33
NetShutdown V100R001C00 User Manual Issue 01 Date 2013-06-13 HUAWEI TECHNOLOGIES CO., LTD.

Huawei Net Shutdown UPS Monitoring and Control Software

  • Upload
    others

  • View
    59

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Huawei Net Shutdown UPS Monitoring and Control Software

NetShutdownV100R001C00

User Manual

Issue 01

Date 2013-06-13

HUAWEI TECHNOLOGIES CO., LTD.

Page 2: Huawei Net Shutdown UPS Monitoring and Control Software

Copyright © Huawei Technologies Co., Ltd. 2013. All rights reserved.No part of this document may be reproduced or transmitted in any form or by any means without prior writtenconsent of Huawei Technologies Co., Ltd. Trademarks and Permissions

and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.All other trademarks and trade names mentioned in this document are the property of their respective holders. NoticeThe purchased products, services and features are stipulated by the contract made between Huawei and thecustomer. All or part of the products, services and features described in this document may not be within thepurchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information,and recommendations in this document are provided "AS IS" without warranties, guarantees or representationsof any kind, either express or implied.

The information in this document is subject to change without notice. Every effort has been made in thepreparation of this document to ensure accuracy of the contents, but all statements, information, andrecommendations in this document do not constitute a warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.Address: Huawei Industrial Base

Bantian, LonggangShenzhen 518129People's Republic of China

Website: http://www.huawei.com

Email: [email protected]

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

i

Page 3: Huawei Net Shutdown UPS Monitoring and Control Software

Contents

1 About This Document..................................................................................................................1

2 Precautions......................................................................................................................................3

3 Product Introduction.....................................................................................................................43.1 Product Description........................................................................................................................................................53.2 Application Scenarios.....................................................................................................................................................5

4 Hardware Installation...................................................................................................................6

5 Software Installation.....................................................................................................................75.1 Installing NetShutdown on Windows OS.......................................................................................................................85.2 Installing NetShutdown on SUSE or Solaris OS............................................................................................................9

6 Communication Matrix..............................................................................................................12

7 Basic Features...............................................................................................................................137.1 Starting or Stopping NetShutdown Services................................................................................................................147.2 Loging In to the Client..................................................................................................................................................147.3 Viewing Event Logs.....................................................................................................................................................177.4 Setting UPS Communication Parameters.....................................................................................................................177.5 Setting Shutdown Policies............................................................................................................................................197.6 Checking UPS Device Information..............................................................................................................................217.7 Setting User Information..............................................................................................................................................217.8 FAQs.............................................................................................................................................................................237.8.1 How Do I Uninstall NetShutdown on Windows OS?...............................................................................................237.8.2 How Do I Uninstall NetShutdown on SUSE or Solaris OS?....................................................................................247.8.3 How Do I Check the Integrity of Software Packages?..............................................................................................257.8.4 What Do I Do When the IE Browser Displays a Message Asking Me to Close the Compatibility View on the LoginPage?...................................................................................................................................................................................267.8.5 What Do I Do When the Login Port of the NetShutdown Installed in the Windows Operating System Has BeenOccupied?...........................................................................................................................................................................277.8.6 What Do I Do When the Login Port of the NetShutdown Installed in the SUSE or Solaris OS Has Been Occupied?............................................................................................................................................................................................287.8.7 How to Use WinSCP to Transfer Files?....................................................................................................................28

NetShutdownUser Manual Contents

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

ii

Page 4: Huawei Net Shutdown UPS Monitoring and Control Software

1 About This Document

To better use this manual, you are advised to familiarize yourself with product model, intendedaudience, and symbol conventions.

Purpose

This document describes the installation, function, maintenance and troubleshooting methodsof the NetShutdown software. Before you install and use the software, you need to familiarizeyourself with the functions and features of uninterruptible power supply (UPS), and read thisdocument to learn the security information.

Product Model

The NetShutdown software operation guidelines in this document apply to the UPS of thefollowing series:

l UPS2000

l UPS5000-E

You are advised to print this manual and store both the paper and electronic documents properlyto facilitate subsequent reference.

Intended Audience

This document is intended for PC and server OM personnel.

