Upload
leque
View
220
Download
0
Embed Size (px)
Citation preview
Beware of fire door troubleWatch for latching and label deficiencies
In the September Healthcare Life Safety Compli-
ance, we wrote about fire barriers as a fundamental meth-
od of protecting facilities.
Fire barriers enclose a room, stairwell, or other space
with fire-rated construction. They also separate build-
ings of different construction types (e.g., a wall between a
hospital and an attached medical office building). Section
8.2.3 in the Life Safety Code® (LSC) runs down the general
provisions for fire barriers.
One concern not addressed in our previous article is
fire doors, which protect openings within fire barriers.
These doors generally must:
Be installed and maintained in accordance with NFPA
80, Fire Doors and Fire Windows
Be self- or automatic-closing and self-latching
Have a fire protection rating as outlined in 8.2.3.2.3.1
of the LSC
Feature a legible label on the door frame
➤
➤
➤
➤
The need for a label isn’t merely for formality’s sake,
said Keith Pardoe, DAHC, CDC, director of education
and certification at the Door and Hardware Institute in
Chantilly, VA.
“Labels on doors and frames contain a lot of informa-
tion,” said Pardoe,
who spoke at the
NFPA’s World
Safety Confer-
ence in Las Vegas
in June. Labels in-
dicate the ratings of doors, their temperature rises, and
necessary hardware for the door.
Also, without a label, the rating of a fire door is techni-
cally void, which is an issue Joint Commission (formerly
JCAHO) surveyors and other inspectors will check on.
For that reason, authorities appreciate having a label
that can easily be seen and read on a fire door, said Jeff
Turcotte, vice president at Intertek ETL SEMKO in Box-
boro, MA, who also spoke at the NFPA conference.
Doors are used and abused
The most common type of fire door you’ll find in
healthcare facilities is a swinging door with builders’
hardware attached (i.e., door knob, hinges, etc.), said
Pardoe.
And that type of door encounters constant use: Peo-
ple might open and close it 1,000 times per day, subjecting
it to constant wear and tear.
Thus, NFPA 80 requires facilities to maintain fire doors.
That’s a problem in healthcare and other industries, be-
cause contractors and facilities crews haven’t historically
installed or maintained fire doors properly, Pardoe said.
The 2000 edition of the LSC references the 1999 edi-
tion of NFPA 80; Chapter 15 in NFPA 80 discusses mainte-
nance concerns. Note that the chapter applies to new and
Without a label, the
rating of a fire door is
technically void, which is
an issue Joint Commission
surveyors will check on.
> continued on p. 2
IN THIS ISSUE
p. 4 Life safety notebookA Joint Commission engineer offers thoughts on creating a life safety committee, expanded building tours, and new notes for your Statement of Conditions.
p. 5 State criticizes hospitalMinnesota investigators found a hospital didn’t follow its own policies on preventing surgical fires, which allegedly led to a patient being burned.
p. 6 Life safety violationsThe following deficiencies were noted at a facility during inspections by the Minnesota Department of Health.
p. 9 Cracking the CodeIn this month’s column, learn about the critical requirements applicable to limited access trash and linen chutes.
p. 10 Questions & AnswersIs there a national standard for fire watch requirements other than NFPA 241?
October 2008 Vol. 10, No. 10
The newsletter to assist healthcare facility managers with fire protection and life safety
HealtHcare life Safety compliance
Page 2 Healthcare Life Safety Compliance October 2008
© 2008 HCPro, Inc. For permission to reproduce part or all of this newsletter for external distribution or use in educational packets, contact the Copyright Clearance Center at www.copyright.com or 978/750-8400.
existing door installations, Pardoe said. The 1999 edi-
tion of NFPA 80 doesn’t mandate the frequency of fire
door inspections. However, the 2007 edition of NFPA
80, which has been retitled Fire Doors and Other Opening
Protectives, requires that these doors undergo annual in-
spections and testing.
Checklist can help you inspect
The most recent edition of NFPA 80 offers the follow-
ing list of 11 items to review during fire door inspections:
Fire door < continued from p. 1
A fire door or frame is free of open holes or breaks
in its surface
Any glazing and vision light frames are intact
A door, frame, hinges, hardware, and threshold are
secure, properly aligned, and in working order
No parts of a door are missing or broken
Door clearances meet limits referenced in sections
4.8.4 and 6.3.1
The self-closing device works properly
An inactive door leaf closes before an active one
Latches work properly
Auxiliary items allow a door to operate properly
There are no field modifications to the door, which
will void the door’s label
Gaskets and edge seals are present when required
Joint Commission life safety specialists are aware of the
above objectives, and during a survey they might confirm
that a sampling of fire doors complies with NFPA 80 (the
diagram on p. 3 illustrates typical deficiencies that affect
fire doors).
Certification trend is afoot
Although NFPA 80 doesn’t require certified individuals
to conduct fire door inspections, there is some movement
to promote the benefits of certification, Turcotte said.
Intertek is among several organizations developing in-
dependent, third-party certification criteria for fire door in-
spectors. Underwriters Laboratories is also exploring fire
door inspection certification, Pardoe said. As with any cer-
tification process, door inspections through an indepen-
dent review may give authorities more confidence that a
door is indeed up to specifications.
