Toll Free (800) 445-4155 • Fax (631) 348-7160 • www.marsdelivers.com REV 2/11/14 HVAC Commercial Refrigeration High Efficiency Motors

High Efficiency Motors · ®7 ECM for HVAC 51/2 INCH DIA. MARS SERIES 036Toll Free (800) 445-4155 • Fax (631) 348-7160 • Evergreen EM motors are high-efficiency ECM replacement

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: High Efficiency Motors · ®7 ECM for HVAC 51/2 INCH DIA. MARS SERIES 036Toll Free (800) 445-4155 • Fax (631) 348-7160 • Evergreen EM motors are high-efficiency ECM replacement

Toll Free (800) 445-4155 • Fax (631) 348-7160 • www.marsdelivers.comREV 2/11/14

HVAC

Commercial Refrigeration

HighEfficiencyMotors

Page 2: High Efficiency Motors · ®7 ECM for HVAC 51/2 INCH DIA. MARS SERIES 036Toll Free (800) 445-4155 • Fax (631) 348-7160 • Evergreen EM motors are high-efficiency ECM replacement

ECM for HVACMARS SERIES 950

Toll Free (800) 445-4155 • Fax (631) 348-7160 • www.marsdelivers.com®

Table of Contents

Table of Contents

ECM for HVAC

Accessories for Azure™ Digi-Motor® ...............................................................................................4

Azure™ Digi-Motor®.........................................................................................................................3

ECM Speed Controllers .............................................................................................................8 – 9

Evergreen CM Motors......................................................................................................................6

Evergreen EM Motors ......................................................................................................................7

Evergreen IM Motors .......................................................................................................................5

PTAC ECM Motors.........................................................................................................................10

ECM for Commercial Refrigeration

Arktic™ 142 Motors .......................................................................................................................12

Arktic™ 59 Motors..........................................................................................................................11

ECM Fan/Motor System.................................................................................................................17

ECplus™ Motors............................................................................................................................14

Elco Motors ....................................................................................................................................15

Evaporator/Condenser Fan Motors, American Iron .......................................................................12

Evaporator/Condenser Motors.......................................................................................................16

SSC Motors....................................................................................................................................13

Two Speed Evaporator Fan Controller...................................................................................18 – 19

MARS Technical Help Line

800-678-9888M-F 8 am – 5 pm EST.

Page 3: High Efficiency Motors · ®7 ECM for HVAC 51/2 INCH DIA. MARS SERIES 036Toll Free (800) 445-4155 • Fax (631) 348-7160 • Evergreen EM motors are high-efficiency ECM replacement

ECM for HVACMARS SERIES 116

Toll Free (800) 445-4155 • Fax (631) 348-7160 • www.marsdelivers.com

The Azure™ Digi-Motor® from MARS is a high efficiency variable speed direct driveblower motor for a multitude of applications. Azure™ is a replacement for both standardPSC and Genteq X-13 motors. Two motors cover ratings from 1/5 HP to 1 HP at 115V or 230V and CW or CCW.

Azure™ features an auto sizing learn mode. In start-up learn mode, Azure™ runs or approximately 2 minutes measuring the external static pressure of the systemapplication. Azure™ then assigns torque values to each of its speed taps self-programming itself to the correct horsepower for the application.

If none of the four speeds provides perfect airflow for the application or if duplicatespeeds are desired on 2 or more taps, an optional hand held programmer (MARS No.08502) can be used. The programmer connects to Azure™ and displays the percentageof torque applied to the speed tap being energized. The percentage (motor speed) canthen be increased or decreased and permanently set with the programmer. This tooloverrides the motor torques established in the auto sizing mode.

Unlike other electronically commutated motors, an outboard surge protector is includedwithin Azure’s™ wire harness. This is a replaceable device (MARS No. 08593).

Features:• Outboard replaceable surge protector• Adjustable speeds (with optionalMARS No. 08502)

• 625 RPM constant fan mode• Reversible rotation• High efficiency 85%• Multi-horsepower• Dual voltage• 4 Speeds• Belly band mount

®

Digi-Motor®

A

C

B

350 RPM to 1400 RPM Operating Range* – Ball BearingMARS NO. HP VOLTS AMPS

120V/230V RPM ROTATION DIMENSIONSA B C

Cross Reference to Competitive ECM Products

* with use of optional hand held programmer MARS No. 08502

Ball Bearing

Specifications:• Class “B” insulation• 48 Frame• Thermal overload protected• Operating temperature range: -20°C to 55°C (-4°F to 131°F)

• UL and CSA recognized

10860 1/5-1/2 115/230 6.4/3.8 1075 Rev 4.93 5.72 1/210861 1/2-1 115/230 11.5/7.0 1075 Rev 4.93 6.66 1/2

MARS No. Azure™ Century/AO Smith US Motors/Emerson GE/Genteq

10860 10800 CS1056, CSL1056 5522ET, 5532ET, 5542ET (1/3 HP & 1/2 HP), 5552ET (1/2 HP)

6001, 6002, 6005, 6103E,6203E, 6105E, 6205E

10861 10801 CS1106, CSL1106 5552ET, 5542ET (3/4 HP) 6003, 6004, 6010, 6107E,6207E, 6110E, 6210E

Page 4: High Efficiency Motors · ®7 ECM for HVAC 51/2 INCH DIA. MARS SERIES 036Toll Free (800) 445-4155 • Fax (631) 348-7160 • Evergreen EM motors are high-efficiency ECM replacement

ECM for HVACMARS SERIES 116

Toll Free (800) 445-4155 • Fax (631) 348-7160 • www.marsdelivers.com

The Azure™ Hand Held Programmer allows the Azure™Digi-Motor® (MARS No. 10860/10861) to be customspeed tuned to each application. Although the motorperforms an auto sizing function that will correctly assigntorque to each of the speed taps for the installedapplication, there may be instances when customspeeds are desired.

