Hot Aisle Containment System Installation

Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

  • Upload
    others

  • View
    14

  • Download
    1

Embed Size (px)

Citation preview

Page 1: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

Hot AisleContainment System

Installation

Page 2: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

Contents

General Information.................................................1

Main Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

System Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Tools — Not Provided . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Hardware and Trim Identification . . . . . . . . . . . . . . . . . . . . . . . 5Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Joining hardware and trim . . . . . . . . . . . . . . . . . . . . . . . . . 5

Installation...............................................................6

Layout and Position of the Main Components . . . . . . . . . . . . . . 6Assemble main components . . . . . . . . . . . . . . . . . . . . . . . . 7

Door Frame Assembly and Installation. . . . . . . . . . . . . . . . . . . . 9Door frame assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Door frame installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Joining Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Joining 900 mm and 900 mm enclosures . . . . . . . . . . . . . . 12

Joining 900 mm and 1070 mm enclosures . . . . . . . . . . . . . 12

Joining 1070 mm enclosures. . . . . . . . . . . . . . . . . . . . . . . 14

Doors and locksets installation . . . . . . . . . . . . . . . . . . . . . 15

Ceiling Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18Types of ceiling panels and required hardware . . . . . . . . . . 18

Preparing for ceiling panel installation . . . . . . . . . . . . . . . . 19

Fire suppression . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

End ceiling panels - new installation . . . . . . . . . . . . . . . . . . 20

End ceiling panels - pre-existing installation . . . . . . . . . . . . . 21

FM-to-rack ceiling panels - new installation . . . . . . . . . . . . . 22

FM-to-rack ceiling panels - pre-existing installation . . . . . . . . 23

Ceiling Panel Inserts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Data Troughs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Side Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Hot Aisle Containment System i
Page 3: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

General Information

The Hot Aisle Containment System encloses an aisle to collect and cool equipment exhaust, making it available for cool air intakes. This creates a self-contained system capable of supporting high power density loads.

The Hot Aisle Containment System can be built using new equipment or with existing equipment.

Hot Aisle Containment System 1

Page 4: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

Main Components

Rack-to-rack (19-inch) ceiling Plinth block

panel assembly Door

Rack-to-rack (23-inch) ceiling Door threshold

panel assembly Door frame upright - left

FM-to-rack ceiling panel assembly Side panel - left

FM-to-FM ceiling panel assembly 1070 mm-to-1070 mm joining bracket

Door header Cap plug

Side panel - right 21U side panels (not shown)

Door frame upright - right 900 mm-to-1070 mm joining trim

Note

Ceiling panel assemblies come with Lexan® inserts that are not yet attached to the frames. Remove these and store them in safe location until beginning the ceiling panel installation process.

2 Hot Aisle Containment System

Page 5: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

System Configuration

Existing equipment used to create the Hot Aisle Containment System must meet dimensional requirements. If your existing layout must be altered to meet these requirements, consider an arrangement that does not require moving and turning off the power to the UPS and PDU. If your new configuration requires that the PDU and/or UPS must be moved, you will be required to remove power from that system.

See also

See the installation manuals provided with the equipment for installation procedures.

See also

See the InfraStruXure System Installation Manual available on the Utility CD that came with the PDU or from the APC Web site, for proper system shut-down.

119.6 (3037.8)

na0771a

* Dimensions are in inches (millimeters)

Hot Aisle Containment System 3

Page 6: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

Tools — Not Provided

P2 Phillipsscrewdriver

P1 Phillipsscrewdriver

T-30 Torx®

screwdriverOpen end wrench

13-mm/14-mmOpen end wrench

7-mm/8-mm

Tape measure Chalk line Cutting tool for door-frame gasket

Drill M5 socket

4 Hot Aisle Containment System

Page 7: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

Hardware and Trim Identification

Hardware

Joining hardware and trim

LocksetCeiling panel bracket

threadedCeiling panel

bracketScrew

M6 × 30-mm

Plasti-GrommetScrew

M6 × 12-mmRetaining fastener

ScrewM3 × 12-mm

Door stop

12–24 × 1/2" FHPHSS undercut screw

M6 flange nutDoor-frame

gasket Ceiling-panel gasketScrew

8-32 × 3/8"

pan-headsocket screw

M6 × 12-mm screw

M6 × 16-mmTorxscrew

M6 flange

nut

Joining trim

FM to FM

Joining trim

900-mm to

900-mm

Joining trim

900-mmto

1070-mm

Joining bracket

1070-mmto

1070-mm

1070-mmtrim

bracket

900-mm trim bracket

M8 flat washer

Hot Aisle Containment System 5

Page 8: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

Installation

Layout and Position of the Main Components

1. Determine the position of the main components and the total length of the Hot Aisle Containment System. Using a chalk line or a similar tool, lay out the perimeter, making sure all corners are square.

