Page 1 of 30
GUJARAT STATE ELECTRICITY CORPORATIOPN LTD.
Engineering, procurement and construction (EPC) contract for disposing of fly ash and bottom ash for 200MW unit no. 3 &4 and 210MW unit no. 5 from the pumping station to the Dykes including Erection, Testing and Commissioning of pipes and Pumping Station with all Civil, Mechanical ,Electrical & instrumental Works with 1 year operation & maintenance for combine ash slurry pump house at Ukai TPS, Nr. Songadh, Dist. Tapi.
SECTION – IV
(SECTION-E)
DATA SHEET FOR ELECTRICAL WORK
Page 2 of 30
1.0 1000 KVA Distribution Transformer
Sr.
No. Description Unit Particulars
Filled by Bidder
1
General
1.1 Application Distribution
1.2 Specification Reference IS:1180(Part1) (2014)
Energy Efficient
1.3 Installation Out door
1.4 Type of winding Double wound
1.5 Rating KVA 1000
1.6
Cooling ONAN
1.8 No load voltage KV/KV 6.6/0.433
1.9 HV winding Delta
1.10 LV winding Delta
1.11 Impulse Voltage withstand (HV)
KVp
RMS
Provide by manufacture
1.13 Frequency Hz 50
1.14 % impedance (Subject to IS: Tol)
% 4.5
1.15 Maximum total Losses Energy Efficiency Level 1 (3 Star)
1.16 At 50% load KW Provide by manufacture
1.17 At 100% Load KW Provide by manufacture
Efficiently at 100% Load UPF
% 99.10%
Page 3 of 30
1.20.1 Winding
1.20.2 Material of winding Copper
1.21 Winding connection
1.22 1) HV side Delta
1.22.1 2) LV side Delta
1.22.2 Vector Group Dyn11
1.22.3 Temperature at full load – winding
Deg C 40 above ambient
1.23 Temperature at full load- oil.
Deg C 45 above ambient
1.24 Termination detail
1.24.1 HV Outdoor cable Box on HV
1.24.2 LV Suitable cable box LV side porcelain insulator
1.24.3 LV winding end Neutral Will be brought out separately
1.25 Earthing Solid
1.26.1 Tapping’s
1.26.2
Tapping Range +5% to -10%
1.26.3 Steps 2.5%
1.26.4 Tap Changer Off circuit taps on HV
1.27 Dimensions/Weight of Transformer
1.27.1 Dimensions L X W X H
1.27.2 Weights (Approx.)
Page 4 of 30
1.28 Core & Winding
Tank & Fittings
Oil
Total Weight
Oil Quantity (Litres)
1.29 Fittings & Accessories:
1.30 Press Steel radiators.
1.31 Rating diagram plate
1.32 Terminal markings.
1.33 Tank lifting lug
1.34 Top cover lifting lug
1.35 Drain valve with plug.
1.36 Silica Gel breather.
1.37 Plain oil level gauge.
1.38 Oil filling hole with cover
1.39 Conservator with oil filling hole.
1.40 Air release plug.
1.41 Explosion vent with diaphragm
1.42 Bottom Filter valve with plug.
1.43 Off circuit tap changing with switch position.
1.44 Neutral terminal for separate earthing
1.45 Suitable cable box on H.V. Side
Page 5 of 30
1.46 Suitable cable box on L.V. side
1.47 Top Filter Valve.
1.48 Jacking Pads.
1.49 6" Dial type OTI with alarm trip contact
1.50 6" Dial type WTI with alarm trip contact.
1.51 Double Float Buchcholz relay with alarm & trip contacts
1.52 Marshalling box.
Page 6 of 30
2.0 HT Station Bus C3A #5
Existing NGEF make Panel
Sr. No.
Description Unit As Per Requirement
To be Filled by
Contractor
1 Quantity Set Qty 1 One Main
With suitable size dummy panel make: ABB Model: VD4 12.12.40
2 Reference Drawings
3 Switchgear cubicles and bus bar Ratings
(a) Rated Voltage, phases and frequency 12 KV, 3 Ph, 50 Hz
(b) System Neutral Earthing Effectively earthed / Non-effectively earthed
Solidly Earthed.
