GeneralSpecifications
GS 01U10B00-02EN-R
GS 01U10B00-02EN-R, 1st edition, 2018-10-24
Features
▪ Interoperability: PROFIBUS specifications grantthe interoperability of the field instruments withoutpreparing designated softwares for the instrument.
▪ Reduction of instrumentation cost: The multi-drop wiring on the PROFIBUS communication linecontributes to the reduction of wiring cost.
▪ Function blocks: AI function blocks, Totalizerfunction blocks and AO function block are avail-able. (PROFIBUS PA Profile 3.02 Compliant)
▪ Supported tools: DTM for FieldMate R3.04 or later, EDDL for SIEMENS SIMATIC PDM V9.0 or V9.1.
PROFIBUS in general
▪ PROFIBUS is a vendor-independent and openfieldbus based on the international standardIEC61158 and IEC61784. It covers a wide rangeof applications in manufacturing and process auto-mation fields. Vendor-independence and open-ness allow communication between devices of dif-ferent manufactures with no special interface ad-justment. Thus, based on PROFIBUS PA specifi-cations, ROTAMASS Total Insight PROFIBUS PAmodels offer more flexible instrumentation througha higher level communication capability and pro-pose the cost reduction by multi-drop wirings withless cables.
Coriolis Mass Flow and Density MeterAddendum to General Specificationsfor PROFIBUS PA
ROTAMASS Total Insight
Table of contents
2 / 10 GS 01U10B00-02EN-R, 1st edition, 2018-10-24
Table of contents1 Introduction................................................................................................................................................ 3
1.1 General information .......................................................................................................................... 3
2 PROFIBUS PA Specifications................................................................................................................... 42.1 Inputs and outputs ............................................................................................................................ 5
2.1.1 PROFIBUS PA Output signals............................................................................................. 5
3 Advanced functions and Features on Demand (FOD) ........................................................................... 7
4 Ordering information................................................................................................................................. 84.1 Model code ....................................................................................................................................... 8
4.1.1 Transmitter ........................................................................................................................... 84.1.2 Communication type and I/O ............................................................................................... 8
4.2 Overview model codes PROFIBUS PA restrictions.......................................................................... 84.3 Overview options PROFIBUS PA restrictions................................................................................... 94.4 Ordering Instructions ........................................................................................................................ 9
General information
Addendum to General Specifications for PROFIBUS PAIntroduction
GS 01U10B00-02EN-R, 1st edition, 2018-10-24 3 / 10
1 Introduction
1.1 General information
This document is an addendum to the General Specifications GS 01U10B0␣ -00␣␣-R. Itdescribes the differences of the delivered product compared to the applicable “GeneralSpecifications” that specifies standard devices of ROTAMASS Total Insight series. Thedeviations could be model code related, design or configuration only and are listed on thenext pages.
Addendum to General Specifications for PROFIBUS PAPROFIBUS PA Specifications
4 / 10 GS 01U10B00-02EN-R, 1st edition, 2018-10-24
2 PROFIBUS PA Specifications
Overviewof functional scopeof the RotamassPROFIBUS PAspecifications
Functional scope Values, ranges and specifications availableModel code(position 13)
G0 (PROFIBUS PA) ●G1 (PROFIBUS PA Intrinsic Safe) ●
Output signal:Digital communication signal based on PROFIBUS PA protocol (Profile Revision R3.02 Compliant)PROFIBUS PA block specifications:
▪ Transducer block (TB):Flow Transducer Block (FTB) ●Concentration Transducer Block (CTB) optionalLCD Indicator Transducer Block (LTB) ●Maintenance Transducer Block (MTB) ●Advanced Diagnostic Transducer Block (ADTB) optional
▪ Analog Input block (AI):1)
AI1: Mass flow ●AI2: Density ●AI3: Temperature ●AI4: Volume flow ●AI5: Reference density ●AI6: Corrected volume flow ●
▪ Totalizer block (TOT):1)
TOT1: Mass ●TOT2: Volume ●TOT3: Corrected volume flow ●
▪ Analog output block (AO):1)
AO: Pressure ●▪ Profile Revision R3.02:
Condensed Status (NE 107) ●Life Cycle Management (Automatic IDENT_NUMBERadaptation) ●
▪ DP-V0 cyclic data:AI x 6, TOT x 3, AO x 1 ●
▪ IDENT number:0x45A0 (manufacturer specific) ●0x9740, 0x9741, 0x9742 (profile specific) ●
▪ GSD:YEC45A0.gsd, pa139740.gsd, pa139741.gsd,pa139742.gsd ●
Conditions of Communication Line:Supply voltagefrom the Bus: 9 to 32 VDC ●
Current draw: 15mA (maximum) ●
Inputs and outputs
Addendum to General Specifications for PROFIBUS PAPROFIBUS PA Specifications
GS 01U10B00-02EN-R, 1st edition, 2018-10-24 5 / 10
Functional scope Values, ranges and specifications availableBus address switch:via Hardware address switch or via SoftwareAlarm selection function:These informations are indicated in DIAGNOSTICS parameter, which can be handledduring normal operation.Displayed language:In the case of PROFIBUS PA communication type, different language packages are possible to choose.