Symbol Conventions

The symbols that may be found in this document are defined as follows:

Symbol Description

Indicates a hazard with ahigh level or mediumlevel of risk which, if notavoided, could result indeath or serious injury.

NetShutdownUser Manual 1 About This Document

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

1

Page 5: Huawei Net Shutdown UPS Monitoring and Control Software

Symbol Description

Indicates a hazard with alow level of risk which, ifnot avoided, could resultin minor or moderateinjury.

Indicates a potentiallyhazardous situation that,if not avoided, couldresult in equipmentdamage, data loss,performancedeterioration, orunanticipated results.

Provides additionalinformation toemphasize orsupplement importantpoints in the main text.

NetShutdownUser Manual 1 About This Document

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

2

Page 6: Huawei Net Shutdown UPS Monitoring and Control Software

2 Precautions

During NetShutdown installation, operation, and maintenance, read the following precautionscarefully:

l Operating system patches must be updated on the computer or server where theNetShutdown is installed in a timely manner.

l Professional firewalls and antivirus software must be available on the computer or serverwhere the NetShutdown is installed, and the antivirus software must be updated in a timelymanner.

NetShutdownUser Manual 2 Precautions

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

3

Page 7: Huawei Net Shutdown UPS Monitoring and Control Software

3 Product Introduction

About This Chapter

3.1 Product Description

3.2 Application Scenarios

NetShutdownUser Manual 3 Product Introduction

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

4

Page 8: Huawei Net Shutdown UPS Monitoring and Control Software

3.1 Product DescriptionNetShutdown is a part of network centralized monitoring system for the NetEco. It monitorsUPS events and takes predefined protective measures when certain events occur, for example,when UPS powering system is facing risks. The protective measures are running commandscripts and shutting down computers or servers. NetShutdown helps protect your computer orserver hardware and software assets.

3.2 Application Scenarios

Figure 3-1 Networking schemes of the NetShutdown

A UPS or a combined server system can provide power supplies for multiple computers orservers.

When the NetShutdown software installed on a computer or server is started, theNetShutdown can listen to the status of a UPS and implement computer or server shutdown.

NetShutdownUser Manual 3 Product Introduction

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

5

Page 9: Huawei Net Shutdown UPS Monitoring and Control Software

4 Hardware Installation

Step 1 Connect the computer or server to the Ethernet.

Step 2 Connect the UPS to the Ethernet.

Step 3 Ping the IP address of the UPS on the computer or server.

If the IP address can be pinged, the UPS is successfully connected to the computer or server.

----End

NetShutdownUser Manual 4 Hardware Installation

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

6

Page 10: Huawei Net Shutdown UPS Monitoring and Control Software

5 Software Installation

About This Chapter

This section describes the methods of installing the NetShutdown software for the Windows,SUSE, and Solaris operating systems.

5.1 Installing NetShutdown on Windows OS

5.2 Installing NetShutdown on SUSE or Solaris OS

NetShutdownUser Manual 5 Software Installation

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

7

Page 11: Huawei Net Shutdown UPS Monitoring and Control Software

5.1 Installing NetShutdown on Windows OS

Installation Requirementsl The software package is available in the DVD-ROM delivered with the product.

Alternatively, you can download the software packageNetShutdownV100R001C00SPC200_Win.zip from http://www.huawei.com/en/ andcheck the integrity of the software package.To download the software package, choose SUPPORT > Software Download > NetworkEnergy > UPS and Inerter > UPS > iManager NetEco 1000U >V100R001C00SPC200.You can check the integrity of the software package by referring to 7.8.3 How Do I Checkthe Integrity of Software Packages?.

l Software Requirements– Operating system: Windows XP or Windows 7.– Web browser: Internet Explorer 8.0 or Firefox 3.6.

l Hardware Requirements– PC: One that runs either of the preceding operating systems.– Hard disk space: 512 MB or above.– Memory: 256 MB or above.

ProcedureTo install NetShutdown on Windows OS, perform the following steps:

Step 1 Insert the installation DVD-ROM into the DVD-ROM drive of the PC, and navigate to theNetShutdown directory in the DVD-ROM. Double-click setup.vbs.TheSelect Installation Language window is displayed.

NOTE

If you download the software package from http://www.huawei.com/en/ for the installation, skip this step.

Step 2 Decompress the software package, open the generated folder, and double-click setup.vbs.

