Please Read This Manual Congratulations on your purchase of an ActronAir air conditioning system. This unit has been designed and manufactured with the highest quality standard in mind. Please read this manual thoroughly and keep it near the unit for future reference. Esc Prg ® HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE Operating Instructions Copyright © 2013 Actron Engineering Pty. Ltd. All rights reserved. This manual is a controlled document which contains condential and proprietary information. Distribution, modication, copying and/or reproduction are prohibited without written consent from ActronAir. Model Number CP10

HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

Please Read This ManualCongratulations on your purchase of an ActronAir air conditioning system. This unit has been designed and manufactured with the highest quality standard in mind.

Please read this manual thoroughly and keep it near the unit for future reference.

Esc

Prg

®

HERCULES AIR CONDITIONING SYSTEMCONTROL INTERFACEOperating Instructions

Copyright © 2013 Actron Engineering Pty. Ltd. All rights reserved. This manual is a controlled document which contains confi dential and proprietary information.

Distribution, modifi cation, copying and/or reproduction are prohibited without written consent from ActronAir.

Model Number CP10

Page 2: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

2 HERCULES PACKAGE UNIT OPERATION MANUAL

CONTENTS

General Information ..................................................................................................... 3Storage & Operating Conditions .................................................................................. 4Waste Electrical & Electronic Equipment Disposal Guidelines .................................... 4Safety and Operational Precautions ............................................................................ 5 Parts & Components Identifi cation .............................................................................. 6Advanced Features ...................................................................................................... 7

Control Interface Functions ......................................................................................... 8Initialisation Displays - Status Indications .................................................................... 9Defrost Operation Indications ...................................................................................... 10Menu Tree Diagram (Consumer / End User Menu) ..................................................... 11Sub-Menu Level Descriptions ...................................................................................... 12Operation Mode ........................................................................................................... 13 Turn Unit ON / OFF via Control Interface ..................................................................... 14Setting Room Temperature .......................................................................................... 15Setting Supply Air Pressure Setpoint ........................................................................... 16 Setting Filter Pressure Alarm Setpoint ......................................................................... 17

Setting the Clock ......................................................................................................... 187- Day Programming .................................................................................................... 20After Hour Timer .......................................................................................................... 22Day Light Saving Time Enable ..................................................................................... 23Day Light Saving Time Disable .................................................................................... 25

Status (Read Only Menu) ............................................................................................ 26Data Logger (Read Only Menu) .................................................................................. 27

Dual Control Operation (Mimic Logic) .......................................................................... 28Controllers Compatibility Matrix for Dual Control ......................................................... 28Alarm Matrix ................................................................................................................ 29Trouble Shooting Guide ............................................................................................... 30Maintenance ................................................................................................................ 31System Information ..................................................................................................... 33

Basic Operation

General Information

7- Day Programming Operation

Monitoring Menu

Additional Features

Page 3: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

3Copyright © 2013 Actron Engineering Pty. Ltd.

CONGRATULATIONS! On your purchase of the latest ActronAir “Hercules” air conditioning system. With the application of an intelligent interactive software technology controller, this system has been designed to give you many years of reliable service and the convenience of menu-driven control. Your controller is manufactured from the highest quality materials and passed numerous “in house” and “external” inspection procedures to ensure years of satisfactory operation.

IN THIS MANUAL, You will fi nd instructions on how to program and utilise the many advanced features this controller has to offer. Please take time to familiarise yourself with all these features, apply their functions to suit your optimum comfort requirement and achieve energy cost savings at the same time. Thoroughly read this manual in order to ensure correct installation and the safe utilisation of your ActronAir air conditioner.

IMPORTANT NOTICE, ActronAir base the development of its air conditioning products on more than 20 years of experience in HVAC, sound & continuous investments in technological innovations and product improvements, advancement in manufacturing processes and quality control through 100% functional product testing. However, ActronAir cannot guarantee that all the aspects of the product and the software included with the product respond to the requirements of fi nal application, despite the product being developed according to state of the art technology. The customer, both end user/specifi er and installer, assume all liability and risks relating to the confi guration of the product in order to reach the expected results in relation to the specifi c design and system installation. ActronAir, based on specifi c agreements, may be consulted for the positive commissioning, installation and application of the unit, however in no case does ActronAir accept liability for the correct operation of the fi nal equipment / system.

Your ActronAir air conditioning unit is one of the most advanced & innovative products in the market. Its operation is specifi ed in the technical documentation supplied with the product or which can be downloaded from our website: www.actronair.com.au. Your air conditioner requires setup/confi guration/programming in order to be able to operate in the best possible way to suit your requirement. Failure to complete such operations, may result in malfunction and/or damage to the unit, for which ActronAir accepts no liability.

Installation, commissioning and other technical services must only be carried out by a qualifi ed technician. Ensure that the unit installation complies with all relevant council regulations and building code standards. All electrical wiring must be in accordance with current electrical authority regulations and all wiring connections to be as per electrical diagram provided. Always use appropriate PPE for your safety and protection. Make sure that any safety guards and covers are always fi rmly secured and not damaged. WH&S rules and regulations must be observed at all times and will take precedence during installation process and operation of the unit.

In addition, the following instructions must be observed:Prevent the electrical components and electronic circuits from getting wet.

Do not install the controlling devices in a particularly hot environment as extreme • temperatures may damage the electronic equipment.

Do not attempt to open the controller and other electronic devices in any way other than • described in this manual.

Do not drop, shake or hit the devices, which can cause irreparable damage to its internal • circuits and mechanisms.

GENERAL INFORMATION

Page 4: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

4 HERCULES PACKAGE UNIT OPERATION MANUAL

Do not use corrosive chemicals, solvents or other aggressive detergents to clean the unit • and the control interface.

Do not use the unit for applications other than those specifi ed in the technical manual. • Contact ActronAir for technical data.

Do not install the unit in environment with highly fl ammable, combustible and/or explosive • articles and materials.

The product, particularly the controlling devices, must be stored and installed in a location • that complies with the temperature and humidity limits specifi ed in this manual.

ActronAir is constantly seeking ways to improve the design of its products, therefore specifi cations are subject to change without prior notice. Please check with your Customer Care Department on toll free number: 1800 119 229.

Storage & Operating Conditions

Storage conditions: -20 to 70• oC, 90% RH non-condensingOperating conditions: -10 to 60• oC, 90% RH non-condensing

Waste Electrical & Electronic Equipment Disposal Guidelines 1. Do not dispose of the waste electrical & electronic equipment with local council waste. These must be disposed of through the council designated hazardous waste collection centre. 2. The terminal contains a battery that must be removed and separated from the rest of the product before disposing of the terminal. 3. The equipment may contain hazardous substances, improper or incorrect disposal 3. The equipment may contain hazardous substances, improper or incorrect disposal

may have a negative effect on human health and on the environment.may have a negative effect on human health and on the environment.

Page 5: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

5Copyright © 2013 Actron Engineering Pty. Ltd.

SAFETY AND OPERATIONAL PRECAUTIONS

Read all instructions in this manual before operating the air conditioning unit. Failure to Read all instructions in this manual before operating the air conditioning unit. Failure to 1. 1. do so may result in damage to the unit and void your warranty.do so may result in damage to the unit and void your warranty.Turn-Off power from mains supply by removing fuse or switching the circuit breaker to Turn-Off power from mains supply by removing fuse or switching the circuit breaker to 2. 2. the "Off" position before installation or servicing this control interface.the "Off" position before installation or servicing this control interface.Follow sound Lock Out & Tag Out procedures to ensure that power supply is not Follow sound Lock Out & Tag Out procedures to ensure that power supply is not 3. 3. re-energised accidentally. re-energised accidentally. This control interface has power supply from the control board via telephone connector, This control interface has power supply from the control board via telephone connector, 4. 4. with voltage of 18/30VDC protected by 250mAT external fuse & maximum power input of with voltage of 18/30VDC protected by 250mAT external fuse & maximum power input of 0.8W. Ensure that this unit is not installed on voltages higher than 30V DC supply.0.8W. Ensure that this unit is not installed on voltages higher than 30V DC supply.Installation and/or servicing must be carried out by a qualifi ed installer or technician.Installation and/or servicing must be carried out by a qualifi ed installer or technician.5. 5. Ensure that the unit installation complies with relevant council regulations and building Ensure that the unit installation complies with relevant council regulations and building 6. 6. code standards. All electrical wiring must be in accordance with current electrical code standards. All electrical wiring must be in accordance with current electrical authority regulations and all wiring connections to be as per electrical diagram provided.authority regulations and all wiring connections to be as per electrical diagram provided.WH&S rules and regulations must be observed and will take precedence during 7. installation process.Only use this wall controller with an ActronAir air conditioner as described in this 8. operating manual.

SAFETY PRECAUTIONS

OPERATIONAL PRECAUTIONS

ACCESS PANELS AND GUARDS: NEVER remove any access panels or guards as this could cause injury from electric shock and burns from extremely hot components. Never allow any bodily parts such as fi ngers or objects to protrude through the fan guards or any other opening as they could cause personal injury and damage the air conditioner.

RETURN AIR FILTER: The air conditioner must never be operated without a return air fi lter as this will allow a build up of dust or dirt on the indoor coil. This is very diffi cult to clean and can cause the system to operate ineffi ciently or even fail.

