Heat Pump Test Apparatus for the Evaluation of Low Global
60
NIST Technical Note 1895 Heat Pump Test Apparatus for the Evaluation of Low Global Warming Potential Refrigerants Harrison Skye http://dx.doi.org/10.6028/NIST.TN.1895 NIST Technical Note 1895
Heat Pump Test Apparatus for the Evaluation of Low Global
Microsoft Word - MBBHP Test Apparatus Tech Note_v11.docxEvaluation
of Low Global Warming
Potential Refrigerants
Harrison Skye
Evaluation of Low Global Warming
Potential Refrigerants
Harrison Skye
Engineering Laboratory
National Institute of Standards and Technology
Willie E. May, Under Secretary of Commerce for Standards and
Technology and Director
i
Certain commercial entities, equipment, or materials may be
identified in this
document in order to describe an experimental procedure or concept
adequately.
Such identification is not intended to imply recommendation or
endorsement by the
National Institute of Standards and Technology, nor is it intended
to imply that the
entities, materials, or equipment are necessarily the best
available for the purpose.
National Institute of Standards and Technology Technical Note
1895
Natl. Inst. Stand. Technol. Tech. Note 1895, 48 pages (September
2015)
http://dx.doi.org/10.6028/NIST.TN.1895 CODEN: NTNOEF
International efforts to reduce human-induced global warming
include restrictions on the
use of chemicals with a high global warming potential (GWP). The
heating, ventilation, air-
conditioning, and refrigeration (HVAC&R) industry subsequently
faces a phasedown of many
commonly used hydrofluorocarbon (HFC) refrigerants that have a
relatively high GWP. A new
family of refrigerants known as hydrofluoroolefins (HFOs),
including their mixtures with HFCs,
show promise as replacements. The overall GWP impact of refrigerant
use includes both the
direct GWP related to inadvertent release of the fluid into the
atmosphere, as well as an indirect
GWP caused by emissions from the power source used to energize the
associated HVAC&R
equipment. In nearly all HVAC&R applications, the indirect
emissions far outweigh the direct
emissions, so the efficiency of candidate replacements must be
carefully quantified to guide the
selection of fluids that actually achieve a reduction in the
overall GWP.
A 3.4 kW (1 ton) heat pump test apparatus has been constructed and
instrumented for
measuring the cycle performance of low-GWP refrigerants; the
description of that apparatus is
the focus of this report. Details are described for the system
components, instrumentation, data
reduction, and uncertainty analysis. Results from baseline
experiments with R134a were used to
test and verify the apparatus and data reduction procedure. The
data will be used to provide a
relative comparison between the low-GWP refrigerants as quantified
by metrics including
coefficient of performance and volumetric capacity.
Future tests with low-GWP refrigerants will be compared with those
from baseline
refrigerants R134a and R410A. Additionally, the test data will be
used to verify a new NIST
heat pump modeling tool, CYCLE_D-HX, which captures both
thermodynamic and heat transfer
processes in HVAC&R equipment. Refrigerants, refrigerant
mixtures, and cycle configurations
that are difficult and/or time consuming to test can be rapidly
explored using the verified model.
iii
Acknowledgements
This apparatus was constructed by John Wamsley based on the initial
design by David
Yashar. Dr. Yashar also helped create the outline of the report,
which was valuable for keeping
the presentation of information organized and complete. I would
like to acknowledge Vance
Payne for his help in determining the operating procedures and
target operating parameters.
Patrick Goenner refined the instrumentation and collected early
sets of data while visiting as a
guest researcher from Germany. I would also like to thank Piotr
Domanski and Riccardo
Brignoli for reviewing data sets and working on the CYCLE_D-HX
model. Thanks to Mark
Kedzierski for thoughtful insight into the calibration and
uncertainty analysis for the test rig.
Tara Fortin, of the NIST Applied Chemicals and Materials Division,
performed differential
scanning calorimeter measurements of the heat transfer fluid
specific heat; these data were
critical for achieving an acceptable energy balance. Finally, I
would like to thank the reviewers
for their helpful suggestions, including Piotr Domanski and Amanda
Pertzborn at NIST, and
Steve Brown at The Catholic University of America.
iv
2.3.2.1 Operating Parameters 1 & 2: Evaporator and Condenser
Saturation
Temperature
......................................................................................................
15
2.3.2.2 Operating Parameters 3, 4, & 5: Capacity and Heat Flux
................................ 17
2.3.2.3 Operating Parameters 6 & 7: HTF-side Thermal Resistance
Ratio ................. 18
2.3.2.4 Operating Parameters 8 & 9: Subcool and Superheat
...................................... 18
2.3.2.5 Operating Parameter 10: LLSL-HX included or bypassed
.............................. 19
3 Data Analysis
..........................................................................................................................
20
3.1 Thermodynamic States
....................................................................................................
20
3.2 Thermodynamic Performance
.........................................................................................
20
3.2.4 Volumetric Capacity
................................................................................................
22
5 Conclusions and Future Work
................................................................................................
28
6 References
...............................................................................................................................
29
A.1 Symbols Used in Uncertainty Analysis
...........................................................................
31
A.2 General Remarks
.............................................................................................................
32
A.4 Thermocouples with Ice-Water Bath Compensation
...................................................... 33
A.5 Thermopiles in Heat Transfer Fluid
................................................................................
34
A.6 Evaporator Heat Transfer Fluid Specific Heat
................................................................
36
A.7 Condenser Heat Transfer Fluid Specific Heat
.................................................................
37
A.8 Evaporator and Condenser Insulation Conductance
....................................................... 37
A.9 Uncertainty Analysis Software
........................................................................................
39
A.10 Moving Window and Steady State Uncertainty
..............................................................
40
A.11 Uncertainty Results Summary
.........................................................................................
41
A.11.1 Uncertainty Results Summary: Cooling
..................................................................
41
A.11.2 Uncertainty Results Summary:
Heating...................................................................
43
Appendix C : Microfin Tube Surface Area
...................................................................................
48
vi
Figure 2-2: Pictures of MBBHP apparatus
................................................................................
6
Figure 2-3: Pictures of MBBHP compressor (a) without and (b) with
safety cage. .................. 7
Figure 2-4: Schematic showing the tube numbering convention in the
(a) condenser and (b)
evaporator.
..............................................................................................................
8
Figure 2-5: Schematics of annular heat exchanger including (a)
refrigerant tube lengths, (b)
cross section of annular heat exchanger, (c) detail cross-section
of microfin tube,
and (d) helix angle of microfins.
.............................................................................
9
Figure 2-6: Capacity and heat flux for baseline R134a tests for (a)
evaporator and (b)
condenser
..............................................................................................................
18
Figure 3-1: Temperature profile in (a) evaporator, showing
superheat and (b) condenser,
showing subcooling
..............................................................................................
23
Figure 4-1: Energy imbalance in the evaporator and condenser
............................................. 25
Figure 4-2: Heat pump cycle pressures on the (a) high pressure side
and (b) low pressure
side
........................................................................................................................
26
Figure 4-3: Performance metrics including (a) compressor power and
(b) mass flow and mass
flux
........................................................................................................................
26
Figure 4-4: Performance metrics including (a) COP, (b) capacity,
(c) volumetric capacity, and
(d) compressor isentropic and volumetric efficiency
............................................ 27
Figure 4-5: Flow regime map for microfin tube (a) evaporation and
(b) condensation .......... 28
Figure A-1: Temperature calibration for CJC compensated
thermocouples where (a) data are
divided by each of the 5 calibrations and (b) all data are
combined..................... 33
Figure A-2: Ice-water bath referenced thermocouple calibration data
..................................... 34
Figure A-3: Thermopile calibration data
..................................................................................
35
Figure A-4: Contours of thermopile (a) uncertainty and (b) relative
contribution to
uncertainty.............................................................................................................
36
Figure A-6: Specific heat of condenser HTF (water)
...............................................................
37
Figure A-7: Insulation conductance for evaporator and condenser
.......................................... 39
Figure A-8: Uncertainty in temperature due to fluctuations at
steady state for (a) evaporator
outlet and (b) evaporator inlet
...............................................................................
41
vii
Table 2-2: Refrigerant microfin tube
specifications..................................................................
11
Table 2-3: List of MBBHP instruments (SI units)
....................................................................
13
Table 2-4: List of MBBHP instruments (I-P units)
...................................................................
14
Table 2-5: List of the Control Parameters and Operating Parameters
...................................... 15
Table 2-6: Evaporator and condenser fluid temperatures for standard
rating tests ................... 17
Table 3-1: Measurements and equations used to define the
thermodynamic states .................. 20
Table A-1: Condenser & evaporator thermopile polynomial
coefficients ................................. 35
Table A-2: Evaporator HTF specific heat polynomial coefficients
........................................... 37
Table A-3: Uncertainty of refrigerant-side evaporator cooling
capacity ................................... 42
Table A-4: Uncertainty of HTF-side evaporator cooling capacity
............................................ 42
Table A-5: Uncertainty of cooling COP
....................................................................................
43
Table A-6: Uncertainty of refrigerant-side condenser heating
capacity .................................... 44
Table A-7: Uncertainty of HTF-side condenser heating
capacity.............................................. 44
Table A-8: Uncertainty of heating COP
.....................................................................................
45
viii
Nomenclature
Symbol Units Definition
A m2 Area
Atotal m2 Total combined heat transfer area from evaporator and
condenser
COPheat -- Coefficient of Performance - Heating
COPcool -- Coefficient of Performance - Cooling
Cp kJ kg-1 K-1 Specific heat
do mm Microfin tube outer diameter
di mm Microfin tube inner diameter
Dcomp m3 Compressor displacement
L m Tube length
N Hz Compressor frequency
Nf -- Number of microfins on inner circumference of refrigerant
tube
NT -- Number of heat exchanger tubes
P kPa Pressure
R K kW-1 Thermal resistance
Rtotal K kW-1 Total resistance in heat exchanger including both
fluids and tube wall
Q kW Energy transfer
,LLSL vQ kW Energy transfer in LLSL-HX, on the vapor side
,LLSL maxQ kW Maximum possible energy transfer in LLSL-HX
T °C Temperature
sf mm Spacing between microfins
s kJ kg-1 K-1 Specific entropy
SC K Condenser subcooling
SH K Evaporator superheat
VCC kJ m-3 Volumetric Cooling Capacity
VHC kJ m-3 Volumetric Heating Capacity
compW kW Compressor power, computed using enthalpy change of
refrigerant
shaftW kW Compressor power, computed using torque and speed of
driveshaft
x -- Vapor quality (mass of vapor divided by total mass of
fluid)
ix
Greek
β ° Microfin angle
ηs -- Compressor isentropic efficiency
ηv -- Compressor volumetric efficiency
τ N m Compressor shaft torque
Subscript Definition
air Air
avg Average
c Condenser
e Evaporator
out Outlet
ref Refrigerant
1 to 11 Refrigerant thermodynamic states as defined in Figure
2-1
x
ANSI American National Standards Institute
CFC Chlorofluorocarbon
COP Coefficient of Performance (W of capacity per W of electric
input)
CYCLE_D-HX A NIST heat pump cycle simulation model currently under
development.