(C) Max. System Voltage KV 13.2
(d) One Minute power frequency withstand voltage
KV (rms) 20
(e) 12/50 µsec. Impulse withstand voltage KV (peak)
60
(f) Short circuit withstand (i) Short time (3 sec) at rated voltage
KA (rms) 40
(ii) Dynamic rating KA (Peak)
47
(g) Reference ambient temperature 45⁰ C
(h) Maximum temperature of bus bar droppers, connectors and contacts at continuous current rating under site reference ambient temperature
Within Limits as specified by IEC
(i) Continuous current rating of bus bar A 1250
(j) Bus bar material Aluminum
(k) Bus bar insulation Fully insulated by encapsulation in epoxy resin with Mould caps protecting all joints or shrinkable PVC sleeves and tapes.
(l) Cable Entry As per Site Condition
Page 7 of 30
(m) Cable type 11KV XLPE unearth Aluminum conductor. (i) Incoming Feeder.
3C ×180 mm2
(ii) Outgoing Feeder. 3C ×180 mm2
4 Switchgear Construction requirements
(a) Thickness of sheet steel Frame, frame enclosures, doors, covers and partitions.
Mm Cold Rolled- 2.0
(b) Degree of Protection IP 4X.
(c) Colour finish shade RAL 7032
RAL7032
(d) Earthing Bus Material & size mm×mm Aluminum 40X10
(e) Earthing Conductor material & size mm×mm GI
(f) Clearance in Air of Live parts (i) Phase to phase (ii) Phase to earth.
Mm 110 & 77.
5 Breaker Particular
(a) Circuit Breaker type Vacuum, Horizontally draw out type.
Applicable Standard IEC-62271/100
(b) Voltage, Phases and frequency 12KV, 3 Ph, 50Hz.
(c) Rated Operating duty 0-0.3 Sec-CO-3 min-CO
(d) Rated current at reference ambient temperature Incoming breaker
A 1250
Outgoing breaker A 1250
(e) Rated breaking capacity KA (rms) 40
(f) Rated making current KA (Peak)
46.84
(g) Short time current withstand for 1 sec. duration.
KA (rms) 40
(h) Total break time Less than 3 cycles
(i) Operating Mechanism type Spring charged store energy
(j) Minimum no. of Auxiliaries contacts 6 NO,6 NC
(k) Withstand test voltage
(I) One Minute power frequency KV (rms) 20
(II) 1.2/50 µ sec. impulse KV (peak)
60
(l) Auxiliaries control voltage
(I) For closing / tripping coil 220 V DC
(II) For Spring charging motor 220V DC
(III) For Space heaters & lighting 220V AC
Page 8 of 30
(m) Anti-pumping features NA
(n) Latching requirement Trip free
(o) Trip coil circuit of all breakers shall be provided with trip circuit supervision relays, to supervise the circuit in both open and closed condition of circuit breaker
Provided
6 Current transformer
(a) Type Cast Resin
(b) Class of Insulation Class B or better
(C) Rated Current ratio and burden
(I) Incomer Feeders-Protection & Metering CL: 1/5P10, Ith 26.3KA / 1SEC
100/1A,10VA & 100/1A,10VA
(II) Output Feeders- Protection & Metering
75/5A, 10VA &
75/5A, 10VA
(d) Accuracy class
(I) Metering 1
(II) Protection 5P10
(e) Short time 1sec. Current rating KA (rms) 40 KA/3 Sec
(f) Dynamic rating KA(Peak) 46
7 Voltage Transformers
(a) Type Cast Resin
(b) Rated Voltage
(I) Primary V 6600/⎷3
(II) Secondary-SI V 110/⎷3
(C) Method of connection
(I) Primary-P Star, Earthed
(II) Secondary- SI Star, Earthed
(d) Application-SI Provide
(e) Rated Burden VA 100
(f) Accuracy class
(I) Metering 1
(II) Protection Standard
(g) Rated Voltage Factor
(I) Continuous 1.1
(II) Short Time 1.5
(h) Insulation Class Class B or better
8 Relays
(a) Inverse time over current relay
Required
(b) Instantaneous over current relay
(C) Motor Protection relay
(d) Instantaneous earth fault relay
Page 9 of 30
(e) Inverse time earth fault relay
(f) Under voltage relay, lock out relay fuse failure relay auxiliary relay, Motor Protection relay
Required
i Indicating Meter Required
a Applicable standard Standard
b Type of movement DIGITAL
ii Load Manager Required
a Make As per Stranded
b Details NA
9 Annunciation
(a) Incoming feeders
(I) Main Incoming Circuit Breaker Trip Required
(II) Transformer #1 Circuit Breaker Trip Required
(III) Transformer #2 Circuit Breaker Trip Required
(IV) Transformer #1 Buchholz Relay alarm Required
(V) Transformer #1 Buchholz Relay Trip Required
(VI) Transformer #2 Buchholz Relay alarm Required
(VII) Transformer #2 Buchholz Relay trip Required
(VIII) Transformer #1 high oil temperature alarm Required
(IX) Transformer #1 high oil temperature trip Required
(X) Transformer #2 high oil Temperature alarm Required
(XI) Transformer #2 high oil Temperature Trip Required
(c) Spare window Required
10 Cubicle Component
Each 12 KV circuit breaker cubicle shall be provided with the following minimum standard accessories with appropriate size of dummy panel to fix
with existing NGEF Panel.