CRANKCASE HEATER PRECAUTION: The main power (switch board) to the system must be kept ON at all times to prevent damage to the outdoor compressor. Should the main power be disconnected or interrupted for 6 hours or longer, then no attempt should be made to start the system for 2 hours after the power has been restored to outdoor unit. This allows the compressor to warm up, and remove any liquid refrigerant that may cause damage.

Page 6: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

6 HERCULES PACKAGE UNIT OPERATION MANUAL

PARTS & COMPONENTS IDENTIFICATION

EC OUTDOOR FANS x 4

ACCESS DOORS - COMPRESSOR &

ELECTRICAL

MAIN ELECTRICAL ISOLATION SWITCH

ACCESS PANEL - AIR FILTERS

ACCESS DOOR - INDOOR FANS

OUTDOOR COIL -LOUVERED PANELS

ACCESS DOOR - CONTROLLER

ACCESS DOOR - RETURN AIR

CONTROL PANEL(Control Interface Mounted-in) CONTROL INTERFACE

(Remote Mounting)

INDOOR FANS SECTION

EC INDOOR FANS x 4

CONTROL INTERFACE(Factory Supplied & Fitted)

Page 7: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

7Copyright © 2013 Actron Engineering Pty. Ltd.

1 Menu Tree Based Program Navigation The control system features ease of operation via menu tree

2 LCD DisplayThe LCD displays the system mode, operation and fault diagnostics log.

3 Auto-Restart After Power FailureThe Hercules control system will automatically restart the air conditioner to the previous state after power failure.

4 7- Day Programmable Time ClockThe control panel can be programmed on each day of the week to turn ON and OFF in order to satisfy your requirement and to provide total control operation.

5 Dual Controller Operation ( Optional ) Two controllers can be installed on the Hercules system. This function is most suitable in the application of BMS control and remote monitoring. Either of the controllers can control the air conditioning system and mimic each other, displaying the same control parameters for ease of system control management.

6 Automatic Compressor Run Time ManagementThe operations of the two compressors are automatically managed in a way that the running time & load are equally distributed between the two compressors.

7 Auto Defrost Function (Heating Mode)At certain outdoor conditions (low temperature) there may be a build up of frost on the outdoor heat exchanger. This gradual build up of frost reduces the performance of the air conditioner. The Hercules control system detects this frost build up and will automatically activate the defrost mode.

8 Hot Start Function (Heating Mode)When the air conditioner starts in heating mode, the indoor fan is delayed for a short period of time, this allows the heat exchanger to warm up before the air fl ow starts, thus preventing cold drafts. The hot start feature also activates itself when the system fi nishes defrosting.

9 Fault DiagnosticsIn the unlikely event that a fault develops with the air conditioner the control system will diagnose the fault (where possible) and display a date & time stamped fault log, with up to 100 events memory.

10 Filter Pressure Alarm The control system automatically measures the air pressure differential between the air fi lters inlet and outlet sides. This is the Filter Pressure Alarm Setpoint, which when triggered sends an alarm fault log, indicating that the fi lters need to be checked for cleaning.

ADVANCE FEATURES

Page 8: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

8 HERCULES PACKAGE UNIT OPERATION MANUAL

CONTROL INTERFACE FUNCTIONS

CONTROL INTERFACE FRONT VIEW

LCD DisplayDisplays the setting and operation conditions (see menu page for details).

Alarm / Reset ButtonAlarm Indication and Reset Button.

Program ButtonTo bring-up programming Main Menu screen. (Display will revert back to default screen after 5 minutes idle time at any stage of programming).

1

2

3

ESC ButtonTo exit programming menu.

Scroll Up / Increment ButtonTo scroll up from existing menu or to increase setting parameter.

Enter ButtonTo lock the selected menu or to enter set parameters.

Scroll Down / Decrement ButtonTo scroll down from existing menu or to decrease setting parameter.

4

5

6

7

SYSTEM DEFAULT SCREEN

Return T. : 23.7oC16.4oC Supply T. :

Comp Rev Vlv Defrost

10:20 Unit: OFF by KEY

Current TimeUnit ON / OFF Indicator via Control Interface

Actual Return Air Temperature

Reversing Valve 2ON / OFF Indicator

Actual Supply AirTemperature

Defrost Cycle Indicator

Reversing Valve 1ON / OFF Indicator

(Dark Filled arrow indicates ON)Compressor 2ON / OFF Indicator

(Dark Filled arrow indicates ON)

Compressor 1ON / OFF Indicator

3

4

5

6

7

2

1

Return T. : 23.7oC16.4oC Supply T. :

Comp Rev Vlv Defrost

10:20 Unit: Unit ON

Esc

Prg

Page 9: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

9Copyright © 2013 Actron Engineering Pty. Ltd.

INITIALISATION DISPLAYS - STATUS INDICATIONS

POWER-UP (INITIALIZATION DISPLAYS COMPRESSORS & REVERSING VALVES STATUS INDICATIONS

Display Progression Display Progression

Esc

Prg

Esc

Prg Return T. : 23.7oC

16.4oC Supply T. :

Comp Rev Vlv

10:20 Unit: OFF by KEY

When the control interface is powered "ON" for the fi rst time, The display will be blank for 5 - 10 seconds

Both Compressors & Reversing Valves areOff, as indicated by clear triangles

Esc

Prg

Esc

Prg Return T. : 23.7oC

16.4oC Supply T. :

Comp Rev Vlv

10:20 Unit: Unit On

ActronAir logo will then be displayed for the next 5 - 10 seconds

Compressor 1 & Reversing Valve 1 are On.(System in Heat Mode), fi rst triangles are darkened

Return T. : 23.7oC16.4oC Supply T. :

Comp Rev Vlv Defrost

10:20 Unit: Unit ON

Esc

Prg

Esc

Prg Return T. : 23.7oC

16.4oC Supply T. :

Comp Rev Vlv

10:20 Unit: Unit On

System Screen (default) provides an overview of system status, showing the Return Temperature, Supply Temperature, Compressors, Reversing Valves ON/OFF status and System Defrost indicator.

Compressors 1 & 2 and Reversing Valves 1 & 2 are On. (Systems are in Heat Mode), all triangles are darkened

Page 10: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

10 HERCULES PACKAGE UNIT OPERATION MANUAL

Normal HeatingOperation

DEFROST OPERATION INDICATIONS

Compressor 1 Defrost Operation Compressor 2 Defrost Operation

Normal HeatingOperation

Call for Defrost System 1

Comp. 1 Off

Comp. 1 Off

Comp. 1 andRev. Valve 1 Off

Comp. 1 OnRev. Valve 1 Off

Comp. 1 Off Rev. Valve 1 On

Normal HeatingOperation

Defrost Complete

1.

2.

3.

7.

4.

5.

8.

9.

6.

Return T. : 23.7oC16.4oC Supply T. :

Comp Rev Vlv

10:20 Unit: Unit ON

Return T. : 23.7oC16.4oC Supply T. :

Comp Rev Vlv

10:21 Unit: Unit ON

Defrost

Return T. : 23.7oC16.4oC Supply T. :

Comp Rev Vlv

10:22 Unit: Unit ON

Defrost

Return T. : 23.7oC16.4oC Supply T. :

Comp Rev Vlv

10:22 Unit: Unit ON

Defrost

Return T. : 23.7oC16.4oC Supply T. :

Comp Rev Vlv

10:22 Unit: Unit ON

Defrost

Return T. : 23.7oC16.4oC Supply T. :

Comp Rev Vlv

10:23 Unit: Unit ON

Return T. : 23.7oC16.4oC Supply T. :

Comp Rev Vlv

10:23 Unit: Unit ON

Return T. : 23.7oC16.4oC Supply T. :

Comp Rev Vlv

10:23 Unit: Unit ON

Return T. : 23.7oC16.4oC Supply T. :

Comp Rev Vlv

10:26 Unit: Unit ON

Call for Defrost System 2

Comp. 2 Off

Comp. 2 Off

Comp. 2 andRev. Valve 2 Off

Comp. 2 OnRev. Valve 2 Off

Comp. 2 Off Rev. Valve 2 On

Normal HeatingOperation

Defrost Complete

1.

2.

3.

7.

4.

5.

8.

9.

6.

Return T. : 23.7oC16.4oC Supply T. :

Comp Rev Vlv

10:26 Unit: Unit ON

Return T. : 23.7oC16.4oC Supply T. :

Comp Rev Vlv

10:27 Unit: Unit ON

Defrost

Return T. : 23.7oC16.4oC Supply T. :

Comp Rev Vlv

10:27 Unit: Unit ON

Defrost

Return T. : 23.7oC16.4oC Supply T. :

Comp Rev Vlv

10:28 Unit: Unit ON

Defrost

Return T. : 23.7oC16.4oC Supply T. :

Comp Rev Vlv

10:27 Unit: Unit ON

Defrost

Return T. : 23.7oC16.4oC Supply T. :

Comp Rev Vlv

10:28 Unit: Unit ON

Return T. : 23.7oC16.4oC Supply T. :

Comp Rev Vlv

10:29 Unit: Unit ON

Return T. : 23.7oC16.4oC Supply T. :

Comp Rev Vlv

10:32 Unit: Unit ON

Return T. : 23.7oC16.4oC Supply T. :

Comp Rev Vlv

10:29 Unit: Unit ON

Page 11: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

11Copyright © 2013 Actron Engineering Pty. Ltd.

