ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLY RESERVES THE COMMON LAW COPYRIGHT ASSOCIATED WITH THESE DRAWINGS, AND THESE DOCUMENTS MAY NOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RD PARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC, INC. THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC AND ARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL OR COMPONENT REQUIRED FOR A COMPLETE, FULLY OPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S). ANY CONTRACTOR RELYING ON THESE DOCUMENTS SHALL DO SO ONLY IN CONCERT WITH CURRENT CODE CONSIDERATION, FIELD INVESTIGATION/VERIFICATION AND UTILITY COORDINATION IN ORDER TO PROVIDE A COMPREHENSIVE INSTALLATION. PO BOX 93024 Albuquerque, NM 87199 505-856-3419 INC. E N G I N E E R S C O N S U L T I N G Project #: Date: PROJECT ARCHITECT: By: File: Sheet of Plot Date: AEC-E-1.0-POWER RISER.DWG 2/12/2015 4:16:17 PM Housing and Economic Rural Opportunity Pase Del Oro Apartments Las Cruces, New Mexico BOB HALL, AIA IDA-14-01-P DECEMBER 22, 2014 AEC 1 01/30/15 REVISION #1. PANEL 1-PHASE 125A MCB "A1-1" 120/240V PANEL 1-PHASE 125A MCB "A1-2" 120/240V PANEL 1-PHASE 125A MCB "A1-3" 120/240V PANEL 1-PHASE 125A MCB "A1-4" 120/240V PANEL "MA1" 400A MCB 120/240V 1-PHASE UTILITY-OWNED SERVICE TRANSFORMERS ST-1, ST-2, AND ST-3 AC AC PV INV. PANEL 1-PHASE 125A MCB "A2-1" 120/240V PANEL 1-PHASE 125A MCB "A2-2" 120/240V PANEL 1-PHASE 125A MCB "A2-3" 120/240V PANEL 1-PHASE 125A MCB "A2-4" 120/240V PANEL "MA2" 400A MCB 120/240V 1-PHASE AC DISC. SW. AC PV INV. PANEL 1-PHASE 125A MCB "A3-1" 120/240V PANEL 1-PHASE 125A MCB "A3-2" 120/240V PANEL 1-PHASE 125A MCB "A3-3" 120/240V PANEL 1-PHASE 125A MCB "A3-4" 120/240V PANEL "MA3" 400A MCB 120/240V 1-PHASE AC AC PV INV. 1 UTILITY-OWNED SERVICE TRANSFORMER WITH 120/240V, 1-PHASE SECONDARY. REFER TO ELECTRICAL SITE PLAN FOR LOCATION. 2 PRIMARY ELECTRICAL FEEDER TO UTILITY SERVICE POINT (BY EL PASO ELECTRIC (EPE), THE ELECTRIC UTILITY COMPANY). 3 PHOTOVOLTAIC (PV) EQUIPMENT PROVIDED AND INSTALLED BY OTHERS UNDER SEPARATE PERMIT AS PART OF THIS PROJECT. REFER TO PV-100 DRAWING BY AFFORDABLE SOLAR INCLUDED FOR REFERENCE. PROVIDE ONE 3/4" CONDUIT STUB-UP FROM METER / PANEL LOCATION TO ROOF FOR PV SYSTEM, COORDINATE EXACT LOCATION WITH PV SYSTEM INSTALLER. 4 METERING EQUIPMENT PER EPE REQUIREMENTS. VERIFY ALL METERING AND SERVICE REQUIREMENTS WITH EPE BLUE BOOK AND EPE REPRESENTATIVE PRIOR TO BEGINNING ANY ELECTRICAL WORK. CONTACT JERRY ORTEGA, PH. (575) 523-3614. 5 LANDLORD METERING UNIT TO READ INDIVIDUAL APARTMENT PANEL USAGE. INSTALL REQUIRED CT'S IN MAIN PANEL AND MAKE ALL FINAL CONNECTIONS PER MANUFACTURER'S RECOMMENDATIONS. LEVITON VERIFYE MINI-METER MULTIPLE UNIT (MMU) WITH MODHOPPER MODBUS/PULSE TRANSCEIVER, PULSE MODULE, EMB HUB, CT'S AND ALL FINAL CONNECTIONS REQUIRED FOR A COMPLETELY OPERATIONAL SYSTEM. 6 ONE #1/0 BSD COPPER SERVICE GROUND IN 1/2" CONDUIT. REFER TO SERVICE GROUNDING DETAIL. 7 400A SERVICE FEEDER. 3 #500KCMIL CU IN 3" CONDUIT. 8 125A FEEDER. 3 #1 CU AND 1 #6 CU E.GR. IN 1.5" CONDUIT. 9 300A SERVICE FEEDER. 3 #350KCMIL CU IN 2.5" CONDUIT. 10 TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) DEVICE. LEVITON #52120-CM2. CONNECT TO PANEL PER MANUFACTURER'S RECOMMENDATIONS. ELECTRICAL KEYED NOTES: 1 2 3 REC METER 4 6 3 3 REC METER 4 6 4 6 REC METER 2 UTILITY-OWNED SERVICE TRANSFORMER ST-4 1 PANEL "MM" 300A MCB 120/240V 1-PHASE AC AC PV INV. ON BUILDING "M" ROOF 3 REC METER 4 POWER RISER DIAGRAM - BUILDINGS A1, A2, & A3 SCALE: NONE PANEL 1-PHASE 125A MCB "B-1" 120/240V PANEL 1-PHASE 125A MCB "B-2" 120/240V PANEL "MB" 300A MCB 120/240V 1-PHASE AC AC PV INV. PANEL 1-PHASE 125A MCB "C-1 120/240V PANEL 1-PHASE 125A MCB "C-2" 120/240V PANEL 1-PHASE 125A MCB "C-3" 120/240V PANEL "MC" 400A MCB 120/240V 1-PHASE AC AC PV INV. PANEL 1-PHASE 125A MCB "D-1" 120/240V PANEL 1-PHASE 125A MCB "D-2" 120/240V PANEL 1-PHASE 125A MCB "D-3" 120/240V PANEL 1-PHASE 125A MCB "D-4" 120/240V PANEL "MD" 400A MCB 120/240V 1-PHASE AC AC PV INV. 3 REC METER 4 5 6 3 3 REC METER 4 6 4 6 REC METER POWER RISER DIAGRAM - BUILDINGS B, C, & D SCALE: NONE PANEL 1-PHASE 125A MCB "C-5" 120/240V PANEL 1-PHASE 125A MCB "C-4" 120/240V PANEL 1-PHASE 125A MCB "C-6" 120/240V POWER RISER DIAGRAM - BUILDING M SCALE: NONE POWER RISER DIAGRAMS E-1.0 9 9 7 7 7 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 6 7 7 2-METER UNIT LEVITON #6M202-CFG 5 6-METER UNIT LEVITON #6L206-CFG 5 4-METER UNIT LEVITON #6M204-CFG 5 4-METER UNIT LEVITON #6M204-CFG 5 4-METER UNIT LEVITON #6M204-CFG 5 4-METER UNIT LEVITON #6M204-CFG C I E X W M N E 0 A L O M e A R C I N I E G A S 18711 N SERVICE FEEDER NEUTRAL BUS GROUND BUS GROUNDING ELECTRODE CONDUCTOR SCHEDULE A. ALL CONDUCTORS USED FOR THE GROUNDING SYSTEM SHALL BE COPPER. B. CONNECT THE GROUNDING SYSTEM TO THE FOUR FOLLOWING COMPONENTS: 1. BUILDING STEEL. 2. METAL U.G. COLD WATER PIPE. 3. CONCRETE ENCASED REBAR OR #4 COPPER UFER. 4. 10' GROUND RODS. C. ANY SPLICING SHALL BE VIA CAD-WELD TYPE PROCESS. D. THE GROUNDING SYSTEM SHALL COMPLY WITH ALL REQUIREMENTS OF ARTICLE 250 OF THE 2011 NEC, AND SHALL PROVIDE 5 OHMS OR LESS RESISTANCE TO GROUND. PROVIDE TEST REPORT VERIFYING RESISTANCE LEVEL IS IN COMPLIANCE WITH 5 OHM MAXIMUM. NEC 250.52(1) COLD WATER PIPE, BUILDING STEEL, NEC 250.52(2) SERVICE GROUNDING SYSTEM DIAGRAM SCALE: NONE SERVICE ENTRANCE EQUIPMENT MAIN DRIVEN COPPER CLAD 5/8" X 10' GROUND ROD (SPACED 15' APART) #4 UFER GROUND, SLAB REBAR OR NEC 250.52(3) AS SHOWN ON GROUNDING CONDUCTOR, MINIMUM SIZE GROUNDING ELECTRODE COPPER SERVICE PANELBOARD SERVICE GROUNDING SYSTEM GENERAL NOTES 200A 225A 400A 600A 800A 1000A 1200A 150A 100A SERVICE AMPACITY METALLIC PIPE CONDUCTOR BUILDING STEEL CONDUCTOR #4 #2 #1/0 #2/0 #3/0 #3/0 250KCMIL #6 #8 #4 #2 #1/0 #2/0 #3/0 #3/0 250KCMIL #6 #8 #4 #2 #1/0 #2/0 #2/0 #3/0 #3/0 #6 #8 #4 #2 #1/0 #2/0 #2/0 #3/0 #6 #8 #3/0 G N ELECTRODE CONDUCTOR SCHEDULE NEC 250.28 MAIN BONDING JUMPER, NEC 250.102(C) EQUIP. BONDING JUMPER, REBAR OR UFER CONDUCTOR #4 #2 #1/0 #2/0 #2/0 #3/0 #6 #8 #3/0 GROUND ROD CONDUCTOR #4 #2 #1/0 #2/0 #2/0 #3/0 #6 #8 #3/0 PHASE BUSES NEUTRAL BUS GROUND BUS EQUIV. CU WIRE SIZE #3/0 #4/0 500 700 1000 1200 1400 #1/0 #2 MAIN BONDING JUMPER EQUIPMENT BONDING JUMPER INTERSYSTEM BONDING TERMINATION (IBT), NEC 250.94 #6 CU 2 TO ST-1 TO ST-2 TO ST-3 TO ST-4 TO ST-5 TO ST-5 UTILITY-OWNED SERVICE TRANSFORMERS ST-4 AND ST-5 1 TVSS TVSS TVSS TVSS TVSS TVSS TVSS 10 10 10 10 10 10 10 DISC. SW. DISC. SW. DISC. SW. DISC. SW. DISC. SW. DISC. SW. PV ARRAY ON BUILDING "B" ROOF PV ARRAY ON BUILDING "C" ROOF PV ARRAY ON BUILDING "D" ROOF PV ARRAY ON BUILDING "A1" ROOF PV ARRAY ON BUILDING "A2" ROOF PV ARRAY ON BUILDING "A3" ROOF PV ARRAY A ALL PHOTOVOLTAIC (PV) SYSTEM COMPONENTS AND WIRING FOR EACH OF THE (7) BUILDINGS SHALL BE PROVIDED AND INSTALLED BY THE PV SYSTEM CONTRACTOR. NOTE: * PV SYSTEM CONTRACTOR IS REQUIRED TO OBTAIN INDEPENDENT PERMIT FROM THE AHJ PRIOR TO STARTING THEIR WORK. B THE PV SYSTEM CONTRACTOR SHALL REFER TO PV SERIES DRAWINGS FOR PV WORK REQUIRED. THE PV SERIES DRAWINGS SHALL BE ENGINEERED AND STAMPED BY A PROFESSIONAL PV SYSTEM DESIGN ENGINEER. COORDINATE ALL PV WORK WITH AFFORDABLE SOLAR, PH. (505) 944-4220). C ELECTRICAL CONTRACTOR SHALL PROVIDE A CONCEALED 3/4" CONDUIT WITH PULL WIRE FROM THE ROOF OF EACH BUILDING TO THE LOCATION OF THE ASSOCIATED BUILDING WALL MOUNTED PV EQUIPMENT. COORDINATE EXACT LOCATION WITH PV SYSTEM INSTALLER. PHOTOVOLTAIC SYSTEM GENERAL NOTES:

GROUNDING ELECTRODE CONDUCTOR SCHEDULE Del Oro/2015 04... · atlas electrical construction, inc. expressly reserves the common law copyright associated with these drawings, and these

Embed Size (px)

Citation preview

ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLYRESERVES THE COMMON LAW COPYRIGHT ASSOCIATEDWITH THESE DRAWINGS, AND THESE DOCUMENTS MAYNOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RDPARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC,INC.

THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ANDARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL ORCOMPONENT REQUIRED FOR A COMPLETE, FULLYOPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S).

ANY CONTRACTOR RELYING ON THESE DOCUMENTSSHALL DO SO ONLY IN CONCERT WITH CURRENT CODECONSIDERATION, FIELD INVESTIGATION/VERIFICATIONAND UTILITY COORDINATION IN ORDER TO PROVIDE ACOMPREHENSIVE INSTALLATION.

PO BOX 93024Albuquerque, NM 87199

505-856-3419

INC.E N G I N E E R S

C O N S U L T I N G

Project #:

Date:

PROJECT ARCHITECT:

By:

File:Sheet of

Plot Date:

AEC-E-1.0-POWER RISER.DWG

2/12/2015 4:16:17 PM

Housing and Economic Rural OpportunityPase Del Oro ApartmentsLas Cruces, New Mexico

BOB HALL, AIA

IDA-14-01-P

DECEMBER 22, 2014

AEC

101/30/15 REVISION #1.

PANEL

1-PHASE

125A MCB

"A1-1"

120/240V

PANEL

1-PHASE

125A MCB

"A1-2"

120/240V

PANEL

1-PHASE

125A MCB

"A1-3"

120/240V

PANEL

1-PHASE

125A MCB

"A1-4"

120/240V

PANEL

"MA1"

400A MCB

120/240V

1-PHASE

UTILITY-OWNED

SERVICE TRANSFORMERS

ST-1, ST-2, AND ST-3

AC

AC

PV

INV.

PANEL

1-PHASE

125A MCB

"A2-1"

120/240V

PANEL

1-PHASE

125A MCB

"A2-2"

120/240V

PANEL

1-PHASE

125A MCB

"A2-3"

120/240V

PANEL

1-PHASE

125A MCB

"A2-4"

120/240V

PANEL

"MA2"

400A MCB

120/240V

1-PHASE

AC

DISC.

SW.

AC

PV

INV.

PANEL

1-PHASE

125A MCB

"A3-1"

120/240V

PANEL

1-PHASE

125A MCB

"A3-2"

120/240V

PANEL

1-PHASE

125A MCB

"A3-3"

120/240V

PANEL

1-PHASE

125A MCB

"A3-4"

120/240V

PANEL

"MA3"

400A MCB

120/240V

1-PHASE

AC

AC

PV

INV.

1 UTILITY-OWNED SERVICE TRANSFORMER WITH 120/240V, 1-PHASE SECONDARY.

REFER TO ELECTRICAL SITE PLAN FOR LOCATION.

2 PRIMARY ELECTRICAL FEEDER TO UTILITY SERVICE POINT (BY EL PASO

ELECTRIC (EPE), THE ELECTRIC UTILITY COMPANY).

3 PHOTOVOLTAIC (PV) EQUIPMENT PROVIDED AND INSTALLED BY OTHERS UNDER

SEPARATE PERMIT AS PART OF THIS PROJECT. REFER TO PV-100 DRAWING BY

AFFORDABLE SOLAR INCLUDED FOR REFERENCE. PROVIDE ONE 3/4" CONDUIT

STUB-UP FROM METER / PANEL LOCATION TO ROOF FOR PV SYSTEM,

COORDINATE EXACT LOCATION WITH PV SYSTEM INSTALLER.

4 METERING EQUIPMENT PER EPE REQUIREMENTS. VERIFY ALL METERING AND

SERVICE REQUIREMENTS WITH EPE BLUE BOOK AND EPE REPRESENTATIVE

PRIOR TO BEGINNING ANY ELECTRICAL WORK. CONTACT JERRY ORTEGA, PH.

(575) 523-3614.

5 LANDLORD METERING UNIT TO READ INDIVIDUAL APARTMENT PANEL USAGE.

INSTALL REQUIRED CT'S IN MAIN PANEL AND MAKE ALL FINAL CONNECTIONS

PER MANUFACTURER'S RECOMMENDATIONS. LEVITON VERIFYE MINI-METER

MULTIPLE UNIT (MMU) WITH MODHOPPER MODBUS/PULSE TRANSCEIVER, PULSE

MODULE, EMB HUB, CT'S AND ALL FINAL CONNECTIONS REQUIRED FOR A

COMPLETELY OPERATIONAL SYSTEM.

6 ONE #1/0 BSD COPPER SERVICE GROUND IN 1/2" CONDUIT. REFER TO SERVICE

GROUNDING DETAIL.

7 400A SERVICE FEEDER. 3 #500KCMIL CU IN 3" CONDUIT.

8 125A FEEDER. 3 #1 CU AND 1 #6 CU E.GR. IN 1.5" CONDUIT.

9 300A SERVICE FEEDER. 3 #350KCMIL CU IN 2.5" CONDUIT.

10 TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) DEVICE. LEVITON

#52120-CM2. CONNECT TO PANEL PER MANUFACTURER'S RECOMMENDATIONS.

ELECTRICAL KEYED NOTES:

1

2

3

REC

METER

4

6

3 3

REC

METER

4

6

4

6

REC

METER

2

UTILITY-OWNED

SERVICE

TRANSFORMER ST-4

1

PANEL

"MM"

300A MCB

120/240V

1-PHASE

AC

AC

PV

INV.

ON BUILDING "M" ROOF

3

REC

METER

4

POWER RISER DIAGRAM - BUILDINGS A1, A2, & A3

SCALE: NONE

PANEL

1-PHASE

125A MCB

"B-1"

120/240V

PANEL

1-PHASE

125A MCB

"B-2"

120/240V

PANEL

"MB"

300A MCB

120/240V

1-PHASE

AC

AC

PV

INV.

