BY LOCAL FLOW & TAMPER SWITCHES).
11 REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATION AND MOUNTING
HEIGHT OF EXTERIOR LIGHTING FIXTURE.
1/8"=1'-0"
ROOF ELECTRICAL PLAN - BUILDING C
NORTH
IECC LIGHTING COMPLIANCE
THE LIGHTING DESIGN SHOWN ON THESE PLANS IS IN COMPLIANCE WITH THE 2009
INTERNATIONAL ENERGY CONSERVATION CODE (IECC) SECTION 505 - ELECTRICAL
POWER AND LIGHTING SYSTEMS AS FOLLOWS:
1. 505.2.2.2 - LIGHTING CONTROLS:
A. THIS PROJECT DOES NOT INCLUDES AREAS LARGER THAN 5,000 SQUARE
FEET.
2. TABLE 505.5.2 - INTERIOR LIGHTING POWER ALLOWANCES: THIS TABLE
LIMITS THE ALLOWABLE LIGHTING POWER DENSITY (LPD) WITHIN A
MULTIFAMILY DWELLING BUILDING TO 0.7 W/SF.
BUILDING "C" AREA IS 5,910 SQ FT, TOTAL ALLOWABLE WATTAGE IS 4,137W.
INTERIOR LIGHTING LOAD = 3,650W. THIS MULTIFAMILY DWELLING BUILDING HAS
AN LPD OF 0.62W/SF AND COMPLIES WITH MAXIMUM ALLOWABLE LPD.
3. TABLE 505.6.2(2) - INDIVIDUAL LIGHTING POWER ALLOWANCES FOR BUILDING
EXTERIORS: THIS TABLE LIMITS EXTERIOR LIGHTING BASED ON ZONE
CLASSIFICATION AND LOCATION OF LIGHTING. THIS BUILDING IS CLASSIFIED
AS ZONE 2: PREDOMINANTLY RESIDENTIAL, NEIGHBORHOOD BUSINESS
DISTRICT. THE EXTERIOR LIGHTING POWER ALLOWANCES ARE:
BASE SITE ALLOWANCE: 600W
PARKING AREAS AND DRIVES: 0.06 W/SF
WALKWAYS LESS THAN 10' WIDE: 0.7 W/LF
SPECIAL FEATURE AREAS: 0.14 W/SF
MAIN ENTRIES: 20W/LINEAR FOOT OF DOOR WIDTH
OTHER DOORS: 20W/LINEAR FOOT OF DOOR WIDTH
EXTERIOR AREA TOTAL ALLOWABLE WATTAGE FOR BLDG "C": 360W.
ACTUAL EXTERIOR LIGHTING LOAD = 112W. THIS BUILDING COMPLIES WITH THE
MAXIMUM EXTERIOR LIGHTING POWER ALLOWANCE.
C
I
E
X
W
M
N
E
0
A
L
O
M
É
AR
C
I
N
I
E
G
A
S
18711
DN
1
APARTMENT 200
(UNIT STYLE "4")
1
APARTMENT 201
(UNIT STYLE "4")
PANEL "A4" 4
4 PANEL "A4"
PANEL "MD"
UP
1
PANEL "A4" 4
APARTMENT 100
(UNIT STYLE "4")
1
APARTMENT 101
(UNIT STYLE "4")
3
4 PANEL "A4"
7
7
8
EUH-1
RISER
-
S
TS
FS
9
TYP
10
TYP
CU-4
5
5
CU-4
CU-4
5
5
CU-4
BUILDING D
ROOF
TO APT. 100
TO APT. 200
TO APT. 101
TO APT. 201
66
ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLYRESERVES THE COMMON LAW COPYRIGHT ASSOCIATEDWITH THESE DRAWINGS, AND THESE DOCUMENTS MAYNOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RDPARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC,INC.
THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ANDARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL ORCOMPONENT REQUIRED FOR A COMPLETE, FULLYOPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S).
ANY CONTRACTOR RELYING ON THESE DOCUMENTSSHALL DO SO ONLY IN CONCERT WITH CURRENT CODECONSIDERATION, FIELD INVESTIGATION/VERIFICATIONAND UTILITY COORDINATION IN ORDER TO PROVIDE ACOMPREHENSIVE INSTALLATION.
PO BOX 93024Albuquerque, NM 87199
505-856-3419
INC.E N G I N E E R S
C O N S U L T I N G
Project #:
Date:
PROJECT ARCHITECT:
By:
File:Sheet of
Plot Date:
AEC-D-ED1.0.DWG
2/12/2015 4:27:19 PM
Housing and Economic Rural OpportunityPase Del Oro ApartmentsLas Cruces, New Mexico
BOB HALL, AIA
IDA-14-01-P
DECEMBER 22, 2014
AEC
101/30/15 REVISION #1.
1/8"=1'-0"
ELECTRICAL PLAN - BUILDING D FIRST FLOOR
NORTH
NTS
KEY PLAN
NORTH
1/8"=1'-0"
ELECTRICAL PLAN - BUILDING D SECOND FLOOR
NORTH
BUILDING D ELECTRICAL PLAN
ED1.0
GENERAL NOTES:
ELECTRICAL KEYED NOTES:
A REFER TO ARCHITECTURAL ELEVATIONS FOR ADDITIONAL DETAILS.
ARCHITECTURAL ELEVATIONS (DEMO & NEW) SHOW EXTERIOR DUPLEX
RECEPTACLES, ALARM BELL, ALARM STROBE, CONDENSERS, ETC.
1 REFER TO ENLARGED UNIT STYLE "4" - ELECTRICAL PLAN FOR WORK REQUIRED
IN THIS DWELLING UNIT.
2 NOT USED.
3 MAIN DISTRIBUTION / HOUSE PANEL FOR THIS BUILDING, REFER TO POWER
RISER DIAGRAM.
4 TYPICAL POWER PANEL FOR STYLE "4" APARTMENTS, REFER TO ASSOCIATED
PANEL SCHEDULE.
5 EXTEND TO CIRCUIT INDICATED IN ASSOCIATED APARTMENT PANEL.
6 INSTALL ROOFTOP GFCI, WR RECEPTACLE ADJACENT TO HVAC UNIT. EXTEND 3
#12 TO CIRCUIT BREAKER INDICATED IN PANEL "MD" AND MAKE ALL FINAL
POWER CONNECTIONS.
7 EXTEND TO CIRCUIT INDICATED THROUGH PHOTOCELL FOR DUSK-TO-DAWN
OPERATION.
8 NUMBER ADJACENT TO RECEPTACLE INDICATES CIRCUIT NUMBER. EXTEND 3
#12 TO CIRCUIT BREAKER IN PANEL "MD" AND MAKE ALL FINAL POWER
CONNECTIONS.
9 CONNECT FIRE SPRINKLER SYSTEM FLOW AND TAMPER SWITCHES TO FIRE
ALARM CONTROL PANEL IN BUILDING "M". PROVIDE FIRE ALARM STROBE ABOVE
DOOR (STROBE ACTIVATED BY LOCAL FLOW & TAMPER SWITCHES).
10 REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATION AND MOUNTING
HEIGHT OF EXTERIOR LIGHTING FIXTURE.
