ADDENDUM #1
H. Smith Richardson Golf Course Clubhouse – Fairfield Addendum #1-1
NEW CLUBHOUSE
H. SMITH RICHARDSON GOLF COURSE 2425 MOREHOUSE HIGHWAY FAIRFIELD, CT 06824
S/P+A PROJECT NO. 18.124
DATE: August 22, 2019
The following changes to the Drawings and Project Specifications shall become a part of the Drawings and Project Specifications; superseding previously issued Drawings and Project Specifications to the extent modified by Addendum No. 1.
General Information:
The deadline for RFIs is Monday, August 26, 2019, 11:00am.
See attached RFIs. (8)
See attached Substitution Requests. (4)
New Specifications:
SECTION 074213.19, INSULATED METAL WALL PANELS has been added and is attached as part of this addendum. (6)
Changes to the Specifications:
TABLE OF CONTENTS:
o Page 2:
Division 07 – Thermal & Moisture Protection, add the following:
“Section 074213.19 Insulated Metal Wall Panels 6”
Division 08 – Openings, Section 081743, delete in its entirety.
o Page 5, Division 27 – Communications, Section 274120, revise “Pathways for Communications Systems” to read “Audio-Visual Systems”. (Per Internal Review)
STANDARD FORM OF AGREEMENT BETWEEN OWNER & CONTRACTOR (AIA A101), Pages 9-19, Articles 9.1.5 and .6, delete all text in red, green and light blue.
SECTION 081423, CLAD COMMERCIAL DOORS, Page 3, Article 2.4, add the following:
“B. Metal Panel: Comply with requirements in Section 074213.19 “Insulated Metal Wall Panels”.”
SECTION 081743, FRP FLUSH DOORS & FRAMES, delete in its entirety.
ADDENDUM #1
H. Smith Richardson Golf Course Clubhouse – Fairfield Addendum #1-2
SECTION 087100, DOOR HARDWARE:
o Page 1, Article 1.2.A.1., add the following:
“b. Sliding doors.”
o Page 11, Part 2, add the following:
“2.21 OPERATING TRIM
A. Operating Trim: BHMA A156.6; brass or bronze, unless otherwise indicated.
1. Basis-of-Design Product:
a. Rockwood Manufacturing Company; 215L
2. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
a. Burns Manufacturing Incorporated b. IVES Hardware; an Allegion company c. Substitutions: Under provisions of Section 012500 “Substitution
Procedures”.
2.22 BARN DOOR HARDWARE A. Barn Door Hardware: Solid steel construction, with spoked wheel rollers and flat
looping track including wall spacers, hangers, stops, bottom guide, and associated screws, fasteners, washers, etc.
1. Basis-of-Design Product:
a. Artisan Hardware, supplied by Specialty Doors & Hardware; Vintage Loop Strap Flat Track Hardware
b. Substitutions: Under provisions of Section 012500 “Substitution Procedures”.” (Per Internal Review)
o Page 15, Article 3.7, HW-18, revise “DUMMY TRIM” to read “PULL” and add “1 BARN DOOR HDWR”. (Per Internal Review)
SECTION 088000, GLAZING:
o Page 5, Article 2.4, add the following:
“A. Decorative Film Overlay: Translucent, dimensionally stable film, 2-mil-minimum thickness, with pressure-sensitive, clear adhesive back for adhering to glass and releasable protective backing.
1. Basis-of-Design:
ADDENDUM #1
H. Smith Richardson Golf Course Clubhouse – Fairfield Addendum #1-3
a. 3M; Prestige 70 Series
2. Products: Subject to compliance with requirements, available products that may be incorporated into the Work include, but are not limited to, the following:
1. Gila Film Products, an Eastman Chemical company 2. Llumar, an Eastman Chemical company 3. Substitutions: Under provisions of Section 012500 “Substitution
Procedures”.” (Per Internal Review)
o Page 7, Article 2.10, add the following:
“D. Decorative Film Overlay: Apply squarely aligned to glass edges, uniformly smooth, and free from tears, air bubbles, wrinkles, and rough edges, in single sheet completely overlaying the back face of clean glass, according to manufacturer's written instructions, including surface preparation and application temperature limitations.”
o Page 10, Article 3.8.A., revise “Not used” to read “Decorative film overlay, applied to surface as recommended by manufacturer”.
SECTION 098433, SOUND-ABSORBING WALL UNITS, Page 2, Article 1.8, delete in its entirety. (Per RFI #005)
SECTION 274120, header, revise “PATHWAYS FOR COMMUNICATIONS SYSTEMS” to read “AUDIO-VISUAL SYSTEMS”. (Per Internal Review)
Changes to the Drawings:
The following ARCHITECTURAL drawings have been deleted in their entirety. New drawings (4) have been added and are attached as part of this addendum*: (Per RFI #003 & Internal Review)
o A630 DOOR SCHEDULE o A640 DOOR & FRAME ELEVATIONS o A650 DOOR DETAILS o A920 SIGNAGE DETAILS
DRAWING A001, GENERAL INFORMATION & DRAWING LIST, List of Drawings, Food Service Drawing List, delete “FS-1.5.1 LOW VOLTAGE PLAN & SCHEDULE”, “FS-1.10.1 REFRIGERATION RACK DETAILS”, “FS-1.11.1 REFRIGERATION LOCATION PLAN”, “FS-1.12.1 BEVERAGE CONDUIT ROUTING PLAN”, and “FS-1.13.1 FABRICATION DETAILS” in their entirety. (Per RFI #001)
DRAWING A600, WINDOW & LOUVER ELEVATIONS, Window Elevations 1, Window Type 2, revise “GL-13” to read “GL-13 & GL-0”. (Per Internal Review)
DRAWING A630, DOOR SCHEDULE, delete in its entirety. A new DRAWING A630 has been added and is attached as part of this addendum.* (Per RFI #003)
ADDENDUM #1
H. Smith Richardson Golf Course Clubhouse – Fairfield Addendum #1-4
The bid date remains unchanged by this addendum. The addendum consists of twenty-two (22) pages of 8½” x 11” text and four (4) 30” x 42” drawings*. End of Addendum ‘1’
J.A. Rosa Construction, LLC
17 Town Line Rd. www.jarosa.com Bus. Office 1-203-879-3495 Wolcott, CT 06716 e-mail [email protected] Fax 1-203-879-0760 CT Reg. #: 565782
REQUEST FOR INFORMATION #1
Project: H. Smith Richardson Clubhouse Rebuild Architect: Silver/Petrucelli + Associates Date: 8/7/19 Drawing No.: A001 Specification:
Description:
The following drawings are missing according to the list of drawings on A001 FS-151FS-1101FS-1111FS-1121FS-1131
SP+A Response: Those sheets are not part of the bid package. The drawing list was incorrect and will be revisedin forthcoming addendum. CTN 08.12.19
RFI #001
1
Rebecca Bouchard
From: Dean PetrucelliSent: Tuesday, August 13, 2019 2:18 PMTo: Dyer, Corinne; Rebecca Bouchard; [email protected]; Chris NardiCc: Byrnes-Jacobsen, Matt ([email protected])Subject: RE: 2020-01
Good afternoon Rob,There is no furniture package as part of this project.Thank you
dean
Dean A Petrucelli, AIA Principal / Project Architect
S I L V E R / P E T R U C E L L I + A S S O C I A T E S P: 203.230.9007 x 207 | F: 203.230.8247 | C: 203.710.4881
From: Dyer, Corinne <[email protected]>Sent: Tuesday, August 13, 2019 2:12 PMTo: Dean Petrucelli <[email protected]>; Aris Stalis ([email protected]) <[email protected]>; RebeccaBouchard <[email protected]>Cc: Byrnes Jacobsen, Matt (Matt.Byrnes [email protected]) <Matt.Byrnes [email protected]>Subject: FW: 2020 01
See RFI below.
Corinne M. Dyer
Senior Buyer Purchasing Department | Town of Fairfield [email protected] | (P) 203-256-3060
http://www.fairfieldct.org/purchasing
From: Rob Pedicano <[email protected]>Sent:Monday, August 12, 2019 4:48 PMTo: Dyer, Corinne <[email protected]>Subject: 2020 01
Hi Corinne,
Is there an FFE (Furniture package) for this project?
Thanks,
Rob PedicanoAccount Executive
RFI #002
1
Rebecca Bouchard
From: Chris NardiSent: Friday, August 16, 2019 9:57 AMTo: Evan BurchellCc: Dyer, Corey; [email protected]; [email protected]; [email protected]; Rebecca BouchardSubject: FW: RFI's - H. Smith Richardson
Evan,
In response to your door RFI’s below, we will be re issuing the door schedule in an upcoming addendum which willaddress all of your questions. Thank You
Chris
Christopher Nardi, AIA Principal, Project Architect
3190 Whitney Avenue Bldg 2 | Hamden, CT 06518 One Post Hill Place | New London, CT 06320 silverpetrucelli.com | P: 203.230.9007 x 209 | F: 203.230.8247
From: Evan Burchell <[email protected]>Sent: Thursday, August 15, 2019 7:39 AMTo: Dyer, Corinne <[email protected]>Cc:Max Wernert <[email protected]>; Marc Gessner <[email protected]>; Mike Lampel <[email protected]>Subject: RFI's H. Smith Richardson
Good Morning,
Please see below RFI’s for the H. Smith Richardson Clubhouse Project?1. What material is Door Type “A” supposed to be? It does not specify on the Door schedule or in any of theDrawings2. What material is Door Type”B” supposed to be? In the Door Schedule it says Wood, but also Clad.3. What material is Door Type”2” supposed to be it doesn’t say anywhere in the Plans/Drawings, but assigned toOpenings below that call for Hollow Metal Frames. (SEE BELOW)4. For Openings 008B, 023, 025, 031B, 032B…. it calls for Hollow Metal Frames, but the drawings it refers to saythey are wood frames.5. What will be actual width for Barn Door at Opening: 004?
