Home Inspection Report
1234, Fayetteville, AR 72761
Inspection Date:Tuesday February 9, 2016
Prepared For:K S
Prepared By:Illuminating-Home-Inspections6375 W Copper Ridge LaneFayetteville, Arkansas 72704
(479) 466 9417
Report Number:02092016
Inspector:Eric Robb
1234, Fayetteville, AR 72761 Page 2
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Report SummaryItems Not Operating
Water heater Fireplace
Major ConcernsNone apparent
Potential Safety HazardsRecommend junction boxes be covered-SAFETY HAZARD. Main disconnect has more than 6 hand movement. Safety hazard. Recommend further evaluation by a qualified electrician. Firewall protection recommended on access to attic.
Deferred Cost ItemsFurnace A/C Water heater
Improvement ItemsPatio screen door does not slide easily, rollers damaged. Recommend repair. Damaged/Missing insulation recommend replacing insulation. Recommend maintaining a positive drainage slope away from the foundation at 1 inch per foot for at least 10 feet. Chimney crown cracked, recommend repair. Flashing around the chimney has some rusting, recommend repair. Gutter guards bent in areas and/or missing in spots. Recommended repair replace. Ground-fault outlet was not operating properly, won't trip recommend replacing. Master bathroom sink drain shows sign of back-up, recommend repair. Open ground is a potential safety hazard. Recommend repair by a qualified electrical contractor. Recommend extending bathroom vents to the exterior. Chimney section through attic showed deterioration recommend repair. Roof had some damage and was in need of some repairs. Faucet is leaking - recommend repair and/or replacement.
Items To Monitor
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 3
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Report SummaryPipe flashing penetrations will need on going caulking where fasteners are located. Gutters appear to be in overall adequate condition. Insides of gutters have some debris recommend cleaning. Recommend caulking around windows, doors, corners, utility penetrations. Moisture stains present in a couple areas on the ceiling. Recommend trimming trees/vegetation so it does not come into contact with the home. Roof pipe flashing will need caulking at nail heads. Some minor corrosion around the joints, but no visible leaks at this time. Flashing at drip edge shows signs of some rusting. One master bath drain was back-up during time of inspection.
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 4
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Report OverviewScope of Inspection
All components designated for inspection in the ASHI Standards of Practice are inspected, except as may be noted in the "Limitations of Inspection" sections within this report. It is the goal of the inspection to put a home buyer in a better position to make a buying decision. Not all improvements will be identified during this inspection. Unexpected repairs should still be anticipated. The inspection should not be considered a guarantee or warranty of any kind. Please refer to the pre-inspection contract for a full explanation of the scope of the inspection.
Main Entrance FacesNorth
State of OccupancyVacant
Weather ConditionsCloudy
Recent RainNo
Ground CoverDry
Approximate Age24 Years
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 5
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
GroundsService Walks
None Not Visible
Material X Concrete Flagstone Gravel Brick Other:
Condition X Satisfactory Marginal Poor Trip hazard X Typical cracks Pitched towards homeSettling cracks Public sidewalk needs repair
Comments Walkway had some minor typical cracking. Patio and typical minor cracks.
Photos
Minor typical cracks
Driveway/Parking
None Not Visible
Material X Concrete Asphalt Gravel/Dirt Brick Other:
Condition X Satisfactory Marginal Poor X Settling Cracks X Typical cracks Pitched towards homeTrip hazard X Fill cracks and seal
Comments Recommend sealing gaps and cracks in driveway.
Photos
Driveway Driveway Driveway
Porch
None Not Visible
Condition X Satisfactory Marginal Poor Railing/Balusters recommended
Support Pier X Concrete Wood Other:
Floor X Satisfactory Marginal Poor Safety Hazard
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 6
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
GroundsPorch cont.
Comments Porch appeared to be in satisfactory shape.
Photos
Stoops/Steps
X None
Material Concrete Wood Other: Railing/Balusters recommended
Condition Satisfactory Marginal Poor Safety Hazard Uneven risers Rotted/DamagedCracked Settled
Comments
Patio
None
Material X Concrete Flagstone Kool-Deck Brick Other:
Condition X Satisfactory Marginal Poor Settling cracks Trip hazardPitched towards home (see remarks) Drainage provided Typical cracks
Comments Patio seemed to be in satisfactory condition.
Photos
Deck/Balcony
X None Not Visible
Material Wood Metal Composite Railing/Balusters recommended
Condition Satisfactory Marginal Poor Wood in contact with soil
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 7
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
GroundsDeck/Balcony cont.
Finish Treated Painted/Stained Other: Safety Hazard Improper attachment to houseRailing loose Not Applicable
Comments
Deck/Patio/Porch Covers
None
Condition X Satisfactory Marginal Poor Posts/Supports need Repair Earth to wood contactMoisture/Insect damage
Recommend Metal Straps/Bolts/Nails/Flashing Improper attachment to house X None
Comments
Photos
Attic at front soffit, water spot Attic area, living room, after stain
Fence/Wall
X Not evaluated None
Type Brick Block X Wood Metal X Chain Link Rusted Vinyl
Condition X Satisfactory Marginal Poor Typical cracks Loose Blocks/Caps
Gate N/A X Satisfactory Marginal Poor Planks missing/damaged Operable: X Yes No
Comments Wood fencing was in need of some maintenance repairs. Fencing remarks do not constitute an inspection. Fencing is not part of a home inspection.