PANEL

1-PHASE

125A MCB

"C-1

120/240V

PANEL

1-PHASE

125A MCB

"C-2"

120/240V

PANEL

1-PHASE

125A MCB

"C-3"

120/240V

PANEL

"MC"

400A MCB

120/240V

1-PHASE

AC

AC

PV

INV.

PANEL

1-PHASE

125A MCB

"D-1"

120/240V

PANEL

1-PHASE

125A MCB

"D-2"

120/240V

PANEL

1-PHASE

125A MCB

"D-3"

120/240V

PANEL

1-PHASE

125A MCB

"D-4"

120/240V

PANEL

"MD"

400A MCB

120/240V

1-PHASE

AC

AC

PV

INV.

3

REC

METER

4

5

6

3 3

REC

METER

4

6

4

6

REC

METER

POWER RISER DIAGRAM - BUILDINGS B, C, & D

SCALE: NONE

PANEL

1-PHASE

125A MCB

"C-5"

120/240V

PANEL

1-PHASE

125A MCB

"C-4"

120/240V

PANEL

1-PHASE

125A MCB

"C-6"

120/240V

POWER RISER DIAGRAM - BUILDING M

SCALE: NONE

POWER RISER DIAGRAMS

E-1.0

9

9

7

7

7

8

8

8

8

8

8

8

8

8

8

8

8

8

8

8

8

8

8

8

8

8

8

8

8

6

7

7

2-METER UNIT

LEVITON #6M202-CFG

5

6-METER UNIT

LEVITON #6L206-CFG

5

4-METER UNIT

LEVITON #6M204-CFG

5

4-METER UNIT

LEVITON #6M204-CFG

5

4-METER UNIT

LEVITON #6M204-CFG

5

4-METER UNIT

LEVITON #6M204-CFG

C

I

E

X

W

M

N

E

0

A

L

O

M

É

ARC

I

N

I

E

G

A

S

18711

N

SERVICE FEEDER

NEUTRAL BUS

GROUND BUS

GROUNDING ELECTRODE CONDUCTOR SCHEDULE

A. ALL CONDUCTORS USED FOR THE GROUNDING SYSTEM SHALL BE COPPER.

B. CONNECT THE GROUNDING SYSTEM TO THE FOUR FOLLOWING COMPONENTS:

1. BUILDING STEEL.

2. METAL U.G. COLD WATER PIPE.

3. CONCRETE ENCASED REBAR OR #4 COPPER UFER.

4. 10' GROUND RODS.

C. ANY SPLICING SHALL BE VIA CAD-WELD TYPE PROCESS.

D. THE GROUNDING SYSTEM SHALL COMPLY WITH ALL REQUIREMENTS OF ARTICLE 250 OF THE 2011 NEC,

AND SHALL PROVIDE 5 OHMS OR LESS RESISTANCE TO GROUND. PROVIDE TEST REPORT VERIFYING

RESISTANCE LEVEL IS IN COMPLIANCE WITH 5 OHM MAXIMUM.

NEC 250.52(1)

COLD WATER PIPE,

BUILDING STEEL,

NEC 250.52(2)

SERVICE GROUNDING SYSTEM DIAGRAM

SCALE: NONE

SERVICE

ENTRANCE

EQUIPMENT

MAIN

DRIVEN

COPPER CLAD

5/8" X 10'

GROUND ROD

(SPACED 15' APART)

#4 UFER GROUND,

SLAB REBAR OR

NEC 250.52(3)

AS SHOWN ON GROUNDING

CONDUCTOR, MINIMUM SIZE

GROUNDING ELECTRODE

COPPER SERVICE

PANELBOARD

SERVICE GROUNDING SYSTEM GENERAL NOTES

200A

225A

400A

600A

800A

1000A

1200A

150A

100A

SERVICE

AMPACITY

METALLIC

PIPE

CONDUCTOR

BUILDING

STEEL

CONDUCTOR

#4

#2

#1/0

#2/0

#3/0

#3/0

250KCMIL

#6

#8

#4

#2

#1/0

#2/0

#3/0

#3/0

250KCMIL

#6

#8

#4

#2

#1/0

#2/0

#2/0

#3/0

#3/0

#6

#8

#4

#2

#1/0

#2/0

#2/0

#3/0

#6

#8

#3/0

G

N

ELECTRODE CONDUCTOR

SCHEDULE

NEC 250.28

MAIN BONDING JUMPER,

NEC 250.102(C)

EQUIP. BONDING JUMPER,

REBAR OR

UFER

CONDUCTOR

#4

#2

#1/0

#2/0

#2/0

#3/0

#6

#8

#3/0

GROUND

ROD

CONDUCTOR

#4

#2

#1/0

#2/0

#2/0

#3/0

#6

#8

#3/0

PHASE

BUSES

NEUTRAL

BUS

GROUND

BUS

EQUIV.

CU WIRE

SIZE

#3/0

#4/0

500

700

1000

1200

1400

#1/0

#2

MAIN

BONDING

JUMPER

EQUIPMENT

BONDING

JUMPER

INTERSYSTEM BONDING

TERMINATION (IBT),

NEC 250.94

#6 CU

2

TO ST-1

TO ST-2

TO ST-3

TO ST-4

TO ST-5

TO ST-5

UTILITY-OWNED

SERVICE TRANSFORMERS

ST-4 AND ST-5

1

TVSS TVSS

TVSS TVSS TVSS

TVSS

TVSS

10

10

10

10

10 1010

DISC.

SW.

DISC.

SW.

DISC.

SW.

DISC.

SW.

DISC.

SW.

DISC.

SW.

PV ARRAY

ON BUILDING "B" ROOF

PV ARRAY

ON BUILDING "C" ROOF

PV ARRAY

ON BUILDING "D" ROOF

PV ARRAY

ON BUILDING "A1" ROOF

PV ARRAY

ON BUILDING "A2" ROOF

PV ARRAY

ON BUILDING "A3" ROOF

PV ARRAY

A ALL PHOTOVOLTAIC (PV) SYSTEM COMPONENTS AND WIRING FOR EACH OF THE (7)

BUILDINGS SHALL BE PROVIDED AND INSTALLED BY THE PV SYSTEM

CONTRACTOR. NOTE: * PV SYSTEM CONTRACTOR IS REQUIRED TO OBTAIN

INDEPENDENT PERMIT FROM THE AHJ PRIOR TO STARTING THEIR WORK.

B THE PV SYSTEM CONTRACTOR SHALL REFER TO PV SERIES DRAWINGS FOR PV

WORK REQUIRED. THE PV SERIES DRAWINGS SHALL BE ENGINEERED AND

STAMPED BY A PROFESSIONAL PV SYSTEM DESIGN ENGINEER. COORDINATE ALL

PV WORK WITH AFFORDABLE SOLAR, PH. (505) 944-4220).

C ELECTRICAL CONTRACTOR SHALL PROVIDE A CONCEALED 3/4" CONDUIT WITH

PULL WIRE FROM THE ROOF OF EACH BUILDING TO THE LOCATION OF THE

ASSOCIATED BUILDING WALL MOUNTED PV EQUIPMENT. COORDINATE EXACT

LOCATION WITH PV SYSTEM INSTALLER.

PHOTOVOLTAIC SYSTEM GENERAL NOTES:

ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLYRESERVES THE COMMON LAW COPYRIGHT ASSOCIATEDWITH THESE DRAWINGS, AND THESE DOCUMENTS MAYNOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RDPARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC,INC.

THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ANDARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL ORCOMPONENT REQUIRED FOR A COMPLETE, FULLYOPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S).

ANY CONTRACTOR RELYING ON THESE DOCUMENTSSHALL DO SO ONLY IN CONCERT WITH CURRENT CODECONSIDERATION, FIELD INVESTIGATION/VERIFICATIONAND UTILITY COORDINATION IN ORDER TO PROVIDE ACOMPREHENSIVE INSTALLATION.

PO BOX 93024Albuquerque, NM 87199

505-856-3419

INC.E N G I N E E R S

C O N S U L T I N G

Project #:

Date:

PROJECT ARCHITECT:

By:

File:Sheet of

Plot Date:

AEC-E-2.0-SYMBOL LEGEND.DWG

2/12/2015 4:18:04 PM

Housing and Economic Rural OpportunityPase Del Oro ApartmentsLas Cruces, New Mexico

BOB HALL, AIA

IDA-14-01-P

DECEMBER 22, 2014

AEC

101/30/15 REVISION #1.

ELECTRICAL SYMBOL LEGEND

E-2.0

ABOVE FINISH FLOOR.

SPLIT-WIRED DUPLEX RECEPTACLE

PHOTOCELL.

THREE-WAY SWITCH

FOUR-WAY SWITCH

WEATHER-RESISTANT SWITCH

KEY-OPERATED SWITCH

DIMMER SWITCH, 1200W MINIMUM WATTAGE.

SINGLE-POLE WALL SWITCH. SUBSCRIPT, IF USED, DESIGNATES

AFF

DUPLEX RECEPTACLE OUTLET, 18"AFF. # INDICATES CIRCUIT.

QUADPLEX RECEPTACLE, 18" AFF TO CENTER.

GROUND FAULT CIRCUIT INTERRUPTER (GFCI) DUPLEX

CEILING JUNCTION BOX

WALL JUNCTION BOX

CONDUIT CAP/STUB-OUT.

CONDUIT TURNING DOWN.

CONDUIT TURNING UP.

FLEXIBLE CONDUIT.

HIDDEN OR BURIED.

HOME-RUN CONDUIT.

CONDUIT, NEW WORK.

SYMBOL DESCRIPTION SYMBOL DESCRIPTION

ELECTRICAL SYMBOL LEGEND

(ALL SYMBOLS SHOWN ARE NOT NECESSARILY USED ON THE DRAWINGS)

THERMOSTAT

EXISTING CONDUIT.EX

ABOVE COUNTER.AC

OCCUPANCY SENSOR SWITCH.

CATV OUTLET

SURVEILLANCE CAMERA, PTZ = PAN, TILT, ZOOM, WEATHER-

1'X4' SURFACE MOUNTED LIGHTING FIXTURE.

SHADING AND "EM" INDICATES LIGHTING FIXTURE SUPPLIED WITH

2'X4' LAY-IN LIGHTING FIXTURE (TROFFER), TYPE INDICATED BY

RECESSED DOWNLIGHT FIXTURE.

A

1'X4' RECESSED (FLANGED) MOUNTED LIGHTING FIXTURE.

POLE MOUNTED AREA LIGHTING FIXTURE, SINGLE-HEAD.

2'X2' LAY-IN LIGHTING FIXTURE (TROFFER).

SURFACE MOUNTED DRUM TYPE LIGHTING FIXTURE.

WALL BRACKET LIGHTING FIXTURE.

EXTERIOR WALL SCONCE LIGHTING FIXTURE.

BOLLARD LIGHTING FIXTURE.

PENDANT HUNG CYLINDER-TYPE LIGHTING FIXTURE.

LINEAR PENDANT MOUNTED LIGHTING FIXTURE, LENGTH AS

EXTERIOR WALLPACK LIGHTING FIXTURE.

STEP LIGHT LIGHTING FIXTURE.

CONDUCTOR TICK MARKS: GROUND, NEUTRAL, PHASE,

RECEPTACLE WITH WEATHER-RESISTANT COVER.

CEILING MOUNTED DUPLEX RECEPTACLE.

SPECIAL RECEPTACLE, TYPE AS NOTED.

FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE.

CONTROL OF PARTICULAR LIGHTING FIXTURES.

MECHANICALLY WOUND TWIST-TIMER SWITCH OR ELECTRONIC

TIME SWITCH.

THERMAL SWITCH.

EVAPORATIVE COOLER SWITCH.

TWIN-EYE EMERGENCY LIGHTING UNIT WITH BATTERY BACK-UP.

EXIT SIGN, SINGLE FACE INDICATED BY SHADED QUADRANT.

EXIT SIGN, DOUBLE-FACED, DIRECTIONAL ARROWS INDICATED.

STANCHION MOUNTED SIGN-LIGHTER FIXTURE.

EXTERIOR WALL MOUNTED EMERGENCY LIGHTING UNIT WITH

MOTOR, HP SIZE AS INDICATED, "F" = FRACTIONAL HORSEPOWER.

FLUSH MOUNTED PANELBOARD, REFER TO ASSOCIATED

FUSED DISCONNECT SWITCH, NEMA 3R IF OUTSIDE, AMPS/

SURFACE MOUNTED PANELBOARD, REFER TO ASSOCIATED

POWER TRANSFORMER.

60/3/45

NON-FUSED DISCONNECT SWITCH, NEMA 3R IF OUTSIDE,60/3

POLES / FUSE SIZE INDICATED.

AMPS / POLES INDICATED.

GROUND FAULT CIRCUIT INTERRUPTER.GFCI

COMBINATION VOICE/DATA OUTLET, UP 18" U.N.O. EXTEND

U.N.O.UNLESS NOTED OTHERWISE.

FLUORESCENT STRIP FIXTURE.

PTZ

OC

S

EC

S

T

S

T

S

D

S

K

S

WR

S

4

S

3

S

aS

#

SWITCHED, AND ISOLATED GROUND RESPECTIVELY.

E.GR.EQUIPMENT GROUND.

WEATHER-RESITANT.WR

AE

FLUSH IN-GROUND LIGHTING FIXTURE.

T

EPRIMARY ELECTRICAL UNDERGROUND FEEDER.

UG

EOVERHEAD PRIMARY ELECTRICAL LINE.

OH

STA

DOORBELL SYSTEM PUSHBUTTON.

DUPLEX RECEPTACLE WITH BUILT-IN USB CHARGER OUTLET.

DOORBELL/CHIME.

MECHANICAL UNIT TAG (EXAMPLE: BOILER B-2 INDICATED),

B-2

PADDLE FAN, WITH OR WITHOUT LIGHT PER LUMINAIRE

SEE MECHANICAL EQUIPMENT SCHEDULE.

RESISTANT AT EXTERIOR; STA = STATIONARY.

COMBO EXIT SIGN/EMERGENCY TWIN-EYE UNIT.

DOOR OPERATOR PUSH-PAD UNIT (ADA COMPLIANT).

FLUSH CEILING VOICE/DATA OUTLET. EXTEND 3/4"C. WITH

PULL STRING TO CEILING.

3/4" CONDUIT WITH PULL STRING TO ACCESSIBLE CEILING.

J-BOX WITH FLEXIBLE CONDUIT CONNECTION TO LAY-IN

TRACK MOUNTED LIGHTING ASSEMBLY, ONE FIXTURE HEAD

PANEL SCHEDULE.

PANEL SCHEDULE.

LETTER.

EMERGENCY BATTERY PACK.

INDICATED.

OWNER FURNISHED, CONTRACTOR INSTALLED.O.F.C.I.

BATTERY BACK-UP.

INDICATED.

SCHEDULE.

LIGHTING FIXTURES.

B

2

T

J

J

T

V

T

BARE SOFT-DRAWN.BSD

J

FLUSH FLOOR VOICE/DATA OUTLET. EXTEND 3/4"C. WITH

PULL STRING TO CEILING.

CONTROL / LOW VOLTAGE TRANSFORMER.T

PROJECT GENERAL ELECTRICAL NOTES:

A ALL DEVICES SHALL BE IVORY WITH COMPATIBLE PLASTIC PLATES, INSTALLED

FOR ADA COMPLIANCE U.N.O.

B ALL TELEPHONE, DATA, SECURITY, CATV, SOUND AND INTERCOM LOW VOLTAGE

SYSTEM ARE PROVIDED BY OTHERS. NOTE: * LOW VOLTAGE CONTRACTORS

ARE REQUIRED TO OBTAIN INDEPENDENT PERMITS FROM THE AHJ PRIOR TO

STARTING THEIR WORK

C UTILIZE "DEEP" 4-SQUARES WHERE REQUIRED TO COMPLY WITH NEC 314.6

EXTRA CONSIDERATION SHALL BE GIVEN TO BOXES SUPPLYING HOME-RUNS

D CONFIRM EXACT ROUGH-IN DIMENSIONS WITH ARCHITECTURAL DRAWINGS,

KITCHEN EQUIPMENT, FURNITURE PLAN (IF AVAILABLE) AND SPECIALTY

EQUIPMENT

E GENERAL CONTRACTOR TO SAW-CUT/REMOVE/PATCH EXISTING

ARCHITECTURAL SURFACES INCLUDING BUT NOT LIMITED TO SLABS, WALLS AND

ROOFS.

F SHARED NEUTRALS ARE NOT PERMISSIBLE U.N.O.

G CONDUCTOR TICK MARKS ARE SHOWN FOR CONVENIENCE ONLY, THE

CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL CONDUCTORS WHETHER

SHOWN OR NOT INCLUDING "TRAVELERS" AS NECESSARY FOR COMPLETELY

OPERATIONAL SYSTEMS.

H PROVIDE GFCI-TYPE RECEPTACLES WITHIN 6' OF ANY SINK, IN KITCHENS,

BATHROOMS, LAUNDRY AREAS AND OUTDOORS PER NEC 210.8.

I PROVIDE AFCI PROTECTION IN DWELLING UNITS PER NEC 210.12.

J ELECTRICAL DEVICE INSTALLATION SHALL COMPLY WITH ACCESSIBILITY CODES

ADOPTED FOR NEW MEXICO. SPECIFICALLY; MOUNT APPLICABLE SWITCHES,

RECEPTACLES, AND ENVIRONMENTAL CONTROLS SO THAT THEY ARE MOUNTED

WITH THE TOP OF THE DEVICE NO HIGHER THAN 48 INCHES ABOVE FINISHED

FLOOR (AFF) AND THE BOTTOM OF THE DEVICE NO LOWER THAN 15 INCHES AFF.