Features:• Allows blower speed to be reduced to the low end ofCFM tolerance for improved dehumidification.• Allows duplicate speeds to be set on multiplespeed taps.• Allows CFM to be maximized especially in high altitude applications.• Provides speed tap flexibility for multi-stage systems.

Azure™ Hand Held Programmer

Accessories for Azure™ Digi-Motor®MARS NO. DESCRIPTION

08502 Azure™ Hand Held Programmer 10860/10861

08593 Surge Protector 10860/10861

08595 Constant Fan Kit

08502

08593

Page 5: High Efficiency Motors · ®7 ECM for HVAC 51/2 INCH DIA. MARS SERIES 036Toll Free (800) 445-4155 • Fax (631) 348-7160 • Evergreen EM motors are high-efficiency ECM replacement

Toll Free (800) 445-4155 • Fax (631) 348-7160 • www.marsdelivers.com 5®

ECM for HVAC51/2 INCH DIA. MARS SERIES 036

Belly Band• Designed by RBC for Evergreen

• Tested by RBC for strength and sound

• Evergreen branded accessory

Evergreen IM is the world’s first high-efficiency ECMreplacement motor that is designed to replace factory PSCblower motors in HVAC systems. Built from the same trusted,field-proven ECM technology that is found in millions of OEMsystems nationwide, Evergreen uses up to 25% fewer watts inoperating mode and up to 74% fewer Watts than a PSC motorin constant fan.

Evergreen’s ECM controls combine thermostat commandswith an advanced permanent-magnet design to run moreefficiently and quietly while offering better airflow control thana PSC. The Evergreen IM is a great replacement for any PSCair-handler motor, adding up to 1 SEER point to an existingsystem. The motor’s airflow benefits are especially importantto homeowners who run (or would like to run) in constant fanmode for better comfort, improved IAQ products, or improvedzoning airflow.

Applications:• Direct drive, 115 or 230VAC motor systems• Clock-wise (CW) or counter clock-wise (CCW) rotation• Residential split and packaged systems• Air conditioning or heat pump systems• Natural gas, propane and oil heat furnaces• Dual fuel systems• Hot water coil and geothermal air handlers

Features:• Two motors cover all applications• Multi-volt 115/230 and reversible rotation• Integrated with HVAC system controls/operation • Four speed selections for heating and cooling• Optimized constant fan speed• Two (2) year warranty• Reduce truck stock, no capacitors to change out orstock

• For accessories, see pages M–51 & M–75

06005 5SME39HXL110 1/5, 1/4, 1/3, 1/2 115/230 REV 1

06010 5SME39SXL111 1/2, 3/4, 1 115/230 REV 1

08025 10” Bolt Pattern 1

08026 11” Bolt Pattern 1

08027 13” Bolt Pattern 1

Heat and Cool Operation -up to $60 at 10¢ / kWh

Constant Fan Operation -up to $268 at 10¢ / kWh

Average Annual Energy Savings

MARS NO. DESCRIPTION MARSPACK

MARS NO. MODEL NO. HP VOLTS ROT MARSPACK

600 - 1075 RPM

Page 6: High Efficiency Motors · ®7 ECM for HVAC 51/2 INCH DIA. MARS SERIES 036Toll Free (800) 445-4155 • Fax (631) 348-7160 • Evergreen EM motors are high-efficiency ECM replacement

ECM for HVAC51/2 INCH DIA. MARS SERIES 036

Toll Free (800) 445-4155 • Fax (631) 348-7160 • www.marsdelivers.com

Evergreen CM is the world’s first high-efficiency motor for replacingan existing blower motor in light commercial heating and coolingequipment. Evergreen is based on over 20 years of field-provenECM technology. The ultra-high-efficiency Evergreen CM ECM motorhas become the preferred motor for energy-saving for HVACsystems. It features flexible control methods to help the installerbalance airflow in HVAC systems such as VAV, Variable Air Volume,Series Boxes or Package Heat Pumps, using auto switch mode.Motor switches to variable speed mode when a PWM input isdetected. Evergreen CM gives businesses the ability to simplyupgrade their inefficient PSC motor with a high-efficiency ECM mode.

Features:• Efficiency up to 80%• Compatible with building automation systems using the optionalPWM speed controller

• Soft start and off ramp for quieter operation• Improved high static CFM performance

Specifications:• Variable speed, constant torque, brushless DC motor• Single phase, ball bearing• 5 Discrete speeds using 24 VAC control (or 3 using 18 VDC control)

• Variable speed control (requires ECM “PWM” speed controlMARS No. 08038 or 08039)

• Operating speed range of 600-1200 RPM with PWM Speed control

• NEMA 48 frame• Belly Band mount• 50/60 Hz• UL CSA recognized

1050 RPM

06703 DXL227 1/3 277 CCW 2.6 3.92 5.25 1/206705 HXL228 1/2 277 CCW 3.6 3.92 5.75 1/206707 NXL229 3/4 277 CCW 4.9 3.92 6.50 1/2

MARSNO.