Beyond independent certification, consider these final
two suggestions for fire door monitoring:
Make the doors part of a formal maintenance
program
Encourage staff members to report potential door
problems to the facilities department n
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
➤
Editorial Advisory Board Healthcare Life Safety Compliance
Group Publisher: Bob Croce, [email protected]
Sr. Managing Editor: Scott Wallask, [email protected],
781/639-1872, Ext. 3119
Contributing Technical Editor: James K. Lathrop
Vice President
Koffel Associates, Inc.
Niantic, CT
James R. Ambrose, PEPrincipalCode Consultants, Inc. St. Louis, MO
Frederick C. Bradley, PEPrincipalFCB Engineering Alpharetta, GA
Michael Crowley, PESenior Vice President, Engineering ManagerRolf Jensen & Associates, Inc. Houston, TX
Joshua W. Elvove, PE, CSP, FSFPEFire Protection EngineerAurora, CO
A. Richard FasanoManager, Western OfficeRussell Phillips & Associates, LLC Elk Grove, CA
Brad Keyes, CHSPSafety ConsultantThe Greeley Company Marblehead, MA
Burton Klein, PE PresidentBurton Klein Associates Newton, MA
Peter LeszczakNetwork 3 Fire Protection EngineerU.S. Department of Veterans Affairs West Haven, CT
David MohilePresidentMedical Engineering Services, Inc. Leesburg, VA
Daniel J. O’Connor, PEVice President, EngineeringSchirmer Engineering Corporation Deerfield, IL
Thomas SalamoneDirector of Healthcare EC ComplianceAKF Engineers Yonkers, NY
William Wilson, CFPSFire Safety CoordinatorWilliam Beaumont Hospitals Royal Oak, MI
Healthcare Life Safety Compliance (ISSN: 1523-7575 [print]; 1937-741X [online]) is published monthly by HCPro, Inc., 200 Hoods Lane, Marblehead, MA, 01945. Subscription rate is $289 for one year and includes unlimited telephone assistance. Single copy price is $25. Healthcare Life Safety Compliance, P.O. Box 1168, Marblehead, MA 01945. Copyright © 2008 HCPro, Inc. All rights reserved. Printed in the USA. Except where explicitly encouraged, no part of this publication may be reproduced, in any form or by any means, without prior written consent of HCPro, Inc., or the Copyright Clearance Center at 978/750-8400. Please notify us immediately if you have received an unauthorized copy. For editorial comments or questions or for technical support with questions about life safety compliance, call 781/639-1872 or fax 781/639-2982. For renewal or subscription information, call customer service at 800/650-6787, fax: 800/639-8511, or e-mail: [email protected]. Occasionally, we make our sub-scriber list available to selected companies/vendors. If you do not wish to be included on this mailing list, please write to the marketing department at the address above. Opinions expressed are not necessarily those of HLSC. Mention of products and services does not constitute endorsement. Advice given is general and based on National Fire Protection Association codes and not based on local building or fire codes. No warranty as to the suitability of the information is expressed or implied. Infor-mation should not be construed as engineering advice specific to your facility and should not be acted upon without consulting a licensed engineer, architect, or other suitable professional. Final acceptability of such information and interpretations will always rest with the authority having jurisdiction, which may differ from that offered in the newsletter or otherwise. Advisory Board members are not responsible for information and opinions that are not their own.
October 2008 Healthcare Life Safety Compliance Page �
© 2008 HCPro, Inc. For permission to reproduce part or all of this newsletter for external distribution or use in educational packets, contact the Copyright Clearance Center at www.copyright.com or 978/750-8400.
Typical deficiencies affecting fire door performance
This diagram illustrates common deficiencies found on or near fire doors.
Improper gaps around the perimeter
of a door in its closed position
Open holes from old
hardware that has
been removed
Door latches that are
missing or don’t work
properly
Fire exit hardware
installed on a door
that isn’t labeled for
this hardware
A door propped open for
convenience
Painted over or missing fire door labels
Other potential deficiencies for fire doors include the following:
Improperly adjusted door closer
Auxiliary hardware (e.g., deadbolt) that interferes with a door’s function
Area surrounding a door assembly blocked by furniture, equipment, or boxes
Missing or incorrect fasteners, which could affect hardware function
Bottom flush bolts that don’t project a ½ inch into a strike plate
➤
➤
➤
➤
➤
Sources: Keith Pardoe, DAHC, CDC, director of education and certification at the Door and Hardware Institute, Chantilly, VA, and Fire
Safety in Healthcare Facilities (2000 edition), published by the NFPA. Illustration by HCPro, Inc.
Page � Healthcare Life Safety Compliance October 2008
© 2008 HCPro, Inc. For permission to reproduce part or all of this newsletter for external distribution or use in educational packets, contact the Copyright Clearance Center at www.copyright.com or 978/750-8400.
Life safety notebook
Consider forming a life safety committee soonEditor’s note: We culled the following notebook items from
presentations by George Mills, FASHE, CEM, CHFM, senior
engineer at The Joint Commission, who spoke at the NFPA’s
World Safety Conference in June in Las Vegas and the Ameri-
can Society for Healthcare Engineering’s annual conference in
July in National Harbor, MD.
New committee idea raised
With the new life safety standards coming on January
1, 2009, it might be a good idea for facilities to take those
concerns beyond their traditional safety committees.
Mills suggested facilities establish a life safety commit-
tee to emphasize the new standards.
Members of the life safety committee would ideally
interact with the safety committee and the emergency
management committee (if one exists), he added.
However, The Joint Commission (formerly JCAHO)
doesn’t require a life safety committee.
