    Carter Ground FuelingHydrant Pit Valve Model 60554

    VFP Fuelling | Tel: +27 11 392 5633 | Email: [email protected] | Website: www.vfp.co.za

  • 7/30/2019 Hydr Valve 60554

    2/7

    2 EATON Aerospace Group TF100-80B January 2011

    Eatons Carter brand Model60554 hydrant pit valve is afamily of valves that includeslanyard, air or dual air/lanyard

    operated pilot valves, with thelatter available with a defuelingoption.

    The latest Model 60554hydrant pit valves meet allthe requirements of the 3rdedition of API/IP bulletin 1584,including the new breakawayand strength requirements.

    The basic hydrant pit valveconsists of three basic parts,lower valve assembly, uppervalve assembly (or API outletadapter) and either the

    standard pilot valve or oneof three patented pilot valveactuators (Model 64230,Model 64231 and Model64280), available as optionX. The lower valve assemblycontains an isolation valvewhich will allow the removaland servicing of the uppervalve assembly and the pilotvalve assembly while the pitvalve is still installed. (Seeservice manual SM60554for proper instructions). Theupper portion of all versions

    of Model 60554 are nowfurnished with a replaceablepart that contains the interfacewith the hydrant coupler. Thisminimizes replacement partsexpense and allows for easyreplacement of the outletwearing surfaces.

    An option is also available tobring the valve into compliancewith IP standards by addingthe appropriate 6 inch inletflange adapter. The outletconforms to the API bulletin1584 standard.

    Model 60554 hydrant pit valveis designed to minimize thepropagation of surge pressureshocks into the upstreampiping system during closureof the valve.

    Features

    Standard aluminum two-piece upper half standard,replaceable API outletadapter of stainless steelper API bulletin 1584.Ductile iron and stainlessuppers with replaceableoutlet optional.

    Standard inlet flange mateswith 4 inch 150 lb. ANSIflange

    Optional inlet flangemates with 6 inch 300 lb.ANSI flange, making valveconform to the IP standard

    Closing time is 2-5 seconds

    New pilotless valve (optionX) reduces maintenancecosts, lanyard, air or dual air/lanyard operated pilot valveavailable (for small or largepit applications)

    Servicing valve, standard,provides means to removethe upper valve assemblyand pilot valve assemblywith the unit still installed

    Dual pilot adds truedeadman backup to coupler,same as air operated

    pilot. Hydrant valve isautomatically closed atthe end of the refuelingoperation. Lanyard operationcan also be used with optionX valves.

    All seals are fieldreplaceable

    Large pressure equalizingvalve in the outlet isstandard

    Defueling capability optionalwith any air or dual air/lanyard operated pilot

    Stone guard optional with 6inch inlet flange option

    Ductile iron epoxy coated forcorrosion protection

    Main piston well guided tominimize piston seal wear

    10 or 20-mesh screen

    options available

    Model Descriptions

    There are seven basic valvesto which various modificationsmay be added by option lettersas shown below. The six basicmodel numbers are as follows:

    Model 60554D Lanyardoperated pilot valve formanual on/off control. Valveallows flow in the fuelingdirection only.

    Model 60554E Air

    operated pilot valve fordeadman control. Valveallows flow in the fuelingdirection only.

    Model 60554F Dual airand lanyard operated pilotvalve for deadman controland manual on/off control foruse in small pits only (12 or13 inch dia.). Uni-directionalonly, unless combined withoption J.

    Model 60554J Airoperated pilot valve fordeadman control with defuelcontrol to allow flow of fuelin either fueling or defuelingdirection

    Model 60554U Dual airand lanyard operated pilotvalve for deadman controland manual on/off control foruse in standard pits (18 inchor larger). Uni-directionalonly, unless combined withoption J.

    Model 60554-3D Sameas Model 60554D exceptmaterial of outer housing

    is ductile iron per ASTMA395 (special order only).The upper and lower valveassemblies are fastenedtogether with 15 metric

    threaded screws instead ofthe normal 8-UNF threadedscrews (replaced Model60554-2D). Two piece upper

    half not available on thisunit.

