HOW TO INSTALL AND CONFIGURE SECURITY FOR RSLOGIX 5000 EDITOR AND CONTROLLOGIX PROCESSOR using FACTORYTALK SECURITY Install FactoryTalk Service Platform, RSSecurity Emulator and Enable RSLogix 5000 editor to make it security aware. 1). Install the Factory Talk Platform onto the target system. 2). Run the RSSecurity Emulator Install. This is launched from Windows Start Menu For XP pro, Click on START --> ALL PROGRAMS --> Rockwell Software --> FactoryTalk Tools --> RSSecurity Emulator Install 3). Run the FactoryTalk Administration Console to create an Administrative account and password. (Write the user account and password down). 4). Install RSlogix5000 Software 5) Enabled Security to the RSLogix 5000 Editor: To activate RSLogix 5000, Navigate onto hard drive --> PROGRAM FILES --> Rockwell Software -- > RSLogix 5000 --> ENU --> V15 ---> Security Folder. Note: (V15 could be any version of Rslogix 5000 installed that supports FactoryTalk Security) Launch SetSecKeys.exe by clicking on it and then select RS5000KEYS.INI and then click OPEN. 6) Use FactoryTalk Administration Console to create other accounts with various privileges. Secure an RSLogix 5000 Software Project File

How to Install and Configure Security for Rslogix 5000 Editor and Controllogix Processor

Embed Size (px)

DESCRIPTION

coba

Citation preview

Page 1: How to Install and Configure Security for Rslogix 5000 Editor and Controllogix Processor

HOW TO INSTALL AND CONFIGURE SECURITY FOR RSLOGIX 5000 EDITOR AND CONTROLLOGIX PROCESSOR using FACTORYTALK SECURITY

Install FactoryTalk Service Platform, RSSecurity Emulator and Enable RSLogix 5000 editor to make it security aware.

1). Install the Factory Talk Platform onto the target system. 2). Run the RSSecurity Emulator Install. This is launched from Windows Start Menu For XP pro, Click on START --> ALL PROGRAMS --> Rockwell Software --> FactoryTalk Tools --> RSSecurity Emulator Install 3). Run the FactoryTalk Administration Console to create an Administrative account and password. (Write the user account and password down).

4). Install RSlogix5000 Software

5) Enabled Security to the RSLogix 5000 Editor: To activate RSLogix 5000, Navigate onto hard drive --> PROGRAM FILES --> Rockwell Software --> RSLogix 5000 --> ENU --> V15 ---> Security Folder. Note: (V15 could be any version of Rslogix 5000 installed that supports FactoryTalk Security) Launch SetSecKeys.exe by clicking on it and then select RS5000KEYS.INI and then click OPEN.

6) Use FactoryTalk Administration Console to create other accounts with various privileges.

Secure an RSLogix 5000Software Project File

Once you have configured the RSLogix 5000 software to be security aware, thenext step is to enable security in a RSLogix 5000 software project file.

Follow these steps to secure a project file.

1. Launch RSLogix 5000 from the start menu or the program icon .The default FactoryTalk Security configuration has Single Sign Onenabled, so you will not be prompted to Log On to FactoryTalk.

Customers upgrading from versions prior to 16.03 or customers thathave modified the default FactoryTalk Security configuration will beprompted to Log On to FactoryTalk.

Page 2: How to Install and Configure Security for Rslogix 5000 Editor and Controllogix Processor

2. If prompted to Log On to FactoryTalk, enter a valid set for FactoryTalkcredentials. In the example below, the FactoryTalk Directory (FTD) wasconfigured with an account called FTADMIN.

3. Open the RSLogix 5000 project file that you want to secure.In this example, the DayOfWeek example project file was opened.

4. Open the Controller Properties page from the Edit Menu.

Page 3: How to Install and Configure Security for Rslogix 5000 Editor and Controllogix Processor

5. Record the Name of the Project file displayed on the General tab. In thisexample, the name is DayOfWeek.

TIP:

TIP The name of the Controller can match the name of the ACDfile, but is not required to.

Page 4: How to Install and Configure Security for Rslogix 5000 Editor and Controllogix Processor

6. Select the Advanced tab in the Controller Properties window.7. Change the Security setting to FactoryTalk and click OK.

8. Click Yes on the warning dial box to confirm you want to enablesecurity for the project file.

9. Save the project file10. From the Communication menu select Who Active.

Page 5: How to Install and Configure Security for Rslogix 5000 Editor and Controllogix Processor

11. In the Who Active windows, locate and select the controller resource.

12. Click Download to continue.

Page 6: How to Install and Configure Security for Rslogix 5000 Editor and Controllogix Processor

13. After the download completes, close RSLogix 5000 software. Ifprompted, save changes.

Apply Security to aController ResourceFollow these steps to apply security to a controller resource.1. Open the FactoryTalk Administration Console, select Start>Programs>Rockwell Software>FactoryTalk Administration Console

2. Select the FactoryTalk Directory that the RSSecurity Emulator wasconfigured to work with.

Refer to the selection you made in the section Install the Rockwell SoftwareSecurity Emulator up above.

The default FactoryTalk Security configuration has Single Sign On enabled, sothe you will not be prompted to Log On to FactoryTalk. Customers upgradingfrom revisions prior to 16.03 or customers that have modified the defaultFactoryTalk Security configuration will be prompted to Log On to FactoryTalk.

Page 7: How to Install and Configure Security for Rslogix 5000 Editor and Controllogix Processor

If prompted to Log On to FactoryTalk, enter a valid set for FactoryTalkcredentials. In the example below, the FactoryTalk Directory (FTD) wasconfigured with an account called FTADMIN.

3. Navigate to the controller resource the secured project file wasdownloaded to.

Refer to the section Secure an RSLogix 5000 Software Project File onUp above.

4. Right click on the controller resource and select Properties.

Page 8: How to Install and Configure Security for Rslogix 5000 Editor and Controllogix Processor

5. In the Logical Name drop down list select the Controller name.This name should match the settings from the Controller Propertiespage that you created during Secure an RSLogix 5000 Software ProjectFile section. The controller name can also be manually typed in if thename does not appear in the drop down list.

TIP

TThe controller in the Network and Devices tree will also displaythe controller name property next to the controller resource.

The controller in the Network and Devices tree will also displaythe controller name property next to the controller resource.

If the name does not appear in the Network and Devices tree,open RSLinx Classic and navigate to the controller resource withRSWho. Navigating to the resource in RSLinx Classic willupdate the Controller path information in RSLinx Classic.FactoryTalk Administration Console uses the controller pathinformation from RSLinx Classic to display Controllers. Once thepath information is updated in RSLinx Classic, open theFactoryTalk Administration Console and right click on theNetwork and Devices tree and select refresh.TIP

6. Once the Logical Name for the Controller has been set to match the

Page 9: How to Install and Configure Security for Rslogix 5000 Editor and Controllogix Processor

Controller name, click OK to continue.

This completes the FactoryTalk Security configuration for an RSLogix 5000controller resource. Individual user or groups rights will still need to beconfigured to control access to secured Controllers. For more FactoryTalkSecurity information, refer to The FactoryTalk Security Quick Start,publication FTSEC-QS001. AID 44903 - Link to FactoryTalk Security Quick Start Guide

http://rockwellautomation.custhelp.com/cgi-bin/rockwellautomation.cfg/php/enduser/std_adp.php?p_faqid=44903