27
HIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor

HIM - Yokogawa Electric › product_HIMHART_IM.us.pdfHIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor 2 The Interface

  • Upload
    others

  • View
    7

  • Download
    0

Embed Size (px)

Citation preview

Page 1: HIM - Yokogawa Electric › product_HIMHART_IM.us.pdfHIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor 2 The Interface

HIMHI

MNovember 2005224-778-00C

Sm

art H

AR

T® L

oo

pIn

terf

ace

and

Mo

nito

rSmart HART ® Loop

Interface and Monitor

Page 2: HIM - Yokogawa Electric › product_HIMHART_IM.us.pdfHIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor 2 The Interface

2 The Interface Solution Experts

Table of Contents

The HIM ..............................................................................................................3About this Manual ...............................................................................................................3

Specifications .....................................................................................................................4

HIM Dimensions .................................................................................................................5

Terminal Designations ........................................................................................................5

Configuring the HIM .........................................................................................6

Installing the HIM ..............................................................................................7Installing the HIM into the Loop ...........................................................................................7

Bench Checking the HIM ....................................................................................................9

PC Configuration Software............................................................................10HART Parameters ............................................................................................................11

Display Parameters ..........................................................................................................13

Alarms Parameters ...........................................................................................................14

Analog Outputs Parameters ..............................................................................................16

Custom Curve Parameters ................................................................................................18

Scaling Parameters ..........................................................................................................19

Customer Service ...........................................................................................20

Appendix A: HIM MODBUS Feature .............................................................21

Page 3: HIM - Yokogawa Electric › product_HIMHART_IM.us.pdfHIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor 2 The Interface

The Interface Solution Experts 3

HIMSmart HART Loop

Interface and Monitor

The HIMThe Moore Industries HIM HART Interface Moduleunlocks the full potential of new and in-place HARTmultivariable transmitters, valves, meters and othersmart instruments.

Converts HART to 4-20mA SignalsThe HIM allows up to three additional analog processvariable measurements from a multivariable transmit-ter or valve with no additional process penetrations.Installed transparently across the 4-20mA instrumentloop, the HIM reads the HART digital process data thatrides on the loop wires. It converts the digital informa-tion for up to three isolated analog (4-20mA) processsignals that are readily accepted by in-place controlsystems, such as a DCS or PLC.

Provides Process and Diagnostic AlarmsRelay alarm trips (optional) can be individually user-seteither to trip when unwanted high/low process condi-tions occur, or provide a diagnostic health warning toalert of loop or instrument fault conditions.

Takes Advantage of Legacy InstrumentsThe device lets you leave existing smart HART trans-mitters and valves in place, yet still take advantage ofall the information they have to offer.

Works with every Smart HART DeviceThe instrument can be programmed in minutes to inter-face with every HART-compatible monitoring and con-trol device.

About this ManualWherever you see a “Note”, “Caution”, or “WARNING ”pay particular attention.

• A “Note” provides information to help you inavoiding minor inconveniences duringcalibration, installation or operation of the HIM.

• A “Caution” provides information on steps to taketo avoid procedures and practices that could riskdamage to the HIM or other equipment.

• A “WARNING ” provides information on steps totake to avoid procedures and practices that couldpose safety risks to personnel.

Figure 1. The HIM Accepts a Digital HART Signal and Outputs Both Analog Signals and Alarm Relays

4-20mA Representing the Primary Variable (Mass Flow)

HIM HART Interface Module"Breaks Out" Data from

Smart HART Instruments(HART Primary Master)

4-20mA Proportional to 2nd Variable (DP)

Control System(DCS or PLC)

Smart HART MultivariableMass FlowTransmitter

4-20mA Proportional to 3rd Variable (P)

4-20mA Proportional to 4th Variable (T)High Alarm in Response to 4th Variable (T)

HART Transmitter Fault Alarm

Flow

HART Communicator can be connected anywhere

along the 4-20mA loop(HART Secondary Master)

HART Digital Signal Carrying Primary, Second, Third, Fourth Variable Process Data, and Instrument Diagnostic Information

Page 4: HIM - Yokogawa Electric › product_HIMHART_IM.us.pdfHIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor 2 The Interface

HIM

4 The Interface Solution Experts

Smart HART LoopInterface and Monitor

SpecificationsInput Accuracy: Reflectsthe accuracy of the HARTfield deviceInput Impedance: TransmitMode: 150 ohms;Receive Mode: Less than5kohmsInput Over-RangeProtection: ±5Vdc

ANALOG OUTPUTSOutput Accuracy: ±0.015%of maximum output span(20mA). Includes thecombined effects of linearity,hysteresis, repeatability andadjustment resolution.Output Response Time:<120ms, 10-90%Isolation: 500Vrms channel-to-channel isolation;1000Vrms between case,input, outputs and powerterminals, and will withstand1500Vac dielectric strengthtest for one minute with nobreakdownRipple: Less than 10mVpeak-to-peak whenmeasured across a250 ohm resistorOutput Limiting: 130% ofspan maximum; 125% ofspan typicalOutput Protection:Transient protection onoutputLoad Capability:0-20mA, 1100 ohmsmaximumLoad Effect: ±0.01% of spanfrom 0 to maximum loadresistanceLine Voltage Effect:±0.005% of output span for a1% change in line voltageInput Fail Modes: PCprogrammable to fail high, faillow, hold last, hold last thenfail high, or hold last then faillow (configurable hold time, 0-60 seconds)Output Limits on InputFailure: 0-20mA: Fail Low to0mA or Fail High to 23.6mA;4-20mA: Fail Low to 3.6mAor Fail High to 23.6mA;X-20mA (0<X<4): Fail Low to90% of XmA or Fail High to23.6mA

Performance

Weight

Performance(Continued)

Indicators

Indicators(Continued)

AmbientConditions

+TX Power Supply: 24.0Vdc±10%@24mAALARM OUTPUTSDigital Response Time:Defined by HART protocol as500msec maximum in NormalHART Mode; 333msecmaximum in HART BurstModeAlarm Response Time:Digital Response Time +150msec (Defined as timefrom the field instrument’sreporting a fault until the HIMalarm is tripped)Alarm Trip Delay:Programmable from 0-120sec

MODBUS OUTPUTSType: Standard MODBUSRTU protocol interface overRS485 (parameters asspecified in U.S. StandardEIA-RS485)Address Range:Configurable from 1 to 247.Unit will assume a MODBUSaddress of 01 by defaultBaud Rate: Interfacesupports the following: 300,600, 1200, 4800, 9600, 19.2k.MODBUS interface willsupport even, odd and noparities. Unit will assume abaud rate of 9600 and noparity by defaultCharacter Format: One startbit, 8 data bits and one stopbitData Format: User-selectable Standard LSW(Least Significant Word) orSwapped MSW (MostSignificant Word). Unit willassume Standard LSW bydefaultPower Consumption:2-3.5W, nominal; 4.5W@24Vdc maximum for unitsusing transmitter excitation tosupply loop power a 2-wireinstrument

LCD Type: Two-line LCD;Top Row, 10mm (0.4 in) highblack digits on a reflectivebackground; Bottom Row,6mm (0.225 in) high digitson a reflective background;two-digit HART addressindicator

Specifications and information subject to change without notice.