Evan Burchell Wernert Builders and Construction Managers Director of Business Development 76 Valley Road, Cos Cob CT 06807 203-869-1110 www.wernert.com
RFI #003
1
Rebecca Bouchard
From: Michael ChambersSent: Tuesday, August 20, 2019 10:13 AMTo: [email protected]: Rebecca BouchardSubject: RE: RFI for BID #2020-01
Good Morning Spencer,
Answers to your questions are below:
1) The price of automatic transfer switch ATS 1 should be included in the base bid, whereas the generator is afuture expense to not be included in the base bid.
2) Yes, MC cable is acceptable in concealed walls & ceilings.
Let me know if there is anything else.
Thanks,Michael Chambers Electrical Engineer
S I L V E R / P E T R U C E L L I + A S S O C I A T E SP: 203.230.9007 x 245 | F: 203.230.8247
From: Dean Petrucelli <[email protected]>Sent: Tuesday, August 20, 2019 9:38 AMTo: Bob Banning <[email protected]>; Michael Chambers <[email protected]>; RebeccaBouchard <[email protected]>; Chris Nardi <[email protected]>Subject: FW: RFI for BID #2020 01
Michael,Answers back to the contractor and also rebecca for inclusion in the next addendumthanks
Dean A Petrucelli, AIA Principal / Project Architect
S I L V E R / P E T R U C E L L I + A S S O C I A T E S P: 203.230.9007 x 207 | F: 203.230.8247 | C: 203.710.4881
From: Dyer, Corinne <[email protected]>Sent: Tuesday, August 20, 2019 9:37 AMTo: Dean Petrucelli <[email protected]>; Rebecca Bouchard <[email protected]>; DaveStein <[email protected]>Cc: Byrnes Jacobsen, Matt (Matt.Byrnes [email protected]) <Matt.Byrnes [email protected]>Subject: FW: RFI for BID #2020 01
RFI #004
2
Good Morning,Please see the RFI below. Thank you,
Corinne M. Dyer
Senior Buyer Purchasing Department | Town of Fairfield [email protected] | (P) 203-256-3060
http://www.fairfieldct.org/purchasing
From: [email protected] <[email protected]>Sent: Tuesday, August 20, 2019 9:29 AMTo: Dyer, Corinne <[email protected]>Subject: RFI for BID #2020 01
Hello Corinne,
We have the following requests for information for the Smith Richardson Clubhouse Rebuild:
1) Should the price of the automatic transfer switch ATS 1 be included in the base bid even though the generator is notincluded in the base bid. Typically these two items are purchased/bundled together.
2) Can MC cable be used in concealed ceilings and walls?
Thank you.
Spencer LawEstimatorMcMellon Electric, LLC360 Sniffens LaneStratford, CT 06615203 377 2026 [email protected]
1
Rebecca Bouchard
From: Dean PetrucelliSent: Tuesday, August 20, 2019 2:36 PMTo: Dyer, Corinne; Rebecca Bouchard; Chris NardiCc: [email protected]; [email protected]; [email protected]: RE: RFI - H. Smith Richardson Club House Rebuild - Fairfield, CT
Good afternoon all,To answer the RFI submitted below, Yes, the attic stock requirements for the acoustical panels per section 098433 canbe waived.Thank you
dean
Dean A Petrucelli, AIA Principal / Project Architect
S I L V E R / P E T R U C E L L I + A S S O C I A T E S P: 203.230.9007 x 207 | F: 203.230.8247 | C: 203.710.4881
From: Dyer, Corinne <[email protected]>Sent: Tuesday, August 20, 2019 2:24 PMTo: Dean Petrucelli <[email protected]>; Dave Stein <[email protected]>; Rebecca Bouchard<[email protected]>Cc: Byrnes Jacobsen, Matt (Matt.Byrnes [email protected]) <Matt.Byrnes [email protected]>Subject: FW: RFI H. Smith Richardson Club House Rebuild Fairfield, CTImportance: High
Good afternoon, Please see the RFI below. Thank you,
Corinne M. Dyer
Senior Buyer Purchasing Department | Town of Fairfield [email protected] | (P) 203-256-3060
http://www.fairfieldct.org/purchasing
From: Steven Dopp <sdopp@thp gc.com>Sent: Tuesday, August 20, 2019 1:50 PMTo: Dyer, Corinne <[email protected]>Cc: 'Rich Jagoe' <richjagoe@thp gc.com>Subject: RFI H. Smith Richardson Club House Rebuild Fairfield, CTImportance: High
Corinne, Can you please submit this sub-contractor RFI below for the Smith Clubhouse rebuild project.
RFI #005
2
Thanks you, Regards, Steve
Steve DoppProject Manager
Tomlinson Hawley Patterson2225 Reservoir AveTrumbull CT 06611203 372 3583 Office203 395 4478 Cell203 371 7549 Faxsdopp@thp gc.com
From: Michael St Hilaire [mailto:[email protected]]Sent: Tuesday, August 20, 2019 10:16 AM To: [email protected]: H Smith Richardson RFI
Steve,
Can you please submit this RFI for review:
1) Reference spec section 098433. The maintenance section calls for 5% attic stock, but not fewer than 5 units. Can this be requirement be waived as there are only 4 units to be installed?
Thanks,
Mike St. Hilaire, Vice President Central Conn. Acoustics, Inc. 105 North Cherry Street Wallingford, CT 06492 p (203) 269-1421 f (203) 265-3211 [email protected]
1
Rebecca Bouchard
From: Michael ChambersSent: Wednesday, August 21, 2019 8:00 AMTo: [email protected]: Rebecca BouchardSubject: RE: RFI for BID #2020-01
Good Morning Spencer,
Sorry for not getting back to you yesterday, see below for the answers to your questions:
1) There is no known service agreements with fire alarm/security vendors. It would be acceptable to bring in anyvendors as long as they meet the specifications.
2) I understand where you’re coming from with the BICSI qualifications, but respectfully we’d like to keep it as isstated in the specifications.
Let me know if you have any questions.
Thanks,Michael Chambers Electrical Engineer
S I L V E R / P E T R U C E L L I + A S S O C I A T E SP: 203.230.9007 x 245 | F: 203.230.8247
From: [email protected] <[email protected]>Sent: Tuesday, August 20, 2019 11:58 AMTo:Michael Chambers <[email protected]>Cc: Rebecca Bouchard <[email protected]>Subject: RE: RFI for BID #2020 01
Thank you Michael.
I have a couple more questions:
Does the town have service agreements with a fire alarm/security vendor(s) for the new fire alarm and accesscontrol systems or can we bring in any vendors as long as they meet the specifications?We would like to request that the BICSI qualifications for low voltage work (communications equipment rooms,backbone cabling, horizontal cabling, control voltage cabling, etc.) be waived as these qualifications greatly limitthe amount of contractors that can complete this work.
Spencer LawEstimatorMcMellon Electric, LLC360 Sniffens LaneStratford, CT 06615203 377 2026 [email protected]
RFI #006
Supporting DataAttached: Drawings Product Data Samples Tests Reports
A/E' s REVIEW AND ACTION
Substitution approved - Make submittals in accordance with Specification Substitution Procedures.
Substitution approved as noted - Make submittals in accordance with Specification Substitution Procedures.
Substitution rejected - Use specified materials.
Substitution Request received too late - Use specified materials.
Signed by: Date:
Submitted by: Courtney Damore
Signed by: Courtney Damore
Firm: Scranton Products
Address: 801 E. Corey Street
Scranton, Pennsylvania 18504
Telephone: (570) 348-0997 ext. 8032, [email protected]
The Undersigned certifies:
Proposed substitution has been fully investigated and determined to be equal or superior in all respects to specified product.Same warranty will be furnished for proposed substitution as for specified product.Same maintenance service and source of replacement parts, as applicable, is available.Proposed substitution will have no adverse effect on other trades and will not affect or delay progress schedule.Proposed substitution does not affect dimensions and functional clearances.
Proposed Substitution: Hiny Hiders Solid Plastic
Manufacturer: Scranton Products Address: scrantonproducts.com Phone: 570-348-0997
Trade Name: Scranton Hiny Hiders Solid Plastic Model No.: N/A
Attached data includes product description, specifications, drawings, photographs, and performance and test data adequate for evaluation ofthe request; applicable portions of the data are clearly identified.
Attached data also includes a description of changes to the Contract Documents that the proposed substitution will require for its properinstallation.
Specification Title: Phenolic-Core Toilet Compartments Description: Phenolic-Core Toilet Compartments
Section: 102113.17 Page: 2 Article/Paragraph: 2.2
Project:H Smith Richardson Golf Course ClubhouseFacility (17-672584)
Substitution RequestNumber: SubReq-04981
FAIRFIELD, CT From: Courtney Damore, Scranton Products
To:Corinne Dyer, Town of Fairfield PurchasingDepartment
Date: 08/08/2019
[email protected], 203-255-8367 A/E Project Number:
Re: Phenolic-Core Toilet Compartments Contract For: Town of Fairfield Purchasing Department
SUBSTITUTION REQUEST(During the Bidding/Negotiating Stage)
R. Bouchard/D. Petrucelli 08.20.19
SR #001
Supporting DataAttached: Drawings Product Data Samples Tests Reports
A/E' s REVIEW AND ACTION
Substitution approved - Make submittals in accordance with Specification Substitution Procedures.
