Efficiency is Everything Engine heating provides essential benefits to organizations that rely on onsite power generation. However, an inefficient heating solution can slowly sap away time and money in the form of excessive electrical costs, frequent repair costs or replacement of hoses and plumbing. HOTSTART EVRHEAT SERIES 20 Efficiency & Performance Results Heaters were evaluated using the same engine block in tests performed at a room-temperature environment (68 °F) and a simulated outdoor temperature (32 °F). The kilowatt-hours of electricity consumed over a 12 hour period of steady state operation were recorded. 2500 W 1500 W 68 °F 32 °F Wattage: 1500 W | 2500 W Engine: 20 L max. Circulation Method: Forced Circulation Set Temperature: 110 °F EVRHEAT TPS EVR 11.77 7.38 CB EVR CTM 14.93 10.41 8.27 CB EVR CTM 28.35 21.62 18.22 0 5 10 15 20 25 30 Analysis The following is the measured average power consumption for an identical setup (above) and one month estimated cost (below). Cost and savings are calculated using a $0.10/kWh rate over a 730 hour period*. TPS EVR 11.77 7.38 CB EVR CTM 14.93 10.41 8.27 CB EVR CTM 28.35 21.62 18.22 Testing To evaluate the EVRHEAT Series 20 in terms of efficiency compared to both standard thermosiphon and forced circulation systems, we tested it against our engine heating benchmarks: the HOTSTART TPS, CB and CTM models. Wattage: 1500 W Engine: 8.2 L max. Circulation Method: Thermosiphon Set Temperature: 100 °F (on) / 120 °F (off) TPS MODEL Wattage: 2500 W Engine: 20 L max. Circulation Method: Forced Circulation Set Temperature: 100 °F (on) / 120 °F (off) Wattage: 2500 W Engine: 13.1 L max. Circulation Method: Thermosiphon Set Temperature: 100 °F (on) / 120 °F (off) CTM MODEL kWh TPS 0.981 kW EVR 0.615 kW TPS $71.62 / mo. EVR $44.90 / mo. CB 1.244 kW CTM 0.868 kW EVR 0.689 kW CB $90.82 / mo. CTM $63.36 / mo. EVR $50.30 / mo. CB 2.363 kW CTM 1.802 kW EVR 1.518 kW CB $172.50 / mo. CTM $131.55 / mo. EVR $110.81 / mo. CB MODEL *Actual savings for installed heaters dependent on application, installation and local utility rates. CS-EVR20-E 2020-3/rev0 © 2020 Hotstart

HOTSTART EVRHEAT SERIES 20 · model 68 °f 1500 w 68 °f 2500 w 32 °f 2500 w tps 104.5 °f evr 102.6 °f tps 146.8 °f evr 104.7 °f cb 113.2 °f ctm112.6 °f evr 106.5 °f

  • Upload
    others

  • View
    10

  • Download
    0

Embed Size (px)

Citation preview

Efficiency is EverythingEngine heating provides essential benefits to organizations that rely on onsite power generation. However, an inefficient heating solution can slowly sap away time and money – in the form of excessive electrical costs, frequent repair costs or replacement of hoses and plumbing.

HOTSTART EVRHEAT SERIES 20 Efficiency & Performance

CB MODEL

ResultsHeaters were evaluated using the same engine block in tests performed at a room-temperature environment (68 °F) and a simulated outdoor temperature (32 °F). The kilowatt-hours of electricity consumed over a 12 hour period of steady state operation were recorded.