Photos
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 8
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Grounds
Fence is leaning and has warped boards
Landscaping affecting foundation
N/A
Negative Grade East X West North X South Satisfactory X Recommend additional backfillRecommend window wells/covers X Trim back trees/shrubberiesWood in contact with/improper clearance to soil
Comments Recommend maintaining a positive drainage slope away from the foundation at 1 inch per foot for at least 10 feet. Low areas of grading next to the foundation recommend adding additional soil and slope away from foundation Recommend trimming trees/vegetation so it does not come into contact with the home.
Photos
Ground slopes towards the home Shrubs touching home need trimming.
Retaining wall
X None
Material Brick Concrete Concrete block Other: Railroad ties Timbers
Condition Satisfactory Marginal Poor Safety Hazard Leaning/cracked/bowedDrainage holes recommended
Comments
Hose bibs
N/A
Condition X Satisfactory Marginal Poor No anti-siphon valve Recommend Anti-siphon valve
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 9
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
GroundsHose bibs cont.
Operable X Yes No Not Tested Not On
Comments Hose bib(s) leaking from handle/stem, recommend repair
Photos
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 10
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
RoofGeneral
Visibility None X All Partial Limited By: Nothing.
Inspected From X Roof X Ladder at eaves X Ground With BinocularsThe inspection was done from some areas of the roof, the ground and a ladder.
Photos
Nail head
Style of Roof
Type Gable X Hip Mansard Shed Flat Other:
Pitch Low X Medium Steep Flat
Roof #1 Type: Asphalt Layers: 1+ Layers Age: 5-10+ Location:
Roof #2 X NoneType: Layers: Age: Location:
Roof #3 X NoneType: Layers: Age: Location:
Comments
Photos
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 11
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Roof
Ventilation System
None N/A
Type X Soffit X Ridge Gable Roof Turbine Powered Other:
Comments Soffit/Eave Ridge
Photos
Ridge vent Soffit vent
Flashing
Material X Not Visible X Galv/Alum Asphalt Copper Foam Rubber Lead Other:
Condition X Not Visible Satisfactory Marginal Poor Rusted MissingSeparated from chimney/roof Recommend Sealing Other: Nails
Comments Flashings are not visible.
Photos
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 12
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Roof
Valleys
X N/A
Material X Not Visible Galv/Alum Asphalt Lead Copper Other:
Condition Not Visible Satisfactory Marginal Poor Holes Rusted Recommend Sealing
Comments Valley flashings are not visible, appear to be working as intended.
Condition of Roof Coverings
Roof #1 Satisfactory X Marginal Poor Curling Cracking Ponding Burn SpotsX Broken/Loose Tiles/Shingles Nail popping X Granules missing Alligatoring Blistering
Missing Tabs/Shingles/Tiles Moss buildup Exposed felt CuppingX Incomplete/Improper Nailing X Recommend roofer evaluate Evidence of Leakage
Roof #2 X N/A Satisfactory Marginal Poor Curling Cracking Ponding Burn SpotsBroken/Loose Tiles/Shingles Nail popping Granules missing Alligatoring BlisteringMissing Tabs/Shingles/Tiles Moss buildup Exposed felt CuppingIncomplete/Improper Nailing Recommend roofer evaluate Evidence of Leakage
Roof #3 X N/A Satisfactory Marginal Poor Curling Cracking Ponding Burn SpotsBroken/Loose Tiles/Shingles Nail popping Granules missing Alligatoring BlisteringMissing Tabs/Shingles/Tiles Moss buildup Exposed felt CuppingIncomplete/Improper Nailing Recommend roofer evaluate Evidence of Leakage
Comments Due to varying insurance standards, it is recommended that your insurance company be contacted about the insurability of the roof. Roof was showing normal wear, but appear to be in overall adequate condition. Water stains in living room, kitchen and front attic above porch, recommend further evaluation.
Skylights
X N/A Not Visible
Condition Cracked/Broken Satisfactory Marginal Poor
Comments
Plumbing Vents
Not Visible Not Present
Condition X Satisfactory Marginal Poor
Comments Pipe flashing will need caulking at nail heads.
Photos
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 13
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Roof
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 14
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
ExteriorChimney(s)
None
Location(s) North
Viewed From X Roof Ladder at eaves Ground (Inspection Limited) With Binoculars
Rain Cap/Spark Arrestor X Yes No Recommended
Chase X Brick Stone Metal Blocks Framed
Evidence of Holes in metal X Cracked chimney cap Loose mortar joints Flaking Loose brick X RustNo apparent defects
Flue X Tile Metal Unlined X Not Visible
Evidence of Scaling Cracks Creosote X Not evaluated Have flue(s) cleaned and re-evaluatedRecommend Cricket/Saddle/Flashing No apparent defects
Condition Satisfactory X Marginal Poor X Recommend Repair
Comments Flue not visible, not evaluate. Chimney flue was not accessible so not evaluated. Chimney crown cracked, recommend repair. Flashing around the chimney has some rusting, recommend repair.
Photos
Minor crack in cap Flashing rusting
Gutters/Scuppers/Eavestrough
X None
Condition X Satisfactory Marginal Poor X Rusting Downspouts needed Recommend repair/replaceX Needs to be cleaned
Material Copper Vinyl/Plastic X Galvanized/Aluminum Other:
Leaking Corners Joints Hole in main run No apparent leaks
Attachment X Loose X Missing spikes Improperly sloped Satisfactory
Extension needed X North X South X East X West N/A
Comments Gutters appear to be in overall adequate condition. However, without water in them it is difficult to judge if they are pitched properly insuring the water flows into the downspouts. Insides of gutters have some debris recommend cleaning Recommend maintaining downspout discharge a minimum of 5-6' away from the house.