Substitution approved as noted - Make submittals in accordance with Specification Substitution Procedures.
Substitution rejected - Use specified materials.
Substitution Request received too late - Use specified materials.
Signed by: Date:
Submitted by: Courtney Damore
Signed by: Courtney Damore
Firm: Scranton Products
Address: 801 E. Corey Street
Scranton, Pennsylvania 18504
Telephone: (570) 348-0997 ext. 8032, [email protected]
The Undersigned certifies:
Proposed substitution has been fully investigated and determined to be equal or superior in all respects to specified product.Same warranty will be furnished for proposed substitution as for specified product.Same maintenance service and source of replacement parts, as applicable, is available.Proposed substitution will have no adverse effect on other trades and will not affect or delay progress schedule.Proposed substitution does not affect dimensions and functional clearances.
Proposed Substitution: Duralife Lockers
Manufacturer: Scranton Products Address: scrantonproducts.com Phone: 570-348-0997
Trade Name: Scranton Duralife Lockers Model No.: N/A
Attached data includes product description, specifications, drawings, photographs, and performance and test data adequate for evaluation ofthe request; applicable portions of the data are clearly identified.
Attached data also includes a description of changes to the Contract Documents that the proposed substitution will require for its properinstallation.
Specification Title: Metal Lockers Description: Welded Corridor Lockers
Section: 105113 Page: 3 Article/Paragraph: 2.3
Project:H Smith Richardson Golf Course ClubhouseFacility (17-672584)
Substitution RequestNumber: SubReq-04982
FAIRFIELD, CT From: Courtney Damore, Scranton Products
To:Corinne Dyer, Town of Fairfield PurchasingDepartment
Date: 08/08/2019
[email protected], 203-255-8367 A/E Project Number:
Re: Metal Lockers Contract For: Town of Fairfield Purchasing Department
SUBSTITUTION REQUEST(During the Bidding/Negotiating Stage)
R. Bouchard/D. Petrucelli 08.20.19
As requested by the Owner.
Supporting DataAttached: Drawings Product Data Samples Tests Reports
A/E' s REVIEW AND ACTION
Substitution approved - Make submittals in accordance with Specification Substitution Procedures.
Substitution approved as noted - Make submittals in accordance with Specification Substitution Procedures.
Substitution rejected - Use specified materials.
Substitution Request received too late - Use specified materials.
Signed by: Date:
Submitted by: Courtney Damore
Signed by: Courtney Damore
Firm: Scranton Products
Address: 801 E. Corey Street
Scranton, Pennsylvania 18504
Telephone: (570) 348-0997 ext. 8032, [email protected]
The Undersigned certifies:
Proposed substitution has been fully investigated and determined to be equal or superior in all respects to specified product.Same warranty will be furnished for proposed substitution as for specified product.Same maintenance service and source of replacement parts, as applicable, is available.Proposed substitution will have no adverse effect on other trades and will not affect or delay progress schedule.Proposed substitution does not affect dimensions and functional clearances.
Proposed Substitution: Tufftec Lockers
Manufacturer: Scranton Products Address: scrantonproducts.com Phone: 570-348-0997
Trade Name: Scranton Tufftec Lockers Model No.: N/A
Attached data includes product description, specifications, drawings, photographs, and performance and test data adequate for evaluation ofthe request; applicable portions of the data are clearly identified.
Attached data also includes a description of changes to the Contract Documents that the proposed substitution will require for its properinstallation.
Specification Title: Metal Lockers Description: Z-Style Lockers
Section: 105113 Page: 4 Article/Paragraph: 2.4
Project:H Smith Richardson Golf Course ClubhouseFacility (17-672584)
Substitution RequestNumber: SubReq-04983
FAIRFIELD, CT From: Courtney Damore, Scranton Products
To:Corinne Dyer, Town of Fairfield PurchasingDepartment
Date: 08/08/2019
[email protected], 203-255-8367 A/E Project Number:
Re: Metal Lockers Contract For: Town of Fairfield Purchasing Department
SUBSTITUTION REQUEST(During the Bidding/Negotiating Stage)
R. Bouchard/D. Petrucelli 08.20.19
As requested by the Owner.
Supporting DataAttached: Drawings Product Data Samples Tests Reports
A/E' s REVIEW AND ACTION
Substitution approved - Make submittals in accordance with Specification Substitution Procedures.
Substitution approved as noted - Make submittals in accordance with Specification Substitution Procedures.
Substitution rejected - Use specified materials.
Substitution Request received too late - Use specified materials.
Signed by: Date:
Submitted by: Courtney Damore
Signed by: Courtney Damore
Firm: Scranton Products
Address: 801 E. Corey Street
Scranton, Pennsylvania 18504
Telephone: (570) 348-0997 ext. 8032, [email protected]
The Undersigned certifies:
Proposed substitution has been fully investigated and determined to be equal or superior in all respects to specified product.Same warranty will be furnished for proposed substitution as for specified product.Same maintenance service and source of replacement parts, as applicable, is available.Proposed substitution will have no adverse effect on other trades and will not affect or delay progress schedule.Proposed substitution does not affect dimensions and functional clearances.
Proposed Substitution: Tufftec Bench
Manufacturer: Scranton Products Address: scrantonproducts.com Phone: 570-348-0997
Trade Name: Scranton Tufftec Bench Model No.: N/A
Attached data includes product description, specifications, drawings, photographs, and performance and test data adequate for evaluation ofthe request; applicable portions of the data are clearly identified.
Attached data also includes a description of changes to the Contract Documents that the proposed substitution will require for its properinstallation.
Specification Title: Metal Lockers Description: Locker Benches
Section: 105113 Page: 6 Article/Paragraph: 2.5
Project:H Smith Richardson Golf Course ClubhouseFacility (17-672584)
Substitution RequestNumber: SubReq-04984
FAIRFIELD, CT From: Courtney Damore, Scranton Products
To:Corinne Dyer, Town of Fairfield PurchasingDepartment
Date: 08/08/2019
[email protected], 203-255-8367 A/E Project Number:
Re: Metal Lockers Contract For: Town of Fairfield Purchasing Department
SUBSTITUTION REQUEST(During the Bidding/Negotiating Stage)
R. Bouchard 08.20.19
INSULATED METAL WALL PANELS
H. Smith Richardson Golf Course Clubhouse – Fairfield 074213.19-1
SECTION 074213.19 - INSULATED METAL WALL PANELS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Foamed-insulation-core metal wall panels.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.
1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for each type of panel and accessory.
B. Shop Drawings:
1. Include fabrication and installation layouts of metal panels; panel profiles, corners, and accessories; and special details.
C. Samples: For each type of exposed finish, prepared on Samples of size indicated below.
1. Metal Panels: 12 inches long by actual panel width. Include metal panel accessories.
1.4 INFORMATIONAL SUBMITTALS
A. Qualification Data: For Installer.
B. Product Test Reports: For each product, tests performed by a qualified testing agency.
C. Field quality-control reports.
D. Sample Warranties: For special warranties.
1.5 CLOSEOUT SUBMITTALS
A. Maintenance Data: For metal panels to include in maintenance manuals.
1.6 QUALITY ASSURANCE
A. Installer Qualifications: An entity that employs installers and supervisors who are trained and approved by manufacturer.
INSULATED METAL WALL PANELS
H. Smith Richardson Golf Course Clubhouse – Fairfield 074213.19-2
1.7 DELIVERY, STORAGE, AND HANDLING
A. Deliver components, metal panels, and other manufactured items so as not to be damaged or deformed. Package metal panels for protection during transportation and handling.
B. Unload, store, and erect metal panels in a manner to prevent bending, warping, twisting, and surface damage.
C. Stack metal panels horizontally on platforms or pallets, covered with suitable weathertight and ventilated covering. Store metal panels to ensure dryness, with positive slope for drainage of water. Do not store metal panels in contact with other materials that might cause staining, denting, or other surface damage.
D. Retain strippable protective covering on metal panels during installation.
1.8 FIELD CONDITIONS
A. Weather Limitations: Proceed with installation only when existing and forecasted weather conditions permit assembly of metal panels to be performed according to manufacturers' written instructions and warranty requirements.
1.9 COORDINATION
A. Coordinate metal panel installation with adjoining work to provide a leakproof, secure, and noncorrosive installation.
1.10 WARRANTY
A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of metal panel systems that fail in materials or workmanship within specified warranty period.
1. Failures include, but are not limited to, the following:
a. Structural failures including rupturing, cracking, or puncturing. b. Deterioration of metals and other materials beyond normal weathering.
2. Warranty Period: Five (5) years from date of Substantial Completion.
B. Special Warranty on Panel Finishes: Manufacturer's standard form in which manufacturer agrees to repair finish or replace metal panels that show evidence of deterioration of factory-applied finishes within specified warranty period.
1. Exposed Panel Finish: Deterioration includes, but is not limited to, the following:
a. Color fading more than 5 Hunter units when tested according to ASTM D 2244. b. Chalking in excess of a No. 8 rating when tested according to ASTM D 4214. c. Cracking, checking, peeling, or failure of paint to adhere to bare metal.