Note

If the existing equipment requires no adjustments, see “Door Frame Assembly and Installation” on page 9.

* Dimensions are in inches (millimeters).

119.6(3037.8)

32.46( 824.48)

NetShelter NetShelter NetShelter PDUUPS

NetShelterNetShelter NetShelterNetworkAIR FM

70.87(1800)

52.25(1327.15)

23.62(600)

na1335a

42.50(1079.50)

36.00(914.40)

36.00(914.40)

23.62(600)

Critical Dimensions

6 Hot Aisle Containment System

Page 9: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

Installation: Layout and Position of the Main Components

2. Position the NetworkAIR™ FM Unit, centering it in the row as shown.

Assemble main components

1. Join enclosures to each side of the FM unit.

See also

See the NetworkAIR FM installation manual for information on how to install this unit.

Note

The installation of the NetworkAIR FM unit does not have to be completed in order to continue with this installation.

Note

Finish installing all of the main components before fully tightening joining trim hardware.

See also

See the joining instructions in the NetworkAIR FM-to-Netshelter Baying Kit installation manual for information on how to join the enclosures to the unit.

Hot Aisle Containment System 7

Page 10: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

Installation: Layout and Position of the Main Components

2. Install the duct extensions.

See also

See the Duct Extension Kit instructions for information on how to install duct extensions.

8 Hot Aisle Containment System

Page 11: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

Door Frame Assembly and Installation

A door and door frame are installed on both ends of the Hot Aisle Containment System, and are used for aligning and joining the two rows of equipment.

Door frame assembly

Assemble both sets of door frames.

1. Attach the header to the left- and right-side door frame uprights using six M6 × 12-mm screws.

2. Attach the plinth blocks to the bottom of the door frame uprights using four M6 × 12-mm screws.

3. Attach the threshold to the bottom of the plinth blocks using two M6 flange nuts.

Hot Aisle Containment System 9

Page 12: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

Installation: Door Frame Assembly and Installation

Door frame installation

1. Use five M6 × 12-mm screws and M6 flange nuts to attach the door frame to the racks at the end of the aisle.

2. Attach the plinth blocks to the enclosure using two M8 × 25-mm screws.

3. Position the end component that will start the second row, and repeat steps 1 and 2 to complete the assembly.

10 Hot Aisle Containment System

Page 13: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

Installation: Door Frame Assembly and Installation

4. Complete the door frame installation process for the remaining door frame by repeating steps 1 through 3.

5. Before installing the enclosures for the second row, install two 21 U side panels to IT racks.

Note

Both rows must be aligned and straight, with the corners square before proceeding.

Note

Existing equipment rows may need to be pulled apart to install the brackets and 21 U panels. The 21U panels are options for enclosures.

Hot Aisle Containment System 11

Page 14: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

Joining Enclosures

Joining 900-mm enclosures

Joining 900-mm and 1070-mm enclosures

1. Attach two 1070-mm trim brackets to the side of the 1070-mm enclosure. Align the bracket’s mounting hole with the bottom hole of the top and bottom set of holes in the enclosure. Use an M6 × 12-mm screw and an M6 flange nut for each bracket.

See also

See the instructions included with your NetShelter Enclosure Installation Manual for information on front, and rear joining of 900-mm enclosures.

1070-mm

900-mm

Joining brackets - top view

1070-mm

900-mm

1070-mmshown

12 Hot Aisle Containment System

Page 15: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

Installation: Joining Enclosures

2. Attach two 900-mm trim brackets to the side of the 900-mm enclosure. Align the bracket’s mounting hole with the top hole of the upper and lower set of holes in the enclosure.Use a M6 × 12-mm screw and a M6 flange nut for each bracket.

3. Move the enclosures into the row, slide them together, and align the joining trim brackets as shown.

900-mm

1070-mm to 900-mm shown

Hot Aisle Containment System 13

Page 16: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

Installation: Joining Enclosures

4. Install the joining trim to the joining trim brackets, using four pan-head screws.

Joining 1070-mm enclosures.