1) Factory default setting; can be changed by parameter "Channel".
meaning of "−": not available; meaning of "●": available
2.1 Inputs and outputs
For the PROFIBUS PA version there is only one configuration of the connection terminal.Following is the configuration of the connection terminal (value G0 and G1 on model codeposition 13):
WP
ON/
OFF
Fieldbus Pulse
(I/O1) (I/O2)
PROFIBUS PA I/O1: Fieldbus PROFIBUS PA communicationI/O2: Pulse Pulse / Frequency outputWP: Write-protect bridge
2.1.1 PROFIBUS PA Output signalsDigital communication signal based on PROFIBUS PA protocol.
Maximum voltage and correct polarity must be observed for wiring.PROFIBUS PA Value
Power supply 9 to 32 VDC
Current draw 15mA (maximum)
ROTAMASSFieldbus+
Fieldbus-
4
3
1
5
22
Fig. 1: PROFIBUS PA connection
① PROFIBUS PA② Terminator③ DP/PA-Coupler④ PROFIBUS DP⑤ Host
Addendum to General Specifications for PROFIBUS PAPROFIBUS PA Specifications Inputs and outputs
6 / 10 GS 01U10B00-02EN-R, 1st edition, 2018-10-24
Passive pulseoutput (only forcalibration)
ValueMaximum load current ≤ 200 mAPower supply ≤ 30 VDC
Maximum pulse rate 10000 pulses/sFrequency range 0 – 12.5 kHz
ROTAMASS
Pulse+
Pulse-
321
Fig. 2: Passive pulse output connection with electronic counter
① Passive pulse② Load resistance③ Electronic counter
ROTAMASS
Pulse+
Pulse-
321
Fig. 3: Passive pulse output connection with electromechanical counter
① Passive pulse② Protective diode③ Electromechanical counter
Addendum to General Specifications for PROFIBUS PAAdvanced functions and Features on Demand (FOD)
GS 01U10B00-02EN-R, 1st edition, 2018-10-24 7 / 10
3 Advanced functions and Features on Demand (FOD)
ROTAMASS Total Insight includes many dedicated application and maintenance func-tions that can be ordered simultaneously with the device or can be purchased and acti-vated in a second time (only with the Ultimate transmitter).
Advancedfunctions
Transmitter Communication type and I/OFunctional scope Ultimate Available type
YOKOGAWA
Ultimate
YOKOGAWA
Ultimate
PROFIBUSPA
Model code (pos. 1 and 13) U G␣Standard concentrationmeasurement ● ●
Advanced concentrationmeasurement ● ●
Net Oil Computing (NOC)following API standard ● ●
Tube health check ● ●Batching function ● −Viscosity function ● ●Measurement of heat quantity ● ●
meaning of "−": not available; meaning of "●": available
To order these functions refer to the related general specifications for FOD functions(GS01U10B20-00␣␣-R).
Addendum to General Specifications for PROFIBUS PAOrdering information Model code
8 / 10 GS 01U10B00-02EN-R, 1st edition, 2018-10-24
4 Ordering information
4.1 Model code
4.1.1 Transmitter
- - - - /-RC
1 2 3 4 6 75 9 10 11 12 13 14 158
Model codeposition 1
Transmitter
U1) Ultimate1) PROFIBUS PA communication protocol is supported by Ultimate transmitter only and isnot available with Essential transmitter.
4.1.2 Communication type and I/O
- - - - /-RC
1 2 3 4 6 75 9 10 11 12 13 14 158
PROFIBUS PA Model codeposition 13
Connection terminal assignmentI/O1 +/- I/O2 +/- I/O3 +/- I/O4 +/- WP
G0 PROFIBUSPA
PulsePassive
– – Write-protect
G1 PROFIBUSPA (IS)
PulsePassive (IS)
– – Write-protect
PROFIBUS PA PA communicationPulse Passive Pulse / Frequency output
Intrinsically safe (IS) outputs are only available in combination with selecting Ex approvalof the device, see chapter Ex approval.
