Guidelines for Earthing

Embed Size (px)

Citation preview

  • 8/3/2019 Guidelines for Earthing

    1/2

    Guidelines for Earthing

    1. Minimum fault level at 11 kV side shall be assumed 150 MVA for all earthing designs.

    2. Number of earth electrodes required shall be calculated for fault current at 11 kVside.

    3. Duration of fault current shall be taken as 3 sec for earthing design at HTinstallations.

    4. Maximum earth resistance at HT premises shall be limited to 1 ohm.

    5 Earth mat shall be provided at EHT premises for limiting step voltage and touchvoltage to tolerable values. Conductor size and mesh size may be designed for faultduration of 1.0 second and 0.5 second respectively.

    6. All earth electrodes shall be interconnected using the conductors of largest size in the

    earthing system.

    7. All non-current carrying metal parts of equipments shall be double earthed usingconductors of adequate size.

    8. Transformer and generator neutral shall be double earthed. One independent earthelectrode shall be provided for neutral earthing. Links shall also be provided in neutralearthing conductor. Generator neutral shall be earthed at control panel.

    9. Lightning arrestor shall be connected to a separate earth electrode using No. 6 SWGCu. The L.A. earth electrode may be interconnected with other earth electrodes.

    10. If fault current exceeds 6 kA plate earth electrodes shall be used.

    11. If soil resistivity is < 60 ohm-m, only copper shall be used as earthing conductor.

    12. Distance between plate earth electrodes shall be 8 m minimum.

    13. Distance between pipe earth electrodes shall be 5 m minimum.

    14. Minimum distance between earth electrode and adjacent civil structure shall be 1.5m.

    15. In location of SBs, DBs etc. sub earth buses of 25 x 3 mm2 copper may be provided.

    16. All joints in earthing conductors shall be properly tinned.

    17. Following guidelines shall be adhered to when GI earthing is adopted.

    (a) GI strips used for earthing shall be minimum 6 mm thick and hot dip galvanised.(b) If round GI conductors are used it shall have double the calculated area of cross-section.(c) The minimum cross-sectional area of the GI should be 50 sq.mm.

  • 8/3/2019 Guidelines for Earthing

    2/2

    (d) Where a Copper conductor is to be joined to GI, the joints should be tinned toprevent electrolytic action.(e) If atmosphere is corrosive, GI conductors shall not be used for earthing.(f) Joints shall be invariably done by means of welding except in such locations whereintermittent disconnection of joints is necessitated for testing purpose, or for the earthingconnection to the body of equipments etc.

    (g) Barium Chromate or Zinc dichromate treatment should be done at the welds. Jointsshould be provided with coating alternative layers of red oxide and aluminium. Jointsare to be covered with hot bitumen. Also jute band covering of adequate thickness is tobe made on the portion of earthing susceptible to higher corrosion and environmentalinfluence.(h) The area of strip electrode thus covered with bitumen and jute should not bereckoned for the calculation of area of dissipation for the fault current.(i) In places where the resistivity is very high and atmospheric corrosion is notsignificant even ordinary steel conductors shall be permitted.(j) Earthing system with GI conductors should be subjected to a thorough physicalexamination after a period of 10 years and modifications made if found necessary on

    such examination.(k) Joints using GI conductors should be welded as far as possible and kept separatedfrom air by a thick coating of tar or similar non-hygroscopic materials. In case bolted

    joints can not be avoided, there should be a minimum of 2 bolts for sizes up to 25 mm x6 mm, 3 bolts for sizes up to 31 mm x 6 mm and zig-zag bolting for large sizes.

    18. Following guidelines shall be adhered to when covered aluminium is used forearthing:-

    (a) Aluminium should not be used for final underground connections to earth electrode.(b) Aluminium shall be used below ground only if efficiently protected or sheathedagainst contact with soil and moisture. PVC covering shall be allowed.(c) Where a copper conductor is to be joined to Aluminium conductor, the joints shouldbe tinned to prevent electrolytic action.(d) Sharp bends required in Aluminium strip should be formed by the use of a bendingmachine.(e) Aluminium to Aluminium joints on strip conductor shall be arc welded using eitherthe Tungsten inert gas arc or Metal inert gas arc techniques. Oxy-acetylene gas weldingor bracing shall also be allowed.(f) Round and rectangular conductors can be joined with bolted clamps. Rectangularconductors can be joined or terminated by drilling and bolting.(g) When making a bolted type joint the surface of the Aluminium strip should becleaned thoroughly by wire brushing and greased or an approved jointing compoundapplied immediately to both mating surfaces. Bolts should then be tightened and allexcess grease or compound wiped off and discarded.(h)Aluminium conductor connections to equipment, whereas possible, should be in thevertical plane. Surface preparation of Aluminium and making of the joint should be aspreviously described. The finished joint should be protected by bitumastic paint.

    19. Earthing shall conform to IS 3043-1987.

    20. Earthing grid should be run at a minimum depth of 50 cm below the ground