Building tours might expand again
Mills proposed to Joint Commission leaders that hos-
pitals with 1.3 million square ft. or more of inpatient
area host life safety specialists for three days.
Currently, life safety specialists use the following
schedule:
Two days for hospitals with 750,000 square ft. or
more of inpatient area
One day for hospitals with less than 750,000 square
ft. of inpatient area
The change to three-day life safety tours could come
as early as this year if the plan is accepted, Mills said.
New mandates bookmarked for 2010
When The Joint Commission published its 2009 stan-
dards, its long-standing intent was to avoid complicating
the changes by adding a variety of new requirements. That
makes 2010 the next year new mandates will come into
➤
➤
play. One of the topics up for discussion in 2010 is all
unannounced fire drills, Mills said. Currently, under
EC.5.30 (which will become EC.02.03.03 in 2009), fa-
cilities must conduct at least half of their drills unan-
nounced, meaning participants won’t be aware of the
exercises ahead of time.
If The Joint Commission moves to all unannounced
drills, it will be more in line with rules set forth by the
Centers for Medicare & Medicaid Services, Mills added.
BBI now notes state actions
Be sure to note a new section on the electronic State-
ment of Conditions’ basic building information (BBI) that
tracks whether a state or local government has imposed
life safety restrictions on your facility.
For example, during lengthy droughts, states might
ask facilities to forgo required flow tests for fire pumps,
Mills said.
The BBI now asks facilities managers to note any state
restrictions, and managers must explain these restrictions
in detail in the BBI’s additional comments section.
When a state or local government lifts a restriction, fa-
cilities should strive to complete any missed testing within
30 days or at the scheduled test frequency if that occurs
sooner than 30 days, Mills said.
Old firestopping needs a close eye
Facilities can continue to use older firestopping
material (e.g., mineral wool) to seal fire and smoke
barrier penetrations as long as the material remains
undisturbed.
Mineral wool isn’t a current firestopping techno-
logy, but if it’s intact and in good condition, it still
works, Mills said.
However, if mineral wool is removed or otherwise
in poor shape, facilities crews or contractors need to
fill the penetration with a current, approved firestop-
ping material (e.g., caulking). n
October 2008 Healthcare Life Safety Compliance Page �
© 2008 HCPro, Inc. For permission to reproduce part or all of this newsletter for external distribution or use in educational packets, contact the Copyright Clearance Center at www.copyright.com or 978/750-8400.
State rebukes hospital about burned surgical patientStaff members failed to follow cautery and draping policies
Minnesota’s Department of Health found a hospital
didn’t follow its own policies on preventing surgical fires,
which allegedly led to a patient being burned during
surgery.
On June 24, a physician at Abbott Northwestern Hos-
pital in Minneapolis was preparing to put a pacemaker in
the patient’s chest and was using a cautery device. The
patient was under conscious sedation.
Flames appeared, burning the drapes, nasal cannula,
and the patient’s lip, nose, and left shoulder, according
to an investigation report provided by the state. Surgical
team members quickly removed the drapes and cannula
and extinguished the fire.
The physician completed the procedure, and the pa-
tient was subsequently transferred to the ICU before
eventually being released.
The state concluded the following:
The surgical team failed to follow Abbott Northwest-
ern’s surgical fire prevention plan by not properly
draping the patient to allow oxygen to vent away
from the patient’s face
The team didn’t adhere to the facility’s electrocautery
policy, which calls for placing cautery devices in hol-
sters when not in use during surgery
➤
➤
“It is not within the scope of our work to determine
the cause of the fire, so we did not determine whether
the cauterizer provided the heat that started it,” says
Darcy Miner, director of compliance monitoring at the
Minnesota Department of Health. “We did note, however,
that hospital procedures were to holster the cauterizer
when not in use, and this was not done each time.”
The root of surgical fires is constant, as they require:
A fuel (e.g., draping material, gauze, or plastic)
Heat (e.g., from a cautery device or laser)
An oxidizer (e.g., pooled oxygen)
Oxygen doesn’t burn, but at certain concentrations
it promotes burning and can contribute to surgical fires.
“While we do not yet know definitively the cause of
this incident, it appears likely to be related to oxygen
pooling and [then] accelerating a spark from the elec-
tocautery equipment,” according to a statement from
Abbott Northwestern provided by Timothy Burke, PR
manager. Involved staff members received refresher ed-
ucation about preventing surgical fires, and the hospital
has stopped performing pacemaker procedures in the op-
erating room in question until better draping equipment
can be purchased. n
➤
➤
➤
Cause of a bassinet fire still undetermined
The investigation continues into a bassinet fire that in-
jured a newborn in January.
The infant was in an open-topped bassinet under a warm-
er and was using an oxygen hood when something ignited.
Nurses attending to the infant quickly extinguished the flames.
The March Healthcare Life Safety Compliance covered
the incident in detail.
The hospital hired ECRI Institute of Plymouth Meeting, PA,
a nationally known healthcare research firm, to look into
the causes of the fire. ECRI Institute is still reviewing the fire
and digging through past records of bassinet and warmer
incidents.
The infant survived the fire but suffered burns of varying
degrees on 17% of his body, according to a report provided
by the Minnesota Department of Health, which also investi-
gated the incident.
The state didn’t reach any conclusions about how the fire
started and it found the facility properly completed preven-
tive maintenance on the equipment prior to the incident.