ELECTRICAL DEVICES ABOVE COUNTERTOP (AC) OR OTHER OBSTRUCTION

SHOULD COMPLY WITH ICC/ANSI 117.1-2003 SECTION 308.

K EXTERIOR LIGHTING SHALL COMPLY WITH THE LAS CRUCES OUTDOOR LIGHTING

ORDINANCE AND THE NEW MEXICO NIGHT SKY PROTECTION ACT.

L ALL ELECTRICAL WORK SHALL COMPLY WITH THE 2011 NEC, 2011 NMEC, AND

APPLICABLE CODES AND ORDINANCES ADOPTED BY THE CITY OF LAS CRUCES.

REFERENCE WEB SITE:

TOTAL CONNECTED LOAD ON "MA1" (SAME FOR "MA2") 110.7 KVA

CODE DEMAND LOAD PER NEC 220.84: MULTIFAMILY DWELLING - (4) UNITS:

17.57 KVA X 4 X .45 DEMAND FACTOR = 31.63 KVA

DESIGN LOAD = DEMAND LOAD + FUTURE 20%: 38.0 KVA (158A).

RECOMMEND SERVICE TRANSFORMER BE SIZED AT 75 KVA.

SINGLE-PHASE FAULT CURRENT CALCULATIONS ARE BASED ON STANDARD

TRANSFORMER IMPEDANCES AND AN INFINITE PRIMARY CURRENT.

ASSUME SERVICE TRANSFORMER SIZE = 75 KVA

STANDARD TRANSFORMER IMPEDANCE (%Z) = 1.5%

MAXIMUM FAULT CURRENT AT TRANSFORMER SECONDARY = 34,639A

(USE RATING PER UTILITY STANDARDS: PADMOUNTED, UNDER 100 KVA,

RESIDENTIAL, MAXIMUM FAULT CURRENT AT SERVICE ENTRANCE = 10,000A.

ALL PANELS SHALL HAVE A.I.C. AS SCHEDULED.

SERVICE SIZING CALCULATIONS - LOAD RECAP

TOTAL CONNECTED LOAD ON "MA3": 111.2 KVA

CODE DEMAND LOAD PER NEC 220.84: MULTIFAMILY DWELLING - (4) UNITS:

17.57 KVA X 4 X .45 DEMAND FACTOR = 31.63 KVA

DESIGN LOAD = DEMAND LOAD + HOUSE LOAD + FUTURE 20%: 38.5 KVA (160A).

RECOMMEND SERVICE TRANSFORMER BE SIZED AT 75 KVA.

SINGLE-PHASE FAULT CURRENT CALCULATIONS ARE BASED ON STANDARD

TRANSFORMER IMPEDANCES AND AN INFINITE PRIMARY CURRENT.

ASSUME SERVICE TRANSFORMER SIZE = 75 KVA

STANDARD TRANSFORMER IMPEDANCE (%Z) = 1.5%

MAXIMUM FAULT CURRENT AT TRANSFORMER SECONDARY = 34,639A

(USE RATING PER UTILITY STANDARDS: PADMOUNTED, UNDER 100 KVA,

RESIDENTIAL, MAXIMUM FAULT CURRENT AT SERVICE ENTRANCE = 10,000A.

ALL PANELS SHALL HAVE A.I.C. AS SCHEDULED.

SERVICE SIZING CALCULATIONS - LOAD RECAP

TOTAL CONNECTED LOAD ON "MB": 56.7 KVA

CODE DEMAND LOAD PER NEC 220.84: MULTIFAMILY DWELLING - (2) UNITS:

17.57 KVA X 2 X 1.0 DEMAND FACTOR = 35.14 KVA

DESIGN LOAD = DEMAND LOAD + FUTURE 20%: 42.17 KVA (176A).

RECOMMEND SERVICE TRANSFORMER BE SIZED AT 75 KVA.

SINGLE-PHASE FAULT CURRENT CALCULATIONS ARE BASED ON STANDARD

TRANSFORMER IMPEDANCES AND AN INFINITE PRIMARY CURRENT.

ASSUME SERVICE TRANSFORMER SIZE = 75 KVA

STANDARD TRANSFORMER IMPEDANCE (%Z) = 1.5%

MAXIMUM FAULT CURRENT AT TRANSFORMER SECONDARY = 34,639A

(USE RATING PER UTILITY STANDARDS: PADMOUNTED, UNDER 100 KVA,

RESIDENTIAL, MAXIMUM FAULT CURRENT AT SERVICE ENTRANCE = 10,000A.

ALL PANELS SHALL HAVE A.I.C. AS SCHEDULED.

SERVICE SIZING CALCULATIONS - LOAD RECAP

TOTAL CONNECTED LOAD ON "MC": 155.0 KVA

CODE DEMAND LOAD PER NEC 220.84: MULTIFAMILY DWELLING - (6) UNITS:

17.57 KVA X 6 X .44 DEMAND FACTOR = 46.38 KVA

DESIGN LOAD = DEMAND LOAD + FUTURE 20%: 55.66 KVA (232A).

RECOMMEND SERVICE TRANSFORMER BE SIZED AT 75 KVA.

SINGLE-PHASE FAULT CURRENT CALCULATIONS ARE BASED ON STANDARD

TRANSFORMER IMPEDANCES AND AN INFINITE PRIMARY CURRENT.

ASSUME SERVICE TRANSFORMER SIZE = 75 KVA

STANDARD TRANSFORMER IMPEDANCE (%Z) = 1.5%

MAXIMUM FAULT CURRENT AT TRANSFORMER SECONDARY = 34,639A

(USE RATING PER UTILITY STANDARDS: PADMOUNTED, UNDER 100 KVA,

RESIDENTIAL, MAXIMUM FAULT CURRENT AT SERVICE ENTRANCE = 10,000A.

ALL PANELS SHALL HAVE A.I.C. AS SCHEDULED.

SERVICE SIZING CALCULATIONS - LOAD RECAP

TOTAL CONNECTED LOAD ON "MD": 111.6 KVA

CODE DEMAND LOAD PER NEC 220.84: MULTIFAMILY DWELLING - (4) UNITS:

17.57 KVA X 4 X 0.45 DEMAND FACTOR = 31.63 KVA

DESIGN LOAD = DEMAND LOAD + FUTURE 20%: 38.0 KVA (158A).

RECOMMEND SERVICE TRANSFORMER BE SIZED AT 75 KVA.

SINGLE-PHASE FAULT CURRENT CALCULATIONS ARE BASED ON STANDARD

TRANSFORMER IMPEDANCES AND AN INFINITE PRIMARY CURRENT.

ASSUME SERVICE TRANSFORMER SIZE = 75 KVA

STANDARD TRANSFORMER IMPEDANCE (%Z) = 1.5%

MAXIMUM FAULT CURRENT AT TRANSFORMER SECONDARY = 34,639A

(USE RATING PER UTILITY STANDARDS: PADMOUNTED, UNDER 100 KVA,

RESIDENTIAL, MAXIMUM FAULT CURRENT AT SERVICE ENTRANCE = 10,000A.

ALL PANELS SHALL HAVE A.I.C. AS SCHEDULED.

SERVICE SIZING CALCULATIONS - LOAD RECAP

TOTAL CONNECTED LOAD ON "MM": 45.6 KVA

CODE DEMAND LOAD PER NEC 220.40: SERVICE LOAD CALCULATION:

DEMAND LOAD = 44.7 KVA

DESIGN LOAD = DEMAND LOAD + FUTURE 20%: 53.6 KVA (224A).

RECOMMEND SERVICE TRANSFORMER BE SIZED AT 75 KVA.

SINGLE-PHASE FAULT CURRENT CALCULATIONS ARE BASED ON STANDARD

TRANSFORMER IMPEDANCES AND AN INFINITE PRIMARY CURRENT.

ASSUME SERVICE TRANSFORMER SIZE = 75 KVA

STANDARD TRANSFORMER IMPEDANCE (%Z) = 1.5%

MAXIMUM FAULT CURRENT AT TRANSFORMER SECONDARY = 34,639A

(USE RATING PER UTILITY STANDARDS: PADMOUNTED, UNDER 100 KVA,

RESIDENTIAL, MAXIMUM FAULT CURRENT AT SERVICE ENTRANCE = 10,000A.

ALL PANELS SHALL HAVE A.I.C. AS SCHEDULED.

SERVICE SIZING CALCULATIONS - LOAD RECAP

BLDGS A1 & A2 SERVICE CHARACTERISTICS: 120/240V, 1-PHASE, 3-WIRE BLDG A3 SERVICE CHARACTERISTICS: 120/240V, 1-PHASE, 3-WIRE

BLDG M SERVICE CHARACTERISTICS: 120/240V, 1-PHASE, 3-WIREBLDGS D SERVICE CHARACTERISTICS: 120/240V, 1-PHASE, 3-WIRE

BLDG B SERVICE CHARACTERISTICS: 120/240V, 1-PHASE, 3-WIRE BLDG C SERVICE CHARACTERISTICS: 120/240V, 1-PHASE, 3-WIRE

SHORT-CIRCUIT CALCULATIONS SHORT-CIRCUIT CALCULATIONS

SHORT-CIRCUIT CALCULATIONS SHORT-CIRCUIT CALCULATIONS

SHORT-CIRCUIT CALCULATIONS SHORT-CIRCUIT CALCULATIONS

SYMBOL DESCRIPTION

FIRE ALARM SYMBOL LEGEND

FIRE ALARM MANUAL PULL STATION.

FIRE ALARM AUDIO/STROBE UNIT.

FIRE ALARM DUCT SMOKE DETECTOR.

FIRE ALARM TAMPER SWITCH.

FIRE ALARM STROBE UNIT.

FIRE ALARM SMOKE DETECTOR.

FIRE ALARM HEAT DETECTOR.

FIRE ALARM FLOW SWITCH.

FIRE ALARM CONTROL PANEL (FACP).

FIRE PROTECTION SPRINKLER SYSTEM POST INDICATOR VALVE (PIV).

(ALL SYMBOLS SHOWN ARE NOT NECESSARILY USED ON THE DRAWINGS)

AUTHORITY HAVING JURISDICTION.AHJ

SLAVE GFCI-PROTECTED RECEPTACLE (NEC 422.52) FOR EDF

ELECTRIC DRINKING FOUNTAIN (EDF) CONCEALED WITHIN CASE.

GFCI PROTECTED DUPLEX RECEPTACLE. RECEPTACLES WITHGFCI

TRIP RESET SHALL BE IN READILY ACCESSIBLE LOCATION.

ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLYRESERVES THE COMMON LAW COPYRIGHT ASSOCIATEDWITH THESE DRAWINGS, AND THESE DOCUMENTS MAYNOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RDPARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC,INC.

THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ANDARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL ORCOMPONENT REQUIRED FOR A COMPLETE, FULLYOPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S).

ANY CONTRACTOR RELYING ON THESE DOCUMENTSSHALL DO SO ONLY IN CONCERT WITH CURRENT CODECONSIDERATION, FIELD INVESTIGATION/VERIFICATIONAND UTILITY COORDINATION IN ORDER TO PROVIDE ACOMPREHENSIVE INSTALLATION.

PO BOX 93024Albuquerque, NM 87199

505-856-3419

INC.E N G I N E E R S

C O N S U L T I N G

Project #:

Date:

PROJECT ARCHITECT:

By:

File:Sheet of

Plot Date:

AEC-E-3.0-PANEL SCHEDULES.DWG

2/12/2015 4:19:37 PM

Housing and Economic Rural OpportunityPase Del Oro ApartmentsLas Cruces, New Mexico

BOB HALL, AIA

IDA-14-01-P

DECEMBER 22, 2014

AEC

101/30/15 REVISION #1.

PANEL SCHEDULES

E-3.0

BUILDING A1

BUILDING A3

BUILDING A2

BUILDING M

BUILDING B

BUILDING C

BUILDING D

2-STORY

2-STORY

2-STORY

(OFFICE / LAUNDRY)

2-STORY

2-STORY

2-STORY

T

1

1

1

2

ELKS DRIVE

E

N

G

L

E

R

D

R

IV

E

G

O

L

D

C

O

U

R

T

PASEO DEL ORO CR

7

12

9

5

12

PP PP

10

11

11

10 10

4

T

EXISTING TRANSFORMER

EXISTING TELE. PED.

T

T

EXISTING TELE. PED.

4

5

5

8

5

5

9

3

5

CATV

13

14

12

9

12

12

9

9

T

T

15TYP

15TYP

15TYP

15TYP

15TYP

4

12

1

4

1

4

5

9

12

4

4

"MA1"

"MA2"

"MA3"

"MB"

"MC" "MD"

"MM"

ST-1

ST-3

ST-2

ST-4

ST-5

(4 APTS)

(4 APTS)

(4 APTS)

(2 APTS)

(6 APTS)

(4 APTS)

1616

16

16

16

16

16

17

17

17

17

17

17

17

UNIT 107

UNIT 115

UNIT 106

UNIT 103

19 19

18

18

6

6

6

6

TS FS

20

TS FS

6

TS FS

6

TS

FS

6

ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLYRESERVES THE COMMON LAW COPYRIGHT ASSOCIATEDWITH THESE DRAWINGS, AND THESE DOCUMENTS MAYNOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RDPARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC,INC.

THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ANDARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL ORCOMPONENT REQUIRED FOR A COMPLETE, FULLYOPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S).

ANY CONTRACTOR RELYING ON THESE DOCUMENTSSHALL DO SO ONLY IN CONCERT WITH CURRENT CODECONSIDERATION, FIELD INVESTIGATION/VERIFICATIONAND UTILITY COORDINATION IN ORDER TO PROVIDE ACOMPREHENSIVE INSTALLATION.

PO BOX 93024Albuquerque, NM 87199

505-856-3419

INC.E N G I N E E R S

C O N S U L T I N G

Project #:

Date:

PROJECT ARCHITECT:

By:

File:Sheet of

Plot Date:

AEC-SITE-ES-1.0.DWG

3/4/2015 1:54:37 PM

Housing and Economic Rural OpportunityPaseo Del Oro ApartmentsLas Cruces, New Mexico

BOB HALL, AIA

IDA-14-01-P

DECEMBER 22, 2014

AEC

101/30/15 REVISION #1.

203/04/15 REVISION #2, RELOCATE ST-5.

ELECTRICAL KEYED NOTES:

1" = 20'-0"

ELECTRICAL SITE PLAN

NORTH

ELECTRICAL SITE PLAN

ES-1.0

1 ONE 2" PVC CONDUIT W/PULL STRING TO COMCAST PEDESTAL.

2 ONE BARE # 6 SOLID CU TO TO INTERSYSTEM BONDING TERMINAL (IBT).

3 COMCAST PROVIDED CABINET.

4 2" PVC CONDUIT WITH PULL STRING.

1

2

3

CATV RISER DIAGRAM

4

SCALE: NONE

CCTV

CAB.

PEDESTAL

CCTV

4

4

4

4

4

3

CCTV

CAB.

3

CCTV

CAB.

3

CCTV

CAB.

3

CCTV

CAB.

3

CCTV

CAB.

3

CCTV

CAB.

1 ONE 4" PVC CONDUIT W/PULL STRING TO CENTURYLINK PEDESTAL.

2 ONE BARE # 6 SOLID CU TO TO INTERSYSTEM BONDING TERMINAL (IBT).

3 CENTURYLINK DEMARK, E.C. TO PROVIDE CIRCLE AW #420 NEMA 3R

ENCLOSURE WITH BACKBOARD.

4 E.C. PROVIDED 24X24X12 NEMA 3R J-BOX WITH PLYWOOD BACKBOARD AND

LOCKING COVER.

5 DIRECT BURY TELEPHONE DISTRIBUTION CABLE.

6 LIGHTNING PROTECTION.

7 CAT 5E PVC COATED TELEPHONE CABLING AND SINGLE PORT TERMINATION

PLATE TO EACH PHONE OUTLET.

8 TYPICAL VOICE/DATA (PHONE) OUTLET, FURNISHED BY E.C.

1

2

3

4

TELEPHONE RISER DIAGRAM

6

5

SCALE: NONE

7

TEL.

CAB.

PEDESTAL

TELEPHONE

4

6

5

7

4

6

5

7

4

6

5

7

4

6

5

7

4

6

5

7

TTB

BLDG. M

2" C.

1 UTILITY-OWNED SERVICE TRANSFORMER (ST) WITH 120/240V, 1-PHASE

SECONDARY, REFER TO POWER RISER DIAGRAM. VERIFY ALL SERVICE

REQUIREMENTS WITH EL PASO ELECTRIC (EPE) PRIOR TO BEGINNING ANY

ELECTRICAL WORK.

2 TELEPHONE TERMINAL BACKBOARD (TTB).

3 EXTEND 4" PVC TELEPHONE SERVICE CONDUIT TO SERVICE PEDESTAL. VERIFY

SERVICE LOCATION AND REQUIREMENTS WITH CENTURYLINK PRIOR TO ANY

INSTALLATION OR TRENCHING WORK.

4 SECONDARY SERVICE FEEDER BY ELECTRICAL CONTRACTOR, REFER TO

POWER RISER DIAGRAM.

5 SERVICE ENTRANCE GEAR, REFER TO POWER RISER DIAGRAM.

6 CONNECT FIRE ALARM DEVICES AT FIRE RISER ROOM TO FIRE ALARM CONTROL

PANEL (FACP) IN BUILDING "M", SEE POWER PLAN FOR THIS BUILDING. REFER

TO FIRE ALARM SYSTEM DIAGRAM AND FIRE ALARM GENERAL NOTES ON SHEET

EM-1.0.

7 TELEPHONE SERVICE PEDESTAL.

8 MAIN TELEPHONE SERVICE DEMARC CABINET, REFER TO TELEPHONE RISER

DIAGRAM.