Photos
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 15
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Exterior
Leaf guard bent Gutter
Siding
Material Stone Slate X Block/Brick Fiberboard Fiber-cement Stucco EIFS* Not InspectedAsphalt Wood Metal/Vinyl Other: Typical cracks Peeling paint Monitor Wood rotLoose/Missing/Holes
Condition X Satisfactory Marginal Poor Recommend repair/painting
Comments Siding appeared to be all intact and in overall satisfactory condition. Brick and mortar appeared to be in overall adequate condition
Photos
Caulking
Trim
Material Wood Fiberboard X Aluminum/Steel X Vinyl Stucco Recommend repair/paintingDamaged wood Other:
Condition X Satisfactory Marginal Poor
Comments Trim appeared to be intact and in overall maintained condition.
Soffit
None
Material X Wood Fiberboard Aluminum/Steel Vinyl Stucco X Recommend repair/paintingDamaged wood Other:
Condition X Satisfactory Marginal Poor
Comments Soffit above front porch / living room showed signs of past leak. Moisture meter reading was in acceptable range.
Photos
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 16
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Exterior
Soffit above front porch
Fascia
X None
Material Wood Fiberboard Aluminum/Steel Vinyl Stucco Recommend repair/paintingDamaged wood Other:
Condition Satisfactory Marginal Poor
Comments
Flashing
None
Material Wood Fiberboard X Aluminum/Steel Vinyl Stucco X Recommend repair/paintingDamaged wood Other:
Condition X Satisfactory Marginal Poor
Comments Flashing at drip edge shows signs of some rusting
Photos
Flashing
Caulking
None
Condition Satisfactory Marginal PoorX Recommend around windows/doors/masonry ledges/corners/utility penetrations
Comments Recommend caulking around windows, doors, corners, utility penetrations.
Photos
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 17
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Exterior
Caulking Monitor caulking Monitor caulking
Windows/Screens
Condition X Satisfactory Marginal Poor Wood rot Recommend repair/paintingRecommend repair/replace damaged screens Failed/fogged insulated glass
Material Wood Metal Vinyl X Aluminum/Vinyl clad
Screens X Torn Bent Not installed Satisfactory
Comments Found minor rip on window screen(s)
Photos
Minor rip
Storms Windows
X None Not installed
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 18
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
ExteriorStorms Windows cont.
Condition Satisfactory Broken/cracked Wood rot Recommend repair/painting
Material Wood Clad comb. Wood/Metal comb. Metal
Putty Satisfactory Needed N/A
Comments
Slab-On-Grade/Foundation
Foundation Wall X Concrete block Poured concrete Post-Tensioned concrete Not Visible Other:
Condition Satisfactory Marginal Monitor Have Evaluated X Not Evaluated
Concrete Slab N/A X Not Visible Satisfactory Marginal Monitor Have Evaluated
Comments Slab not visible due to flooring materials (carpet, hardwood, tile, etc.) not evaluated.
Service Entry
Location X Underground Overhead
Condition X Satisfactory Marginal Poor Weather head/mast needs repair Overhead wires too low
Exterior receptacles Yes X No Operable: X Yes No Condition: X Satisfactory Marginal Poor
GFCI present X Yes No Operable: Yes No Safety Hazard Reverse polarity Open ground(s)Recommend GFCI Receptacles
Comments
Photos
Building(s) Exterior Wall Construction
Type X Not Visible Framed Masonry Other:
Condition X Not Visible Satisfactory Marginal Poor
Comments Building structure not visible due to siding, not evaluated
Exterior Doors
Main Entrance N/A Weatherstripping: X Satisfactory Marginal Poor Missing Replace Door condition:X Satisfactory Marginal Poor
Patio N/A Weatherstripping: X Satisfactory Marginal Poor Missing Replace Door condition:X Satisfactory Marginal Poor
Rear door N/A Weatherstripping: X Satisfactory Marginal Poor Missing Replace Door condition:X Satisfactory Marginal Poor
Other door N/A Weatherstripping: X Satisfactory Marginal Poor Missing Replace Door condition:
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 19
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
ExteriorExterior Doors cont.
Other door N/A Weatherstripping: X Satisfactory Marginal Poor Missing Replace Door condition:Marginal Poor
Comments Back patio screen door does not slide recommend repair. Front storm door does not fully close, recommend repair.
Photos
Entry storm door does not close properly
Sliding screen door broke.