State investigators took a full tour of the building during
the inspection and found several Life Safety Code® violations
(see “Life safety citations noted during a hospital inspection”
on p. 6). These violations weren’t related to the bassinet fire,
according to the report.
Page � Healthcare Life Safety Compliance October 2008
© 2008 HCPro, Inc. For permission to reproduce part or all of this newsletter for external distribution or use in educational packets, contact the Copyright Clearance Center at www.copyright.com or 978/750-8400.
Life safety citations noted during a hospital inspection
The following life safety deficiencies were noted at Mercy
Medical Center in Coon Rapids, MN, during inspections by
the Minnesota Department of Health in January and February.
The state provided this information. Mercy Medical undertook
the solutions mentioned below, which the state included in
the inspection report. Noted NFPA references come from:
NFPA 13, Installation of Sprinkler Systems
NFPA 25, Inspection, Testing, and Maintenance
of Water-Based Fire Protection Systems
➤
➤
NFPA 70, National Electrical Code
NFPA 72, National Fire Alarm Code
NFPA 99, Healthcare Facilities
Life Safety Code® (LSC)
K-tags refer to violation categories in the Centers for Med-
icare & Medicaid Services’ (CMS) Fire Safety Survey Report
(form CMS-2786). The deficiencies stem from section 482.41
of CMS’ Conditions of Participation.
➤
➤
➤
➤
Problems K-tags NFPA references Solutions from hospital
Corridor wall not smoke tight
because of the presence of a
transfer grill
K17 LSC: 19.3.6.1,
19.3.6.2.1, and
19.3.6.5 (corridor
separation and
construction)
Removed the transfer grill and repaired the wall
Two out of 63 inspected stairway
doors didn’t latch properly
K20 LSC: 8.2.5.6 and
19.3.1.1 (protection
of vertical openings)
Repaired one of the doors in question (the other
door latched when the hospital retested it)
Monitoring door latching through a building
maintenance program*
➤
➤
In three instances from February
2007 through January 2008, staff
members failed to pull the fire alarm
box or notify hospital security during
fire drills or an actual fire
K48 LSC: 19.7.1.1 (written
emergency plan)
Re-educated staff members in a birth center
about the need to pull the fire alarm and alert
security for all fires, even those quickly extinguished
Conducted a fire drill in a birth center
Held fire safety presentations before a leaders’
and employees’ forum
Required workers who didn’t attend the employ-
ees’ forum to view a DVD of the presentation
Published fire safety articles in the hospital’s
internal newsletter
Required employees to complete an electronic
training module about fire safety
Created a new exercise in the hospital’s online
annual competency training about the impor-
tance of pulling the fire alarm and alerting secu-
rity during a fire
Added a question to the fire drill debriefing form
asking whether staff members pull the fire alarm
and alert security during a fire
Began monthly audits of fire safety procedures
➤
➤
➤
➤
➤
➤
➤
➤
➤
October 2008 Healthcare Life Safety Compliance Page �
© 2008 HCPro, Inc. For permission to reproduce part or all of this newsletter for external distribution or use in educational packets, contact the Copyright Clearance Center at www.copyright.com or 978/750-8400.
Problems K-tags NFPA references Solutions from hospital
Revised new employee orientation to highlight
the importance of fire safety
Redistributed badge buddy safety cards with
information about various emergency responses
➤
➤
Day shift fire drills during the prior
12 months all occurred between
9:16 a.m. and 10:16 a.m., instead
of at varied times
K50 LSC: 19.7.1.2
(quarterly fire drills)
The 2008 fire drill schedule reflects varied times
for drills
Safety manager stressed the importance of varied
drill times to staff members during two meetings
➤
➤
A smoke detector wasn’t secured
to its base in one location
A smoke detector was improperly
placed within 3 ft. of an air diffuser
in one location
A fire alarm contractor noted four
smoke detectors had indicating
lights that didn’t work
➤
➤
➤
K52 LSC: 9.6.1.4
(fire alarm systems);
NFPA 70; NFPA 72
Attached the smoke detector to its base
Relocated the smoke detector to the required
distance from the air diffuser
Ordered and installed smoke detector indicating
lights
➤
➤
➤
Equipment in a basement blocked
a sprinkler controller for a preac-
tion system
Sprinkler was missing a deflector
in one location
A closet in a computer training
lab didn’t have a sprinkler in it
Ceiling tiles were missing in three
locations
A sprinkler hung more than
12 inches below the ceiling slab
➤
➤
➤
➤
➤
K62 LSC: 4.6.12 and 9.7.5
(sprinkler system main-
tenance and testing);
NFPA 13; NFPA 25
Cleared equipment blocking the sprinkler
controller
Monitored sprinkler access through hazard
surveillance rounds
Installed missing sprinkler deflector
Installed sprinkler in the closet
Replaced missing ceiling tiles
Corrected the distance the sprinkler hung
below the ceiling
➤
➤
➤
➤
➤
➤
Emergency generators didn’t have
manual stop switches outside the
generator room
Emergency generators didn’t have
remote alarm panels outside the
generator room
➤
➤
K106 NFPA 99 Approved a capital project request to install the
manual stop switches and remote alarm panels
Four elevators didn’t have the
required firefighter recall service
K160 LSC: 9.4.3.2
and 19.5.3
Approved a capital request to upgrade the elevators
to phase II firefighter recall service **
* The building maintenance program is a Joint Commission approach that CMS doesn’t recognize, although the program is a useful
maintenance tool.