(a) One control switch ‘trip-neutral-close’ spring return to neutral position.
Required
(b) One control selector switch ‘Load-remote stay-put’ type
Required
(c) Indicating lamps with series resistors. Required
(I)‘Red’ for breaker in ‘ON’ indication (this shall also supervise trip coil)
Required
(II)Green’ for breaker ‘OFF’ position. Required
(III)‘Blue’ for breaker in ‘Spring Charge’ Required
(IV)‘Amber’ for breaker in ‘Auto Trip’ position. Required
(V)‘White’ for breaker closing spring ‘TCH’. Required
Indicating lamps (III), (IV) and (v) shall be provided when positive mechanical indicators for these conditions are not available/visible.
Required
Page 10 of 30
(d) One electrical anti-pumping relay. Required
(e) One Double pole control supply switch and set of fuses.
Required
(f) Cubicle space heater of adequate capacity. Required
(g) 240V, 1 phase, 50 Hz, 5A,3 pin receptacle with switch.
Required
(h) Cubicle lamp. Required
(i) One control selector switch ‘Local-remote stay-put’ type.
Required
3.11 Auxiliary A.C. Supply
240V, 1 Ph, 50 Hz supply shall be made available to each cubicle of 11 KV switchgear separately for provision of following.
(a) Spring charging motor Required
(b) Cubicle space heater Required
(c) Cubicle Lamp Required
Page 11 of 30
3.0 HT Unit Bus 4B #4
Existing NGEF make Panel
Sr. No.
Description Unit As Per Requirement
To be Filled by
Contractor
1 Quantity Set Qty 1 One Main
With suitable size dummy panel make: ABBModel: VD4 12.12.40
2 Reference Drawings
3 Switchgear cubicles and bus bar Ratings
(a) Rated Voltage, phases and frequency
12 KV, 3 Ph, 50 Hz
(b) System Neutral Earthing Effectively earthed / Non-effectively earthed
Solidly Earthed.
(C) Max. System Voltage KV 13.2
(d) One Minute power frequency withstand voltage
KV (rms) 20
(e) 12/50 µsec. Impulse withstand voltage
KV (peak)
60
(f) Short circuit withstand (i) Short time (3 sec) at rated voltage
KA (rms) 40
(ii) Dynamic rating KA (Peak)
47
(g) Reference ambient temperature
45⁰ C
(h) Maximum temperature of bus bar droppers, connectors and contacts at continuous current rating under site reference ambient temperature
Within Limits as specified by IEC
(i) Continuous current rating of bus bar
A 1250
(j) Bus bar material Aluminum
Page 12 of 30
(k) Bus bar insulation
Fully insulated by encapsulation in epoxy resin with Mould caps protecting all joints or shrinkable PVC sleeves and tapes.
(l) Cable Entry As per Site Condition
(m) Cable type 11KV XLPE unearth Aluminum conductor. (i) Incoming Feeder.
3C ×180 mm2
(ii) Outgoing Feeder. 3C ×180 mm2
4 Switchgear Construction requirements
(a) Thickness of sheet steel Frame, frame enclosures, doors, covers and partitions.
mm Cold Rolled- 2.0
(b) Degree of Protection IP 4X.