MENU TREE DIAGRAM

CONSUMER / END USER MENU

Main Menu

D. Clock

Day, Date, Hour, Scheduler

Day Light Saving Time

A / H duration

Auto

Cool Only

Fan Only

Heat Only

C. Mode of Operation50+o

C

10o

C-

E. Status

Return Temp Supply Temp Outside Temp

Cond. Temp 1 Cond. Temp 2 Low Press 1 High Press 1 Low Press 2 High Press 2

Supply Press Filter Press Disch Temp 1 Disch Temp 2

LP 1 Switch Ok / Fault HP 1 Switch Ok / Fault LP 2 Switch Ok / Fault HP 2 Switch Ok / Fault

Remote On / Off S / fan O / L Ok / Fault C/fan 1* O / L Ok / Fault C/fan 2** O / L Ok / Fault

Cond fan 1* speed % Cond fan 2** speed % Supply fan speed % Econ cycle speed %

Comp 1 ON/OFF Comp 1 req % Rev valve 1 On/Off Crankcase heater 1 On/Off

Comp 2 ON/OFF Comp 2 req % Rev valve 2 On/Off Crankcase heater 2 On/Off

Supply Fan 4 Parameters

EEV 2 Status

Outdoor Fan 4 Parameters

Log 100 - Recent Alarm

System 2 Suction Temp.

Supply Fan 1 Parameters

VSD 1 Status

Outdoor Fan 1 Parameters

System 1 Evaporating Temp.

Supply Fan 3 Parameters

EEV 1 Status

Outdoor Fan 3 Parameters

System 2 Evaporating Temp.

Supply Fan 2 Parameters

VSD 2 Status

Outdoor Fan 2 Parameters

System 1 Suction Temp.

F. Data logger

Log 1 - Recent Alarm

Log 3 - Recent Alarm

Log 2 - Recent Alarm

UP TO

A. On / Off Unit

Unit "ON"

Unit "OFF"

Room Setpoint

B. Setpoint

Supply Pressure Setpoint Filter Press. Alarm Setpoint

Note: To toggle (scroll) "Up" or "Down" from existing menu, press “ ” or “ ” Button.

** Fan 3 & 4

** Fan 3 & 4

* Fan 1 & 2

* Fan 1 & 2

Page 12: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

12 HERCULES PACKAGE UNIT OPERATION MANUAL

SUB-MENU LEVEL DESCRIPTIONS

Note: Only up to level 6 covered by this manual are accessible by the end user.

A. On/Off Unit Sub-Menu Level 1 Menu screen to Turn ON / OFF the unit.

B. Setpoint Sub-Menu Level 2 Menu screen to set the room temperature.

C. Mode of Operation Sub-Menu Level 3 Menu screen for selection of COOL, HEAT, FAN or AUTO CHANGEOVER operation.

D. Clock Sub-Menu Level 4 Menu screen to set the date & time.

E. Status Sub-Menu Level 5 Read only Menu screen to view the unit running conditions, such as Supply/Return Air temperature, Airfl ow, Outside temperature, Condensing temperatures, LP/HP, Supply Air pressure, Discharge Temperatures, Fans Speed, Variable Speed Drive operating conditions, etc..

F. Data logger Sub-Menu Level Read only Menu screen that indicates the alarm history

A. On / Off Unit B. Setpoint

Main Menu 1/8

C. Mode of Operation

A. On / Off Unit B. Setpoint

Main Menu 2/8

C. Mode of Operation

B. Setpoint

Main Menu 3/8

C. Mode of Operation

A. On / Off Unit

C. Mode of Operation B. Setpoint

Main Menu 4/8

D. Clock

Sub-Menu Level Indicator(Level 1 of 8 levels)

Sub-Menu Title(Description)

C. Mode of Operation

Main Menu 5/8

D. Clock E. Status

F. Data logger

Main Menu 6/8

D. Clock E. Status

Page 13: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

13Copyright © 2013 Actron Engineering Pty. Ltd.

OPERATION MODE

Display Progression

A. On / Off Unit B. Setpoint

Main Menu 1/8

C. Mode of Operation B. Setpoint

Main Menu 3/8

C. Mode of Operation

A. On / Off Unit

Heat / Cool

Mode: HEAT ONLY

Heat / Cool

Mode: HEAT ONLY

Step 1 Step 2 Step 3 Step 4

Heat / Cool

Mode: COOL ONLY

Heat / Cool

Mode: HEAT ONLY Mode: FAN ONLY

Heat / Cool Heat / Cool

Mode: A UTO CHANGE OVER

Step 5

Heat / Cool

Mode: COOL ONLY

B. Setpoint

Main Menu 3/8

C. Mode of Operation

A. On / Off Unit A. On / Off Unit B. Setpoint

Main Menu 1/8

C. Mode of Operation

Step 6 Step 7

Press 1. “Prg” Button to get into the Main Menu. Display will show Main Menu and highlighted Sub-Menu A. On / Off Unit.

Press 2. “ ” Button to scroll down into C. Mode of Operation sub-menu.

Press 3. “ ” Button to lock-in C. Mode of Operation sub-menu. Display will change into Heat / Cool mode selection menu showing COOL ONLY mode, HEAT ONLY mode, FAN ONLY mode or AUTO CHANGE OVER mode, depending on the previous mode selected.

Press 4. “ ” Button to change the mode and the cursor “ ” will be blinking at the fi rst letter of the current mode.

TO SELECT COOL ONLY MODE (from HEAT ONLY mode)Press 5. “ ” or “ ” Button to scroll into COOL ONLY mode. Display will show COOL ONLY mode with the cursor “ ” still blinking.

Press 6. “ ” Button to lock-in COOL ONLY mode, the cursor “ ” will disappear indicating that the operation is now in COOL ONLY mode.

Note: To Select HEAT ONLY, FAN ONLY or AUTO CHANGE OVER Mode, follow steps 4 to 6 above.

TO RETURN TO THE MAIN MENUKeep 7. pressing “Esc” (Escape/Return) Button until you get to the Main Menu screen

A. On / Off Unit B. Setpoint

Main Menu 1/8

C. Mode of OperationEsc

Prg

Page 14: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

14 HERCULES PACKAGE UNIT OPERATION MANUAL

TURN ON / OFF

Press 1. “Prg” Button to get into the Main Menu. Display will show Main Menu and highlighted Sub-Menu A. On / Off Unit. Press 2. “ ” Button to lock-in Sub-Menu A. On / Off Unit. Display will show the ON/OFF page with switch symbol pointing towards “OFF” position, indicating the unit is Turned-Off. (Symbol will be pointing towards "ON" position when unit is ON.

TO TURN-ON THE UNITPress 3. “ ” Button, the cursor “ ” will appear and blinking near “ON”.

Press 4. “ ” or “ ” Button to select switch “ON” position. Display will show the ON/OFF page with switch symbol pointing towards “ON” and the cursor “ ” still blinking.

Press 5. “ ” (Enter) Button to Turn-On the unit. The cursor “ ” will disappear and the unit will Turn-On.

TO TURN-OFF THE UNITRepeat Steps 1 & 2, then press 6. “ ” Button, cursor “ ” will appear and blinking near “ON”.

Press 7. “ ” or “ ” Button to select switch “OFF” position. Display will show the ON/OFF page with switch symbol pointing towards “OFF” and the cursor “ ” still blinking .

Press 8. “ ” Button to Turn-Off the unit. The cursor “ ” will disappear and the unit will Turn-Off.

TO RETURN TO THE MAIN MENUPress 9. “Esc” (Escape/Return) Button twice to return to the Main Menu. Otherwise press “Prg” Button.

Display Progression

A. On / Off Unit B. Setpoint

Main Menu 1/8

C. Mode of Operation

Heat / Cool

ON OFF ON OFF

Heat / Cool Heat / Cool

ON OFF

Step 1 Step 2 Step 3 Step 4

Heat / Cool

ON OFF

Heat / Cool

ON OFF ON OFF

Heat / Cool Heat / Cool

ON OFF

Step 5 Step 6 Step 7 Step 8

A. On / Off Unit B. Setpoint

Main Menu 1/8

C. Mode of Operation

Step 9

Heat / Cool

ON OFF

Esc

Prg

Page 15: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

15Copyright © 2013 Actron Engineering Pty. Ltd.

SETTING ROOM TEMPERATURE SETPOINT

Press 1. “Prg” Button to get into the Main Menu. Display will show Main Menu and highlighted Sub-Menu A. On / Off Unit.

Press 2. “ ” Button to scroll down into B. Setpoint sub-menu.

Press 3. “ ” Button to lock-in B. Setpoint sub-menu. “Room setpoint” (room set point temperature) screen will appear.

Press 4. “ ” Button cursor “ ” will appear and blink next to the setpoint temperature.

Press 5. “ ” or “ ” Button to change room temperature setting. Note: Temperature can be changed with an incremental/decremental value of 0.10C.

Press 6. “ ” Button to lock-in your desired room set point temperature. The cursor “ ” will disappear and the new room setpoint temperature will be displayed.

TO RETURN TO THE MAIN MENUKeep 7. pressing “Esc” (Escape/Return) Button until you get to the Main Menu screen. Otherwise press “Prg” Button.