Format: Top row is fivealphanumeric characters,plus sign and decimal point;bottom row is fivealphanumeric charactersDecimal Points: User-selectable for 0, 1, 2 or 3places after the decimal pointor automatically adjusting witha four decimal point maximumRange: -99999 to 99999Minimum Display Span:1.00Display Update Rate:100msecLED Type: Dual colorred/green indicate:INPUT LED: Whether (green)or not (red) the HART input isconnected and functioningproperlyREADY LED: Whether(green) or not (red) the HIM isinitialized and operatingproperlyTRIP 1 and 2 LED: Shows thestatus of alarm off (green) oralarm on (red)

Operating & StorageRange:-40°C to +85°C(-40°F to +185°F)Display Range:-25°C to +85°C(-13°F to +185°F)Relay Range:-25°C to +70°C(-13°F to +158°F)Relative Humidity:0-95%, non-condensingAmbient TemperatureEffect: ±0.0065% ofspan/°C maximumRFI/EMI Immunity(Standard):20V/m@20-1000MHz, 1kHzAM, when tested according toIEC1000-4-3-1995RFI/EMI Immunity (with-RF Option): 30V/m@20-1000MHz, 1kHz AM, whentested according to IEC1000-4-3-1995Noise Rejection: CommonMode: 100dB@50/60Hz

567 grams (16 ounces)

Page 5: HIM - Yokogawa Electric › product_HIMHART_IM.us.pdfHIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor 2 The Interface

The Interface Solution Experts 5

HIMSmart HART Loop

Interface and Monitor

Single Alarm (–1PRG)

Dual Alarm (–2PRG)Relay 1

Table 1. Terminal Designations

NOTES:1. The standard Single Alarm unit (1PRG) utilizes a DPDT relay.2. Terminal blocks can accommodate 14-22 AWG solid wiring(torque to 4 inch-pounds, maximum).

KEY:+IN/–IN = Current input to HIM from HART device +TX = Transmitter Excitation Current+I/–I Source = Analog Source Output +I/–I Sink = Analog Sink OutputA/B = MODBUS Output NO/NO# = Normally OpenNC/NC# = Normally Closed CM/CM# = CommonDC/DCC = 24VDC Connection (AO#) = Analog Output

INPUT / OUTPUT

HART Input, 2 Analog Outputs (2AO)

HART Input, 3 Analog Outputs (3AO)

HART Input, 2 MODBUS Oututsand 1 Analog Output (MB1AO)

HART Input, 2 MODBUS Outputs (MB)

T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 T11 T12

+TX

+TX

+TX

+TX

+IN

+IN

+IN

+IN

–IN

–IN

–IN

–IN

No Label +I Source(AO2)

+I Source(AO2)

AMODBUS

2

AMODBUS

2

ALARM RELAYS / POWER

NO1 CM1 NC1

–I Sourceor

+I Sink(AO2)

–I Sourceor

+I Sink(AO2)

BMODBUS

2

BMODBUS

2

–I Sink(AO2)

–I Sink(AO2)

SMODBUS

2

SMODBUS

2

B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12

+I Source(AO1)

+I Source(AO1)

AMODBUS

1

AMODBUS

1

DC

DC

–I Sink(AO1)

–I Sink(AO1)

SMODBUS

1

SMODBUS

1

Ground

Ground

–I Sink(AO3)

–I Sink(AO)

–I Sourceor

+I Sink(AO3)

–I Sourceor

+I Sink(AO)

+ISource(AO3)

+ISource(AO)

NO2 CM2 NC2

Relay 1

No Label

Relay 2

No Label

–I Sourceor

+I Sink(AO1)

–I Sourceor

+I Sink(AO1)

BMODBUS

1

BMODBUS

1

DCC

DCC

NO1 CM1 NC1 NO2 CM2 NC2

No Alarm No Label

DC GroundDCC

65mm(2.56 in)

138mm(5.45 in)

133mm(5.25 in)

100mm(3.94 in)

HIM HART INTERFACEMODULE

READYINPUT

60.278TRIP 2TRIP 1

COM

DEG C0ADDR

T1 T2 T3 T4 T5 T6 T7 T8 T9 T10 T11 T12

B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12

Figure 2. HIM Dimensions

Page 6: HIM - Yokogawa Electric › product_HIMHART_IM.us.pdfHIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor 2 The Interface

HIM

6 The Interface Solution Experts

Smart HART LoopInterface and Monitor

Precision LoadResistor

Multimeter orAmmeter

PowerSupply

Personal Computer

PC OperatingSystem

Moore IndustriesPC Configuration

Software

CommunicationCable

250 ohms, ±0.01%

Accurate to ±0.009% of span;e.g. HP Model 3487A

24Vdc, ±10%

80386-based(or faster) IBM PC, or 100%compatible; (Pentium recommended)CD Drive4Mb free RAM; 16Mb recommended20Mb free disk space on hard drive1 (one) serial port (COM 1, 2, 3 or 4)

Microsoft Windows® 95, 98, 2000, ME, orNT with Internet Explorer 4.0+

orMicrosoft Windows® NT withService Pack 3 or greater

Version 1.0 or higher, successfullyinstalled to the hard drive

Part Number: 803-053-26, or equivalent

Device Specifications

Table 2. Assembling the Necessary EquipmentConfiguring the HIMOne of the benefits of the HIM is that there are nointernal or external controls to adjust or settings tochange. All operating parameters are set using the PCConfiguration software.

Once these software settings are made, they aredownloaded to the monitor in the form of a ConfigurationFile and stored in the unit’s non-volatile memory. Youcan choose to save a backup copy of the file on yourPC hard drive or external media. The HIM communi-cates with the PC through a proprietary communica-tions cable to the PC’s serial (COM) port.

Begin by installing the PC Configuration Software.

Installing the PC Configuration SoftwareRefer to Table 2 for the equipment needed.

1. Insert the Moore Industries Interface SolutionPC Configuration Software CD into the CD driveof the PC. Access the CD and open the HIMPC Configuration Software folder.

2. Double-click the installation program located inthe folder. Follow the prompts to correctlyinstall the program.

Once the Configuration Program is installed on the PC,the unit can be connected either into the loop or to testequipment to simulate input and monitor output. Withthe PC program, the user can then view and/or changeits operating parameters. To begin the process, connectthe HIM either into the loop (see Installing the HIM intothe Loop) or into a configuration setup (see BenchChecking the HIM).

Page 7: HIM - Yokogawa Electric › product_HIMHART_IM.us.pdfHIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor 2 The Interface

The Interface Solution Experts 7

HIMSmart HART Loop

Interface and Monitor

Installing the HIMThere are two methods for connecting the HIM forconfiguration. The recommended method requires youto install the instrument into the loop before it isconfigured. The secondary method allows you to benchcheck the HIM by attaching it to test equipment thatwill simulate the input and monitor the output.