The simulation captures both thermodynamic and transport processes
in the
cycle.
DOE Department of Energy (United States)
EER Energy Efficiency Ratio (Btu of capacity per W of electric
input)
EOS Equation of State
GWP Global Warming Potential
LLSL-HX Liquid-Line Suction-Line Heat Exchanger
MBBHP Mini Breadboard Heat Pump
NIST National Institute of Standards and Technology (United
States)
PID Proportional Integral Derivative controller
RPM Revolutions per Minute (compressor shaft)
1
1 Introduction
Concerns about the environmental impacts of global warming (i.e.,
global climate change)
are driving an effort to limit anthropogenic sources of atmospheric
pollutants that trap longwave
radiation emitted from the earth’s surface. The chlorinated- and
fluorinated-hydrocarbon
working fluids (i.e., refrigerants) employed by the heating,
ventilation, air-conditioning, and
refrigeration (HVAC&R) industry exhibit a particularly large
global warming potential (GWP)
with 100-year GWP values hundreds to thousands of times larger than
an equivalent mass of
carbon dioxide (Solomon, et al., 2007, p. 212). In the European
Union, the F-gas regulation (EU,
2014) mandates a phase-down of hydrofluorocarbons (HFCs) with high
GWP to 21 % of the
average levels from years 2009 through 2012 by 2030. The current
North American proposal
would amend the Montreal Protocol to limit HFC consumption to have
a weighted GWP of 15 %
of average levels from years 2011 through 2013 by 2036 (EPA,
2015).
Major efforts are underway to identify alternative refrigerants
with a lower GWP. Chemical
manufacturers are proposing halogenated olefins (e.g.,
hydrofluoroolefins, or HFOs), which offer
substantially lower GWP due to short atmospheric lifetimes. For
some HFOs, the lower GWP
comes at the cost of an increase in flammability. The
Air-Conditioning, Heating, and
Refrigeration Institute (AHRI) is leading a collaborative effort to
evaluate the drop-in and soft-
optimized performance of low-GWP alternatives largely consisting of
HFOs and HFO/HFC
blends (AHRI, 2015). The National Institute of Standards and
Technology (NIST) investigated
the maximum thermodynamic potential expected for working fluids by
optimizing the
parameters governing the Equations of State (EOS) (Domanski et al.,
2014). In a companion
NIST study, a coarse filter criteria was developed (based on the
atomic elements, GWP, toxicity,
flammability, critical temperature, and stability) to sift through
the 100 million chemicals
currently listed in the public-domain PubChem database for possible
low-GWP refrigerant
candidates, 1234 of which were identified (Kazakov et al., 2012).
The candidate list was further
refined to 62 by limiting the critical temperature to the range 300
K to 400 K, which is typical for
fluids in HVAC&R equipment (McLinden et al., 2014).
The remaining 62 candidates, and their mixtures, must be evaluated
using more stringent
criteria that consider detailed performance in HVAC&R
equipment. In particular, the criteria
must include the cycle efficiency of the fluid since the carbon
dioxide emissions from the power
source (i.e., “indirect emissions”) far outweighs the direct GWP
impact (i.e., the GWP from the
release of the fluid into the atmosphere) of the working fluid in
nearly all HVAC&R equipment.
A cycle modeling tool, CYCLE_D-HX, is being developed at NIST to
evaluate the efficiency of
low-GWP refrigerants and refrigerant mixtures. The model expands
upon the thermodynamic
considerations from CYCLE_D (Brown et al., 2011) by including
transport phenomena. In this
way, appropriate penalties can be applied to refrigerants whose
thermodynamic properties are
favorable but exhibit poor performance in HVAC&R systems
because of large pressure drops or
poor heat transfer. The consideration of transport processes
represents a lesson learned from the
previous effort to find replacements for chlorofluorocarbon (CFC)
fluids that were found to
cause stratospheric ozone destruction. R410A, the dominant
replacement for the CFC R22, was
initially considered to be a significantly inferior replacement
based on thermodynamic properties
alone. However, later practice showed that the lower pressure drop
(due to high operating
pressure) and superior heat transfer of R410A could be exploited
with optimized heat exchangers
to yield performance competitive with R22. Including transport
processes also allows for the
2
optimization of mass flux; the number of parallel heat exchanger
tube circuits are adjusted to
balance performance enhancement/degradation of increased heat
transfer/pressure drop with
higher mass flux. The more sophisticated capabilities of the new
model will allow for more
accurate identification of optimal low-GWP fluids using
computational methods.
A heat pump test apparatus has been constructed for the purpose of
generating cycle
performance data to compare low-GWP refrigerants and to tune and
verify the new NIST model;
that test apparatus is the focus of this report. The apparatus is
highly configurable, which allows
the system to operate with a wide variety of working fluids as if
tailored to each one.
Specifically, the apparatus features a variable-speed compressor,
variable-area heat exchangers,
and a manually adjusted throttle valve. These adjustable components
allow for operation at
constant capacity per total combined evaporator and condenser
conductance ( )totalQ UA across
all test fluids, a condition required for equitable comparison of
refrigerants (as well as fixed heat
transfer fluid inlet/outlet temperatures) (McLinden et al., 1987).
In practice, it is difficult to hold
totalQ UA constant because the conductance depends on the
refrigerant side heat transfer
coefficient, which changes for each fluid and operating condition.
Rather, a fixed capacity per
total heat exchanger area ( totalQ A ) is used as a close
approximation. For example, with a fixed
heat exchanger area, totalQ A is held constant from R134a (low
volumetric capacity) to R410A
(high volumetric capacity) by decreasing the compressor speed. If
adjustment of compressor
speed is insufficient to maintain constant totalQ A between
refrigerants, the heat exchanger area
can be adjusted as well. The adjustability and relatively small
capacity of 1.7 kW to 3.5 kW (0.5
ton to 1 ton) provide the etymology for the apparatus name, the
Mini Breadboard Heat Pump
(MBBHP). Measurements of cycle performance with legacy high-GWP
HFCs and novel low-
GWP fluids in the MBBHP will provide a rich data set to test the
predictive capability of the new
NIST model. This report describes the construction and operation of
the test apparatus, the data analysis
used to quantify performance, an uncertainty analysis of the
performance metrics, and baseline
and validation results using refrigerant R134a.
3
2.1 Components
The test apparatus, shown in Figure 2-1 through Figure 2-3, was
designed to emulate
refrigerant-side operating conditions of typical HVAC&R
equipment. (Figure B-1 and Figure B-
2 in Appendix B show the instrument numbering convention used in
the raw data files). The rig
design is partially based on one used in a previous NIST effort to
investigate alternatives to
CFCs (Pannock et al., 1991). The refrigerant circuit includes a
variable-speed compressor
powered by an electric motor and inverter, where the speed controls
cooling/heating capacity.
The evaporator and condenser, shown in detail in Figure 2-4 and
Figure 2-5 (a) and (b), are
single-circuit (i.e., there are no parallel tube branches) annular
heat exchangers where the
refrigerant is on the inner tube and the liquid heat transfer fluid
(HTF) is in the annular space.
As shown in Figure 2-5(c), the refrigerant tube is smooth on the
outside and enhanced with rifled
microfins on the inside. The size of the heat exchangers can be
adjusted by changing the number
of active refrigerant tubes; the valves on the side of the heat
exchanger allow for up to 10 (in
increments of 2) of the 20 refrigerant tubes to be bypassed (this
section of the rig is referred to as
the “bypass valve header”). When operating these bypass valves,
care is taken to avoid trapping
subcooled liquid in a closed section; a section completely filled
with subcooled liquid will
experience a catastrophic increase in pressure if the temperature
rises enough to vaporize the
refrigerant. A liquid-line suction-line heat exchanger (LLSL-HX)
can be included or bypassed
as needed. Each of three heat exchangers (evaporator, condenser and
LLSL-HX) are arranged in
counterflow configuration. Two sizes of manually controlled
Vernier-handled needle valves are
used to throttle the refrigerant and can be used individually or in
tandem; the needle valve sizes
were selected using a correlation for short tubes (Kim et al.,
2005). A filter-dryer is used to
control contaminants, and an oil separator is used to ensure proper
oil return to the compressor
and to minimize oil circulation in the heat exchangers. The system
refrigerant charge is adjusted
using two Shrader access valves, where refrigerant is removed from
or added to the
liquid/suction line valves, respectively. Two 40 W heaters preheat
the compressor before startup
to avoid foam in the oil (the heaters are turned off after the
discharge temperature has warmed to
about 60 °C). A safety cage was constructed around the compressor
because during cooling tests
with high pressure fluids such as R410A, the compressor will be
operated slightly above the
manufacturer’s specified maximum pressure of 2600 kPa (363 psig).
Finally, a series of sight
glasses provide visual confirmation of fully subcooled liquid
exiting the condenser, vapor only
(i.e., no liquid) entering the compressor suction port, proper oil
level in the compressor, and
proper oil return from the oil separator. Detailed component
specifications are listed in Table
2-1. The microfin tube parameters are shown in Figure 2-5 and Table
2-2, and Appendix C
shows how the microfin surface area was calculated.
The HTF circuits include a water heater/chiller to respectively
control the evaporator and
condenser HTF inlet temperatures, where the heater/chiller contains
a pump for circulating the
fluid. The evaporator HTF is a potassium formate and water solution
with freeze protection
to -40 °C (-40 °F), whereas water is used for the HTF in the
condenser. Flow control provided
by three valves in each HTF circuit allows for a wide range of
flowrates: two in-line valves are
used where the larger/smaller (gate/needle) valve provides
gross/fine flow adjustment and the
third valve bypasses the heater (or chiller) for flow and pressure
control. Air bubbles in the
condenser HTF circuit are controlled by drawing from the bottom of
the vented chiller reservoir
4
tank. The evaporator HTF circuit is pressurized with an expansion
tank, so air bubbles can be
removed by venting trapped air from local high spots using Shrader
valves. Experience
operating the test apparatus has shown that the vented reservoir
tank (in the chiller) is a superior
solution for minimizing air bubbles. The temperature of the fluid
delivered to the heat
exchangers is regulated using proportional-integral-derivative
(PID) controllers.