1/8"=1'-0"
ELECTRICAL PLAN - BUILDING D ROOF
NORTH
IECC LIGHTING COMPLIANCE
THE LIGHTING DESIGN SHOWN ON THESE PLANS IS IN COMPLIANCE WITH THE 2009
INTERNATIONAL ENERGY CONSERVATION CODE (IECC) SECTION 505 - ELECTRICAL
POWER AND LIGHTING SYSTEMS AS FOLLOWS:
1. 505.2.2.2 - LIGHTING CONTROLS:
A. THIS PROJECT DOES NOT INCLUDES AREAS LARGER THAN 5,000 SQUARE
FEET.
2. TABLE 505.5.2 - INTERIOR LIGHTING POWER ALLOWANCES: THIS TABLE
LIMITS THE ALLOWABLE LIGHTING POWER DENSITY (LPD) WITHIN A
MULTIFAMILY DWELLING TO 0.7 W/SF.
BUILDING "D" AREA IS 5,444 SQ FT, TOTAL ALLOWABLE WATTAGE IS 3,811W.
INTERIOR LIGHTING LOAD = 3200W. THIS MULTIFAMILY DWELLING BUILDING HAS
AN LPD OF 0.59W/SF AND COMPLIES WITH MAXIMUM ALLOWABLE LPD.
3. TABLE 505.6.2(2) - INDIVIDUAL LIGHTING POWER ALLOWANCES FOR BUILDING
EXTERIORS: THIS TABLE LIMITS EXTERIOR LIGHTING BASED ON ZONE
CLASSIFICATION AND LOCATION OF LIGHTING. THIS BUILDING IS CLASSIFIED
AS ZONE 2: PREDOMINANTLY RESIDENTIAL, NEIGHBORHOOD BUSINESS
DISTRICT. THE EXTERIOR LIGHTING POWER ALLOWANCES ARE:
BASE SITE ALLOWANCE: 600W
PARKING AREAS AND DRIVES: 0.06 W/SF
WALKWAYS LESS THAN 10' WIDE: 0.7 W/LF
SPECIAL FEATURE AREAS: 0.14 W/SF
MAIN ENTRIES: 20W/LINEAR FOOT OF DOOR WIDTH
OTHER DOORS: 20W/LINEAR FOOT OF DOOR WIDTH
EXTERIOR AREA TOTAL ALLOWABLE WATTAGE FOR BLDG "D": 240W.
ACTUAL EXTERIOR LIGHTING LOAD = 140W. THIS BUILDING COMPLIES WITH THE
MAXIMUM EXTERIOR LIGHTING POWER ALLOWANCE.
C
I
E
X
W
M
N
E
0
A
L
O
M
É
ARC
I
N
I
E
G
A
S
18711
SSS SS
S S
S
S
GREAT ROOM
101
10
18
9
18
A
A
D
D
E
CC
F
F
F
C
E
E
B
A
SA
SA
SA
SA
SA
SA
20
S
A
19
19
20
S
A
AA
A A A
A
A
23
RESTROOM 2
106
RESTROOM 1
105
SA
MAILBOXES
A
A
S
S
26
9
9
B
CO
5
5
5
5
5
1414
7
5
5
16
16
16
16
6
PANEL "MM"
12
12
13
15
1
4
1
3
1
11
5
T
V
17
17
17
FM
IWH1
F
F
EF2
EF2
24
F
F
F
F
F
TT
CO
21
CU-M
22
25
ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLYRESERVES THE COMMON LAW COPYRIGHT ASSOCIATEDWITH THESE DRAWINGS, AND THESE DOCUMENTS MAYNOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RDPARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC,INC.
THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ANDARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL ORCOMPONENT REQUIRED FOR A COMPLETE, FULLYOPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S).
ANY CONTRACTOR RELYING ON THESE DOCUMENTSSHALL DO SO ONLY IN CONCERT WITH CURRENT CODECONSIDERATION, FIELD INVESTIGATION/VERIFICATIONAND UTILITY COORDINATION IN ORDER TO PROVIDE ACOMPREHENSIVE INSTALLATION.
PO BOX 93024Albuquerque, NM 87199
505-856-3419
INC.E N G I N E E R S
C O N S U L T I N G
Project #:
Date:
PROJECT ARCHITECT:
By:
File:Sheet of
Plot Date:
AEC-M-EM-1.0.DWG
2/12/2015 4:28:17 PM
Housing and Economic Rural OpportunityPase Del Oro ApartmentsLas Cruces, New Mexico
BOB HALL, AIA
IDA-14-01-P
DECEMBER 22, 2014
AEC
101/30/15 REVISION #1.
1/4"=1'-0"
LIGHTING PLAN - BUILDING M
NORTH
ELECTRICAL KEYED NOTES:
NTS
KEY PLAN
NORTH
BUILDING M ELECTRICAL PLANS
EM-1.01/4"=1'-0"
POWER PLAN - BUILDING M
NORTH
1 GFCI PROTECTED DUPLEX RECEPTACLE, 6" ABOVE COUNTERTOP WITH MAJOR AXIS
HORIZONTAL. SPACE RECEPTACLES PER NEC 210.52(C)(1) FOR EVERY WALL COUNTERTOP
SPACE 12" OR WIDER.
2 GFCI PROTECTED DUPLEX RECEPTACLE, INSTALL 42" AFF.
3 INSTALL GFCI PROTECTED DUPLEX RECEPTACLE BELOW COUNTERTOP FOR CONNECTION OF
DISPOSER.
4 INSTALL GFCI PROTECTED DUPLEX RECEPTACLE BELOW COUNTERTOP FOR CONNECTION OF
DISHWASHER.
5 INSTALL RECEPTACLE WITH MAJOR AXIS HORIZONTAL, 6" ABOVE COUNTERTOP.
6 WEATHER-RESISTANT, GFCI-PROTECTED RECEPTACLE, REFER TO SYMBOL LEGEND. INSTALL
24" AFF.
7 DEDICATED RECEPTACLE FOR REFRIGERATOR, INSTALL 42" AFF.
8 COORDINATE EXACT LOCATION OF PANEL WITH ARCHITECT/OWNER PRIOR TO ROUGH-IN.
9 CEILING PADDLE FAN WITH LIGHT KIT, PROVIDE J-BOX AND SUPPORT FOR FAN PER NEC
314.27(D).
10 CEILING FAN (CF) CONTROL SWITCH, MAKE ALL FINAL LIGHTING AND FAN CONTROL
CONNECTIONS TO ASSOCIATED CEILING FAN UNIT.
11 DEDICATED RECEPTACLE FOR MICROWAVE, INSTALL 6" ABOVE COUNTERTOP. REFER TO
ARCHITECTURAL DRAWINGS FOR EXACT HEIGHT/LOCATION.
INSTALL ROOFTOP GFCI, WR RECEPTACLE ADJACENT TO HVAC UNIT.
23 52" PADDLE FAN BY THE BIG ASS FAN COMPANY, MODEL K3127-A2 WITH L.E.D. MODULE.