2. Finish Warranty Period: Twenty (20) years from date of Substantial Completion.
INSULATED METAL WALL PANELS
H. Smith Richardson Golf Course Clubhouse – Fairfield 074213.19-3
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Structural Performance: Provide metal panel systems capable of withstanding the effects of the following loads, based on testing according to ASTM E 72:
1. Wind and Other Design Loads: As required by code and per authorities having jurisdiction.
2. Deflection Limits: For wind loads, no greater than 1/180 of the span.
B. Air Infiltration: Air leakage of not more than 0.06 cfm/sq. ft. when tested according to ASTM E 283 at the following test-pressure difference:
1. Test-Pressure Difference: 1.57 lbf/sq. ft.
C. Water Penetration under Static Pressure: No water penetration when tested according to ASTM E 331 at the following test-pressure difference:
1. Test-Pressure Difference: 6.24 lbf/sq. ft.
D. Thermal Movements: Allow for thermal movements from ambient and surface temperature changes by preventing buckling, opening of joints, overstressing of components, failure of joint sealants, failure of connections, and other detrimental effects. Base calculations on surface temperatures of materials due to both solar heat gain and nighttime-sky heat loss.
1. Temperature Change (Range): 120 deg F (67 deg C), ambient; 180 deg F (100 deg C), material surfaces.
E. Fire-Test-Response Characteristics: Provide metal wall panels and system components with the following fire-test-response characteristics, as determined by testing identical panels and system components per test method indicated below by UL or another testing and inspecting agency acceptable to authorities having jurisdiction. Identify products with appropriate markings of applicable testing agency.
1. Surface-Burning Characteristics: Provide wall panels with a flame-spread index of 25 or less and a smoke-developed index of 450 or less, per ASTM E 84.
2.2 FOAMED-INSULATION-CORE METAL WALL PANELS
A. General: Provide factory-formed and -assembled metal wall panels fabricated from two (2) metal facing sheets over a corrugated polyallomer (CPA) stabilizers on both faces and insulation core foamed in place during fabrication. Include accessories required for weathertight installation.
1. Basis-of-Design Product:
a. Laminators, Inc.; Thermolite Panel b. Substitutions: Under provisions of Section 012500 “Substitution Procedures”.
2. Overall Panel Thickness: 1-inch. 3. Exterior Skin: Aluminum, ASTM B 209.
INSULATED METAL WALL PANELS
H. Smith Richardson Golf Course Clubhouse – Fairfield 074213.19-4
a. Thickness: Manufacturer's standard for finish and texture indicated. b. Finish: Match system in which being installed. c. Texture: Smooth. d. Backing Sheet: 0.125-inch-thick, corrugated, high-density polyethylene.
4. Interior Skin: Aluminum.
a. Thickness: Manufacturer's standard for finish and texture indicated. b. Finish: Match system in which being installed. c. Texture: Smooth. d. Backing Sheet: 0.125-inch-thick, corrugated, high-density polyethylene.
5. Insulation Core: Manufacturer’s standard modified polyisocyanurate or polyurethane foam using a non-CFC blowing agent, with maximum flame-spread and smoke-developed indexes of 25 and 450, respectively.
a. Closed-Cell Content: Ninety percent (90%) when tested according to ASTM D 6226.
b. Density: 2.0 to 2.6 lb/cu. ft. when tested according to ASTM D 1622. c. Compressive Strength: Minimum 20 psi when tested according to ASTM D 1621. d. Shear Strength: 26 psi when tested according to ASTM C 273.
6. Thermal-Resistance Value (R-Value): 7 according to ASTM C 1363.
2.3 MISCELLANEOUS MATERIALS
A. Panel Sealants: Provide sealant type recommended by manufacturer that are compatible with panel materials, are non-staining, and do not damage panel finish.
1. Sealant Tape: Pressure-sensitive, one hundred percent (100%) solids, gray polyisobutylene compound sealant tape with release-paper backing. Provide permanently elastic, non-sag, nontoxic, non-staining tape ½ inch wide and 1/8 inch thick.
2. Joint Sealant: ASTM C 920; elastomeric polyurethane or silicone sealant; of type, grade, class, and use classifications required to seal joints in metal panels and remain weathertight; and as recommended in writing by metal panel manufacturer.
3. Butyl-Rubber-Based, Solvent-Release Sealant: ASTM C 1311.
2.4 FABRICATION
A. General: Fabricate and finish metal panels and accessories at the factory, by manufacturer's standard procedures and processes, as necessary to fulfill indicated performance requirements demonstrated by laboratory testing. Comply with indicated profiles and with dimensional and structural requirements.
2.5 FINISHES
A. Protect mechanical and painted finishes on exposed surfaces from damage by applying a strippable, temporary protective covering before shipping.
B. Appearance of Finished Work: Variations in appearance of abutting or adjacent pieces are acceptable if they are within one-half of the range of approved Samples. Noticeable variations
INSULATED METAL WALL PANELS
H. Smith Richardson Golf Course Clubhouse – Fairfield 074213.19-5
in same piece are not acceptable. Variations in appearance of other components are acceptable if they are within the range of approved Samples and are assembled or installed to minimize contrast.
C. Aluminum Panels and Accessories:
1. Two-Coat Fluoropolymer: AAMA 620. Fluoropolymer finish containing not less than seventy percent (70%) PVDF resin by weight in color coat. Prepare, pretreat, and apply coating to exposed metal surfaces to comply with coating and resin manufacturers' written instructions.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates, areas, and conditions, with Installer present, for compliance with requirements for installation tolerances, and other conditions affecting performance of the Work.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 METAL PANEL INSTALLATION
A. General: Install metal panels according to manufacturer's written instructions in orientation, sizes, and locations indicated. Anchor metal panels and other components of the Work securely in place, with provisions for thermal and structural movement.
1. Shim or otherwise plumb substrates receiving metal panels. 2. Apply a continuous ribbon of sealant tape to panel side laps and elsewhere as needed to
make panels weathertight.
B. Metal Protection: Where dissimilar metals contact each other or corrosive substrates, protect against galvanic action as recommended in writing by metal panel manufacturer.
C. Joint Sealers: Install gaskets, joint fillers, and sealants where indicated and where required for weathertight performance of metal wall panel assemblies. Provide types of gaskets, fillers, and sealants indicated by metal panel manufacturer; or, if not indicated, provide types recommended by metal wall panel manufacturer.
1. Seal metal wall panel end laps with double beads of tape or sealant, full width of panel. Seal side joints where recommended by metal wall panel manufacturer.
2. Prepare joints and apply sealants to comply with requirements in Section 079200 "Joint Sealants."
3.3 FIELD QUALITY CONTROL
A. Testing Agency: Engage a qualified testing agency to perform tests and inspections.
B. Metal wall panels will be considered defective if they do not pass test and inspections.
INSULATED METAL WALL PANELS
H. Smith Richardson Golf Course Clubhouse – Fairfield 074213.19-6
C. Additional tests and inspections, at Contractor's expense, are performed to determine compliance of replaced or additional work with specified requirements.
D. Prepare test and inspection reports.
3.4 CLEANING AND PROTECTION
A. Remove temporary protective coverings and strippable films, if any, as metal panels are installed, unless otherwise indicated in manufacturer's written installation instructions. On completion of metal panel installation, clean finished surfaces as recommended by metal panel manufacturer. Maintain in a clean condition during construction.
B. Replace metal panels that have been damaged or have deteriorated beyond successful repair by finish touchup or similar minor repair procedures.
END OF SECTION 074213.19
SILVER / PETRUCELLI + ASSOCIATES Drawing Title:Revised By:Date:Description:Revision:Project Title: Date:
Scale:
Drawn By:
Project Number:
Drawing Number:
Architects / Engineers / Interior DesignersH. Smith Richardson Golf Course Clubhouse2425 Morehouse HwyFairfield, CT 06824
Revised By:
June 28, 2019100% CD
Tel. 203 230 9007 Fax. 203 230 8247One Post Hill Place, New London, CT 06320
silverpetrucelli.com
3190 Whitney Avenue, Hamden, CT 06518-2340
Issued for Bid July 31, 2019
Addendum 1 August 22, 2019 A630DOOR SCHEDULE
CAC
JULY 31, 2019
18.124
DOOR SCHEDULEDOOR FRAME
FIRERATING HARDWARE - SEE SPECIFICATIONS
REMARKSDO
OR
NU
MB
ER
FRO
M R
OO
M N
o.
TO R
OO
M N
o.
DO
UB
LE L
EA
F D
OO
R
UN
EV
EN
DO
UB
LE L
EA
F
WID
TH
HE
IGH
T
DO
OR
TY
PE
DO
OR
MA
TER
IAL
DO
OR
FIN
ISH
DO
OR
GLA
ZIN
G
FRA
ME
TY
PE
FRA
ME
MA
TER
IAL
FRA
ME
FIN
ISH
HE
AD
DE
TAIL
JAM
B D
ETA
IL
SA
DD
LE D
ETA
IL
FRA
ME
GLA
ZIN
G
RE
SIS
TS P
AS
SA
GE
OF
SM
OK
E
90
MIN
UTE
LA
BE
LED
60
MIN
UTE
LA
BE
LED
45
MIN
UTE
LA
BE
LED
NO
T R
EQ
UIR
ED
FIRE CODE DISABLED REQUIREMENTS
PA
NIC
/EX
IT D
EV
ICE
PO
SIT
IVE
LA
TCH
ING
ELE
CTR
O-M
AG
NE
TIC
HO
LD
DE
LAY
ED
AC
TIO
N C
LOS
ER
PU
SH
PLA
TE/P
ULL
HA
ND
LES
ALA
RM
ED
EX
IT -
SE
E E
LEC
.
PO
WE
R A
SS
IST.