TheSelect Installation Language window is displayed.

NOTE

If you use the DVD-ROM delivered with the product for the installation, skip this step.

Step 3 Choose English, and click OK.

Step 4 Click Next.The Copyright Notice window is displayed.Read the terms of the copyright notice in the Copyright Notice window.

Step 5 Select I accept these terms, and click Next.The Select Installation Directory window is displayed.The default directory is D:\NetShutdown.

NetShutdownUser Manual 5 Software Installation

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

8

Page 12: Huawei Net Shutdown UPS Monitoring and Control Software

Step 6 Specify an installation path and click Next.The Select Software Components window is displayed.

Step 7 Select NetShutdown for installation and click Next.The Security Configure window is displayed.

Step 8 Determine whether to select Use Security Web Service according to the actual communicationsecurity requirements. Then, click Next.The Confirm Installation window is displayed.

Step 9 Confirm the installation settings and click Next.The Installation Status window is displayed.The Installation Completed window is displayed after the installation process reaches 100%.

Step 10 Click Finish.When the software is installed successfully, the NetShutdown shortcut menu is available underStart > All Program.

NOTE

During the installation, you can click Cancel in any window with Cancel on it, and the Conformationwindow is displayed.

l You can click Yes to quit the installation.

l You can click No to proceed with the installation.

----End

5.2 Installing NetShutdown on SUSE or Solaris OS

Installation Requirementsl The software package is available in the DVD-ROM delivered with the product.

Alternatively, you can download the software package from http://www.huawei.com/en/ and check the integrity of the software package.To download the software package, choose SUPPORT > Software Download > NetworkEnergy > UPS and Inerter > UPS > iManager NetEco 1000U >V100R001C00SPC200.– The software package for SUSE OS is

NetShutdownV100R001C00SPC200_Linux.zip.– The software package for Solaris OS is

NetShutdownV100R001C00SPC200_Solaris.zip.You can check the integrity of the software package by referring to 7.8.3 How Do I Checkthe Integrity of Software Packages?.

l Hardware Requirements– Hard disk space: 512 MB or above.– Memory: 256 MB or above.

Procedure

Step 1 Log in to the server on which you want to install the NetShutdown software.

NetShutdownUser Manual 5 Software Installation

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

9

Page 13: Huawei Net Shutdown UPS Monitoring and Control Software

Step 2 Run the following command to create a temporary directory /Shutdown in the root directory ofOS:

# mkdir Shutdown

Step 3 Upload the software package to the /Shutdown directory on the server using SFTP. For detailedoperations, see 7.8.7 How to Use WinSCP to Transfer Files?.

Step 4 Run the following commands to access the /Shutdown directory:

# cd /Shutdown

Step 5 Run the following commands to decompress the software package:l Commands for SUSE OS:

# unzip NetShutdownV100R001C00SPC200_Linux.zip# unzip NetShutdown_Linux.zip

l Commands for Solaris OS:# unzip NetShutdownV100R001C00SPC200_Solaris.zip# unzip NetShutdown_Solaris.zip

Step 6 Run the following command to assign execution rights to the install.sh file:

# chmod +x install.sh

Step 7 Run the following command to install NetShutdown:#./install.sh

The following information is displayed:

Please input installation path [default:/opt/NetShutdown]:

Step 8 Enter the installation directory for NetShutdown and press Enter.

NOTE

You can also press Enter to install the NetShutdown software in the default installation directory /opt/Netshutdown.

The following information is displayed:

Please select the language in which you want to install the NetEco:1) English2) Chinese3) exitPlease enter your choice [1 or 2]:

Step 9 Enter 1 and press Enter.

The following information is displayed:

Are you sure enable https?[Default:n]

Step 10 Enter n to disable HTTPS or enter y to enable HTTPS according to site requirements.l Enter y to enable HTTPS, and press Enter.

The following information is displayed:--------------------------------------------------| || || Install Information || Install path:/opt/Netshutdown || Install Language:Chinese |

NetShutdownUser Manual 5 Software Installation

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

10

Page 14: Huawei Net Shutdown UPS Monitoring and Control Software

| Enable https:true || |-------------------------------------------------Are you sure to continue?(y/n)

l Enter n to disable HTTPS, and press Enter.The following information is displayed:--------------------------------------------------| || || Install Information || Install path:/opt/Netshutdown || Install Language:Chinese || Enable https:false || |-------------------------------------------------Are you sure to continue?(y/n)

Step 11 Enter y and press Enter.