Installing the HIM into the LoopInstallation consists of physically mounting the unit,grounding the instrument, and completing the electricalconnections. To install the HIM into the loop forconfiguration, use the equipment in Table 2 to hookupthe HIM into the loop as shown in Figure 3 (withoutusing the HIM to power a transmitter) or Figure 4 (usingthe TX terminal to power a transmitter). If you need acomplete terminal description, refer to Table 1.

MountingThe HIM is designed to snap easily onto 32mm, G-type(EN50035) or 35mm Top Hat (EN50022) DIN rails.

Electrical ConnectionsAfter mounting, you are ready to connect the HIM tothe loop. Each unit comes equipped with a transmitterexcitation terminal which allows it to supply power tothe monitored HART instrument, if necessary. Figures2 and 3 show the connection diagrams for an HIM withor without using the transmitter excitation current.

CE ConformityInstallation of any Moore Industries products that carrythe CE certification (Commission Electrotechnique)must adhere to the guidelines in Installing the HIM inorder to meet the requirements set forth in applicable

Figure 3. Installing a HIM Into the Loop Without Using the Transmitter Excitation (+TX) Terminal

READYINPUT TRIP 2TRIP 1

COM

0ADDR

COMMON

NC (normally closed)

NO (normally open)

4-20mA

DCS

SensorInput

NO

NC

DC

GN

D

+

24VdcPowerSource

DC

C

R

HART Multivariable Field Instrument

(TemperaturePressure, Level

and Flow)Analog Output tied to Any Process Variable

Event Recorder

HART Communicatorcan be connected anywhere on the loop

CO

M

+IN –IN

24VdcPower

+ –

R must be > 250 and <1100 Ohms1

2

3

4

56

78

9

0

.—

➤➤

25.1deg-c

80.120.3

50.7

Page 8: HIM - Yokogawa Electric › product_HIMHART_IM.us.pdfHIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor 2 The Interface

HIM

8 The Interface Solution Experts

Smart HART LoopInterface and Monitor

Figure 4. Installing a HIM Into the Loop Using the Transmitter Excitation (+TX) Terminal

EMC (Electromagnetic Compatibility) directives(EN55011, EN 50082-1, EN50082-2, etc.). Consult thefactory for the most current information on productsthat have been CE certified.

Recommended Ground Wiring PracticesMoore Industries recommends the following groundwiring practices:

• Any Moore Industries product in a metalcase or housing should be grounded.

• The protective earth conductor must beconnected to a system safety earth groundbefore making any other connections.

• All input signals to, and output signalsfrom, Moore Industries’ products should bewired using a shielded, twisted pairtechnique. Shields are to be connected to anearth or safety ground at the unit itself.

• The maximum length of unshielded inputand output signal wiring should be 2 inches.

Power Sourcing Parameters for GeneralLocations, Intrinsically Safe, andNon-Incendive/Type N applicationsIn accordance with IEC 1010.1 Annex H(all models), the input terminals must beconnected to and/or supplied from a certifiedenergy limiting Class 2 or a Separate Extra LowVoltage (S.E.L.V.) power supply separated fromall mains by double/reinforced insulation.

READYINPUT TRIP 2TRIP 1

COM

0ADDR

COMMON

NC (normally closed)

NO (normally open)

4-20mA

DCS

SensorInput

NO

NC

DC

GN

D

+

24VdcPowerSource

DC

C

R must be > 250 and <1100 Ohms

R

HART MultivariableField Instrument(Temperature,

Pressure, Leveland Flow)

Analog Output tied to Any Process Variable

Event Recorder

HART Communicatorcan be connected anywhere on the loop

CO

M

+IN

+TX –IN

12

3

4

56

78

9

0

.—

➤➤

Page 9: HIM - Yokogawa Electric › product_HIMHART_IM.us.pdfHIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor 2 The Interface

The Interface Solution Experts 9

HIMSmart HART Loop

Interface and Monitor

Figure 5. Bench Checking the HIM Using the TransmitterExcitation (+TX) Terminal to Power a Transmitter

Figure 6. Bench Checking the HIM Without Using theTransmitter Excitation (+TX) Terminal to Power a Transmitter

Bench Checking the HIMIf you would like to configure the HIM beforeattaching it to the loop, you need to hook it upwith the equipment listed in Table 1. Refer toFigures 5 and 6 for instructions on how to benchcheck the HIM either with or without takingadvantage of the Transmitter Excitation (+TX)terminal. If you need further descriptions of theterminals, see Table 2.

READYINPUT TRIP 2TRIP 1

COM

0ADDR

For a HART Transmitter, the resistor must be >250 and <1100 ohms.For a HART Receiver, such as a valve positioner, no resistor is necessary.

HARTField Device

orSimulator

SensorInput

Optional

Optional

Checks forcontinuity

24VdcPower

R

+IN

NO

NC

DC

GN

D

CO

M

–IN

+

+ –

+

+

Multimeter

Multimeter 24VdcPower

DC

C

READYINPUT TRIP 2TRIP 1

COM

0ADDR

Optional

Checks forcontinuity

NO

NC

DC

GN

D

CO

M

+

–+ –

Multimeter

Multimeter 24VdcPower

DC

C

HARTField Device

orSimulator

SensorInput

Equipment Hook-Upfor HART field device using

Transmitter Excitation

R

+TX –IN

+IN+

–R must be > 250 and <1100 Ohms

Page 10: HIM - Yokogawa Electric › product_HIMHART_IM.us.pdfHIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor 2 The Interface

HIM

10 The Interface Solution Experts

Smart HART LoopInterface and Monitor

The HIM PC Configuration Software can be used toprogram all of the HIM’s parameters. Once the defaultconfiguration has been saved, it is safe to programother parameters. The PC Software is made up ofthese sections:

1. HIM Status and Information Section–The leftside of the screen includes seven boxes that displaythe different settings of the attached HIM.

Program Status–Displays the activity of theconnected HIM. It will show you if the unit is Idle,Uploading, Downloading, Monitoring or Searching.

HIM Device Info–Displays the individual characteristics of the attached HIM, such as its Identifi-cation, Hardware and Software Revisions, and thelast date that the device was configured.

HIM Tag–A phrase used to identify a HIM.

Figure 7. HIM PC Configuration Software Screen

HIM Device Status–Displays how the HIM is function-ing, giving a brief summary of any errors or displayingOK if it is operating normally.

HIM Displayed Data–this display mirrors what the at-tached HIM is displaying.

Progress–This bar stays in motion any time the HIMis monitoring, uploading or downloading.

Communication Status–monitors the PC Software’sability to communicate with the HIM.

2. HART/Display/ Alarms/Analog Outputs/CustomCurve/ Scaling Tabs–These tabs change the rightside of the screen to allow you to set the appropriatepart of the HIM’s configuration. Refer to the associ-ated pages in this document for additional informationon these tabs.

3. Menu Bar/Tool Bar– Dropdown menus and corre-sponding icons allow you to perform various functionsthroughout the PC Configuration Program.