OP
ER
ATO
R
LEV
ER
HA
ND
LES
PR
OTE
CTI
ON
PLA
TE
TAC
TILE
WA
RN
ING
AC
CE
SS
IBLE
TH
RE
SH
OLD
SIG
NA
GE
TY
PE
- S
EE
A9
30
SIGNAGE TEXT
001A 001 6' - 0" 7' - 0" H FF/PTD GL-13 H FF/PTD 2/A650 11/A650 GL-13 ● ● ● ● ● ● ● DOOR SECURITY CONTACT001B 001 6' - 0" 7' - 0" F FF/PTD GL-13 F FF/PTD 2/A650 9/A650 GL-13 ● FIXED DOOR001C 002 001 6' - 0" 7' - 0" F PTD GL-2 F PTD 6/A650 8/A650 GL-2 ● ● ● ● ● ● ● S8 EXIT001D 001 6' - 0" 7' - 0" F FF/PTD GL-13 F FF/PTD 2/A650 9/A650 GL-13 ● FIXED DOOR002A 002 6' - 0" 7' - 0" F FF/PTD GL-13 F FF/PTD 2/A650 9/A650 GL-13 ● FIXED DOOR002B 002 6' - 0" 7' - 0" F FF/PTD GL-13 F FF/PTD 2/A650 9/A650 GL-13 ● FIXED DOOR002C 002 014 6' - 0" 7' - 0" B PTD GL-2 B PTD 7/A650 8/A650 -- ● ● ● ● ● ● ●002E 002 6' - 0" 7' - 0" F FF/PTD GL-13 F FF/PTD 5/A650 9/A650 GL-13 ● ● ● ● ● ● ● S8 EXIT DOOR SECURITY CONTACT003A 002 003 6' - 0" 7' - 0" B PTD GL-2 B PTD 7/A650 8/A650 -- ● ● ● ● ● ● S9 DINING003B 003 002 6' - 0" 7' - 0" B PTD GL-2 B PTD 7/A650 8/A650 -- ● ● ● ● ● ● S9 DINING003C 003 002 6' - 0" 7' - 0" B PTD GL-2 B PTD 7/A650 8/A650 -- ● ● ● ● ● ● S9 DINING003D 003 6' - 0" 7' - 0" F FF/PTD GL-13 F FF/PTD 5/A650 9/A650 GL-13 ● ● ● ● ● ● ● S8 EXIT DOOR SECURITY CONTACT003E 003 6' - 0" 7' - 0" F FF/PTD GL-13 F FF/PTD 5/A650 9/A650 GL-13 ● ● ● ● ● ● DOOR SECURITY CONTACT003F 003 6' - 0" 7' - 0" F FF/PTD GL-13 F FF/PTD 5/A650 9/A650 GL-13 ● ● ● ● ● ● DOOR SECURITY CONTACT003G 003 6' - 0" 7' - 0" F FF/PTD GL-13 F FF/PTD 5/A650 9/A650 GL-13 ● ● ● ● ● ● DOOR SECURITY CONTACT003H 003 6' - 0" 7' - 0" F FF/PTD GL-13 F FF/PTD 5/A650 9/A650 GL-13 ● ● ● ● ● ● DOOR SECURITY CONTACT003J 003 6' - 0" 7' - 0" F FF/PTD GL-13 F FF/PTD 5/A650 9/A650 GL-13 ● ● ● ● ● ● DOOR SECURITY CONTACT003K 007A 6' - 0" 7' - 0" F FF/PTD GL-13 F FF/PTD 5/A650 9/A650 GL-13 ● ● ● ● ● ● DOOR SECURITY CONTACT003L 007A 6' - 0" 7' - 0" F FF/PTD GL-13 F FF/PTD 5/A650 9/A650 GL-13 ● ● ● ● ● ● DOOR SECURITY CONTACT003M 007A 6' - 0" 7' - 0" F FF/PTD GL-13 F FF/PTD 5/A650 9/A650 GL-13 ● ● ● ● ● ● ● S8 EXIT DOOR SECURITY CONTACT003N 002 007A 6' - 0" 7' - 0" B PTD GL-2 B PTD 7/A650 8/A650 -- ● ● ● ● ● S9 BAR004 002 004 0' - 0" 0' - 0" A PTD -- ** PTD 1 (SIM) 3 (SIM) -- ● ● ● ● S9 COATS BARN DOOR - SEE SHEET A660 (**) FRAME OPENING TO BE 2'-8" CLEAR
(DOOR OVERLAPS OPENING)005 005 002 3' - 0" 7' - 0" A PTD -- A PTD 3 1 -- ● ● ● ● ● S3 UNISEX006 006 002 3' - 0" 7' - 0" A PTD -- A PTD 3 1 -- ● ● ● ● ● S3 UNISEX008A 008 007A 6' - 0" 7' - 0" C FF ACRYLIC C PTD 2 2 -- ● S9 KITCHEN DUAL ACTING w/ CLOSERS008B 008 3' - 6" 7' - 0" D FF/PTD INSUL.
PNL.D CLAD FF/PTD 1/A650 9/A650 -- ● ● ● ● ● ● S8 EXIT DOOR SECURITY CONTACT
009 008 009 3' - 0" 7' - 0" A PTD -- A PTD 3 1 -- ● ● ● ● S9 OFFICE010 010 002 3' - 0" 7' - 0" A PTD -- A PTD 3 1/A140 -- ● ● ● ● ● S9 STORAGE011A 002 011 3' - 0" 7' - 0" A PTD -- A PTD 3 1/A140 -- ● ● ● ● S9 CONFERENCE011B 011 9' - 0" 7' - 0" G FF/PTD GL-13 G FF/PTD 2/A650 10/A650 GL-13 ● ● ● ● ● ● S8 EXIT DOOR SECURITY CONTACT (***) TWO FIXED PANELS, ONE OPERABLE012 012 014 3' - 0" 7' - 0" A PTD -- A PTD 3 1 -- ● ● ● ● ● S9 IT013 013 014 3' - 0" 7' - 0" A PTD -- A PTD 3 1 -- ● ● ● ● ● S9 CUSTODIAL014 014 6' - 0" 7' - 0" F FF/PTD GL-13 F FF/PTD 2/A650 9/A650 GL-13 ● ● ● ● ● ● ● S9 EXIT DOOR SECURITY CONTACT015 014 015 6' - 0" 7' - 0" F PTD GL-2 F PTD 6/A650 8/A650 GL-2 ● ● ● ● ● S9 PRO SHOP016A 015 016 3' - 0" 7' - 0" A PTD -- A PTD 3 1 -- ● ● ● ● S9 PRO OFFICE016B 016 6' - 0" 7' - 0" F**** FF/PTD GL-13 F**** FF/PTD 3/A650 9/A650 GL-13 ● ● ● ● ● ● S8 EXIT DOOR SECURITY CONTACT (****) ONE FIXED PANEL, ONE OPERABLE017 017 6' - 0" 7' - 0" F FF/PTD GL-13 F FF/PTD 2/A650 9/A650 GL-13 ● ● ● ● ● ● ● S8 EXIT DOOR SECURITY CONTACT018 014 018 3' - 0" 7' - 0" A PTD -- A PTD 3 1 -- ● ● ● ● ● S2 WOMEN018A 018 017 3' - 0" 7' - 0" E PTD -- E PTD 3 1 -- ● ● ● ● ● S2 WOMEN020 018 020 3' - 0" 7' - 0" A PTD -- A PTD 3 1 -- ● ● ● ● ● S2 WOMEN021 021 020 0' - 0" 0' - 0" -- -- -- A PTD 1 3 -- CASED OPENING022 020 022 0' - 0" 0' - 0" -- -- -- A PTD 1 3 -- CASED OPENING023 023 3' - 6" 7' - 0" D FF/PTD INSUL.
PNL.D CLAD FF/PTD 1/A650 9/A650 -- ● ● ● ● ● ● S8 EXIT DOOR SECURITY CONTACT
023A 023 017 3' - 0" 7' - 0" A PTD -- A PTD 3 1 -- ● ● ● ● ● S9 MECHANICAL024 017 024 3' - 0" 7' - 0" A PTD -- A PTD 3 1 -- ● ● ● ● ● S9 STORAGE025 025 3' - 6" 7' - 0" D FF/PTD INSUL.
PNL.D CLAD FF/PTD 1/A650 9/A650 -- ● ● ● ● ● ● S8 EXIT DOOR SECURITY CONTACT
026 026 014 3' - 0" 7' - 0" A PTD -- A PTD 3 1 -- ● ● ● ● ● S1 MEN026A 026 017 3' - 0" 7' - 0" E PTD -- E PTD 3 1 -- ● ● ● ● ● S1 MEN028 028 026 3' - 0" 7' - 0" A PTD -- A PTD 3 1 -- ● ● ● ● ● S1 MEN029 029 028 0' - 0" 0' - 0" -- -- -- A PTD 1 3 -- CASED OPENING030 028 030 0' - 0" 0' - 0" -- -- -- A PTD 1 3 -- CASED OPENING031A 031 12' - 0" 8' - 0" J FF GL-13 J PTD 1/A660 2/A660 -- OVERHEAD DOOR031B 031 3' - 6" 7' - 0" D FF/PTD INSUL.
PNL.D CLAD FF/PTD 1/A650
(SIM)9/A650
(SIM)-- ● ● ● ● ● ● S9 CART BARN DOOR SECURITY CONTACT
032A 032 12' - 0" 8' - 0" J FF GL-13 J PTD 1/A660 2/A660 -- OVERHEAD DOOR032B 032 3' - 6" 7' - 0" D FF/PTD INSUL.