** For more details about elevator recall requirements, see the January Healthcare Life Safety Compliance.
Page 8 Healthcare Life Safety Compliance October 2008
© 2008 HCPro, Inc. For permission to reproduce part or all of this newsletter for external distribution or use in educational packets, contact the Copyright Clearance Center at www.copyright.com or 978/750-8400.
Retrofitting sprinklers will cost nursing homes $8�� millionAffected facilities have until August 2013 to get the work done
The five-year phase-in period established by the Cen-
ters for Medicare & Medicaid Services (CMS) for nursing
homes to install sprinklers has started a clock ticking for
a variety of work, all of which will cost hundreds of mil-
lions of dollars. CMS says 2,446 of the country’s 13,391
nursing homes do not have full sprinkler protection, ei-
ther because they lack equipment outright or only have
partial sprinkler coverage.
After hinting about the publication of the long-await-
ed nursing home sprinkler regulation in a press release
in June, CMS formally released the rule on August 13
in the Federal Register.
Rundown of the CMS rule
The provisions of the regulation include the following:
All nursing homes with sprinkler protection have un-
til August 13, 2013, to retrofit such equipment into
their buildings
All nursing homes must maintain, inspect, and test
their sprinkler systems in accordance with NFPA 13,
Installation of Sprinkler Systems, and NFPA 25, Inspec-
tion, Testing, and Maintenance of Water-Based Fire Protec-
tion Systems
As of August 13, 2013, CMS will no longer require
nursing homes to install and maintain battery-operat-
ed smoke alarms in resident rooms and common ar-
eas (e.g., dining, activity, and meeting rooms)
The last bullet about smoke alarms went into effect
in 2006 only for nursing homes without sprinklers or
hardwired smoke detection systems. The provision off-
set some of the risks those facilities shouldered without
sprinkler protection.
Phase-in needed for work
CMS believes the five-year phase-in period will give
nursing homes enough time to complete the following
activities necessary for sprinkler retrofitting:
➤
➤
➤
Allocating funds to pay for the work
Hiring a sprinkler system designer and installation
contractor
Ordering and purchasing sprinkler system
components
Completing necessary permits
Installing the equipment
“A five-year phase-in period balances our dual goals
of improved fire safety and feasibility,” CMS said in the
final rule.
The work will cost affected nursing homes $846.6
million during the phase-in period (see “Nursing home
sprinkler costs” below).
Some nursing homes will have difficulty obtaining
funds for the retrofits without financial assistance, said a
spokesperson for the American Health Care Association
(AHCA), which represents nursing, assisted living, and
disabled care facilities.
AHCA is supporting proposed federal legislation to es-
tablish a low-interest loan program for nursing homes in
need of help with sprinkler installation.
Sprinkler protection in nursing homes came under
scrutiny in 2003, when nursing home fires in Hartford,
CT, and Nashville killed a total of 31 residents and raised
questions about how well protected the residents were
before the fire. n
➤
➤
➤
➤
➤
Nursing home sprinkler costs
Nursing homes that need sprinklers: 2,446
Average cost for sprinkler system installation: $7.95 per
square foot
Average cost for a 50,000-square-foot nursing home to
install a full sprinkler system: $397,500
Average cost of a quarterly sprinkler inspection: $150
Average cost of an annual sprinkler test: $250
Source: The Centers for Medicare & Medicaid Services.
➤
➤
➤
➤
➤
October 2008 Healthcare Life Safety Compliance Page �
© 2008 HCPro, Inc. For permission to reproduce part or all of this newsletter for external distribution or use in educational packets, contact the Copyright Clearance Center at www.copyright.com or 978/750-8400.
NFPA 82 sets the rules for sprinklers and ratings related to your facility’s limited access chutes
Editor’s note: Each month in this column, the staff at fire
protection consulting firm Koffel Associates, Inc., in Elkridge,
MD, clarify the code references behind commonly misunder-
stood healthcare requirements. Fire protection engineer
Sharon Gilyeat, PE, authored this installment.
Waste and linen chutes transport material to central-
ized areas for collection, processing, treatment, or disposal.
There are numerous types of chutes, but the most common
type in healthcare facilities is the limited access, gravity-
type system, which we’ll focus on. People access this type
of chute through locked chute doors or locked service
opening room doors.
Linen chutes must be of the limited access type. Waste
chutes can either be limited access or general access, which
doesn’t require a locked chute door and is typical in apart-
ment buildings.
NFPA 82, Incinerators and Waste and Linen Handling Sys-
tems and Equipment, prescribes requirements for the con-
struction and protection of chutes in buildings. Section
9.5.2 of the Life Safety Code® (LSC), 2000 edition, requires
that all newly constructed chutes comply with NFPA 82
(1999 edition). Let’s summarize the critical requirements
applicable to limited access, gravity-type chutes.
Chute diameters set by NFPA 82
To start, you can construct gravity-type chutes of un-
lined steel, refractory-lined steel, or masonry (NFPA 82,
section 3-2). Waste chutes must have at least a 24-inch in-
side diameter (NFPA 82, 3-2.2.3). However, linen chutes
can’t have an inside diameter less than 20 inches.
Properly sized chute service openings help prevent
clogging by stopping someone from shoving large waste
containers or excessive quantities of waste into the chute.
With that in mind, NFPA 82 restricts limited access, grav-
ity-type chute loading doors to two-thirds of the cross-sec-
tional area of a waste chute (NFPA 82, 3-2.4.2).