(c) Colour finish shade RAL 7032
RAL7032
(d) Earthing Bus Material & size mm×mm Aluminum 40X10
(e) Earthing Conductor material & size
mm×mm GI
(f) Clearance in Air of Live parts (i) Phase to phase (ii) Phase to earth.
mm 110 & 77.
5 Breaker Particular
(a) Circuit Breaker type Vacuum, Horizontally draw out type.
Applicable Standard IEC-62271/100
(b) Voltage, Phases and frequency
12KV, 3 Ph, 50Hz.
(c) Rated Operating duty 0-0.3 Sec-CO-3 min-CO
(d) Rated current at reference ambient temperature Incoming breaker
A 1250
Outgoing breaker A 1250
(e) Rated breaking capacity KA (rms) 40
Page 13 of 30
(f) Rated making current KA (Peak)
46.84
(g) Short time current withstand for 1 sec. duration.
KA (rms) 40
(h) Total break time Less than 3 cycles
(i) Operating Mechanism type Spring charged store energy
(j) Minimum no. of Auxiliaries contacts
6 NO,6 NC
(k) Withstand test voltage
(I) One Minute power frequency
KV (rms) 20
(II) 1.2/50 µ sec. impulse KV (peak)
60
(l) Auxiliaries control voltage
(I) For closing / tripping coil 220 V DC
(II) For Spring charging motor 220V DC
(III) For Space heaters & lighting
220V AC
(m) Anti-pumping features NA
(n) Latching requirement Trip free
(o) Trip coil circuit of all breakers shall be provided with trip circuit supervision relays, to supervise the circuit in both open and closed condition of circuit breaker
Provided
6 Current transformer
(a) Type Cast Resin
(b) Class of Insulation Class B or better
(C) Rated Current ratio and burden
(I) Incomer Feeders-Protection & Metering CL: 1/5P10, Ith 26.3KA / 1SEC
100/1A,10VA & 100/1A,10VA
(II) Output Feeders- Protection & Metering
75/5A, 10VA &
75/5A, 10VA
(d) Accuracy class
(I) Metering 1
(II) Protection 5P10
(e) Short time 1sec. Current rating
KA (rms) 40 KA/3 Sec
(f) Dynamic rating KA(Peak) 46
Page 14 of 30
7 Voltage Transformers
(a) Type Cast Resin
(b) Rated Voltage
(I) Primary V 6600/⎷3
(II) Secondary-SI V 110/⎷3
(C) Method of connection
(I) Primary-P Star, Earthed
(II) Secondary- SI Star, Earthed
(d) Application-SI Provide
(e) Rated Burden VA 100
(f) Accuracy class
(I) Metering 1
(II) Protection Standard
(g) Rated Voltage Factor
(I) Continuous 1.1
(II) Short Time 1.5
(h) Insulation Class Class B or better
8 Relays
(a) Inverse time over current relay
Required
(b) Instantaneous over current relay
(C) Motor Protection relay
(d) Instantaneous earth fault relay
(e) Inverse time earth fault relay
(f) Under voltage relay, lock out relay fuse failure relay auxiliary relay, Motor protection Relay
Required
i Indicating Meter Required
a Applicable standard Standard
b Type of movement DIGITAL
ii Load Manager Required
a Make As per Stranded
b Details NA
9 Annunciation
(a) Incoming feeders
(I) Main Incoming Circuit Breaker Trip Required
(II) Transformer #1 Circuit Breaker Trip Required
(III) Transformer #2 Circuit Breaker Trip Required
(IV) Transformer #1 Buchholz Relay alarm
Required
Page 15 of 30
(V) Transformer #1 Buchholz Relay Trip Required
(VI) Transformer #2 Buchholz Relay alarm
Required
(VII) Transformer #2 Buchholz Relay trip Required
(VIII) Transformer #1 high oil temperature alarm
Required
(IX) Transformer #1 high oil temperature trip
Required
(X) Transformer #2 high oil Temperature alarm
Required
(XI) Transformer #2 high oil Temperature Trip
Required
(c) Spare window Required
10 Cubicle Component
Each 12 KV circuit breaker cubicle shall be provided with the following minimum standard accessories with appropriate size of dummy panel to fix with existing NGEF Panel.