2500 W1500 W

68 °F 32 °F

Wattage: 1500 W | 2500 WEngine: 20 L max. Circulation Method: Forced CirculationSet Temperature: 110 °F

EVRHEAT

20 °C 1500 W 20 °C 2500 W 0 °C 2500 W

0

5

10

15

20

25

TPS EVR CB EVRCTM CB EVRCTM

30

11.77

7.38

14.93

10.418.27

28.35

21.62

18.22

20 °C 1500 W 20 °C 2500 W 0 °C 2500 W

0

5

10

15

20

25

TPS EVR CB EVRCTM CB EVRCTM

30

11.77

7.38

14.93

10.418.27

28.35

21.62

18.22

20 °C 1500 W 20 °C 2500 W 0 °C 2500 W

0

5

10

15

20

25

TPS EVR CB EVRCTM CB EVRCTM

30

11.77

7.38

14.93

10.418.27

28.35

21.62

18.22

20 °C 1500 W 20 °C 2500 W 0 °C 2500 W

0

5

10

15

20

25

TPS EVR CB EVRCTM CB EVRCTM

30

11.77

7.38

14.93

10.418.27

28.35

21.62

18.22

20 °C 1500 W 20 °C 2500 W 0 °C 2500 W

0

5

10

15

20

25

TPS EVR CB EVRCTM CB EVRCTM

30

11.77

7.38

14.93

10.418.27

28.35

21.62

18.22

20 °C 1500 W 20 °C 2500 W 0 °C 2500 W

0

5

10

15

20

25

TPS EVR CB EVRCTM CB EVRCTM

30

11.77

7.38

14.93

10.418.27

28.35

21.62

18.22

20 °C 1500 W 20 °C 2500 W 0 °C 2500 W

0

5

10

15

20

25

TPS EVR CB EVRCTM CB EVRCTM

30

11.77

7.38

14.93

10.418.27

28.35

21.62

18.22

20 °C 1500 W 20 °C 2500 W 0 °C 2500 W

0

5

10

15

20

25

TPS EVR CB EVRCTM CB EVRCTM

30

11.77

7.38

14.93

10.418.27

28.35

21.62

18.22

20 °C 1500 W 20 °C 2500 W 0 °C 2500 W

0

5

10

15

20

25

TPS EVR CB EVRCTM CB EVRCTM

30

11.77

7.38

14.93

10.418.27

28.35

21.62

18.22

20 °C 1500 W 20 °C 2500 W 0 °C 2500 W

0

5

10

15

20

25

TPS EVR CB EVRCTM CB EVRCTM

30

11.77

7.38

14.93

10.418.27

28.35

21.62

18.22

20 °C 1500 W 20 °C 2500 W 0 °C 2500 W

0

5

10

15

20

25

TPS EVR CB EVRCTM CB EVRCTM

30

11.77

7.38

14.93

10.418.27

28.35

21.62

18.22

AnalysisThe following is the measured average power consumption for an identical setup (above) and one month estimated cost (below). Cost and savings are calculated using a $0.10/kWh rate over a 730 hour period*.

20 °C 1500 W 20 °C 2500 W 0 °C 2500 W

0

5

10

15

20

25

TPS EVR CB EVRCTM CB EVRCTM

30

11.77

7.38

14.93

10.418.27

28.35

21.62

18.22

20 °C 1500 W 20 °C 2500 W 0 °C 2500 W

0

5

10

15

20

25

TPS EVR CB EVRCTM CB EVRCTM

30

11.77

7.38

14.93

10.418.27

28.35

21.62

18.22

20 °C 1500 W 20 °C 2500 W 0 °C 2500 W

0

5

10

15

20

25

TPS EVR CB EVRCTM CB EVRCTM

30

11.77

7.38

14.93

10.418.27

28.35

21.62

18.22

TestingTo evaluate the EVRHEAT Series 20 in terms of efficiency compared to both standard thermosiphon and forced circulation systems, we tested it against our engine heating benchmarks: the HOTSTART TPS, CB and CTM models.

Wattage: 1500 WEngine: 8.2 L max. Circulation Method: ThermosiphonSet Temperature: 100 °F (on) / 120 °F (off)

TPS MODEL

Wattage: 2500 WEngine: 20 L max. Circulation Method: Forced CirculationSet Temperature: 100 °F (on) / 120 °F (off)

Wattage: 2500 WEngine: 13.1 L max. Circulation Method: ThermosiphonSet Temperature: 100 °F (on) / 120 °F (off)

CTM MODEL

37% 21 – 45% 16 – 36%

68 °F / 1500 W

kW

h

68 °F / 2500 W 32 °F / 2500 WTPS 0.981 kWEVR 0.615 kW

TPS $71.62 / mo.EVR $44.90 / mo.