24 FIRE ALARM CONTROL PANEL (FACP), REFER TO FIRE ALARM SYSTEM DIAGRAM.
25 SOLAR PANEL (BY OTHERS, INSTALLED BY PHOTOVOLTAIC SYSTEM INSTALLER). REFER TO
SHEET PV-1.00.
26 REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATION AND MOUNTING HEIGHT OF
EXTERIOR LIGHTING FIXTURE.
A. ALL ELECTRICAL WORK SHALL CONFORM TO THE 2014 EDITION OF NATIONAL ELECTRICAL
CODE (NEC).
B. NFPA 72 / FIRE ALARM CODE (1996 EDITION) CHAPTER 2 / HOUSEHOLD FIRE WARNING
EQUIPMENT GOVERNS; SPECIFICALLY 2-2.1.1.1 AND 2-2.3.
C. EACH DWELLING UNIT HAS SINGLE STATION ALARM DEVICE(S) WHICH ALARMS IN THAT
DWELLING UNIT ONLY.
D. LOCATION OF DWELLING UNIT RECEPTACLES IS GOVERNED BY NEC 210.52; SPECIFIC
ATTENTION IS DIRECTED TO EXHIBIT 210.24 AND 210.26.
E. LOCATIONS OF ALL DWELLING UNIT PANELBOARDS SHALL BE FIELD IDENTIFIED AND THE
LOCATIONS FIELD APPROVED BY THE ARCHITECT PRIOR TO ANY ELECTRICAL SYSTEMS
ROUGH-IN.
F. LUMINAIRE AND CEILING PADDLE FAN LOCATIONS SHALL BE FIELD LOCATED BY ARCHITECT
PRIOR TO ANY BRANCH CIRCUIT INSTALLATION.
G. LOCATION OF DEVICES MAY BE ALTERED WITHIN NEC PARAMETERS AND ONLY WITH
ARCHITECT WRITTEN APPROVAL.
H. ALL 120V, 15 AND 20 AMP RECEPTACLES SHALL BE LISTED TAMPER-RESISTANT RECEPTACLES.
GENERAL NOTES:
1/4"=1'-0"
ELECTRICAL PLAN - BUILDING M ROOF (PARTIAL)
NORTH
IECC LIGHTING COMPLIANCE
THE LIGHTING DESIGN SHOWN ON THESE PLANS IS IN COMPLIANCE WITH THE 2009
INTERNATIONAL ENERGY CONSERVATION CODE (IECC) SECTION 505 - ELECTRICAL POWER AND
LIGHTING SYSTEMS AS FOLLOWS:
1. 505.2.2.2 - LIGHTING CONTROLS:
A. THIS PROJECT DOES NOT INCLUDES AREAS LARGER THAN 5,000 SQUARE FEET.
2. TABLE 505.5.2 - INTERIOR LIGHTING POWER ALLOWANCES: THIS TABLE LIMITS THE
ALLOWABLE LIGHTING POWER DENSITY (LPD) WITHIN AN OFFICE BUILDING TO 1.0 W/SF.
BUILDING "M" AREA IS 1,344 SQ FT, TOTAL ALLOWABLE WATTAGE IS 1,344W.
INTERIOR LIGHTING LOAD = 1,300W. THIS OFFICE/COMMONS BUILDING HAS AN LPD OF 0.97W/SF
AND COMPLIES WITH MAXIMUM ALLOWABLE LPD.
3. TABLE 505.6.2(2) - INDIVIDUAL LIGHTING POWER ALLOWANCES FOR BUILDING EXTERIORS:
THIS TABLE LIMITS EXTERIOR LIGHTING BASED ON ZONE CLASSIFICATION AND LOCATION
OF LIGHTING. THIS BUILDING IS CLASSIFIED AS ZONE 2: PREDOMINANTLY RESIDENTIAL,
NEIGHBORHOOD BUSINESS DISTRICT. THE EXTERIOR LIGHTING POWER ALLOWANCES
ARE:
BASE SITE ALLOWANCE: 600W
PARKING AREAS AND DRIVES: 0.06 W/SF
WALKWAYS LESS THAN 10' WIDE: 0.7 W/LF
SPECIAL FEATURE AREAS: 0.14 W/SF
MAIN ENTRIES: 20W/LINEAR FOOT OF DOOR WIDTH
OTHER DOORS: 20W/LINEAR FOOT OF DOOR WIDTH
EXTERIOR AREA TOTAL ALLOWABLE WATTAGE FOR BLDG "M": 360W.
ACTUAL EXTERIOR LIGHTING LOAD = 182W. THIS BUILDING COMPLIES WITH THE MAXIMUM
EXTERIOR LIGHTING POWER ALLOWANCE.
SYSTEM
WITH BATTERIES
TO DEDICATED CIRCUIT MM-11,
PROVIDE CODE REQUIRED
INITIATING CIRCUIT
INDICATING CIRCUIT
INTERFACE RELAY TO VARIOUS
NON-ADDRESSABLE DEVICES
ADDRESSABLE
F F
AUTO-DIALER
T
CONNECT AUTO-DIALER TO TTB,
PROGRAM EMER. CALL NUMBER
PER OWNER'S INSTRUCTION
FIRE ALARM
CONTROL
PANEL
(FACP)
E.O.L.
E.O.L.
E.O.L.
E.O.L.
DIAGRAM IS SCHEMATIC ONLY, NOT
ALL DEVICES SHOWN NECESSARILY USED
FIRE ALARM SYSTEM DIAGRAM
SCALE: NONE
A THE FIRE ALARM CONTRACTOR SHALL EMPLOY THE SERVICES OF A NICET 3 (OR BETTER) FIRE ALARM DESIGNER AND SHALL PROCESS SHOP
DRAWINGS FOR APPROVAL BY THE FIRE MARSHAL. ALL DEVICES REQUIRED BY CODE AND/OR THE AHJ, WHETHER OR NOT SHOWN ON THIS
DRAWING, SHALL BE THE RESPONSIBILITY OF THE FIRE ALARM CONTRACTOR AND SHALL BE INSTALLED AT NO ADDITIONAL COST.
B ALL DEVICES SHALL BE SUITABLE FOR THE ENVIRONMENT IN WHICH THEY ARE LOCATED AND APPROPRIATELY U.L. LISTED WHENEVER APPLICABLE.
C SMOKE DETECTORS SHALL NOT BE LOCATED WITHIN 36" OF ANY AIR REGISTER (SUPPLY OR RETURN).
D PULL STATIONS: PULL STATIONS ARE REQUIRED AT EVERY EXTERIOR MEANS OF EGRESS. MOUNT 3'-5" - 4'-5" TO CENTER OF DEVICE, LOCATE
WITHIN 5' OF EXTERIOR DOOR. MAXIMUM TRAVEL BETWEEN PULL STATIONS IS 200 '.
E WALL MOUNTED STROBES AND HORN/STROBES SHALL BE LOCATED SO THE ENTIRE LENS IS BETWEEN 80" AND 96" AFF
F IN CORRIDORS STROBES AND HORN/STROBES SHALL BE LOCATED WITHIN 15'-0" OF THE END OF THE CORRIDOR AND NOT MORE THAN 100'-0" APART.