1

2

3

PC Configuration Software

Page 11: HIM - Yokogawa Electric › product_HIMHART_IM.us.pdfHIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor 2 The Interface

The Interface Solution Experts 11

HIMSmart HART Loop

Interface and Monitor

HART ParametersTo program the HART parameters, change the settingsin the Communications Settings box, then press QuickSet. See the descriptions below of the varioussections of the screen.

HART AddressThe HART Address is the address of the HART devicethat the HIM will be monitoring.

Number of RetriesThe Number of Retries can be set between 1 and 9,and will determine how many times the HIM willattempt to poll the HART transmitter (without success),before it indicates a HART Fault condition.

Normal/Burst/Listen (Passive) ModesThe HIM can operate in one of four modes: Normal,Burst, or Listen (Passive) and Listen (Specified Slave).In each of these modes, the HIM attempts to find aHART transmitter.

In Normal mode, the HIM polls the HART loop for atransmitter, then polls the HART instrument twice persecond, requesting the current process status and theHART instrument’s diagnostic status. The HARTinstrument responds with the requested data.

In Burst mode, the monitored HART instrument isprogrammed to continuously transmit its processvariable and health status. The HIM samples thecontinuous HART data three times per second.

Listen (Passive) mode allows the HIM to operate on aloop that already has primary and secondary HARTmasters. In Listen (Passive) mode, the monitorconnects passively, continuously sampling HART datafrom a smart instrument without affecting normal loopoperation. When using this mode, either the monitoredsmart HART instrument must be set in Burst Mode or aHART master must be continuously polling the smartHART slave device.

The HART protocol allows for two communicationsmasters on the loop, a Primary and a Secondary.Setting the HIM to function as the Primary HARTMaster in the application means that any other HARTdevice in the loop must be configured either as a HARTSecondary Master (1 per loop) or as a HART Slave (upto 16 per loop). Conversely, setting the HIM to functionas the Secondary HART Master allows other HARTdevices to function either as a Primary Master or asslaves. Configuring more than one device on a singleloop as a Primary or Secondary HART Master willcause a communications failure.

Listen (Specified Slave) When multiple HART instruments are present, theListen (Passive) mode cannot be used because datareturned from one instrument will overwrite the datapreviously stored in the HIM. If multiple HART slaveinstruments are communicating on the loop, the HIMwill overwrite its internal HART data sets with the latestdevice read from the bus, no matter where the dataoriginates. To allow selective monitoring on a multi-instrument loop, and to allow multiple HIMs to be usedon a digital loop, the Listen (Specified Slave) feature isused.

If the HIM is in “Listen” mode it is not a HART commu-nication master and therefore is not in control ofcommunication. Other HART masters are controllingthe polling of slaves and the HIM can only “Listen”.

The HIM must be able to detect when it has not heardfrom its assigned slave device so that it can declare a“No HART” input and force outputs to the valuesspecified by the user. The HIM must therefore be toldto wait an appropriate amount of time for the slavedevice to send its message before the HIM declares“No HART”. This timing coordination is accomplishedwith Timeout Period.

Timeout Period is a value between 1 and 30sec andmust be greater than the period between polls by theHART master of the Specified Slave. For example,assume that there are five HART transmitters on thesame multi-drop loop as the HIM. The HART master isconfigured to poll each device every second. It thentakes the HART master five seconds to repeat the pollto the one device being monitored by the HIM. the HIMTimeout Period must be set at a value greater than five

Page 12: HIM - Yokogawa Electric › product_HIMHART_IM.us.pdfHIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor 2 The Interface

HIM

12 The Interface Solution Experts

Smart HART LoopInterface and Monitor

seconds. In this example, we will use seven seconds.The HIM then sees its slave device speak and waitsseven seconds for it to speak again. As long as theHIM sees a new message from its slave device itsoutputs are updated based upon the measured vari-ables. If the slave device does not speak within theseven second period, the HIM declares a “No HART”situation and sends its outputs to the failed communi-cations values.

To use this feature, proceed with the following steps:

1. Select the Listen (Specified Slave) button.

2. Enter your desired value into the Timeout Period(s)text box.

Factory default is 5 seconds. The maximum TimeoutPeriod is 30 seconds.

3. Set the exact slave address of the instrument youwish to monitor. Click the Set Slave Address button.This brings up the HART Slave Device Long FormatAddress Settings screen (Figure 8). Enter the requiredinformation into the appropriate text boxes.

The Manufacturer’s ID and Device Type ID for theinstrument that the HIM will listen to are available fromthe HART Foundation website at www.hartcomm.organd/or the instrument manufacturer.

Values obtained from the HART website are in HEXcode. The HIM does not use HEX code; you mustconvert this value to Decimal code.

Figure 8. HART Slave Device Long Format Address SettingsScreen

To convert HEX to Decimal code, perform thefollowing steps:

Access the Calculator feature in MicrosoftWindows® by opening the Start menu. Next,select Programs then Accessories and finallyCalculator.

Ensure that the Calculator is in Scientific mode.To do this, select the View dropdown menuand choose Scientific.

Click the Hex radio button and enter the HEXcode value.

Next, click the Dec button and the value will beconverted into the Decimal value.

Enter the converted value into the proper parameter.

The Device ID Number is the serial number ofthe exact device to which the HIM will listen.

4. Once complete, press OK.

Download the information to your instrument once youare finished.

Auto Clear Status BitMost HART instruments indicate when a device'sconfiguration has been changed. This indication(status bit) can be reset by sending HART command38–reset configuration changed. Checking the AutoClear Status Bit box causes the HIM to issue thiscommand whenever the HART instrument it ismonitoring has its configuration changed. However,the HIM can also be set to alarm on this bit (seeProgramming the Alarm Parameters). If the HIM isboth set to alarm and to auto clear, then it will doboth–going into alarm mode and resetting thatindication.

Quick Read/SetThe Quick Read button causes the PC ConfigurationSoftware to read the communications information fromthe attached HIM; the Quick Set button causes thesoftware to configure the HIM’s communicationssettings to match those of the PC Software.

Page 13: HIM - Yokogawa Electric › product_HIMHART_IM.us.pdfHIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor 2 The Interface

The Interface Solution Experts 13

HIMSmart HART Loop

Interface and Monitor

HART Device InfoThis box displays the identification and revisioninformation of the monitored HART instrument.

HART Device StatusThe HART Device Status box displays the currentstatus of the monitored HART transmitter. In a smalldouble-box, the software displays the code (hexnumber) associated with the status.

VariablesThe device will monitor up to the first four HARTvariables sent by your transmitter. This portion of thescreen displays those variables and the Loop Current.

HART Device Range & LimitsThis portion of the screen displays the range and thesensor limits of the monitored HART transmitter.

Display ParametersThe Display tab configures the HIM’s LCD display. Toprogram the Display parameters, change the settings inthe Display Source box, then press Quick Set. Seethe following descriptions of the various sections of thescreen.