5
6
7
(a) (b)
Figure 2-3: Pictures of MBBHP compressor (a) without and (b) with
safety cage.
8
(a) (b)
Figure 2-4: Schematic showing the tube numbering convention in the
(a) condenser
and (b) evaporator.
(b) (c) (d)
Figure 2-5: Schematics of annular heat exchanger including (a)
refrigerant tube
lengths, (b) cross section of annular heat exchanger, (c) detail
cross-
section of microfin tube, and (d) helix angle of microfins.
10
Component Characteristics
Compressor Type: Reciprocating
(500 RPM to 4000 RPM)
Displacement rate: 1.31 m3h-1 to 10.81 m3h-1
Displacement: 7.165 cm3
Electric motor Maximum power: 3.73 kW (5 hp)
Expansion tank (HTF) Size: 19 liter (5 gallon)
Filter (HTF) Filter size: 50 µm
Filter-dryer (refrig.) Line size: 9.5 mm (0.375 in)
Inverter Voltage: 230 VAC, 3-phase
Maximum power: 3.73 kW (5 hp)
Heater Heating capacity: 10 kW (2.8 ton)
Heat exchanger
Tube active length: 560 mm (22 in)
Return bend length: 83 mm (3.25 in)
Outer tube ID: 25.4 mm (1 in)
Outer tube OD: 26.8 mm (1.125 in)
Outer tube material: Copper
Liquid-line suction-line heat
Type: Corrugated (liquid side)
Orifice:
Flow coeff. (Cv): 0.73*
Height: 356 mm (14 in)
Capacity: 10 to 17 kW (3 to 5 ton)
Pressure relief valve Cracking pressure: 800 psig
*Note: valve orifice sizes and flow coefficients (Cv) can vary
between 0 and the listed
maximum values
Parameter Symbol Value Uncertainty
Inside diameter di 8.46 mm (0.333 in) Unknown
Outside diameter do 9.52 mm (0.375 in) ±0.050 mm (±0.002 in)
Bottom wall thickness tb 0.33 mm (0.013 in) ±0.025 mm (±0.001
in)
Fin height e 0.20 mm (0.008 in) ±0.025 mm (±0.001 in)
Spacing between fins sf 0.22 mm (0.009 in) Unknown
Number of fins Nf 60 --
Fin angle β 60° Unknown
Helix angle α 18° 2°
Internal surface area
Material Copper
2.2 Instrumentation
Refrigerant-side instrumentation is selected to capture the key
thermodynamic state points in
the cycle. Specifications for the instruments (including instrument
uncertainty) in both the
refrigerant and HTF circuits are listed in Table 2-3 (Table 2-4
shows I-P units). The pressure
transducers and in-stream thermocouple probes are numbered in
Figure 2-1 according to the
eleven states computed in Section 3.1; the thermodynamic state
number convention is also
consistent with that used in the new CYCLE_D-HX model. The
thermocouple probes are
referenced to a cold junction in an ice-water bath. Differential
pressure transducers quantify the
pressure drop in the condenser, evaporator, and suction line. The
location of the heat exchanger
pressure taps has been selected at the bottom of the bypass valve
header, where the pressure is
equal to that of the refrigerant leaving the heat exchanger
regardless of how many tubes are
bypassed. A coriolis flowmeter measures the refrigerant mass flow
and density, and provides
confirmation of fully subcooled liquid in the liquid line (a
two-phase mixture will exhibit large
oscillations in measured flowrate). The compressor shaft power is
captured by the in-line torque
meter and tachometer.
On the HTF fluid side, energy transfers are measured in the
evaporator and condenser to
provide verification of the refrigerant-side calculations. The mass
flow and temperature
difference in the heat exchangers are measured with coriolis meters
and thermopiles (in
thermowells), which are combined with the fluid heat capacity to
compute energy transfer.
Thermocouples inserted into the thermowells with the thermopiles
provide the measure of
absolute temperature required for applying the thermopile
calibration. Additionally, the
thermocouples provide verification of the thermopile temperature
difference measurement.
Figure 2-1 and Figure 2-4 also show the tube-surface-mounted
thermocouples used to
measure both refrigerant and HTF temperature profiles in the
evaporator and condenser. As
shown in Section 3.2.6, these temperature profiles are useful for
determining refrigerant tube
12
number where the phase transitions (superheat, subcooling,
two-phase) occur. The refrigerant-
and HTF-side sensors are mounted on the return bends of each
inner/outer tube, respectively.
The instruments are scanned once per minute by the data acquisition
(DAQ) system, and
when steady state is achieved, the measurements are calculated as
the average of a moving
window of 30 readings (i.e., the average over the last 30 minutes).
The measurements inevitably
fluctuate during steady state, which contributes to the uncertainty
of the measurement. This
“steady state” uncertainty has been quantified for a nominal test
condition and is listed in Table
2-3. The total measurement uncertainty (last column of Table 2-3)
is found by adding the
instrument error and the steady state error in quadrature. A
detailed discussion of the selection
of the steady state moving window size and computation of steady
state uncertainty is shown in
Appendix A.10.
Instrument Range
Density:
Mass flow 3:
Density:
Mass flow 4:
±0.0005 gcm-3
Data acquisition system (-10 to 10) V ±1 µV -- ±1 µV
Press. transducer (diff.) – condenser (0 to 172) kPa ±0.7 kPa ±0.8
kPa ±1.3 kPa
Press. transducer (diff.) – evaporator (0 to 345) kPa ±0.1 kPa ±0.8
kPa ±0.8 kPa
Press. transducer (diff.) – suction (0 to 69) kPa ±0.01 kPa ±0.3
kPa ±0.3 kPa
Press. transducer (high press.) (0 to 3447) kPa ±3.4 kPa ±0.7 kPa
±3.5 kPa
Press. transducer (low press.) (0 to 1724) kPa ±3.4 kPa ±0.7 kPa
±3.5 kPa
Tachometer (0.17 to 1667) Hz
(10 to 99 999) RPM
±0.0167 Hz
±1 RPM
±0.005 Hz
±0.3 RPM
±0.0173 Hz
±1.04 RPM
Thermocouple (in-stream probe, ice ref.) (-10 to 100) °C ±0.08 °C
±0.06 °C ±0.09 °C
Thermocouple (surface-mount, CJC) (-10 to 60) °C ±0.6 °C ±0.04 °C
±0.6 °C
Thermopile5 (1 to 10) K ±0.015 K ±0.013 K ±0.0153 K
Thermopile voltage (-10 to 10) V ±1 µV ±6.5 µV ±7 µV
Torque meter (0 to 40) N m ±0.33 Nm ±0.005 Nm 0.33 Nm
1 95% confidence interval (k = 2) 2 % rdg values have been applied
to nominal values 3 Maximum of 0.1% and (z.s./flowrate)*100 %,
where z.s. is zero stability = 0.0491 g s -1. 4 Maximum of 0.1% and
(z.s./flowrate)*100 %, where z.s. is zero stability = 0.0075 g s
-1. 5 For temperature differences in 1 K to 10 K range. Outside
range, uncertainty is higher. See Appendix A.5 for more
detail.
14
Instrument Range
Density:
Mass flow 3:
Density:
Mass flow 4:
±0.062 lb ft-3
Data acquisition system (-10 to 10) V ±1 µV -- ±1 µV
Press. transducer (diff.) – condenser (0 to 25) psi ±0.1 psi ±0.1
psi ±0.18 psi
Press. transducer (diff.) – evaporator (0 to 50) psi ±0.015 psi
±0.1 psi ±0.1 psi
Press. transducer (diff.) – suction (0 to 10) psi ±0.0015 psi ±0.04
psi ±0.04 psi
Press. transducer (high press.) (0 to 500) psia ±0.5 psi ±0.1 psi
±0.51 psi
Press. transducer (low press.) (0 to 250) psia ±0.5 psi ±0.1 psi
±0.51 psi
Tachometer (0.17 to 1667) Hz
(10 to 99 999) RPM
±0.0167 Hz
±1 RPM
±0.005 Hz
±0.3 RPM
±0.0173 Hz
±1.04 RPM
Thermocouple (in-stream probe, ice ref.) (14 to 212) °F ±0.15 °F
±0.11 °F ±0.18 °F
Thermocouple (surface-mount, CJC) (14 to 140) °F ±1.1 °F ±0.08 °F
±1.1 °F
Thermopile5 (1.8 to 18) °F ±0.027 °F ±0.023 °F ±0.04 °F
Torque meter (0 to 350) in lb ±2.9 in lb ±0.045 in lb ±2.9 in
lb
1 95% confidence interval (k = 2) 2 % rdg values have been applied
to nominal values 3 Maximum of 0.1% and (z.s./flowrate)*100 %,
where z.s. is zero stability = 0.0065 lb min-1 4 Maximum of 0.1%
and (z.s./flowrate)*100 %, where z.s. is zero stability = 0.001 lb
min-1 5 For temperature differences in 1.8 °F to 18 °F range.
Outside range, uncertainty is higher. See Appendix A.5 for
more
detail.
15
There are ten Control Parameters (i.e., settings of adjustable
components) listed in Table 2-5
that the MBBHP operator sets to achieve a desired set of Operating
Parameters. Each Control
Parameter primarily governs one or two Operating Parameters; the
correspondence is shown in
the table.
Table 2-5: List of the Control Parameters and Operating
Parameters
# Operating Parameter Operating Parameter Values Control
Parameter
1 Evaporator saturation temperature See Table 2-6 Heater setpoint
(HTF inlet temp.)
2 Condenser saturation temperature See Table 2-6 Chiller setpoint
(HTF inlet temp.)