G INSTALL MONITOR MODULES AT EACH FLOW AND TAMPER SWITCH (INCLUDING DAMPERS AND P.I.V.'S). VERIFY LOCATIONS WITH MECHANICAL AND
FIRE SPRINKLER DRAWINGS PRIOR TO INSTALLATION.
H INSTALL DUCT DETECTORS ON THE RETURN SIDE OF ALL AIR HANDLING UNITS RATED OVER 2000 CFM. COORDINATE OPERATING VOLTAGE PRIOR TO
INSTALLATION. DUCT DETECTORS SHALL BE FURNISHED BY FIRE ALARM CONTRACTOR AND INSTALLED BY MECHANICAL CONTRACTOR.
I ELECTRICAL CONTRACTOR SHALL INSTALL ALL 3/4" CONDUIT REQUIRED FOR FIRE ALARM SYSTEM. ALL CONDUIT SHALL BE RED OR HAVE RED
BANDING EVERY 5'-0". BUSH ALL EXPOSED CONDUIT ENDS.
J ALL CONDITIONS THAT APPLY SHALL COMPLY WITH NFPA 72.
K FIRE ALARM SYSTEM SHALL HAVE A MINIMUM 1 YEAR WARRANTY ON ALL PARTS AND INSTALLATION. UPON COMPLETION OF INSTALLATION AND
TRAINING THE CONTRACTOR SHALL GIVE THE OWNER A COMPLETE COPY OF THE FIRE ALARM PROGRAMMING MANUAL (INCLUDING PASSWORDS).
L FIRE ALARM CONTRACTOR SHALL HAVE A MINIMUM OF 5 YEARS EXPERIENCE AND UPON REQUEST DEMONSTRATE AT LEAST 3 PAST PROJECTS OF
SIMILAR SCALE AND SCOPE. CONTRACTOR SHALL PROVIDE 24 HOUR EMERGENCY RESPONSE SERVICES DURING THE WARRANTY PERIOD AT NO
ADDITIONAL COST TO THE OWNER. INSTALLER SHALL BE RESPONSIBLE FOR CABLING, TERMINATIONS, PROGRAMMING, ETC... "PARTS & SMARTS"
JOINT VENTURES ARE UNACCEPTABLE.
M FIRE ALARM CONTRACTOR SHALL HAVE 20 CALENDAR DAYS FROM NOTICE OF AWARD TO PRODUCE JOB SPECIFIC SHOP DRAWINGS AND SUBMIT
THEM TO THE FIRE MARSHAL FOR APPROVAL.
N SMOKE DETECTORS IN RESIDENCES SHALL BE INSTALLED PER NFPA 72. SMOKE DETECTORS WITH INTEGRAL ALARM SHALL BE LOCATED IN EACH
BEDROOM, OUTSIDE EACH SLEEPING AREA, AND ON EVERY FLOOR LEVEL. THE SMOKE DETECTORS SHALL BE INTERCONNECTED SO THAT WHEN
ONE SOUNDS, THEY ALL SOUND.
FIRE ALARM GENERAL NOTES:
SUCH AS TAMPER AND FLOW SWITCHES
AT ALL (7) BUILDINGS, REFER TO SITE PLAN.
LOCK-OUT CLIP AT CIRCUIT BREAKER
C
I
E
X
W
M
N
E
0
A
L
O
M
É
AR
C
I
N
I
E
G
A
S
18711
2
2
18
12
T
V
S
S
17
T
V
T
V
17
F
F
8
21
6
4
5
11
SS
PANEL "A1"
7
S
19
7
STORAGE
110
STORAGE
111
BEDROOM 2
106
BEDROOM 1
102
LIVING
109
DINING
108
BATH
104
LINEN
103
MECH
101
PORCH
KITCHEN
107
LAUNDRY
105
W
D
20
22
1
IWH13
F2
9
6
6
6
23
17
24
25
EF3
26
(UNIT 103 ONLY)
26(UNIT 106 ONLY)
18
4
S
T
V
T
V
2
2
7
8
6
T
V
11
F
PANEL "A3"
LIVING
102
PORCH
DINING
103
BEDROOM 1
106
KITCHEN
107
LAUNDRY
104
STORAGE
108
17
S
9
21
1
6
5
6
6
6
20
22
23
W
D
24
BATH 1
105
B
25
EF3
S
17
26
12
(UNITS 106, 107, 115 ONLY)
S
DECK
BEDROOM 2
111
T
V17
17
T
V
18
7
F
BEDROOM 3
114
MECH.
110
BATH
112
STORAGE
109
STAIRS
101
HALLWAY
113
19
IWH13
F3
23
24
17
S
EF1
26
(UNITS 106, 107, 115 ONLY)
T
V
54
8
SS
T
V
S
SS
F
F
H
T
V
S
S
S
17
17
PANEL "A4"
17
17
S
S
19
S
F
SS
SS
SS
11
LIVING
PORCH
DINING
23
20
22
21
W
D
1
IWH13
F4
9
6
6
6
17
C
B
B
B
G
SD
E
E
B
K
H
G
25
B
14
EF3
EF3
12
7
18
T
V
T
V
SS
12
6
8
5
T
V
F
F
SS
11
17
PANEL "A2"
17
4
S
2
SS
SS
2
KITCHEN
109
DINING
110
BEDROOM 2
106
BEDROOM 1
105
BATH
104
DECK
LIVING ROOM
102
MECH.
101
LINEN
108
PANTRY
107
LAUNDRY
103
19IWH1
3F2
22
20
9
21
1
6
6
23
W/D
17
24
25
EF3
ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLYRESERVES THE COMMON LAW COPYRIGHT ASSOCIATEDWITH THESE DRAWINGS, AND THESE DOCUMENTS MAYNOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RDPARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC,INC.
THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ANDARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL ORCOMPONENT REQUIRED FOR A COMPLETE, FULLYOPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S).
ANY CONTRACTOR RELYING ON THESE DOCUMENTSSHALL DO SO ONLY IN CONCERT WITH CURRENT CODECONSIDERATION, FIELD INVESTIGATION/VERIFICATIONAND UTILITY COORDINATION IN ORDER TO PROVIDE ACOMPREHENSIVE INSTALLATION.
PO BOX 93024Albuquerque, NM 87199
505-856-3419
INC.E N G I N E E R S
C O N S U L T I N G
Project #:
Date:
PROJECT ARCHITECT:
By:
File:Sheet of
Plot Date:
AEC-EU-1.0 UNIT PLANS.DWG
2/12/2015 4:29:14 PM
Housing and Economic Rural OpportunityPase Del Oro ApartmentsLas Cruces, New Mexico
BOB HALL, AIA
IDA-14-01-P
DECEMBER 22, 2014
AEC
101/30/15 REVISION #1.
TYPICAL UNIT ELECTRICAL PLANS
EU-1.0
1/4"=1'-0"
UNIT STYLE "1" - ELECTRICAL PLAN
1
1/4"=1'-0"
UNIT STYLE "2" - ELECTRICAL PLAN
2
1/4"=1'-0"
UNIT STYLE "3" - SECOND FLOOR ELECTRICAL PLAN
4
1/4"=1'-0"
UNIT STYLE "3" - FIRST FLOOR ELECTRICAL PLAN5
1/4"=1'-0"
UNIT STYLE "4" - ELECTRICAL PLAN
3
ELECTRICAL KEYED NOTES:
1
.