Figure 9. Display Tab

Toggle, Variable ListThe Toggle checkbox causes the HIM to sequentiallydisplay two HART variables in five second increments.Directly below the Toggle checkbox are two list boxesto select the variables that you would like to bedisplayed. Notice that if you select a scaled variable,it is important to check on the Scaling page to verifythat you have set all of the scaling parameters.

Use Custom LabelThe Custom Label is used to display a calculated orscaled variable. Clicking the Use Custom Label boxcauses the HIM to always display the custom label asEngineering Units (EGUs).

PrecisionThe Precision buttons allow you to change the numberof decimal places displayed by the HIM.

Quick SetThe Quick Set button programs the HIM with theinformation on the Display page.

Display FormatThe HIM reads the dynamic process variable supportedby HART sensors. Generally, the HIM’s LCD displayedvalues range from -99999 to 99999. Occasionally,these process variable values may extend past thisrange. To improve the displayed readings, valuesbelow -XXXXX and above XXXXX are translated intoexponential form. Below is an example of the appear-ance of the display when certain values are sensed.

Value Display

12345 123451234500 1.23E06

-500000 -5.00E05

Page 14: HIM - Yokogawa Electric › product_HIMHART_IM.us.pdfHIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor 2 The Interface

HIM

14 The Interface Solution Experts

Smart HART LoopInterface and Monitor

Alarms ParametersThe Alarms tab controls the programmable alarmtrip(s) option. This screen will be grayed out if theattached HIM is not equipped with at least one alarmtrip. To program the Alarm parameters, change thesettings in the Alarm1 and/or Alarm2 box, then pressQuick Set. The sections of the screen are describedbelow.

Trip/Fault AlarmsA Trip Alarm monitors a selected variable and tripseither when the variable exceeds a set value (TripHigh) or when the variable falls below a selected value(Trip Low). The Source specifies which variable will bemonitored, while the Trip Point sets the point at whichthe alarm will trip. After the alarm trips, the DeadBand determines how far past the trip point thevariable will have to go before the alarm conditionreturns to normal.

There are two types of Fault Alarms. A HIM FaultAlarm monitors the health of the HART monitor. It willtrip whenever the internal error status word is set. Forexample, if the HIM’s configuration file becomescorrupt, this alarm will trip and the monitor will displayBAD_CONFIG. A Field Device Fault Alarm monitorsthe health of the HART transmitter. This fault alarmwill trip for any of these eight malfunctions:

Figure 10. Alarms Tab

Device Malfunction (Bit 7)Relay trips whenever it detects that a hardware error orfailure has occurred in the connected HART device.

Configuration Changed (Bit 6)Relay trips whenever it detects that the connectedHART device has had its configuration changed.

Cold Start (Bit 5)Relay trips whenever the power to the HART device isinterrupted. It will also trip during a HART MasterReset or Self Test Command.

Additional Status (Bit 4)Relay trips whenever the connected HART devicereports a condition requiring HART Command #48,which is Read Additional Information. This indicatesthat the instrument needs attention from a device withfull HART command capability.

Output Current Fixed (Bit 3)Relay trips whenever the HIM detects that theconnected HART device’s output is no longerresponding to changes in its input, and is being held ata predefined level.

PV Analog Output Saturated (Bit 2)Relay trips whenever it detects that both its analog anddigital representations of the Primary Variable areoutside rated operating limits, and no longer reflect thetrue sensor input.

Non-PV Out of Limits (Bit 1)Relay trips whenever one of the HART ancillaryvariables (second, third or fourth), is operating outsidethe limits that can be effectively measured.

PV Out of Limits (Bit 0)Relay trips whenever the HART Primary Variable isoperating outside the limits that can be effectivelymeasured.

Delay & Fail SafeBy entering a value in the Delay box, you can specifyhow long (in seconds) the alarm condition needs toexist before the alarm trips. Failsafe alarms (boxchecked) de-energize when in alarm condition;Non-Failsafe alarms energize when tripped.

Page 15: HIM - Yokogawa Electric › product_HIMHART_IM.us.pdfHIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor 2 The Interface

The Interface Solution Experts 15

HIMSmart HART Loop

Interface and Monitor

HART Additional Status Alarm BitsHART Additional Status also called “More Status” and“Command 48” is where device manufacturers installthe custom diagnostics for the specific device. Foryour particular application, you may choose all of thesediagnostics to cause the HIM relay to trip or just onediagnostic bit to trip the HIM relay (or any combinationin between). The manufacturer of the HART device willbe the source for the specific diagnostic information.

Selecting the Field Device Fault Alarm function in theAlarms screen allows you to enable the HIM to setalarm states, when in fault mode, based on the bitsettings of the additional status information returned bycertain HART instruments. This provides flexibility tothe requirement of alarming on additional status infor-mation.

Choosing this feature, you are given the ability tospecify the bit(s) on which to alarm. To access thisfeature, check the Additional Status box. The Editbutton will appear in the HART Additional Status Bitssection of the screen. Clicking the Edit box brings upthe Additional HART Status Alarm Bits Settings window(Figure 11). Check the box(es) that correspond to thebits you wish to use; click OK.

Download the information to your instrument once youare finished.

Figure 11. Additional HART Status Alarm Bits Settings Window

Read & Quick Set ButtonsThe Read button causes the PC Configuration Softwareto read the alarm information from the attached HIM;The Quick Set button causes the software to configurethe HIM's alarm settings to match those currentlyentered in the PC Software.

Page 16: HIM - Yokogawa Electric › product_HIMHART_IM.us.pdfHIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor 2 The Interface

HIM

16 The Interface Solution Experts

Smart HART LoopInterface and Monitor

Analog Outputs ParametersThe HIM comes with either two (–2AO) or three (–3AO)analog outputs. The Analog Outputs tab allows you tospecify which HART variable is to be monitored as thesource of the analog output, the input range and outputrange, and how the output will react when the variableinput is out of range. To program the Analog Outputsparameters, change the settings in the Output1/2/3boxes, then press Quick Set. See the descriptionsbelow of the various sections of the screen.

SourceSource defines the variable that the analog output willmonitor. Notice that selecting one of the scaledoutputs will require you to make changes to theScaling tab, and selecting the Custom Curve option willrequire you to make changes to the Custom Curve tab.

Input/Output RangeThe Input or Output Range defines the range of thesource input and the range of the analog output.These two sets of fields can be used to scale theHIM’s output.

Figure 12. Analog Outputs Tab

For example, you have a vortex flow meter with animbedded RTD that measures the processtemperature, and that temperature is assigned to theHART Secondary Variable. The full range of the RTDsensor is from –400°F to +1760°F, but your flowstream will always be between 0° and 400°F. To scalethe analog output, for Output 1, set the Source as SV.Set the Input Range to 0° and 400°F, and the OutputRange to 4mA to 20mA. Click Quick Set to downloadthe new configuration file to the HIM.

Output Current BoxThe Output Current Box on the Analog Outputs Tabdisplays up-to-the-second information on the value, inmA, of the analog output.