3 Capacity/heat flux 1760 W to 3520 W
(0.5 ton to 1 ton)
Compressor speed
4 Evaporator heat flux 2000 W m-2 to 12 000 W m-2
(600 Btu h-1 ft-2 to 3800 Btu h-1 ft-2)
Number of evaporator tubes
5 Condenser heat flux 2000 W m-2 to 12 000 W m-2
(600 Btu h-1 ft-2 to 3800 Btu h-1 ft-2)
Number of condenser tubes
6 Condenser HTF-side resistance 50 % to 70 % of overall resistance
Condenser HTF flowrate
7 Evaporator HTF-side resistance 70 % to 85 % of overall resistance
Evaporator HTF flowrate
8 Subcool/ Superheat ≤ 2 tubes1 / ≤ 1 tube2 Refrigerant needle
valve setting
9 Subcool/ Superheat ≤ 2 tubes1 / ≤ 1 tube2 Refrigerant
charge
10 LLSL-HX included/bypassed Included/bypassed LLSL-HX valves
1achieved with subcooling of 2 K to 3 K (1.8 °F to 3.6 °F)
2achieved with superheat of 3 K to 6 K (5.4 °F to 10.8 °F)
2.3.2 Test Rig Operating Parameters
This section describes each of the target Operating Parameters, and
how they are set using
the Control Parameters. Note that the headings for Sections 2.3.2.1
through 2.3.2.5 include the
Operating Parameters numbers (1 to 10) as listed in Table
2-5.
2.3.2.1 Operating Parameters 1 & 2: Evaporator and Condenser
Saturation Temperature
The U.S. Department of Energy (DOE) requires heat pumps and air
conditioners to be rated
at conditions prescribed in the ANSI/AHRI 210/240-2008 (AHRI, 2008)
standard. The standard
specifies temperatures of the HTF (air, in the standard) entering
the evaporator and condenser. A
somewhat different, but derivative, method is employed here; the
HTF inlet temperatures are set
to achieve refrigerant saturation temperatures expected under
ANSI/AHRI Cooling A, Cooling B
and Heating H1 Rating Tests for the baseline refrigerant
R134a.
The target saturation temperatures are computed first for the
Cooling A test where the
assumed Coefficient of Performance (COPcool) is 4.4 (energy
efficiency ratio, EER, is 15). The
16
ANSI/AHRI standard is not prescriptive about airflow, so typical
values per unit evaporator
capacity are used: for the evaporator ,( )air evap evapV Q , 0.189
m3 s-1kW-1 (400 ft3 min-1ton-1), and
for the condenser ,( )air cond evapV Q , 0.378 m3 s-1kW-1 (800 ft3
min-1ton-1). Inlet air temperatures
(Tair,in) prescribed by the ANSI/AHRI standard are listed in Table
2-6; the temperature change
across the evaporator and condenser (Tair,evap, Tair,cond) is 12.6
K and 9.7 K (22.8 °F and 17.5
°F), respectively, as computed using an energy balance on the
airstream, where the condenser
energy is larger by an amount that reflects the compressor power
(in the COP term):
( ) 1
air p air
cool air p air
T V Q Cρ
,air cond evapV Q = condenser airflow per unit evaporator
capacity
,air evap evapV Q = evaporator airflow per unit evaporator
capacity
ρair = density of air
The air outlet temperatures (Tair,out) are then computed by
respectively subtracting or adding the
Tair,evap, Tair,cond, from the Tair,in values.
The average temperature difference between the refrigerant and the
air (Tair,ref) for
Cooling A is specified as 10 K and 3.3 K (18 °F and 6 °F) in the
evaporator and condenser,
respectively, based on experience and measurements at NIST for
air-source heat pumps with comparable COPs. Table 2-6 shows the
average air (Tair,avg) and average refrigerant saturation
temperatures (Tref,avg) computed using this method. The Cooling B
refrigerant saturation
temperatures are computed using the same Tair and Tair,ref. In
heating, the heat exchangers
operating as the evaporator/condenser swap, so the values of Tair
and Tair,ref for the evaporator
(in cooling) are used for the condenser, and vice versa. The
resulting refrigerant saturation
temperatures are nominally aligned with values observed in heat
pump measurements at NIST.
The HTF inlet temperatures (THTF,in) are adjusted to achieve the
target refrigeration saturation
temperature at a compressor speed of 30 Hz (1800 RPM) with R134a,
and then held constant for
all other speeds. The corresponding HTF outlet temperatures
(THTF,out) are defined as:
, , , ,HTF e out HTF e in eT T T= + (2.1)
, , , ,HTF c out HTF c in cT T T= + (2.2)
where Te and Tc are the HTF temperature differences across the
evaporator/condenser
measured by the thermopiles. The THTF,out values differ for each
speed; Table 2-6 shows the
values at 30 Hz (1800 RPM) as a nominal example. As discussed in
Section 1, a completely fair
comparison of refrigerants requires the same HTF inlet and outlet
temperatures (McLinden et al.,
1987). However, it is only possible to match either the evaporator
or condenser (but not both)
THTF,out by adjusting the heat pump capacity (via compressor
speed); the other THTF,out will be an
17
uncontrolled value, which will vary somewhat from the R134a value,
depending on the COP of
each fluid (note the HTF mass flow rate is fixed as described in
Section 2.3.2.3, so it cannot be
adjusted to control the other THTF,out). Tests with future
refrigerants will be carried out with an
evaporator or condenser THTF,out equal to the measurements for
R134a in cooling or heating,
respectively, and the other THTF,out will vary for each
fluid.
Table 2-6: Evaporator and condenser fluid temperatures for standard
rating tests
Rating Test
Tair,in Tair Tair,out Tair,avg Tair,ref Tref,avg THTF,in THTF,out 1
HTFm
°C K °C °C K °C °C °C kg s-1
(°F) (°F) (°F) (°F) (°F) (°F) (°F) (°F) lb min-1
Condenser
Cooling A 35.0 9.7 44.7 39.9 3.3 43.2 33.9 39.1 0.098
(95.0) (17.5) (112.5) (103.8) (6.0) (109.8) (93.0) (102.4)
(13)
Cooling B 27.8 9.7 37.5 32.6 3.3 36.0 24.9 30.9 0.098
(82.0) (17.5) (99.5) (90.8) (6.0) (96.8) (76.7) (87.6) (13)
Heating H1 21.1 12.6 33.8 27.4 10.0 37.4 32.0 36.3 0.098
(70.0) (22.8) (92.8) (81.4) (18.0) (99.4) (89.5) (97.3) (13)
Evaporator
Cooling A 26.7 12.6 14.0 20.3 10.0 10.3 20.2 15.4 0.131
(80.0) (22.8) (57.3) (68.6) (18.0) (50.6) (68.5) (59.7)
(17.3)
Cooling B 26.7 12.6 14.0 20.3 10.0 10.3 19.9 14.2 0.131
(80.0) (22.8) (57.3) (68.6) (18.0) (50.6) (67.8) (57.6)
(17.3)
Heating H1 8.3 9.7 -1.4 3.5 3.3 0.1 10.3 6.5 0.131
(47.0) (17.5) (29.5) (38.3) (6.0) (32.3) (50.5) (43.7) (17.3)
1 Values for R134a at a compressor speed of 30 Hz (1800 RPM)
2.3.2.2 Operating Parameters 3, 4, & 5: Capacity and Heat
Flux
Baseline capacities were established for R134a at speeds of 23.3 Hz
to 36.7 Hz (1400 RPM to
2200 RPM), in 3.3 Hz (200 RPM) increments, for each Rating Test.
Tests with subsequent
refrigerants will be carried out with compressor speeds that match
the capacities from the
baseline tests; this ensures the refrigerants are tested at the
same totalQ A . The target refrigerant-
side heat flux range was 2 kW m-2 to 12 kW m-2 (600 Btu h-1 ft-2 to
3800 Btu h-1 ft-2) to coincide
with values from typical HVAC&R equipment. The average heat
flux in the evaporator and
condenser was controlled by setting the number of active tubes to
10 and 12, respectively.
Figure 2-6 summarizes the capacity for the baseline tests, where
the evaporator capacity varies
from 1.2 kW to 2.1 kW (0.34 ton to 0.60 ton) and condenser capacity
ranges from 1.6 kW to 2.8
kW (0.45 ton to 0.80 ton). The heat flux in the evaporator varies
from 5 kW m-2 to 9 kW m-2
(1600 Btu h-1 ft-2 to 2900 Btu h-1 ft-2) and in the condenser from
5 kW m-2 to 10 kW m-2 (1700
Btu h-1 ft-2 to 3200 Btu h-1 ft-2), meeting the target heat flux
range.
18
(a) (b)
Figure 2-6: Capacity and heat flux for baseline R134a tests for (a)
evaporator and (b)
condenser
2.3.2.3 Operating Parameters 6 & 7: HTF-side Thermal Resistance
Ratio
In typical air-to-air heat pumps the air-side convection provides
the majority of the
resistance to heat transfer. Evaporation heat transfer coefficients
are generally larger than those
for condensation, so the HTF-side resistance ratio (RHTF/Rtotal) is
selected in the range of 50 % to
70 % for the condenser and 70 % to 85 % in the evaporator. The
CYCLE_D-HX model reports
heat exchanger thermal resistances for both the evaporator and
condenser when given
measurements of HTF in/out temperatures, capacity, compressor
efficiency, and heat exchanger
geometry, pressure drop, and log-mean temperature difference. These
resistances include the
heat exchanger total conductance (UA) (the total resistance,
Rtotal, is the inverse of UA), the heat
transfer-side resistance (RHTF) in the evaporator/condenser, and
the refrigerant-side thermal
resistance (Rref) in the evaporator/condenser. Note that the tube
wall thermal resistance is
neglected.
The MBBHP was operated under varied HTF flowrates ( HTFm ), and the
resulting data were
processed using the CYCLE_D-HX model to determine RHTF/Rtotal for
each flowrate. The
evaporator and condenser HTF flowrates used for the tests are 0.131
kgs-1 and 0.098 kgs-1 (17.3
lb min-1 and 13 lb min-1) as shown in Table 2-6, which yield
RHTF/Rtotal of 80 % and 60 % for the
baseline Cooling A test with R134a at 30 Hz (1800 RPM). The
flowrates are kept constant for
all other speeds, test conditions, and refrigerants. Maintaining a
constant flowrate is important
for verifying the CYCLE_D-HX model; the model evaluates the
HTF-side thermal resistance for
a reference data set, and then holds this resistance constant as
other operating parameters,
refrigerants, and tube circuit configurations are computationally
explored.