Exterior A/C - Heat pump #1
Unit #1 N/ALocation: South Brand: Rheem Model #: Rama 036jaz Serial #: 5340 f5193 4070Approximate Age: Approximant age 20-25+
Condition Satisfactory X Marginal Poor Cabinet/housing rusted
Energy source X Electric Gas Other:
Unit type Air cooled Water cooled Geothermal X Heat pump
Outside Disconnect X Yes No Maximum fuse/breaker rating (amps): 40 Fuses/Breakers installed (amps):X Improperly sized fuses/breakers
Level X Yes No Recommend re-level unit
Condenser Fins Damaged Need cleaning Damaged base/pad Damaged Refrigerant Line X Satisfactory
Insulation Yes No X Replace
Improper Clearance (air flow) Yes X No
Comments Damaged/Missing insulation recommend replacing insulation
Photos
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 20
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Exterior
Max fuse breaker 40 amps Damaged / torn insulation
Exterior A/C - Heat pump #2
Unit #2 X N/ALocation: Brand: Model #: Serial #:Approx. Age:
Energy source Electric Gas Other:
Unit type Air cooled Water cooled Geothermal Heat pump
Outside Disconnect Yes No Maximum fuse/breaker rating (amps): Fuses/Breakers installed (amps):Improperly sized fuses/breakers
Level Yes No Recommend re-level unit
Condenser Fins Damaged Need cleaning Damaged base/pad Damaged Refrigerant Line Satisfactory
Insulation Yes No Replace
Condition Satisfactory Marginal Poor Cabinet/housing rusted
Improper Clearance (air flow) Yes No
Comments
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 21
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Garage/CarportType
None
Type Attached Detached 1-Car X 2-Car 3-Car 4-Car Carport
Comments 2-car
Automatic Opener
None N/A
Operation X Operable Inoperable
Comments
Photos
Safety Reverse
None N/A
Operation X Operable Not Operable Need(s) adjusting Safety hazardPhoto eyes and pressure reverse tested
Comments The electrics eyes worked properly. The auto reverse was not tested.
Photos
Roofing
Material X Same as houseType: Approx. age: Approx. layers:
Comments Roof had some damage and was in need of some repair.
Photos
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 22
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Garage/Carport
Gutters/Eavestrough
Condition X Satisfactory Marginal Poor Same as house
Comments Gutter guards bent in areas and/ or missing in spots. Recommended repair replace.
Photos
Garage gutter
Siding
N/A
Material X Same as house Wood Metal Vinyl Stucco Masonry Slate Fiberboard
Condition X Satisfactory Marginal Poor Recommend repair/replace Recommend painting
Comments Siding was intact and in overall adequate condition.
Photos
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 23
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Garage/CarportTrim
N/A
Material X Same as house Wood Aluminum Vinyl
Condition X Satisfactory Marginal Poor Recommend repair/replace Recommend painting
Comments
Floor
Material X Concrete Gravel Asphalt Dirt Other:
Condition X Satisfactory Typical cracks Large settling cracks Recommend evaluation/repairSafety hazard
Source of Ignition within 18" of the floor X N/A Yes No
Comments The foundation is overall adequate with no major defects evident.
Photos
Sill Plates
None X Not Visible
Type Floor level Elevated
Condition Rotted/Damaged Recommend repair
Comments Sill plates not visible.
Overhead Door(s)
N/A
Material Wood Fiberglass Masonite X Metal Recommend repair
Condition X Satisfactory Marginal Poor Hardware loose Safety Cable RecommendedWeatherstripping missing/damaged Loose/missing
Recommend Priming/Painting Inside & Edges Yes X No
Comments Garage door and opener was in normal working order.
Photos
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 24
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Garage/Carport
Exterior Service Door
X None
Condition Satisfactory Marginal Poor Damaged/Rusted
Comments
Electrical Receptacles
X Yes No Not Visible Operable: X Yes No
Reverse polarity Yes X No
Open ground X Yes No X Safety Hazard
GFCI Present X Yes No Operable: Yes X No Handyman/extension cord wiringRecommend GFCI Receptacles
Comments Open ground is a potential safety hazard. Recommend repair by a qualified electrical contractor.
Photos
Garage. Open ground
Fire Separation Walls & Ceiling
N/A X Present Missing Recommend repair
Condition X Satisfactory Recommend repair Holes walls/ceiling Safety hazard(s)
Moisture Stains Present X Yes No
Typical Cracks Yes X No
Fire door X Not verifiable Not a fire door Needs repair Satisfactory
Self closure N/A Satisfactory Inoperative X Missing
Comments Firewall protection recommended on access to attic.
Photos
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 25
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Garage/Carport
Pull down ladder
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 26
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
KitchenCountertops
Condition X Satisfactory Marginal Recommend repair/caulking
Comments Counter top has normal wear.
Photos
Cabinets
Condition X Satisfactory Marginal Recommend repair/adjustment
Comments Cabinets have normal wear.
Photos
Plumbing
Faucet Leaks Yes X No
Pipes leak/corroded Yes X No
Sink/Faucet X Satisfactory Corroded Chipped Cracked Recommend repair
Functional drainage X Satisfactory Marginal Poor
Functional flow X Satisfactory Marginal Poor
Comments Some minor corrosion around the joints, but no visible leaks at this time. Water flow was normal with several fixtures operated at the same time. There were no visible active piping leaks at the time of the inspection. Drain lines had no visible leaks or signs of backup at the time of inspection.
Photos
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 27
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Kitchen
Evidence of past leak
Walls & Ceiling
Condition Satisfactory Marginal Poor Typical cracks X Moisture stains
Comments Moisture stains present, recommend further evaluation.