2 SPLIT-WIRED RECEPTACLE, CONNECT TOP HALF OF DUPLEX RECEPTACLE FOR SWITCH
CONTROL.
3
4 INSTALL GFCI PROTECTED DUPLEX RECEPTACLE BELOW COUNTERTOP FOR CONNECTION
OF DISPOSER.
5 INSTALL GFCI PROTECTED DUPLEX RECEPTACLE BELOW COUNTERTOP FOR CONNECTION
OF DISHWASHER.
6 INSTALL KITCHEN COUNTERTOP RECEPTACLE HORIZONTALLY, 6" ABOVE COUNTERTOP
(AC). SPACE RECEPTACLES PER NEC 210.52(C)(1) FOR EVERY WALL COUNTERTOP SPACE
12" OR WIDER.
7 WEATHER-RESISTANT, GFCI-PROTECTED RECEPTACLE, REFER TO SYMBOL LEGEND.
INSTALL 24" AFF.
8 POWER J-BOX FOR CONNECTION TO RANGE HOOD.
9 TYPICAL APARTMENT PANEL FOR THIS UNIT STYLE, REFER TO ASSOCIATED PANEL
SCHEDULE.
10 NUMBER ADJACENT TO RECEPTACLE INDICATES CIRCUIT NUMBER. EXTEND 3 #12 TO
CIRCUIT BREAKER IN ASSOCIATED APARTMENT PANEL AND MAKE ALL FINAL POWER
CONNECTIONS.
11 DOOR CHIME, INSTALL 6'-6" AFF TO CENTER. CONNECT ASSOCIATED BELL SYSTEM 24V
TRANSFORMER TO NEAREST UNSWITCHED 120V RECEPTACLE CIRCUIT AND MAKE ALL
FINAL POWER AND CONTROL CONNECTIONS.
12 DOOR CHIME SYSTEM PUSH BUTTON (SUPPLIED AS PART OF DOOR CHIME PACKAGE).
13 CEILING PADDLE FAN WITH LIGHT KIT, PROVIDE J-BOX AND SUPPORT FOR FAN PER NEC
314.27(D).
14 FAN SPEED CONTROL SWITCH FURNISHED WITH CEILING PADDLE FAN, MAKE ALL FINAL
CONTROL CONNECTIONS TO ASSOCIATED FAN (CONTROL LIGHTING INDEPENDENTLY AS
SHOWN).
15 DEDICATED RECEPTACLE FOR MICROWAVE, INSTALL IN CASEWORK. REFER TO
ARCHITECTURAL DRAWINGS FOR EXACT HEIGHT/LOCATION.
16 ALL DWELLING UNIT 120V, 15 AND 20A RECEPTACLES SHALL BE TAMPER-RESISTANT.
17 120V COMBINATION SMOKE DETECTOR/
DEDICATED RECEPTACLE FOR REFRIGERATOR, INSTALL 42" AFF
A. ALL ELECTRICAL WORK SHALL CONFORM TO THE 2014 EDITION OF NATIONAL ELECTRICAL
CODE (NEC).
B. PROVIDE HOUSEHOLD FIRE WARNING EQUIPMENT IN CONFORMANCE WITH NFPA 72 / FIRE
ALARM CODE (1996 EDITION) CHAPTER 2; SPECIFICALLY 2-2.1.1.1 AND 2-2.3.
C. EACH DWELLING UNIT HAS SINGLE STATION ALARM DEVICE(S) WHICH ALARMS IN THAT
DWELLING UNIT ONLY.
D. THE LOCATION OF DWELLING UNIT RECEPTACLES SHALL CONFORM TO NEC 210.52.
E. LOCATIONS OF ALL DWELLING UNIT PANELBOARDS SHALL BE FIELD APPROVED BY THE
ARCHITECT PRIOR TO ANY ELECTRICAL SYSTEMS ROUGH-IN.
F. LUMINAIRE AND CEILING PADDLE FAN LOCATIONS SHALL BE FIELD APPROVED BY THE
ARCHITECT PRIOR TO ANY BRANCH CIRCUIT INSTALLATION.
G. DEVICE LOCATION AS SHOWN ON DRAWINGS IS SOMEWHAT SCHEMATIC AND MAY BE
ALTERED WITHIN NEC PARAMETERS AND AS FIELD CONDITIONS REQUIRE. ANY DEVICE
RELOCATION GREATER THAN 12" REQUIRES ARCHITECT'S WRITTEN APPROVAL.
H. ALL 120V, 15 AND 20 AMP RECEPTACLES SHALL BE LISTED TAMPER-RESISTANT
RECEPTACLES.
I. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER (AFCI) PROTECTION FOR 15 AND 20 AMP
BRANCH CIRCUITS AS REQUIRED BY NEC 210.12.
GENERAL NOTES:
ESP-1.0
ELECTRICAL SPECIFICATIONS
ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLYRESERVES THE COMMON LAW COPYRIGHT ASSOCIATEDWITH THESE DRAWINGS, AND THESE DOCUMENTS MAYNOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RDPARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC,INC.
THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ANDARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL ORCOMPONENT REQUIRED FOR A COMPLETE, FULLYOPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S).
ANY CONTRACTOR RELYING ON THESE DOCUMENTSSHALL DO SO ONLY IN CONCERT WITH CURRENT CODECONSIDERATION, FIELD INVESTIGATION/VERIFICATIONAND UTILITY COORDINATION IN ORDER TO PROVIDE ACOMPREHENSIVE INSTALLATION.
PO BOX 93024Albuquerque, NM 87199
505-856-3419
INC.E N G I N E E R S
C O N S U L T I N G
Project #:
Date:
PROJECT ARCHITECT:
By:
File:Sheet of
Plot Date:
AEC-ESP-1.0-SPECS.DWG
2/12/2015 4:30:57 PM
Housing and Economic Rural OpportunityPase Del Oro ApartmentsLas Cruces, New Mexico
BOB HALL, AIA
IDA-14-01-P
DECEMBER 22, 2014
AEC
101/30/15 REVISION #1.
SECTION 26 0500- BASIC ELECTRICAL MATERIALS AND METHODS
PART 1 GENERAL
1.1 RELATED DOCUMENTS
A The Contractor shall make a thorough field investigation of all work described above and shown
on the contract drawings prior to submitting a bid on this project to ensure the bid is complete
and comprehensive.
1.2 SUMMARY
A This Section includes the following electrical materials and methods:
1. Building wire, connectors, and splices for branch circuits and feeders.
2. Supporting devices for electrical components.
B Furnish all labor and materials necessary for complete electrical service to all equipment which
requires electric connections installed as part of this project. Provide temporary electric power of
1.3 ELECTRICAL SPECIFICATION INDEX
26 0500 - Basic Electrical Materials and Methods
26 0533 - Raceways and Boxes
26 2816 - Enclosed Switches and Circuit Breakers
26 2416 - Panelboards
1.4 SUBMITTALS
A General: Electrical submittals shall be provided. The Contractor shall provide submittal
information for:
1. Panelboards
2. Safety switches
3. Fuses
4. Light Fixtures
5. Occupancy Sensors (Controls)
6. Fire Alarm
1.5 QUALITY ASSURANCE
A Comply with the 2011 edition of NFPA 70 (NEC) for components and installation.