Display Progression

A. On / Off Unit B. Setpoint

Main Menu 1/8

C. Mode of Operation

A. On / Off Unit B. Setpoint

Main Menu 2/8

C. Mode of Operation

Room Setpoint: 22.0oC

Setpoint

Room Setpoint: 22.0oC

Setpoint

Step 1 Step 2 Step 3 Step 4

Room Setpoint: 22.1oC

Setpoint

Room Setpoint: 22.0oC

Setpoint

A. On / Off Unit B. Setpoint

Main Menu 2/8

C. Mode of Operation

A. On / Off Unit B. Setpoint

Main Menu 1/8

C. Mode of Operation

Step 5 Step 6 Step 7

Esc

Prg Room Setpoint: 22.0oC

Setpoint

Page 16: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

16 HERCULES PACKAGE UNIT OPERATION MANUAL

SETTING SUPPLY AIR PRESSURE SETPOINT

Follow procedures 1-3 for Setting 1. Room Temperature on previous page to lock into B. Setpoint sub-menu.

Press 2. “ ” Button to scroll down into Supply Pressure Setpoint & Filter Alarm Setpoint screen. (Setpoint 02)

Press 3. “ ” Button to lock-in Setpoint 02 sub-menu. The cursor “ ” will appear next to the Supply Pressure Setpoint.

Press 4. “ ” or “ ” Button to change the Supply Pressure Setpoint. Note: Supply Pressure Setpoint can be changed with an incremental/decremental value of 1Pa.

Press 5. “ ” Button to lock-in your desired Supply Pressure Setpoint. The cursor “ ” will move next to the Filter Pressure Alarm Setpoint. (See next page for Setting Filter Pressure Alarm Setpoint procedures).

Press 6. “ ” Button again and the menu will prompt you to apply changes. The cursor “ ” will move to Apply changes now prompt, next to "No" answer.

Press 7. “ ” or “ ” Button to change prompt to "Yes".

Press 8. “ ” Button to lock-in the new Supply Pressure Setpoint.

TO RETURN TO THE MAIN MENUKeep 9. pressing “Esc” (Escape/Return) Button until you get to the Main Menu screen. Otherwise press “Prg” Button.

Display Progression

A. On / Off Unit B. Setpoint

Main Menu 1/8

C. Mode of Operation

A. On / Off Unit B. Setpoint

Main Menu 2/8

C. Mode of Operation

Room Setpoint: 22.0oC

Setpoint

Filter Pressure Alarm Setpoint: 300Pa

Supply Pressure Setpoint: 650Pa

Apply changes now ? : No

Setpoint 02

Step 1 Step 2

Filter Pressure Alarm Setpoint: 300Pa

Supply Pressure Setpoint: 650Pa

Apply changes now ? : No

Setpoint 02

Filter Pressure Alarm Setpoint: 300Pa

Supply Pressure Setpoint: 655Pa

Apply changes now ? : No

Setpoint 02

Filter Pressure Alarm Setpoint: 300Pa

Supply Pressure Setpoint: 655Pa

Apply changes now ? : No

Setpoint 02

Filter Pressure Alarm Setpoint: 300Pa

Supply Pressure Setpoint: 655Pa

Apply changes now ? : No

Setpoint 02

Step 3 Step 4 Step 5 Step 6

Filter Pressure Alarm Setpoint: 300Pa

Supply Pressure Setpoint: 655Pa

Apply changes now ? : Yes

Setpoint 02

Filter Pressure Alarm Setpoint: 300Pa

Supply Pressure Setpoint: 655Pa

Apply changes now ? : No

Setpoint 02

A. On / Off Unit B. Setpoint

Main Menu 2/8

C. Mode of Operation

A. On / Off Unit B. Setpoint

Main Menu 1/8

C. Mode of Operation

Step 7 Step 8 Step 9

Esc

Prg Filter Pressure Alarm Setpoint: 300Pa

Supply Pressure Setpoint: 650Pa

Apply changes now ? : No

Setpoint 02

Page 17: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

17Copyright © 2013 Actron Engineering Pty. Ltd.

SETTING FILTER PRESSURE ALARM SETPOINT

Esc

Prg Filter Pressure Alarm Setpoint: 300Pa

Supply Pressure Setpoint: 650Pa

Apply changes now ? : No

Setpoint 02

Follow procedures 1-3 for Setting 1. Pressure Setpoint on previous page to scroll down and lock into Supply Pressure Setpoint & Filter Alarm Setpoint screen (Setpoint 02). The cursor “ ” will appear next to the Supply Pressure Setpoint.

Press 2. “ ” Button to move the cursor “ ” down into Filter Pressure Alarm Setpoint.

Press 3. “ ” or “ ” Button to change the Filter Pressure Alarm Setpoint. Note: Filter Pressure Alarm Setpoint can be changed with an incremental/decremental value of

1Pa.

Press 4. “ ” Button to lock-in your desired Filter Pressure Alarm Setpoint and the menu will prompt you to apply changes. The cursor “ ” will move to Apply changes now prompt, next to "No" answer.

Press 5. “ ” or “ ” Button to change prompt to "Yes".

Press 6. “ ” Button to lock-in the new Filter Pressure Alarm Setpoint.

TO RETURN TO THE MAIN MENUKeep 7. pressing “Esc” (Escape/Return) Button until you get to the Main Menu screen. Otherwise press “Prg” Button.

Display Progression

A. On / Off Unit B. Setpoint

Main Menu 1/8

C. Mode of Operation

A. On / Off Unit B. Setpoint

Main Menu 2/8

C. Mode of Operation

Room Setpoint: 22.0oC

Setpoint

Filter Pressure Alarm Setpoint: 300Pa

Supply Pressure Setpoint: 650Pa

Apply changes now ? : No

Setpoint 02

Step 1

Filter Pressure Alarm Setpoint: 300Pa

Supply Pressure Setpoint: 650Pa

Apply changes now ? : No

Setpoint 02

Filter Pressure Alarm Setpoint: 299Pa

Supply Pressure Setpoint: 650Pa

Apply changes now ? : No

Setpoint 02

Filter Pressure Alarm Setpoint: 301Pa

Supply Pressure Setpoint: 650Pa

Apply changes now ? : No

Setpoint 02

Filter Pressure Alarm Setpoint: 310Pa

Supply Pressure Setpoint: 650Pa

Apply changes now ? : No

Setpoint 02

Step 2 Step 3 Step 4

Filter Pressure Alarm Setpoint: 310Pa

Supply Pressure Setpoint: 650Pa

Apply changes now ? : Yes

Setpoint 02

Filter Pressure Alarm Setpoint: 310Pa

Supply Pressure Setpoint: 650Pa

Apply changes now ? : No

Setpoint 02

A. On / Off Unit B. Setpoint

Main Menu 2/8

C. Mode of Operation

A. On / Off Unit B. Setpoint

Main Menu 1/8

C. Mode of Operation

Step 5 Step 6 Step 7

Page 18: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

18 HERCULES PACKAGE UNIT OPERATION MANUAL

Press 1. “Prg” Button to get into the Main Menu. Display will show Main Menu and highlighted Sub-Menu A. On / Off Unit.

Press 2. “ ” Button to scroll down into D. Clock sub-menu

Press 3. “ ” Button to lock-in D. Clock sub-menu. Display will show the Day, Date, Time page and Scheduler.

Press 4. “ ” Button and the cursor “ ” will appear next to the date indicator and the corresponding day will be shown,

i.e. Thursday, 06/09/12 (6th September 2012 ).

Press 5. “ ” or “ ” Button to change the date. Note: Day changes corresponding to the change in date, as follows: Wednesday, 05/09/12 (5th September 2012), Friday, 07/09/12 (7th September 2012).

Press 6. “ ” Button to lock-in the Date and the cursor “ ” will move next to the month indicator.

Press 7. “ ” or “ ” Button to change the month. Note: Day changes corresponding to the change in month as follows: Monday, 06/08/12 (8th August 2012), Saturday, 06/10/12 (6th October 2012).

Press 8. “ ” Button to lock-in the Month and the cursor “ ” will move next to the year date.

Press 9. “ ” or “ ” Button to change the year. Note: Day changes corresponding to the change in year as follows: Tuesday, 06/09/11 (6th September 2011), Friday, 06/09/13 (6th September 2013).

SETTING THE CLOCK ...

Esc

Prg Hour: 12:57 Enable Scheduler: No

Date: 06 / 09 / 12 Day: Thursday Clock

Display Progression

A. On / Off Unit B. Setpoint

Main Menu 1/8

C. Mode of Operation C. Mode of Operation B. Setpoint

Main Menu 4/8

D. Clock

Hour: 12:57 Enable Scheduler: No

Date: 06 / 09 / 12 Day: Thursday Clock

Hour: 12:57 Enable Scheduler: No

Date: 06 / 09 / 12 Day: Thursday Clock

Step 1 Step 2 Step 3 Step 4

Hour: 12:57 Enable Scheduler: No

Date: 05 / 09 / 12 Day: Wednesday Clock

Hour: 12:57 Enable Scheduler: No

Date: 07 / 09 / 12 Day: Friday Clock

Hour: 12:57 Enable Scheduler: No

Date: 06 / 09 / 12 Day: Thursday Clock

Hour: 12:57 Enable Scheduler: No

Date: 06 / 08 / 12 Day: Monday Clock

Step 5 Step 6 Step 7

Hour: 12:57 Enable Scheduler: No

Date: 06 / 10 / 12 Day: Saturday Clock

Hour: 12:57 Enable Scheduler: No

Date: 06 / 09 / 12 Day: Thursday Clock

Hour: 12:57 Enable Scheduler: No

Date: 06 / 09 / 11 Day: Tuesday Clock

Hour: 12:57 Enable Scheduler: No

Date: 06 / 09 / 13 Day: Friday Clock

Step 7 Step 8 Step 9

Page 19: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

19Copyright © 2013 Actron Engineering Pty. Ltd.