When joining two 1070-mm enclosures, the appropriate rear joining bracket must be used. Orient the brackets so that the two round holes are at the top position. The slots should be located in the middle and lower positions. Use six M6 × 12-mm screws to join two 1070-mm enclosures.

na0835a

ElectricalHazard

The rear doors of the enclosures must be removed before the joining brackets can be installed. Do not remove the rear doors of the UPS, PDU, or XR Battery.

See also

See the instructions included with your equipment for information on how to remove the rear doors.

14 Hot Aisle Containment System

Page 17: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

Installation: Joining Enclosures

Doors and locksets installation

1. Apply the door frame gasket material to the door frame sides, and cut off any excess. Position the door gasket bulb on the outside of the door frame where it will make contact when the door is closed.

2. Hang the door on the frame.

na0767b

Hot Aisle Containment System 15

Page 18: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

Installation: Joining Enclosures

3. Attach a lockset to each door.

4. Install the strike plate onto each door frame, using two 12-24 × 1/2-inch FHPHSS undercut screws (provided).

Note

Position the lock cylinder on the outside of the door.

Note

Do not use the screws supplied with the lockset.na0777b

16 Hot Aisle Containment System

Page 19: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

Installation: Joining Enclosures

5. Install door stops using four M3 × 12-mm Phillips screws.

Hot Aisle Containment System 17

Page 20: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

Ceiling Panels

Ceiling panels are available in different lengths and widths based on the size of the enclosures they span. Ceiling panels are available as a complete assembly or as a multi-part unit that can be disassembled for existing applications that require that cables not be disconnected. Each ceiling panel configuration has a unique set of installation hardware.

Types of ceiling panels and required hardware

Configuration Ceiling panel Hardware required

FM-to-FMFour 8–32 × 3/8-inch screws

FM-to-rack

Two Plasti-GrommetsTwo M6 × 12-mm screwsTwo 8–32 × 3/8-inch screws

Rack-to-rack (19-inch)

Four Plasti-GrommetsFour M6 × 12-mm screws

Rack-to-rack (23-inch)

Four Plasti-GrommetsFour M6 × 12-mm screws

Caution

Ceiling panels are not designed to support weight. Do not use ceiling panels to route power or data cables.

See also

See the instructions that come with your equipment for proper installation of the ladders.

na1316a

18 Hot Aisle Containment System

Page 21: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

Installation: Ceiling Panels

Preparing for ceiling panel installation

Install Plasti-Grommets into the tops of the equipment (two grommets per enclosure top).

Fire suppression

A hole is located in the center of each ceiling panel for a fire suppression device. If no fire suppression device is used, close off the hole in each panel with the supplied caps.

If this installation is to use existing equipment, proceed to “End ceiling panels - pre-existing installation” on page 20 to begin the installation process

End ceiling panels - new installation

na1337a

10 holespaces

10 holespaces

na1337a

Hot Aisle Containment System 19

1. Apply the foam gasket to the end ceiling panels (rack-to-rack ceiling panels)

Page 22: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

Installation: Ceiling Panels

2. Attach the ceiling panels to the racks using eight M6 × 12-mm screws (four per panel).

End ceiling panels - pre-existing installation

20 Hot Aisle Containment System

1. Disassemble the end ceiling panels using a 7-mm wrench.

Page 23: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

Installation: Ceiling Panels

2. Apply a foam gasket to door frame.

3. Lift up the cable troughs, and attach ceiling panel ends using four M6 × 12-mm screws (two screws per end). Re-attach cable troughs; see the instructions supplied with the troughs for proper installation.

Rack end

Rack end

Remove

Loosen

Mid-railangle bracket

na1325a

Hot Aisle Containment System 21

Page 24: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

Installation: Ceiling Panels

4. Re-attach the ceiling panel centers to the ceiling panel ends using a 7-mm wrench.

FM-to-rack ceiling panels - new installation

1. Apply the foam gasket to two of the three remaining ceiling panel frames to be installed.

2. Attach a ceiling panel (without a foam gasket) first to the racks using two M6 × 12-mm screws and two 8-32 × 3/8-inch screws.