1.6 DRAWINGS
A All drawings included in the Contract Documents are to be considered as part of the work.
Architectural drawings shall take precedence over electrical drawings.
B As-built drawings: During project construction, the Contractor shall maintain an accurate record
of the installation of all electrical work, carefully noting any deviations from the contract
drawings. Upon project completion, the Contractor shall transfer all as-built information to a
single neat and legible drawing set.
C Upon completion of the fire alarm system installation, the contractor shall give the owner a complete
copy of the fire alarm programming manual (including passwords).
PART 2 - PRODUCTS
2.1 EQUIPMENT REQUIREMENTS
A The electrical equipment connections on the drawings are based on specific equipment
and models. Any additional costs resulting from any changes in equipment furnished will
be the complete responsibility of the Division furnishing the equipment.
2.2 BUILDING WIRE
A Description: Single conductor, copper. Solid conductor for No. 10 AWG and smaller; stranded
conductor for larger than No. 10 AWG.
2.3 SUPPORTING DEVICES
A Channel and angle support systems, hangers, anchors, sleeves, brackets, fabricated items, and
fasteners are designed to provide secure support from the building structure for electrical
components.
1. Material: Steel, except as otherwise indicated, protected from corrosion with zinc coating or
with treatment of equivalent corrosion resistance using approved alternative finish or
inherent material characteristics.
2. Metal Items for Use Outdoors or in Damp Locations: Hot-dip galvanized steel, except as
otherwise indicated.
B Steel channel supports have 9/16-inch diameter holes at a maximum of 8 inches o.c., in at least 1
surface.
1. Fittings and accessories mate and match with channels and are from the same
manufacturer.
C Nonmetallic Channel and Angle Systems: Structural-grade, factory-formed, fiberglass-resin
channels and angles with 9/16-inch diameter holes at a maximum of 8 inches o.c., in at least one
surface.
1. Fittings and accessories shall mate with channels or angles and be of the same manufacturer.
2. Fitting and Accessory Material: Same as channels, except metal items may be stainless steel.
2.4 ELECTRICAL IDENTIFICATION
A Color code all wiring as follows: For 120/240V:
Phase A-Black; Phase B-Red; Neutral-White; Ground-Green.
2.5 TOUCH-UP PAINT
A For Equipment: Provided by equipment manufacturer and selected to match equipment finish.
B For Non-equipment Surfaces: Matching type and color of undamaged, existing adjacent finish.
PART 3 - EXECUTION
3.1 EQUIPMENT INSTALLATION REQUIREMENTS
A Where components and equipment are indicated to be installed, the term "install" includes all
work, materials, and associated accessories necessary to obtain a completely operational system.
B Install items level, plumb, and parallel and perpendicular to other building systems and
components, except where otherwise indicated.
3.2 WIRING METHODS
A Feeders: Type THHN/THWN, in copper conductor, RHW or XHHW in aluminum conductor, in
raceway, except as otherwise indicated. Branch Circuits: Type THHN/THWN, in raceway or type
MC Cable or type NM, NMC or NMS where allowed by NEC and State of New Mexico codes.
B Type MC cable shall be acceptable where in compliance with current NEC.
3.3 ELECTRICAL SUPPORTING METHODS
A Damp Locations and Outdoors: Hot-dip galvanized materials.
B Dry Locations: Steel materials.
C Strength of Supports: Adequate to carry all present and future loads, times and safety factor of at
least 4; 200-lb-minimum design load.
3.4 INSTALLATION
A Install conductors according to manufacturer's written instructions and NECA's "Standard
of Installation". Coordinate special systems work with Owner and Cabling Contractor.
B Conductor Splices: Keep to the minimum possible.
C Install devices to securely and permanently fasten and support electrical components.
D Raceway Supports: Comply with NFPA 70 and the following requirements:
1. Conform to manufacturer's recommendations for selecting and installing supports.
E Fire stopping: Apply to cable and raceway penetrations of fire-rated floor and wall assemblies.
Perform fire stopping to reestablish the original fire-resistance rating of the assembly at the
penetration.
F Fastening: Unless otherwise indicated, securely fasten electrical items and their supporting
Install identification devices where required.
1. Install labels where indicated and at locations for best convenience of viewing.
3.5 CUTTING AND PATCHING
A Cut, channel, chase, and drill floors, walls partitions, ceilings, and other surfaces necessary for
electrical installations. Perform cutting by skilled mechanics of the trades involved.
B General Contractor shall repair disturbed surfaces to match adjacent undisturbed surfaces.
3.6 TESTING
A Perform complete testing on all systems to ensure proper operation.
END OF SECTION 26 0500
SECTION 26 0533 - RACEWAYS AND BOXES
PART 1 GENERAL
1.1 SECTION INCLUDES
A Conduits and fittings
B Outlet boxes
1.2 QUALITY ASSURANCE
A Comply with the 2011 National Electrical Code (NEC) for installation.
PART 2 PRODUCTS
2.1 COATINGS
A Provide products with zinc coating or with treatment of equivalent corrosion resistance.
2.2 ELECTRICAL METALLIC TUBING AND FITTINGS (EMT)
A Furnish galvanized electrical metallic tubing (EMT) that meets the requirements of UL797 -
Electrical Metallic Tubing, NEMA C80.3 - Steel Electrical Metallic Tubing (EMT).
B Furnish compression or set-screw type fittings that meet the requirements of UL514B - Fittings
for Conduit and Outlet Boxes, and ANSI/NEMA FB1 - Fittings, Cast Metal Boxes, and Conduit
Bodies for Conduit and Cable Assemblies. Furnish insulated throat connectors.
2.3 FLEXIBLE METAL CONDUIT AND FITTINGS
A Furnish galvanized steel flexible metal conduit that meets the requirements of UL1 - Flexible
Metal Electrical Conduit.
2.4 OUTLET BOXES
A Provide outlet boxes selected for specific installations using the guidance in NEMA OS 3, Selection
and Installation Guidelines for Electrical Outlet Boxes, and the requirements of this Selection.
B For dry locations provide galvanized steel outlet boxes that comply with UL Standard 514-A -
Metallic Outlet Boxes and ANSI/NEMA OS1 - Sheet-Steel Outlet Boxes, Device Boxes, Device
Boxes, Covers, and Box Supports.
C For damp or wet locations and for surface-mounted RMC or IMC raceways systems, provide
outlet boxes that comply with UL Standard 498 and 514, ANSI/NEMA FB1.
2.5 PULL AND JUNCTION BOXES
A For dry locations in clean, non-contaminated environments use galvanized sheet steel pull and
junction boxes that comply with UL Standard 50 Type 1 and the NEC as to size and construction.
Use boxes not less than 4 inches square x 1-1/2 inches deep with screw-secured covers. Provide
larger boxes as required by the number and size of conduits and conductors.