... SETTING THE CLOCK

Display Progression

Hour: 12:57 Enable Scheduler: No

Date: 06 / 09 / 12 Day: Thursday Clock

Hour: 11:57 Enable Scheduler: No

Date: 06 / 09 / 12 Day: Thursday Clock

Hour: 13:57 Enable Scheduler: No

Date: 06 / 09 / 12 Day: Thursday Clock

Hour: 12:57 Enable Scheduler: No

Date: 06 / 09 / 12 Day: Thursday Clock

Step 10 Step 11 (11:57) Step 11 (13:57) Step 12

Hour: 12:56 Enable Scheduler: No

Date: 06 / 09 / 12 Day: Thursday Clock

Hour: 12:58 Enable Scheduler: No

Date: 06 / 09 / 12 Day: Thursday Clock

Hour: 12:58 Enable Scheduler: No

Date: 06 / 09 / 12 Day: Thursday Clock

C. Mode of Operation B. Setpoint

Main Menu 4/8

D. Clock

Step 13 (12:56) Step 13 (12:58) Step 14 Step 15

A. On / Off Unit B. Setpoint

Main Menu 1/8

C. Mode of Operation

Step 15

Press 10. “ ” Button to lock-in the Year & Date and the cursor “ ” will move next to the hour indicator.

Press 11. “ ” or “ ” Button to change the hour.

Note: Hour can be changed with an incremental value of 1 hour.

Press 12. “ ” Button to lock-in the hour and the cursor “ ” will move next to the minute indicator.

Press 13. “ ” or “ ” Button to change the minute. Note: Minute can be changed with an incremental value of 1 minute.

Press 14. “ ” Button to lock-in the minute and the cursor “ ” will disappear. Set date & time are now locked-in.

TO RETURN TO THE MAIN MENUKeep 15. pressing “Esc” (Escape/Return) Button until you get to the Main Menu screen. Otherwise press “Prg” Button.

Note: Use the “ ” or “ ” Button to toggle on all of the D. Clock sub-menu functions.

Esc

Prg Hour: 12:57 Enable Scheduler: No

Date: 06 / 09 / 12 Day: Thursday Clock

Page 20: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

20 HERCULES PACKAGE UNIT OPERATION MANUAL

7-DAY PROGRAMMING ...

Display Progression

C. Mode of Operation B. Setpoint

Main Menu 4/8

D. Clock

Hour: 12:57 Enable Scheduler: No

Date: 06 / 09 / 12 Day: Thursday Clock

Hour: 12:58 Enable Scheduler: No

Date: 06 / 09 / 12 Day: Thursday Clock

Hour: 12:58 Enable Scheduler: Yes

Date: 06 / 09 / 12 Day: Thursday Clock

Step 1 Step 2 Step 3

Hour: 12:58 Enable Scheduler: Yes

Date: 06 / 09 / 12 Day: Thursday Clock

Mon 00:00 to 00:00 Tue 00:00 to 00:00 Wed 00:00 to 00:00 Thu 00:00 to 00:00 Fri 00:00 to 00:00 Sat 00:00 to 00:00 Sun 00:00 to 00:00

Clock Schedule 02 Mon 00:00 to 00:00 Tue 00:00 to 00:00 Wed 00:00 to 00:00 Thu 00:00 to 00:00 Fri 00:00 to 00:00 Sat 00:00 to 00:00 Sun 00:00 to 00:00

Clock Schedule 02 Mon 05:00 to 00:00 Tue 00:00 to 00:00 Wed 00:00 to 00:00 Thu 00:00 to 00:00 Fri 00:00 to 00:00 Sat 00:00 to 00:00 Sun 00:00 to 00:00

Clock Schedule 02

Step 4 Step 5 Step 6 Step 7

Mon 17:00 to 00:00 Tue 00:00 to 00:00 Wed 00:00 to 00:00 Thu 00:00 to 00:00 Fri 00:00 to 00:00 Sat 00:00 to 00:00 Sun 00:00 to 00:00

Clock Schedule 02 Mon 17:00 to 00:00 Tue 00:00 to 00:00 Wed 00:00 to 00:00 Thu 00:00 to 00:00 Fri 00:00 to 00:00 Sat 00:00 to 00:00 Sun 00:00 to 00:00

Clock Schedule 02 Mon 17:01 to 00:00 Tue 00:00 to 00:00 Wed 00:00 to 00:00 Thu 00:00 to 00:00 Fri 00:00 to 00:00 Sat 00:00 to 00:00 Sun 00:00 to 00:00

Clock Schedule 02 Mon 17:59 to 00:00 Tue 00:00 to 00:00 Wed 00:00 to 00:00 Thu 00:00 to 00:00 Fri 00:00 to 00:00 Sat 00:00 to 00:00 Sun 00:00 to 00:00

Clock Schedule 02

Step 7 Step 8 Step 9 (17:01) Step 9 (17:59)

From the main menu, scroll down 1. into D. Clock sub-menu following the procedures from Setting the Clock.

Press 2. “ ” Button repeatedly until the cursor “ ” get down into Enable Scheduler sub-menu

Press 3. “ ” or “ ” Button to prompt Enable Scheduler, "Yes" will replace "No" in this sub-menu with the cursor “ ” fl ashing.

Press 4. “ ” Button to enable the scheduler sub-menu, note the cursor “ ” will disappear.

Press 5. “ ” Button to scroll down into "Clock Schedule 02" sub-menu.

Press 6. “ ” Button to lock-in the Clock Scheduler sub-menu and the cursor “ ” will appear on Monday starting hour indicator.

Press 7. “ ” or “ ” Button to change the hour. Note: The time clock is in 24:00 format, i.e. 5:00 AM will be 05:00 and 5:00 PM will be 17:00.

Press 8. “ ” Button to lock-in the time and the cursor “ ” will move next to the minute indicator.

Press 9. “ ” or “ ” Button to change the minute.

Esc

Prg Hour: 12:57 Enable Scheduler: Yes

Date: 06 / 09 / 12 Day: Thursday Clock

Page 21: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

21Copyright © 2013 Actron Engineering Pty. Ltd.

... 7-DAY PROGRAMMING

Display Progression

Mon 17:00 to 00:00 Tue 00:00 to 00:00 Wed 00:00 to 00:00 Thu 00:00 to 00:00 Fri 00:00 to 00:00 Sat 00:00 to 00:00 Sun 00:00 to 00:00

Clock Schedule 02 Mon 17:00 to 22:30 Tue 00:00 to 00:00 Wed 00:00 to 00:00 Thu 00:00 to 00:00 Fri 00:00 to 00:00 Sat 00:00 to 00:00 Sun 00:00 to 00:00

Clock Schedule 02 Mon 17:00 to 22:30 Tue 18:00 to 21:30 Wed 19:00 to 21:00 Thu 19:00 to 21:00 Fri 18:00 to 22:30 Sat 08:00 to 18:00 Sun 10:00 to 17:00

Clock Schedule 02

C. Mode of Operation B. Setpoint

Main Menu 4/8

D. Clock

Step 10 Step 11 Step 12 Step 13

A. On / Off Unit B. Setpoint

Main Menu 1/8

C. Mode of Operation

Step 13

Press to lock-in Monday starting 10. time, the cursor will now move to Monday ending hour indicator.

Example: Monday starting time is set at 5:00 PM, i.e. 17:00.

Repeat steps 7- 10 to set up Monday 11.

ending time and the cursor will next move to Tuesday starting hour indicator.

Example: Monday ending time is set at 10:30 PM, i.e. 22:30.

Repeat steps 7- 12 to set up the succeeding days programming start and end times. 12. Note: The scheduled program for each nominated day will be in operation every time each nominated day occurs during the year, i.e. the program for Monday will be repeated on every Monday, until the program is revised.

The scheduled time may need to be synchronized with the daylight saving time. See daylight saving time set-up procedures.

TO RETURN TO THE MAIN MENUKeep 13. pressing “Esc” (Escape/Return) Button until you get to the Main Menu screen. Otherwise press “Prg” Button.

Note: Use the “ ” or “ ” Button to toggle on all of the D. Clock sub-menu functions.

Esc

Prg Hour: 12:57 Enable Scheduler: Yes

Date: 06 / 09 / 12 Day: Thursday Clock

Page 22: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

22 HERCULES PACKAGE UNIT OPERATION MANUAL

AFTER HOUR TIMER

Display Progression

C. Mode of Operation B. Setpoint

Main Menu 4/8

D. Clock

Hour: 12:58 Enable Scheduler: Yes

Date: 06 / 09 / 12 Day: Thursday Clock

Mon 17:00 to 22:30 Tue 18:00 to 21:30 Wed 19:00 to 21:00 Thu 19:00 to 21:00 Fri 18:00 to 22:30 Sat 08:00 to 18:00 Sun 10:00 to 17:00

Clock Schedule 02

A / H duration: 0 H

Clock 03

Step 1 Step 2

A / H duration: 0 H

Clock 03

A / H duration: 1 H

Clock 03

A / H duration: 8 H

Clock 03

A / H duration: 1 H

Clock 03

Step 3 Step 4 Step 5

C. Mode of Operation B. Setpoint

Main Menu 4/8

D. Clock

A. On / Off Unit B. Setpoint

Main Menu 1/8

C. Mode of Operation

Step 6

From the main menu, scroll down 1. into D. Clock sub-menu following the procedures from Setting the Clock section.