Fail ModeThe Fail Mode setting determines how the HIM willrespond when its monitored input fails. If Fail Mode isset to High and the measured input goes out of range,or any detected error occurs in the HART transmitter,the analog output will output a 23.6mA signal. If FailMode is set to Low and the measured input goes out ofrange, or any detected error occurs in the HARTtransmitter, the analog output will output a signal thatis 90% of the lower range value below 4mA; it willoutput 0mA if the lower range is set to 0mA.

If Fail Mode is set to Hold Last, the HIM will continueto output the last value it recorded before the inputfailed. If Fail Mode is set to Hold Last Then High orHold Last Then Low, the HIM will continue to output thelast value recorded for a set amount of time (accordingto Hold Last Duration box), then either fail high or faillow, respectively.

Quick Set ButtonThe Quick Set button causes the software to configurethe instrument’s analog output settings to match thosecurrently entered in the PC Software.

Trim ButtonThe Trim button brings up the Trim Menu, allowing youto set the device’s output to match the reading of theloop. Refer to the Programming the TrimmingParameters section of this manual for moreinformation.

Page 17: HIM - Yokogawa Electric › product_HIMHART_IM.us.pdfHIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor 2 The Interface

The Interface Solution Experts 17

HIMSmart HART Loop

Interface and Monitor

Configuring Analog Output TrimmingThe Analog Output Trimming section of the softwareallows you to match the HART monitors analog outputto the output measured by a calibration device. Thiswill require a calibrated multimeter, such as a HP Model3478A or equivalent, accurate to ±0.009%.

Note:Trimming the analog output of the monitornullifies any scaling that may have been

performed in the Scaling tab.

User TrimmingTo trim the device, attach a multimeter to the analogoutput, then click the Fix Output at Low Point button.Read the value on the multimeter, enter it into theMeasured Output Loop Current portion of the Trimmingbox, and press Trim. Repeat this sequence until theanalog output matches the minimum point (4mA for a4-20mA output) when you click the Fix Output at LowPoint button.

After the low point is trimmed, press the Fix Output atHigh Point button. Read the value on the multimeter,enter it into the Measured Output Loop Current portionof the Trimming box, and press Trim. Repeat thissequence until the analog output matches themaximum point (20mA for a 4-20mA output) when youclick the Fix Output at High Point button.

When finished, press the Unfix Output button.

Figure 13. Trimming Window

Fix Current UtilityThe Fix Current Utility allows you to force the HIM tooutput any current value from 0-20mA. This can beused to match the calibration of your other equipment.To fix the current, simply enter the value in the Currentbox (in mA) that you want the HIM to output, and clickFix Output. When you are finished, make sure topress the Unfix Output button so that the HIM canreturn to normal operation.

Page 18: HIM - Yokogawa Electric › product_HIMHART_IM.us.pdfHIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor 2 The Interface

HIM

18 The Interface Solution Experts

Smart HART LoopInterface and Monitor

Custom Curve ParametersThe custom curve tab allows you to set up a customcurve of up to 128 points. A custom curve can eitherbe created from scratch or loaded from a previouslycreated comma separated value (.csv) file. Toprogram the Analog Outputs parameters, change thesettings in the Custom Curve tab, then press DownloadTable. See the descriptions below of the varioussections of the screen.

ModeCheck the Enabled box to begin programming thecustom curve.

Source VariableThe Source Variable defines the variable that thecustom curve will calculate. Notice that if you select ascaled variable, you may need to click on the Scalingtab and verify the settings for your scaled variable.

Quick SetThe Quick Set button causes the software to configurethe HIM’s custom curve settings to match thosecurrently entered in the PC Software.

Figure 14. Custom Curve Tab

Custom Curve VariableThe Custom Curve Variable displays up-to-the-secondinformation on the value of the Custom Curve. Pressthe Monitor button to display the variable information.

Custom CurveThe middle section of the screen displays the customcurve table. After enabling custom curve mode andsetting the variable to be monitored, continue byselecting the number of points for the curve. Enter theactual linearization points into the custom curve table,inserting the source variable into the X Column, andthe corresponding data (i.e. the °C, °F, Gallons, PSIG,Millimeters, etc.) into the Y Column.

Note:When entering data in the linearization table, makesure that you enter a number into every open cell.

Custom Curve FileThese buttons allow you to manipulate custom curvefiles, including the important Save Table command thatwill save a table to your hard drive.

Upload TableMoves a custom curve file from the connected HIM tothe PC Software for editing or storage.

Download TableConfigures the HIM by downloading the custom curvetable from the PC Software to the HIM.

Save TableSaves a displayed custom curve table to memory onyour computer’s hard drive.

Load TableLoads a previously saved custom curve table.

Clear TableClears the displayed custom curve table.

When you have finished changing all your settings,download the information to the HIM using theDownload Table button. If you have selected a scaledvariable, you should also click on the Scaling tab andset the scaling parameters.

Page 19: HIM - Yokogawa Electric › product_HIMHART_IM.us.pdfHIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor 2 The Interface

The Interface Solution Experts 19

HIMSmart HART Loop

Interface and Monitor

Full PrimaryVariable range (in PSI)

Control level range

(50% to 100% of total level)

DigitalPressure

TransmitterHART Monitor

(120 PSI)HARTSignal

Loop Display(reads 0-100%

of controllevel)

Controller maintainingcontrol from 50-100% of full scale

(60-120 inH 0/2.15-4.3 PSI). 4-20mA from HART Monitor

should represent 60-120inH 0.

4-20mASignal

4-20mASignal

2

2

Figure 15. Scaling Tab

Figure 16. The HIM’s Scaling feature works to get the most out of your existing process instruments

Scaling ParametersThe Scaling tab allows you to configure the values forscaled variables. To scale the selected variable, enterthe values into the appropriate boxes, then click on theTransfer menu and click Download to transfer the newscaled values to the HIM. (If any scaled variable wasselected in the Display, Alarm or Analog Outputs tabs,then the corresponding scaled variable section willbecome active for editing).

The HIM’s versatile scaling feature has many possibleapplications, as is shown in the illustration below.

Suppose you are using a digital pressure (DP)transmitter to measure the level of a tank in eithercentimeters/inches or PSI. Since the tank is only 300centimeters (10 feet) high, the full range of the primaryvariable (PV) output from the DP transmitter is 0-4.3PSI. You want to display the full level range (incentimeters/inches of water) on the HIM. You alsoneed to control the level from 50% to 100%, since thetank must be at least 50% full at all times. Finally,your existing loop indicator and level controller needs4-20mA to represent 150 to 300 centimeters (60 to 120inches) of water. How do you do this?

Scaling Illustration1. Since you want to display the full level range ininches of water (in H

2O) on the HIM, and the HIM is

reading PSI as the primary variable, first go to theDisplay tab and select Scaled PV as your displaysource.

2. Go to the Scaling tab and set up the PV Zero andPV Full values, and the Scaled PV Zero and Fullvalues. PV Zero would be 0 (PSI) and PV Full wouldbe 4.3 (PSI). Scaled PV would correlate to zero being0 in H

2O and full being 120 in H

2O. The HIM should

now (after downloading) display the full range inin H2O.