NOTE

If you want to stop the installation, type n and press Enter.

The NetShutdown software installation starts.

NetShutdown is successfully installed when the following information is displayed:

Installation of <NetShutdown> was successful.

----End

NetShutdownUser Manual 5 Software Installation

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

11

Page 15: Huawei Net Shutdown UPS Monitoring and Control Software

6 Communication Matrix

Table 6-1 Communication matrix

ProtocolType

SourceDevice

Source PortNumber

TargetDevice

Destination PortNumber

PortDescription

Authentication Mode

EncryptionMode

HTTP

Webbrowser

Random port

NetShutdownserver

8011 Used as acommonport forNetShutdown client

Usernameand password

None

HTTPS

Webbrowser

Random port

NetShutdownserver

8445 Used as anencryptedport forNetShutdown client

Usernameand password

SSL

SNMP

NetShutdownserver

Random port

UPS 161 Used forquery of theUPS tocommunicate with theNetShutdown

l SNMPV1/V2:Readcommunity name &Writecommunity name

l SNMPV3:Usernameandpassword

l SNMPV1/V2:None

l SNMPV3:DES

SNMP

UPS Random port

NetShutdownserver

162 Used forUPS datareporting

None None

NetShutdownUser Manual 6 Communication Matrix

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

12

Page 16: Huawei Net Shutdown UPS Monitoring and Control Software

7 Basic Features

About This Chapter

7.1 Starting or Stopping NetShutdown ServicesThis section describes how to start or stop NetShutdown services. The methods of starting andstopping these services vary according to operating system types.

7.2 Loging In to the ClientThis section describes how to log in to the NetShutdown before using NetShutdown services.

7.3 Viewing Event LogsThis section describes how to view event logs on the NetShutdown, including types of eventsthat have occurred, occurrence time, and details about each event.

7.4 Setting UPS Communication ParametersThis section describes how to set UPS communication parameters to ensure that the a computeror server can communicate with the UPS properly.

7.5 Setting Shutdown PoliciesThis section describes how to set shutdown polices to enable a computer or server to take themeasures defined in the Local Settings area of the Shutdown Settings page based on concernedUPS shutdown events.

7.6 Checking UPS Device InformationThis section describes how to view UPS device information to learn about UPS operating status.

7.7 Setting User InformationThis section describes how to set user information to change user name, password, and remarks.

7.8 FAQs

NetShutdownUser Manual 7 Basic Features

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

13

Page 17: Huawei Net Shutdown UPS Monitoring and Control Software

7.1 Starting or Stopping NetShutdown ServicesThis section describes how to start or stop NetShutdown services. The methods of starting andstopping these services vary according to operating system types.

Starting NetShutdown Services on Windows OSChoose Start > All Program > NetShutdown > NetShutdown Service to start theNetShutdown service on Windows OS.

After being started, the NetShutdown service icon is displayed in the lower right corner ofthe taskbar of the desktop.

Stopping NetShutdown Services on Windows OS

Right-click the NetShutdown service icon in the lower right corner of the taskbar of thedesktop and choose Exit from the shortcut menu.

Starting NetShutdown Services on SUSE or Solaris OSRun the netshutdown start command to start NetShutdown services.

Stopping NetShutdown Services on SUSE or Solaris OSRun the netshutdown stop command to stop NetShutdown services.

Restarting NetShutdown Services on SUSE or Solaris OSRun the netshutdown restart command to restart NetShutdown services.

Checking NetShutdown Service Status on SUSE or Solaris OSRun the netshutdown status command to check the NetShutdown service status.

7.2 Loging In to the ClientThis section describes how to log in to the NetShutdown before using NetShutdown services.

PrerequisitesYou have started the NetShutdown services. For details about how to start the services, see 7.1Starting or Stopping NetShutdown Services.

Procedure

Step 1 Enter http://IP address:8011/shutdown/ (for example, http://192.168.0.1:8011/shutdown/) in theaddress bar of the web browser.l If you have chosen Use Security Web Service when installing NetShutdown, a page reading

There is a problem with this website's security certificate. is displayed, as shown in Figure7-1.