Meanwhile, NFPA 82 requires that chutes open into
fire-rated rooms. However, it can be confusing to figure
out the required protection of the chute access room. Let’s
go back to the LSC, as 18/19.5.4.3 refer you to section 8.4,
which requires access rooms to either:
Have a one-hour rating with ¾-hour opening
protection
Have sprinklers
However, there’s another section to check in the LSC:
In newly constructed healthcare occupancies, soiled linen
rooms and trash collection rooms must have one-hour-
rated construction, regardless of sprinkler protection (LSC,
18.3.2.1).
Existing soiled linen and trash rooms can be protected
like a hazardous area, with either a one-hour rating or
sprinkler protection (LSC, 19.3.2.1).
Things get even muddier. NFPA 82 is more restric-
tive than the LSC and requires the access room to have
the same rating as the chute enclosure, which means any
chute more than three stories in height needs a two-hour-
rated access room with 1 ½-hour-rated opening protec-
tion (NFPA 82, 3-2.4.3).
When two codes conflict—such as the LSC and NFPA
82 in this case—facilities should obey the more restric-
tive rules. However, the NFPA 82 technical committee is
addressing this conflict for the 2009 edition of NFPA 82,
which will reduce the required rating to one hour.
Chutes might need sprinkler protection
Chutes must discharge or terminate in a fire-rated dis-
charge room, and the discharge room must have sprinklers
(NFPA 82, 3-2.6.2). Also, chutes must have sprinklers at
the top level, lowest inlet level, and alternate floor levels
(NFPA 82, 3-2.5.1). There is an exception from sprinkler
protection for lined masonry and metal chutes and listed
medium-heat chimneys that comply with NFPA 82. n
➤
➤
&AnswersQuestions
Page 10 Healthcare Life Safety Compliance October 2008
© 2008 HCPro, Inc. For permission to reproduce part or all of this newsletter for external distribution or use in educational packets, contact the Copyright Clearance Center at www.copyright.com or 978/750-8400.
Editor’s note: Each month, Jennifer Frecker and James
K. Lathrop of fire protection consulting firm Koffel Associ-
ates, Inc., in Elkridge, MD, answer your questions about life
safety compliance. Our editorial advisory board also reviews
the Q&A column.
Tracking various code editions
Is there a list that shows which years of which codes
are being used? How would an NFPA novice locate
such a document?
See Chapter 2 of the 2000 Life Safety Code® (LSC).
That chapter lists all of the LSC’s referenced docu-
ments and their editions.
There is also additional information on other docu-
ments in Annex B of the LSC. This is useful for con-
struction projects so that you can see what additional
requirements apply when using specific editions of
the LSC.
Finally, the American Society for Healthcare Engi-
neering publishes the Fire, Electrical, and Life Safety Com-
pendium, which is also helpful (go to www.ashe.org for
more information).
Occupancy rules for family sleeping rooms
We have a family sleeping area in the wing adja-
cent to our neonatal ICU. We have 20 family
sleeping rooms that are separated from the health-
care occupancy by two-hour fire-rated construction.
We have been told that this area is required to be
surveyed under The Joint Commission’s (formerly
JCAHO) Statement of Conditions (SOC) as a residen-
tial occupancy. What suboccupancy would this fall
under, and are there any different requirements
that we need to meet?
You are correct that the area you describe requires
an SOC. You would classify the area as a hotel and
dormitory occupancy because there are 17 or more
rooms. In this case, the corridor walls must be 30-min-
ute, fire-rated construction with 20-minute, self-closing
and self-latching doors. Remember that corridors and
doors can simply be smoke resistive in smoke compart-
ments with sprinklers, but the doors must still self-close
and self-latch.
Each sleeping room also requires a smoke alarm that
will alert occupants to any smoke in the area. See Chap-
ters 28 and 29 in the LSC for additional requirements.
National provisions for fire watches
Is there a national standard for fire watch require-
ments other than NFPA 241, Safeguarding Construc-
tion, Alteration, and Demolition Operations? What is your
recommendation for how often to perform fire watch-
es, what type of documentation to keep, etc.?
No, there is nothing in writing and it is up to inter-
pretation. Some people think a fire watch means
someone sitting in the area 24/7 with the sole job of
looking for fires and eliminating possible fire scenarios.
Other people think a security officer walking through
the area every hour or so is sufficient.
If there is any hot work (e.g., welding) in an area,
it is a good idea to have someone overlooking the pro-
cess and dealing with any sparks.
On the other hand, having someone sit in an empty
construction area at 3 a.m. to ensure that there is no fire
might be excessive.
Ultimately, it is up to you to develop a definition and
procedure for fire watches, and we suggest you ask your
authorities for their interpretations.
October 2008 Healthcare Life Safety Compliance Page 11
© 2008 HCPro, Inc. For permission to reproduce part or all of this newsletter for external distribution or use in educational packets, contact the Copyright Clearance Center at www.copyright.com or 978/750-8400.
Paragraphs 9.6.1.8 and 9.7.6 set the provisions
for when fire watches are necessary. Annex notes
A.9.6.1.8 and A.9.7.6 offer further guidance about
what a person conducting a fire watch might need,
including the following:
Training in fire prevention and occupant notifica-
tion strategies
Knowing how to use a portable fire extinguisher
Understanding the fire safety risks involved with the
particular activity at hand (e.g., construction work)
Annex notes aren’t mandatory parts of the LSC, but
instead explanatory.