9 TELEPHONE CABINET, REFER TO TELEPHONE RISER DIAGRAM.

10 EXISTING EPE-OWNED OVERHEAD 3-PHASE PRIMARY POWER LINE TO REMAIN.

11 EXISTING EPE-OWNED POWER POLE TO REMAIN.

12 CATV TERMINAL CABINET, FURNISHED BY COMCAST, INSTALLED BY ELECTRICAL

CONTRACTOR.

13 2" PVC CATV SERVICE CONDUIT PER COMCAST REQUIREMENTS. VERIFY

SERVICE POINT AND CONDUIT ROUTING WITH COMCAST REPRESENTATIVE

PRIOR TO ANY INSTALLATION OR TRENCHING WORK.

14 CATV SERVICE PEDESTAL.

15 PRIMARY UNDERGROUND ELECTRICAL FEEDER BY EL PASO ELECTRIC.

16 PHOTOVOLTAIC (PV) REC METER AND INVERTER SHALL BE LOCATED ADJACENT

TO SERVICE ENTRANCE EQUIPMENT, REFER TO POWER RISER DIAGRAM ON

SHEET E1.0.

17 PV PANELS SHALL BE INSTALLED ON THE ROOF OF THIS BUILDING, REFER TO

SHEET PV-1.00 FOR QUANTITY, LOCATION, AND ELECTRICAL CHARACTERISTICS.

18 THIS APARTMENT UNIT IS FOR THE HEARING IMPAIRED.

19 THIS APARTMENT UNIT IS FULLY ACCESSIBLE FOR THE PHYSICALLY

CHALLENGED.

20 FIRE ALARM CONTROL PANEL, REFER TO SHEET EM-1.0.

C

I

E

X

W

M

N

E

0

A

L

O

M

É

AR

C

I

N

I

E

G

A

S

18711

2

BUILDING A1

BUILDING A3

BUILDING A2

BUILDING M

BUILDING B

BUILDING C

BUILDING D

(6 APTS)

(4 APTS)(2 APTS)

(OFFICE / LAUNDRY)

(4 APTS)

(4 APTS)

(4 APTS)

2

ELKS DRIVE

E

N

G

L

E

R

D

R

IV

E

G

O

L

D

C

O

U

R

T

PASEO DEL ORO CR

1

2

3TYP

3TYP

3TYP

2

2

ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLYRESERVES THE COMMON LAW COPYRIGHT ASSOCIATEDWITH THESE DRAWINGS, AND THESE DOCUMENTS MAYNOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RDPARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC,INC.

THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ANDARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL ORCOMPONENT REQUIRED FOR A COMPLETE, FULLYOPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S).

ANY CONTRACTOR RELYING ON THESE DOCUMENTSSHALL DO SO ONLY IN CONCERT WITH CURRENT CODECONSIDERATION, FIELD INVESTIGATION/VERIFICATIONAND UTILITY COORDINATION IN ORDER TO PROVIDE ACOMPREHENSIVE INSTALLATION.

PO BOX 93024Albuquerque, NM 87199

505-856-3419

INC.E N G I N E E R S

C O N S U L T I N G

Project #:

Date:

PROJECT ARCHITECT:

By:

File:Sheet of

Plot Date:

AEC-SITE-ES-1.1 SITE LIGHTING.DWG

2/12/2015 4:22:10 PM

Housing and Economic Rural OpportunityPaseo Del Oro ApartmentsLas Cruces, New Mexico

BOB HALL, AIA

IDA-14-01-P

DECEMBER 22, 2014

AEC

1 EXTEND TO CIRCUIT INDICATED THROUGH PHOTOCELL/TIMECLOCK CONTROLS.

USE #10 WIRING THROUGHOUT ENTIRE RUN.

2 PARKING LOT FIXTURE ON 12' POLE, REFER TO POLE BASE MOUNTING DETAIL.

3 REFER TO ASSOCIATED BUILDING ELECTRICAL PLAN FOR CIRCUITING TO THIS

LIGHTING FIXTURE.

ELECTRICAL KEYED NOTES:

1" = 20'-0"

ELECTRICAL SITE LIGHTING PLAN

NORTH

ELECTRICAL SITE LIGHTING PLAN

ES-1.1

FINISHED GRADE

POLE BASE MOUNTING DETAIL

SCALE: NONE

TO BRANCH

CIRCUIT PER

PLAN

TO

EXTERIOR

LIGHTS

LIGHTING CONTROL DIAGRAM

SCALE: NONE

IECC LIGHTING COMPLIANCE - SITE LIGHTING

THE SITE LIGHTING DESIGN SHOWN ON THESE PLANS IS IN COMPLIANCE WITH THE

2009 INTERNATIONAL ENERGY CONSERVATION CODE (IECC).

REFERENCE SECTION 505 - ELECTRICAL POWER AND LIGHTING SYSTEMS

505.6 - EXTERIOR LIGHTING

1. TABLE 505.6.2(1) - EXTERIOR LIGHTING ZONES: THIS PROJECT SITE IS

CLASSIFIED AS LIGHTING ZONE 2: PREDOMINANTLY RESIDENTIAL,

NEIGHBORHOOD BUSINESS DISTRICT.

2. TABLE 505.6.2(2) - LIGHTING POWER ALLOWANCES FOR BUILDING

EXTERIORS:

BASE SITE ALLOWANCE: 600W

PARKING AREAS AND DRIVES: 0.06 W/SF

WALKWAYS LESS THAN 10' WIDE: 0.7 W/LF

SPECIAL FEATURE AREAS: 0.14 W/SF

STAIRWAYS: 1.0 W/SF

MAIN ENTRIES: 20W/LINEAR FOOT OF DOOR WIDTH

OTHER DOORS: 20W/LINEAR FOOT OF DOOR WIDTH

EXTERIOR AREA TOTAL ALLOWABLE WATTAGE FOR THE SITE: 2,140W.

ACTUAL EXTERIOR LIGHTING LOAD = 1,026W. THIS BUILDING COMPLIES WITH THE

MAXIMUM EXTERIOR LIGHTING POWER ALLOWANCE.

BUILDING A1

BUILDING A3

BUILDING A2

BUILDING M

BUILDING B

BUILDING C

BUILDING D

(6 APTS)

(4 APTS)(2 APTS)

(OFFICE / LAUNDRY)

(4 APTS)

(4 APTS)

(4 APTS)

2

ELKS DRIVE

E

N

G

L

E

R

D

R

IV

E

G

O

L

D

C

O

U

R

T

PASEO DEL ORO CR

6

16TYP

17

17

17

TYP

TYP

TYP

SA

SA

SASA

SA

SD

SD

SD

SE

SE

SE

SA

SA

SA

SA

SA

SA

SA

SB

SB

SC

SC

SB

SC

SC

SA

SA

SA

SA

SA

SA

SA

SA

SA

SA

SA

SA

SA

SA

SA

SA

SA

SA

SA

SD

SD

SD

SA

MM-7

0.1

0.1

0.1

0.1

0.1

0.0

0.0

0.0

0.0

0.1

0.2

0.7

1.6

2.9

10.0

4.4

5.9

0.1

1.5

1.4

0.9

0.1 0.1 0.1 0.00.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1

0.0

0.0

0.0

0.0

0.0

0.0

0.1

0.1

0.2

0.3

0.5

0.9

1.2

1.5

1.7

1.5

1.5

1.0

0.8

0.6

0.4

0.3

0.3

0.3

0.4

0.5

0.8

1.1

1.6

3.43.5

8.8

15.0

18.7

15.1

8.9

3.0

1.1

0.3

0.0

0.0

0.0

0.1

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.10.1

0.1 0.0 0.0 0.0 0.00.0 0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.00.0

0.1

0.1

0.2

0.3

0.4

0.5

0.5

0.8

1.0

0.6

0.3

0.2

0.2

0.2

0.3

0.5

2.73.7

8.2

10.3

9.4

3.9

2.41.40.7

0.10.00.10.20.20.20.10.00.00.00.00.00.00.00.00.00.0 0.0 0.0 0.00.8 0.6 0.2 0.9 2.3 6.9 10.9 11.5 7.7 4.1 1.1 0.3 0.2 0.1 0.1 0.1 0.0

2.5

6.5

9.6

8.8

6.6

0.4

0.4

1.0

1.3

0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.10.1

1.3

0.7

0.4

0.3

0.2

0.1

0.110.4

0.0

0.0

0.0

ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLYRESERVES THE COMMON LAW COPYRIGHT ASSOCIATEDWITH THESE DRAWINGS, AND THESE DOCUMENTS MAYNOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RDPARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC,INC.

THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ANDARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL ORCOMPONENT REQUIRED FOR A COMPLETE, FULLYOPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S).

ANY CONTRACTOR RELYING ON THESE DOCUMENTSSHALL DO SO ONLY IN CONCERT WITH CURRENT CODECONSIDERATION, FIELD INVESTIGATION/VERIFICATIONAND UTILITY COORDINATION IN ORDER TO PROVIDE ACOMPREHENSIVE INSTALLATION.

PO BOX 93024Albuquerque, NM 87199

505-856-3419

INC.E N G I N E E R S

C O N S U L T I N G

Project #:

Date:

PROJECT ARCHITECT:

By:

File:Sheet of

Plot Date:

AEC-SITE-ES-1.2 SITE LIGHTING LUMEN CALCS.DWG

2/12/2015 4:23:16 PM

Housing and Economic Rural OpportunityPaseo Del Oro ApartmentsLas Cruces, New Mexico

BOB HALL, AIA

IDA-14-01-P

DECEMBER 22, 2014

AEC

1" = 20'-0"

ELECTRICAL SITE LIGHTING LUMENS CALC

NORTH

ELECTRICAL SITE LIGHTING LUMENS CALC

ES-1.2

Luminaire Schedule

Symbol Qty Label Arrangement Total Lamp Lumens LLF Description

34 SA SINGLE N.A. 0.930 RAB # SLIM26YWPC

3 SB SINGLE N.A. 0.930 RAB # SLIM26YWPC-ON 12 FT POLE

4 SC SINGLE N.A. 0.930 BK LIGHTING # BQL-LED-E36A9-WHP

3 SD SINGLE 1200 0.930 VOLUME # V8853-6 WHITE

3 SE SINGLE 1200 0.930 VOLUME # V8853-6 WHITE

Calculation Summary: Lighting levels calculated by point-to-point method using AGi32 software

Label CalcType Units Avg Max Min Avg/Min Max/Min

PARKING_Top Illuminance Fc 0.38 7.0 0.0 N.A. N.A.

SIDEWALK AROUND SITE_Top Illuminance Fc 0.30 2.5 0.0 N.A. N.A.

SIDEWALK INTERIOR SITE_1_Top Illuminance Fc 1.96 13.0 0.0 N.A. N.A.

SIDEWALK INTERIOR SITE_Top Illuminance Fc 2.04 18.8 0.0 N.A. N.A.

2

2

2

2

APARTMENT 111

(UNIT STYLE "3")

APARTMENT 112

(UNIT STYLE "3")

APARTMENT 113

(UNIT STYLE "3")

APARTMENT 114

(UNIT STYLE "3")

STAIRS

101

BATH

112

MECH.

101

BEDROOM 2

111

BEDROOM 3

114

DECK

HALLWAY

113

STORAGE

109

STAIRS

101

BATH

112

MECH.

101

BEDROOM 2

111

BEDROOM 3

114

DECK

HALLWAY

113

STORAGE

109

STAIRS

101

BATH

112

MECH.

101

BEDROOM 2

111

BEDROOM 3

114

DECK

HALLWAY

113

STORAGE

109

1

1 1

1

PANEL "MA1"3

APARTMENT 111

(UNIT STYLE "3")

APARTMENT 112

(UNIT STYLE "3")

APARTMENT 113

(UNIT STYLE "3")

APARTMENT 114

(UNIT STYLE "3")

PANEL "A3"4

BEDROOM 1

106

BATH 1

105

LAUNDRY

104

DINING

103

LIVING

102

KITCHEN

107

STORAGE

108

BEDROOM 1

106

BATH 1

105

LAUNDRY

104

DINING

103

LIVING

102

KITCHEN

107

STORAGE

108

PORCH PORCH

BEDROOM 1

106

BATH 1

105

LAUNDRY

104

DINING

103

LIVING

102

KITCHEN

107

STORAGE

108

PORCH

BEDROOM 1

106

BATH 1

105

LAUNDRY

104

DINING

103

LIVING

102

KITCHEN

107

STORAGE

108

PORCH

PANEL "A3"4 PANEL "A3"4

PANEL "A3"4

7

8

(APARTMENTS 107, 115)

EUH-1

S

RISER

-

TSFS

9

TYP

10 TYP

10TYP

5

CU-3

TO APT. 111

6

5

CU-3

TO APT. 112

6

5

CU-3

TO APT. 113

6

ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLYRESERVES THE COMMON LAW COPYRIGHT ASSOCIATEDWITH THESE DRAWINGS, AND THESE DOCUMENTS MAYNOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RDPARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC,INC.

THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ANDARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL ORCOMPONENT REQUIRED FOR A COMPLETE, FULLYOPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S).

ANY CONTRACTOR RELYING ON THESE DOCUMENTSSHALL DO SO ONLY IN CONCERT WITH CURRENT CODECONSIDERATION, FIELD INVESTIGATION/VERIFICATIONAND UTILITY COORDINATION IN ORDER TO PROVIDE ACOMPREHENSIVE INSTALLATION.

PO BOX 93024Albuquerque, NM 87199

505-856-3419

INC.E N G I N E E R S

C O N S U L T I N G

Project #:

Date:

PROJECT ARCHITECT:

By:

File:Sheet of

Plot Date:

AEC-A-EA-1.0.DWG

2/12/2015 4:24:29 PM

Housing and Economic Rural OpportunityPase Del Oro ApartmentsLas Cruces, New Mexico

BOB HALL, AIA

IDA-14-01-P

DECEMBER 22, 2014

AEC

101/30/15 REVISION #1.

1/8"=1'-0"

SECOND FLOOR ELECTRICAL PLAN - BUILDINGS A1, A2, A3

NORTH

1/8"=1'-0"

GROUND FLOOR ELECTRICAL PLAN - BUILDINGS A1, A2, A3

NORTH

GENERAL NOTES:

ELECTRICAL KEYED NOTES:

A REFER TO ARCHITECTURAL ELEVATIONS FOR ADDITIONAL DETAILS.

ARCHITECTURAL ELEVATIONS (DEMO & NEW) SHOW EXTERIOR DUPLEX

RECEPTACLES, ALARM BELL, ALARM STROBE, CONDENSERS, ETC.

B BUILDING A1 WITH APARTMENTS 111, 112, 113, AND 114 IS SHOWN ON THIS

SHEET, BUILDINGS A2 AND A3 ARE SIMILAR BUILDINGS. APARTMENT NUMBERS

ARE 107, 108, 109, 110 FOR BUILDING A2, AND 115, 116, 117, 118 FOR BUILDING A3.

1 REFER TO ENLARGED UNIT STYLE "3" - FIRST FLOOR ELECTRICAL PLAN FOR

WORK REQUIRED IN THIS LEVEL OF THE DWELLING UNIT.

2 REFER TO ENLARGED UNIT STYLE "3" - SECOND FLOOR ELECTRICAL PLAN FOR

WORK REQUIRED IN THIS LEVEL OF THE DWELLING UNIT.

3 MAIN DISTRIBUTION / HOUSE PANEL FOR BUILDING A1, SIMILAR FOR PANELS

"MA2" AND "MA3" WHICH SERVE BUILDINGS A2 AND A3 RESPECTIVELY. REFER

TO POWER RISER DIAGRAM.

4 TYPICAL POWER PANEL FOR STYLE "3" APARTMENTS, REFER TO ASSOCIATED

PANEL SCHEDULE.

5 EXTEND TO CIRCUIT INDICATED IN ASSOCIATED APARTMENT PANEL.

6 INSTALL ROOFTOP GFCI, WR RECEPTACLE ADJACENT TO HVAC UNIT. EXTEND 3

#12 TO CIRCUIT BREAKER INDICATED IN PANEL "MA" AND MAKE ALL FINAL

POWER CONNECTIONS.

7 EXTEND TO CIRCUIT INDICATED THROUGH PHOTOCELL FOR DUSK-TO-DAWN

OPERATION.

8 NUMBER ADJACENT TO RECEPTACLE INDICATES CIRCUIT NUMBER. EXTEND 3

#12 TO CIRCUIT BREAKER IN PANEL "MA" AND MAKE ALL FINAL POWER

CONNECTIONS.

9 CONNECT FIRE SPRINKLER SYSTEM FLOW AND TAMPER SWITCHES TO FIRE

ALARM CONTROL PANEL IN BUILDING "M". PROVIDE FIRE ALARM STROBE ABOVE

DOOR (STROBE ACTIVATED BY LOCAL FLOW & TAMPER SWITCHES).

10 REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATION AND MOUNTING

HEIGHT OF EXTERIOR LIGHTING FIXTURE.

BUILDINGS A1, A2, & A3 ELECTRICAL PLAN

EA-1.0

NTS

KEY PLAN

NORTH

1/8"=1'-0"

ROOF ELECTRICAL PLAN - BUILDINGS A1, A2, A3

NORTH

IECC LIGHTING COMPLIANCE

THE LIGHTING DESIGN SHOWN ON THESE PLANS IS IN COMPLIANCE WITH THE 2009

INTERNATIONAL ENERGY CONSERVATION CODE (IECC) SECTION 505 - ELECTRICAL

POWER AND LIGHTING SYSTEMS AS FOLLOWS:

1. 505.2.2.2 - LIGHTING CONTROLS:

A. THIS PROJECT DOES NOT INCLUDES AREAS LARGER THAN 5,000 SQUARE

FEET.