3. To manipulate the HIM’s analog output, go to theAnalog Outputs tab. Select Scaled PV as the Output 1source. Since you need to control the level from 50%to 100%, the Input Range should be 60 to 120 in H

2O

and the Output Range should be 4mA to 20mA.

Page 20: HIM - Yokogawa Electric › product_HIMHART_IM.us.pdfHIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor 2 The Interface

HIM

20 The Interface Solution Experts

Smart HART LoopInterface and Monitor

Customer SupportMoore Industries is recognized as the industry leaderin delivering top quality to its customers in productsand services. We perform a battery of stringent qualityassurance checks on every unit we ship. If any MooreIndustries product fails to perform up to rated specifi-cations, call us for help. Our highly skilled staff oftrained technicians and engineers pride themselves ontheir ability to provide timely, accurate and practicalanswers to your process instrumentation questions.

Factory phone numbers are listed on the back cover ofthis manual.

If problems involve a particular instrument, there areseveral pieces of information that can be gatheredbefore you call the factory that will help our staff getthe answers you need in the shortest time possible.For fastest service, gather the complete model andserial number(s) of the problem unit(s) and the jobnumber of the original sale.

Page 21: HIM - Yokogawa Electric › product_HIMHART_IM.us.pdfHIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor 2 The Interface

The Interface Solution Experts 21

HIMSmart HART Loop

Interface and Monitor

Appendix A: HIM MODBUSFeatureThe HIM PC program allows you to configure theHART monitor. A HART Monitor with the MODBUSoption provides a digital MODBUS output to a con-nected MODBUS-based controller. Selecting theMODBUS tab allows you to set the MODSBUS com-munications parameters. Notice that the MODBUS tabwill only be available in units with the MODBUS option.

Figure A-1. MODBUS Tab

Comms SettingsThe Comms Settings include the following:

MODBUS AddressThe MODBUS Address is the number that the HIMmonitor uses to identify itself on the MODBUS net-work. The MODBUS address is configurable from 1 to247. By default, it will assume a MODBUS address of01.

Baud RateThe Baud Rate is the speed of data transmission. Itshould be set to match the baud rate of the attachedcontroller. The interface supports the following baudrates: 300, 600, 1200, 2400, 4800, 9600 and 19200.

ParityThe HART monitor supports even, odd and no Parity.The data format is one start bit, 8 data bits and onestop bit.

Floating Point Word OrderBy default, the HART monitor will use the StandardLSW (least significant word) floating point word orderformat. This stores the most significant bits in thesecond register and the least significant bits in the firstregister. Selecting Swapped MSW (most significantword) will reverse the order, storing the most signifi-cant bits in the first register and the least significantbits in the second register.

MODBUS RegistersThe HART Monitor outputs a MODBUS signal to theattached controller. To access the MODBUS registersfor variable, input/output or error information, refer toTable A-1 (MODBUS Register Definitons table) and/orTable A-2 (System Status Registers table).

Page 22: HIM - Yokogawa Electric › product_HIMHART_IM.us.pdfHIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor 2 The Interface

HIM

22 The Interface Solution Experts

Smart HART LoopInterface and Monitor

Figure A-2. Installing a HIM with MODBUS output into the loop using the Transmitter Excitation (+TX) terminal

READYINPUT

60.278TRIP 2TRIP 1

COM

DEG C0ADDR

COMMON

NC (normally closed)

NO (normally open)

4-20mA

DCS

SensorInput

NO

NC

DC

GN

D

+

24VdcPower Source

DC

C

R must be > 250 ohms and <1100 ohms

R

HARTField Instrument(Temperature,

Pressure,Level,

Flow Multivariable)

HART Communicatorcan be connectedanywhere on the loop

CO

M+IN

+TX –IN

MODBUS output (with MODBUS option)

AB

S

RS485 / RS232 Converter

TO serial(COM) portof PC

MODBUS Host

Page 23: HIM - Yokogawa Electric › product_HIMHART_IM.us.pdfHIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor 2 The Interface

The Interface Solution Experts 23

HIMSmart HART Loop

Interface and Monitor

Register Range Description

HART Primary variable

HART Secondary variable

HART Third variable

HART Fourth variable

PV scaled

SV scaled

TV scaled

FV scaled

Linearized variable

Analog Output 1 current x 100mA

Analog output 2 current x 100mA

Analog output 3 currentx 100mA

HIM Status InformationBit 0 = hardware failureBit 1 = EEPROM failBit 2 = EEPROM configuration checksum errorBit 3 = EEPROM calibration checksum errorBit 4 = EEPROM blankBit 5 = Out of range errorBit 6 = Division by zero errorBit 7 = Configuration data bad errorBit 8 = COP SW failBit 9 = RAM test failBit 10-13 = not usedBit 14 = HART device malfunction status bit setBit 15 = No HART communications status

HART status information (as per HART specification)

Table A-1. MODBUS Register Definitions

0

1

2

3

4

5

6

7

8

9

10

11

12

13

Page 24: HIM - Yokogawa Electric › product_HIMHART_IM.us.pdfHIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor 2 The Interface

HIM

24 The Interface Solution Experts

Smart HART LoopInterface and Monitor

HART instrument SV EGU (MSB = 0, LSB = HART EGU code)

HART instrument TV EGU (MSB = 0, LSB = HART EGU code)

HART instrument QV EGU (MSB = 0, LSB = HART EGU code)

Device ID MSW

Device ID LSW

HART Device Manufacturer ID

HART Device, device type code

HART device, device ID MSW

HART Device, device ID LSW

HIM Alarm Status (Bit 0 = alarm 1, Bit 2 = alarm 2)

HART Primary variable (float format)

HART Secondary variable (float format)

HART Third variable (float format)

Hart Fourth variable (float format)

Scaled Primary variable (float format)

Scaled Secondary variable (float format)

Scaled Third variable (float format)

Scaled Fourth variable (float format)

Linearized varialbe (float format)

Analog output 1 current x 100mA

Analog output 2 current x 100mA

Analog output 3 current x 100mA

14 HART instrument PV EGU (MSB = 0, LSB = HART EGU code)

15

16

17

18

19

20

21

22

23

24

256-257

258-259

260-261

262-263

264-265

266-267

268-269

270-271

272-273

274-275

276-277

278-279

Page 25: HIM - Yokogawa Electric › product_HIMHART_IM.us.pdfHIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor 2 The Interface

The Interface Solution Experts 25

HIMSmart HART Loop

Interface and Monitor

Table A-2. System Status Registers

Bit 7

Bit 6

Bit 0

Bit 1

Bit 2

Bit 3

Bit 4

Bit 5

Bit 6

Bit 7

MSB = device status

LSB = device error code

Bit Position Description

HART device no comms

HART device malfunction

HW fail

EEPROM fail

EEPROM checksum error

EEPROM calib data error

EEPROM blank

out of range value

division by zero

bad configuration

MSB/LSBInt 16

(16 bit integar)

Page 26: HIM - Yokogawa Electric › product_HIMHART_IM.us.pdfHIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor 2 The Interface

United States • [email protected]: (818) 894-7111 • FAX: (818) 891-2816

Australia • [email protected]: (02) 8536-7200 • FAX: (02) 9525-7296

Belgium • [email protected]: 03/448.10.18 • FAX: 03/440.17.97

The Netherlands • [email protected]: (0)344-617971 • FAX: (0)344-615920

China • [email protected]: 86-21-62491499 • FAX: 86-21-62490635

United Kingdom • [email protected]: 01293 514488 • FAX: 01293 536852

Declaration of ConformityEMC Directive 89/336/EEC

Quality Assurance Director Moore Industries-Europe General Mgr.