PNL.D CLAD FF/PTD 1/A650
(SIM)9/A650
(SIM)-- ● ● ● ● ● ● S9 CART BARN DOOR SECURITY CONTACT
033 033 6' - 0" 7' - 0" H FF/PTD GL-13 H FF/PTD 1/A650 9/A650 GL-13 ● ● ● ● ● ● S9 LOCKER ROOM DOOR SECURITY CONTACT036 3' - 0" 3' - 0" K PTD -- K PTD 6/A113 5/A113 ● ● ROOF ACCESS DOOR.038 038 6' - 0" 7' - 0" F FF/PTD GL-13 F FF/PTD 5/A650 9/A650 GL-13 ● ● ● ● ● ● ● S9 CONCESSION DOOR SECURITY CONTACT
CLAD● CLADCLAD● CLADWD● WDCLAD● CLADCLAD● CLADCLAD● CLADWD● WDCLAD● CLADWD● WDWD● WDWD● WDCLAD● CLADCLAD● CLADCLAD● CLADCLAD● CLADCLAD● CLADCLAD● CLADCLAD● CLADCLAD● CLADCLAD● CLADWD● WD
8/A6408/A640
8/A6408/A6408/A640
8/A640
8/A6408/A6408/A6408/A6408/A6408/A6408/A6408/A6408/A640
WD WDWD WD
WD WD3' - 0" 7' - 0"
●
●***
●●
●●
●
● 8/A640
8/A640
8/A640
8/A640
8/A640
8/A640
8/A6408/A640
8/A640
8/A640
8/A640
CASED OPENINGCASED OPENING
CASED OPENINGCASED OPENING
SS WDCLAD
WD WDWD WDWD WDCLAD CLADWD WDWD WDCLAD CLADWD WDWD WDCLAD CLADCLAD CLADWD WDWD WDWD WD-- WD-- WD
CLAD
WD WDWD WDCLAD
WD WDWD WDWD WD-- WD-- WD
STL WDCLAD
STL WDCLAD
CLAD CLAD
CLAD CLADHM HM
OVERHEAD DOOR
OVERHEAD DOOR
ABBREVIATIONS
CLAD ALUMINUM CLAD EXTERIOR/WOOD INTERIORFF FACTORY FINISHHM HOLLOW METALINSUL. PNL. INSULATED PANELPTD PAINTEDSS STAINLESS STEELSTL STEEL
ADD ALTERNATE No. 2 - DOORS 003E, 003F, 003G, 003H, 003J, 003K, AND 003L TO BE REMOVED FROM SCOPE AND REPLACED w/ OPERABLE WALL SYSTEMS. REFER TO SHEET 103 FOR ADDITIONAL INFO.
TYPE "B" TYPE "C"TYPE "A"
9"x14" CLEAR ACRYLIC WINDOW SET IN BLACK RUBBER MOLDING.
TEMPERED GLASS.
OPERABLE DBL. DOORS.
KITCHEN SWINGING DOOR.
STAINLESS STEEL
NOTES:- TEMP. INSULATED GLASS, TYP. TO ALL EXTERIOR GLASS WINDOWS & DOORS.- EQUALLY SPACED SIMULATED DIVIDED LITES (REMOVABLE) INTERIOR & EXTERIOR. OF ALL WINDOWS & DOORS.- REFER TO DOOR SCHEDULE FOR DOOR SIZES, GLAZING TYPES, FINISHES, MATERIALS, ETC.
PAINTED DOOR CASING, REFER TO DETAILS
R.O.
25"3"
R.O.
73"3"
R.O.
25"
TYPE "E" TYPE "F" TYPE "G"
SIDELITES.
24"
SIDELITES.
24"
FIXED
36"
OPERABLE
36"
FIXED
36"
DOUBLE DOORS.
72"
TYPE "D" TYPE "H"
1
A650
2
A650
9
A650
10
A650
11
A650
12
A65012
A650
12
A650
PRESENCE OF TOP FRAME TRIM BRD. VARIES WHERE FRAME MEETS TOP OF WALL CROWN MOLDING OR SOFFIT BRD. SEE EXTERIOR ELEVATIONS & RESPECTIVE SECTIONS.
GL-13 GL-13 GL-13 GL-13 GL-13 GL-13 GL-13 GL-13GL-13
GL-13GL-13 GL-13 GL-13
R.O.
10' - 9"
EQ EQ
EQ
SINGLE PANEL WOODDOOR w/ WOOD FRAME
ALUMINUM CLAD WOOD DOORw/ ALUMINUM CLAD WOOD FRAME
PROVIDE 1" INSULATED, ALUMINUM METAL PANEL IN LIEU OF GLAZING
PAINTED DOOR CASING, REFER TO DETAILS
STAINLESS STEEL DUAL ACTING IMPACT DOORS w/ WOOD FRAME
ALUMINUM CLAD / WOOD FRENCH DOORS w/ ALUMINUM CLAD / WOOD FRAME
SINGLE PANEL WOOD DOOR w/ WOOD FRAME
ALUMINUM CLAD / WOOD FRENCH DOORS w/ ALUMINUM CLAD / WOOD FRAME
ALUMINUM CLAD / WOOD FRENCH DOORS w/ ALUMINUM CLAD / WOOD FRAME
ALUMINUM CLAD / WOOD FRENCH DOORS w/ ALUMINUM CLAD / WOOD FRAME
HOLLOW METAL, INSULATED ACCESS DOOR w/ HOLLOW METAL FRAME
STEEL, INSULATED SECTIONAL DOOR w/ WOOD FRAME
GL-13GL-13GL-13GL-13 GL-13
SEE DR. SCH.
2x HEADER, SEE STRUCTURAL DWGS. FOR DTLS.
1 x 6 HEAD CASING (PTD)
7'-0
" O
PE
NIN
G.
7'-0
" O
PE
NIN
G.
5/8" GYP. BRD. EA. SIDE
CASED OPENING, PAINTED PER FIN. SCH.
HEAD DTL. "1" HEAD DTL. "3"
SEE DR. SCH.
7'-0
" O
PE
NIN
G.
HEAD DTL. "2"
WALL TYPE
VARIESSEE WALL
TYPE
VARIESSEE WALL
TYPE
VARIESSEE WALL
2x HEADER, SEE STRUCTURAL DWGS. FOR DTLS.
1 x 6 HEAD CASING (PTD)
5/8" GYP. BRD. EA. SIDE
CASED OPENING, PAINTED PER FIN. SCH.
2x HEADER, SEE STRUCTURAL DWGS. FOR DTLS.
1 x 6 HEAD CASING (PTD)
5/8" GYP. BRD. EA. SIDE
1 x WOOD FRAME w/ STOP (PTD)
EXISTING T.O. PLATE8' - 7"
8' -
0"
TYPE "J"
6"
5" 12' - 0" 5"
PROVIDE PEEL & STICK WINDOW/DOOR FLASHING AROUND PERIMETER OF OPENINGS.
1
A660
2
A660
2
A660
GL-13GL-13 GL-13
SEE DOOR SCH.
METAL DOOR THRESHOLD WITH WEATHER STRIP SEAL, FASTENED TO
FLOOR PER MFG. RECOMMENDATION..
SEE DR. SCH.
JAMB DTL. "1"
TYP
ES
VA
RIE
SS
EE
WA
LL
1 x 4 WOOD CASING (PTD), BOTH SIDES (TYP)
5/8" GYP. BRD. EA. SIDE
1 x WOOD FRAME w/ STOP (PTD)
DUAL ACTING S.S. IMPACT DOOR, MOUNTED W/ ANGLES TO WOOD FRAME (JAMB TYPE "2" ONLY). JAMB TYPE "3" IS CASED OPENING (NO DOOR)
JAMB DTL. "2" AND "3"
TYP
ES
VA
RIE
SS
EE
WA
LL
1 x 4 WOOD CASING (PTD, BOTH SIDES (TYP)
5/8" GYP. BRD. EA. SIDE
1 x WOOD FRAME (NO STOP) PTD.
TYPE "K"
3' -
0"
3"
3"
3" 3' - 0" 3"
PROVIDE PEEL & STICK WINDOW/DOOR FLASHING AROUND PERIMETER OF OPENING.
6A113
5A113
SILVER / PETRUCELLI + ASSOCIATES Drawing Title:Revised By:Date:Description:Revision:Project Title: Date:
Scale:
Drawn By:
Project Number:
Drawing Number:
Architects / Engineers / Interior DesignersH. Smith Richardson Golf Course Clubhouse2425 Morehouse HwyFairfield, CT 06824
Revised By:
June 28, 2019100% CD
Tel. 203 230 9007 Fax. 203 230 8247One Post Hill Place, New London, CT 06320
silverpetrucelli.com
3190 Whitney Avenue, Hamden, CT 06518-2340
Issued for Bid July 31, 2019
Addendum 1 August 22, 2019 As indicated A640DOOR AND FRAMEELEVATIONS
CAC
JULY 31, 2019
18.124
SCALE: 1/2" = 1'-0" A6401DOOR AND FRAME ELEVATIONS
SCALE: 1 1/2" = 1'-0" A6407INTERIOR DR. HEAD & JAMB DTLS.
SCALE: 6" = 1'-0" A6408EXTERIOR DR. THRESHOLD DETAIL.
PTD WD. TRIM.
7'-0
1/2"
R.O
.
TRIM
5/4
x 6
PTD
PV
C
5/4
PV
C E
XTE
RIO
R T
RIM
(PTD
)
TRIM
.
1 x 6
PTD
WO
OD
ME
TAL
CLA
D W
OO
D D
OO
R.
1x W
OO
D C
AS
ING
PA
INTE
D P
ER
FIN
. SC
H.
SE
T IN
TO D
OO
R F
RA
ME
1" A
LUM
INU
M IN
SU
L. P
AN
EL.
SEE CIVIL DWGS. FOR CONC. PATION WALK.
2x HEADER, SEE STRUCTURAL DWGS. FOR DTLS.