2.3.2.4 Operating Parameters 8 & 9: Subcool and Superheat
The number of evaporator tubes containing superheated-vapor and
condenser tubes with
subcooled-liquid are controlled to one and two, respectively. It is
important to limit the number
of tubes in superheat and subcooling for comparison with the
CYCLE_D-HX model because the
20 25 30 35 40 1.2
1.4
1.6
1.8
2.0
2.2
5.1
6.0
6.8
7.6
8.5
9.4
f luid = R134a
1.6
1.8
2.0
2.2
2.4
2.6
2.8
5.6
6.3
7.0
7.7
8.4
9.1
9.8
f luid = R134a
19
model does not consider the pressure drop or area required for heat
transfer in these sections,
rather, it only accounts for transport phenomena in the two-phase
section. (Note that the
superheat and subcooling are included as an input to the model to
determine the thermodynamic
states at the heat exchanger outlets.) The superheat and subcooling
are also limited because of
performance considerations; the single phase fluid exhibits a lower
heat transfer coefficient
compared to a two-phase fluid. The superheat is bound at the low
end by the need to prevent
liquid from entering the compressor. The lower limit for subcooling
is governed by a
requirement of fully subcooled liquid entering the expansion valve;
vapor bubbles entering the
expansion valve cause oscillations in the flow that make it
difficult to achieve steady state. In
general, a superheat range of 3 K to 6 K and a subcooling range of
2 K to 3 K satisfies this
Operating Parameter requirement.
Closing the refrigerant needle valve increases the superheat and
the subcooling, whereas
adding refrigerant increases the subcooling and reduces the
superheat. The combination of these
two controls allows for independent regulation of superheat and
subcooling.
2.3.2.5 Operating Parameter 10: LLSL-HX included or bypassed
The LLSL-HX heat exchanger is included or bypassed using the six
valves shown in Figure
2-1. When the LLSL-HX is bypassed, only one (rather than both) of
the valves that stops flow
through the heat exchanger is closed; this prevents the possibility
of trapping subcooled liquid
between the valves (and presenting the same pressure hazard
discussed in Section 2.1.
20
3 Data Analysis
3.1 Thermodynamic States
The thermodynamic states numbered 1 through 11 in Figure 2-1 are
fixed with two intensive
properties defined by the measurements and equations presented in
Table 3-1. Thermodynamic
property data for R134a are computed using the Engineering Equation
Solver (EES) software
(Klein, 2015); the software uses the equation of state developed by
Tilner-Roth et al. (1994) for
R134a. Note that property data for mixtures and for fluids not
directly available in EES will be
computed using the NIST REFPROP database (Lemmon et al.,
2013).
Table 3-1: Measurements and equations used to define the
thermodynamic states
State Description Measurement Equations
1 Compressor inlet, LLSL-HX vapor outlet T1 P1 = P11 – Ps
2 Compressor cylinder before compression T2 = T1 P2 = P1
3 Compressor outlet T3 P3 = P4
4 Condenser inlet T4 P4 = P7 + Pc
5 Condenser saturated vapor P5 = P4 x5 = 1
6 Condenser saturated liquid P6 = P7 x6 = 0
7 Condenser outlet, LLSL-HX liquid inlet T7, P7
8 Expansion valve inlet, LLSL-HX liquid outlet T8 P8 = P7
9 Evaporator inlet, Expansion valve outlet P9 h9 = h8
10 Evaporator saturated vapor P10 = P11 x10 = 1
11 Evaporator outlet, LLSL-HX vapor inlet T11 P11 = P9 – Pe
T = temperature, P = pressure, h = enthalpy, x = thermodynamic
quality
3.2 Thermodynamic Performance
Given the fixed state points identified in Table 3-1 (and all
associated intensive properties),
the key thermodynamic performance metrics are calculated according
to the equations in
Sections 3.2.1 through 3.2.7. Nominal values and uncertainties of
the metrics are shown in
Section 4, and Appendix A, respectively.
3.2.1 Capacity
according to:
( ), 4 7c ref refQ m h h= − (3.1)
( ), 9 11e ref refQ m h h= − (3.2)
c, ,c , , ,HTF HTF p HTF c c ins cQ m C T Q= − (3.3)
21
, , , , ,e HTF HTF e p HTF e e ins eQ m C T Q= − (3.4)
where the variables represent:
,eHTFm ,HTF cm = mass flow of HTF in evaporator/condenser
C p,HTF,e
C p,HTF,c
,ins eQ ,ins cQ = insulation heat leak in
evaporator/condenser
Te Tc = temperature change of HTF in evaporator/condenser
The insulation heat leak is a non-trivial 30 W to 50 W, and
therefore must be accounted for in the
heat exchanger capacity. The heat leak is debited from the HTF-side
capacity because the HTF
is the annulus, and therefore thermally interacts with the
surrounding ambient air. The heat
exchangers are divided into active and inactive sections (i.e.,
tubes where the HTF flows, but the
refrigerant does and does not, respectively) to compute the heat
leak according to:
( ) ( ), e,
e active inactive
ins e ins e HTF e active avg amb e HTF e inactive avg amb e
e total total
NT NT
c active c inactive
ins c ins c HTF c active avg amb c HTF c inactive avg amb c
c total c total
NT NT
NTe,total NTe,total = number of tubes in evaporator/condenser total
(20)
NTe,active NTc,active = number of active tubes in
evaporator/condenser
NTe,inactive NTe,inactive = number of inactive tubes in
evaporator/condenser
THTF,e,active,avg THTF,c,active,avg = avg. HTF temp. in the active
evaporator/condenser tubes
THTF,e,inactive,avg THTF,c,inactive,avg = avg. HTF temp. in the
inactive evaporator/condenser tubes
Tamb,e Tamb,c = temp. of ambient air surrounding
evaporator/condenser
The HTF temperatures are taken from the surface-mounted
thermocouples, and the ambient air
temperature is taken from a thermocouple near each of the heat
exchangers. The heat exchangers
are split into active/inactive sections because the slope of the
HTF temperature profile is
different in each section; the heat transfer is only governed by
the average temperature difference
if the slopes (and specific heats) are constant throughout the
section. The UAins,e and UAins,c
values for all 20 tubes are 5.48 W K-1 ±0.31 W K-1 and 6.52 W K-1
±0.41 WK-1 (10.4 Btu h-1 °F-1
±0.59 Btu h-1 °F-1 and 12.4 Btu h-1 °F-1 ±0.78 Btu h-1 °F-1). The
method used to compute the
conductance values and their uncertainties is described in Appendix
A.8.
3.2.2 Compressor Power
The compressor power is computed using the change in enthalpy
across the compressor:
22
( )3 1comp refW m h h= − (3.7)
The shaft power is computed for comparison with the compressor
power:
2shaftW Nπτ= (3.8)
where the variables represent:
N = compressor shaft speed
τ = compressor shaft torque
3.2.3 Coefficient of Performance
The cooling and heating COP are computed using the refrigerant-side
capacity and the
compressor power applied to the refrigerant:
,COPcool e ref compQ W= (3.9)
,COPheat c ref compQ W= (3.10)
3.2.4 Volumetric Capacity
The volumetric cooling and heating capacity (VCC and VHC)
are:
( ), 1e ref ref VCC Q m v= (3.11)
( ), 1c ref ref VHC Q m v= (3.12)
where:
3.2.5 Compressor Efficiency
( )3 1 1
The volumetric efficiency is quantified by the refrigerant
displacement normalized by the
compressor swept volume displacement:
3.2.6 Superheat and Subcooling
The evaporator superheat is:
and the condenser subcooling is:
( )7 7, 0SC T P x T= = − (3.16)
where:
T(P11, x = 1) = saturated vapor temperature at the evaporator exit
pressure
T(P7, x = 0) = saturated liquid temperature at the condenser exit
pressure
The number of refrigerant tubes containing superheated/subcooled
fluid in the
evaporator/condenser is controlled to one and two, respectively,
during experimental tests.
Visual inspection of the temperature profile, such as the one shown
in Figure 3-1, is used to
determine the locations of the various phase transitions. The tube
number on the x-axis reflects
the convention established in Figure 2-5.
(a) (b)
Figure 3-1: Temperature profile in (a) evaporator, showing
superheat and (b)
condenser, showing subcooling
*The location 21 is the exit of the 20th tube
3.2.7 LLSL-HX Effectiveness
The LLSL-HX effectiveness is computed as the ratio of the heat
transferred on the vapor
24
( )
C T TQ
− = =
−
where:
Cp,avg,1,11 = average specific heats of the refrigerant on the
vapor side
Cp,avg,7,8 = average specific heats of the refrigerant on the
liquid side
The heat transfer on the vapor side, rather than liquid side, is
chosen for the numerator because
the larger temperature difference exhibited on the vapor side (due
to lower specific heat) results
in a smaller uncertainty in the effectiveness.
25
4 Validation and Baseline Tests with R134a
An initial set of tests were carried out with R134a to provide
verification of the
instrumentation and show the nominal uncertainties of the
measurements. One of the most
important validations is to show an energy balance between the
refrigerant and the HTF in the
heat exchangers. The energy imbalance, defined as ( ) ,ref ref HTF
Q Q Q− for the initial tests is
shown in Figure 4-1; the imbalance is generally around 1 % to 1.5 %
or better in both the
evaporator and condenser. The imbalance falls well within its
uncertainty at the 95 %
confidence interval, indicating that the estimation of the
uncertainty in HTF capacity (3 %) is
likely too conservative; note that the HTF capacity accounts for
more than 90 % of the relative
uncertainty in the imbalance metric.
Figure 4-1: Energy imbalance in the evaporator and condenser
The performance of R134a in the MBBHP, as described by the metrics
defined in Section
3.2, are presented in Figure 4-2 through Figure 4-4. Figure 4-2 (a)
and (b) show nominal
pressure profiles on the low/high pressure sides of the cycle,
where the error bars represent
measurement uncertainty listed in Table 2-3. The compressor power
measured both by the shaft
power and change of enthalpy of the working fluid are shown in
Figure 4-3(a), where the
conversion from mechanical to fluid power is about 65 % efficient.
The error bars represent the
uncertainty calculated by propagating measurement uncertainty
through Eqs. (3.7) and (3.8).
The mass flow ranges from 8 gs-1 to 13 gs-1 (1.1 lb min-1 to 1.7 lb
min-1). Figure 4-4 shows the
COP ranges from 2.4 to 4, and the capacity ranges from 1.6 kW to
2.1 kW (0.45 ton to 0.60 ton).
The figure shows the uncertainties of the COP and capacity, where
the computation and
tabulation of uncertainty is described further in Appendix A.10 and
A.11. The volumetric
capacity ranges from 2100 kJ m-3 to 2800 kJ m-3 (56 Btu ft-3 to 75
Btu ft-3), and the compressor
isentropic and volumetric efficiencies are nominally 0.46 and 0.55;
uncertainties in all three of
these metrics are shown in the figures and are computed using a
similar method as the
capacity/COP, but the computation is not discussed in detail in
this report.