MODEL #5SME39 HP VOLTS ROT

OSE FLA DIMENSIONSA B C

*A Power Factor Correction Choke may be required for Retrofits where many ECM motors are installed on 277 Volt systems where a shared neutralis being used for multiple ECM motors on a 3-phase supply. For more literature details see www.EvergreenDealer.com

Belly Band

08025 10” Bolt Pattern 1

08026 11” Bolt Pattern 1

08027 13” Bolt Pattern 1

PART NO. DESCRIPTION PACK

A

B

C

Page 7: High Efficiency Motors · ®7 ECM for HVAC 51/2 INCH DIA. MARS SERIES 036Toll Free (800) 445-4155 • Fax (631) 348-7160 • Evergreen EM motors are high-efficiency ECM replacement

ECM for HVAC51/2 INCH DIA. MARS SERIES 036

Toll Free (800) 445-4155 • Fax (631) 348-7160 • www.marsdelivers.com

Evergreen EM motors are high-efficiency ECM replacementmotors that are designed to replace the Genteq X-13 motorsin HVAC systems. Built from the same trusted, field-provenECM technology that is found in millions of OEM systemsnationwide. Like the IM, the EM features auto rotation sensingtechnology and discrete speed taps. In addition, the EM alsoaccepts a PWM input. To simplify installation the EM acceptsthe OEM power harness containing 24V common, line, groundand neutral. Efficiency up to 80%, the motor’s airflow benefitsare especially important to homeowners who run (or would liketo run) in constant fan mode for better comfort, improved IAQproducts, or improved zoning airflow.

Features:• Multi-speed, constant torque, brushless DC motor• Designed to replace standard ECM motors, such as X-13 or equivalent competitor model. Not intended to replacepremium ECM constant airflow products such as Eon, 3.0,2.3, and 2.5

• NEMA 48 frame • 5 Pre-programmed, discrete torque inputs using 24VAC (3 using 18 VDC)

• Automatically determines motor direction using Genteq’srotation sensing technology

• Capable of operating using a 3rd party aftermarket ECMPWM controller

• 4kV surge protection

Specifications:• Variable speed operation from 600-1100 rpm• Electronic overload protection• UL and CSA recognized

600-1200 RPM, Reversible

06103 DXL442 1/3 115 Dual 5.00 5.25 1/206105 HXL443 1/2 115 Dual 5.00 5.75 1/206107 NXL444 3/4 115 Dual 5.00 6.50 1/206110 SXL445 1 115 Dual 5.00 7.25 1/2

MARS NO. MODEL NO.5SME39 HP VOLTS ROT DIMENSIONS

A B C

A

B

C

Belly Band

08025 10” Bolt Pattern 1

08026 11” Bolt Pattern 1

08027 13” Bolt Pattern 1

PART NO. DESCRIPTION PACK

Page 8: High Efficiency Motors · ®7 ECM for HVAC 51/2 INCH DIA. MARS SERIES 036Toll Free (800) 445-4155 • Fax (631) 348-7160 • Evergreen EM motors are high-efficiency ECM replacement

ECM for HVACMARS SERIES 950

Toll Free (800) 445-4155 • Fax (631) 348-7160 • www.marsdelivers.com

760-ECM Motor Speed ControllerThe 760-ECM motor speed controller is designed to provide manually adjustable proportional speed control for all sizes andvoltages of ECM DC Brushless motors.

Manual speed control is accomplished by adjusting the control pot in the clock-wise direction to increase motor speed. Adjustingthe pot in the counter clockwise direction will slow down and eventually stop the motor as the PWM signal is removed.

The 760-ECM is line voltage independent and requires only a 24VAC supply. This unit is fully enclosed and can be mounted instandard electrical boxes.

Variable speed control is accomplished via a Pulse Width Modulated (PWM) output signal. The PWM signal operates at anominal 13.5VDC at 80Hz and is capable of sourcing up to 5mA drive current to drive a single motor.

Specifications:• Motor speed: Manual adjustable• Input voltage: 24VAC (+20%/-10%)• Output: 0% to 100% PWM @ 80 Hz

º 13.5VDC, 5mA (max.)

º Max wire length (twisted pair) 100 ft.

760-ECM

ECMMotor

T2or Neutral

T1 AC Line VoltageFrom Contactor

(+) Signal

(-) GND24VAC

BLAC

KOR

ANGE

BLAC

KRE

D

!If a ground reference is applied to the 24VAC power source, the "grounded" lead must be connected to terminal 24V COM ONLY.

CAUTION!

• Humidity: 95% non-condensing• Operating ambient temperature: 32°F - 120° F• Dimensions (L x W x H): 4.25” x 2.40” x 1.25”

MARS NO. DESCRIPTION MARSPACK

08032 ECM Motor Manual Speed Controller 1

792-ECM Motor Speed ControllerThe 792-ECM (Vma) motor speed controller is designed to provide both continuously variable and/or manually adjustable proportionalspeed control for all sizes and voltages of ECM DC Brushless motors. The 792-ECM (VmA) controller also includes an output to“enable” operation of ECM motors that require such a signal for operation.

Continuously variable speed control is accomplished via 2-10VDC or 4-20mA input signal to the control. This controller providesa linear increase of the output as the input signal increases over the 2-10VDC or 4-20mA span.

Manual Speed Control is accomplished by adjusting the control pot in the clock-wise direction to increase motor speed.Adjusting the pot in the counter clock-wise direction will slow down and eventually stop the motor as the PWM signal is removed.

The two control methods may be used together by manually setting a minimum speed for the motor to always maintain,regardless of input signal. When the input signal exceeds the level set manually, full variable speed control is resumed as longas the input is above the manually set level.

The 792-ECM is line voltage independent and requires only a 24VAC supply. This unit is circuit board on standoffs for mounting directly to control panel surfaces.

Variable speed control is accomplished via a Pulse Width Modulated (PWM) output signal. The PWM signal operates at a nominal 13.5VDC at 80 Hz andis capable of sourcing up to 5mA drive current to drive a single motor.