Press 2. “ ” Button to scroll down into A / H duration sub-menu.

Press 3. “ ” Button to lock-in A / H duration sub-menu and the cursor “ ” will appear on After Hour time indicator.

Press 4. “ ” or “ ” Button to select the duration of after hour timer. Note: The duration of the after hour timer can be set in 1 hour increment up to 8 hour maximum.

Press 5. “ ” Button to lock-in the selected after hour duration, note the cursor “ ” will disappear and the selected duration will be displayed. i.e. 1 hour (1 H).

TO RETURN TO THE MAIN MENUKeep 6. pressing “Esc” (Escape/Return) Button until you get to the Main Menu screen. Otherwise press “Prg” Button.

Esc

Prg A / H duration: 0 H

Clock 03

Note: Use the “ ” or “ ” Button to toggle on all of the D. Clock sub-menu functions.

Page 23: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

23Copyright © 2013 Actron Engineering Pty. Ltd.

DAYLIGHT SAVING TIME ENABLE ...

Display Progression

C. Mode of Operation B. Setpoint

Main Menu 4/8

D. Clock

Clock DST: ENABLE Transition time: --- min Start: --- --- --- in --- --- --- at --- .00 End: --- --- --- in --- --- --- at --- .00

Clock DST: ENABLE Transition time: --- min Start: --- --- --- in --- --- --- at --- .00 End: --- --- --- in --- --- --- at --- .00

Clock DST: ENABLE Transition time: --- min Start: --- --- --- in --- --- --- at --- .00 End: --- --- --- in --- --- --- at --- .00

Step 1 Step 2 Step 3 Step 4

Clock DST: ENABLE Transition time: 01 min Start: --- --- --- in --- --- --- at --- .00 End: --- --- --- in --- --- --- at --- .00

Clock DST: ENABLE Transition time: 60 min Start: --- --- --- in --- --- --- at --- .00 End: --- --- --- in --- --- --- at --- .00

Clock DST: ENABLE Transition time: 60 min Start: --- --- --- in --- --- --- at --- .00 End: --- --- --- in --- --- --- at --- .00

Clock DST: ENABLE Transition time: 60 min Start: FIRST SUNDAY in --- --- --- at --- .00 End: --- --- --- in --- --- --- at --- .00

Step 5 Step 6 Step 7

Clock DST: ENABLE Transition time: 60 min Start: LAST SUNDAY in --- --- --- at --- .00 End: --- --- --- in --- --- --- at --- .00

Clock DST: ENABLE Transition time: 60 min Start: FIRST SUNDAY in --- --- --- at --- .00 End: --- --- --- in --- --- --- at --- .00

Clock DST: ENABLE Transition time: 60 min Start: FIRST SUNDAY in JANUARY at --- .00 End: --- --- --- in --- --- --- at --- .00

Clock DST: ENABLE Transition time: 60 min Start: FIRST SUNDAY in OCTOBER at --- .00 End: --- --- --- in --- --- --- at --- .00

Step 7 Step 8 Step 9 (January) Step 9 (October)

From the main menu, scroll down 1. into D. Clock sub-menu following the procedures from Setting the Clock section.

Press 2. “ ” Button to scroll down into Daylight Saving Time sub-menu.

Press 3. “ ” Button to lock-in Daylight Saving Time sub-menu and the cursor “ ” will appear on "ENABLE" indicator.

Press 4. “ ” Button again to enable Daylight Saving Time mode and the cursor “ ” will move to the "Transition time" segment.

Press 5. “ ” or “ ” Button to select the number of minutes for transition into daylight saving time.. Note: The transition time can be set in 1 minute increment up to 60 minutes maximum.

Press 6. “ ” Button to lock-in the selected length of transition time, i.e. 60min. The cursor “ ” will next move into the Sunday for the start of the transition to occur.

Press 7. “ ” or “ ” Button to select the "Sunday" for the transition into daylight saving time. Note: The "Sunday" transition can be set as First Sunday, Second... Fourth or Last Sunday.

Press 8. “ ” Button to lock-in the Sunday for the transition to occur, i.e. FIRST SUNDAY. The cursor “ ” will next move into the starting month selection segment.

Press 9. “ ” or “ ” Button to select the "Month" for the transition into daylight saving time.

Press 10. “ ” Button to lock-in the Month for the transition to occur, i.e. October. The cursor “ ” will next move into the starting time selection segment.

Esc

Prg

Clock DST: ENABLE Transition time: 60min Start: LAST SUNDAY End: LAST SUNDAY in MARCH at 2.00 in OCTOBER at 3.00

Page 24: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

24 HERCULES PACKAGE UNIT OPERATION MANUAL

... DAYLIGHT SAVING TIME ENABLE

Display Progression

Clock DST: ENABLE Transition time: 60 min Start: FIRST SUNDAY in OCTOBER at --- .00 End: --- --- --- in --- --- --- at --- .00

Clock DST: ENABLE Transition time: 60 min Start: FIRST SUNDAY in OCTOBER at 2.00 End: --- --- --- in --- --- --- at --- .00

Clock DST: ENABLE Transition time: 60 min Start: FIRST SUNDAY in OCTOBER at 16.00 End: --- --- --- in --- --- --- at --- .00

Clock DST: ENABLE Transition time: 60 min Start: FIRST SUNDAY in OCTOBER at 2.00 End: --- --- --- in --- --- --- at --- .00

Step 10 Step 11 (2.00) Step 11 (16.00) Step 12

Clock DST: ENABLE Transition time: 60 min Start: FIRST SUNDAY in OCTOBER at 2.00 End: FIRST SUNDAY in --- --- --- at --- .00

Clock DST: ENABLE Transition time: 60 min Start: FIRST SUNDAY in OCTOBER at 2.00 End: FIRST SUNDAY in APRIL at --- .00

Clock DST: ENABLE Transition time: 60 min Start: FIRST SUNDAY in OCTOBER at 2.00 End: FIRST SUNDAY in APRIL at 3.00

C. Mode of Operation B. Setpoint

Main Menu 4/8

D. Clock

Step 13 Step 14 Step 15

A. On / Off Unit B. Setpoint

Main Menu 1/8

C. Mode of Operation

Step 15

Press 11. “ ” or “ ” Button to select the "hour" on the Sunday for the transition into daylight saving time.

Note: The time clock is in 24:00 format, i.e. 2:00 AM will be 2.00 and 8:00 PM will be 20.00.

Press 12. “ ” Button to lock-in the time on the Sunday for the transition to occur, i.e. 2.00. The cursor “ ” will next move into the Sunday for the transition to end.

Repeat steps 7- 11 to set up the end of Daylight Saving Time parameters.13.

Press 14. “ ” Button to enable the Daylight Saving Time and lock-in the parameters. TO RETURN TO THE MAIN MENU

Keep 15. pressing “Esc” (Escape/Return) Button until you get to the Main Menu screen. Otherwise press “Prg” Button.

Note: Use the “ ” or “ ” Button to toggle on all of the D. Clock sub-menu functions.

Esc

Prg

Clock DST: ENABLE Transition time: 60min Start: LAST SUNDAY End: LAST SUNDAY in OCTOBER at 2.00 in APRIL at 3.00

Page 25: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

25Copyright © 2013 Actron Engineering Pty. Ltd.

DAYLIGHT SAVING TIME DISABLE

Display Progression

C. Mode of Operation B. Setpoint

Main Menu 4/8

D. Clock

Clock DST: ENABLE Transition time: 60 min Start: FIRST SUNDAY in OCTOBER at 2.00 End: FIRST SUNDAY in APRIL at 3.00

Clock DST: ENABLE Transition time: 60min Start: FIRST SUNDAY in OCTOBER at 2.00 End: FIRST SUNDAY in APRIL at 3.00

Clock DST: DISABLE Transition time: 60min Start: FIRST SUNDAY in OCTOBER at 2.00 End: FIRST SUNDAY in APRIL at 3.00

Step 1 Step 2 Step 3 Step 4 (DISABLE)

Clock DST: DISABLE Transition time: _ --- min Start: --- --- --- in --- --- --- at --- .00 End: --- --- --- in --- --- --- at --- .00

C. Mode of Operation B. Setpoint

Main Menu 4/8

D. Clock

A. On / Off Unit B. Setpoint

Main Menu 1/8

C. Mode of Operation

Step 5 Step 6

From the main menu, scroll down 1. into D. Clock sub-menu following the procedures from Setting the Clock section.

Press 2. “ ” Button to scroll down into Daylight Saving Time sub-menu.

Press 3. “ ” Button to lock-in Daylight Saving Time sub-menu and the cursor “ ” will appear on "ENABLE" indicator.

Press 4. “ ” or “ ” Button to select the "DISABLE" Daylight Saving Time function. Note: The segment will change from "ENABLE" to "DISABLE".

Press 5. “ ” Button to disable the Daylight Saving Time function. The cursor will disappear and the "DISABLE" sub-menu screen will be displayed.