2. TABLE 505.5.2 - INTERIOR LIGHTING POWER ALLOWANCES: THIS TABLE

LIMITS THE ALLOWABLE LIGHTING POWER DENSITY (LPD) WITHIN A

MULTI-FAMILY DWELLING TO 0.7 W/SF.

BUILDINGS "A1", "A2", AND "A3" AREA IS 5,368 SQ FT, TOTAL ALLOWABLE WATTAGE

IS 3,758W.

INTERIOR LIGHTING LOAD = 3,200W. THIS MULTIFAMILY DWELLING BUILDING HAS

AN LPD OF 0.60W/SF AND COMPLIES WITH MAXIMUM ALLOWABLE LPD.

3. TABLE 505.6.2(2) - INDIVIDUAL LIGHTING POWER ALLOWANCES FOR BUILDING

EXTERIORS: THIS TABLE LIMITS EXTERIOR LIGHTING BASED ON ZONE

CLASSIFICATION AND LOCATION OF LIGHTING. THIS BUILDING IS CLASSIFIED

AS ZONE 2: PREDOMINANTLY RESIDENTIAL, NEIGHBORHOOD BUSINESS

DISTRICT. THE EXTERIOR LIGHTING POWER ALLOWANCES ARE:

BASE SITE ALLOWANCE: 600W

PARKING AREAS AND DRIVES: 0.06 W/SF

WALKWAYS LESS THAN 10' WIDE: 0.7 W/LF

SPECIAL FEATURE AREAS: 0.14 W/SF

MAIN ENTRIES: 20W/LINEAR FOOT OF DOOR WIDTH

OTHER DOORS: 20W/LINEAR FOOT OF DOOR WIDTH

EXTERIOR AREA TOTAL ALLOWABLE WATTAGE FOR BLDGS "A1, "A2, & "A3": 240W.

ACTUAL EXTERIOR LIGHTING LOAD = 168W. THIS BUILDING COMPLIES WITH THE

MAXIMUM EXTERIOR LIGHTING POWER ALLOWANCE.

C

I

E

X

W

M

N

E

0

A

L

O

M

É

AR

C

I

N

I

E

G

A

S

18711

22

APARTMENT 206

(UNIT STYLE "3")

APARTMENT 205

(UNIT STYLE "3")

1

1

PANEL "MB"3

APARTMENT 106

(UNIT STYLE "3")

APARTMENT 105

(UNIT STYLE "3")

PORCH PORCH

7

TYP8

EUH-1

RISER

-

S

TSFS

TYP10

BUILDING B

ROOF

5

CU-3

TO APT. 106

6

5

CU-3

TO APT. 105

6

ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLYRESERVES THE COMMON LAW COPYRIGHT ASSOCIATEDWITH THESE DRAWINGS, AND THESE DOCUMENTS MAYNOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RDPARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC,INC.

THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ANDARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL ORCOMPONENT REQUIRED FOR A COMPLETE, FULLYOPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S).

ANY CONTRACTOR RELYING ON THESE DOCUMENTSSHALL DO SO ONLY IN CONCERT WITH CURRENT CODECONSIDERATION, FIELD INVESTIGATION/VERIFICATIONAND UTILITY COORDINATION IN ORDER TO PROVIDE ACOMPREHENSIVE INSTALLATION.

PO BOX 93024Albuquerque, NM 87199

505-856-3419

INC.E N G I N E E R S

C O N S U L T I N G

Project #:

Date:

PROJECT ARCHITECT:

By:

File:Sheet of

Plot Date:

AEC-B-EB-1.0.DWG

2/12/2015 4:25:13 PM

Housing and Economic Rural OpportunityPase Del Oro ApartmentsLas Cruces, New Mexico

BOB HALL, AIA

IDA-14-01-P

DECEMBER 22, 2014

AEC

101/30/15 REVISION #1.

GENERAL NOTES:

ELECTRICAL KEYED NOTES:

A REFER TO ARCHITECTURAL ELEVATIONS FOR ADDITIONAL DETAILS.

ARCHITECTURAL ELEVATIONS (DEMO & NEW) SHOW EXTERIOR DUPLEX

RECEPTACLES, ALARM BELL, ALARM STROBE, CONDENSERS, ETC.

1 REFER TO ENLARGED UNIT STYLE "3" - FIRST FLOOR ELECTRICAL PLAN FOR

WORK REQUIRED IN THIS LEVEL OF THE DWELLING UNIT.

2 REFER TO ENLARGED UNIT STYLE "3" - SECOND FLOOR ELECTRICAL PLAN FOR

WORK REQUIRED IN THIS LEVEL OF THE DWELLING UNIT.

3 MAIN DISTRIBUTION /HOUSE PANEL FOR THIS BUILDING, REFER TO POWER

RISER DIAGRAM.

4 TYPICAL POWER PANEL FOR STYLE "3" APARTMENTS, REFER TO ASSOCIATED

PANEL SCHEDULE.

5 EXTEND TO CIRCUIT INDICATED IN ASSOCIATED APARTMENT PANEL.

6 INSTALL ROOFTOP GFCI, WR RECEPTACLE ADJACENT TO HVAC UNIT. EXTEND 3

#12 TO CIRCUIT BREAKER INDICATED IN PANEL "MB" AND MAKE ALL FINAL

POWER CONNECTIONS.

7 EXTEND TO CIRCUIT INDICATED THROUGH PHOTOCELL FOR DUSK-TO-DAWN

OPERATION.

8 NUMBER ADJACENT TO RECEPTACLE INDICATES CIRCUIT NUMBER. EXTEND 3

#12 TO CIRCUIT BREAKER IN PANEL "MB" AND MAKE ALL FINAL POWER

CONNECTIONS.

9 CONNECT FIRE SPRINKLER SYSTEM FLOW AND TAMPER SWITCHES TO FIRE

ALARM CONTROL PANEL IN BUILDING "M". PROVIDE FIRE ALARM STROBE ABOVE

DOOR (STROBE ACTIVATED BY LOCAL FLOW & TAMPER SWITCHES).

10 REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATION AND MOUNTING

HEIGHT OF EXTERIOR LIGHTING FIXTURE.

BUILDING B ELECTRICAL PLAN

EB-1.0

1/8"=1'-0"

SECOND FLOOR ELECTRICAL PLAN - BUILDING B

NORTH

1/8"=1'-0"

FIRST FLOOR ELECTRICAL PLAN - BUILDING B

NORTH

NTS

KEY PLAN

NORTH

1/8"=1'-0"

ROOF ELECTRICAL PLAN - BUILDING B

NORTH

IECC LIGHTING COMPLIANCE

THE LIGHTING DESIGN SHOWN ON THESE PLANS IS IN COMPLIANCE WITH THE 2009

INTERNATIONAL ENERGY CONSERVATION CODE (IECC) SECTION 505 - ELECTRICAL

POWER AND LIGHTING SYSTEMS AS FOLLOWS:

1. 505.2.2.2 - LIGHTING CONTROLS:

A. THIS PROJECT DOES NOT INCLUDES AREAS LARGER THAN 5,000 SQUARE

FEET.

2. TABLE 505.5.2 - INTERIOR LIGHTING POWER ALLOWANCES: THIS TABLE

LIMITS THE ALLOWABLE LIGHTING POWER DENSITY (LPD) WITHIN A

MULTIFAMILY DWELLING TO 0.7 W/SF.

BUILDING "B" AREA IS 2,684 SQ FT, TOTAL ALLOWABLE WATTAGE IS 1,879W.

INTERIOR LIGHTING LOAD = 1600W. THIS MULTIFAMILY DWELLING BUILDING HAS

AN LPD OF 0.60W/SF AND COMPLIES WITH MAXIMUM ALLOWABLE LPD.

3. TABLE 505.6.2(2) - INDIVIDUAL LIGHTING POWER ALLOWANCES FOR BUILDING

EXTERIORS: THIS TABLE LIMITS EXTERIOR LIGHTING BASED ON ZONE

CLASSIFICATION AND LOCATION OF LIGHTING. THIS BUILDING IS CLASSIFIED

AS ZONE 2: PREDOMINANTLY RESIDENTIAL, NEIGHBORHOOD BUSINESS

DISTRICT. THE EXTERIOR LIGHTING POWER ALLOWANCES ARE:

BASE SITE ALLOWANCE: 600W

PARKING AREAS AND DRIVES: 0.06 W/SF

WALKWAYS LESS THAN 10' WIDE: 0.7 W/LF

SPECIAL FEATURE AREAS: 0.14 W/SF

MAIN ENTRIES: 20W/LINEAR FOOT OF DOOR WIDTH

OTHER DOORS: 20W/LINEAR FOOT OF DOOR WIDTH

EXTERIOR AREA TOTAL ALLOWABLE WATTAGE FOR BLDG "B": 240W.

ACTUAL EXTERIOR LIGHTING LOAD = 168W. THIS BUILDING COMPLIES WITH THE

MAXIMUM EXTERIOR LIGHTING POWER ALLOWANCE.

C

I

E

X

W

M

N

E

0

A

L

O

M

É

AR

C

I

N

I

E

G

A

S

18711

DNDN

2

22

APARTMENT 203

(UNIT STYLE "2")

APARTMENT 204

(UNIT STYLE "2")

APARTMENT 202

(UNIT STYLE "2")

LIVING

ROOM

102

PANEL "A2"4

DECK

KITCHEN

109

BATH

104

BEDROOM 1

105

BEDROOM 2

106

BEDROOM 2

106

BEDROOM 1

105

BATH

104

KITCHEN

109

LIVING

ROOM

102

DECK DECK

BEDROOM 2

106

BEDROOM 1

105

KITCHEN

109

BATH

104

LIVING

ROOM

102

MECH.

101

MECH.

101

MECH.

101

PANEL "A2" 4

PANEL "A2"4

LINEN

108

PANTRY

107

LINEN

108

PANTRY

107

LINEN

108

PANTRY

107

PANEL "MC"

UPUP

1

1

1

3

APARTMENT 103

(UNIT STYLE "1")

APARTMENT 104

(UNIT STYLE "1")

APARTMENT 102

(UNIT STYLE "1")

BEDROOM 2

106

BATH

104

BEDROOM 1

102

LIVING

109

PORCH

LINEN

103

DINING

108

KITCHEN

107

LAUNDRY

105

MECH.

101

STORAGE

111

STORAGE

110

BEDROOM 2

106

LAUNDRY

105

BATH

104

KITCHEN

107

DINING

108

BEDROOM 1

102

STORAGE

110

STORAGE

110

STORAGE

111

STORAGE

111

KITCHEN

107

BEDROOM 2

106

LAUNDRY

105

BATH

104

DINING

108

BEDROOM 1

102

LIVING

109

LIVING

109

MECH.

101

MECH.

101

PORCH PORCH

PANEL "A1"9 PANEL "A1"9PANEL "A1" 9

7

EUH-1

RISER

-

S

7

8

TYP

7

S

TS

FS

10

11

TYP

CU-4

5

5

CU-4

TO APT. 102

TO APT. 202

6

CU-4

5

5

CU-4

TO APT. 103

TO APT. 203

6

CU-4

5

5

CU-4

TO APT. 104

TO APT. 204

6

BUILDING C

ROOF

ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLYRESERVES THE COMMON LAW COPYRIGHT ASSOCIATEDWITH THESE DRAWINGS, AND THESE DOCUMENTS MAYNOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RDPARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC,INC.

THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ANDARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL ORCOMPONENT REQUIRED FOR A COMPLETE, FULLYOPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S).

ANY CONTRACTOR RELYING ON THESE DOCUMENTSSHALL DO SO ONLY IN CONCERT WITH CURRENT CODECONSIDERATION, FIELD INVESTIGATION/VERIFICATIONAND UTILITY COORDINATION IN ORDER TO PROVIDE ACOMPREHENSIVE INSTALLATION.

PO BOX 93024Albuquerque, NM 87199

505-856-3419

INC.E N G I N E E R S

C O N S U L T I N G

Project #:

Date:

PROJECT ARCHITECT:

By:

File:Sheet of

Plot Date:

AEC-C-EC-1.0.DWG

2/12/2015 4:26:17 PM

Housing and Economic Rural OpportunityPase Del Oro ApartmentsLas Cruces, New Mexico

BOB HALL, AIA

IDA-14-01-P

DECEMBER 22, 2014

AEC

101/30/15 REVISION #1.

BUILDING C ELECTRICAL PLAN

EC1.0

1/8"=1'-0"

SECOND FLOOR ELECTRICAL PLAN - BUILDING C

NORTH

1/8"=1'-0"

GROUND FLOOR ELECTRICAL PLAN - BUILDING C

NORTH

NTS

KEY PLAN

NORTH

GENERAL NOTES:

ELECTRICAL KEYED NOTES:

A REFER TO ARCHITECTURAL ELEVATIONS FOR ADDITIONAL DETAILS.

ARCHITECTURAL ELEVATIONS (DEMO & NEW) SHOW EXTERIOR DUPLEX

RECEPTACLES, ALARM BELL, ALARM STROBE, CONDENSERS, ETC.

1 REFER TO ENLARGED UNIT STYLE "1" - ELECTRICAL PLAN FOR WORK REQUIRED

IN THIS DWELLING UNIT.

2 REFER TO ENLARGED UNIT STYLE "2" - ELECTRICAL PLAN FOR WORK REQUIRED

IN THIS DWELLING UNIT.

3 MAIN DISTRIBUTION / HOUSE PANEL FOR THIS BUILDING, REFER TO POWER

RISER DIAGRAM.

4 TYPICAL POWER PANEL FOR STYLE "2" APARTMENTS, REFER TO ASSOCIATED

PANEL SCHEDULE.

5 EXTEND TO CIRCUIT INDICATED IN ASSOCIATED APARTMENT PANEL.

6 INSTALL ROOFTOP GFCI, WR RECEPTACLE ADJACENT TO HVAC UNIT. EXTEND 3

#12 TO CIRCUIT BREAKER INDICATED IN HOUSE PANEL "MC" AND MAKE ALL FINAL

POWER CONNECTIONS.

7 EXTEND TO CIRCUIT INDICATED THROUGH PHOTOCELL FOR DUSK-TO-DAWN

OPERATION.

8 NUMBER ADJACENT TO RECEPTACLE INDICATES CIRCUIT NUMBER. EXTEND 3

#12 TO CIRCUIT BREAKER IN HOUSE PANEL "MC" AND MAKE ALL FINAL POWER

CONNECTIONS.

9 TYPICAL POWER PANEL FOR STYLE "1" APARTMENTS, REFER TO ASSOCIATED

PANEL SCHEDULE.

10 CONNECT FIRE SPRINKLER SYSTEM FLOW AND TAMPER SWITCHES TO FIRE

ALARM CONTROL PANEL IN BUILDING "M". PROVIDE FIRE ALARM STROBE ABOVE

DOOR (STROBE ACTIVATED BY LOCAL FLOW & TAMPER SWITCHES).

11 REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATION AND MOUNTING

HEIGHT OF EXTERIOR LIGHTING FIXTURE.

1/8"=1'-0"

ROOF ELECTRICAL PLAN - BUILDING C

NORTH

IECC LIGHTING COMPLIANCE

THE LIGHTING DESIGN SHOWN ON THESE PLANS IS IN COMPLIANCE WITH THE 2009

INTERNATIONAL ENERGY CONSERVATION CODE (IECC) SECTION 505 - ELECTRICAL

POWER AND LIGHTING SYSTEMS AS FOLLOWS:

1. 505.2.2.2 - LIGHTING CONTROLS:

A. THIS PROJECT DOES NOT INCLUDES AREAS LARGER THAN 5,000 SQUARE

FEET.

2. TABLE 505.5.2 - INTERIOR LIGHTING POWER ALLOWANCES: THIS TABLE

LIMITS THE ALLOWABLE LIGHTING POWER DENSITY (LPD) WITHIN A

MULTIFAMILY DWELLING BUILDING TO 0.7 W/SF.

BUILDING "C" AREA IS 5,910 SQ FT, TOTAL ALLOWABLE WATTAGE IS 4,137W.

INTERIOR LIGHTING LOAD = 3,650W. THIS MULTIFAMILY DWELLING BUILDING HAS

AN LPD OF 0.62W/SF AND COMPLIES WITH MAXIMUM ALLOWABLE LPD.

3. TABLE 505.6.2(2) - INDIVIDUAL LIGHTING POWER ALLOWANCES FOR BUILDING

EXTERIORS: THIS TABLE LIMITS EXTERIOR LIGHTING BASED ON ZONE

CLASSIFICATION AND LOCATION OF LIGHTING. THIS BUILDING IS CLASSIFIED

AS ZONE 2: PREDOMINANTLY RESIDENTIAL, NEIGHBORHOOD BUSINESS

DISTRICT. THE EXTERIOR LIGHTING POWER ALLOWANCES ARE:

BASE SITE ALLOWANCE: 600W

PARKING AREAS AND DRIVES: 0.06 W/SF

WALKWAYS LESS THAN 10' WIDE: 0.7 W/LF

SPECIAL FEATURE AREAS: 0.14 W/SF

MAIN ENTRIES: 20W/LINEAR FOOT OF DOOR WIDTH

OTHER DOORS: 20W/LINEAR FOOT OF DOOR WIDTH

EXTERIOR AREA TOTAL ALLOWABLE WATTAGE FOR BLDG "C": 360W.

ACTUAL EXTERIOR LIGHTING LOAD = 112W. THIS BUILDING COMPLIES WITH THE

MAXIMUM EXTERIOR LIGHTING POWER ALLOWANCE.