3. Repeat steps 1 through 2 for each of the remaining ceiling panels.

Attach

Mid-railangle bracket

Tighten

22 Hot Aisle Containment System

Page 25: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

Installation: Ceiling Panels

FM-to-rack ceiling panels - pre-existing installation

1. Disassemble FM-to-rack ceiling panels using a 7-mm wrench.

2. Apply a foam gasket to both previously installed rack-to-rack ceiling panels.

Rack end

Remove

Mid-railangle bracket

Loosen

Hot Aisle Containment System 23

Page 26: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

Installation: Ceiling Panels

3. Lift up the cable trough and attach the ceiling panel rack end to the enclosure using twoM6 × 12-mm screws.

4. Re-attach the cable trough to the ceiling panel end; see the instructions supplied with the troughs for proper installation.

5. Re-attach the ceiling panel center to the ceiling panel end using a 7-mm wrench.

6. Attach the ceiling panel (FM end) to the FM unit using two 8-32 × 3/8-inch screws.

7. Repeat steps 1 through 6 for each FM-to-rack ceiling panel.

na1333a

Attach

Tighten

Mid-railangle bracket

24 Hot Aisle Containment System

Page 27: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

Installation: Ceiling Panels

Ceiling Panel Inserts

1. Remove the adhesive backing film from the panel frame; remove the protective plastic from both sides of the Lexan and carefully set the Lexan panel in place, pressing the edges firmly.

2. Attach each end ceiling panel to the door header using three angle brackets andfive M6 × 30-mm screws.

3. Remove the adhesive backing film from the panel frame; remove the protective plastic from both sides of the Lexan. Carefully set the Lexan panels in place, pressing the edges firmly.

na1308a

na1309a

Hot Aisle Containment System 25

Page 28: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

Installation: Ceiling Panels

4. Secure the ceiling panel to the previously installed ceiling panel. Use a set of fasteners consisting of a M6 × 30-mm screw, a ceiling panel bracket, and a threaded ceiling panel bracket at each connection point.

5. Repeat steps 3 through 4 for each of the remaining FM-to-rack ceiling panels.

6. Complete the installation by repeating steps 1 and 2 for the last rack-to-rack ceiling panel.

Panel FM-to-FM FM-to-rack Rack-to-rack

FM-to-FM 3 3 3

FM-to-rack 3 4 4

Rack-to-rack 3 4 5

na0762a

Threaded ceiling bracket

Ceiling bracket

M6 × 30-mm screw

26 Hot Aisle Containment System

Page 29: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

Data Troughs

Install the troughs into the slots located in the ceiling panel frames.

See also

See the instructions supplied with the troughs for proper installation.

Hot Aisle Containment System 27

Page 30: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

Side Panels

Install the side panels at the ends of each row of the Hot Aisle Containment System.

28 Hot Aisle Containment System

Page 31: Hot Aisle Containment Systemorigin-faq.pro-face.com/resources/sites/PROFACE/content/live/FAQS... · The Hot Aisle Containment System encloses an aisle to collect and cool equipment

*990-1607A*

APC Worldwide Customer Support

Customer support for this or any other APC product is available at no charge in any of the following ways:• Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer

support requests.– www.apc.com (Corporate Headquarters)

Connect to localized APC Web sites for specific countries, each of which provides customer support information.

– www.apc.com/support/Global support searching APC Knowledge Base and using e-support.

• Contact an APC Customer Support center by telephone or e-mail.– Regional centers:

– Local, country-specific centers: go to www.apc.com/support/contact for contact information.

Contact the APC representative or other distributor from whom you purchased your APC product for information on how to obtain local customer support.

To obtain a repair authorization number for a NetworkAIR product, call APC NetworkAIR technical services between 8:00 A.M. and 5:00 P.M. Eastern time, Monday through Friday:

• Phone: (1)(888)695-6500 (USA and Canada only, toll free)• Fax: (1)(401)788-2691

Direct InfraStruXure Customer Support Line (1)(877)537-0607 (toll free)

APC headquarters U.S., Canada (1)(800)800-4272 (toll free)

Latin America (1)(401)789-5735 (USA)

Europe, Middle East, Africa (353)(91)702000 (Ireland)

Japan (0) 35434-2021

Australia, New Zealand, South Pacific area (61) (2) 9955 9366 (Australia)

Entire contents © 2005 American Power Conversion. All rights reserved. Reproduction in whole or in part without permission is prohibited. APC, the APC logo, NetworkAIR, NetShelter, and

InfraStruXure are trademarks of American Power Conversion Corporation and may be registered in some jurisdictions. All other trademarks, product names, and corporate names are the property

of their respective owners and are used for informational purposes only.

990-1607A 05/2005