Photos
Above fridge moisture stain
Heating/Cooling Source
X Yes No
Comments
Floor
Condition X Satisfactory Marginal Poor Sloping Squeaks
Comments
Photos
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 28
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Kitchen
Appliances
Disposal X N/A Not tested Operable: X Yes No
Oven X N/A Not tested Operable: X Yes No
Range X N/A Not tested Operable: X Yes No
Dishwasher X N/A Not tested Operable: X Yes No
Trash Compactor X N/A Not tested Operable: Yes No
Exhaust fan X N/A Not tested Operable: X Yes No
Refrigerator X N/A Not tested Operable: X Yes No
Microwave X N/A Not tested Operable: X Yes No
Other Operable: X Yes No
Dishwasher airgap X Yes No
Dishwasher drain line looped X Yes No
Receptacles present X Yes No Operable: X Yes No
GFCI X Yes No Operable: X Yes No Recommend GFCI Receptacles: Yes NoPotential Safety Hazard(s)
Open ground/Reverse polarity: Yes X No Potential Safety Hazard
Comments Appliances only tested for operation, working or not. Gas top knobs loose, recommend repair.
Photos
Knobs loose
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 29
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Kitchen
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 30
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Laundry RoomLaundry
Laundry sink X N/A
Faucet leaks Yes X No
Pipes leak Yes X No Not Visible
Cross connections Yes X No Potential Safety Hazard
Heat source present X Yes No
Room vented X Yes No
Dryer vented N/A X Wall Ceiling X Floor Not vented Plastic dryer vent not recommendedNot vented to exterior Recommend repair Safety hazard
Electrical Open ground/reverse polarity: Yes X No Safety hazard
GFCI present Yes X No Operable: Yes No X Recommend GFCI Receptacles
Appliances X Washer X Dryer Water heater Furnace/Boiler
Washer hook-up lines/valves Satisfactory Leaking X Corroded X Not Visible
Gas shut-off valve X N/A Yes No Cap Needed Safety hazard Not Visible
Comments No washer or dryer present.
Photos
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 31
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Bathroom (1)Bath
Location First floor hall bathroom
Sinks Faucet leaks: Yes X No Pipes leak: Yes X No
Tubs N/A Faucet leaks: X Yes No Pipes leak: Yes No X Not Visible
Showers N/A Faucet leaks: Yes X No Pipes leak: Yes No X Not Visible
Toilet Bowl loose: Yes X No Operable: X Yes No Cracked bowl Toilet leaks
Whirlpool Yes X No Operable: Yes No Not tested No access door GFCI: Yes NoGFCI Recommended
Shower/Tub area Ceramic/Plastic Fiberglass X Masonite Other: Condition: X Satisfactory MarginalPoor Rotted floors Caulk/Grouting needed: Yes X No
Where: N/A
Drainage X Satisfactory Marginal Poor
Water flow X Satisfactory Marginal Poor
Moisture stains present Yes X No Walls Ceilings Cabinetry
Doors X Satisfactory Marginal Poor
Window None X Satisfactory Marginal Poor
Receptacles present X Yes No Operable: X Yes No
GFCI X Yes No Operable: Yes X No X Recommend GFCI
Open ground/Reverse polarity Yes X No Potential Safety Hazard
Heat source present X Yes No
Exhaust fan X Yes No Operable: X Yes No Noisy
Comments Ground-fault outlet was not operating properly, won't trip recommend replacing. Non of the bathroom sinks have over flow drains. Moisture stains present under sink, appears to be from a past leak. Recommend venting exhaust fan to exterior.
Photos
Shower faucet leaks Water stain, appears old
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 32
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Bathroom (1)
Sink cabinet, moisture meter test good
Hall bath outlet No over flow drain
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 33
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Bathroom (2)Bath
Location Master bath
Sinks Faucet leaks: X Yes No Pipes leak: Yes X No
Tubs X N/A Faucet leaks: Yes No Pipes leak: Yes No Not Visible
Showers N/A Faucet leaks: Yes X No Pipes leak: Yes X No X Not Visible
Toilet Bowl loose: Yes X No Operable: X Yes No Cracked bowl Toilet leaks
Whirlpool Yes X No Operable: Yes No Not tested No access door GFCI: Yes NoGFCI Recommended
Shower/Tub area X Ceramic/Plastic Fiberglass Masonite Other: Condition: X Satisfactory MarginalPoor Rotted floors Caulk/Grouting needed: Yes X No
Where: X N/A
Drainage Satisfactory X Marginal Poor
Water flow X Satisfactory Marginal Poor
Moisture stains present Yes X No Walls Ceilings Cabinetry
Doors X Satisfactory Marginal Poor
Window None X Satisfactory Marginal Poor
Receptacles present X Yes No Operable: X Yes No
GFCI X Yes No Operable: X Yes No Recommend GFCI
Open ground/Reverse polarity Yes X No Potential Safety Hazard
Heat source present X Yes No
Exhaust fan X Yes No Operable: X Yes No Noisy
Comments Drains backup, recommend repair left side master bath. No overflow drains in any bathroom sinks. Recommend venting exhaust fan to exterior. Faucet is leaking - recommend repair and/or replacement.
Photos
Master bath Master bath right side faucet leaks
Master bath left side drains slow
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 34
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Bathroom (2)
No overflow drain
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 35
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Room (1)Room
Location First floor
Type BEDROOM next to the living room.
Walls & Ceiling X Satisfactory Marginal Poor Typical cracks Damage
Moisture stains Yes X NoWhere:
Floor X Satisfactory Marginal Poor Squeaks Slopes Tripping hazard
Ceiling fan None X Satisfactory Marginal Poor Recommend repair/replace
Electrical Switches: X Yes No X Operable Receptacles: X Yes No X OperableOpen ground/Reverse polarity: Yes X No Safety hazard Cover plates missing
Heating source present X Yes No Holes: Doors Walls Ceilings
Bedroom Egress restricted N/A Yes X No
Doors None X Satisfactory Marginal Poor Cracked glass Broken/Missing hardware
Windows None X Satisfactory Marginal Poor Cracked glass Evidence of leaking insulated glassBroken/Missing hardware
Comments
Photos
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 36
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Room (1) Photos
Landry room screen ripped
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 37
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Room (2)Room
Location First floor
Type BEDROOM front across from the master bedroom.