METAL DOOR THRESHOLD WITH WEATHER STRIP SEAL, FASTENED TO
FLOOR PER MFG. RECOMMENDATION..
A6408
PR
OV
IDE
PE
EL
& S
TIC
K W
IND
OW
/DO
OR
FLA
SH
ING
AR
OU
ND
P
ER
IME
TER
OF
OP
EN
ING
S.
CONT. METAL FLASHING PRE-FINISHED TO MATCH SIDING.
7' -
0 1/
2" R
.O.
PTD
. PV
C
5 1/
2"
R.O
.
1' -
6 1/
2"
TRIM
.
5 1/
2"P
TD P
VC
.
TRIM
.
1 x 6
WO
OD
TRIM
.
6 3
/4"
WO
OD
PR
OV
IDE
PE
EL
& S
TIC
K W
IND
OW
/DO
OR
FLA
SH
ING
AR
OU
ND
PE
RIM
ETE
R O
F O
PE
NIN
GS
.
5/4
" PV
C T
RIM
/CA
SIN
G (P
TD)
INS
UL.
TE
MP
ER
ED
GLA
SS
.
ME
TAL
CLA
D W
OO
D D
OO
R/S
IDE
LITE
S.
FIX
ED
TR
AN
SO
M.
INS
UL.
TE
MP
. GLA
SS
.
1x W
OO
D C
AS
ING
PA
INTE
D P
ER
FIN
. SC
H.
PTD WD. TRIM.
INS
UL.
TE
MP
ER
ED
GLA
SS
.
SEE CIVIL DWGS. FOR CONC. PATION WALK.
3/4" WOOD CASING PAINTED PER FIN. SCH.
2x HEADER, SEE STRUCTURAL DWGS. FOR DTLS.
3/4" WOOD BULLNOSE SILL, PAINTED PER FIN.
SCH.
3/4" WOOD TRIM, PAINTED PER FIN. SCH.
(3) 2x6 HEADER
1/2" PLYWD. BETWEEN 2x6 STUDS.
METAL DOOR THRESHOLD WITH WEATHER STRIP SEAL, FASTENED TO
FLOOR PER MFG. RECOMMENDATION..
A6408
CONT. METAL FLASHING PAINTED TO MATCH SIDING.
5/4" PVC EXTERIOR TRIM/CASING (PTD)
TRIM
1 x 4PTD PVC
TRIM
1 x 4PTD PVC
3/4" WOOD TRIM, PAINTED PER FIN. SCH.
R.O. VARIES.
3/4" WOOD BULLNOSE SILL, PAINTED PER FIN. SCH.
1 x 4 WOOD CASING PAINTED PER FIN. SCH., EACH SIDE
FIBER CEMENT BRD. LEAVE MFG. RECOMMENDED GAP & CAULK.
TRANSOM, INSUL. TEMP. GLASS.KING & JACK 2x
STUDS. SEE STRUCTURAL DWGS.
FOR DTLS.
1/4" WD. SHIMS
PROVIDE PEEL & STICK WINDOW/DOOR FLASHING AROUND PERIMETER OF OPENINGS.
TRIM
1 x 4PTD WD
TRIM
1 x 4PTD WD
5/4" PVC CASING/TRIM (PTD)
TRIM
1 x 4PTD PVC
TRIM
1 x 4PTD PVCR.O. VARIES.
3/4" WOOD TRIM, PAINTED PER FIN. SCH.
3/4" WOOD CASING PAINTED PER FIN. SCH.
FIBER CEMENT BRD. LEAVE MFG. RECOMMENDED GAP & CAULK.
METAL CLAD WOOD DOOR AND FRAME W/ INSUL.
TEMP. GLASS. OR INSULATED METAL PANEL
KING & JACK 2x STUDS. SEE
STRUCTURAL DWGS. FOR DTLS.
PROVIDE PEEL & STICK WINDOW/DOOR FLASHING AROUND PERIMETER OF OPENINGS.
TRIM
1 x 4PTD WD
TRIM
1 x 4PTD WD
FIXED 36" OPERABLE DOOR FIXED.
TRIM
1 x 4PTD PVC
TRIM
1 x 4PTD PVCMETAL CLAD WOOD SIDELITES W/ INSUL. TEMP. GLASS.
PROVIDE PEEL & STICK WINDOW/DOOR FLASHING AROUND PERIMETER OF OPENINGS.
5/4 PVC EXTERIOR TRIM/CASING (PTD)
3/4" WOOD CASING PAINTED PER FIN. SCH.
FIBER CEMENT BRD. LEAVE MFG. RECOMMENDED GAP & CAULK.
KING & JACK 2x STUDS. SEE
STRUCTURAL DWGS. FOR DTLS.
3/4" WOOD TRIM, PAINTED PER FIN. SCH.
3/4" WOOD TRIM, PAINTED PER FIN. SCH.
5/4" PVC. CASING (PTD)
METAL CLADDED WOOD DOORS W/ INSUL. TEMP. GLASS. METAL CLAD WOOD
SIDELITES W/ INSUL. TEMP. GLASS.
25" R.O.3"
1 x 6 WOOD CASING PAINTED PER FIN. SCH.
FIBER CEMENT BRD. LEAVE MFG. RECOMMENDED GAP & CAULK.
KING & JACK 2x STUDS. SEE
STRUCTURAL DWGS. FOR DTLS.
3/4" WOOD TRIM, PAINTED PER FIN. SCH.
5 1/2"
1 x 4 PTD PVC TRIM
TRIM
1 x 4PTD PVC
METAL CLAD WOOD SIDELITES W/ INSUL. TEMP.
GLASS.
25" R.O. 3" 73" R.O.
1 x 6 WOOD CASING PAINTED PER FIN. SCH.
3/4" WOOD TRIM, PAINTED PER FIN. SCH.
5 1/2"
7'-0
1/2"
R.O
.
PTD
PV
C
5 1/
2"1'
- 6
1/2"
R.O
.
TRIM
.
6"
WO
OD
TRIM
.
6 3
/4"
WO
OD
INS
UL.
TE
MP
ER
ED
GLA
SS
.
ME
TAL
CLA
D W
OO
D D
OO
R/S
IDE
LITE
S.
FIX
ED
TR
AN
SO
M.
INS
UL.
TE
MP
. GLA
SS
.
1x W
OO
D C
AS
ING
PA
INTE
D P
ER
FIN
. SC
H.
PTD WD. TRIM.
INS
UL.
TE
MP
ER
ED
GLA
SS
.
SEE CIVIL DWGS. FOR CONC. PATION WALK.
3/4" WOOD CASING PAINTED PER FIN. SCH.
3/4" WOOD BULLNOSE SILL, PAINTED PER FIN.
SCH.
3/4" WOOD TRIM, PAINTED PER FIN. SCH.
(3) 2x6 HEADER
3/4" PLYWD. B/ 2x6 STUDS.
METAL DOOR THRESHOLD WITH WEATHER STRIP SEAL, FASTENED TO
FLOOR PER MFG. RECOMMENDATION..
A6408
PR
OV
IDE
PE
EL
& S
TIC
K W
IND
OW
/DO
OR
FLA
SH
ING
AR
OU
ND
PE
RIM
ETE
R O
F O
PE
NIN
GS
.
5/4
PV
C T
RIM
/CA
SIN
G (P
TD)
PVC. CROWN MOLDING PROFILE. (PTD)
2x HEADER, SEE STRUCTURAL DWGS.
FOR DTLS.
CROWN.
5 1/4"1 1/4"
5/4" WD. BLOCKING.
7'-0
1/2"
R.O
.5
1/2"
GL-
14 G
LAZI
NG
.
1' -
6 1/
2" R
.O.
TRIM
.
5/4
x 6
PTD
PV
C
TRIM
.
6 3
/4"
WO
OD
PR
OV
IDE
PE
EL
& S
TIC
K W
IND
OW
/DO
OR
FLA
SH
ING
AR
OU
ND
PE
RIM
ETE
R O
F O
PE
NIN
GS
.
5/4
" PV
C T
RIM
/CA
SIN
G (P
TD)
INS
UL.
TE
MP
ER
ED
GLA
SS
.
ME
TAL
CLA
D W
OO
D D
OO
R/S
IDE
LITE
S.
FIX
ED
TR
AN
SO
M.
INS
UL.
SP
AN
DR
EL
GLA
SS
.
1x W
OO
D C
AS
ING
PA
INTE
D P
ER
FIN
. SC
H.
PTD WD. TRIM.
INS
UL.
TE
MP
ER
ED
GLA
SS
.
SEE CIVIL DWGS. FOR CONC. PATION WALK.
(3) 2x6 HEADER
3/4" PLYWD. B/ 2x6 STUDS.
METAL DOOR THRESHOLD WITH WEATHER STRIP SEAL, FASTENED TO
FLOOR PER MFG. RECOMMENDATION..
A6408
SEE RCP. FOR CLNG. DTLS.
2X BLOCKING AS REQ.
2x HEADER, SEE STRUCTURAL DWGS. FOR DTLS.
CONT. METAL FLASHING PAINTED TO MATCH SIDING.
5/8" GYPSUM BOARD (PTD),EXTEND PAST CEILING AND LEAVE GAP FOR VENTILATION OF WINDOW CAVITY
PTD WD. TRIM.
7'-0
1/2"
R.O
.
TRIM
5/4
x 6
PTD
WD
1x W
OO
D C
AS
ING
PA
INTE
D P
ER
FIN
. SC
H.
TRIM
.
1 x 6
PTD
WO
OD
WO
OD
DO
OR
.