NetShutdownUser Manual 7 Basic Features

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

14

Page 18: Huawei Net Shutdown UPS Monitoring and Control Software

Click Continue to this website (not recommended) to choose the default securitycertificate. The Login page is displayed.

l The Login page is displayed.

Figure 7-1 Page indicating that there is a problem with this website's security certificate

Step 2 (Optional. Required only for the first login) Set User Name, Password, Confirm Password,and Remarks on the System Initial Password page shown in Figure 7-2. Then, click OK. Themain page of the software is displayed, as shown in Figure 7-4.

NOTEWhen you log in to the NetShutdown for the first time, the default user name is admin.

Figure 7-2 System initial password

NetShutdownUser Manual 7 Basic Features

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

15

Page 19: Huawei Net Shutdown UPS Monitoring and Control Software

Step 3 If this is not your first-time login, set User Name and Password on the Login page shown inFigure 7-3. Then, click OK. The main page of the software is displayed, as shown in Figure7-4.

Figure 7-3 Login

Figure 7-4 Main page

----End

NetShutdownUser Manual 7 Basic Features

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

16

Page 20: Huawei Net Shutdown UPS Monitoring and Control Software

7.3 Viewing Event LogsThis section describes how to view event logs on the NetShutdown, including types of eventsthat have occurred, occurrence time, and details about each event.

Choose Event Log from the main menu. The Event Log page is displayed.

NOTE

A maximum of 20 event logs can be displayed on the Event Log page. If the number of event logs reaches 20,the NetShutdown automatically deletes the earliest one when a new event log is recorded.

You can click Clear to remove all logs.

7.4 Setting UPS Communication ParametersThis section describes how to set UPS communication parameters to ensure that the a computeror server can communicate with the UPS properly.

Step 1 Choose Communication Settings from the main menu.

The Communication Settings page is displayed.

NetShutdownUser Manual 7 Basic Features

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

17

Page 21: Huawei Net Shutdown UPS Monitoring and Control Software

Step 2 Specify IP Address of the UPS and click Next.

The Select page is displayed.

NOTE

l If you enter the IP address of a UPS single-server system, information about a single UPS is displayed.

l If you enter the IP address of a UPS combined server system, information about multiple UPSs is displayed.

Step 3 On the displayed Select page, select a UPS device and click Next.

The Information Confirmed page is displayed.

NetShutdownUser Manual 7 Basic Features

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

18

Page 22: Huawei Net Shutdown UPS Monitoring and Control Software

Step 4 Click Finish.

When the UPS communication parameters are set successfully, the Event Log page isautomatically displayed with a Device access shutdown software event log added.

----End

7.5 Setting Shutdown PoliciesThis section describes how to set shutdown polices to enable a computer or server to take themeasures defined in the Local Settings area of the Shutdown Settings page based on concernedUPS shutdown events.

Step 1 Choose Shutdown Settings from the main menu.

The Shutdown Settings page is displayed.

Step 2 Select the events in the Shutdown Event area.

When a selected event occurs, NetShutdown takes measures defined in the Local Settings area.

Step 3 Select the Execution Of Command File check box if you want command scripts to be executedwhen the selected events occur.

NetShutdownUser Manual 7 Basic Features

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

19

Page 23: Huawei Net Shutdown UPS Monitoring and Control Software

1. Set Script Delay.l If you set this parameter to 0, the command scripts are executed immediately after a

selected event occurs.l If Script Delay is set, the NetShutdown executes command scripts after the specified

delay when the selected UPS shutdown event occurs. If the event is cleared within thespecified time, the timer stops and the command scripts will not be executed.

CAUTIONYou must evaluate the UPS battery time (depending on load) and time required for scriptexecution before setting Script Delay. The value of Script Delay must be smaller than theUPS battery time minus time required for script execution. Otherwise, power will be cutoff before the script execution is complete.

2. Set Script File to the directory of the command scripts.

NOTE

If the NetShutdown is installed in the SUSE or Solaris OS, you need to perform the following steps togrant execute permission on the script file.

a. Log in to the server where the NetShutdown is installed .

b. Navigate to the directory of the script file.