Walls & Ceiling X Satisfactory Marginal Poor Typical cracks Damage
Moisture stains Yes X NoWhere:
Floor X Satisfactory Marginal Poor Squeaks Slopes Tripping hazard
Ceiling fan None X Satisfactory Marginal Poor Recommend repair/replace
Electrical Switches: X Yes No X Operable Receptacles: X Yes No X OperableOpen ground/Reverse polarity: Yes X No Safety hazard Cover plates missing
Heating source present X Yes No Holes: Doors Walls Ceilings
Bedroom Egress restricted N/A Yes X No
Doors None X Satisfactory Marginal Poor Cracked glass Broken/Missing hardware
Windows None X Satisfactory Marginal Poor Cracked glass Evidence of leaking insulated glassBroken/Missing hardware
Comments
Photos
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 38
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Room (3)Room
Location First floor
Type BEDROOM. Master
Walls & Ceiling X Satisfactory Marginal Poor Typical cracks Damage
Moisture stains Yes X NoWhere:
Floor X Satisfactory Marginal Poor Squeaks Slopes Tripping hazard
Ceiling fan None X Satisfactory Marginal Poor Recommend repair/replace
Electrical Switches: X Yes No X Operable Receptacles: X Yes No X OperableOpen ground/Reverse polarity: Yes X No Safety hazard Cover plates missing
Heating source present X Yes No Holes: Doors Walls Ceilings
Bedroom Egress restricted N/A Yes X No
Doors None X Satisfactory Marginal Poor Cracked glass Broken/Missing hardware
Windows None X Satisfactory Marginal Poor Cracked glass Evidence of leaking insulated glassBroken/Missing hardware
Comments
Photos
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 39
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
InteriorFireplace
None
Location(s) Living room
Type X Gas Wood Solid fuel burning stove Electric Ventless
Material X Masonry Metal (pre-fabricated) Metal insert Cast Iron
Miscellaneous Blower built-in Operable: Yes No Damper operable: X Yes NoOpen joints or cracks in firebrick/panels should be sealed Fireplace doors need repair
Damper modified for gas operation N/A X Yes No Damper missing
Hearth extension adequate X Yes No
Mantel N/A X Secure Loose Recommend repair/replace
Physical condition Satisfactory Marginal Poor Recommend having flue cleaned and re-examinedX Not evaluated
Comments Flue could not be examined so no representation could be made. Open joints or cracks in firebrick recommend properly sealing in attic.
Photos
Stairs/Steps/Balconies
X None
Condition Satisfactory Marginal Poor Loose/Missing
Handrail Satisfactory Marginal Poor Safety hazard Hand Rail/Railing/Balusters recommended
Risers/Treads Satisfactory Marginal Poor Risers/Treads uneven Trip hazard
Comments
Smoke/Carbon Monoxide detectors
Smoke Detector X Present Not Present Operable: Yes No X Not tested Recommend additionalSafety Hazard
CO Detector Present X Not Present Operable: Yes No X Not tested Recommend additionalSafety Hazard
Comments Recommend changing smoke detectors batteries every 6 months.
Photos
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 40
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Interior
Attic/Structure/Framing/Insulation
N/A
Access Stairs X Pulldown Scuttlehole/Hatch No Access Other: Access limited by:
Inspected from Access panel X In the attic Other
Location Hallway Bedroom Closet X Garage Other
Flooring Complete X Partial None
Insulation Fiberglass Batts X Loose Cellulose Foam Other Vermiculite Rock woolDepth: Various Damaged X Displaced Missing CompressedX Recommend additional insulation
Installed in Rafters/Trusses Walls X Between ceiling joists Underside of roof deck Not Visible
Vapor barriers Kraft/foil faced Plastic sheeting X Not Visible Improperly installed
Ventilation X Ventilation appears adequate Recommend additional ventilation Recommend baffles at eaves
Fans exhausted to Attic: X Yes No X Recommend repair Outside: Yes X No Not Visible
HVAC Duct N/A X Satisfactory Damaged Split Disconnected Leaking Repair/ReplaceRecommend Insulation
Chimney chase N/A Satisfactory X Needs repair Not Visible
Structural problems observed Yes X No Recommend repair Recommend structural engineer
Roof structure Rafters Trusses X Wood Metal Collar ties Purlins Knee wall Not Visible Other:
Ceiling joists X Wood Metal Not Visible
Sheathing Plywood X OSB Planking Rotted Stained Delaminated
Evidence of condensation Yes X No
Evidence of moisture X Yes No
Evidence of leaking X Yes No
Firewall between units X N/A Yes No Needs repair/sealing
Electrical No apparent defects X Open junction box(es) Handyman wiringKnob and tube covered with insulation Safety Hazard
Comments Rafters appeared to be in overall adequate condition. Roof sheathing, examined from the attic, showed no major defects. Insulation was average, but could be upgraded. Ventilation was normal. Recommend junction boxes be covered-SAFETY HAZARD. Recommend extending bathroom vents to the exterior. Chimney section through attic showed deterioration recommend repair.
