Home Inspection Report

5555 Treetop Lane Newberg, Oregon 97132

Prepared for: Robert Baker

Prepared by: Duff Home Inspections

CCB# 205217 OCHIU# 1618

Page 2: Home Inspection Report · 1. Fireplace Construction: Prefab 2.Type: natural gas 3. Fireplace Insert: Standard 4. Smoke Chamber: Metal 5. Hearth: Flush Mounted Tile Heating System

Table of Contents Definitions 2

General Information 2

Lots and Grounds 3

Exterior 4

Roof 4

Garage/Carport 5

Electrical 5

Structure 6

Attic 6

Crawl Space 7

Air Conditioning 8

Fireplace/Wood Stove 9

Heating System 9

Plumbing 10

Bathroom 11

Kitchen 12

Bedroom 13

Living Space 14

Laundry Room/Area 14

Summary 15

Duff Home InspectionsRobert Baker

5555 Treetop LanePage 1 of 19

Palm-Tech Inspector, Copyright © 1998-2016, PDmB, Inc.

Page 3: Home Inspection Report · 1. Fireplace Construction: Prefab 2.Type: natural gas 3. Fireplace Insert: Standard 4. Smoke Chamber: Metal 5. Hearth: Flush Mounted Tile Heating System

DefinitionsNOTE: All definitions listed below refer to the property or item listed as inspected on this report at the time of inspection

A Acceptable Functional with no obvious signs of defect. NP Not Present Item not present or not found. NI Not Inspected Item was unable to be inspected for safety reasons or due to lack of power, inaccessible, or disconnected at

time of inspection. M Marginal Item is not fully functional and requires repair or servicing. D Defective Item needs immediate repair or replacement. It is unable to perform its intended function.

General Information

Property Information

Property Address 5555 Treetop Lane

City Newberg Oregon Oregon Zip 97132

Client Information

Client Name Robert Baker Phone (555)555-5555

Inspection Company

Inspector Name Daniel Duff Company Name Duff Home Inspections

Conditions

Others Present Buyer's Agent Property Occupied Vacant Estimated Age 2010 Entrance Faces North Inspection Date 04/03/2015 Start Time 10:30am End Time 1:00pm Electric On Yes No Not Applicable Gas/Oil On Yes No Not Applicable Water On Yes No Not Applicable Temperature 55 Weather Partly sunny Soil Conditions Wet Space Below Grade Basement Building Type Single family Garage Attached Sewage Disposal City How Verified Visual Inspection Water Source City How Verified Visual Inspection Additions/Modifications None Permits Obtained N/A How Verified Seller

Duff Home InspectionsRobert Baker

5555 Treetop LanePage 2 of 19

Palm-Tech Inspector, Copyright © 1998-2016, PDmB, Inc.

Page 4: Home Inspection Report · 1. Fireplace Construction: Prefab 2.Type: natural gas 3. Fireplace Insert: Standard 4. Smoke Chamber: Metal 5. Hearth: Flush Mounted Tile Heating System

Lots and GroundsA NP NI M D

1. Driveway: Pebble top 2. Walks: Pebble top an concrete 3. Steps/Stoops: Pebble top 4. Deck: Treated and stained wood - Crack in kick plate, wood broken off on

the far right. Paint needed to prevent damage to the exposed wood.

5. Balcony: Treated and stained wood - Balcony/deck ledger is mounted incorrectly on the left side section. Currently the deck ledger is being help to the wall by nails only. 1/2 lag bolts (see example photo below) spaced roughly every 16 inches are needed. Improper mounting can be a safety issue. Recommend a licensed contractor install proper mounting bolts.

Properly secured

6. Grading: Minor slop in front/Steep slope in rear 7. Swale: Adequate slope and depth for drainage 8. Vegetation: Shrubs 9. Window Wells: Drain present

10. Exterior Surface Drain: Culvert drain 11. Fences: Wood 12. Lawn Sprinklers: Front yard only - Box housing has shifted from soil

movement, and lip with no longer shut.