# cd directory of the script file

c. Grant execute permission on the script file.

# chmod +x script file name

Step 4 Select the Turn off the Computer check box if you want the computers or servers to be shutdown when the selected events occur and set Delay Time.

This protects computers or servers from damages caused by forced shutdown.

l If you set this parameter to 0, the computers or servers are shut down immediately after aselected event occurs.

l If you set this parameter to a positive value other than 0, the computers or servers will beshut down when the specified time has elapsed. If the event is cleared within the specifiedtime, the timer stops and the computers or servers will not be shut down.

l If you select both Execution Of Command File and Turn off the Computer check boxes,ensure that the value of Delay Time must be greater than the value of Script Delay plus timerequired for script execution. With this setting, the script execution can be finished beforethe computers or servers are shut down.

CAUTIONYou must evaluate the UPS battery time (depending on load) and time required for scriptexecution before setting Delay Time. The value of Delay Time must be smaller than the UPSbattery time minus time required for script execution. Otherwise, power will be cut off beforethe script execution is complete.

Step 5 Click Save.

NetShutdownUser Manual 7 Basic Features

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

20

Page 24: Huawei Net Shutdown UPS Monitoring and Control Software

When the shutdown policies are set successfully, the Event Log page is automatically displayedwith a Shutdown Settings event log added.

----End

7.6 Checking UPS Device InformationThis section describes how to view UPS device information to learn about UPS operating status.

Choose UPS Information from the main menu, the UPS Information page is displayed.

When a UPS is upgraded or its operating status is changed, the NetShutdown updates the deviceinformation and operating status of the UPS in real time.

7.7 Setting User InformationThis section describes how to set user information to change user name, password, and remarks.

NOTE

The NetShutdown software supports only one user, and therefore each time there is only user who logs in to theNetShutdown from the NetShutdown client.

Changing the User Name

Step 1 Choose User Information from the main menu.

The User Information page is displayed.

NetShutdownUser Manual 7 Basic Features

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

21

Page 25: Huawei Net Shutdown UPS Monitoring and Control Software

Step 2 Click .

The Modify Name dialog box is displayed.

Step 3 Enter the new user name in the User Name text box.

Step 4 Enter the password in the Password text box.

Step 5 Click Save.

The message Successfully saved is displayed.

NetShutdownUser Manual 7 Basic Features

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

22

Page 26: Huawei Net Shutdown UPS Monitoring and Control Software

Step 6 Click Save.

When the user name is changed successfully, the Event Log page is displayed.

----End

Changing the Password

Step 1 Choose User Information from the main menu.

The User Information page is displayed.

Step 2 Enter the old password in the Old Password text box.

Step 3 Enter a new password in the New Password text box and enter it again in the ConfirmPassword text box.

Step 4 Click Save.

When the password is changed successfully, the Event Log page is displayed.

----End

Changing the Remarks

Step 1 Choose User Information from the main menu.

The User Information page is displayed.

Step 2 Enter information in the Remarks text box.

Step 3 Click Save.

When the remarks is changed successfully, the Event Log page is displayed.

----End

7.8 FAQs7.8.1 How Do I Uninstall NetShutdown on Windows OS?

QuestionHow do I uninstall NetShutdown on Windows OS?

Answer

Step 1 Right-click NetShutdown in the lower right corner of the desktop and choose Exit from theshortcut menu.

NOTE

If the NetShutdown service is not started, skip this step.

Step 2 Choose Start > All Program > NetShutdown > Uninstall NetShutdown to start theuninstallation program.

NetShutdownUser Manual 7 Basic Features

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

23

Page 27: Huawei Net Shutdown UPS Monitoring and Control Software

The Select Software Components window is displayed.

Step 3 Select the NetShutdown component, and click Next.

Step 4 Click Yes.

The NetShutdown uninstallation progress is displayed in the window.

Step 5 Click Finish when the uninstallation is complete.The Conformation dialog box is displayed.

Step 6 Determine whether to restart the operating system.l If you click Yes, the operating system is restarted, and the NetShutdown installation directory

is deleted automatically.l If you click No, the operating system will not be restarted, and you need to manually delete

the NetShutdown installation directory.