TO RETURN TO THE MAIN MENUKeep 6. pressing “Esc” (Escape/Return) Button until you get to the Main Menu screen. Otherwise press “Prg” Button.

Notes: 1. Use the “ ” or “ ” Button to toggle on all of the D. Clock sub-menu functions. 2. The programmed Day Light Saving Time parameters will be retained for next time Day Light Saving Time is enabled.

Esc

Prg

Clock DST: DISABLE Transition time: - - - min Start: - - - - - - - - - End: - - - - - - - - - in - - - - - - - - - at - - - .00 in - - - - - - - - - at - - - .00

Page 26: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

26 HERCULES PACKAGE UNIT OPERATION MANUAL

Display Progression

A. On / Off Unit B. Setpoint

Main Menu 1/8

C. Mode of Operation

C. Mode of Operation

Main Menu 5/8

D. Clock E. Status

Return Temp. : 22.8oC

Outside Temp. : 8.9oC Supply Temp. : 18.0oC

Status AIN 01 Cond. Temp. 1: 21.2oC

Low Press. 2: 52.6 B Low Press. 1: 13.4 B Cond. Temp. 2: 19.0oC

High Press. 2: 50.4 B High Press. 1: 13.4 B

Status AIN 02

Step 1 Step 2 Step 3 Step 4

Supply Vol. : 9002Ls Supply Press. : 350Pa Filter Press. : 3Pa Disch. Temp.1 : 6oC Disch. Temp.2 22oC

Status AIN 03 Compressor 1: Off

Rev. Valve 1: Off Comp Request 1: 0.0

Crank Heater 1: Off

Status DOUT 10 Condenser 1 Fan: 80%

Supply Fan: 100% Condenser 2 Fan: 60%

Economy Cycle: 20%

Status AOUT 09

C. Mode of Operation

Main Menu 5/8

D. Clock E. Status

Step 5 Step 6 Step 7

A. On / Off Unit B. Setpoint

Main Menu 1/8

C. Mode of Operation

Step 7

STATUS (Read Only Menu)

Esc

Prg Return Temp.: 23.8oC

Outside Temp.: 27.6oC Supply Temp.: 22.0oC

Input / Output_AIN 01

Press 1. “Prg” Button to get into the Main Menu. Display will show Main Menu and highlighted Sub-Menu A. On / Off Unit.

Press 2. “ ” Button to scroll down into E. Status sub-menu.

Press 3. “ ” Button to lock-in E. Status sub-menu. Display will show the fi rst screen under this sub-menu.

Press 4. “ ” Button to scroll down into the second screen and view the operating parameters.

Press 5. “ ” Button repeatedly to scroll down into the next succeeding operating parameter screens.

Press 6. “ ” Button to scroll up and to view the previews screens.

TO RETURN TO THE MAIN MENUKeep 7. pressing “Esc” (Escape/Return) Button until you get to the Main Menu screen. Otherwise press “Prg” Button.

Page 27: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

27Copyright © 2013 Actron Engineering Pty. Ltd.

DATA LOGGER (Read Only Menu)

Esc

Prg Return Temp.: 18.4oC

Supply fan1 offl ine Supply Temp.: 18.9oC

Alarm History AL28 No 015 15:32 06 / 09 / 12

Press 1. “Prg” Button to get into the Main Menu. Display will show Main Menu and highlighted Sub-Menu A. On / Off Unit.

Press 2. “ ” Button to scroll down into F. Data logger sub-menu.

Press 3. “ ” Button to lock-in F. Data logger sub-menu. Display will show the fi rst screen under this sub-menu.

Note: Data logger is time & date stamped.

Press 4. “ ” Button to scroll down into the second screen and view the alarm history.

Press 5. “ ” Button repeatedly to scroll down into the next succeeding screens and view the other alarm log.

Press 6. “ ” Button to scroll up and to view the previews alarm history screens.

TO RETURN TO THE MAIN MENUKeep 7. pressing “Esc” (Escape/Return) Button until you get to the Main Menu screen. Otherwise press “Prg” Button.

TO RESET THE ALARM

Press the “ 8. ” Button twice to reset or clear the alarm.

Display Progression

A. On / Off Unit B. Setpoint

Main Menu 1/8

C. Mode of Operation F. Data logger

Main Menu 6/8

D. Clock E. Status

Return Temp.: 18.4oC

Supply fan1 offl ine Supply Temp.: 18.9oC

Alarm History AL28 No 015 15:32 06 / 09 / 12

Return Temp.: 18.3oC

Outdoor fan 2 offl ine Supply Temp.: 18.8oC

Alarm History AL30 No 018 16:02 06 / 09 / 12

Step 1 Step 2 Step 3 Step 4

Return Temp.: 18.3oC

Outdoor fan 1 offl ine Supply Temp.: 18.8oC

Alarm History AL29 No 016 15:52 06 / 09 / 12

Return Temp.: 18.3oC

Outdoor fan 2 offl ine Supply Temp.: 18.8oC

Alarm History AL30 No 018 16:02 06 / 09 / 12

F. Data logger

Main Menu 6/8

D. Clock E. Status

A. On / Off Unit B. Setpoint

Main Menu 1/8

C. Mode of Operation

Step 5 Step 6 Step 7

Important Note: All alarm fault conditions must be investigated and rectifi ed before proceeding to reset or clear the alarm. If the cause of the fault condition has not been eliminated, the alarm fault conditions will be reported and logged in again on next data cycle. Repeated resetting and restarting can cause damage to the unit and may invalidate the warranty.

Page 28: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

28 HERCULES PACKAGE UNIT OPERATION MANUAL

DUAL CONTROL OPERATION

MIMIC CONTROL OPERATION

The air conditioning system can be operated from either of the two control interfaces.• Information displayed on the control interfaces are identical.• Last control interface used has the priority.•

Example 1:Using Control Interface # 1, the cooling operation is started, both control interfaces will nowshow the system is in cooling mode. If another person uses Control Interface # 2 to select heating mode, the system will now change to heating operation and both controls will display that the system is in heating mode.

Example 2:Using Control Interface # 2, the Room Setpoint temperature is set at 16.0oC, both controlinterfaces will now show that the room setpoint temperature is at 16.0oC. If another person uses Control Interface # 1 to change the setpoint temperature to 18.0oC, the system will now be operating at the new Room Setpoint Temperature and both controls will display thesame setpoint temperature.

MIMIC CONTROL

Controllers Compatibility Matrix for Dual Control

Combination Options Controller Controller

Option 1 ActronAir Control Interface ActronAir Control Interface

Option 2 ActronAir Control Interface BMS Controller

* Example above is for illustration purposes only and shows that Control Interface #1 remotely re-located from the air conditioning unit.

S H O P P I N G C E N T R E

PLANT ROOM

ACTRONAIRHERCULES UNIT

CONTROLINTERFACE # 1 *

CONTROL ROOM

CONTROLINTERFACE # 2

(Optional)

Page 29: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

29Copyright © 2013 Actron Engineering Pty. Ltd.

ALARM MATRIX

Serial Number Description Type Start Condition Stop Condition

1 Compressor 1 HP fault Alarm Pd > 4216kPA Pd < 2647kPa2 Compressor 2 HP fault Alarm Pd > 4216kPA Pd < 2647kPa3 Compressor 1 LP fault Alarm Ps < 401kPa Ps > 686kPa4 Compressor 2 LP fault Alarm Ps < 401kPa Ps > 686kPa

5 Compressor 1 overload Alarm Drive alarm high current Current less than 90% of maximum

6 Compressor 2 overload Alarm Drive alarm high current Current less than 90% of maximum

7 Compressor 1 offl ine Alarm Communication loss Communication OK8 Compressor 2 offl ine Alarm Communication loss Communication OK9 Evaporator Fan 1 offl ine Alarm Communication loss Communication OK10 Evaporator Fan 2 offl ine Alarm Communication loss Communication OK11 Evaporator Fan 3 offl ine Alarm Communication loss Communication OK12 Evaporator Fan 4 offl ine Alarm Communication loss Communication OK13 Condenser Fan 1 offl ine Alarm Communication loss Communication OK14 Condenser Fan 2 offl ine Alarm Communication loss Communication OK15 Condenser Fan 3 offl ine Alarm Communication loss Communication OK16 Condenser Fan 4 offl ine Alarm Communication loss Communication OK

17 Probe 1 Faulty / Wiring open or short circuit Warning Return Air temperature

sensor fault Sensor OK

18 Probe 2 Faulty / Wiring open or short circuit Warning Supply Air temperature

sensor fault Sensor OK

19 Probe 3 Faulty / Wiring open or short circuit Alarm Suction Comp 1

temperature sensor fault Sensor OK

20 Probe 4 Faulty / Wiring open or short circuit Alarm Suction Comp 2

temperature sensor fault Sensor OK

21 Probe 6 Faulty / Wiring open or short circuit Alarm Low pressure Comp 1

temperature sensor fault Feedback signal OK

22 Probe 7 Faulty / Wiring open or short circuit Alarm Low pressure Comp 2

temperature sensor fault Feed back signal OK

23 Probe 8 Faulty / Wiring open or short circuit Warning Outdoor coil Comp 1

temperature sensor fault Sensor OK

24 Probe 9 Faulty / Wiring open or short circuit Warning Outdoor coil Comp 2

temperature sensor fault Sensor OK

25 Probe 10 Faulty / Wiring open or short circuit Warning Outside air temperature

sensor fault Sensor OK

26 Probe 11 Faulty / Wiring open or short circuit Alarm High Pressure Comp 1

pressure sensor fault Feed back signal OK

27 Probe 12 Faulty / Wiring open or short circuit Alarm High Pressure Comp 2

pressure sensor fault Feed back signal OK

28 Filter Differential Pressure alarm Warning Filter Dirty Filter Clean

29 Filter Differential Pressure sensor fault Warning Air pressure < 15 Pa and

fan speed > 250rpmAir pressure > 15 Pa and fan speed > 250rpm

30 Supply Air pressure sensor fault Warning Air pressure < 15 Pa and

fan speed > 250rpmAir pressure > 15 Pa and fan speed > 250rpm

Page 30: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

30 HERCULES PACKAGE UNIT OPERATION MANUAL

CONDITION PROBABLE CAUSE RECOMMENDED ACTIONS / CHECKPOINTS

Unit will not operate

No Power to the unitNo power to the variable speed driveUnit under fault condition

Check whether the mains power switch is ON.Check whether the Drive Circuit breakers are switched ON.Check the Fault details.