Duff Home InspectionsRobert Baker

5555 Treetop LanePage 3 of 19

Palm-Tech Inspector, Copyright © 1998-2016, PDmB, Inc.

Page 5: Home Inspection Report · 1. Fireplace Construction: Prefab 2.Type: natural gas 3. Fireplace Insert: Standard 4. Smoke Chamber: Metal 5. Hearth: Flush Mounted Tile Heating System

ExteriorA NP NI M D

Main Exterior Surface 1. Type: Fibrous - Holes (circled in red) from previous hardware mounting need to be properly

sealed to prevent water penetration. Back: Left of

deck. Back: Below

deck. Back: Below

deck.\ West Side: Near

gate.

2. Trim: Composite material 3. Fascia: Composite material 4. Soffits: Composite material 5. Door Bell: Hard wired 6. Entry Doors: Metal 7. Patio Door: Vinyl sliding 8. Windows: Vinyl slider 9. Window Screens: Vinyl mesh

10. Exterior Lighting: Surface mounted lamps front and rear 11. Exterior Electric Outlets: 110 VAC GFCI 12. Hose Bibs: Rotary 13. Gas Meter: Exterior surface mount at east side of home 14. Main Gas Valve: Located at gas meter

RoofA NP NI M D

Main Roof Surface 1. Method of Inspection: Ladder at eaves 2. Unable to Inspect: 30% 3. Material: Asphalt shingle 4. Type: Gable 5. Approximate Age: 5 years 6. Flashing: Painted metal 7. Plumbing Vents: ABS 8. Gutters: Aluminum 9. Downspouts: Aluminum

10. Leader/Extension: Galvanized West Chimney 11. Chimney: Metal surface mount direct vent

Duff Home InspectionsRobert Baker

5555 Treetop LanePage 4 of 19

Palm-Tech Inspector, Copyright © 1998-2016, PDmB, Inc.

Page 6: Home Inspection Report · 1. Fireplace Construction: Prefab 2.Type: natural gas 3. Fireplace Insert: Standard 4. Smoke Chamber: Metal 5. Hearth: Flush Mounted Tile Heating System

Roof (Continued)12. Flue/Flue Cap: Metal surface mount direct vent 13. Chimney Flashing: Metal

Garage/CarportA NP NI M D

Attached Garage 1. Type of Structure: Attached Car Spaces: 2 2. Garage Doors: Insulated aluminum 3. Door Operation: Mechanized 4. Door Opener: Lift Master 5. Exterior Surface: Fibrous and Brick 6. Service Doors: Fire rated 7. Ceiling: Texture paint 8. Walls: Paint 9. Floor/Foundation: Poured concrete

10. Electrical: 110 VAC GFCI

ElectricalA NP NI M D

1. Service Size Amps: 200 Volts: 110-240 VAC 2. Service: Aluminum 3. 120 VAC Branch Circuits: Copper 4. 240 VAC Branch Circuits: Copper 5. Conductor Type: Non-metallic sheathed cable 6. Ground: 7. Smoke Detectors: Hard wired with battery back up

Garage Electric Panel 8. Manufacturer: Square D - Electrical panel is missing a couple knock-out covers.

Covers are needed to prevent fingers, or any other objects from making contact with wires.

9. Maximum Capacity: 200 Amps 10. Main Breaker Size: 200 Amps 11. Breakers: Copper 12. GFCI: Basement, garage, kitchen, bathrooms 13. Is the panel bonded? Yes No

Duff Home InspectionsRobert Baker

5555 Treetop LanePage 5 of 19

Palm-Tech Inspector, Copyright © 1998-2016, PDmB, Inc.