Photos
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 41
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Interior
Attic framing Attic repair
HVAC air ducts Attic chimney need repair Attic moister stain
Bath vents should vent to exterior Attic electrical box needs cover Attic junction box
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 42
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
PlumbingWater service
Main shut-off location Outside at curbside
Water entry piping X Not Visible Copper/Galv. PVC Plastic CPVC Plastic Polybutylene PlasticPEX Plastic Lead Polyethylene
Lead other than solder joints Yes X No Unknown Service entry
Visible water distribution piping Copper Galvanized X PVC Plastic CPVC Plastic Polybutylene PlasticPEX Plastic Other:
Condition X Satisfactory Marginal Poor
Flow X Satisfactory Marginal Poor Water pressure over 80 psi Recommend plumber evaluateX Recommend pressure regulator
Pipes Supply/Drain Corroded Leaking X Valves broken/missing Dissimilar metal Cross connection: YesX No Safety Hazard Recommend repair Recommend a dielectric union X Satisfactory
Drain/Waste/Vent pipe Copper Cast iron Galvanized X PVC ABS Brass
Condition X Satisfactory Marginal Poor
Support/Insulation X N/AType:
Traps proper P-Type X Yes No P-traps recommended
Drainage X Satisfactory Marginal Poor
Interior fuel storage system X N/A Yes No Leaking: Yes No
Fuel line X N/A Copper Brass Black iron Stainless steel CSST Not Visible GalvanizedRecommend CSST be properly bonded
Condition X N/A Satisfactory Marginal Poor Recommend plumber evaluate
Comments
Photos
Main water shut off
Main fuel shut-off location
N/A
Location In the utility room
Comments Gas meter on exterior of home.
Photos
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 43
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Plumbing
Well pump
X N/A
Type Submersible In basement Well house Well pit Shared well
Pressure gauge operable Yes No Well pressure: Not Visible
Comments
Sanitary/Grinder pump
X N/A Operable: Yes No
Sealed Crock Sealed crock: Yes No
Check Valve Check valve: Yes No
Shut-off Valve Shut-off valve: Yes No
Vented Yes No
Comments
Water heater #1
N/A
General Brand Name: American Water Heater Company Serial #: 1024T425883Capacity: 50 Approx. age: Approximant age of water heater-10+
Type X Gas Electric Oil LP Other:
Combustion air venting present X Yes No N/A
Seismic restraints needed Yes X No N/A
Relief valve X Yes No Extension proper: X Yes No Missing Recommend repairImproper material
Vent pipe N/A X Satisfactory X Pitch proper Improper Rusted Recommend repair
Condition X Satisfactory Marginal Poor
Comments Their is no drain pan to catch overflow.
Photos
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 44
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Plumbing
Water heater, shut off valve Water heater vent
Water heater #2
X N/A
General Brand Name: Serial #:Capacity: Approx. age:
Type Gas Electric Oil LP Other:
Combustion air venting present Yes No N/A
Seismic restraints needed Yes No N/A
Relief valve Yes No Extension proper: Yes No Missing Recommend repairImproper material
Vent pipe N/A Satisfactory Pitch proper Improper Rusted Recommend repair
Condition Satisfactory Marginal Poor
Comments
Water softener
X None
Loop installed Yes No
Plumbing hooked up Yes No
Plumbing leaking Yes No
Comments
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 45
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Heating SystemHeating system
Unit #1 Brand name: Rheem forced air furnance Approx. age: Heating system approximant age 15-20+ X Unknown Model #: RGDG-10EAMER Serial #: CY5D302 F1094 1281 Satisfactory X Marginal
Poor Recommended HVAC technician examine
Unit #2 X NoneBrand name: Approx. age:
UnknownModel #: Serial #: X Satisfactory Marginal Poor Recommended HVAC technician examine
Energy source X Gas LP Oil Electric Solid fuel
Warm air system Belt drive Direct drive Gravity X Central system Floor/wall furnace
Heat exchanger N/A Sealed Not Visible Visual w/mirror Flame distortion X RustedCarbon/soot buildup
Carbon monoxide N/A Detected at plenum Detected at register X Not testedTester:
Combustion air venting present N/A X Yes No
Controls Disconnect: X Yes No Normal operating and safety controls observed Gas shut off valve:X Yes No
Distribution Metal duct X Insulated flex duct Cold air returns Duct board Asbestos-like wrapSafety Hazard
Flue piping N/A X Satisfactory Rusted Improper slope Safety hazard Recommend repair/replace
Filter X Standard Electrostatic Satisfactory Needs cleaning/replacement MissingElectronic (not tested)
When turned on by thermostat X Fired Did not fire Proper operation: X Yes No Not tested
Heat pump X N/A Supplemental electric Supplemental gas
Sub-slab ducts X N/A Satisfactory Marginal Poor Water/Sand Observed: Yes No
System not operated due to X N/A Exterior temperature Other:
Comments Furnace was in normal working order at the time of the inspection. Heat exchanger had limited visibility due to its high-efficiency design and can not be fully inspected without disassembly which is not part of the home inspection. Heat exchanger showed no major defects; flames appeared normal. Flue was drafting properly at the time of the inspection. Filter should be changed monthly.