Xylene storage limits under NFPA ��
What is the maximum storage allowance for
xylene in a laboratory?
Paragraphs 18/19.3.2.2 of the LSC require labo-
ratories using flammable and combustible liquids
considered a severe hazard to meet NFPA 99, Health-
care Facilities (1999 edition).
Severe hazards in labs are quantities of flammable,
combustible, or hazardous materials that could sustain
a fire that would breach a one-hour fire barrier.
NFPA 99 imposes the following requirements:
Class I, II and IIIA liquids outside of safety cans and
cabinets can’t exceed 1 gal. per 100 square ft. The
total volume, including what is in safety cans and
cabinets, can’t exceed 2 gal. per 100 square ft. (See
paragraph 10-7.2.2 in NFPA 99.)
Transfers of flammable liquids from bulk stock con-
tainers must be done in flammable liquid storage
rooms meeting the requirements in NFPA 30, Flam-
mable and Combustible Liquids Code (see 10-7.3 in
NFPA 99).
Laboratories must comply with NFPA 45, Fire Pro-
tection for Laboratories Using Chemicals (see 10-1.2.1
in NFPA 99).
➤
➤
➤
➤
➤
➤
NFPA 45 (2000 edition) calls for additional require-
ments for flammable liquid handling or storage. When
dispensing from larger containers to processors or small-
er containers under 7.2.2.6, take the following actions:
When dispensing 5 gal. or less, do so under a lab
hood or within an inside storage room designed
and constructed in accordance with NFPA 30
When dispensing 5 gal. or more, do so in a separate
facility or in an inside storage room designed and
constructed in accordance with NFPA 30
Section 4-4 of NFPA 30 (2000 edition) dictates the
design requirements for an inside storage room.
There’s often confusion about whether labs should
refer to NFPA 45 or 99.
Generally, medical labs should use NFPA 99 as a
starting point for lab provisions. From there, NFPA
99 further delineates requirements in labs, including
through NFPA 45.
Editor’s note: See the March 2007 Healthcare Life
Safety Compliance for more details on the differences
between NFPA 45 and 99.
All subscribers can access our electronic archives by
logging on to www.hcpro.com. If you don’t have a user-
name or password, call our customer service center at
800/650-6787. n
➤
➤
If you have a question about life safety compliance,
fire codes and standards, or the EC, pass it along to us
and we’ll include it in one of Healthcare Life Safety
Compliance’s future “Questions & Answers” columns.
Send us your questions in writing by:
Mail to Healthcare Life Safety Compliance, 200
Hoods Lane, P.O. Box 1168, Marblehead, MA 01945
E-mail to [email protected] (include “Q&A” in the
subject line)
Fax to 781/639-2982 (send your fax to the attention
of Healthcare Life Safety Compliance)
➤
➤
➤
Send us your questions
Page 12 Healthcare Life Safety Compliance October 2008
© 2008 HCPro, Inc. For permission to reproduce part or all of this newsletter for external distribution or use in educational packets, contact the Copyright Clearance Center at www.copyright.com or 978/750-8400.
HLSC Subscriber Services Coupon Your source code: N0001
Name
Title
Organization
Address
City State ZIP
Phone Fax
E-mail address(Required for electronic subscriptions)
❏ Payment enclosed. ❏ Please bill me.❏ Please bill my organization using PO # ❏ Charge my: ❏ AmEx ❏ MasterCard ❏ VISA ❏ Discover
Signature(Required for authorization)
Card # Expires(Your credit card bill will reflect a charge to HCPro, the publisher of HLSC.)
❏ Start my subscription to HLSC immediately. Options No. of issues Cost Shipping Total
❏ Electronic 12 issues $289 (HLSCE) N/A
❏ Print & Electronic 12 issues of each $289 (HLSCPE) $24.00
Sales tax (see tax information below)*
Grand total
Order online at www.hcmarketplace.com.
Be sure to enter source code N0001 at checkout!
Mail to: HCPro, P.O. Box 1168, Marblehead, MA 01945 Tel: 800/650-6787 Fax: 800/639-8511 E-mail: [email protected] Web: www.hcmarketplace.com
For discount bulk rates, call toll-free at 888/209-6554.
*Tax InformationPlease include applicable sales tax. Electronic subscriptions are exempt. States that tax products and shipping and handling: CA, CO, CT, FL, GA, IL, IN, KY, LA, MA, MD, ME, MI, MN, MO, NC, NJ, NM, NY, OH, OK, PA, RI, SC, TN, TX, VA, VT, WA, WI, WV. State that taxes products only: AZ. Please include $27.00 for shipping to AK, HI, or PR.
Quick tip
With holidays looming, monitor decoration risksSome of you may dread the start of the fall holidays
not because you don’t enjoy them, but because these
celebrations bring with them plenty of fire safety risks.
The Life Safety Code® (LSC) and The Joint Commission
(formerly JCAHO) address this matter. Paragraph 7.1.
10.2.1 in the LSC states that no furnishings or decora-
tions can block exits, access to and from them, or their
visibility.
Also, paragraphs 18/19.7.5.4 prohibit combustible
decorations in any hospital unless they are flame-re-
tardant. An exception allows combustible decorations,
such as photographs and paintings, if they are in limit-
ed quantities that don’t create a risk of fire developing
or spreading.