Page 7: Home Inspection Report · 1. Fireplace Construction: Prefab 2.Type: natural gas 3. Fireplace Insert: Standard 4. Smoke Chamber: Metal 5. Hearth: Flush Mounted Tile Heating System

StructureA NP NI M D

1. Structure Type: Wood frame 2. Foundation: Poured 3. Differential Movement: No movement or displacement noted 4. Beams: Bonded wood 5. Bearing Walls: Frame 6. Joists/Trusses: 2x4 7. Piers/Posts: Poured piers and wood posts - Wood posts should be secured to concrete piers to

prevent any movement. It is recommended that a licensed contractor properly assets the issue.

Bracket needed

8. Floor/Slab: Composite wood or plywood 9. Stairs/Handrails: Wood stairs with wood handrails

10. Subfloor: Plywood -

AtticA NP NI M D

Main Attic 1. Method of Inspection: From the attic access 2. Unable to Inspect: 25% - Unable to access all areas of the attic. 3. Roof Framing: 2x4 Truss 4. Sheathing: Particle board - Moisture stains noted on the east side attic sheathing (pictured below).

Moisture meter came back with a higher than normal reading indicating that the stains are a current moisture issue. Evaluation and repair by a licensed contractor is recommend to prevent further damage.

Duff Home InspectionsRobert Baker

5555 Treetop LanePage 6 of 19

Palm-Tech Inspector, Copyright © 1998-2016, PDmB, Inc.

Page 8: Home Inspection Report · 1. Fireplace Construction: Prefab 2.Type: natural gas 3. Fireplace Insert: Standard 4. Smoke Chamber: Metal 5. Hearth: Flush Mounted Tile Heating System

Attic (Continued)5. Ventilation: Roof and soffit vents 6. Insulation: Blown in 7. Insulation Depth: 18+" 8. Vapor Barrier: Not Visible - Not visible through insulation 9. Moisture Penetration: Ongoing water penetration noted - Please see above notes.

10. Bathroom Fan Venting: Electric fan

Crawl Space

A NP NI M D

Main Crawl Space 1. Method of Inspection: From the access 2. Unable to Inspect: 10% 3. Access: Basement door 4. Moisture Penetration: See notes. Water was entering the crawlspace through a drain pipe. The

drain pipe appears to be installed to help move water out of the crawl space, but the ground outside of the crawl space has negative slope leading towards the drain pipe. Leveling the outside ground, and adding an extension that is sloped away from the crawl space will eliminate the water issue.

Water present near entrace to

crawlspace/ basement

5. Moisture Location: Near entrance, and through vents. 6. Moisture Barrier: Vinyl covering gravel as part of a radon mitigation system 7. Ventilation: Vents

More insulation in the

crawlspace/basement could be used for

more efficient heating and

cooling of the house

8. Insulation: Fiberglass - Missing in areas. Adding insulation to bare areas will lower heating and cooling costs. Roll insulation can be purchased from most hardware stores, and can be easily installed by homeowner.

Duff Home InspectionsRobert Baker

5555 Treetop LanePage 7 of 19

Palm-Tech Inspector, Copyright © 1998-2016, PDmB, Inc.

Page 9: Home Inspection Report · 1. Fireplace Construction: Prefab 2.Type: natural gas 3. Fireplace Insert: Standard 4. Smoke Chamber: Metal 5. Hearth: Flush Mounted Tile Heating System

Crawl Space (Continued)9. Vapor Barrier: Under entire home - Few areas where vapor barrier has been moved, or where

more barrier is needed. Recommend that vapor barrier is properly installed over covering the entire crawlspace ground.

Exposed dirt due to missing vapor

barrier can caused excess moister in crawl

space.

Air ConditioningA NP NI M D

East side of home AC System Model and serial number sticker

worn out

1. A/C System Operation: Appears serviceable - Model and serial number are new visible.

2. Condensate Removal: PVC 3. Exterior Unit: Pad mounted 4. Manufacturer: Bryant 5. Model Number: N/A Serial Number: N/A 6. Area Served: Whole building Approximate Age: 5 years 7. Fuel Type: 220 VAC Temperature Differential: N/A 8. Type: Central A/C Capacity: Not listed 9. Visible Coil: Copper core with aluminum fins

10. Refrigerant Lines: Low pressure and high pressure 11. Electrical Disconnect: Breaker disconnect 12. Exposed Ductwork: Insulated flex 13. Blower Fan/Filters: Direct drive with disposable filter 14. Thermostats: Programmable

Duff Home InspectionsRobert Baker

5555 Treetop LanePage 8 of 19

Palm-Tech Inspector, Copyright © 1998-2016, PDmB, Inc.