Figure 4-3 (b) also shows the mass flux, which is used to determine
the two-phase flow
regimes indicated in Figure 4-5. The refrigerant generally entered
the annular flow regime in the
evaporator and condenser, though for some tests with low mass flux
the refrigerant never left the
stratified-wavy regime.
(a) (b)
Figure 4-2: Heat pump cycle pressures on the (a) low pressure side
and (b) high
pressure side
(a) (b)
Figure 4-3: Performance metrics including (a) compressor power and
(b) mass flow and
mass flux
1100
1150
1200
350
400
450
0.6
0.9
1.2
shaft pow er (Wshaf t)
20 25 30 35 40
0.008
0.009
0.01
0.011
0.012
0.013
140
160
180
200
220
lo w
[ k g
lu x [
k g
/s -m
(a) (b)
(c) (d)
Figure 4-4: Performance metrics including (a) COP, (b) capacity,
(c) volumetric
capacity, and (d) compressor isentropic and volumetric
efficiency
20 25 30 35 40 2
2.5
3
3.5
4
4.5
1.6
1.7
1.8
1.9
2
2.1
2200
2400
2600
2800
0.5
0.6
0.7
0.3
0.4
0.5
0.6
0.7
(a)1,3 (b)2,3
Figure 4-5: Flow regime map for microfin tube (a) evaporation and
(b) condensation
1 Flow boiling regime map from (Wojtan et al., 2005) 2 Flow
condensation regime map from (Hajal et al., 2003) 3 Boundary
between Intermittent/Annular regimes from (Thome, 2007), using
equation 12.6.1 with a coefficient
of 0.678, for helical microfins
5 Conclusions and Future Work
This report shows that the test apparatus is capable of measuring
the performance of
low-GWP refrigerants with high fidelity, including less than 0.5 %
uncertainty in both capacity
and COP. The energy balance closure on the evaporator and condenser
was better than 1.5 %
and will be continually tracked to ensure continued high quality
data are collected.
Future tests will include a second baseline refrigerant R410A,
followed by a series of
comparative tests with low-GWP refrigerants and refrigerant
mixtures. The HTF flowrates will
remain fixed from the R134a baseline tests, so that the CYCLE_D-HX
simulations of the test
data can be carried out for all test data based on a single
reference data set. After the model
results are verified, the model will be used to identify additional
candidate refrigerants to test in
the MBBHP test apparatus.
50
100
150
200
250
300
350
lu x [
k g
/s -m
M
S = Stratified SG = Slug SW = Stratified-Wavy
SW
50
100
150
200
250
300
350
lu x [
k g
/s -m
A
I
SG
Vapor quality A = Annular D = Dryout I = Intermittant M =
Mist
S = Stratified SG = Slug SW = Stratified-Wavy
29
AHRI. (2008). 2008 Standard for Performance Rating of Unitary
Air-Conditioning & Air-
Source Heat Pump Equipment. Air-Conditioning, Heating, and
Refrigeration Institute,
Arlington, VA, United States. Retrieved from www.ahrinet.org
AHRI. (2015). Participants' Handbook: AHRI Low-GWP Alternative
Refrigerants Evaluation
Program (Low-GWP AREP). Arlington, VA, United States:
Air-Conditioning, Heating,
and Refrigeration Institute. Retrieved from
http://www.ahrinet.org/site/514/Resources/Research/AHRI-Low-GWP-Alternative-
Refrigerants-Evaluation
Brown, J. S., Domanski, P. A., & Lemmon, E. (2011). Standard
Reference Database 49,
CYCLE_D: NIST Vapor Compression Cycle Design Program, Version 5.0.
Retrieved
from http://www.nist.gov/srd/nist49.cfm
Domanski, P. A., Brown, S. J., Heo, J., Wojtusiak, J., &
McLinden, M. O. (2014). A
thermodynamic analysis of refrigerants: Performance limits of the
vapor compression
cycle. International Journal of Refrigeration, 38, 71-79.
doi:10.1016/j.ijrefrig.2013.09.036
EPA. (2015). 2015 North American Amendment Proposal to Address HFCs
under the Montreal
Protocol. Retrieved from
http://www.epa.gov/ozone/intpol/mpagreement.html and
http://www.epa.gov/ozone/intpol/HFC_Amendment_2015_Summary.pdf
EU. (2014, April 16). Regulation (EU) No 517/2014 of the European
Parliament and of the
Council of 16 April 2014 on fluorinated greenhouse gases and
repealing Regulation (EC)
No 842/2006. Journal of the European Union. Retrieved from
http://eur-
lex.europa.eu/legal-content/EN/TXT/?uri=uriserv:OJ.L_.2014.150.01.0195.01.ENG
Fortin, T. J. (2015). Personal communication.
Hajal, J. E., Thome, J. R., & Cavallini, A. (2003).
Condensation in horizontal tubes, part 1: two-
phase flow pattern map. International Journal of Heat and Mass
Transfer, 3349-3363.
doi:10.1016/S0017-9310(03)00139-X
Harr, L., Gallagher, J. S., & Kell, G. S. (1984). NBS/NRC Steam
Tables. Hemisphere Publishing
Co.
Kazakov, A., McLinden, M. O., & Frenkel, M. (2012).
Computational Design of New
Refrigerant Fluids Based on Environmental, Safety, and
Thermodynamic Characteristics.
Industrial & Engineering Chemistry Research, 51, 12537-12548.
doi:10.1021/ie3016126
Kim, Y., Payne, V., Choi, J., & Domanski, P. A. (2005). Mass
flow rate of R-410A through short
tubes working near the critical point. International Journal of
Refrigeration, 28, 547-553.
doi:10.1016/j.ijrefrig.2004.10.007
Klein, S. A. (2015). Engineering Equation Solver, v 9.908.
Retrieved from
http://www.fchart.com/ees/
Lemmon, E. W., Huber, M. L., & McLinden, M. O. (2013). NIST
Standard Reference Database
23, Reference Fluid Thermodynamic and Transport Properties
(REFPROP), Version 9.1.
30
http://www.nist.gov/srd/nist23.cfm
McLinden, M. O., & Radermacher., R. (1987). Methods for
Comparing the Performance of Pure
and Mixed Refrigerants in the Vapour Compression Cycle.
International Journal of
Refrigeration, 10(6), 318-325.
doi:10.1016/0140-7007(87)90117-4
McLinden, M. O., Kazakov, A., Heo, J., Brown, J. S., &
Domanski, P. A. (2014). A
thermodynamic analysis of refrigerants: Possibilities and tradeoffs
for Low-GWP
refrigerants. International Journal of Refrigeration, 38,
80-92.
doi:10.1016/j.ijrefrig.2013.09.032
Pannock, J., & Didion, D. A. (1991). The Performance of
Chlorine-Free Binary Zeotropic
Refrigerant Mixtures in a Heat Pump, NISTIR 4748. Internal Report,
National Institute of
Standards and Technology, U.S. Department of Commerce,
Gaithersburg. Retrieved from
http://fire.nist.gov/bfrlpubs/build91/art002.html
Solomon, S., Qin, D., Manning, M., Chen, Z., Marquis, M., Averyt,
K. B., . . . Miller, H. L.
(2007). Contribution of Working Group I to the Fourth Assessment
Report of the
Intergovernmental Panel on Climate Change. New York, NY, USA:
Cambridge
University Press. Retrieved July 29, 2015, from
http://www.ipcc.ch/publications_and_data/publications_ipcc_fourth_assessment_report_
wg1_report_the_physical_science_basis.htm
Taylor, B. N., & Kuyatt, C. E. (1994). Guidelines for
Evaluating and Expressing the Uncertainty
of NIST Measurement Results, National Institute of Standards and
Technology Technical
Note 1297.
Thome, J. R. (Updated in 2007). Wolverine Heat Transfer Engineering
Data book III. Germany:
Weiland-Werke AG. Retrieved from
http://www.wlv.com/heat-transfer-databook/
Tilner-Roth, R., & Baehr, H. D. (1994). An International
Standard Formulation for the
Thermodynamic Properties of 1,1,1,2-Tetrafluoroethane (HFC-134a)
for Temperatures
from 170 K to 455 K and Pressures up to 70 MPa. J. Phys. Chem, Ref.
Data, 23(5).
Wojtan, L., Ursenbacher, T., & Thome, J. R. (2005).
Investigation of flow boiling in horizontal
tubes: Part I—A new diabatic two-phase flow pattern map.
International Journal of Heat
and Mass Transfer, 2955-2969.
doi:10.1016/j.ijheatmasstransfer.2004.12.012
31
Symbol Units Definition
Q kW Energy transfer
SX -- Standard deviation of measured quantity “X”
T °C Temperature
TTC,cal °C Calibrated thermocouple measurement
TTC,CJC °C Thermocouple measurement with Cold Junction
Compensation
Tlm K Log-mean temperature difference
TTC,cal K Thermocouple calibration temperature difference
TTP K Temperature difference of thermopile
UA W K-1 Thermal conductance
, ,UA ins e U W K-1 Uncertainty of average of evaporator insulation
conductance
UTC °C Total instrument uncertainty of thermocouple
UTC,cal °C Thermocouple instrument uncertainty from calibrating
device uncertainty
UTC,fit °C Instrument uncertainty of thermocouple due to fit of
calibration regression
UX -- Uncertainty of measured quantity “X”
X U -- Uncertainty of average of measured quantity “X”
UY Uncertainty of calculated quantity “Y”
V V Voltage
V1 V Thermopile voltage of cold end of thermopile (referenced to
ice-point)
VCC kJ m-3 Volumetric Cooling Capacity
VHC kJ m-3 Volumetric Heating Capacity
VTC V Thermocouple voltage
VTP V Thermopile voltage
in Inlet
ins Insulation
out Outlet
1 to 11 Refrigerant thermodynamic states as defined by Figure
2-1
Abbreviation Definition
COP Coefficient of Performance (W capacity per W of input
power)
CJC Cold Junction Compensation (for thermocouples)
DAQ Data Acquisition
DSC Differential Scanning Calorimeter (used to measure fluid
specific heat)
EES Engineering Equation Solver (software used to reduce
data)
HTF Heat Transfer Fluid
RPM Revolutions per Minute (compressor shaft)
RTD Resistance Temperature Detector
A.2 General Remarks
The uncertainty analyses for key performance metrics are presented
in this section. All
uncertainties are estimated based on instrument uncertainties
computed at a 95 % confidence
interval.