C

I

E

X

W

M

N

E

0

A

L

O

M

É

AR

C

I

N

I

E

G

A

S

18711

DN

1

APARTMENT 200

(UNIT STYLE "4")

1

APARTMENT 201

(UNIT STYLE "4")

PANEL "A4" 4

4 PANEL "A4"

PANEL "MD"

UP

1

PANEL "A4" 4

APARTMENT 100

(UNIT STYLE "4")

1

APARTMENT 101

(UNIT STYLE "4")

3

4 PANEL "A4"

7

7

8

EUH-1

RISER

-

S

TS

FS

9

TYP

10

TYP

CU-4

5

5

CU-4

CU-4

5

5

CU-4

BUILDING D

ROOF

TO APT. 100

TO APT. 200

TO APT. 101

TO APT. 201

66

ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLYRESERVES THE COMMON LAW COPYRIGHT ASSOCIATEDWITH THESE DRAWINGS, AND THESE DOCUMENTS MAYNOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RDPARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC,INC.

THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ANDARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL ORCOMPONENT REQUIRED FOR A COMPLETE, FULLYOPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S).

ANY CONTRACTOR RELYING ON THESE DOCUMENTSSHALL DO SO ONLY IN CONCERT WITH CURRENT CODECONSIDERATION, FIELD INVESTIGATION/VERIFICATIONAND UTILITY COORDINATION IN ORDER TO PROVIDE ACOMPREHENSIVE INSTALLATION.

PO BOX 93024Albuquerque, NM 87199

505-856-3419

INC.E N G I N E E R S

C O N S U L T I N G

Project #:

Date:

PROJECT ARCHITECT:

By:

File:Sheet of

Plot Date:

AEC-D-ED1.0.DWG

2/12/2015 4:27:19 PM

Housing and Economic Rural OpportunityPase Del Oro ApartmentsLas Cruces, New Mexico

BOB HALL, AIA

IDA-14-01-P

DECEMBER 22, 2014

AEC

101/30/15 REVISION #1.

1/8"=1'-0"

ELECTRICAL PLAN - BUILDING D FIRST FLOOR

NORTH

NTS

KEY PLAN

NORTH

1/8"=1'-0"

ELECTRICAL PLAN - BUILDING D SECOND FLOOR

NORTH

BUILDING D ELECTRICAL PLAN

ED1.0

GENERAL NOTES:

ELECTRICAL KEYED NOTES:

A REFER TO ARCHITECTURAL ELEVATIONS FOR ADDITIONAL DETAILS.

ARCHITECTURAL ELEVATIONS (DEMO & NEW) SHOW EXTERIOR DUPLEX

RECEPTACLES, ALARM BELL, ALARM STROBE, CONDENSERS, ETC.

1 REFER TO ENLARGED UNIT STYLE "4" - ELECTRICAL PLAN FOR WORK REQUIRED

IN THIS DWELLING UNIT.

2 NOT USED.

3 MAIN DISTRIBUTION / HOUSE PANEL FOR THIS BUILDING, REFER TO POWER

RISER DIAGRAM.

4 TYPICAL POWER PANEL FOR STYLE "4" APARTMENTS, REFER TO ASSOCIATED

PANEL SCHEDULE.

5 EXTEND TO CIRCUIT INDICATED IN ASSOCIATED APARTMENT PANEL.

6 INSTALL ROOFTOP GFCI, WR RECEPTACLE ADJACENT TO HVAC UNIT. EXTEND 3

#12 TO CIRCUIT BREAKER INDICATED IN PANEL "MD" AND MAKE ALL FINAL

POWER CONNECTIONS.

7 EXTEND TO CIRCUIT INDICATED THROUGH PHOTOCELL FOR DUSK-TO-DAWN

OPERATION.

8 NUMBER ADJACENT TO RECEPTACLE INDICATES CIRCUIT NUMBER. EXTEND 3

#12 TO CIRCUIT BREAKER IN PANEL "MD" AND MAKE ALL FINAL POWER

CONNECTIONS.

9 CONNECT FIRE SPRINKLER SYSTEM FLOW AND TAMPER SWITCHES TO FIRE

ALARM CONTROL PANEL IN BUILDING "M". PROVIDE FIRE ALARM STROBE ABOVE

DOOR (STROBE ACTIVATED BY LOCAL FLOW & TAMPER SWITCHES).

10 REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATION AND MOUNTING

HEIGHT OF EXTERIOR LIGHTING FIXTURE.

1/8"=1'-0"

ELECTRICAL PLAN - BUILDING D ROOF

NORTH

IECC LIGHTING COMPLIANCE

THE LIGHTING DESIGN SHOWN ON THESE PLANS IS IN COMPLIANCE WITH THE 2009

INTERNATIONAL ENERGY CONSERVATION CODE (IECC) SECTION 505 - ELECTRICAL

POWER AND LIGHTING SYSTEMS AS FOLLOWS:

1. 505.2.2.2 - LIGHTING CONTROLS:

A. THIS PROJECT DOES NOT INCLUDES AREAS LARGER THAN 5,000 SQUARE

FEET.

2. TABLE 505.5.2 - INTERIOR LIGHTING POWER ALLOWANCES: THIS TABLE

LIMITS THE ALLOWABLE LIGHTING POWER DENSITY (LPD) WITHIN A

MULTIFAMILY DWELLING TO 0.7 W/SF.

BUILDING "D" AREA IS 5,444 SQ FT, TOTAL ALLOWABLE WATTAGE IS 3,811W.

INTERIOR LIGHTING LOAD = 3200W. THIS MULTIFAMILY DWELLING BUILDING HAS

AN LPD OF 0.59W/SF AND COMPLIES WITH MAXIMUM ALLOWABLE LPD.

3. TABLE 505.6.2(2) - INDIVIDUAL LIGHTING POWER ALLOWANCES FOR BUILDING

EXTERIORS: THIS TABLE LIMITS EXTERIOR LIGHTING BASED ON ZONE

CLASSIFICATION AND LOCATION OF LIGHTING. THIS BUILDING IS CLASSIFIED

AS ZONE 2: PREDOMINANTLY RESIDENTIAL, NEIGHBORHOOD BUSINESS

DISTRICT. THE EXTERIOR LIGHTING POWER ALLOWANCES ARE:

BASE SITE ALLOWANCE: 600W

PARKING AREAS AND DRIVES: 0.06 W/SF

WALKWAYS LESS THAN 10' WIDE: 0.7 W/LF

SPECIAL FEATURE AREAS: 0.14 W/SF

MAIN ENTRIES: 20W/LINEAR FOOT OF DOOR WIDTH

OTHER DOORS: 20W/LINEAR FOOT OF DOOR WIDTH

EXTERIOR AREA TOTAL ALLOWABLE WATTAGE FOR BLDG "D": 240W.

ACTUAL EXTERIOR LIGHTING LOAD = 140W. THIS BUILDING COMPLIES WITH THE

MAXIMUM EXTERIOR LIGHTING POWER ALLOWANCE.

C

I

E

X

W

M

N

E

0

A

L

O

M

É

ARC

I

N

I

E

G

A

S

18711

SSS SS

S S

S

S

GREAT ROOM

101

10

18

9

18

A

A

D

D

E

CC

F

F

F

C

E

E

B

A

SA

SA

SA

SA

SA

SA

20

S

A

19

19

20

S

A

AA

A A A

A

A

23

RESTROOM 2

106

RESTROOM 1

105

SA

MAILBOXES

A

A

S

S

26

9

9

B

CO

5

5

5

5

5

1414

7

5

5

16

16

16

16

6

PANEL "MM"

12

12

13

15

1

4

1

3

1

11

5

T

V

17

17

17

FM

IWH1

F

F

EF2

EF2

24

F

F

F

F

F

TT

CO

21

CU-M

22

25

ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLYRESERVES THE COMMON LAW COPYRIGHT ASSOCIATEDWITH THESE DRAWINGS, AND THESE DOCUMENTS MAYNOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RDPARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC,INC.

THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ANDARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL ORCOMPONENT REQUIRED FOR A COMPLETE, FULLYOPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S).

ANY CONTRACTOR RELYING ON THESE DOCUMENTSSHALL DO SO ONLY IN CONCERT WITH CURRENT CODECONSIDERATION, FIELD INVESTIGATION/VERIFICATIONAND UTILITY COORDINATION IN ORDER TO PROVIDE ACOMPREHENSIVE INSTALLATION.

PO BOX 93024Albuquerque, NM 87199

505-856-3419

INC.E N G I N E E R S

C O N S U L T I N G

Project #:

Date:

PROJECT ARCHITECT:

By:

File:Sheet of

Plot Date:

AEC-M-EM-1.0.DWG

2/12/2015 4:28:17 PM

Housing and Economic Rural OpportunityPase Del Oro ApartmentsLas Cruces, New Mexico

BOB HALL, AIA

IDA-14-01-P

DECEMBER 22, 2014

AEC

101/30/15 REVISION #1.

1/4"=1'-0"

LIGHTING PLAN - BUILDING M

NORTH

ELECTRICAL KEYED NOTES:

NTS

KEY PLAN

NORTH

BUILDING M ELECTRICAL PLANS

EM-1.01/4"=1'-0"

POWER PLAN - BUILDING M

NORTH

1 GFCI PROTECTED DUPLEX RECEPTACLE, 6" ABOVE COUNTERTOP WITH MAJOR AXIS

HORIZONTAL. SPACE RECEPTACLES PER NEC 210.52(C)(1) FOR EVERY WALL COUNTERTOP

SPACE 12" OR WIDER.

2 GFCI PROTECTED DUPLEX RECEPTACLE, INSTALL 42" AFF.

3 INSTALL GFCI PROTECTED DUPLEX RECEPTACLE BELOW COUNTERTOP FOR CONNECTION OF

DISPOSER.

4 INSTALL GFCI PROTECTED DUPLEX RECEPTACLE BELOW COUNTERTOP FOR CONNECTION OF

DISHWASHER.

5 INSTALL RECEPTACLE WITH MAJOR AXIS HORIZONTAL, 6" ABOVE COUNTERTOP.

6 WEATHER-RESISTANT, GFCI-PROTECTED RECEPTACLE, REFER TO SYMBOL LEGEND. INSTALL

24" AFF.

7 DEDICATED RECEPTACLE FOR REFRIGERATOR, INSTALL 42" AFF.

8 COORDINATE EXACT LOCATION OF PANEL WITH ARCHITECT/OWNER PRIOR TO ROUGH-IN.

9 CEILING PADDLE FAN WITH LIGHT KIT, PROVIDE J-BOX AND SUPPORT FOR FAN PER NEC

314.27(D).

10 CEILING FAN (CF) CONTROL SWITCH, MAKE ALL FINAL LIGHTING AND FAN CONTROL

CONNECTIONS TO ASSOCIATED CEILING FAN UNIT.

11 DEDICATED RECEPTACLE FOR MICROWAVE, INSTALL 6" ABOVE COUNTERTOP. REFER TO

ARCHITECTURAL DRAWINGS FOR EXACT HEIGHT/LOCATION.

INSTALL ROOFTOP GFCI, WR RECEPTACLE ADJACENT TO HVAC UNIT.

23 52" PADDLE FAN BY THE BIG ASS FAN COMPANY, MODEL K3127-A2 WITH L.E.D. MODULE.

24 FIRE ALARM CONTROL PANEL (FACP), REFER TO FIRE ALARM SYSTEM DIAGRAM.

25 SOLAR PANEL (BY OTHERS, INSTALLED BY PHOTOVOLTAIC SYSTEM INSTALLER). REFER TO

SHEET PV-1.00.

26 REFER TO ARCHITECTURAL ELEVATIONS FOR EXACT LOCATION AND MOUNTING HEIGHT OF

EXTERIOR LIGHTING FIXTURE.

A. ALL ELECTRICAL WORK SHALL CONFORM TO THE 2014 EDITION OF NATIONAL ELECTRICAL

CODE (NEC).

B. NFPA 72 / FIRE ALARM CODE (1996 EDITION) CHAPTER 2 / HOUSEHOLD FIRE WARNING

EQUIPMENT GOVERNS; SPECIFICALLY 2-2.1.1.1 AND 2-2.3.

C. EACH DWELLING UNIT HAS SINGLE STATION ALARM DEVICE(S) WHICH ALARMS IN THAT

DWELLING UNIT ONLY.

D. LOCATION OF DWELLING UNIT RECEPTACLES IS GOVERNED BY NEC 210.52; SPECIFIC

ATTENTION IS DIRECTED TO EXHIBIT 210.24 AND 210.26.

E. LOCATIONS OF ALL DWELLING UNIT PANELBOARDS SHALL BE FIELD IDENTIFIED AND THE

LOCATIONS FIELD APPROVED BY THE ARCHITECT PRIOR TO ANY ELECTRICAL SYSTEMS

ROUGH-IN.

F. LUMINAIRE AND CEILING PADDLE FAN LOCATIONS SHALL BE FIELD LOCATED BY ARCHITECT

PRIOR TO ANY BRANCH CIRCUIT INSTALLATION.

G. LOCATION OF DEVICES MAY BE ALTERED WITHIN NEC PARAMETERS AND ONLY WITH

ARCHITECT WRITTEN APPROVAL.

H. ALL 120V, 15 AND 20 AMP RECEPTACLES SHALL BE LISTED TAMPER-RESISTANT RECEPTACLES.

GENERAL NOTES:

1/4"=1'-0"

ELECTRICAL PLAN - BUILDING M ROOF (PARTIAL)

NORTH

IECC LIGHTING COMPLIANCE

THE LIGHTING DESIGN SHOWN ON THESE PLANS IS IN COMPLIANCE WITH THE 2009

INTERNATIONAL ENERGY CONSERVATION CODE (IECC) SECTION 505 - ELECTRICAL POWER AND

LIGHTING SYSTEMS AS FOLLOWS:

1. 505.2.2.2 - LIGHTING CONTROLS:

A. THIS PROJECT DOES NOT INCLUDES AREAS LARGER THAN 5,000 SQUARE FEET.

2. TABLE 505.5.2 - INTERIOR LIGHTING POWER ALLOWANCES: THIS TABLE LIMITS THE

ALLOWABLE LIGHTING POWER DENSITY (LPD) WITHIN AN OFFICE BUILDING TO 1.0 W/SF.

BUILDING "M" AREA IS 1,344 SQ FT, TOTAL ALLOWABLE WATTAGE IS 1,344W.

INTERIOR LIGHTING LOAD = 1,300W. THIS OFFICE/COMMONS BUILDING HAS AN LPD OF 0.97W/SF

AND COMPLIES WITH MAXIMUM ALLOWABLE LPD.

3. TABLE 505.6.2(2) - INDIVIDUAL LIGHTING POWER ALLOWANCES FOR BUILDING EXTERIORS:

THIS TABLE LIMITS EXTERIOR LIGHTING BASED ON ZONE CLASSIFICATION AND LOCATION

OF LIGHTING. THIS BUILDING IS CLASSIFIED AS ZONE 2: PREDOMINANTLY RESIDENTIAL,

NEIGHBORHOOD BUSINESS DISTRICT. THE EXTERIOR LIGHTING POWER ALLOWANCES

ARE:

BASE SITE ALLOWANCE: 600W

PARKING AREAS AND DRIVES: 0.06 W/SF

WALKWAYS LESS THAN 10' WIDE: 0.7 W/LF

SPECIAL FEATURE AREAS: 0.14 W/SF

MAIN ENTRIES: 20W/LINEAR FOOT OF DOOR WIDTH

OTHER DOORS: 20W/LINEAR FOOT OF DOOR WIDTH

EXTERIOR AREA TOTAL ALLOWABLE WATTAGE FOR BLDG "M": 360W.

ACTUAL EXTERIOR LIGHTING LOAD = 182W. THIS BUILDING COMPLIES WITH THE MAXIMUM

EXTERIOR LIGHTING POWER ALLOWANCE.

SYSTEM

WITH BATTERIES

TO DEDICATED CIRCUIT MM-11,

PROVIDE CODE REQUIRED

INITIATING CIRCUIT

INDICATING CIRCUIT

INTERFACE RELAY TO VARIOUS

NON-ADDRESSABLE DEVICES

ADDRESSABLE

F F

AUTO-DIALER

T

CONNECT AUTO-DIALER TO TTB,

PROGRAM EMER. CALL NUMBER

PER OWNER'S INSTRUCTION

FIRE ALARM

CONTROL

PANEL

(FACP)

E.O.L.

E.O.L.

E.O.L.

E.O.L.

DIAGRAM IS SCHEMATIC ONLY, NOT

ALL DEVICES SHOWN NECESSARILY USED

FIRE ALARM SYSTEM DIAGRAM

SCALE: NONE

A THE FIRE ALARM CONTRACTOR SHALL EMPLOY THE SERVICES OF A NICET 3 (OR BETTER) FIRE ALARM DESIGNER AND SHALL PROCESS SHOP

DRAWINGS FOR APPROVAL BY THE FIRE MARSHAL. ALL DEVICES REQUIRED BY CODE AND/OR THE AHJ, WHETHER OR NOT SHOWN ON THIS

DRAWING, SHALL BE THE RESPONSIBILITY OF THE FIRE ALARM CONTRACTOR AND SHALL BE INSTALLED AT NO ADDITIONAL COST.

B ALL DEVICES SHALL BE SUITABLE FOR THE ENVIRONMENT IN WHICH THEY ARE LOCATED AND APPROPRIATELY U.L. LISTED WHENEVER APPLICABLE.

C SMOKE DETECTORS SHALL NOT BE LOCATED WITHIN 36" OF ANY AIR REGISTER (SUPPLY OR RETURN).

D PULL STATIONS: PULL STATIONS ARE REQUIRED AT EVERY EXTERIOR MEANS OF EGRESS. MOUNT 3'-5" - 4'-5" TO CENTER OF DEVICE, LOCATE

WITHIN 5' OF EXTERIOR DOOR. MAXIMUM TRAVEL BETWEEN PULL STATIONS IS 200 '.

E WALL MOUNTED STROBES AND HORN/STROBES SHALL BE LOCATED SO THE ENTIRE LENS IS BETWEEN 80" AND 96" AFF

F IN CORRIDORS STROBES AND HORN/STROBES SHALL BE LOCATED WITHIN 15'-0" OF THE END OF THE CORRIDOR AND NOT MORE THAN 100'-0" APART.