Specifications:• Motor speed: Continuously variable/manuallyadjustable/Off

• Input voltage: 24VAC (+20%/-10%)• Input signal:

º DC Volts: 2-10VDCn Input impedance: 10,000 Ohms Min.

º DC milliAmps: 4-20mA DCn Input impedance: 500 Ohms

• Output: 0% to 100% PWM @ 80Hz

º 13.5VDC, 5mA (max.)

º Max wire length (twisted pair) 100 ft.• Operating ambient: 32°F to 120°F• Humidity: 95% non-condensing• Dimensions: (L x W x H): 2.50” x 3.00” x 1.25

ECMMotor

T2or Neutral

!

CAUTION!

T1 AC Line VoltageFrom Contactor

(+) Signal(-) GND

24 VACVDC or mA

Connect “GO” to motor enable pin(if required)

- + G

If a ground reference is applied to the 24VAC power source, the "grounded" lead must be connected to terminal 24V COM ONLY.

CAUTION!

MARS NO. DESCRIPTION MARSPACK

08033 ECM Motor Variable Speed Controller 1

Page 9: High Efficiency Motors · ®7 ECM for HVAC 51/2 INCH DIA. MARS SERIES 036Toll Free (800) 445-4155 • Fax (631) 348-7160 • Evergreen EM motors are high-efficiency ECM replacement

ECM for HVACMARS SERIES 950

Toll Free (800) 445-4155 • Fax (631) 348-7160 • www.marsdelivers.com

MARS NO. DESCRIPTION MARSPACK

08034 ECM Motor Manual Speed Controller 1

761-ECM Motor Speed ControllerThe 761-ECM motor speed controller is designed to provide manually adjustable proportional speed control for all sizes andvoltages of ECM DC Brushless motors.

Manual speed control is accomplished by adjusting the control pot in the clock-wise direction to increase motor speed. Adjustingthe pot in the counter clock-wise direction will slow down and eventually stop the motor as the PWM signal is removed.

The 761-ECM is line voltage independent and requires only a 24VAC supply. This unit is a circuit board on standoffs formounting directly to control panel surfaces.

Variable speed control is accomplished via a Pulse width Modulated (PWM) output signal. The PWM signal operates at anominal 13.5VDC at 80 Hz and is capable of sourcing up to 5mA drive current to drive a single motor.

Specifications:• Motor speed: Manually adjustable• Input voltage: 24VAC (+20%/-10%)• Output: 0% to 100% PWM @ 80 Hzº 13.5VDC, 5mA (max.)

º Max wire length (twisted pair) 100 ft.

ECMMotor

T2or Neutral

T1 AC Line VoltageFrom Contactor

(+) Signal

(-) GND

24VAC

!If a ground reference is applied to the 24VAC power source, the "grounded" lead must be connected to terminal 24V COM ONLY.

CAUTION!

• Operating ambient: 32°F to 120°F• Humidity: 95% non-condensing• Dimensions (L x W x H): 1.50" x 2.50" x 1.25"”

791-ECM Motor Speed ControllerThe 791-ECM (VmA) motor speed controller is designed to provide continuously variable proportional speed control for allsizes and voltages of ECM DC brushless motors.

Continuously variable speed control is accomplished via 2-10VDC or 4-20mA input signal to the control. This controller providesa linear increase of the output as the input signal increases over the 2-10VDC or 4-20mA span.

The 791-ECM is line voltage independent and requires only a 24VAC supply. This unit is a circuit board on standoffs formounting directly to a control panel surfaces.

Variable speed control is accomplished via Pulse Width Modulated (PWM) output signal. The PWM signal operates at a nominal13.5VDC at 80 Hz and is capable of sourcing up to 5mA drive current to drive a single motor

Specifications:• Motor speed: Continuously variable/Off• Input voltage: 24VAC (+20%/-10%)• Input signals:º DC volts: 2-10VDC

n Input impedance: 10,000 Ohms Min.

º DC milliAmps: 4-20mA DCn Input impedance: 500 Ohms

ECMMotor

T2or Neutral

!

T1 AC Line VoltageFrom Contactor

(+) Signal(-) GND

24 VACVDC or mA

If a ground reference is applied to the 24VAC power source, the "grounded" lead must be connected to terminal 24V COM ONLY.

CAUTION!

• Output: 0% to 100% PWM @ 80 Hz

º 13.5VDC, 5mA (max.)

º Max wire length (twisted pair) 100 ft.• Operating ambient: 32°F to 120°F• Humidity: 95%, non-condensing• Dimensions (L x W x H): 2.50” x 2.50” x 1.25”

MARS NO. DESCRIPTION MARSPACK

08035 ECM Motor Variable Speed Controller 1

Page 10: High Efficiency Motors · ®7 ECM for HVAC 51/2 INCH DIA. MARS SERIES 036Toll Free (800) 445-4155 • Fax (631) 348-7160 • Evergreen EM motors are high-efficiency ECM replacement

10®

ECM for HVAC51/2 INCH DIA. MARS SERIES 116

Toll Free (800) 445-4155 • Fax (631) 348-7160 • www.marsdelivers.com

The MARS double shaft PTAC-ECM motors are highefficiency motors for direct replacement for shadedpole and PSC motors used in a wide range of fan coilassemblies and PTAC applications as an energysaving retrofit.