The surface-mounted thermocouples, as well as the thermocouples
measuring the air
temperature near the evaporator/condenser, are compensated at the
DAQ using a thermistor-
based Cold Junction Compensation (CJC). A calibration (Tcal) is
applied to the resulting
temperature reading (TTC,CJC) to compute the calibrated temperature
(TTC,cal) according to:
,cal , ,TC TC CJC TC cal
T T T= + (A.1)
where the calibration is fit to a 2nd order polynomial (the order
of this curve fit, and others
presented in Appendix A, were selected based on t-test of
polynomial coefficients):
2
, , 0 1 , 2 ,TC cal cal TC CJC TC CJC TC CJCT T T a a T a T = − = +
+ (A.2)
The polynomial coefficients (a0, a1, a2) are fit using the least
square error method, and Tcal is the
temperature measured by the calibrating instrument (two calibrated
RTDs read by a precision
digital thermometer, expanded uncertainty of ±0.02 °C). The
thermocouples were calibrated over
a temperature range of -10 °C to 60 °C, and this calibration was
repeated five times over the
33
course of two weeks; Figure A-1 (a) shows the calibration data and
polynomial curve fits for a
representative thermocouple. Each calibration shows a significant
offset from the others; this is
likely a manifestation of the repeatability error of the CJC, which
has an overall uncertainty of
±0.5 °C. Figure A-1 (b) shows the aggregation of the five data sets
and the resulting curve fit
and 95 % confidence interval (±0.6 °C). The uncertainty of the
calibrated RTDs is more than an
order of magnitude smaller than the curve fit confidence interval,
and is therefore neglected. The
CJC thermocouple instrument uncertainty listed in Table 2-3 is
therefore ±0.6 °C.
(a) (b)
Figure A-1: Temperature calibration for CJC compensated
thermocouples where
(a) data are divided by each of the 5 calibrations and (b) all data
are
combined.
A.4 Thermocouples with Ice-Water Bath Compensation
A lower level of uncertainty is achieved for the in-stream probe
thermocouples, which
measure the refrigerant temperatures at key thermodynamic states,
by utilizing an ice-water bath
reference junction. The ice-water bath consists of a vacuum
insulated Dewar filled with crushed
ice and water; the reference junction is submerged in the bath
inside of a water-filled test tube.
Using the ice-water bath removes the large uncertainty associated
with the electronic CJC on the
DAQ system. The thermocouples were calibrated against the RTDs
(same ones used to calibrate
thermocouples with CJC), where the resulting data and curve fit are
shown for a representative
thermocouple in Figure A-2. The data were fit to 5th order
polynomials according to:
5
=∑ (A.3)
where VTC is the thermocouple voltage. The resulting instrument
uncertainty (±0.08 °C) listed in
Table 2-3 is the combination of the curve fit standard error
(UTC,fit, k = 2) and the calibrating
RTD error (UT,cal):
2 2 2 2
, , 0.079 0.02 0.08TC TC fit T calU U U C= ± + = ± + = ± °
(A.4)
-10 0 10 20 30 40 50 60 -1.5
-1
-0.5
0
0.5
-1
-0.5
0
0.5
34
A.5 Thermopiles in Heat Transfer Fluid
The 13-junction thermopiles were calibrated by immersing one end in
an ice-water bath
(inside a water-filled test tube) and the other end in a
temperature controlled bath. The
temperature in the controlled bath was measured using the two
calibrated RTDs. A thermopile
voltage-temperature dataset was generated and fit to a 4th order
polynomial. Figure A-3 shows
the calibration data and the curve fit, and Table A-1 shows the
polynomial coefficients. The
calibration data are fit to the equation:
4
The temperature difference for a thermopile is computed according
to:
( )1 1TP TPT T V V T = + − (A.6)
where VTP is the measured thermopile voltage and T1 is the
temperature measured at the cold
end of the thermopile by a CJC-corrected thermocouple. Eq. (A.5) is
substituted into Eq. (A.6)
to calculate the thermopile temperature difference:
( ) 4
=
= + −∑ (A.7)
where V1 (cold-end voltage) is computed by numerically solving Eq.
(A.5) where T is set to (T1):
4
=
= − =
∑ (A.8)
The thermopile uncertainties are computed with respect to the curve
fit, voltage
measurement, and temperature measurement at the cold end of the
thermopile (characterized
respectively by the coefficient uncertainties in Table A-1, the
thermopile voltage uncertainty in
Table 2-3, and the CJC corrected thermocouple in Table 2-3). The
EES (Klein, 2015) software
-0.0005 0 0.0005 0.001 0.0015 0.002 0.0025 -20
0
20
40
60
80
datadata
35
is used to numerically compute the partial derivatives and
subsequent thermopile uncertainties.
Figure A-4(a) shows the contours of uncertainty in the temperature
difference measured by the
evaporator/condenser HTF thermopiles.
Figure A-4(b) shows the contours of relative contribution to
uncertainty in the thermopile
measurement. Each of the uncertainty sources is dominant in
different regions:
• voltage measurement: dominant at low temperature differences
(less than 1 K)
• curve fit error: dominant at high cold end temperatures (greater
than 50 °C)
• cold end temperature: dominant at moderate cold end temperatures
-5 °C to 20 °C and temperature differences 2.5 K to 20 K
As noted in this discussion, the thermopile uncertainty is a
complex function of the curve fit,
voltage measurement, and cold end temperature measurement. For the
temperature difference
range expected for this application, 1 K to 10 K (1.8 °F to 18 °F),
the upper bound of uncertainty
is about 0.015 K (0.027 °F); for simplicity, this is the value
listed in Table 2-3. Note that the
contribution to the uncertainty by the calibrating instrument (two
calibrated RTDs) is negligible
here as the error in slope (which is the error that propagates into
the thermopile temperature
difference) is less than 0.000248 K per K of temperature difference
(e.g. 0.00248 K for a 10 K
temperature difference).
Table A-1: Condenser & evaporator
aTP,e,1 2.0243 E+03 ±1.2 E-01
aTP,e,2 -5.5466 E+03 ±2.2 E+01
aTP,e,3 3.9023 E+04 ±1.3 E+03
aTP,e,4 -2.6229 E+05 ±2.2 E+04
aTP,c,0 3.8494 E-02 ±5.3 E-04
aTP,c,1 2.0241 E+03 ±1.5 E-01
aTP,c,2 -5.5190 E+03 ±2.8 E+01
aTP,c,3 3.8551 E+04 ±1.6 E+03
aTP,c,4 -2.5440 E+05 ±2.9 E+04
-0.01 0 0.01 0.02 0.03 0.04
-10
0
10
20
30
40
50
60
(a) (b)
Figure A-4: Contours of thermopile (a) uncertainty and (b) relative
contribution to
uncertainty
A.6 Evaporator Heat Transfer Fluid Specific Heat
The evaporator HTF is a potassium formate and water heat transfer
fluid that is freeze
protected to -40 °C. The manufacturer’s specific heat data were
found to have error of at least
10 %, so a sample of the fluid was analyzed in a Differential
Scanning Calorimeter (DSC) by the
NIST-Boulder Applied Chemicals and Materials Division. The
temperature dependent specific
heat and the 2nd order curve fit to the data are shown in Figure
A-5; the curve fit coefficients and
their uncertainties are listed in Table A-2. Figure A-5 also shows
the manufacturer’s reported
specific heat data for comparison. The exact uncertainty of the DSC
measurement was not
available at the time of writing, but was estimated to be about 2 %
to 3 % of reading based on the
experience of the DSC operator (Fortin, 2015). An uncertainty of 3
% of reading is therefore
assigned as a conservative estimate. Both the curve fit and DSC
calibration uncertainties are
included in the calculation of overall uncertainties.
0 10 20 30 40 50 60 -5
0
5
10
15
0.035
0.002
0
5
10
15
20
T e m
p e ra
37
heat polynomial coefficients
aCp,e,1 1.1015 E-03 ±2.1 E-04
aCp,e,2 1.7422 E-05 ±9.5 E-06
Figure A-5: Specific heat measurements for
evaporator HTF
A.7 Condenser Heat Transfer Fluid Specific Heat
The condenser HTF is water; the specific heat data are computed in
EES using the data from
(Harr et al., 1984) and are shown in Figure A-6. A conservative
estimate of ±3 % is used for the
uncertainty in the specific heat.
Figure A-6: Specific heat of condenser HTF (water)
A.8 Evaporator and Condenser Insulation Conductance
The total evaporator and condenser insulation conductances (UAins,e
and UAins,c) for thermal
interaction with the ambient air were measured during an initial
test where the HTFs were
circulated at various flow rates through the apparatus at an
elevated temperature, while the
refrigerant tubes were under vacuum. The temperature change of the
HTF across the heat
-10 0 10 20 30
2.5
2.6
2.7
2.8
2.9
3
4.19
4.2
4.21
4.22
4.23
38
exchanger was assumed to be entirely attributed to insulation heat
leak, and therefore an
effective insulation conductance could be computed. The resulting
UAins,e and UAins,c values for
all 20 tubes are shown in Figure A-7. Average values of
conductances for the evaporator and
condenser were calculated as 5.48 W K-1 ±0.31 W K-1 and 6.52 W K-1
±0.41 W K-1
(10.4 Btu h-1 °F-1 ±0.59 Btu h-1 °F-1 and 12.4 Btu h-1 °F-1 ±0.78
Btu h-1 °F-1), respectively, where the
uncertainty accounts for both instrumentation error and test
variance. The evaporator insulation
conductance for these tests is computed according to:
( )
( ) ( ) ( ) ( )
, , , , , , ,,
,
ln
HTF e p HTF e HTF in e HTF out eins e
ins e
lm HTF HTF in e amb e HTF e amb e
HTF in e amb e
HTF out e amb e
m C T TQ UA
T T T T T
T T
T T
,HTF e m = evaporator HTF mass flow
,ins eQ = evaporator insulation heat leak
Tamb,e = ambient air temperature surrounding evaporator
THTF,in,e = evaporator HTF inlet temperature
THTF,out,e = evaporator HTF outlet temperature
Tlm,HTF,e = evaporator log-mean temperature difference
and the uncertainty of the average value is calculated according
to:
, ,, , UA ins eUA ins e U k S n= (A.10)
where the variables represent:
k = expanded uncertainty coverage factor (k = 2) for 95 %
confidence interval
SUA,ins,e = standard deviation of conductances
n = number of conductance data points
The condenser conductance is computed using the same method with
the corresponding
measurements from that heat exchanger.