Page 10: Home Inspection Report · 1. Fireplace Construction: Prefab 2.Type: natural gas 3. Fireplace Insert: Standard 4. Smoke Chamber: Metal 5. Hearth: Flush Mounted Tile Heating System

Fireplace/Wood StoveA NP NI M D

Living Room Fireplace 1. Fireplace Construction: Prefab 2. Type: natural gas 3. Fireplace Insert: Standard 4. Smoke Chamber: Metal 5. Hearth: Flush Mounted Tile

Heating SystemA NP NI M D

Garage Heating System 1. Heating System Operation: Adequate 2. Manufacturer: Lennox 3. Model Number: cnphp3017avaabaa Serial Number: 1610x43333

4. Type: Forced air Capacity: 91,000 BTUHR 5. Area Served: Whole building Approximate Age: 5 years 6. Fuel Type: Natural gas 7. Heat Exchanger: 3 Burner 8. Unable to Inspect: 50% 9. Blower Fan/Filter: Direct drive with disposable filter

10. Distribution: Insulflex duct 11. Circulator: Gravity 12. Draft Control: Automatic 13. Flue Pipe: Double wall 14. Controls: Limit switch 15. Devices: Temp gauge 16. Thermostats: Programmable 17. Suspected Asbestos: No

Duff Home InspectionsRobert Baker

5555 Treetop LanePage 9 of 19

Palm-Tech Inspector, Copyright © 1998-2016, PDmB, Inc.

Page 11: Home Inspection Report · 1. Fireplace Construction: Prefab 2.Type: natural gas 3. Fireplace Insert: Standard 4. Smoke Chamber: Metal 5. Hearth: Flush Mounted Tile Heating System

PlumbingA NP NI M D

1. Service Line: PVC 2. Water Lines: ABS 3. Drain Pipes: ABS 4. Service Caps: Accessible 5. Vent Pipes: ABS 6. Gas Service Lines: Cast iron

Garage Water Heater 7. Water Heater Operation: Functional at time of inspection

8. Manufacturer: A.O. Smith 9. Model Number: na Serial Number: 1011j004171

10. Type: Natural gas Capacity: 40 Gal. 11. Approximate Age: 5 years Area Served: Whole building 12. Flue Pipe: Double wall

Needs water catch. 13. TPRV and Drain Tube: PVC - Drain tube opening is not within six inches of the

floor, and is missing catch basin/drain. Drain and or catch is needed to prevent water from damaging any outlying areas.

Duff Home InspectionsRobert Baker

5555 Treetop LanePage 10 of 19

Palm-Tech Inspector, Copyright © 1998-2016, PDmB, Inc.

Page 12: Home Inspection Report · 1. Fireplace Construction: Prefab 2.Type: natural gas 3. Fireplace Insert: Standard 4. Smoke Chamber: Metal 5. Hearth: Flush Mounted Tile Heating System

BathroomA NP NI M D

1st floor Bathroom 1. Ceiling: Texture paint 2. Walls: Paint 3. Floor: Laminate 4. Doors: Hollow wood 5. Windows: Vinyl slider 6. Electrical: 110 VAC GFCI 7. Counter/Cabinet: Laminate and wood 8. Sink/Basin: Porcelain coated 9. Faucets/Traps: Metal fixture - Leak noted a P-trap junction. The coupler threads

appear to be stripped out, and P-trap pipes will need need to be replaced. A licensed plumber is recommended to evaluate and estimate repairs.

