Upload
vuongnhan
View
229
Download
3
Embed Size (px)
Citation preview
Data BulletinMED90111100
04/2011
Hospital Power and Ground Modules
Retain for future use.
© 2011 Schneider Electric All Rights Reserved
™
Standard Power and Ground Modules
When both ground jacks and power receptacles are required, these modules offer convenience and save labor in field wiring. The units include four power receptacles, four twist-to-lock ground jacks, and a ground bus with a generous number of lugs for external ground connections.
The main ground connection in the module accommodates up to a #1/0 cable. The units are completely factory wired; only field power connections and ground connections are necessary. They are furnished with Type 304, brushed stainless steel faceplates.
Back boxes are ordered separately. The size of the back box will depend on the outlet options for the overall device.
8.00(283)
12.00(305)
10.00(254)
14.00(356)
Ground jack:30 A, twist-to-lock
Red or ivory duplex receptacle:20 A, hospital grade
Stainless steel faceplate
4.00(102)
8.00(283)
12.00(305)
10.00(254)
14.00(356)Locking receptacle:
20 A, hospital grade
4.00(102)
Ground jack:30 A, twist-to-lock
Stainless steel faceplate
4 Locking Receptaclesand 4 Ground Jacks
4 Red Duplex Receptacles and 4 Ground Jacks
Dual Dimensions: Inches(mm)
Hospital Power and Ground Modules MED90111100Data Bulletin 04/2011
© 2011 Schneider Electric All Rights Reserved2
Power and Ground Modules to Fit Gang Boxes
These modules contain both ground jacks and power receptacles, but do not contain a ground bar with lugs. A single lug for #14 through #2 AWG wire is included for the incoming ground. These modules use standard electrical gang boxes; therefore, back boxes are not included. They are furnished with Type 304, brushed stainless steel faceplates.
These modules can be used where additional ground jacks and power receptacles are needed, but where lugs for hard grounding of non-electrical items are not required.
Back boxes are customer provided. Suggested boxes are gangable outlet boxes.
4.50(114)
3.50(89)
15.43(392)
3.75(95)
Stainless steel faceplate
Ground jack:30 A, twist-to-lock
Note: 8-gang back box not supplied.
Locking receptacle:20 A, hospital grade
Lug for #14–#2 AWG
Copper equalizer ground bus bar:0.125 in. (3 mm) thick x 0.75 in. (19 mm) wide
4.50(114)
3.50(89)
15.43(392)
3.75(95)
Stainless steel faceplate
Ground jack:30 A, twist-to-lock
Note: 8-gang back box not supplied.
Single receptacle:20 A, hospital grade
Lug for #14–#2 AWG
Copper equalizer ground bus bar:0.125 in. (3 mm) thick x 0.75 in. (19 mm) wide
4.50(114)
3.50(89)
15.43(392)
3.75(95)
Stainless steel faceplate
Ground jack:30 A, twist-to-lock
Note: 8-gang back box not supplied.
Duplex receptacle:20 A, hospital grade
Lug for #14–#2 AWG
Copper equalizer ground bus bar:0.125 in. (3 mm) thick x 0.75 in. (19 mm) wide
4 Ivory Single Receptacles and 4 Ground Jacks
4 Red Duplex Receptacles and 4 Ground Jacks
4 Locking Receptacles and 4 Ground Jacks
Dual Dimensions: Inches(mm)
MED90111100 Hospital Power and Ground Modules04/2011 Data Bulletin
© 2011 Schneider Electric All Rights Reserved 3
Master Grounding Station Module This unit can be used as a collection point for ground connectors in a large area such as a coronary care or intensive care ward. The primary application is where the equipment ground bus in the emergency distribution panel is not conveniently located or cannot accept the large number of connections that may be required for the area. Up to 18 individual grounds can be routed to this module, which can then be connected to the ground bus by a single conductor.
The unit contains a terminal block for the connection to the ground bus, and a bus bar with 18 lugs for field connections. It is furnished with a Type 304, brushed stainless steel faceplate.
Back boxes are ordered separately. The size of the back box will depend on the outlet options for the overall device.
12.00(305)
4.00(102)
8.00(203)
Top view ofground bus
Stainless steel faceplate
18 lugs for #14–#6 AWG1 terminal block for #12–1/0 AWG
10.00(254)
14.00(356)
Master Grounding Station Module
Dual Dimensions: Inches(mm)
Hospital Power and Ground Modules MED90111100Data Bulletin 04/2011
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
Schneider Electric USA, Inc.1010 Airpark Center DriveNashville, TN 372171-888-SquareD (1-888-778-2733)www.schneider-electric.us
© 2011 Schneider Electric All Rights Reserved4
Ground Modules Ideal for room ground bus extensions to make ground connections in large operating rooms convenient. These units contain four ground jacks and a ground bus. They are furnished with Type 304, brushed stainless steel faceplates.
Back boxes for the large ground modules are ordered separately. The size of the back box will depend on the outlet options for the overall device. Back boxes for the small ground modules are customer provided. Suggested boxes are gangable outlet boxes.
Stainless steel faceplate
Ground jack:30 A, twist-to-lock
18 lugs for #14–#6 AWG1 terminal block for #12–1/0 AWG
12.00(305)
4.00(102)
8.00(203)
10.00(254)
14.00(356)
Stainless steel faceplate
Ground jack:30 A, twist-to-lock
4.50(114)
3.50(89)
3.75(95)
Note: 4-gang back box not supplied.
Copper equalizer ground bus bar:0.125 in. (3 mm) thick x 0.75 in. (19 mm) wide
Lug for #14–#2 AWG
8.18(208)
4 Ground Jacks
4 Ground Jacks
Dual Dimensions: Inches(mm)