1x W
OO
D C
AS
ING
PA
INTE
D P
ER
FIN
. SC
H.
2x HEADER, (WALL TYPES VARY)REFER TO ARCH. AND STRUCTURAL
5/8" GYP. BD (PTD) EACH SIDE
FINISH FLOOR
7' -
0 1/
2" R
.O.
TRIM
1 x 6
PTD
. WD
R.O
.
1' -
6 1/
2"
TRIM
.
1 x 6
PTD
WD
TRIM
.
1 x 6
WO
OD
TRIM
.
6 3
/4"
WO
OD
1x W
OO
D C
AS
ING
PA
INTE
D P
ER
FIN
. SC
H.
TEM
PE
RE
D G
LAS
S.
WO
OD
DO
OR
/SID
ELI
TES
.FI
XE
D T
RA
NS
OM
1x W
OO
D C
AS
ING
PA
INTE
D P
ER
FIN
. SC
H.
PTD WD. TRIM.
TEM
PE
RE
D G
LAS
S.
5/8" GYP. BD (PTD) EACH SIDE
2x HEADER, SEE STRUCTURAL DWGS. FOR DTLS.
3/4" WOOD BULLNOSE SILL, PAINTED PER FIN.
SCH.
3/4" WOOD TRIM, PAINTED PER FIN. SCH.
WD 2x6 HEADER(WALL TYPES VARY)
REFER TO ARCH. AND STRUCTURAL
1/2" PLYWD. BETWEEN 2x6 STUDS.
FINISH FLOOR
TRIM
1 x 4PTD WD
TRIM
1 x 4PTD WD
TRIM
1 x 4PTD WD
TRIM
1 x 4PTD WDR.O. VARIES.
3/4" WOOD TRIM, PAINTED PER FIN. SCH.
3/4" WOOD CASING PAINTED PER FIN. SCH.
WOOD DOOR AND FRAME W/ TEMP. GLASS.KING & JACK 2x
STUDS. WALL TYPE VARIES, REFER TO
ARCH AND STRUCTURAL DWGS.
FOR DTLS.
5/8" GYP. BD (PTD), EACH SIDE
SILVER / PETRUCELLI + ASSOCIATES Drawing Title:Revised By:Date:Description:Revision:Project Title: Date:
Scale:
Drawn By:
Project Number:
Drawing Number:
Architects / Engineers / Interior DesignersH. Smith Richardson Golf Course Clubhouse2425 Morehouse HwyFairfield, CT 06824
Revised By:
June 28, 2019100% CD
Tel. 203 230 9007 Fax. 203 230 8247One Post Hill Place, New London, CT 06320
silverpetrucelli.com
3190 Whitney Avenue, Hamden, CT 06518-2340
Issued for Bid July 31, 2019
Addendum 1 August 22, 2019 1 1/2" = 1'-0" A650DOOR DETAILS
CAC
JULY 31, 2019
18.124
SCALE: 1 1/2" = 1'-0" A6501EXTERIOR DOOR VERT. DTL. "1"
SCALE: 1 1/2" = 1'-0" A6502EXTERIOR DOOR VERT. DTL. "2"
SCALE: 1 1/2" = 1'-0" A6504NOT USED
SCALE: 1 1/2" = 1'-0" A65012EXTERIOR TRANSOM JAMB. DTL. "1"
SCALE: 1 1/2" = 1'-0" A6509EXTERIOR DOOR JAMB DTL. "1"
SCALE: 1 1/2" = 1'-0" A65010EXTERIOR DOOR JAMB DTL. "2"
SCALE: 1 1/2" = 1'-0" A65011EXTERIOR DOOR JAMB DTL. "3"
SCALE: 1 1/2" = 1'-0" A6505EXTERIOR DOOR VERT. DTL. "5"
SCALE: 1 1/2" = 1'-0" A6503EXTERIOR DOOR VERT. DTL. "3"
SCALE: 1 1/2" = 1'-0" A6507INTERIOR DOOR VERT. DTL. "2"
SCALE: 1 1/2" = 1'-0" A6506INTERIOR DOOR VERT. DTL. "1"
SCALE: 1 1/2" = 1'-0" A6508INTERIOR DOOR JAMB DTL. "1"
WOMEN
S2TYPE S3TYPE S4TYPES1TYPE NOT USED S9TYPES8TYPES5TYPE S6TYPE
6"
9"
6"
EQ
.E
Q.
5"
4 1/
2"
MEN
9"
6"
EQ
.E
Q.
5"
6"
4 1/
2"
UNISEX
4 1/
2"
9"
6"
EQ
.4
"E
Q.
9"
NOSMOKING
MAXIMUMOCCUPANCY
NOT TOEXCEED XXX
PERSONS CO DETECTORS LOCATED INSIDE
THIS SPACE EXIT
8"
4"
6"
9"
6"
EQ
.4
3/4
"E
Q.
6"
9"
6"
ROOM NAME
6"
3"
SEE ELECTRICAL DRAWINGS FOR ALL ILLUMINATED SIGNAGE
9"
6"
PROVIDE AT DINING AND GRILL ROOMS. PROVIDE (4) SIGNS - COORDINATE LOCATIONS w/ OWNER
PROVIDE AT ALL CO DETECTOR LOCATIONS
REFER TO DOOR SCHEDULE FOR LOCATIONS
REFER TO DOOR SCHEDULE FOR LOCATIONS
REFER TO DOOR SCHEDULE FOR LOCATIONS
REFER TO DOOR SCHEDULE FOR LOCATIONS
REFER TO DOOR SCHEDULE FOR LOCATIONS
WOMEN
COLOR COMBINATION BETWEENTEXT, SYMBOLS AND BACKGROUNDSHALL BE CONTRASTING ANDSELECTED BY THE ARCHITECT.
SILICONE ADHESIVE TOATTACH TO WALL, TYPICAL
1/32" MIN. RAISED INTERNATIONALSYMBOL OF ACCESSIBILITY AND PICTOGRAM, TYPICAL.
1/32" MIN. RAISED GRADE 2 BRAILLE, FOR INFORMATION ONLY. COORDINATE ACTUAL BRAILLE LETTERING FOR EACH SIGN.
1/32" MIN. RAISED SANS SERIFCHARACTERS, 5/8" HIGH, MIN.PROVIDE SECOND LINE OF TEXTAND VARY LETTER SIZES AS REQUIRED. SEE DOOR SCHEDULE AND OTHER DRAWINGS FOR TEXT AND LOCATION.
CLCENTER PICTOGRAMSAND TEXT, TYPICALEQ EQ
3/8
"
BOTTOM OFBRAILLE
EXIT
LC
LATCH SIDE
HINGE SIDE
TYPICAL SIGN, SEE TYPE REQUIRED AS DESIGNATED BYDOOR SCHEDULE OR OTHER DRAWINGS.
NOTE: AT DOUBLE DOORS MOUNT ON INACTIVE LEAF. WHEN BOTH LEAVES ARE ACTIVE MOUNT ON RIGHT SIDE ON WALL.
FINISH FLOOR
ILLUMINATED EXIT SIGN AT EXIT DOORS,IN TAMPER PROOF HOUSING SEE ELECTRICAL DRAWINGS.
ILLUMINATED EXIT SIGN AT EXIT DOORS(ASSEMBLY USE), SOME MOUNTED ON DOOR SEE ELECTRICAL DRAWINGS.
BO
TTO
M O
F B
RA
ILLE
.
48
" MIN
.
9"
NOTE: TACTILE SIGNAGE MOUNTED AT 48" MIN. AFF TO BASELINE OF BRAILLE AND 60" MAX. AFF TO BASELINE OF THE HIGHEST TACTILE CHARACTER PER ICC/ANSI A117.1-MOST CURRENT.
EXIT EXIT
4"
EXIT
8"
LC
TYPICAL SIGN, SEE TYPE REQUIRED AS DESIGNATED BY DOOR SCHEDULE OR OTHER DRAWINGS.
9"
NOTE:TACTILE SIGNAGE MOUNTED AT 48" MIN. AFF TO BASELINE OF BRAILLE AND 60" MAX. AFF TO BASELINE OF THE HIGHEST TACTILE CHARACTER PER ICC/ANSI A117.1-MOST CURRENT.
LATCH SIDE
HINGE SIDE
FINISH FLOOR
NOTE: AT DOUBLE DOORS MOUNT ON INACTIVE LEAF. WHEN BOTH LEAVES ARE ACTIVE MOUNT ON RIGHT SIDE ON WALL.
EXIT
BO
TTO
M O
F B
RA
ILLE
.
48
" MIN
.
SILVER / PETRUCELLI + ASSOCIATES Drawing Title:Revised By:Date:Description:Revision:Project Title: Date:
Scale:
Drawn By:
Project Number:
Drawing Number:
Architects / Engineers / Interior DesignersH. Smith Richardson Golf Course Clubhouse2425 Morehouse HwyFairfield, CT 06824
Revised By:
June 28, 2019100% CD
Tel. 203 230 9007 Fax. 203 230 8247One Post Hill Place, New London, CT 06320
silverpetrucelli.com
3190 Whitney Avenue, Hamden, CT 06518-2340
Issued for Bid July 31, 2019
Addendum 1 August 22, 2019 As indicated A920SIGNAGE DETAILS
CAC
JULY 31, 2019
18.124
SCALE: 3" = 1'-0" A9201SIGNAGE DETAILS
SCALE: 6" = 1'-0" A9202TYPICAL SIGN DETAIL
SCALE: 1/2" = 1'-0" A9203TYP. EXIT SIGN MOUNTING DTL.
SCALE: 1/2" = 1'-0" A9204TYP. SIGN MOUNTING DTL.