(a) One control switch ‘trip-neutral-close’ spring return to neutral position.
Required
(b) One control selector switch ‘Load-remote stay-put’ type
Required
(c) Indicating lamps with series resistors. Required
(I)‘Red’ for breaker in ‘ON’ indication (this shall also supervise trip coil)
Required
(II)Green’ for breaker ‘OFF’ position. Required
(III)‘Blue’ for breaker in ‘Spring Charge’ Required
(IV)‘Amber’ for breaker in ‘Auto Trip’ position.
Required
(V)‘White’ for breaker closing spring ‘TCH’.
Required
Indicating lamps (III), (IV) and (v) shall be provided when positive mechanical indicators for these conditions are not available/visible.
Required
(d) One electrical anti-pumping relay. Required
(e) One Double pole control supply switch and set of fuses.
Required
(f) Cubicle space heater of adequate capacity.
Required
(g) 240V, 1 phase, 50 Hz, 5A,3 pin receptacle with switch.
Required
(h) Cubicle lamp. Required
Page 16 of 30
(i) One control selector switch ‘Local-remote stay-put’ type.
Required
3.11 Auxiliary A.C. Supply
240V, 1 Ph, 50 Hz supply shall be made available to each cubicle of 11 KV switchgear separately for provision of following.
(a) Spring charging motor Required
(b) Cubicle space heater Required
(c) Cubicle Lamp Required
Page 17 of 30
4.0 HT PUMPING STATION SUB STATION PANEL
Sr.
No.
Description Unit As Per Requirement
To be Filled by
Contractor
1 Quantity Set 2+2=4 Set Main
With suitable size Side cable entry panel make: ABB Model: VD4 12.12.40
2 Reference Drawings
3 Switchgear cubicles and bus bar Ratings
(a) Rated Voltage, phases and frequency 12 KV, 3 Ph, 50 Hz
(b) System Neutral Earthing Effectively earthed / Non-effectively earthed
Solidly Earthed.
(C) Max. System Voltage KV 13.2
(d) One Minute power frequency withstand voltage
KV (rms) 20
(e) 12/50 µsec. Impulse withstand voltage KV (peak)
60
(f) Short circuit withstand (i) Short time (3 sec) at rated voltage
KA (rms) 40
(ii) Dynamic rating KA (Peak)
47
(g) Reference ambient temperature 45⁰ C
(h) Maximum temperature of bus bar droppers, connectors and contacts at continuous current rating under site reference ambient temperature
Within Limits as specified by IEC
(i) Continuous current rating of bus bar A 1250
(j) Bus bar material Aluminum
(k) Bus bar insulation Fully insulated by encapsulation in epoxy resin with mould caps protecting all joints or shrinkable PVC sleeves and tapes.
Page 18 of 30
(l) Cable Entry Both right and Left Side Cable Entry
(m) Cable type 11KV XLPE unearth Aluminum conductor. (i) Incoming Feeder.
3C ×180 mm2
(ii) Outgoing Feeder. 3C ×180 mm2
4 Switchgear Construction requirements
(a) Thickness of sheet steel Frame, frame enclosures, doors, covers and partitions.
mm Cold Rolled- 2.0
(b) Degree of Protection IP 4X.
(c) Colour finish shade RAL 7032
RAL7032
(d) Earthing Bus Material & size mm×mm Aluminum 40X10
(e) Earthing Conductor material & size mm×mm GI
(f) Clearance in Air of Live parts (i) Phase to phase (ii) Phase to earth.
mm 110 & 77.
5 Breaker Particular
(a) Circuit Breaker type Vacuum, Horizontally draw out type.
Applicable Standard IEC-62271/100
(b) Voltage, Phases and frequency 12 KV, 3 Ph, 50Hz.
(c) Rated Operating duty 0-0.3 Sec-CO-3 min-CO
(d) Rated current at reference ambient temperature Incoming breaker
A 1250
Outgoing breaker A 1250
(e) Rated breaking capacity KA (rms) 40
(f) Rated making current KA (Peak)
46.84
(g) Short time current withstand for 1 sec. duration.