G INSTALL MONITOR MODULES AT EACH FLOW AND TAMPER SWITCH (INCLUDING DAMPERS AND P.I.V.'S). VERIFY LOCATIONS WITH MECHANICAL AND

FIRE SPRINKLER DRAWINGS PRIOR TO INSTALLATION.

H INSTALL DUCT DETECTORS ON THE RETURN SIDE OF ALL AIR HANDLING UNITS RATED OVER 2000 CFM. COORDINATE OPERATING VOLTAGE PRIOR TO

INSTALLATION. DUCT DETECTORS SHALL BE FURNISHED BY FIRE ALARM CONTRACTOR AND INSTALLED BY MECHANICAL CONTRACTOR.

I ELECTRICAL CONTRACTOR SHALL INSTALL ALL 3/4" CONDUIT REQUIRED FOR FIRE ALARM SYSTEM. ALL CONDUIT SHALL BE RED OR HAVE RED

BANDING EVERY 5'-0". BUSH ALL EXPOSED CONDUIT ENDS.

J ALL CONDITIONS THAT APPLY SHALL COMPLY WITH NFPA 72.

K FIRE ALARM SYSTEM SHALL HAVE A MINIMUM 1 YEAR WARRANTY ON ALL PARTS AND INSTALLATION. UPON COMPLETION OF INSTALLATION AND

TRAINING THE CONTRACTOR SHALL GIVE THE OWNER A COMPLETE COPY OF THE FIRE ALARM PROGRAMMING MANUAL (INCLUDING PASSWORDS).

L FIRE ALARM CONTRACTOR SHALL HAVE A MINIMUM OF 5 YEARS EXPERIENCE AND UPON REQUEST DEMONSTRATE AT LEAST 3 PAST PROJECTS OF

SIMILAR SCALE AND SCOPE. CONTRACTOR SHALL PROVIDE 24 HOUR EMERGENCY RESPONSE SERVICES DURING THE WARRANTY PERIOD AT NO

ADDITIONAL COST TO THE OWNER. INSTALLER SHALL BE RESPONSIBLE FOR CABLING, TERMINATIONS, PROGRAMMING, ETC... "PARTS & SMARTS"

JOINT VENTURES ARE UNACCEPTABLE.

M FIRE ALARM CONTRACTOR SHALL HAVE 20 CALENDAR DAYS FROM NOTICE OF AWARD TO PRODUCE JOB SPECIFIC SHOP DRAWINGS AND SUBMIT

THEM TO THE FIRE MARSHAL FOR APPROVAL.

N SMOKE DETECTORS IN RESIDENCES SHALL BE INSTALLED PER NFPA 72. SMOKE DETECTORS WITH INTEGRAL ALARM SHALL BE LOCATED IN EACH

BEDROOM, OUTSIDE EACH SLEEPING AREA, AND ON EVERY FLOOR LEVEL. THE SMOKE DETECTORS SHALL BE INTERCONNECTED SO THAT WHEN

ONE SOUNDS, THEY ALL SOUND.

FIRE ALARM GENERAL NOTES:

SUCH AS TAMPER AND FLOW SWITCHES

AT ALL (7) BUILDINGS, REFER TO SITE PLAN.

LOCK-OUT CLIP AT CIRCUIT BREAKER

C

I

E

X

W

M

N

E

0

A

L

O

M

É

AR

C

I

N

I

E

G

A

S

18711

2

2

18

12

T

V

S

S

17

T

V

T

V

17

F

F

8

21

6

4

5

11

SS

PANEL "A1"

7

S

19

7

STORAGE

110

STORAGE

111

BEDROOM 2

106

BEDROOM 1

102

LIVING

109

DINING

108

BATH

104

LINEN

103

MECH

101

PORCH

KITCHEN

107

LAUNDRY

105

W

D

20

22

1

IWH13

F2

9

6

6

6

23

17

24

25

EF3

26

(UNIT 103 ONLY)

26(UNIT 106 ONLY)

18

4

S

T

V

T

V

2

2

7

8

6

T

V

11

F

PANEL "A3"

LIVING

102

PORCH

DINING

103

BEDROOM 1

106

KITCHEN

107

LAUNDRY

104

STORAGE

108

17

S

9

21

1

6

5

6

6

6

20

22

23

W

D

24

BATH 1

105

B

25

EF3

S

17

26

12

(UNITS 106, 107, 115 ONLY)

S

DECK

BEDROOM 2

111

T

V17

17

T

V

18

7

F

BEDROOM 3

114

MECH.

110

BATH

112

STORAGE

109

STAIRS

101

HALLWAY

113

19

IWH13

F3

23

24

17

S

EF1

26

(UNITS 106, 107, 115 ONLY)

T

V

54

8

SS

T

V

S

SS

F

F

H

T

V

S

S

S

17

17

PANEL "A4"

17

17

S

S

19

S

F

SS

SS

SS

11

LIVING

PORCH

DINING

23

20

22

21

W

D

1

IWH13

F4

9

6

6

6

17

C

B

B

B

G

SD

E

E

B

K

H

G

25

B

14

EF3

EF3

12

7

18

T

V

T

V

SS

12

6

8

5

T

V

F

F

SS

11

17

PANEL "A2"

17

4

S

2

SS

SS

2

KITCHEN

109

DINING

110

BEDROOM 2

106

BEDROOM 1

105

BATH

104

DECK

LIVING ROOM

102

MECH.

101

LINEN

108

PANTRY

107

LAUNDRY

103

19IWH1

3F2

22

20

9

21

1

6

6

23

W/D

17

24

25

EF3

ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLYRESERVES THE COMMON LAW COPYRIGHT ASSOCIATEDWITH THESE DRAWINGS, AND THESE DOCUMENTS MAYNOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RDPARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC,INC.

THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ANDARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL ORCOMPONENT REQUIRED FOR A COMPLETE, FULLYOPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S).

ANY CONTRACTOR RELYING ON THESE DOCUMENTSSHALL DO SO ONLY IN CONCERT WITH CURRENT CODECONSIDERATION, FIELD INVESTIGATION/VERIFICATIONAND UTILITY COORDINATION IN ORDER TO PROVIDE ACOMPREHENSIVE INSTALLATION.

PO BOX 93024Albuquerque, NM 87199

505-856-3419

INC.E N G I N E E R S

C O N S U L T I N G

Project #:

Date:

PROJECT ARCHITECT:

By:

File:Sheet of

Plot Date:

AEC-EU-1.0 UNIT PLANS.DWG

2/12/2015 4:29:14 PM

Housing and Economic Rural OpportunityPase Del Oro ApartmentsLas Cruces, New Mexico

BOB HALL, AIA

IDA-14-01-P

DECEMBER 22, 2014

AEC

101/30/15 REVISION #1.

TYPICAL UNIT ELECTRICAL PLANS

EU-1.0

1/4"=1'-0"

UNIT STYLE "1" - ELECTRICAL PLAN

1

1/4"=1'-0"

UNIT STYLE "2" - ELECTRICAL PLAN

2

1/4"=1'-0"

UNIT STYLE "3" - SECOND FLOOR ELECTRICAL PLAN

4

1/4"=1'-0"

UNIT STYLE "3" - FIRST FLOOR ELECTRICAL PLAN5

1/4"=1'-0"

UNIT STYLE "4" - ELECTRICAL PLAN

3

ELECTRICAL KEYED NOTES:

1

.

2 SPLIT-WIRED RECEPTACLE, CONNECT TOP HALF OF DUPLEX RECEPTACLE FOR SWITCH

CONTROL.

3

4 INSTALL GFCI PROTECTED DUPLEX RECEPTACLE BELOW COUNTERTOP FOR CONNECTION

OF DISPOSER.

5 INSTALL GFCI PROTECTED DUPLEX RECEPTACLE BELOW COUNTERTOP FOR CONNECTION

OF DISHWASHER.

6 INSTALL KITCHEN COUNTERTOP RECEPTACLE HORIZONTALLY, 6" ABOVE COUNTERTOP

(AC). SPACE RECEPTACLES PER NEC 210.52(C)(1) FOR EVERY WALL COUNTERTOP SPACE

12" OR WIDER.

7 WEATHER-RESISTANT, GFCI-PROTECTED RECEPTACLE, REFER TO SYMBOL LEGEND.

INSTALL 24" AFF.

8 POWER J-BOX FOR CONNECTION TO RANGE HOOD.

9 TYPICAL APARTMENT PANEL FOR THIS UNIT STYLE, REFER TO ASSOCIATED PANEL

SCHEDULE.

10 NUMBER ADJACENT TO RECEPTACLE INDICATES CIRCUIT NUMBER. EXTEND 3 #12 TO

CIRCUIT BREAKER IN ASSOCIATED APARTMENT PANEL AND MAKE ALL FINAL POWER

CONNECTIONS.

11 DOOR CHIME, INSTALL 6'-6" AFF TO CENTER. CONNECT ASSOCIATED BELL SYSTEM 24V

TRANSFORMER TO NEAREST UNSWITCHED 120V RECEPTACLE CIRCUIT AND MAKE ALL

FINAL POWER AND CONTROL CONNECTIONS.

12 DOOR CHIME SYSTEM PUSH BUTTON (SUPPLIED AS PART OF DOOR CHIME PACKAGE).

13 CEILING PADDLE FAN WITH LIGHT KIT, PROVIDE J-BOX AND SUPPORT FOR FAN PER NEC

314.27(D).

14 FAN SPEED CONTROL SWITCH FURNISHED WITH CEILING PADDLE FAN, MAKE ALL FINAL

CONTROL CONNECTIONS TO ASSOCIATED FAN (CONTROL LIGHTING INDEPENDENTLY AS

SHOWN).

15 DEDICATED RECEPTACLE FOR MICROWAVE, INSTALL IN CASEWORK. REFER TO

ARCHITECTURAL DRAWINGS FOR EXACT HEIGHT/LOCATION.

16 ALL DWELLING UNIT 120V, 15 AND 20A RECEPTACLES SHALL BE TAMPER-RESISTANT.

17 120V COMBINATION SMOKE DETECTOR/

DEDICATED RECEPTACLE FOR REFRIGERATOR, INSTALL 42" AFF

A. ALL ELECTRICAL WORK SHALL CONFORM TO THE 2014 EDITION OF NATIONAL ELECTRICAL

CODE (NEC).

B. PROVIDE HOUSEHOLD FIRE WARNING EQUIPMENT IN CONFORMANCE WITH NFPA 72 / FIRE

ALARM CODE (1996 EDITION) CHAPTER 2; SPECIFICALLY 2-2.1.1.1 AND 2-2.3.

C. EACH DWELLING UNIT HAS SINGLE STATION ALARM DEVICE(S) WHICH ALARMS IN THAT

DWELLING UNIT ONLY.

D. THE LOCATION OF DWELLING UNIT RECEPTACLES SHALL CONFORM TO NEC 210.52.

E. LOCATIONS OF ALL DWELLING UNIT PANELBOARDS SHALL BE FIELD APPROVED BY THE

ARCHITECT PRIOR TO ANY ELECTRICAL SYSTEMS ROUGH-IN.

F. LUMINAIRE AND CEILING PADDLE FAN LOCATIONS SHALL BE FIELD APPROVED BY THE

ARCHITECT PRIOR TO ANY BRANCH CIRCUIT INSTALLATION.

G. DEVICE LOCATION AS SHOWN ON DRAWINGS IS SOMEWHAT SCHEMATIC AND MAY BE

ALTERED WITHIN NEC PARAMETERS AND AS FIELD CONDITIONS REQUIRE. ANY DEVICE

RELOCATION GREATER THAN 12" REQUIRES ARCHITECT'S WRITTEN APPROVAL.

H. ALL 120V, 15 AND 20 AMP RECEPTACLES SHALL BE LISTED TAMPER-RESISTANT

RECEPTACLES.

I. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER (AFCI) PROTECTION FOR 15 AND 20 AMP

BRANCH CIRCUITS AS REQUIRED BY NEC 210.12.

GENERAL NOTES:

ESP-1.0

ELECTRICAL SPECIFICATIONS

ATLAS ELECTRICAL CONSTRUCTION, INC. EXPRESSLYRESERVES THE COMMON LAW COPYRIGHT ASSOCIATEDWITH THESE DRAWINGS, AND THESE DOCUMENTS MAYNOT BE REPRODUCED, ALTERED, OR GIVEN TO ANY 3RDPARTY WITHOUT EXPRESS WRITTEN PERMISSION OF AEC,INC.

THESE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ANDARE NOT MEANT TO FULLY DESCRIBE EVERY DETAIL ORCOMPONENT REQUIRED FOR A COMPLETE, FULLYOPERATIONAL CURRENT CODE COMPLIANT SYSTEM(S).

ANY CONTRACTOR RELYING ON THESE DOCUMENTSSHALL DO SO ONLY IN CONCERT WITH CURRENT CODECONSIDERATION, FIELD INVESTIGATION/VERIFICATIONAND UTILITY COORDINATION IN ORDER TO PROVIDE ACOMPREHENSIVE INSTALLATION.

PO BOX 93024Albuquerque, NM 87199

505-856-3419

INC.E N G I N E E R S

C O N S U L T I N G

Project #:

Date:

PROJECT ARCHITECT:

By:

File:Sheet of

Plot Date:

AEC-ESP-1.0-SPECS.DWG

2/12/2015 4:30:57 PM

Housing and Economic Rural OpportunityPase Del Oro ApartmentsLas Cruces, New Mexico

BOB HALL, AIA

IDA-14-01-P

DECEMBER 22, 2014

AEC

101/30/15 REVISION #1.

SECTION 26 0500- BASIC ELECTRICAL MATERIALS AND METHODS

PART 1 GENERAL

1.1 RELATED DOCUMENTS

A The Contractor shall make a thorough field investigation of all work described above and shown

on the contract drawings prior to submitting a bid on this project to ensure the bid is complete

and comprehensive.

1.2 SUMMARY

A This Section includes the following electrical materials and methods:

1. Building wire, connectors, and splices for branch circuits and feeders.

2. Supporting devices for electrical components.

B Furnish all labor and materials necessary for complete electrical service to all equipment which

requires electric connections installed as part of this project. Provide temporary electric power of

1.3 ELECTRICAL SPECIFICATION INDEX

26 0500 - Basic Electrical Materials and Methods

26 0533 - Raceways and Boxes

26 2816 - Enclosed Switches and Circuit Breakers

26 2416 - Panelboards

1.4 SUBMITTALS

A General: Electrical submittals shall be provided. The Contractor shall provide submittal

information for:

1. Panelboards

2. Safety switches

3. Fuses

4. Light Fixtures

5. Occupancy Sensors (Controls)

6. Fire Alarm

1.5 QUALITY ASSURANCE

A Comply with the 2011 edition of NFPA 70 (NEC) for components and installation.

1.6 DRAWINGS

A All drawings included in the Contract Documents are to be considered as part of the work.

Architectural drawings shall take precedence over electrical drawings.

B As-built drawings: During project construction, the Contractor shall maintain an accurate record

of the installation of all electrical work, carefully noting any deviations from the contract

drawings. Upon project completion, the Contractor shall transfer all as-built information to a

single neat and legible drawing set.

C Upon completion of the fire alarm system installation, the contractor shall give the owner a complete

copy of the fire alarm programming manual (including passwords).

PART 2 - PRODUCTS

2.1 EQUIPMENT REQUIREMENTS

A The electrical equipment connections on the drawings are based on specific equipment

and models. Any additional costs resulting from any changes in equipment furnished will

be the complete responsibility of the Division furnishing the equipment.

2.2 BUILDING WIRE

A Description: Single conductor, copper. Solid conductor for No. 10 AWG and smaller; stranded

conductor for larger than No. 10 AWG.

2.3 SUPPORTING DEVICES

A Channel and angle support systems, hangers, anchors, sleeves, brackets, fabricated items, and

fasteners are designed to provide secure support from the building structure for electrical

components.

1. Material: Steel, except as otherwise indicated, protected from corrosion with zinc coating or

with treatment of equivalent corrosion resistance using approved alternative finish or

inherent material characteristics.

2. Metal Items for Use Outdoors or in Damp Locations: Hot-dip galvanized steel, except as

otherwise indicated.

B Steel channel supports have 9/16-inch diameter holes at a maximum of 8 inches o.c., in at least 1

surface.

1. Fittings and accessories mate and match with channels and are from the same

manufacturer.

C Nonmetallic Channel and Angle Systems: Structural-grade, factory-formed, fiberglass-resin

channels and angles with 9/16-inch diameter holes at a maximum of 8 inches o.c., in at least one

surface.

1. Fittings and accessories shall mate with channels or angles and be of the same manufacturer.

2. Fitting and Accessory Material: Same as channels, except metal items may be stainless steel.

2.4 ELECTRICAL IDENTIFICATION

A Color code all wiring as follows: For 120/240V:

Phase A-Black; Phase B-Red; Neutral-White; Ground-Green.

2.5 TOUCH-UP PAINT

A For Equipment: Provided by equipment manufacturer and selected to match equipment finish.

B For Non-equipment Surfaces: Matching type and color of undamaged, existing adjacent finish.

PART 3 - EXECUTION

3.1 EQUIPMENT INSTALLATION REQUIREMENTS

A Where components and equipment are indicated to be installed, the term "install" includes all

work, materials, and associated accessories necessary to obtain a completely operational system.

B Install items level, plumb, and parallel and perpendicular to other building systems and

components, except where otherwise indicated.

3.2 WIRING METHODS

A Feeders: Type THHN/THWN, in copper conductor, RHW or XHHW in aluminum conductor, in

raceway, except as otherwise indicated. Branch Circuits: Type THHN/THWN, in raceway or type

MC Cable or type NM, NMC or NMS where allowed by NEC and State of New Mexico codes.