4.2 Overview model codes PROFIBUS PA restrictions
- - - - /-RC
1 2 3 4 6 75 9 10 11 12 13 14 158
Model code
position
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. Description Restriction
Transmitter E Essential (basic function) not with communication type and I/O G␣
Ex approval
FF11 FM, groups A, B, C, D, E, F, Gnot with communication type and I/O G␣
FF12 FM, groups C, D, E, F, G
NF21 NEPSI, explosion group IIC and IIICnot with communication type and I/O G␣
NF22 NEPSI, explosion group IIB and IIIC
Overview options PROFIBUS PArestrictions
Addendum to General Specifications for PROFIBUS PAOrdering information
GS 01U10B00-02EN-R, 1st edition, 2018-10-24 9 / 10
4.3 Overview options PROFIBUS PA restrictions
Option category
Options Description Restriction
Presetting of customer para-meters
PS Presetting according to customer parameters not with communication typeand I/O G␣
Country-specific application Q11 PESO approval delivery not with communication type
and I/O G1
Marine ApprovalMC2 Marine approval according to DNV GL piping class 2 not with communication type
and I/O G␣MC3 Marine approval according to DNV GL piping class 3
Batching function BT Batching and filling function not with communication typeand I/O G␣
4.4 Ordering Instructions
In addition to the ordering information described in GS 01U10B0˽ -00˽ ˽-R, forPROFIBUS PA communication type please specify the following information when ordering a product:
Ordering information Parameter ValueNODE ADDRESS (HEX): up to 4 characters length Default value '0x7E' unless otherwise specified
SOFTWARE TAG: up to 32 characters length Default value 'FT2001' unless otherwise specified
YOKOGAWA ELECTRIC CORPORATION
YOKOGAWA CORPORATION OF AMERICA
YOKOGAWA AMERICA DO SUL LTDA.
YOKOGAWA EUROPE B. V.
Euroweg 2, 3825 HD Amersfoort,
THE NETHERLANDS
Phone : 31-88-4641000
Fax : 31-88-4641111
YOKOGAWA INDIA LTD.
Plot No.96, Electronic City Complex,
Hosur Road, Bangalore - 560 100,
INDIA
Phone : 91-80-4158-6000
Fax : 91-80-2852-1442
YOKOGAWA AUSTRALIA PTY. LTD.
Tower A, 112-118 Talavera Road,
Macquarie Park NSW 2113,
AUSTRALIA
Phone : 61-2-8870-1100
Fax : 61-2-8870-1111
YOKOGAWA MIDDLE EAST & AFRICA B.S.C.(C)
P.O. Box 10070, Manama, Building 577,
Road 2516, Busaiteen 225, Muharraq,
Kingdom of BAHRAIN
Phone : 973-17358100
Fax : 973-17336100
Headquarters
2-9-32, Nakacho, Musashino-shi,
Tokyo, 180-8750 JAPAN
Phone : 81-422-52-5555
Branch Sales Offices
Osaka, Nagoya, Hiroshima,
Kurashiki, Fukuoka, Kitakyusyu
Head Office
12530 West Airport Blvd, Sugar Land,
Texas 77478, USA
Phone : 1-281-340-3800
Fax : 1-281-340-3838
Georgia Office
2 Dart Road, Newnan, Georgia 30265, USA
Phone : 1-800-888-6400/ 1-770-253-7000
Fax : 1-770-254-0928
Praca Acapulco, 31 - Santo Amaro, Sáo Paulo/SP,
BRAZIL, CEP-04675-190
Phone : 55-11-5681-2400
Fax : 55-11-5681-4434
YOKOGAWA ELECTRIC CIS LTD.
Grokholskiy per 13 Building 2, 4th Floor 129090,
Moscow, RUSSIA
Phone : 7-495-737-7868
Fax : 7-495-737-7869
YOKOGAWA CHINA CO., LTD.
3F Tower D Cartelo Crocodile Building,
No.568 West Tianshan Road,
Shanghai 200335, CHINA
Phone : 86-21-62396262
Fax : 86-21-62387866Z
YOKOGAWA ELECTRIC KOREA CO., LTD.
(Yokogawa B/D, Yangpyeong-dong 4-Ga),21, Seonyu-ro 45-gil, Yeongdeungpo-gu,Seoul, 150-866, KOREA
Phone : 82-2-2628-6000
Fax : 82-2-2628-6400
YOKOGAWA ENGINEERING ASIA PTE. LTD.
5 Bedok South Road, Singapore 469270,
SINGAPORE
Phone : 65-6241-9933
Fax : 65-6241-2606 ISO 9001
GS 01U10B00-02EN-R, 1st edition, 2018-10-24
All rights reserved. Copyright © 2018-10-24