KA (rms) 40
(h) Total break time Less than 3 cycles
(i) Operating Mechanism type Spring charged store energy
(j) Minimum no. of Auxiliaries contacts 6 NO,6 NC
(k) Withstand test voltage
(I) One Minute power frequency KV (rms) 20
(II) 1.2/50 µ sec. impulse KV (peak)
60
Page 19 of 30
(l) Auxiliaries control voltage
(I) For closing / tripping coil 220 V DC
(II) For Spring charging motor 220V DC
(III) For Space heaters & lighting 220V AC
(m) Anti-pumping features NA
(n) Latching requirement Trip free
(o) Trip coil circuit of all breakers shall be provided with trip circuit supervision relays, to supervise the circuit in both open and closed condition of circuit breaker
Provided
6 Current transformer
(a) Type Cast Resin
(b) Class of Insulation Class B or better
(C) Rated Current ratio and burden
(I) Incomer Feeders-Protection & Metering CL: 1/5P10, Ith 26.3KA / 1SEC
100/1A,10VA & 100/1A,10VA
(II) Output Feeders- Protection & Metering
75/5A, 10VA &
75/5A, 10VA
(d) Accuracy class
(I) Metering 1
(II) Protection 5P10
(e) Short time 1sec. Current rating KA (rms) 40 KA/3 Sec
(f) Dynamic rating KA(Peak) 46
7 Voltage Transformers
(a) Type Cast Resin
(b) Rated Voltage
(I) Primary V 6600/⎷3
(II) Secondary-SI V 110/⎷3
(C) Method of connection
(I) Primary-P Star, Earthed
(II) Secondary- SI Star, Earthed
(d) Application-SI Provide
(e) Rated Burden VA 100
(f) Accuracy class
(I) Metering 1
(II) Protection Standard
(g) Rated Voltage Factor
(I) Continuous 1.1
(II) Short Time 1.5
(h) Insulation Class Class B or better
8 Relays
Page 20 of 30
(a) Inverse time over current relay
Required
(b) Instantaneous over current relay
(C) Motor Protection relay
(d) Instantaneous earth fault relay
(e) Inverse time earth fault relay
(f) Under voltage relay, lock out relay fuse failure relay auxiliary relay. Motor Protection relay
Required
i Indicating Meter Required
a Applicable standard Standard
b Type of movement DIGITAL
ii Load Manager Required
a Make As per Stranded
b Details NA
9 Annunciation
(a) Incoming feeders
(I) Main Incoming Circuit Breaker Trip Required
(II) Transformer #1 Circuit Breaker Trip Required
(III) Transformer #2 Circuit Breaker Trip Required
(IV) Transformer #1 Buchholz Relay alarm Required
(V) Transformer #1 Buchholz Relay Trip Required
(VI) Transformer #2 Buchholz Relay alarm Required
(VII) Transformer #2 Buchholz Relay trip Required
(VIII) Transformer #1 high oil temperature alarm Required
(IX) Transformer #1 high oil temperature trip Required
(X) Transformer #2 high oil Temperature alarm Required
(XI) Transformer #2 high oil Temperature Trip Required
(c) Spare window Required
10 Cubicle Component
Each 12 KV circuit breaker cubicle shall be provided with the following minimum standard accessories. with electrical and Mechanical interlocking provision
(a) One control switch ‘trip-neutral-close’ spring return to neutral position.
Required
(b) One control selector switch ‘Load-remote stay-put’ type
Required
(c) Indicating lamps with series resistors. Required
(I)‘Red’ for breaker in ‘ON’ indication (this shall also supervise trip coil)
Required
(II)Green’ for breaker ‘OFF’ position. Required
(III)‘Blue’ for breaker in ‘Spring Charge’ Required
(IV)‘Amber’ for breaker in ‘Auto Trip’ position. Required
Page 21 of 30
(V)‘White’ for breaker closing spring ‘TCH’. Required
Indicating lamps (III), (IV) and (v) shall be provided when positive mechanical indicators for these conditions are not available/visible.
Required
(d) One electrical anti-pumping relay. Required
(e) One Double pole control supply switch and set of fuses.
Required
(f) Cubicle space heater of adequate capacity. Required
(g) 240V, 1 phase, 50 Hz, 5A,3 pin receptacle with switch.
Required
(h) Cubicle lamp. Required
(i) One control selector switch ‘Local-remote stay-put’ type.