----End

7.8.2 How Do I Uninstall NetShutdown on SUSE or Solaris OS?

QuestionHow do I uninstall NetShutdown on SUSE or Solaris OS?

Answer

Step 1 Run the following command to check the operating status of the NetShutdown.

# netshutdown status

l If the command output is the following information, go to Step 2.SUCCESS! NetShutdown running.

l If the command output is the following information, go to Step 3. NetShutdown is not running.

Step 2 Run the following command to stop NetShutdown services.

# netshutdown stop

Step 3 Run the following command to access the directory where the uninstall.sh file is stored:

# cd /opt/Netshutdown/uninstall

NOTE

/opt/Netshutdown is the installation directory for NetShutdown. Replace it as required.

Step 4 Run the following command to uninstall NetShutdown.

# ./uninstall.sh

The following information is displayed:

Are you sure unistall Netshutdown server?(y/n)

Step 5 Enter y and press Enter.

NetShutdown is successfully uninstalled when the following information is displayed:

NetShutdownUser Manual 7 Basic Features

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

24

Page 28: Huawei Net Shutdown UPS Monitoring and Control Software

Unistall Netshutdown software successful.

----End

7.8.3 How Do I Check the Integrity of Software Packages?

Question

How do I check the integrity of software packages?

Answer

The methods of checking the integrity of NetShutdown software packages for the SUSE, Solaris,and Windows operating systems (OSs) are the same. For each type of OS, the integrity checkmust be performed on a PC.

The following takes checking software package integrity on Windows OS as an example.

Step 1 Log in to http://www.huawei.com/cn/.

Step 2 Choose SUPPORT > Software Download > Network Energy > UPS and Inerter > UPS >iManager NetEco 1000U > V100R001C00SPC200. Then, download the NetShutdownsoftware package and software package integrity check tool iPSI Sign Tool Setup.exe to adirectory on the NetShutdown server. This section takes D:\ for example.

Step 3 Install the software package integrity check tool.

1. Double-click iPSI Sign Tool Setup.exe.

2. Click Next.

3. Choose I accept the terms in the License Agreement, and click Next.

4. Specify an installation path and click Install.

5. Click Finish.

Step 4 Decompress the software package.

Step 5 Choose Start > Run. In the displayed dialog box, enter cmd and press Enter. The command-line interface (CLI) is displayed.

Step 6 Run the following command to navigate to the installation directory of the software packageintegrity check tool.

cd C:\Program Files\iPSI Sign Tool

NOTE

C:\Program Files\iPSI Sign Tool is the installation directory of the software package integrity check tool.Replace it as required.

Step 7 Run the following commands to check the integrity of the software package:

ipsisign /verify /p d:\NetShutdownV100R001C00SPC200_Win /d NetShutdown_Win.rar /s d:\NetShutdownV100R001C00SPC200_Win\NetShutdown_Win.rar_SIGN.txt

NetShutdownUser Manual 7 Basic Features

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

25

Page 29: Huawei Net Shutdown UPS Monitoring and Control Software

NOTE

l If the file name or directory contains spaces, you must add a pair of quotation marks (") before commandexecution.

For example: ipsisign /verify /p “d:\NetShutdownV100R001C00SPC200_Win” /d"NetShutdown_Win.rar" /s “d:\NetShutdownV100R001C00SPC200_Win\NetShutdown_Win.rar_SIGN.txt".

l “d:\NetShutdownV100R001C00SPC200_Win” is the directory generated after software packagedecompression. Replace it as required.

l If information similar to the following is displayed, the software package is intact.SignCLI Info: Successfully verified

l If the information containing fail or error is displayed, the software package failed theintegrity check. In this case, contact Huawei technical support.

----End

7.8.4 What Do I Do When the IE Browser Displays a MessageAsking Me to Close the Compatibility View on the Login Page?

QuestionWhat do I do when the IE browser displays a message asking me to close the compatibility viewon the login page?

Answer

Step 1 Choose Tools > Compatibility View Settings on the IE menu bar.

Step 2 Clear the check box for Display all websites in Compatibility View.

NetShutdownUser Manual 7 Basic Features

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

26

Page 30: Huawei Net Shutdown UPS Monitoring and Control Software

----End

7.8.5 What Do I Do When the Login Port of the NetShutdownInstalled in the Windows Operating System Has Been Occupied?

QuestionWhat do I do when the login port of the NetShutdown installed in the Windows operating systemhas been occupied?