39
A.9 Uncertainty Analysis Software
The uncertainty analyses on each of the performance metrics shown
in Figure 4-1 through
Figure 4-4 were calculated using the uncertainty propagation
capability in EES. The software
numerically computes the performance metric uncertainty by
evaluating the partial derivatives
with respect to each relevant measurement and applying the
specified measurement uncertainty.
Assuming the measurements are independent and uncorrelated, the
uncertainty of a quantity is
computed according to (Taylor & Kuyatt, 1994):
2
2
Xi = measurement
5
6
7
8
A.10 Moving Window and Steady State Uncertainty
A moving window average was used to compute the measurements at
steady state during the
tests. In order to determine a proper window size, the variation of
measurement steady state
uncertainty with window size was examined. The steady state
uncertainty is defined as the
expanded standard uncertainty for the average reading within the
window:
X
X
n = number of samples in the window
Sx = standard deviation of measurement
X = average value of measurement
The data for analysis were generated by holding the MBBHP at a
nominal steady operating
condition and recording the measurements at 1-minute intervals
(same as collection rate for all
performance testing) for an extended time (3 hours). Figure A-8
shows the fluctuation of steady
state uncertainty for the evaporator inlet and outlet temperatures
(T9 and T11). The figure
highlights two characteristic trends observed for all of the
instruments, both of which suggest the
need for a large moving window: (1) the steady state uncertainty
decreases as the window size
increases, and (2) the steady state uncertainty is highly
oscillatory for small windows (the
oscillations are undesirable because short-term fluctuations can
have a disproportionate impact
on the averaged result). A 30 sample moving window was selected to
achieve low uncertainty
while allowing for collection of data in a timely manner.
Figure A-8 shows that the measurement steady state uncertainty is
not constant in time (it
would be constant if the fluctuations at steady state were purely
random), but rather exhibits
drifting and periodic movements. This is possibly due to hunting by
the PID controllers
regulating HTF fluid temperatures, changes in air temperature in
the lab space, or some other
uncontrolled and/or uncharacterized phenomena. These non-random
fluctuations are accounted
for by using the maximum steady state uncertainty value observed
during the extended steady
state test. For example, Figure A-8(a) shows the maximum steady
state uncertainty for the
evaporator outlet (T9) is ±0.06 °C; this value and values for all
other sensors are listed in Table
2-3. The data in the moving window are only recorded when steady
state uncertainties are below
these established thresholds. The total uncertainty (±0.09 °C),
also shown in Table 2-3, is
subsequently computed by adding the instrument uncertainty (±0.08
°C) and steady state
uncertainty (±0.06 °C) in quadrature.
Note that different sensors of the same type exhibit different
levels of fluctuation; as a
conservative estimate, the largest uncertainty of any one is
applied to all of them. For example,
Figure A-8(b) shows the fluctuations of steady state uncertainty
for the evaporator inlet
temperature (T9) are much smaller than for the evaporator outlet
(T11). In fact, the evaporator
outlet temperature (T11) shows the most fluctuation of all the
ice-water bath compensated
thermocouple probes; therefore, its value (±0.06 °C) is used in
Table 2-3 to represent them all.
41
(a) (b)
Figure A-8: Uncertainty in temperature due to fluctuations at
steady state for (a)
evaporator outlet and (b) evaporator inlet
A.11 Uncertainty Results Summary
refrigerant/HTF-side capacities and the COPs are tabulated in
Appendices A.11.1 (cooling) and
A.11.2 (heating). The tables show the performance metric and its
total uncertainty (including
both instrument and steady state contributions), as well as the
measurements that contribute to
the uncertainty. The measurement values, uncertainties, partial
derivatives (of performance
metric with respect to the measurement), and relative errors
(contribution to the overall error in
the performance metric) are also shown, where the measurements are
listed in order of
decreasing relative error. Uncertainties for other performance
metrics (e.g. VCC/VHC, ηisen)
were analyzed using similar techniques, but are not shown in detail
in this report. Note that
Appendices A.11.1 and A.11.2 show sample calculations for a single
nominal operating
condition, whereas the uncertainty values presented in the Section
4 figures are computed for
each test run.
The uncertainty in cooling performance metrics are shown for a
nominal operating point for
R134a during a Cooling A test with a compressor speed of about 30
Hz (1800 RPM). Similarly,
the uncertainty in heating performance metrics are shown for R134a
during a Heating H1 test
with a compressor speed of about 30 Hz (1800 RPM).
A.11.1 Uncertainty Results Summary: Cooling
Table A-3 shows that the dominant sources of instrument uncertainty
for the refrigerant-side
capacity are refrigerant mass flow (66 %), expansion valve inlet
temperature (17 %), evaporator
exit pressure (8 %), and evaporator exit temperature (7 %). Table
A-4 shows the dominant
source of instrument uncertainty for the HTF-side capacity is the
HTF specific heat (97 %,
estimate for instrument used to measure fluid properties). Table
A-5 shows the dominant
sources of instrument uncertainty for cooling COP are evaporator
inlet pressure (39 %),
compressor discharge temperature (25 %), and compressor suction
temperature (18 %).
8000 12000 16000 20000 0.002
0.01
0.1
0.5
0.01
0.1
0.5
Parameter Symbol Value
(0.20%) -- --
Refrigerant mass flow refm 11.00 g s-1 ±0.024 g s-1 1.538 E-01 66
%
Refrigerant temp. at expansion valve inlet T8 38.16 C ±0.09 °C
-1.634 E-02 17 %
Refrigerant press. at evaporator inlet P9 412 kPa ±3.5 kPa -2.817
E-04 8 %
Refrigerant temp. at evaporator exit T11 12.09 C ±0.09 °C 1.009
E-02 7 %
Refrigerant press. at condenser exit P7 1104 kPa ±3.5 kPa 2.103
E-06 0 %
Refrigerant evaporator differential press. Pe 43.92 kPa ±0.8 kPa
2.817 E-04 0 %
Table A-4: Uncertainty of HTF-side evaporator cooling
capacity
Parameter Symbol Value
(3.0%) -- --
Evaporator HTF capacity
calibration uncertainty ,HTF ecp 2.59 J g-1 K-1 ±3 % of ,HTF ecp
6.369 E-01 97 %
Temperature of ambient air
surrounding evaporator Tamb,e 23.0 °C ±0.6 °C 5.474 E-03 1 %
HTF mass flow ,HTF em 131.2 g s-1 ±0.26 g s-1 1.257 E-02 1 %
Evaporator HTF thermopile voltage VTP,e 2.512 mV ±0.007 mV 6.537
E-01 1 %
Evaporator HTF thermopile
aTP,e,1 2.0243 E+03 ±1.2 E-01 8.832 E-04 0 %
aTP,e,2 -5.5466 E+03 ±2.2 E+01 1.559 E-05 0 %
aTP,e,3 3.9023 E+04 ±1.3 E+03 2.106 E-07 0 %
aTP,e,4 -2.6229 E+05 ±2.2 E+04 2.554 E-09 0 %
Evaporator HTF capacity
Temperature at cold end of
evaporator HTF thermopile THTF,e,out 15.42 °C ±0.6 °C -2.963 E-03 0
%
Evaporator insulation conductance UAins,e 5.474 W K-1 ±0.3052 W K-1
4.175 E-03 0 %
43
Parameter Symbol Value
±0.01
(0.35 %) -- --
Refrigerant press. at evaporator inlet P9 412 kPa ±3.5 kPa -1.232
E-02 39 %
Refrigerant temp. at compressor discharge T3 81.97 °C ±0.09 °C
5.571 E-02 25 %
Refrigerant temp. at compressor suction T1 12.73 °C ±0.09 °C 4.788
E-02 18 %
Refrigerant press. at condenser exit P7 1104 kPa ±3.5 kPa 5.144
E-03 7 %
Refrigerant temp. at expansion valve inlet T8 38.16 °C ±0.09 °C
-2.746 E-02 6 %
Refrigerant temp. at evaporator exit T11 12.09 °C ±0.09 °C 1.696
E-02 2 %
Refrigerant evaporator diff. press. Pe 43.92 kPa ±0.8 kPa 7.432
E-04 2 %
Refrigerant condenser diff. press. Pc 32.34 kPa ±1.3 kPa 4.731 E-04
1 %
Refrigerant suction line diff. press. Ps 14.22 kPa ±0.3 kPa 1.314
E-03 0 %
Refrigerant mass flow refm 11.00 g s-1 ±0.016 g s-1 2.209 E-04 0
%
A.11.2 Uncertainty Results Summary: Heating
Table A-6 shows the dominant sources of instrument uncertainty for
the refrigerant-side
capacity are refrigerant mass flow (85 %), condenser exit
temperature (9 %), and condenser inlet
temperature (5 %). Table A-7 shows the dominant source of
instrument uncertainty for the HTF-
side capacity is the HTF specific heat (97 %, estimate for
instrument used to measure specific
heat of water in the reference). Table A-8 shows the dominant
sources of instrument uncertainty
for cooling COP are evaporator inlet pressure (32 %), compressor
discharge temperature (31 %),
and compressor suction temperature (22 %).
44
Parameter Symbol Value
(0.2%) -- --
Refrigerant mass flow refm 9.06 g s-1 ±0.016 g s-1 2.067 E-01 85
%
Refrigerant temp. at condenser exit T7 37.39 °C ±0.09 °C -1.343
E-02 9 %
Refrigerant temp. at condenser inlet T4 77.22 °C ±0.09 °C 9.443
E-03 5 %
Refrigerant press. at condenser exit P7 992.8 kPa ±3.5 kPa -1.296
E-04 1 %
Refrigerant condenser differential press. Pc 27.2 kPa ±1.3 kPa
-9.028 E-04 0 %
Table A-7: Uncertainty of HTF-side condenser heating capacity
Parameter Symbol Value
(2.9%) -- --
Condenser HTF capacity calibration
uncertainty ,cHTFcp 4.183 J g-1 K-1 ±3 % of ,cHTFcp 4.262 E-01 97
%
Condenser insulation conductance UAins,c 6.521 W K-1 ±0.4071 W K-1
1.056 E-02 1 %
HTF mass flow ,cHTFm 98.81 g s-1 ±0.23 g s-1 1.804 E-02 1 %
Condenser HTF thermopile voltage VTP,c 2.318