10. Tub/Surround: Fiberglass tub and fiberglass surround 11. Shower/Surround: Fiberglass pan and fiberglass surround 12. Toilets: GlacierBay 1.6 Gpf 13. HVAC Source: Air exchange ventilation 14. Ventilation: Electric ventilation fan 2nd floor Bathroom 15. Closet: Small 16. Ceiling: Texture paint 17. Walls: Paint 18. Floor: Linoleum 19. Doors: Hollow wood 20. Electrical: 110 VAC GFCI 21. Counter/Cabinet: Laminate and wood 22. Sink/Basin: Porcelain 23. Faucets/Traps: Metal fixtures with a PVC trap 24. Tub/Surround: Fiberglass tub and fiberglass surround 25. Shower/Surround: Fiberglass pan and fiberglass surround 26. Spa Tub/Surround: Porcelain tub and fiberglass surround 27. Toilets: GlacierBay 1.6 Gpf 28. HVAC Source: Heating system register 29. Ventilation: Electric ventilation fan Master Bathroom 30. Closet: Walk In and Large 31. Ceiling: Texture paint 32. Walls: Paint

Duff Home InspectionsRobert Baker

5555 Treetop LanePage 11 of 19

Palm-Tech Inspector, Copyright © 1998-2016, PDmB, Inc.

Page 13: Home Inspection Report · 1. Fireplace Construction: Prefab 2.Type: natural gas 3. Fireplace Insert: Standard 4. Smoke Chamber: Metal 5. Hearth: Flush Mounted Tile Heating System

Bathroom (Continued)33. Floor: Laminate 34. Doors: Hollow wood 35. Electrical: 110 VAC GFCI 36. Counter/Cabinet: Laminate and wood 37. Sink/Basin: Ceramic dual bowl 38. Faucets/Traps: Metal fixtures with a PVC trap 39. Shower/Surround: Fiberglass pan and fiberglass surround 40. Spa Tub/Surround: Porcelain tub 41. Toilets: GlacierBay 1.6 Gpf 42. HVAC Source: Heating system register 43. Ventilation: Electric ventilation fan

KitchenA NP NI M D

1st Floor Kitchen 1. Cooking Appliances: General Electric 2. Ventilator: Whirlpool 3. Disposal: General Electric 4. Dishwasher: General Electric 5. Air Gap Present? Yes No 6. Refrigerator: Whirlpool 7. Microwave: General Electric 8. Sink: Stainless Steel 9. Electrical: 110 VAC GFCI

10. Plumbing/Fixtures: Chrome 11. Counter Tops: Tile 12. Cabinets: Laminate and composite materials 13. Pantry: Small 14. Ceiling: Texture paint 15. Walls: Paint 16. Floor: Laminate 17. Doors: Laminate wood 18. Windows: Vinyl slider 19. HVAC Source: Heating system register

Duff Home InspectionsRobert Baker

5555 Treetop LanePage 12 of 19

Palm-Tech Inspector, Copyright © 1998-2016, PDmB, Inc.

Page 14: Home Inspection Report · 1. Fireplace Construction: Prefab 2.Type: natural gas 3. Fireplace Insert: Standard 4. Smoke Chamber: Metal 5. Hearth: Flush Mounted Tile Heating System

BedroomA NP NI M D

East Bedroom 1. Closet: Small 2. Ceiling: Texture paint 3. Walls: Paint 4. Floor: Carpet 5. Doors: Hollow wood 6. Windows: Vinyl slider

Outlet working, but loose. Needs

to be secured.

7. Electrical: 110 VAC - Loose outlet should be secured properly

8. HVAC Source: Heating system register 9. Smoke Detector: None Present

West Bedroom 10. Closet: Small 11. Ceiling: Texture paint 12. Walls: Paint 13. Floor: Carpet 14. Doors: Hollow wood 15. Windows: Vinyl slider 16. Electrical: 110 VAC 17. HVAC Source: Heating system register 18. Smoke Detector: Battery operated Master Bedroom 19. Closet: Walk In and Large 20. Ceiling: Texture paint 21. Walls: Paint 22. Floor: Carpet 23. Doors: Hollow wood 24. Windows: Vinyl slider - Faulty operating hardware. Channel balances need

repair or replacement.