    Model 60554X Valve withthe major operating part ofthe pilot valve contained ona quick disconnect actuatorassembly located on thehydrant servicer hose. Canbe used as air/fuel pressureoperation (with Model 64230actuator assembly) or withlanyard backup (with Model64231 actuator assembly).Actuator assemblies orderedseparately. Includes ductileiron inlet housing, two-piecealuminum upper housingwith replaceable stainlesssteel outlet, dust cap & highcapacity pressure equalizingvalve.

    Design Concepts

    U.S. Pat. No.

    7,762,274

    Model 64231Pilot Valve Actuatorwith lanyard override

    Model 64230Pilot Valve Actuator

    Model 64280

    Pilot Valve Actuator

    VFP Fuelling | Tel: +27 11 392 5633 | Email: [email protected] | Website: www.vfp.co.za

  • 7/30/2019 Hydr Valve 60554

    3/7

    EATON Aerospace Group TF100-80B January 2011

    Installation Information

    It is critical that the matingcoupler (shown at right) beconnected correctly and the pitlid be able to close completely.The hydrant valves installation

    depth depends upon the brandof pit used. The thickness ofthe pit lid should be checkedto be sure that it will clear thehydrant valve before settingthe pit. The dimensions notedherein were correct for pitsmade in the United States atthe time of printing. Eaton cannot be responsible for changesin the pits. The dimensions,shown are for reference only.

    Technical Information

    Working Pressure 300 psi(20.7 bar)

    Closing Time 2 to 5 secon

    Overshoot 60.0 gals (225liters) maximum at 1200 USgpm (4500 l/min.)

    Pilot valve air pressure requirfor options E, F, J, U or X 6psi min. (4.2 bar)

    Mates Eatons Carter brandcoupler Models 60600, 60600-60700-1, 64702, 64800, 648064802, 64804, 64900, 6490164902, 61525 and all other Astyle couplers

    Dimensional Specifications

    The drawing (right) providesenvelope dimensions forinstallation purposes only.They are not intended forinspection purposes.

    Technical Data

    Dimensions are shown in inches

    (millimeters)

    VFP Fuelling | Tel: +27 11 392 5633 | Email: [email protected] | Website: www.vfp.co.za

  • 7/30/2019 Hydr Valve 60554

    4/7

    4 EATON Aerospace Group TF100-80B January 2011

    Flow Characteristics

    The graphs on this page depict

    typical pressure drop versus

    flow characteristics of the 60554

    series hydrant pit valves. (Option

    X does not alter the pressure drop

    characteristics of the 60554).

    Curve 1 Model 60554BDGH (IPhydrant) or 60554BFGH,20-mesh screen & 61525coupler

    Curve 2 Model 60554BD, (BE), (BU),20-mesh screen & 61525

    Curve 3 Model 60554BJ, 20-meshscreen & 61525, fuelingdirection

    Curve 4 Model 60554BJ, 20-meshscreen & 61525, defuelingdirection

    Curve 5 Model 60554D, (E), (U), noscreen & 61525

    Curve 6 Model 60554E (D), (U), no

    screen & 60600HCurve 7 Model 60554E (D), (F), no

    screen & 60700K

    Curve 8 Model 60554E (D), (U), noscreen & 60600K

    VFP Fuelling | Tel: +27 11 392 5633 | Email: [email protected] | Website: www.vfp.co.za

  • 7/30/2019 Hydr Valve 60554

    5/7

    EATON Aerospace Group TF100-80B January 2011

    Figure AValve Open

    Figure BValve Closed

    Valve Operation

    Figure A reflects a lanyardoperated pilot valve shown inthe open position. Figure Breflects an air operated pilot in aclosed position. The operation ofthe hydrant valve, whether thepilot is lanyard or air operated,is identical. The only differencesare in the operating mechanismthat supplies the power to openand close the pilot valve. In theair operated pilot, the closinglanyard and opening latching

    mechanisms are replaced withan air operated piston as canbe seen in the cutaway on theprevious page. The dual air/lanyard operated pilot valve hasthe same normal air operatedpilot valve function with amanual (lanyard) over-ride of theair supply. (Option X works thesame as that shown in figure Bwith the air/fuel operated pistonbeing placed on the hose fromthe servicer.)

