HRN-55
HRN-55N
HRN-55
HRN-55N
HRN-55 HRN-55N
HRN-55NHRN-55
8
L1
L2
L3
15-18
Umin
UOFF
Umax
Umin
UOFF
Umax
Umin
UOFF
Umax
onitoring terminals:
upply terminals:
oltage:evel Umax:
evel Umin:
onsumption:
ysteresis:
ax. permanent:
eak overload <1ms:
me delay T1:
me delay T2:
utput
umber o contacts:
ated current:
eaking capacity:
rush current:
witching voltage:
in. breaking capacity DC:
utput indication:
echanical lie:
ectrical lie (AC1):
ther inormation
perating temperature:
orage temperature:
ectrical strength:
perating position:
ounting:
otection degree:
vervoltage cathegory:
ollution degree:
ax. cable size (mm2):
mensions:
eight:
andards:
Relay for monitoring phase sequence and failure HRN-55, HRN-55N
replacement or HRN-51 and HRN -51N
relay monitors phase sequence and ailure, exceeding o monitored voltage in 3 phase main
HRN-55 - supply rom all phases, which means that unction o relay is applicable also i one phase ails
HRN-55N - supply L1-N, it means that relay also monitors break o neutral point
fxed delay T1 (500ms) and a djustable delay T2 (0.5-10s)
aulty state is indicated by LED and output contact o relay is OFF.
output contact: 1x changeover 16 A / 250 V AC1
1-MODULE, DIN rail mounting
Supply/monitoring terminals
Supply/monitoring terminals
Indication
Adjusting o time delay T2
Output contact
125% Un
75% Un
max. 2 VA
5%
max. 500 ms
adjustable 0.1-10 s
1x changeover (AgNi)
8 A / AC1
2500 VA / AC1, 240 W / DC
10 A
250 V AC1 / 24 V DC
500 mW
red LED
1x107
1x105
-20.. +55 0C
-30.. +70 0C
4 kV (supply - output)
any
DIN rail EN 60715
IP 40 rom ront panel
III.
2
solid wire max. 2x2.5 or 1x4with sleeve max. 1x2.5 or 2x1.5
90 x 17.6 x 64 mm, see page 157-159
67 g 66 g
EN 60255-6, EN 61010-1
L1, L2, L3
L1, L2, L3
3x400 V
L1, L2, L3, N
L1, N
3x400 V/230 V
AC 3x265 V
AC 3x288 V
AC 3x460 V
AC 3x500 V
ay in 3-phase main monitors correct phase sequence and ailure o any phase. GreenD is permanently ON and indicates presence o power supply voltage. In case o phaseure or exceeding voltage level red LED fashes and relay breaks. When changing tolty state, time delay applies. Time delay setting is set by a potentiometer on ront
nel o the device. In case o incorrect phase sequence red LED shines permanently
d relay is open. In case supply voltage alls below 60% Un (OFF lower level)relaymediately opens with no delay and aulty state is indicated by red LED.N-55: thanks to supply orm all phases, this relay is able to stay operational alsone phase is out.N-55N -supply L1-N, means that relay monitor also ailure in neutral wire
echnical parameters Symbol Connection
Function
Description
unction description
!
!
!
!
!
!
!
!
Hysteresis
red LED
green LED