B Type MC cable shall be acceptable where in compliance with current NEC.

3.3 ELECTRICAL SUPPORTING METHODS

A Damp Locations and Outdoors: Hot-dip galvanized materials.

B Dry Locations: Steel materials.

C Strength of Supports: Adequate to carry all present and future loads, times and safety factor of at

least 4; 200-lb-minimum design load.

3.4 INSTALLATION

A Install conductors according to manufacturer's written instructions and NECA's "Standard

of Installation". Coordinate special systems work with Owner and Cabling Contractor.

B Conductor Splices: Keep to the minimum possible.

C Install devices to securely and permanently fasten and support electrical components.

D Raceway Supports: Comply with NFPA 70 and the following requirements:

1. Conform to manufacturer's recommendations for selecting and installing supports.

E Fire stopping: Apply to cable and raceway penetrations of fire-rated floor and wall assemblies.

Perform fire stopping to reestablish the original fire-resistance rating of the assembly at the

penetration.

F Fastening: Unless otherwise indicated, securely fasten electrical items and their supporting

Install identification devices where required.

1. Install labels where indicated and at locations for best convenience of viewing.

3.5 CUTTING AND PATCHING

A Cut, channel, chase, and drill floors, walls partitions, ceilings, and other surfaces necessary for

electrical installations. Perform cutting by skilled mechanics of the trades involved.

B General Contractor shall repair disturbed surfaces to match adjacent undisturbed surfaces.

3.6 TESTING

A Perform complete testing on all systems to ensure proper operation.

END OF SECTION 26 0500

SECTION 26 0533 - RACEWAYS AND BOXES

PART 1 GENERAL

1.1 SECTION INCLUDES

A Conduits and fittings

B Outlet boxes

1.2 QUALITY ASSURANCE

A Comply with the 2011 National Electrical Code (NEC) for installation.

PART 2 PRODUCTS

2.1 COATINGS

A Provide products with zinc coating or with treatment of equivalent corrosion resistance.

2.2 ELECTRICAL METALLIC TUBING AND FITTINGS (EMT)

A Furnish galvanized electrical metallic tubing (EMT) that meets the requirements of UL797 -

Electrical Metallic Tubing, NEMA C80.3 - Steel Electrical Metallic Tubing (EMT).

B Furnish compression or set-screw type fittings that meet the requirements of UL514B - Fittings

for Conduit and Outlet Boxes, and ANSI/NEMA FB1 - Fittings, Cast Metal Boxes, and Conduit

Bodies for Conduit and Cable Assemblies. Furnish insulated throat connectors.

2.3 FLEXIBLE METAL CONDUIT AND FITTINGS

A Furnish galvanized steel flexible metal conduit that meets the requirements of UL1 - Flexible

Metal Electrical Conduit.

2.4 OUTLET BOXES

A Provide outlet boxes selected for specific installations using the guidance in NEMA OS 3, Selection

and Installation Guidelines for Electrical Outlet Boxes, and the requirements of this Selection.

B For dry locations provide galvanized steel outlet boxes that comply with UL Standard 514-A -

Metallic Outlet Boxes and ANSI/NEMA OS1 - Sheet-Steel Outlet Boxes, Device Boxes, Device

Boxes, Covers, and Box Supports.

C For damp or wet locations and for surface-mounted RMC or IMC raceways systems, provide

outlet boxes that comply with UL Standard 498 and 514, ANSI/NEMA FB1.

2.5 PULL AND JUNCTION BOXES

A For dry locations in clean, non-contaminated environments use galvanized sheet steel pull and

junction boxes that comply with UL Standard 50 Type 1 and the NEC as to size and construction.

Use boxes not less than 4 inches square x 1-1/2 inches deep with screw-secured covers. Provide

larger boxes as required by the number and size of conduits and conductors.

B For damp or wet, non-corrosive locations, in conduit runs 1 inch trade size and larger, provide

galvanized sheet-steel pull and junction boxes and covers that comply with UL 50 Type 3R.

PART 3 EXECUTION

3.1 EXAMINATION

A Examine surfaces to receive raceways and boxes for compliance with installation tolerances and

other conditions affecting performance of the raceway system. Do not proceed with installation

until unsatisfactory conditions have been corrected.

3.2 GENERAL

A Install raceways and boxes according to NECA 1 Standard Practices for Good Workmanship in

Electrical Construction.

B Raceway termination points and box locations shown on the Drawings are in approximate

locations unless dimensioned. Verify locations before rough-in.

C Ground and bond raceways and boxes as required by the NEC.

D Support raceways and boxes in accordance with the NEC. Arrange raceways and boxes to

maintain headroom and present a neat, workmanlike appearance.

3.3 CONDUIT INSTALLATION

A For wiring systems less than 1000 volts use conduit materials in accordance with the NEC.

B Use 3/4-inch or larger conduit to enclose multiple conductors larger than 12 AWG. For

C Conceal conduits within walls, floors and ceilings.

D Install insulating bushing or connectors with an insulated throat to protect conductors or cables

at conduit terminations.

E Join nonmetallic conduit using cement as recommended by manufacturer.

F Install plastic-coated RMC and fittings according to the NEC and manufacturer's instructions. Use

only fittings approved for use with that material. Patch all nicks and scrapes in PVC coating after

installing conduits.

G Do not use RNC 90 degree elbows larger than 3 inch trade size; use plastic-coated RMC,

tape-wrapped RMC, or tape-wrapped IMC for 3-1/2 inch trade size and larger 90 degree elbows.

H Maintain the following minimum clearances between conduit and surfaces with temperatures

exceeding 104 degrees F (40 degrees C):

1. 6" at perpendicular crossings, 12" between parallel runs.

3.5 OUTLET BOX INSTALLATION

A Install outlet boxes with centers at the following heights unless noted otherwise on the Drawings:

1. Receptacles, general use duplex type: 18 inches to center of j-box above finished floor (AFF).

3. Light switches: center 44 inches AFF to center and within 6 inches of door frame.

5. Fire alarm audible/visible alarm devices: center of strobe light 80 inches AFF or 6 inches below

the ceiling, whichever is lower.

6. Fire alarm pull stations: center 44 inches AFF to center.

B Install a multi-gang box where more than one device is mounted together. Do not use sectional

type boxes. Mount multiple controls as close together as possible and in-line with each other.

C Install box with plaster ring for single or multiple device outlets.

D Use flush mounted outlet boxes in finished areas.

F Install a blank cover plate on each outlet box in which no device is installed.

3.6 CLEANING

A Clean interior of boxes to remove dust, debris, and other material.

B Repair damage to galvanized finishes with zinc-rich paint recommended by manufacturer.

C Repair damage to paint finishes with matching touch-up paint.

END OF SECTION 26 0533

SECTION 26 2816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS

PART 1 GENERAL

1.1 SECTION INCLUDES

A Safety switches, fuses, enclosed circuit breakers.

1.2 SUBMITTALS

A Submit the following:

1. Product Data: Submit manufacturer's technical data for each type of safety switch and

enclosed circuit breaker.

1.3 QUALITY ASSURANCE

A Comply with the 2011 National Electrical Code (NEC) for components and installation.

B Provide safety switches and circuit breaks that are listed and labeled by a Nationally Recognized

Testing Laboratory (NRTL) for the application, installation condition, and the environment in

which installed.

C Comply with the following standards as applicable:

1. NEMA AB 1 (UL 489) Molded Case Circuit Breakers, Molded Case Switches, and Circuit

Breaker Enclosures; UL 50 - Enclosures for Electrical Equipment.

PART 2 PRODUCTS

2.1 SAFETY SWITCHES

A Provide NRTL-listed, NEMA KS 1 Type HD safety switches with ratings and number of poles as

indicated on the Drawings. Use Type HD for switches rated 100A and above.

B Provide safety switches for use as service equipment that are NRTL labeled for the application.

C Provide enclosure type in accordance with NEMA ratings as required by the conditions of use.

D For fusible safety switches provide rejection clip designed to accommodate NEMA FU 1, Class R.

E Furnish each safety switch with an equipment ground bar.

F Furnish a neutral bar for each safety switch used on a circuit that includes a grounded "neutral"

G Provide each safety switch with a factory-installed cover-mounted viewing window positioned

over the blades to allow visual verification of ON-OFF status.

H Provide auxiliary electrical interlock switches with safety switches as indicated on the Drawings

or as required by the application.

2.2 FUSES

A Provide NRTL-listed, NEMA FU 1 Class R fuses for fusible safety switches as indicated on the

Drawings or required by the manufacturer of served equipment.

2.3 ENCLOSED CIRCUIT BREAKERS

A Provide NRTL-listed, NEMA AB 1 enclosed molded-case circuit breakers with ratings and number

of poles and indicated on the Drawings.

PART 3 EXECUTION

3.1 EXAMINATION

A Examine surfaces to receive safety switches and enclosed circuit breakers for compliance with

installation tolerances and other conditions affecting performance of the product. Do not proceed

with installation until unsatisfactory conditions have been corrected.

3.2 INSTALLATION

A Install safety switches and enclosed circuit breakers where indicated on the Drawings and

according to manufacturer's instructions, NECA 1, and the NEC. Have the manufacturer's

installation instruction available at the construction site.

B Install each safety switch and enclosed circuit breaker so the interlock bypass will be accessible.

C Provide supports and seismic anchorage in accordance with the manufacturer's installation

instructions.

D Ground and bond safety switches and enclosed circuit breakers as required by NEC.

E Install conduits as required in Section 26 0533 Raceways and Boxes for Electrical Systems.

F Install conductors as follows:

1. Use compression type lugs to connect all service feeders.

2. Tighten electrical connectors and terminals to the manufacturer's published torque

tightening values. Where manufacturer's torque values are not indicated, use those

specified in UL 486A.

G Install fuses in fusible safety switches as indicated on the Drawings or as required to match

installed motor or load characteristics.

3.3 IDENTIFICATION

A Identify safety switches and enclosed circuit breakers with unit name and circuit number.

3.4 FIELD QUALITY CONTROL

A Clean interior and exterior of safety switches and enclosed circuit breakers.

B Verify that ratings for safety switches and enclosed circuit breakers match values indicated on

the Drawings.

SECTION 26 2416 - PANELBOARDS

PART 1 GENERAL

A Power panelboards

1.2 SUBMITTALS

A Submit the following:

1. Catalog data: Submit catalog data describing each type panelboard, accessory item,

and component specified. Include data substantiating that materials comply with

specified requirements.

1.3 QUALITY ASSURANCE

A Comply with the 2011 National Electrical Code (NEC) for installation.

PART 2 PRODUCTS

2.1 PANELBOARDS, GENERAL REQUIREMENTS

A Provide panelboard cabinets for flush or surface mounted as indicated on the Drawings.

1. Furnish NEMA Type 1 enclosures, except where the Drawings indicate the following

enclosure requirements: NEMA 3R - Raintight

2. Provide galvanized steel cabinets constructed according to UL 50 requirements.

B Provide trim fronts that meet the strength and rigidity requirements of UL 50.

1. Fronts for flush panels shall overlap boxes at least 1 inch.

2. Fronts shall have ANSI 49 medium gray enamel.

3. For NEMA 1 panelboards, provide fronts with hinged trim construction having a piano

hinge down one side. The front shall contain a smaller lockable door, which when open,

shall provide access to all conductors and wiring terminals.

4. Provide a metal panelboard directory frame mounted inside the panelboard door.

C Panelboard phase and neutral bus shall be copper.

D Provide copper equipment ground bus that is adequate for feeder and branch circuit equipment

ground conductors. Bond ground bus to cabinet.

E Provide thermal-magnetic circuit breakers that meet the requirements of UL 489 Molded Case

Circuit Breakers and NEMA AB 1 Molded Case Circuit Breakers and Molded Case Switches.

2.2 LIGHTING AND APPLIANCE PANELBOARDS

A Provide lighting and appliance branch circuit panelboards as indicated on the Drawings.

B Lighting and appliance branch circuit panelboards enclosures shall be not less than 20 inches or

more than 26 inches in width.

C Manufacturers:

1. Cutler-Hammer: PRL3a (480Y/277V) and PRL1a and PRL2a (208Y/120V or 120/240V).

2. General Electric: Spectra (480Y/277V) and AQ (208Y/120V or 120/240V).

3. Siemens: P2 (480Y/277V) and P1 (208Y/120V or 120/240V).

4. Square D: I-Line (480Y/277V) and NQOD (208Y/120V or 120/240V).

2.3 LIGHTING AND APPLIANCE LOAD CENTERS

A Provide lighting and appliance branch circuit load centers as indicated on the Drawings.

B Load centers identified for use as service equipment are to be labeled for this application.

C A directory label shall be provided with circuits identified as indicated on the schedule.

D Bus bar connections to the branch circuit breakers shall be the distributed phase type and shall

accept plug on circuit breakers.

E Manufacturers:

1 Cutler Hammer, General Electric, Siemens or Square D

PART 3 EXECUTION

A Examine surfaces to receive panelboards for compliance with installation tolerances and other

installation instructions.

3.2 INSTALLATION

A Install panelboards where indicated on the Drawings and according to manufacturer's

instructions, NECA 407, and the NEC.

B Ground and bond panelboards as required by NEC.

C At all flush panelboards install four 1-inch spare conduits, extend to above accessible ceiling space.

3.3 IDENTIFICATION

A Provide typewritten circuit directories for each branch circuit panel board. Revise directories to

reflect ANY field circuiting changes.

3.4 FIELD QUALITY CONTROL

A Clean, inspect, test, and energize installed panelboards in accordance with NECA 407.

B After completing installation, cleaning, and testing, touch-up any scratches to match finish.

END OF SECTION 26 2916

END OF SECTION 26 2816

3.1 EXAMINATION

1.1 SECTION INCLUDES

4. Thermostats: center 44 inches AFF to center.

C Upsize circuits and feeders as necessary to limit overall voltage drop to the furthest outlet on a

branch circuit to 5% maximum.

B Fuses shall be dual element Buss Fusetrins unless noted otherwise.

C Safety switches rated 100A and above shall be heavy-duty rated.

Where shown within two feet of each other, group voice/data outlets and receptacles together.

2. Voice/data outlets: 18 inches AFF to center.

3.8 TOUCH-UP PAINT

A Thoroughly clean damaged areas and provide primer, intermediate, and finish coats.

I Install pull string in all empty and spare conduits.

B Provide plastic nameplates for power panels. Nameplate to include panel designation, voltage,

and phase, e.g. PANEL "MM" / 120/240V / 1-PHASE.

3.7 TRAINING

A Instruct Owner's personnel in the proper operation of electrical systems.

sufficient capacity to allow construction.

home-run circuits, conduit shall be a minimum of 3/4".

D Home-run conduits (all conduits connected to a panel) shall be a minimum of 3/4 inch.

J Any conduit run below slab on grade shall be a minimum of 6" below slab.

conductor.

B Provide a lime green spare fuse cabinet with "Fuses" stenciled in OSHA purple. Cabinet shall be

sized to hold one set of (2) fuses of each size used on this project.

H Install spare fuse cabinet in main electrical room or alternate location as shown on Drawings.

PART 1 GENERAL

1.1 SUMMARY

A. SECTION INCLUDES

1. Receptacles, Snap switches, Dimmer switches, Wall plates, Multi-outlet assemblies.

1.2 QUALITY ASSURANCE

A. Furnish products listed and labeled by a nationally recognized testing laboratory (NRTL) for the

PART 2 PRODUCTS

2.1 RECEPTACLES

A. 120V convenience duplex receptacles connected to general use branch circuits: Provide

straight-blade NEMA 5-15R, 15A, duplex receptacles. Use "Decora" style, ivory-colored

receptacles.

B. 120V ground fault circuit interrupter (GFCI) receptacles: Provide straight-blade NEMA 5-15R, 15A,

feed-through type, self-testing GFCI, duplex receptacles that meet the requirements of UL

Standard 943, Ground Fault Circuit Interrupters.

C. 120V exterior duplex receptacles: Provide GFCI type with integral weather-resistant (WR) cover

D. Dedicated duplex receptacles: Provide 20A rated device.

2.4 SNAP SWITCHES

A. Provide single pole, double pole, three-way, four-way and pilot handle snap switches as indicated

on the Drawings. Use "Decora" style, ivory-colored switches.

B. Switches shall be rated 20A, 120-277 volts AC, back and side wired, screw pressure terminal,

quiet type AC switch with yoke grounding screw.

2.5 WALLBOX DIMMING CONTROLS

A. Dimmer wattage rating shall exceed connected load by 10 percent minimum, contractor shall verify

load indicated on the Drawings matches actual fixtures/lamps supplied.

2.6 WALL PLATES

A. For flush mounted interior receptacles and wall switches, provide compatible nylon cover plate,

ivory in color.

PART 3 EXECUTION

3.1 PREPARATION

A. Verify outlet boxes are installed at proper locations and heights.

3.2 INSTALLATION

A. Install devices plumb, level, and secure.

B. All duplex receptacles in dwelling units shall be tamper-resistant in accordance with NEC 406.12.

C. All duplex receptacles in dwelling units shall be AFCI protected in accordance with NEC 210.12.

D. All duplex receptacles within 6' of a sink or bathtub/shower stall, in bathrooms, in garages, and in

laundry area shall be GFCI protected in accordance with NEC 210.8.

E. Install wall plates on each switch, receptacle, and blank outlet after painting is complete.

F. Install GFCI-protected slave receptacle for electric drinking fountains (EDF) per NEC 422.52

concealed within EDF cabinet.

3.4 IDENTIFICATION

A. Identify wiring devices with circuit number written on back of cover plate using permanent ink pen.

3.5 FIELD QUALITY CONTROL

A. Operate each switch and receptacle at least six times with circuit energized.

SECTION 26 2726 - WIRING DEVICES

26 2726 - Wiring Devices

END OF SECTION 26 2726