AnswerWhen the NetShutdown login port is occupied, you can solve the problem by changing the portnumber.

Step 1 Navigate to the NetShutdown installation directory\WebRoot_Shutdown\WEB-INF\classes directory.

Step 2 Open the struts.properties file.

Step 3 Change the values of the following parameters:struts.httpPort=8011struts.httpsPort=8445

Step 4 Restart the NetShutdown service. For detailed operations, see 7.1 Starting or StoppingNetShutdown Services.

NetShutdownUser Manual 7 Basic Features

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

27

Page 31: Huawei Net Shutdown UPS Monitoring and Control Software

Step 5 Start the web browser and enter http://IP address:the value of the struts.httpPort/shutdown/ inthe address box.

----End

7.8.6 What Do I Do When the Login Port of the NetShutdownInstalled in the SUSE or Solaris OS Has Been Occupied?

Question

What do I do when the login port of the NetShutdown installed in the SUSE or Solaris OS hasbeen occupied?

Answer

When the NetShutdown login port is occupied, you can solve the problem by changing the portnumber.

Step 1 Run the following commands to access the /opt/Netshutdown/WebRoot_Shutdown/WEB-INF/classes directory:

# cd /opt/Netshutdown/WebRoot_Shutdown/WEB-INF/classes

NOTE

/opt/Netshutdown is the installation directory for NetShutdown. Replace it as required.

Step 2 Open the struts.properties file.

# vi struts.properties

Step 3 Change the values of the following parameters in the struts.properties file.struts.httpPort=8011struts.httpsPort=8445

1. Move the cursor to the parameter value to be changed.2. Press x to delete the parameter value.3. Press i and then enter an available port number.4. Press Esc.

5. Enter :wq! and press Enter.

Step 4 Restart the NetShutdown service. For detailed operations, see 7.1 Starting or StoppingNetShutdown Services.

Step 5 Start the web browser and enter http://IP address:the value of the struts.httpPort/shutdown/ inthe address box.

----End

7.8.7 How to Use WinSCP to Transfer Files?SFTP transfer improves the security of file transfer. WinSCP is a dedicated file transfer tool thatsupports both SFTP transfer and resumable download. You are advised to use WinSCP to transferfiles.

NetShutdownUser Manual 7 Basic Features

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

28

Page 32: Huawei Net Shutdown UPS Monitoring and Control Software

Prerequisitesl You have obtained the IP address of the destination server.l The communication between the PC and the destination server is normal.l You have obtained the file to be uploaded to the destination server and have saved the file

to the PC.l You have obtained the user password of the destination server.l You have logged to http://support.huawei.com, downloaded the WinSCP.zip file based

on the navigation path Software Center > Controlled Tool (Mini-tool Software) > CoreNetwork Product Line > Wireless-OSS > iManger M2000-II > Public Tools, anddecompress the file on the PC.

Procedure

Step 1 Double-click WinSCP.exe to start the tool.

Step 2 On the WinSCP Login page, enter the target server IP address in Host name, set Portnumber to 22 and File protocol to SFTP, and click Login. Figure 7-5 shows the WinSCP loginpage.

Figure 7-5 WinSCP Login

NOTE

If you use WinSCP to connect to a Linux server the first time, the system will ask you to add host key.Click Yes.

Step 3 In the displayed dialog box, enter the user name of the target server, and click OK. If the messageYou are trying to access a restricted zone. Only Authorized Users allowed. is displayed,click Continue.

NetShutdownUser Manual 7 Basic Features

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

29

Page 33: Huawei Net Shutdown UPS Monitoring and Control Software

Step 4 In the displayed dialog box, enter the password for the target server user, and click OK.

NOTE

If a dialog box is displayed asking you to confirm the login, enter Yes, and click OK.

Step 5 After you log in to the WinSCP, a page is displayed. The left pane on the page displays the localdirectory, and the right pane displays the target directory for you to select.

Step 6 In the left pane, select the desired software file from the local file list, and press F5. On thedisplayed page for transferring files, click Copy to upload the file.

----End

NetShutdownUser Manual 7 Basic Features

Issue 01 (2013-06-13) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.

30