Applications:Fan Coils, Air Conditioners, Blowers, Shaded Pole,PTAC Units

Features:• Single phase• Energy efficient• Includes resilient mounting base• 54 Inch leads

Specifications:• 42 Frame• 60 Hertz• Class “B” insulation

1100/900/700 RPM

10820 1/10 120 1.6 CCW 9.30 4.52 9.30 1/2

10821 1/10 208-230 1.6 CCW 9.30 4.52 9.30 1/2

MARSNO. HP VOLTS AMPS ROT

OSEDIMENSIONS

A B C D

PTAC-ECM Motor Replacement

Page 11: High Efficiency Motors · ®7 ECM for HVAC 51/2 INCH DIA. MARS SERIES 036Toll Free (800) 445-4155 • Fax (631) 348-7160 • Evergreen EM motors are high-efficiency ECM replacement

Toll Free (800) 445-4155 • Fax (631) 348-7160 • www.marsdelivers.com 11®

ECM for Commercial RefrigerationMARS SERIES 064

The Morrill ARKTIC 59 motor is primarily used in the evaporator ofcommercial refrigeration walk-in coolers and freezers, but can be used inany application demanding high efficiency and dependability with outputratings up to 50 watts. The ARKTIC 59 significantly outperforms bothshaded pole and PSC technology with efficiencies three times higher thanshaded pole motors and 40% higher than PSC. In addition to the reliabledesign, the ARKTIC 59 provides users the ease of drop-in replacementand extraordinary energy savings for their applications.

08040 Krack Refrigeration RetrofitBracket Kit

1

MARS NO. DESCRIPTION MARSPACK

Features:• Universal “Drop-In” replacement for walk-in evaporator applications• Totally enclosed, non-vented• Shaft water slinger• Standard thru-bolt configuration• All angle mount• Power cord with lyall plug

Specifications:• Automatic torque variation, constant speed• Low temp (-20º F) lubrication system• 50/60 Hz• 1 Discrete speed• CUL (CE & VDE pending) UL file # E306123• Ball bearing • Thermally protected

1550 RPM - Front Or Rear Thru-Bolt Mount

05104 BVA 1036 1/15 115 1.1 CW 2.61 3.36 5/1605105 BVA 1038 1/15 115 1.1 CCW 2.61 3.36 5/1605204 BVA 2037 1/15 208-230 0.63 CW 2.61 3.36 5/1605205 BVA 2039 1/15 208-230 0.63 CCW 2.61 3.36 5/16

05127 BVA 1065 1/15 115 1.1 CCW 2.61 3.36 5/1605128 BVA 1066 1/15 115 1.1 CW 2.61 3.36 5/1605227 BVA 2070 1/15 208-230 0.63 CCW 2.61 3.36 5/1605228 BVA 2071 1/15 208-230 0.63 CW 2.61 3.36 5/16

MARS NO. MFG MODEL5SME59

NOMINALHP VOLTS AMPS OSE

ROTDIMENSIONS

A B C

1550/500 RPM - Two Speed - Front or Rear Thru Bolt MountMARS NO. MFG MODEL

5SME59NOMINALHP VOLTS AMPS OSE

ROTDIMENSIONS

A B C

Page 12: High Efficiency Motors · ®7 ECM for HVAC 51/2 INCH DIA. MARS SERIES 036Toll Free (800) 445-4155 • Fax (631) 348-7160 • Evergreen EM motors are high-efficiency ECM replacement

Toll Free (800) 445-4155 • Fax (631) 348-7160 • www.marsdelivers.com12®

ECM for Commercial RefrigerationMARS SERIES 006 & 064

MARS American Iron Motors are high efficiency designs that are made in Americaincorporating EM&S patented, permanent magnet ECM technology that brings outstandingenergy savings.

Features:• 3.3 Interchangeability• Shaft down andHorizontal mounting

• Cast iron unit bearingConstruction

• Front mount studs• Rotation: shaft end

00225* Evaporator/Condenser 1/15 115 1.25 CW 1550/1000 100226* Evaporator/Condenser 1/15 230 0.77 CW 1550/1000 1

MARS NO. APPLICATIONS HP VOLTS AMPS ROT SE RPM MARS PACK

Evaporator/Condenser Fan Motors

Made In America

03604 DLHE044 1/5 115 4.6 CW 3.92 5.45 1/203605 DLHE053 1/5 208-230 1.9-2.8 CW 3.92 5.45 1/203606 DLHE052 1/3 115 5.8 CCW 3.92 5.95 1/203607 DLHE043 1/3 208-230 2.6-3.5 CCW 3.92 5.95 1/2

1050 RPMMARS MFG MODEL NOMINAL OSE DIMENSIONSNO. 5SME59 HP VOLTS AMPS ROT A B C

* Shaft and leads are on the same end

Specifications:• Universal, fits most 1/15HP and smaller applications,1550 RPM

• 230 Volt 60/50 Hz ; 115 Volt 60 Hz. • 22.5” Leads with EMF/Lyall Plug• 4 10-32 Hex Flange nuts are supplied with each motor• UL and cUL recognized

SEE THIS MOTOR IN ACTION!Scan for video

BA

C

The ARKTIC 142 Series of ECM’s manufactured by Morrill, offers significant energysavings over traditional PSC or shaded pole designs. ARKTIC 142 ECM’s can be appliedin condenser or evaporator applications requiring 1/5 or 1/3 HP output at 1050 RPM.

Applications:Designed for condenser and evaporator fans for walk-in refrigerators, walk-in freezersand similar applications.