Required
3.11 Auxiliary A.C. Supply
240V, 1 Ph, 50 Hz supply shall be made available to each cubicle of 11 KV switchgear separately for provision of following.
(a) Spring charging motor Required
(b) Cubicle space heater Required
(c) Cubicle Lamp Required
Page 22 of 30
4.0 100 KVA Auxiliary Transformer
Sr. No.
Description Unit Particulars To be Filled by
Bidder
1
General Dry Type Resin
Cast Transformer
1.1 Application Auxiliary
1.2 Specification Reference IS:11171
IS 2026
1.3 Insulation Class ‘F’ Class
1.4 Type Dry Type Resin Cast Transformer
1.5 Rating KVA 100
1.6
Cooling Air Natural (AN)
1.8 No load voltage KV/KV 0.433/0.433 kV
1.9 HV winding Delta
1.10 LV winding Star
1.11 Impulse Voltage withstand (HV)
kVp RMS
Provide by manufacture
1.13 Frequency Hz 50
1.14 % impedance (Subject to IS: Tol)
% 4.0
1.15 Maximum total Losses Standard
1.16 At 50% load KW Provide by manufacture
1.17 At 100% Load KW Provide by manufacture
Efficiently at 100% Load UPF % 98.60%
1.20.1 Winding
1.20.2 Material of winding . Copper
Page 23 of 30
1.21 Winding connection
1.22 1) HV side Delta
1.22.1 2) LV side Star
1.22.2 Vector Group Dyn11
1.22.3 Max Temperature rise Deg C 90’ C, over 50’ above ambient
1.23 Ambient Temperature. Deg C 50 above ambient
1.24 Termination detail
1.24.1 HV Not Applicable
1.24.2 LV Cable end box primary and secondary
1.24.3 LV winding end Neutral Provided
1.25 Earthing Solid
1.261 Tapping’s
1.262
Tapping Range + 5%
1.263 Steps 2.5
1.26.4 Tap Changer -5%,-2.5%, +2.5%,+5%
1.27 Dimensions/Weight of Transformer
Dimensions L X W X H
Weights (Approx.)
Core & Winding
Tank & Fittings
Total Weight
1.28 Rating diagram plate
1.29 Terminal markings.
Page 24 of 30
1.30 Tank lifting lug.
1.31 Primary Bushing 1.1 kV class
1.32 Secondary Bushing 1.1 kV class
1.33 Off circuit tap changing links
1.34 Neutral terminal for separate earthing
1.35 Suitable cable box on L.V. Side (LT)
1.36 Suitable cable box on L.V. side. (LT)
1.37 Jacking Pads.
Page 25 of 30
5.0 HT CABLE
Sr
No Particulars Unit
Filled by Bidder
1 Type of Cable A2XFY
2 Voltage Grade kV 6.6 Kv
3 No of cores X size in sq.mm
2 run 3 X 240 for C2B Power Supply Source 2 run 3 X 240 for 4B Power Supply Source
4
a) Maximum conductor
temperature under normal
operating conditions
90°C
b) Maximum conductor
temperature at the termination
of short circuit
250°C
5 a) Permissible Voltage Variation ± 10%
b) Permissible Frequency
Variation ± 5%
c)Combined Voltage &
Frequency variation ± 10%
6 Conductor
a) Material
H4 Grade Aluminum as
per Class 2 of
IS:8130/84, latest
b) Maximumd.c. resistance of
conductor at 20° C (ohm/km) 0.443
c)Shape Stranded Compact
Circular
7 Conductor Screening
a) Material Extruded Semi-
Conducting Compound
b) Nominal thickness (mm) 0.3
8 Insulation
a) Material XLPE as per IS
7098(Pt-2)/85, latest
b) Nominal thickness (mm) 3.6
Page 26 of 30
9 Insulation Screening
(i)Non - Metallic
a) Material Extruded
Semi-conducting compound
b) Nominal thickness (mm) 0.3
(ii)Metallic
a) Material Copper Tape
b) Approximate thickness (mm) 0.045
10 Inner Sheath
a) Material Extruded PVC Type
ST2 to IS:5831/84
b) Minimum thickness (mm) 0.5
11 Armoring
a) Material Gal.Steel
b) Type of armoring Flat Strip
c)Nominal size of armor (mm) 4.0 x 0.8
12 Outer Sheath
(i) Material
(ii) Thickness (mm)
PVC Type 'ST2' as per
IS:5831/84
1.88 (Min.)