Meanwhile, The Joint Commission:
Requires compliance with the LSC under EC.5.20
(which will transition to the new life safety stan-
dards in 2009)
Discusses decorations under EC.5.10, element of
performance (EP) 5
EP 5 will disappear in the 2009 EC standards, likely
because the new life safety chapter will bring up deco-
rations under LS.02.01.70, EP 1.
This is a good example of The Joint Commission elim-
inating redundant provisions in its standards in 2009.
➤
➤
Take a reasonable approach
When it comes to combustible decorations, “we don’t
want to go over the top here,” said David Hood, presi-
dent of Russell Phillips & Associates, LLC, in Fairport,
NY. Hood spoke during HCPro’s July audio conference,
“Conquer Your Next Life Safety Code® Survey.”
Hood has found that decoration policies need to
obey the LSC while also observing common sense.
For example, holiday greeting cards could clearly
catch fire if they are near a flame. However, two cards
taped to a door on a unit don’t really qualify as a risk
from combustible decorations, Hood said.
On the other hand, hanging 150 greeting cards on
a wall in a unit clearly violates the LSC because they
aren’t of limited quantity, he added.
Holiday decorations can also create the following
hazards:
Obstruction of sprinkler spray patterns
Use of electric lights or displays not approved by
a testing laboratory
Susceptibility to burning from displays that include
cut trees and wreaths, which may dry out
It also makes sense during the holidays to include
decorations on your hazard surveillance rounds. n
➤
➤
➤
Join Us in Dallas or Orlando for Upcoming Sessions of the Life Safety Code® Boot Camp – Hospital Version
Within Healthcare Life Safety Compliance’s pages, we’ve written about many life safety citations issued by the Centers for Medicare & Medicaid Services and The Joint Commission. And now, with The Joint
Commission’s new life safety standards debuting in 2009, it is more important than ever to understand the nuances of the Life Safety Code®. If you’re looking for in-depth help understanding the 2000 Life Safety Code’s provisions for healthcare occupancies, then register for one of two upcoming Life Safety Code Boot Camps:
HCProbootCamPs tm OctOber 2008
OrlandoNovember 10–12
DallasOctober 15–17
For full information about the Life Safety Code Boot Camp and to register, visit http://hcpro.com/url/1221 or call our customer service center at 877/207-4036. In either case, use source code MT74217A.
The two-and-a-half-day course agenda for the Life Safety Code Boot Camp is intensive and covers the following material:
General requirements for healthcare occupancies Why facilities use the Life Safety Code and how it ties into other industry codes Application of the Life Safety Code in healthcare occupancies Special definitions and classifications for healthcare occupancies, and mixed occupancies in healthcare Construction types and occupant load requirements Additions, conversions, and renovations
Means of egress requirements for healthcare occupancies Brief overview of means of egress components Brief overview of provisions for the number of required exits Arrangement of means of egress Provisions for lights and signs in egress routes
Protection feature requirements for healthcare occupancies Vertical opening protection Hazardous areas Interior finish Alarm, detection, and extinguishing systems Corridors Smoke compartments
Our instructors will also discuss requirements for building services, operating features, and ambulatory and business settings, and present an overview of alternative approaches to Life Safety Code requirements. n
■
■
■
■
■
■
■
■
■
■
■
■
■
■
■
1. (T) (F) The three roots of a surgical fire are fuel, heat, and the procedure.
2. (T) (F) Fire doors must have legible labels or their ratings are void.
3. (T) (F) Corridors and doors can be smoke resistive in smoke compartments with sprinklers, but the doors must still be self-closing and self-latching.
4. (T) (F) The Life Safety Code® (LSC) prohibits combustible decorations in healthcare facilities.
5. (T) (F) NFPA 80, Fire Doors and Fire Windows, requires individuals who inspect fire doors to hold certification.
6. (T) (F) Staff members participating in fire drills should pull the fire alarm box during an exercise.
7. (T) (F) In the 2009 life safety standards, The Joint Commission requires facilities to establish life safety committees.
8. (T) (F) Facilities can continue to use all older firestopping material because of a grandfather clause.
9. (T) (F) Limited access trash and linen chutes feature locked chute doors or locked service opening room doors.
10. (T) (F) Nursing homes without sprinklers have until August 2009 to retrofit this equipment.
QuizQuizHealtHcare life Safety complianceThe newsletter to assist healthcare facility managers with fire protection and life safety
Vol. 10 No. 10October 2008
Quiz questions October 2008 (Vol. 10, No. 10)
A supplement to Healthcare Life Safety Compliance
1. False. The three roots are fuel, heat, and an oxidizer.
2. True
3. True
4. False. The LSC allows combustible decorations if they are flame-retardant and in limited quantities that don’t create a risk of fire development.
5. False. NFPA 80 doesn’t require certification for individuals who inspect fire doors.
6. True
7. False. The Joint Commission doesn’t require a life safety committee, although the agency’s senior engineer suggested such a committee is a good idea.
8. False. Facilities can continue to use older firestopping material only if the material remains undisturbed and is in good condition.
9. True
10. False. Nursing homes have until August 2013 to retrofit sprinklers if they don’t already have them installed.
Quiz answers October 2008 (Vol. 10, No. 10)
Copyright © 2008 HCPro, Inc. Current subscribers to Healthcare Life Safety Compliance may copy this quiz for use at their facilities. Use by others, including those who are no longer subscribers, is a viola-tion of applicable copyright laws. ® Registered trademark, the National Fire Protection Association, Inc.