Features:• Three phase drive, NEMA 48FR BLDC motor;TEAO

• 77% motor efficiency @ 1050 RPM full load• Regulated speed; +/-6% full scale• -40 Deg C to 55 Deg C Amb.• 1/2” Diameter, single flat shaft ext. up to 6.0”

• Totally enclosed, non-vented (air-over ECM required)

• Shaft water slinger• 26" cord set attached to motor• Ball bearings• Horizontal-vertical down orientation desired

• RoHS compliant• 60/50 Hz

00211* Evaporator/Condenser 1/15 115 1.25 CW 1550 1

00212* Evaporator/Condenser 1/15 115 1.25 CCW 1550 1

00221* Evaporator/Condenser 1/15 230 0.77 CW 1550 1

00222* Evaporator/Condenser 1/15 230 0.77 CCW 1550 1

MARS NO. APPLICATIONS HP VOLTS AMPS ROT SE RPM MARS PACK

1550 RPM - Single Speed

1550/1000 RPM - Two Speed

Page 13: High Efficiency Motors · ®7 ECM for HVAC 51/2 INCH DIA. MARS SERIES 036Toll Free (800) 445-4155 • Fax (631) 348-7160 • Evergreen EM motors are high-efficiency ECM replacement

Toll Free (800) 445-4155 • Fax (631) 348-7160 • www.marsdelivers.com 13®

ECM for Commercial RefrigerationMARS SERIES 064

The Morrill SSC unit bearing motor is primarily used incommercial refrigeration applications, both evaporator andcondenser, but can be used in any application demanding highefficiency and dependability with output ratings between4 – 12 watts and 13 – 23 watts.The SSC significantly outperforms both shaded pole and PSCtechnology. With efficiencies three times higher than shadedpole motors and 45% higher than PSC, in addition to thereliable and quiet unit bearing design, the SSC providesusers great reliability and excellent energy savings for their applications.

Applications:• Bottle Coolers• Display Cases• Reach-In Coolers• Vending Machines

Features:• Output 4 – 12W and 13 – 23W• ~66% peak efficiency • Speed regulated within +/-6%• Regulated speed; +/-6% full scale• 1 Discrete speed• 51fr unit bearing motor; cast aluminum frame• Side pedestal mounting feet (2 sets standard)

Environmental Summary:• Storage Temps: -40 to 80° C ambient• Operating Temps: -40 to 55° C ambient• Design Life: 10 years, 83,720 hours on time

Mechanical Summary• 3.3” Electronically commutated aluminum or castiron unit bearing

• ¼” x 20 threaded shaft • Aluminum enclosure (totally enclosed)• Five .150” diameter cored mounting holes on rear • Horizontal shaft (+/- 15°) or vertical shaft upoperating position

• Standard 18 gauge, 2 conductor leads • Lead cord may be terminated with 1/2” strippedwire, in-house molded plugs, eyelets, ¼” quickconnects, or special terminals

• RoHS compliant

00650 Evaporator/Condenser 4-12 115 CW 1550 1

00651 Evaporator/Condenser 4-12 230 CW 1550 1

00652 Evaporator/Condenser(90˚ lyall plug) 4-12 115 CW 1550 1

00654 Evaporator/Condenser 13-23 115 CW 1550 1

00655 Evaporator/Condenser 13-23 230 CW 1550 1

00656 Evaporator/Condenser 13-23 115 CCW 1550 1

00657 Evaporator/Condenser 13-23 230 CCW 1550 1

MARS NO. APPLICATION OUTPUT WATTS VOLTS ROT. RPM MARS PACK

Page 14: High Efficiency Motors · ®7 ECM for HVAC 51/2 INCH DIA. MARS SERIES 036Toll Free (800) 445-4155 • Fax (631) 348-7160 • Evergreen EM motors are high-efficiency ECM replacement

Toll Free (800) 445-4155 • Fax (631) 348-7160 • www.marsdelivers.com14®

ECM for Commercial RefrigerationMARS SERIES 064

The ECplus™ electronically commutated ball bearing motor is used incommercial refrigeration applications and can replace standard shadedpole or other EC type motors ranging in size from 1 W to 22 W. TheECplus™ is approximately 3 times more efficient than standard shadedpole motors making it an excellent choice for upgrade retrofit projects.The robust IP55 rating ensures protection against water spray frommaintenance wash downs.

Applications:• Light commercial ventilation units• Bottle coolers• Vending machines• Small walk in coolers

Features:• Peak efficiency greater than 65%• Incorporating ‘soft start’ feature ensures quiet ramp up to desiredspeed which assists in eliminating vibration noise & increasing lifeexpectancy of integrated electronics

• One model covers 1 Watt to 22 Watt shaft power• Support 6", 7", 8" & 10" (maximum 10" 28 degree pitch) fan blades• 90° Angle lyall plug

Specifications:• Thermally protected with electronic overload protection• IP55 Rating• 1550 RPM• Approvals UL & CUL

ECplus™ Wide Range Universal Refrigeration Motor

1550 RPM

MARSNO. WATTS VOLTS MAX

AMPSROTOSE

DIMENSIONS

A B C

05620 1 - 22 Watts 120 0.42 CW 1.14 2.48 1/4

• Display/refrigeration display units• Freezer cabinets• Ice machines

05620

05620

08030

08030

MARSNO. DESCRIPTION

08030 8" Plastic Basket for ECplus™ Motor

SEE THIS MOTOR IN ACTION!Scan for video

Page 15: High Efficiency Motors · ®7 ECM for HVAC 51/2 INCH DIA. MARS SERIES 036Toll Free (800) 445-4155 • Fax (631) 348-7160 • Evergreen EM motors are high-efficiency ECM replacement

Toll Free (800) 445-4155 • Fax (631) 348-7160 • www.marsdelivers.com 15®

ECM for Commercial RefrigerationMARS SERIES 008

Elco Hi Efficiency ECM motors are drop in replacementsof the traditional front mount shaded pole motors. Theyuse all the same accessories with no extra work for aneasy and hassle-free installation. These are built withECM technology to run more efficiently, reduced CO2

emissions, longer life expectancy and quieter than thenormal PSC shaded pole motors. They offer better airflowcontrol than a PSC, up to 70%, 4 to 5 times more efficientthan a regular shaded pole motor. Higher efficiencymeans cooler motor operation and reduced heatdelivered to the refrigeration cycle, for a combined energysaving advantage and improved refrigeration quality. TheECM Series offers IP65 moisture protection grade, one ofthe highest in the industry. These motors are designed tosatisfy the growing demands of energy savings.