B For damp or wet, non-corrosive locations, in conduit runs 1 inch trade size and larger, provide
galvanized sheet-steel pull and junction boxes and covers that comply with UL 50 Type 3R.
PART 3 EXECUTION
3.1 EXAMINATION
A Examine surfaces to receive raceways and boxes for compliance with installation tolerances and
other conditions affecting performance of the raceway system. Do not proceed with installation
until unsatisfactory conditions have been corrected.
3.2 GENERAL
A Install raceways and boxes according to NECA 1 Standard Practices for Good Workmanship in
Electrical Construction.
B Raceway termination points and box locations shown on the Drawings are in approximate
locations unless dimensioned. Verify locations before rough-in.
C Ground and bond raceways and boxes as required by the NEC.
D Support raceways and boxes in accordance with the NEC. Arrange raceways and boxes to
maintain headroom and present a neat, workmanlike appearance.
3.3 CONDUIT INSTALLATION
A For wiring systems less than 1000 volts use conduit materials in accordance with the NEC.
B Use 3/4-inch or larger conduit to enclose multiple conductors larger than 12 AWG. For
C Conceal conduits within walls, floors and ceilings.
D Install insulating bushing or connectors with an insulated throat to protect conductors or cables
at conduit terminations.
E Join nonmetallic conduit using cement as recommended by manufacturer.
F Install plastic-coated RMC and fittings according to the NEC and manufacturer's instructions. Use
only fittings approved for use with that material. Patch all nicks and scrapes in PVC coating after
installing conduits.
G Do not use RNC 90 degree elbows larger than 3 inch trade size; use plastic-coated RMC,
tape-wrapped RMC, or tape-wrapped IMC for 3-1/2 inch trade size and larger 90 degree elbows.
H Maintain the following minimum clearances between conduit and surfaces with temperatures
exceeding 104 degrees F (40 degrees C):
1. 6" at perpendicular crossings, 12" between parallel runs.
3.5 OUTLET BOX INSTALLATION
A Install outlet boxes with centers at the following heights unless noted otherwise on the Drawings:
1. Receptacles, general use duplex type: 18 inches to center of j-box above finished floor (AFF).
3. Light switches: center 44 inches AFF to center and within 6 inches of door frame.
5. Fire alarm audible/visible alarm devices: center of strobe light 80 inches AFF or 6 inches below
the ceiling, whichever is lower.
6. Fire alarm pull stations: center 44 inches AFF to center.
B Install a multi-gang box where more than one device is mounted together. Do not use sectional
type boxes. Mount multiple controls as close together as possible and in-line with each other.
C Install box with plaster ring for single or multiple device outlets.
D Use flush mounted outlet boxes in finished areas.
F Install a blank cover plate on each outlet box in which no device is installed.
3.6 CLEANING
A Clean interior of boxes to remove dust, debris, and other material.
B Repair damage to galvanized finishes with zinc-rich paint recommended by manufacturer.
C Repair damage to paint finishes with matching touch-up paint.
END OF SECTION 26 0533
SECTION 26 2816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS
PART 1 GENERAL
1.1 SECTION INCLUDES
A Safety switches, fuses, enclosed circuit breakers.
1.2 SUBMITTALS
A Submit the following:
1. Product Data: Submit manufacturer's technical data for each type of safety switch and
enclosed circuit breaker.
1.3 QUALITY ASSURANCE
A Comply with the 2011 National Electrical Code (NEC) for components and installation.
B Provide safety switches and circuit breaks that are listed and labeled by a Nationally Recognized
Testing Laboratory (NRTL) for the application, installation condition, and the environment in
which installed.
C Comply with the following standards as applicable:
1. NEMA AB 1 (UL 489) Molded Case Circuit Breakers, Molded Case Switches, and Circuit
Breaker Enclosures; UL 50 - Enclosures for Electrical Equipment.
PART 2 PRODUCTS
2.1 SAFETY SWITCHES
A Provide NRTL-listed, NEMA KS 1 Type HD safety switches with ratings and number of poles as
indicated on the Drawings. Use Type HD for switches rated 100A and above.
B Provide safety switches for use as service equipment that are NRTL labeled for the application.
C Provide enclosure type in accordance with NEMA ratings as required by the conditions of use.
D For fusible safety switches provide rejection clip designed to accommodate NEMA FU 1, Class R.
E Furnish each safety switch with an equipment ground bar.
F Furnish a neutral bar for each safety switch used on a circuit that includes a grounded "neutral"
G Provide each safety switch with a factory-installed cover-mounted viewing window positioned
over the blades to allow visual verification of ON-OFF status.
H Provide auxiliary electrical interlock switches with safety switches as indicated on the Drawings
or as required by the application.
2.2 FUSES
A Provide NRTL-listed, NEMA FU 1 Class R fuses for fusible safety switches as indicated on the
Drawings or required by the manufacturer of served equipment.
2.3 ENCLOSED CIRCUIT BREAKERS
A Provide NRTL-listed, NEMA AB 1 enclosed molded-case circuit breakers with ratings and number
of poles and indicated on the Drawings.
PART 3 EXECUTION
3.1 EXAMINATION
A Examine surfaces to receive safety switches and enclosed circuit breakers for compliance with
installation tolerances and other conditions affecting performance of the product. Do not proceed
with installation until unsatisfactory conditions have been corrected.
3.2 INSTALLATION
A Install safety switches and enclosed circuit breakers where indicated on the Drawings and
according to manufacturer's instructions, NECA 1, and the NEC. Have the manufacturer's
installation instruction available at the construction site.
B Install each safety switch and enclosed circuit breaker so the interlock bypass will be accessible.
C Provide supports and seismic anchorage in accordance with the manufacturer's installation
instructions.
D Ground and bond safety switches and enclosed circuit breakers as required by NEC.
E Install conduits as required in Section 26 0533 Raceways and Boxes for Electrical Systems.
F Install conductors as follows:
1. Use compression type lugs to connect all service feeders.
2. Tighten electrical connectors and terminals to the manufacturer's published torque
tightening values. Where manufacturer's torque values are not indicated, use those
specified in UL 486A.
G Install fuses in fusible safety switches as indicated on the Drawings or as required to match
installed motor or load characteristics.
3.3 IDENTIFICATION
A Identify safety switches and enclosed circuit breakers with unit name and circuit number.
3.4 FIELD QUALITY CONTROL
A Clean interior and exterior of safety switches and enclosed circuit breakers.
B Verify that ratings for safety switches and enclosed circuit breakers match values indicated on
the Drawings.
SECTION 26 2416 - PANELBOARDS
PART 1 GENERAL
A Power panelboards
1.2 SUBMITTALS
A Submit the following:
1. Catalog data: Submit catalog data describing each type panelboard, accessory item,
and component specified. Include data substantiating that materials comply with
specified requirements.
1.3 QUALITY ASSURANCE
A Comply with the 2011 National Electrical Code (NEC) for installation.
PART 2 PRODUCTS
2.1 PANELBOARDS, GENERAL REQUIREMENTS
A Provide panelboard cabinets for flush or surface mounted as indicated on the Drawings.
1. Furnish NEMA Type 1 enclosures, except where the Drawings indicate the following
enclosure requirements: NEMA 3R - Raintight
2. Provide galvanized steel cabinets constructed according to UL 50 requirements.
B Provide trim fronts that meet the strength and rigidity requirements of UL 50.