13 Electrical Parameters
a) Max. a.c. resistance of conductor at 90° C(ohm/km) 0.568
b) Approx. Cable Capacitance
(mfd/km) 0.25
c) Approx. Cable reactance
(ohm/km) 0.106
d) Impedance of cable
(ohm/km) 0.578
14 Continuous Current carrying
capacities
(a) In Ground at 30°C (A) 161
(b) In Air at 40°C (A) 184
Page 27 of 30
15
Short Circuit rating of
conductor for the
duration of 1 sec (kA)
6.61
16 Standard to which the cables
confirm
IS 8130/84, IS 7098
Part 2/85, IS 5831/84,
IS
3975/88 etc. with
latest up to date
amendments
17 Approx. Overall diameter (mm) Provide by
Manufacture
Page 28 of 30
6.0 Cable Tray6.0 Cable Tray6.0 Cable Tray6.0 Cable Tray
Sl. Sl. Sl. Sl.
NoNoNoNo
DescriptionDescriptionDescriptionDescription UnitUnitUnitUnit Supplier’s offerSupplier’s offerSupplier’s offerSupplier’s offer To be Filled by BidderTo be Filled by BidderTo be Filled by BidderTo be Filled by Bidder
1 Type Ladder/ Perforated Type
2 Material. /Thickness
3 Size of Runner mm
4 Construction Hot Dip G.I.
5 Standard Length mtr 2.5 mtr
6 Painting thickness mm Two coats of Red oxide
primer & final coat of
aluminum paint
7 Standard Width mm As per your site requirement
8 Accessories -2 # Coupler
plates with each length
Yes/No Yes
9 Hardware – Galvanized
Bolts Nuts and Washers
of required dimeter
Yes/No Yes
10 Load Bearing Capacity
Between two supported
point
Kg As per cable weight and cable
tray Size
11 Load bearing capacity
under cantilever condition
Kg As per cable weight and cable
tray Size
Page 29 of 30
Sr. No.
Technical Data Specification Design Requirement
Data to be filled up /Confirmed by Bidder
1 Site Condition
1.1 1.2 1.3
Type Mounting Ambient Temperature
Outdoor Floor/Plinth, Outdoor 50° C.
2 OPERATIVE CONDITION
2.1 2.2 2.3 2.4
Voltage System Frequency Fault Current
415 V ± 10 %, 3 phase 3 Ø, 4 WIRE 50 HZ, + 3 % / - 6 %. 25 kA for 1 sec
3 ENCLOSURE
3.1 Top cover, bottom sheet, component mounting plates, side covers, Canopy
2 mm
3.2 Front doors, rear doors, cable alley doors, Cubicle partition covers
1.6 mm
3.3 Gland plate 3 mm
3.4 Base frame Not Applicable
4 CONTROL SYSTEM
4.1
4.2
4.3
Voltage For Indication For Metering For Protection Control Supply Through Control Transformer Control Wiring
Not Applicable
5 BUSBAR
5.1 A. B. C. D.
E. F.
Phase Bus Bar Material Support Insulation Insulating Barriers Max. Current Density Permissible Permissible temp. rise over ambient
Aluminum SMC/DMC Epoxy Moulded(Resin) Fiber Glass / Poly Carbonate Of Minimum 1.5 Mm Thick 0.8 Amp. / mm² 40 deg. Cen
5.2 5.3
Neutral Bus bar Material Earth Bus Bar Material
50% of phase bus Aluminum Size as per SLD GI
6 PAINTING
Page 30 of 30
6.1
6.2 6.3 6.4 6.5
Type Of Paint Shade Exterior Interior Degree Of Protection Max. Temperature Rise Inside The Panel (°C.)
Powder coated RAL-7032 Semi pebble white IP 5x 35 ° C. above ambient
7 CABLE ENTRY Bottom
8 CONTROL TRANSFORMER
9 HARDWARE (ZINC PLATED)
10 SPACE HEATER
11 POCKET FOR DRAWINGS AT DOOR
12 Illumination and switched power plug