Unit will not Cool or Heat, only Fan operates

The mode of operation is “Fan only”.Indoor condition is equal to the set point

Set the correct mode of operation.Try setting the min setpoint for Cooling 16ºC (If cooling required).Try setting the max setpoint for Heating 28ºC (If heating required)

Unit Cools or Heats, but will not control to setpoint

Return air sensor is defective.Return air sensor wrongly calibrated.

Check the Alarm on the Control Interface.Need to correct the calibration through service

Compressor 1 or 2 will not operate, outdoor fan will operate

Head pressure highDischarge pressure sensor faulty.

Check the Alarm on the Control Interface.

Compressor 1 or 2 will not operate, outdoor fan will also not operate

The mode of operation is “Fan Only”. Set the correct mode of operation

Outdoor Motor will not operate

Motor in fault.Head pressure not above the set limit for the fan to start.

Check the Alarm on the Control Interface.Need to correct the setpoint through service.

Indoor Motor will not operate

Motor in fault.Supply air pressure sensor faulty.

Check the Alarm on the Control Interface.

Crankcase Heater will not operate

Heater contactor has failed.Heater element has failed.Wiring or terminal failure

Check the Crankcase heater switching setting through service. Replace heater element through service.Check wiring or terminal and replace as required through service.

TROUBLE SHOOTING GUIDE

Page 31: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

31Copyright © 2013 Actron Engineering Pty. Ltd.

TROUBLE SHOOTING GUIDE

CONDITION PROBABLE CAUSE RECOMMENDED ACTIONS / CHECKPOINTS

Evaporator coil freezes up during low ambient operation

System low on refrigerant.System low on airfl ow.Outdoor air sensor failure.

Check the pressures and the temps for suction and discharge.Check the ID fan airfl ow through the Control Interface.Check the Alarm on the Control Interface.

Economiser, outside air and/or spill air will not operate

Economiser connector not plugged into unit wiring harnessEconomiser, outside air, and/or spill air motor has failed.Wiring or terminal failure

Check the connection.Motor wiring to be checked and replaced as required.Wiring or terminal to be checked and replaced as required.

Control Interface keys not operating

Control Interface hanged.RJ12 cable failure.

Reset the power to the Control Interface by turning it OFF/ON.Replace RJ12 cable through service.

Control Interface does not power up

Wiring fault.RJ12 cable fault.

Wiring to be checked as per the wiring diagram.Replace RJ12 cable through service.

Page 32: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

32 HERCULES PACKAGE UNIT OPERATION MANUAL

MAINTENANCE

Maintenance ProceduresMaintenance ProceduresThis section describes the specifi c maintenance procedures that must be performed as a part of This section describes the specifi c maintenance procedures that must be performed as a part of normal maintenance program. Always disconnect electrical power to the unit before performing these normal maintenance program. Always disconnect electrical power to the unit before performing these procedures. It is always a safe practice to observe all safety warnings and cautions when conducting procedures. It is always a safe practice to observe all safety warnings and cautions when conducting maintenance tasks. maintenance tasks.

Live Electrical Connections !It may be necessary to work near live electrical components on certain maintenance tasks. Only licensed electricians and/or qualifi ed technicians who are competently trained are allowed to perform service tasks.

DANGER

Hazardous Voltage !Always make sure that all power supplies, including remote controls, are isolated before performing maintenance. Observe proper Lock-Out / Tag-Out procedures to ensure that power cannot be inadvertently energised. Failure to isolate power before maintenance procedures can result in serious injury or death.

WARNING

Periodic Maintenance CheckpointPeriodic Maintenance CheckpointPerform all monthly maintenance inspectionsPerform all monthly maintenance inspections• • Inspect coil surfaces for cleanliness. Clean as Inspect coil surfaces for cleanliness. Clean as • •

required, apply cleaning procedures based on required, apply cleaning procedures based on prevailing industry standard. prevailing industry standard.

Inspect unit air fi lters, clean or replace as Inspect unit air fi lters, clean or replace as • • required. required.

Annual Maintenance ChecklistsAnnual Maintenance ChecklistsPerform general maintenance inspections.Perform general maintenance inspections.• • Perform scheduled start-up checks.Perform scheduled start-up checks.• • Leak test refrigerant circuits. Leak test refrigerant circuits. • • Inspect contacts of all contactors and relays. Inspect contacts of all contactors and relays. • •

Replace all worn contacts as required.Replace all worn contacts as required.Inspect, clean and tighten all electrical Inspect, clean and tighten all electrical • •

connections.connections.Check fans for balanced operation. Make Check fans for balanced operation. Make • •

sure that there are no loose screws/bolts, no sure that there are no loose screws/bolts, no fan blades interference and no damage to the fan blades interference and no damage to the fans and guards.fans and guards.

Inspect unit air fi lters, clean or replace as Inspect unit air fi lters, clean or replace as • • required.required.

Clean and repaint any corroded panel Clean and repaint any corroded panel • • surface.surface.

Cleaning the Control InterfaceCleaning the Control InterfaceWipe the control interface with dry cloth. Do not Wipe the control interface with dry cloth. Do not use water or any other solvent base solutions use water or any other solvent base solutions as it can cause damage to the outer case and as it can cause damage to the outer case and electronic components of the controller.electronic components of the controller.

Air Filter Maintenance.Air Filter Maintenance.Regularly check the air fi lters for cleanliness or Regularly check the air fi lters for cleanliness or when a fi lter alarm is indicated on the control when a fi lter alarm is indicated on the control interface. interface.

Cleaning the Condenser CoilsCleaning the Condenser CoilsClean the coils at least once a year or more Clean the coils at least once a year or more frequently if unit is located in a dusty and/or dirty frequently if unit is located in a dusty and/or dirty environment, in order to maintain your system’s environment, in order to maintain your system’s proper operating performance. High discharge proper operating performance. High discharge pressures are a good indication that the coils pressures are a good indication that the coils need cleaning. When using detergent or solvents need cleaning. When using detergent or solvents to clean the coils, follow the manufacturer’s to clean the coils, follow the manufacturer’s instructions to avoid potential damage to the coils instructions to avoid potential damage to the coils and to the unit. and to the unit.

To clean the refrigerant coils, use a soft brush To clean the refrigerant coils, use a soft brush and water spray, such as garden hose or and water spray, such as garden hose or pressure washer with low pressure nozzle. pressure washer with low pressure nozzle.

Outdoor MaintenanceOutdoor MaintenanceDo not obstruct airfl ow to the outdoor coil to Do not obstruct airfl ow to the outdoor coil to ensure your air conditioner operates effi ciently. ensure your air conditioner operates effi ciently. Use light detergent solutions to clean the surface Use light detergent solutions to clean the surface of the panels. Repaint corroded panel surface, as of the panels. Repaint corroded panel surface, as required. required.

Page 33: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

33Copyright © 2013 Actron Engineering Pty. Ltd.

SYSTEM INFORMATION

UNIT INFORMATION

Model Number : Serial Number :

The air conditioner model and serial number is situated on the side panel of the unit’s bottom left corner, near the compressor compartment.

Date Installed :

INSTALLER INFORMATION

Company Name :

Address :

Tel. Number : Fax. Number :

Technician - Name :

Tel. Number : Fax. Number :

CUSTOMER INFORMATION

Name : Tel. Number :

Address :

Page 34: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

34 HERCULES PACKAGE UNIT OPERATION MANUAL

NOTES

Page 35: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

35Copyright © 2013 Actron Engineering Pty. Ltd.

THIS PAGE INTENTIONALLY LEFT BLANK

Page 36: HERCULES AIR CONDITIONING SYSTEM CONTROL INTERFACE ...climatemaster.com.au/.../0525-022-HERCULES-OP-MAN-VERSION-2.… · 2 LCD Display The LCD displays the system mode, operation

36 HERCULES PACKAGE UNIT OPERATION MANUAL

1800 119 229www.actronair.com.au

Refrigerant Trading Authorisation No.: AU06394

N2018

Actron Engineering Pty LtdABN 34 002 767 240HEAD OFFICE SYDNEY AUSTRALIA

Printed in Australia Part No. 0525-022 Version No. 2.0 130408