1. Fronts for flush panels shall overlap boxes at least 1 inch.
2. Fronts shall have ANSI 49 medium gray enamel.
3. For NEMA 1 panelboards, provide fronts with hinged trim construction having a piano
hinge down one side. The front shall contain a smaller lockable door, which when open,
shall provide access to all conductors and wiring terminals.
4. Provide a metal panelboard directory frame mounted inside the panelboard door.
C Panelboard phase and neutral bus shall be copper.
D Provide copper equipment ground bus that is adequate for feeder and branch circuit equipment
ground conductors. Bond ground bus to cabinet.
E Provide thermal-magnetic circuit breakers that meet the requirements of UL 489 Molded Case
Circuit Breakers and NEMA AB 1 Molded Case Circuit Breakers and Molded Case Switches.
2.2 LIGHTING AND APPLIANCE PANELBOARDS
A Provide lighting and appliance branch circuit panelboards as indicated on the Drawings.
B Lighting and appliance branch circuit panelboards enclosures shall be not less than 20 inches or
more than 26 inches in width.
C Manufacturers:
1. Cutler-Hammer: PRL3a (480Y/277V) and PRL1a and PRL2a (208Y/120V or 120/240V).
2. General Electric: Spectra (480Y/277V) and AQ (208Y/120V or 120/240V).
3. Siemens: P2 (480Y/277V) and P1 (208Y/120V or 120/240V).
4. Square D: I-Line (480Y/277V) and NQOD (208Y/120V or 120/240V).
2.3 LIGHTING AND APPLIANCE LOAD CENTERS
A Provide lighting and appliance branch circuit load centers as indicated on the Drawings.
B Load centers identified for use as service equipment are to be labeled for this application.
C A directory label shall be provided with circuits identified as indicated on the schedule.
D Bus bar connections to the branch circuit breakers shall be the distributed phase type and shall
accept plug on circuit breakers.
E Manufacturers:
1 Cutler Hammer, General Electric, Siemens or Square D
PART 3 EXECUTION
A Examine surfaces to receive panelboards for compliance with installation tolerances and other
installation instructions.
3.2 INSTALLATION
A Install panelboards where indicated on the Drawings and according to manufacturer's
instructions, NECA 407, and the NEC.
B Ground and bond panelboards as required by NEC.
C At all flush panelboards install four 1-inch spare conduits, extend to above accessible ceiling space.
3.3 IDENTIFICATION
A Provide typewritten circuit directories for each branch circuit panel board. Revise directories to
reflect ANY field circuiting changes.
3.4 FIELD QUALITY CONTROL
A Clean, inspect, test, and energize installed panelboards in accordance with NECA 407.
B After completing installation, cleaning, and testing, touch-up any scratches to match finish.
END OF SECTION 26 2916
END OF SECTION 26 2816
3.1 EXAMINATION
1.1 SECTION INCLUDES
4. Thermostats: center 44 inches AFF to center.
C Upsize circuits and feeders as necessary to limit overall voltage drop to the furthest outlet on a
branch circuit to 5% maximum.
B Fuses shall be dual element Buss Fusetrins unless noted otherwise.
C Safety switches rated 100A and above shall be heavy-duty rated.
Where shown within two feet of each other, group voice/data outlets and receptacles together.
2. Voice/data outlets: 18 inches AFF to center.
3.8 TOUCH-UP PAINT
A Thoroughly clean damaged areas and provide primer, intermediate, and finish coats.
I Install pull string in all empty and spare conduits.
B Provide plastic nameplates for power panels. Nameplate to include panel designation, voltage,
and phase, e.g. PANEL "MM" / 120/240V / 1-PHASE.
3.7 TRAINING
A Instruct Owner's personnel in the proper operation of electrical systems.
sufficient capacity to allow construction.
home-run circuits, conduit shall be a minimum of 3/4".
D Home-run conduits (all conduits connected to a panel) shall be a minimum of 3/4 inch.
J Any conduit run below slab on grade shall be a minimum of 6" below slab.
conductor.
B Provide a lime green spare fuse cabinet with "Fuses" stenciled in OSHA purple. Cabinet shall be
sized to hold one set of (2) fuses of each size used on this project.
H Install spare fuse cabinet in main electrical room or alternate location as shown on Drawings.
PART 1 GENERAL
1.1 SUMMARY
A. SECTION INCLUDES
1. Receptacles, Snap switches, Dimmer switches, Wall plates, Multi-outlet assemblies.
1.2 QUALITY ASSURANCE
A. Furnish products listed and labeled by a nationally recognized testing laboratory (NRTL) for the
PART 2 PRODUCTS
2.1 RECEPTACLES
A. 120V convenience duplex receptacles connected to general use branch circuits: Provide
straight-blade NEMA 5-15R, 15A, duplex receptacles. Use "Decora" style, ivory-colored
receptacles.
B. 120V ground fault circuit interrupter (GFCI) receptacles: Provide straight-blade NEMA 5-15R, 15A,
feed-through type, self-testing GFCI, duplex receptacles that meet the requirements of UL
Standard 943, Ground Fault Circuit Interrupters.
C. 120V exterior duplex receptacles: Provide GFCI type with integral weather-resistant (WR) cover
D. Dedicated duplex receptacles: Provide 20A rated device.
2.4 SNAP SWITCHES
A. Provide single pole, double pole, three-way, four-way and pilot handle snap switches as indicated
on the Drawings. Use "Decora" style, ivory-colored switches.
B. Switches shall be rated 20A, 120-277 volts AC, back and side wired, screw pressure terminal,
quiet type AC switch with yoke grounding screw.
2.5 WALLBOX DIMMING CONTROLS
A. Dimmer wattage rating shall exceed connected load by 10 percent minimum, contractor shall verify
load indicated on the Drawings matches actual fixtures/lamps supplied.
2.6 WALL PLATES
A. For flush mounted interior receptacles and wall switches, provide compatible nylon cover plate,
ivory in color.
PART 3 EXECUTION
3.1 PREPARATION
A. Verify outlet boxes are installed at proper locations and heights.
3.2 INSTALLATION
A. Install devices plumb, level, and secure.
B. All duplex receptacles in dwelling units shall be tamper-resistant in accordance with NEC 406.12.
C. All duplex receptacles in dwelling units shall be AFCI protected in accordance with NEC 210.12.
D. All duplex receptacles within 6' of a sink or bathtub/shower stall, in bathrooms, in garages, and in
laundry area shall be GFCI protected in accordance with NEC 210.8.
E. Install wall plates on each switch, receptacle, and blank outlet after painting is complete.
F. Install GFCI-protected slave receptacle for electric drinking fountains (EDF) per NEC 422.52
concealed within EDF cabinet.
3.4 IDENTIFICATION
A. Identify wiring devices with circuit number written on back of cover plate using permanent ink pen.
3.5 FIELD QUALITY CONTROL
A. Operate each switch and receptacle at least six times with circuit energized.
SECTION 26 2726 - WIRING DEVICES
26 2726 - Wiring Devices
END OF SECTION 26 2726