ECM High Efficiency Motors

Features:• Life expectancy of 60,000+ hrs.• Protection rating - IP65 moisture protection grade• Totally enclosed• All angle • Continuous air over• Long life sealed ball bearings

Specifications:• Working temp: -40°C +55°C• 50/60 Hz• M4 Studs on 3.72” B.C. for shroud/guard• UL recognized & CE Certified

Cross Reference

EDA12153UC0147 Arneg Canada & US 34410013, 34410009, 24681010

EDA15253UC0176 Hill Phoenix P078449H

EDA10153UC0182 Hill Phoenix P079441C, P066237A

00851 EDA12153UC0147 12 1/63 115 1450 CCW 0.18 3.61 14" 3 Pin 90°

00852 EDA15253UC0176 15 1/50 115 1600 CCW 0.22 4.00 16" 2 Pin 90°

00858 EDA10153UC0182 10 1/75 115 1550 CCW 0.19 3.61 16" 2 Pin 90°

MARSNO. MFG NO. WATTS HP VOLTS RPM ROT.

S.E AMPS A DIM CORDLENGTH

TERM.PLUG

Page 16: High Efficiency Motors · ®7 ECM for HVAC 51/2 INCH DIA. MARS SERIES 036Toll Free (800) 445-4155 • Fax (631) 348-7160 • Evergreen EM motors are high-efficiency ECM replacement

Toll Free (800) 445-4155 • Fax (631) 348-7160 • www.marsdelivers.com16®

ECM for Commercial RefrigerationMARS SERIES 006

Evaporator/CondenserMotors & Armatures, Inc. proudly introduces the ElectricMotors & Specialties, Inc. new ECM for refrigerated caseevaporator and condenser applications, the Unitronix DoubleDuty. The Unitronix Double Duty is an electronicallycommutated motor that brings outstanding energy savings tothe refrigeration market in the form of a direct drop-inreplacement for practically all unit bearing motors. Noadditional labor or sheet metal work is required to replace anexisting shaded pole unit bearing motor with a UnitronixDouble Duty.Heat in a refrigerated space has always been a necessaryevil in the food marketing industry. Lights, motors and defrostheating elements are the culprits. But, heat shortens foodstorage life and adds to the load placed on the refrigerationsystem. The new Unitronix Double Duty dramaticallyreduces (by as much as 75%) the waste heat generated byrefrigerated case evaporator motors.The Unitronix Double Duty is the latest in a long line ofinnovations by EM&S, a 35 year leader in developing energysaving motor designs for the commercial refrigerationindustry. EM&S motors are manufactured in the U.S.

Features:• Special wide temperature range lubrication system• High capacity oil reservoir spiral grooved shaft for efficientdistribution of oil to the bearing surface

• Mounting hardware included• Water shield included• Tapped & Drilled Mounting Holes:Universal Evaporator Mount

- Standard 3-Hole- Custom 4-Hole Hussmann Style

Universal Condenser Mount- Double Boss

Specifications:• 1550 RPM standard• Cast iron• Unit bearing• EMF P-2-1A lyall power plug• 15” leads• UL file no. E128044

The universal 5 rear mountinghole configuration and the

double boss with 4 drilled andtapped mounting holes on eachboss mean no additional labor

or sheet metal work!

00621 Evaporator/Condenser 6-12 115 0.25 CW 1550 100621 BULK Evaporator/Condenser 6-12 115 0.25 CW 1550 600622 Evap/Cond, 90˚Lyall Plug 6-12 115 0.25 CW 1550 100624 Evaporator/Condenser 14-16 115 0.50 CW 1550 100624 BULK Evaporator/Condenser 14-16 115 0.50 CW 1550 600625 Evap/Cond, 90˚Lyall Plug 14-16 115 0 .50 CW 1550 1

MARS OUTPUT NOMINAL ROT MARSNO. APPLICATIONS WATTS VOLTS AMPS OSE RPM PACK

Page 17: High Efficiency Motors · ®7 ECM for HVAC 51/2 INCH DIA. MARS SERIES 036Toll Free (800) 445-4155 • Fax (631) 348-7160 • Evergreen EM motors are high-efficiency ECM replacement

Toll Free (800) 445-4155 • Fax (631) 348-7160 • www.marsdelivers.com 17®

ECM for Commercial RefrigerationMARS SERIES 064

The 58MM Series replacement ECM Fan/Motor systems are primarilyused in commercial refrigeration air moving applications demanding highefficiency and dependability. These motors are moisture resistant,reliable, quiet unit bearing design with efficiencies three times higherthan shaded pole motors and 45% higher than PSC. These replacementECM Fan/Motor systems are all metal in design and have 1 discretespeed, variable torque, low temperature lubrication system which makesthem extremely quiet with low vibration.

