    Embedded DC Power System

    ETP48200-A6A1 and ETP48200-B6 are AC/DC embedded power

    system with excellent performance such as high power efficiency,

    intelligent battery management, remote monitoring, wide range of

    AC input voltage, etc. The system configures 50A of 2U high

    rectifier modules, and provides rated current output of 200A.

    ETP48200-A6A1 and ETP48200-A6A3 can be embedded in 19-inch

    rack or cabinet.

    Wireless base station

    Transmission network

    Communication network of enterprise

    Application Scenarios

    Features

    Introduction

    ETP48200-A6A1, ETP48200-B6

    Wide range of AC input voltage from 85V to 300V

    Wide operation temperature range of rectifier from -40 to 75

    Online-swappable rectifier provides easy installation and

    maintenance

    Standard installation structure design, adapting to various

    scenarios

    Compact design, saving space and installation cost

    High rectifier efficiency over 96% helps to save energy

    Excellent rectifier dormancy function helps to increase system

    efficiency

    Intelligent battery management and protection helps to prolong

    battery lifespan

    Support environment monitoring and remote management

    through dry contact, serial interface or Ethernet interface

    ETP48200-A6A1

    ETP48200-A6A3

  • 8/11/2019 Huawei Embedded Power System ETP48200-A6A1 B6 DataSheet

    2/2

    HUAWEITECHNOLOGIESCO.,LTD.

    HuaweiIndustrialBase

    Bantian

    LonggangShenzhen518129,P.R.China

    Tel:+86-755-28780808

    www.huawei.com

    Copyright Huawei Technologies Co., Ltd. 2013. All rights reserved.

    No part of this document may be reproduced or transmitted in any form or by any means without prior

    written consent of Huawei Technologies Co., Ltd.

    General DisclaimerThe information in this document may contain predictive statements including,without limitation, statements regarding the future

    financial and operating results, future product portfolio, new technology, etc. There are a number of factors that could cause actual

    results and developments to differ materially from those expressed or implied in the predictive statements. Therefore,

    such information is provided for reference purpose only and constitutes neither an offer nor an acceptance.

    Huawei may change the information at any time without notice.

    Specifications

    Type ETP48200-A6A1 ETP48200-B6

    System

    Dimension 482.6mm(W)310mm(D)266.7mm(6U,H)

    Weight 20kg (without rectifiers)

    Cooling mode Natural cooling

    Installation mode Installed on 19-inch rack or cabinet

    Cabling mode Left inlet and right outlet

    Maintenance mode Front access, support module grade change

    Protection level IP20

    ACDistribution

    Input mode 220/380VAC 3-phase or 220VAC single phase 220VAC single phase or 110VAC dual-live wire

    Input voltage 220VAC/380VAC 220VAC/110VAC

    Input breakers 163A/3P 1100A/2P

    Output breakers 120A/1P, 216A/1P 116A/2P

    Input frequency 45~66Hz, rated value: 50Hz/60Hz

    SPD 30kA/60kA, 8/20s 30kA/60kA, 8/20s

    DCDistribution

    Output voltage 42~58V DC, rated value: 53.5V DC

    Maximum capacity 12kW

    Battery breakers 2125A/1P

    Load breakersLLVD: 2100A/1PBLVD: 163A/1P, 132A/1P, 316A/1P

    LLVD: 2100A/1P, 120A/1PBLVD: 163A/1P, 132A/1P, 316A/1P

    SPD 10kA/20kA8/20s NA

    Rectifier

    Input voltage 85VAC300 VAC, rated value: 220VAC

    Efficiency 96%

    Rated Power 3000W(176~300VAC)

    Workingtemperature

    -40~+75(derated output above 55)

    Dimension 103mm(W)243mm(D)88.9mm(2U,H)

    Weight 2.8kg

    Cooling mode Forced cooling

    Power factor 0.99

    THD 5%

    Controller

    Signal input6 digital input, 1 door magnetism, 1 water logging, 1 smoke, 2 temperature, 1 battery temperature, 1environment temperature and humidity

    Alarm output 8 dry contact output

    Communication port RS232/485, FE

    Display mode LCD

    Environment

    Operatingtemperature

    -40~+65

    Storage temperature -40~+70

    Operating humidity 5%~95%(non-condensing)

    Altitude0~4000m(If the altitude is within the range of 2000m to 4000m, the maximum operating temperaturedecreases by 1 as the altitude increases by 200m.)

    Remark: Optional rectifiers with power efficiency >92% are available for this system.