25. Electrical: 110 VAC 26. HVAC Source: Heating system register 27. Smoke Detector: Battery operated

Duff Home InspectionsRobert Baker

5555 Treetop LanePage 13 of 19

Palm-Tech Inspector, Copyright © 1998-2016, PDmB, Inc.

Page 15: Home Inspection Report · 1. Fireplace Construction: Prefab 2.Type: natural gas 3. Fireplace Insert: Standard 4. Smoke Chamber: Metal 5. Hearth: Flush Mounted Tile Heating System

Living SpaceA NP NI M D

Living Room Living Space 1. Closet: Small 2. Ceiling: Texture paint

Crack near back door 3. Walls: Paint - Cracks present

4. Floor: Laminate 5. Windows: Vinyl slider 6. Electrical: 110 VAC 7. HVAC Source: Heating system register 8. Smoke Detector: Hard wired with battery back up

Family Room (front room) Living Space 9. Ceiling: Texture paint

10. Walls: Paint 11. Floor: Carpet 12. Windows: Vinyl slider 13. Electrical: 110 VAC 14. HVAC Source: Heating system register 15. Smoke Detector: Hard wired with battery back up and light

Laundry Room/AreaA NP NI M D

1st Floor Laundry Room/Area 1. Closet: Small & Walk-in 2. Ceiling: Texture paint 3. Walls: Paint 4. Floor: Linoleum 5. Doors: Hollow wood 6. Electrical: 110 VAC/220 VAC 7. HVAC Source: Heating system register 8. Laundry Tub: 9. Laundry Tub Drain: PVC

10. Washer Hose Bib: Gate valves 11. Washer and Dryer Electrical: 110-240 VAC 12. Dryer Vent: Metal flex 13. Washer Drain: Drain pan to main drain system

Duff Home InspectionsRobert Baker

5555 Treetop LanePage 14 of 19

Palm-Tech Inspector, Copyright © 1998-2016, PDmB, Inc.

Page 16: Home Inspection Report · 1. Fireplace Construction: Prefab 2.Type: natural gas 3. Fireplace Insert: Standard 4. Smoke Chamber: Metal 5. Hearth: Flush Mounted Tile Heating System

Marginal SummaryThis summary is not the entire report. The complete report may include additional information of concern to the client. It is recommended that the client read the complete report.

Lots and Grounds

1. Deck: Treated and stained wood - Crack in kick plate, wood broken off on the far right. Paint needed to prevent damage to the exposed wood.

2. Balcony: Treated and stained wood - Balcony/deck ledger is mounted incorrectly on the left side section. Currently the deck ledger is being help to the wall by nails only. 1/2 lag bolts (see example photo below) spaced roughly every 16 inches are needed. Improper mounting can be a safety issue. Recommend a licensed contractor install proper mounting bolts.

Properly secured

Exterior

3. Main Exterior Surface Type: Fibrous - Holes (circled in red) from previous hardware mounting need to be properly sealed to prevent water penetration.

Back: Left of deck.

Back: Below deck.

Back: Below deck.\

West Side: Near gate.

Electrical

4. Garage Electric Panel Manufacturer: Square D - Electrical panel is missing a couple knock-out covers. Covers are needed to prevent fingers, or any other objects from making contact with wires.

Duff Home InspectionsRobert Baker

5555 Treetop LanePage 15 of 19

Palm-Tech Inspector, Copyright © 1998-2016, PDmB, Inc.