Features:• Lyall plug• Class B insulation• 60 Hertz• Thermal protection• Single phase

Specifications:• -40 to 55°C ambient operating temp.• Single speed• Maximum watts 36

05470 5R026 AAF1027 1340 115 0.30 CW 330 270 21005471 5R027 AAF1026 1470 115 0.40 CW 370 300 20005472 5R028 AAF1031 1650 115 0.40 CW 400 360 255

MARS NO. MFG NO. GE NO. 5SME58

REPLACESRPM VOLTAGE MAX

AMPS ROT. OSE

AT 0.05"CFM

AT 0.10"CFM

AT 0.15"CFM

58 MM Series Replacement ECM Fan/Motor System

Rear View054700547105472

Side View05470

Side View0547105472

Page 18: High Efficiency Motors · ®7 ECM for HVAC 51/2 INCH DIA. MARS SERIES 036Toll Free (800) 445-4155 • Fax (631) 348-7160 • Evergreen EM motors are high-efficiency ECM replacement

Toll Free (800) 445-4155 • Fax (631) 348-7160 • www.marsdelivers.com18®

ECM for Commercial RefrigerationMARS SERIES 950

08041 Evaporator Fan Controller for 2 Speed Motors

MARS NO. DESCRIPTION

OrangeBlack

Red

Low SpeedControl Input

EvaporatorFan

Controller

Incoming120 Vac

through240 Vac

Low SpeedControl Input

Two-Speed ECM Motors Only

The Evaporator Fan Controllers are developed for use in walk-in coolers andfreezers. The fans in the evaporator boxes run at normal speed at all times,even if the thermostat is not calling for a cooling cycle. To save money, theEvaporator Fan Controllers monitor the temperature on both the intake andexhaust of the evaporator fan unit: 1. Evaporator fan speed is reduced.

2. Cooling or compressor “runtime” is reduced.• When the temperature of the exhaust is lower than that of the intake, thefans will run at normal speed.

• When the temperature of the exhaust is equal to the intake temperaturehowever, the Evaporator Fan Controllers will reduce the speed of the fansto save energy, significantly reducing energy costs.

When the compressor turns back on to meet thermostat requirements, theEvaporator Fan Controllers will then once again return the fans to normalspeed. This temperature monitoring and fan speed control allows for energysavings without an impact on the overall temperature of the cooler or freezer.

Features:• Fast and easy installation (30 minutes)• Automatically reduces evaporator fan speed when compressor is off• Automatically selects between 120-240 Vac for ease of wiring • Used with 2 speed ECM motors only • Reduces heat load inside coolers• Thermistors included • 3-5˚ F reduces compressor runtime by slowing warm up cycle in cooler

Specifications:• Operating temperature: -30 to 80°F• LED status: o Red led-normal speedo Green led-low speed

• Input voltage 120-240 Vac • UL listed, CUL, and CE approved

Output:• Org – 1/3 HP @ 120/240 Vac• 10A general purpose @ 120/240 Vac• B300 pilot duty

2 Speed Evaporator Fan Controller

Page 19: High Efficiency Motors · ®7 ECM for HVAC 51/2 INCH DIA. MARS SERIES 036Toll Free (800) 445-4155 • Fax (631) 348-7160 • Evergreen EM motors are high-efficiency ECM replacement

Toll Free (800) 445-4155 • Fax (631) 348-7160 • www.marsdelivers.com 19®

ECM for Commercial RefrigerationMARS SERIES 950

The MARS 2 speed ARKTIC evaporator fan controller is acomplementary technology for ECM 2 speed motors. By implementingthe controller, the ECM motor will automatically adjust RPM betweenhigh and low speed operation. During low speed operations, thecontroller enables significant (additional) energy savings (typically up to92%) of the EC motor power draw. Low speed operation is during thosetimes where walk in case is at temperature, refrigerant is not requiredand compressor is not operating. Industry average indicates this portionof the duty cycle to be approx 50%. In addition to significant energysavings, the addition of the controller reduces EC motor heat gain up to 90%. The superior design allows for a single control unit to control up to 15ECM motors within typical walk-in coolers and freezers. Installation ofthis technology is recommended simultaneously during walk in ECM 2speed motor retrofit procedures.

Specifications:• SPST continuous duty coil• 10 Million cycles minimummechanical life

• -30° F to 140° F• Status: LED on = activated• Dimensions: 2.30 x 3.20 x 1.80with .50 NPT nipple

• 16 Awg, 600V rated• UL listed, UL916, C-UL, CE,RoHS

• Plenum, NEMA1• Override Switch

Power Input:• 42 mA @ 120 Vac• 62 mA @ 208-277 Vac

Contact Ratings:• 20 Amp Resistive @ 277 Vac• 1110 VA Pilot Duty @ 277 Vac• 770 VA Pilot Duty @ 120 Vac• 20 Amp Ballast N/O @ 277 Vac• 10 Amp Tungsten N/O @ 120 Vac• 2 HP @ 277 Vac• 1 HP @ 120 Vac

08038 FA-120V-1HP 2 SPEED ARKTIC CONTROLLER 120V08039 FA-208-277-1HP 2 SPEED ARKTIC CONTROLLER 208/277

MARS NO. MFG NO. DESCRIPTION

Notes:Dry Contact Input Operation: Close White/Red wire to White/Blue wireto activate relay. If more than one DRY-CONTACT RIB shares a single dry-contact input, White/Blue must be common.

2 Speed Evaporator Fan Controller

Page 20: High Efficiency Motors · ®7 ECM for HVAC 51/2 INCH DIA. MARS SERIES 036Toll Free (800) 445-4155 • Fax (631) 348-7160 • Evergreen EM motors are high-efficiency ECM replacement

Toll Free (800) 445-4155 • Fax (631) 348-7160 • www.marsdelivers.com

98693

®