CB 1.244 kWCTM 0.868 kWEVR 0.689 kW

CB $90.82 / mo.CTM $63.36 / mo.EVR $50.30 / mo.

CB 2.363 kWCTM 1.802 kWEVR 1.518 kW

CB $172.50 / mo.CTM $131.55 / mo.EVR $110.81 / mo.

CB MODEL

*Actual savings for installed heaters dependent on application, installation and local utility rates.

CS-EVR20-E2020-3/rev0© 2020 Hotstart

The Performance EdgeAll engine heating systems provide baseline benefits. But to avoid common pitfalls of nuisance low temperature alarms, damaged hoses and wasted heating costs, engine heating systems should be capable of providing uniform, even heating throughout the engine block around the clock regardless of ambient conditions.

HOTSTART EVRHEAT SERIES 20 Efficiency & Performance

CB MODEL

ResultsWithout pumps, the TPS and CB models registered well behind the two forced circulation options. Instead, we focused on the 2500 W CTM and EVR models in 32 °F ambient conditions. With inlet and outlet temperatures closest to 110 °F, the EVR showed minimal potential for hot or cold areas in the block.

Wattage: 1500 W | 2500 WEngine: 20 L max. Circulation Method: Forced CirculationSet Temperature: 110°F

EVRHEAT

AnalysisThe benefits of the EVR model’s advanced solid-state controls were readily apparent, keeping average inlet and outlet temperatures extremely close to the optimal 110 °F mark on our test engine*.

TestingTo evaluate the EVRHEAT Series 20 in terms of performance compared to both standard thermosiphon and forced circulation systems, we tested it against our engine heating benchmarks: the HOTSTART TPS, CB and CTM models.

Wattage: 1500 WEngine: 8.2 L max. Circulation Method: ThermosiphonSet Temperature: 100 °F (on) / 120 °F (off)

TPS MODEL

Wattage: 2500 WEngine: 20 L max. Circulation Method: Forced CirculationSet Temperature: 100 °F (on) / 120 °F (off)

Wattage: 2500 WEngine: 13.1 L max. Circulation Method: ThermosiphonSet Temperature: 100 °F (on) / 120 °F (off)

CTM MODEL

68 °F / 1500 W 68 °F / 2500 W 32 °F / 2500 WTPS 104.5 °F EVR 102.6 °F

TPS 146.8 °FEVR 104.7 °F

CB 113.2 °F CTM 112.6 °F EVR 106.5 °F

CB 144.1 °FCTM 113.5 °FEVR 109.2 °F

CB 123.3 °F CTM 116.4 °F EVR 107.8 °F

CB 174.0 °FCTM 119.5 °FEVR 113.2 °F

95

EVR CTM

125

-2.2

120

115

110

105

100

90

130

+6.4

-2.9

-17.9

-1.7

+13.8

+3.2

+9.5

-1.9

-17.0

+5.7

+19.6

EVR CTM

MIN MAX AVG MIN MAX AVG

Tem

p. (

ºF)

95

EVR CTM

125

-2.2

120

115

110

105

100

90

130

+6.4

-2.9

-17.9

-1.7

+13.8

+3.2

+9.5

-1.9

-17.0

+5.7

+19.6

EVR CTM

MIN MAX AVG MIN MAX AVG

Tem

p. (

ºF)

95

EVR CTM

125

-2.2

120

115

110

105

100

90

130

+6.4

-2.9

-17.9

-1.7

+13.8

+3.2

+9.5

-1.9

-17.0

+5.7

+19.6

EVR CTM

MIN MAX AVG MIN MAX AVG

Tem

p. (

ºF)

INLET OUTLET

INLE

TO

UTL

ET

INLE

TO

UTL

ET

INLE

TO

UTL

ET

CB MODEL

*Heater performance based on test engine. Temperatures may vary due to installation and application.

CS-EVR20-E2020-3/rev0© 2020 Hotstart