Photos
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 46
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Heating System
Monitor fittings
Past water stain
Boiler system
X N/A
General Brand name: Approx. age: Model #: Serial #:
Energy source Gas LP Oil Electric Solid fuel
Distribution Hot water Baseboard Steam Radiator Radiant floor
Circulator Pump Gravity Multiple zones
Controls Temp/pressure gauge exist: Yes No Operable: Yes No
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 47
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Heating SystemBoiler system cont.
Oil fired units Disconnect: Yes No
Combustion air venting present Yes No N/A
Relief valve Yes No Missing Extension proper: Yes No Recommend repair/replace
Operated When turned on by thermostat: Fired Did not fire
Operation Satisfactory: Yes No Recommend HVAC technician examine before closing
Comments
Other systems
X N/A
Type Electric baseboard Radiant ceiling cable Gas space heater Solid fuel burning stove
Proper operation Yes No
System condition Satisfactory Marginal Poor Recommend HVAC Technician Examine
Comments
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 48
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Electric/Cooling SystemMain panel
Location Garage
Condition Satisfactory X Poor
Adequate Clearance to Panel Yes X No
Amperage/Voltage X Unknown 60a 100a 150a 200a 400a 120v/240v
Breakers/Fuses X Breakers Fuses
Appears grounded Yes No X Not Visible
GFCI breaker X Yes No Operable: Yes X No
AFCI breaker Yes X No Operable: Yes No Not Tested
Main wire Copper Aluminum X Not Visible Double tapping of the main wire Condition: SatisfactoryMarginal X Poor
Branch wire Copper Aluminum Solid Branch Aluminum Wiring X Not Visible Safety Hazard
Branch wire condition Satisfactory Poor X Recommend electrician evaluate/repair Romex BX cableConduit Knob/Tube Double tapping Wires undersized/oversized breaker/fuse
X Panel not accessible X Not evaluatedReason: Could not remove panel cover. Main disconnect has more than 6 hand movements. Safety hazard Recommenced further evaluation by a qualified electrician.
Comments
Photos
Non accessible panel More than 6 hand movements to disconnect all
Sub panel(s)
X None apparent
Location(s) Location 1: Location 2: Location 3:
Evaluation Panel not accessible Not evaluatedReason:
Recommend separating/isolating neutrals Recommend electrician repair/evaluate box
Branch wire Copper Aluminum Safety hazard Neutral/ground separated: Yes No Neutral isolated:Yes No
Condition Satisfactory Marginal Poor
Comments
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 49
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Electric/Cooling SystemEvaporator Coil Section Unit #1
X N/A
General X Central system Wall unitLocation: Interior hall closet Age: Unknown
Evaporator coil X Satisfactory Not Visible Needs cleaning Damaged
Refrigerant lines Leak/Oil present Damage Insulation missing X Satisfactory
Condensate line/drain X To exterior To pump Floor drain Other:
Secondary condensate line/drain Present: Yes X No Needed: X Yes No Primary pan appears cloggedRecommend technician evaluate
Operation Differential:
Condition X Satisfactory Marginal Poor Recommend HVAC technician examine/clean/serviceX Not operated due to exterior temperature
Comments A/C was not operated due to outside temperature.
Evaporator Coil Section Unit #2
X N/A
General Central system Wall unitLocation: Age:
Evaporator coil Satisfactory Not Visible Needs cleaning Damaged
Refrigerant lines Leak/Oil present Damage Insulation missing SatisfactoryRecommend/Replace damaged/missing insulation
Condensate line/drain To exterior To pump Floor drain Other:
Secondary condensate line/drain Present: Yes No Needed: Yes No Primary pan appears cloggedRecommend technician evaluate
Operation Differential:
Condition Satisfactory Marginal Poor Recommend HVAC technician examine/clean/serviceNot operated due to exterior temperature
Comments
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 50
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Living RoomLiving Room
Location First floor
Walls & Ceiling X Satisfactory Marginal Poor Typical cracks Damage
Moisture stains X Yes NoWhere: Ceiling water stain near chimney recommend further evaluation.
Floor X Satisfactory Marginal Poor Squeaks Slopes Tripping hazard
Ceiling fan None X Satisfactory Marginal Poor Recommend repair/replace
Electrical Switches: X Yes No X Operable Receptacles: X Yes No X OperableOpen ground/Reverse polarity: Yes X No Safety hazard Cover plates missing
Heating source present X Yes No Holes: Doors Walls Ceilings
Doors None X Satisfactory Marginal Poor Cracked glass Broken/Missing hardware
Windows None X Satisfactory Marginal Poor Cracked glass Evidence of leaking insulated glassBroken/Missing hardware
Comments
Photos
Water stain
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
1234, Fayetteville, AR 72761 Page 51
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections
Dining RoomDining Room
Location First floor
Walls & Ceiling X Satisfactory Marginal Poor Typical cracks Damage
Moisture stains Yes X NoWhere:
Floor X Satisfactory Marginal Poor Squeaks Slopes Tripping hazard
Ceiling fan None X Satisfactory Marginal Poor Recommend repair/replace
Electrical Switches: X Yes No X Operable Receptacles: X Yes No X OperableOpen ground/Reverse polarity: Yes X No Safety hazard Cover plates missing
Heating source present X Yes No Holes: Doors Walls Ceilings
Doors None X Satisfactory Marginal Poor Cracked glass Broken/Missing hardware
Windows None X Satisfactory Marginal Poor Cracked glass Evidence of leaking insulated glassBroken/Missing hardware
Comments
Photos
This confidential report is prepared exclusively for K S©2018 Illuminating-Home-Inspections