Page 17: Home Inspection Report · 1. Fireplace Construction: Prefab 2.Type: natural gas 3. Fireplace Insert: Standard 4. Smoke Chamber: Metal 5. Hearth: Flush Mounted Tile Heating System

Marginal Summary (Continued)Crawl Space

5. Main Crawl Space Moisture Penetration: See notes. Water was entering the crawlspace through a drain pipe. The drain pipe appears to be installed to help move water out of the crawl space, but the ground outside of the crawl space has negative slope leading towards the drain pipe. Leveling the outside ground, and adding an extension that is sloped away from the crawl space will eliminate the water issue.

Water present near entrace to

crawlspace/ basement

More insulation in the

crawlspace/basement could be used for

more efficient heating and

cooling of the house

6. Main Crawl Space Insulation: Fiberglass - Missing in areas. Adding insulation to bare areas will lower heating and cooling costs. Roll insulation can be purchased from most hardware stores, and can be easily installed by homeowner.

7. Main Crawl Space Vapor Barrier: Under entire home - Few areas where vapor barrier has been moved, or where more barrier is needed. Recommend that vapor barrier is properly installed over covering the entire crawlspace ground.

Exposed dirt due to missing vapor

barrier can caused excess moister in crawl

space.

Plumbing Needs water

catch. 8. Garage Water Heater TPRV and Drain Tube: PVC - Drain tube opening is not within six inches of the floor, and is missing catch basin/drain. Drain and or catch is needed to prevent water from damaging any outlying areas.

Duff Home InspectionsRobert Baker

5555 Treetop LanePage 16 of 19

Palm-Tech Inspector, Copyright © 1998-2016, PDmB, Inc.

Page 18: Home Inspection Report · 1. Fireplace Construction: Prefab 2.Type: natural gas 3. Fireplace Insert: Standard 4. Smoke Chamber: Metal 5. Hearth: Flush Mounted Tile Heating System

Marginal Summary (Continued)Bedroom

Outlet working, but loose. Needs

to be secured. 9. East Bedroom Electrical: 110 VAC - Loose outlet should be secured properly

Living Space Crack near back door

10. Living Room Living Space Walls: Paint - Cracks present

Duff Home InspectionsRobert Baker

5555 Treetop LanePage 17 of 19

Palm-Tech Inspector, Copyright © 1998-2016, PDmB, Inc.

Page 19: Home Inspection Report · 1. Fireplace Construction: Prefab 2.Type: natural gas 3. Fireplace Insert: Standard 4. Smoke Chamber: Metal 5. Hearth: Flush Mounted Tile Heating System

Defective SummaryThis summary is not the entire report. The complete report may include additional information of concern to the client. It is recommended that the client read the complete report.

Structure

1. Piers/Posts: Poured piers and wood posts - Wood posts should be secured to concrete piers to prevent any movement. It is recommended that a licensed contractor properly assets the issue.

Bracket needed

Attic

2. Main Attic Sheathing: Particle board - Moisture stains noted on the east side attic sheathing (pictured below). Moisture meter came back with a higher than normal reading indicating that the stains are a current moisture issue. Evaluation and repair by a licensed contractor is recommend to prevent further damage.

3. Main Attic Moisture Penetration: Ongoing water penetration noted - Please see above notes.

Bathroom

4. 1st floor Bathroom Faucets/Traps: Metal fixture - Leak noted a P-trap junction. The coupler threads appear to be stripped out, and P-trap pipes will need need to be replaced. A licensed plumber is recommended to evaluate and estimate repairs.

Bedroom

5. Master Bedroom Windows: Vinyl slider - Faulty operating hardware. Channel balances need repair or replacement.

Duff Home InspectionsRobert Baker

5555 Treetop LanePage 18 of 19

Palm-Tech Inspector, Copyright © 1998-2016, PDmB, Inc.

Page 20: Home Inspection Report · 1. Fireplace Construction: Prefab 2.Type: natural gas 3. Fireplace Insert: Standard 4. Smoke Chamber: Metal 5. Hearth: Flush Mounted Tile Heating System

Defective Summary (Continued)

Duff Home InspectionsRobert Baker

5555 Treetop LanePage 19 of 19