June 20, 2003

• Manufacturer’s Name: Moore Industries-International, Inc.• Manufacturer’s Address: 16650 Schoenborn Street

North Hills, CA 91343-6196USA

Declares that the product(s):

• Product Name: HIM

MODEL / INPUT / OUTPUT / POWER / OPTIONS / HOUSING

• Model Number(s): HIM * * * * *

* Indicates any input, output, power, option and housing as listed on the product data sheet

• Conforms to the following EMC specifications:EN 61326-1, 1998, Electromagnetic Compliance (EMC) requirements for electrical equipment for control use.

• Supplementary Information:None

Date Fred Adt Robert Stockham

European Contact: Your Local Moore Industries Sales and Service Office

Page 27: HIM - Yokogawa Electric › product_HIMHART_IM.us.pdfHIM HIM November 2005 224-778-00C Smart HART ® Loop Interface and Monitor Smart HART ® Loop Interface and Monitor 2 The Interface

To return equipment to Moore Industries for repair, follow these four steps:

1. Call Moore Industries and request a Returned Material Authorization (RMA) number.

Warranty Repair –If you are unsure if your unit is still under warranty, we can use the unit’s serial numberto verify the warranty status for you over the phone. Be sure to include the RMAnumber on all documentation.

Non-Warranty Repair –If your unit is out of warranty, be prepared to give us a Purchase Order number whenyou call. In most cases, we will be able to quote you the repair costs at that time.The repair price you are quoted will be a “Not To Exceed” price, which means that theactual repair costs may be less than the quote. Be sure to include the RMA number onall documentation.

2. Provide us with the following documentation:

a) A note listing the symptoms that indicate the unit needs repairb) Complete shipping information for return of the equipment after repair

c) The name and phone number of the person to contact if questions arise at the factory

3. Use sufficient packing material and carefully pack the equipment in a sturdy shippingcontainer.

4. Ship the equipment to the Moore Industries location nearest you.

The returned equipment will be inspected and tested at the factory. A Moore Industriesrepresentative will contact the person designated on your documentation if more information isneeded. The repaired equipment, or its replacement, will be returned to you in accordance withthe shipping instructions furnished in your documentation.

WARRANTY DISCLAIMERTHE COMPANY MAKES NO EXPRESS, IMPLIED OR STATUTORY WARRAN-TIES (INCLUDING ANY WARRANTY OF MERCHANTABILITY OR OF FITNESSFOR A PARTICULAR PURPOSE) WITH RESPECT TO ANY GOODS OR SER-VICES SOLD BY THE COMPANY. THE COMPANY DISCLAIMS ALL WARRAN-TIES ARISING FROM ANY COURSE OF DEALING OR TRADE USAGE, ANDANY BUYER OF GOODS OR SERVICES FROM THE COMPANY ACKNOWL-EDGES THAT THERE ARE NO WARRANTIES IMPLIED BY CUSTOM ORUSAGE IN THE TRADE OF THE BUYER AND OF THE COMPANY, AND THATANY PRIOR DEALINGS OF THE BUYER WITH THE COMPANY DO NOT IM-PLY THAT THE COMPANY WARRANTS THE GOODS OR SERVICES IN ANYWAY.

ANY BUYER OF GOODS OR SERVICES FROM THE COMPANY AGREESWITH THE COMPANY THAT THE SOLE AND EXCLUSIVE REMEDIES FORBREACH OF ANY WARRANTY CONCERNING THE GOODS OR SERVICESSHALL BE FOR THE COMPANY, AT ITS OPTION, TO REPAIR OR REPLACETHE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE. THECOMPANY SHALL IN NO EVENT BE LIABLE FOR ANY CONSEQUENTIAL ORINCIDENTAL DAMAGES EVEN IF THE COMPANY FAILS IN ANY ATTEMPTTO REMEDY DEFECTS IN THE GOODS OR SERVICES , BUT IN SUCH CASETHE BUYER SHALL BE ENTITLED TO NO MORE THAN A REFUND OF ALLMONIES PAID TO THE COMPANY BY THE BUYER FOR PURCHASE OF THEGOODS OR SERVICES.

RETURN PROCEDURES

ANY CAUSE OF ACTION FOR BREACH OF ANY WARRANTY BY THECOMPANY SHALL BE BARRED UNLESS THE COMPANY RECEIVESFROM THE BUYER A WRITTEN NOTICE OF THE ALLEGED DEFECT ORBREACH WITHIN TEN DAYS FROM THE EARLIEST DATE ON WHICH THEBUYER COULD REASONABLY HAVE DISCOVERED THE ALLEGED DE-FECT OR BREACH, AND NO ACTION FOR THE BREACH OF ANY WAR-RANTY SHALL BE COMMENCED BY THE BUYER ANY LATER THANTWELVE MONTHS FROM THE EARLIEST DATE ON WHICH THE BUYERCOULD REASONABLY HAVE DISCOVERED THE ALLEGED DEFECT ORBREACH.

RETURN POLICYFor a period of thirty-six (36) months from the date of shipment, and undernormal conditions of use and service, Moore Industries ("The Company") willat its option replace, repair or refund the purchase price for any of its manu-factured products found, upon return to the Company (transportation chargesprepaid and otherwise in accordance with the return procedures establishedby The Company), to be defective in material or workmanship. This policyextends to the original Buyer only and not to Buyer's customers or the usersof Buyer's products, unless Buyer is an engineering contractor in which casethe policy shall extend to Buyer's immediate customer only. This policy shallnot apply if the product has been subject to alteration, misuse, accident, ne-glect or improper application, installation, or operation. THE COMPANYSHALL IN NO EVENT BE LIABLE FOR ANY INCIDENTAL OR CONSE-QUENTIAL DAMAGES.

Specifications and Information subject to change without notice.© 2005 Moore Industries-International, Inc.

United States • [email protected]: (818) 894-7111 • FAX: (818) 891-2816

Australia • [email protected]: (02) 8536-7200 • FAX: (02) 9525-7296

Belgium • [email protected]: 03/448.10.18 • FAX: 03/440.17.97

The Netherlands • [email protected]: (0)344-617971 • FAX: (0)344-615920

China • [email protected]: 86-21-62491499 • FAX: 86-21-62490635

United Kingdom • [email protected]: 01293 514488 • FAX: 01293 536852