    Servicing Valve Closed/Pilot Valve Open or Closed

    The closing of the servicingvalve has the same affect asclosing the pilot valve. That is,the flow passage from the pistonchamber to the downstreamside of the piston is blocked. Thepiston chamber pressure beginsto equalize to the inlet pressure(P1) through the check valve.

    The piston area is greater thanthe effective seal area, hencethe unbalance of forces causedby the equal pressure, plus thespring, will cause the valve tostay closed.

    Pilot Valve Open/Servicing Valve Open

    The open pilot valve allowsthe continuous passagewayfrom the main piston chamberand from the closing controlorifice. The piston chamber isvented through an openingcontrol orifice and the openservicing valve to a point in thelower valve half. The pressure(P2) at this point is less thanthe inlet pressure (P1). Thepiston chamber pressure isalso maintained at P2 causingan unbalance of forces on thepiston. The inlet pressure forceis greater than the combinedpiston pressure force plus thespring force hence the valvewill open to allow flow. This isassuming that the outlet adapterpoppet in the upper valve halfhas been opened by a coupler.

    The pilot poppet is maintained inthe open position by one of twomethods:

    Lanyard operated pilot The pilot is opened bythe pull of the T handlelocated on the top of the

    pilot valve. When it is pulledupward, the spring loadedlatch attached to the lanyardpivots to lock the pilot intothe open position.

    Air operated pilot/dual air-lanyard pilot air pressureapplied to the pilot pistonwill maintain the pilot inthe open position until thepressure has been depleted(by release of deadman).

    Pilot Valve Closed/Servicing Valve Open

    Pulling the lanyard, or depletingthe air supplied to theirrespective pilots, will allowthe spring loaded pilot poppetto close. This action blocksoff the venting of the pistonchamber to the lower pressurearea downstream. The pistonchamber begins to equalize tothe inlet pressure (P1) throughthe check valve.

    The piston area is greater than

    the effective seal area, hencethe unbalance of forces causedby the equal pressure plus thespring will cause the piston tobegin to close. As the pistonmoves toward the closedposition, the piston chambervolume increases and must befilled through the two in seriesorifices. The primary orifice is

    considerably larger than thesecondary (slot). During theinitial and majority of the traveof the piston, the primaryorifice is fully exposed to theinlet pressure, hence the rateof closure is controlled by thisorifice.

    When the piston moves farenough closed to cover theprimary orifice, the secondary(smaller) orifice begins to con

    the closure rate. Hence thevalve begins to close relativelyrapidly and then slows downas it nears its closed position.The relative size and locationsof these two orifices allowsthe valve to close to provide aminimum of overshoot and yelimit the surge pressure shocon closing, and still maintaina closure rate in accordancewith applicable internationalspecifications.

    On Model 60554J withdefueling option, the pilot valvis manually held closed by the

    thumb screw to allow defuelinflow.

    The dual pilot valve optionsF or U perform under normalsituations the same as optionThe lanyard operation is only femergency situations where tair supply is not released by thdeadman valve.

    VFP Fuelling | Tel: +27 11 392 5633 | Email: [email protected] | Website: www.vfp.co.za

  • 7/30/2019 Hydr Valve 60554

    6/7

    6 EATON Aerospace Group TF100-80B January 2011

    Illustrated Options

    VFP Fuelling | Tel: +27 11 392 5633 | Email: [email protected] | Website: www.vfp.co.za

  • 7/30/2019 Hydr Valve 60554

    7/7

    EATON Aerospace Group TF100-80B January 2011

    Option letters may be combinedwith the basic units, exceptas noted, to customize thevalve to fit specific installationrequirements. Note basicmodels referenced on page 2,

    Model Descriptions section.

    Option Description Option Description

    A Adds 10-mesh screen between upper and lowerhalves of the unit (81557-10)

    M Adds dry break (with bleed) to option E, F, J or U airconnection (not available on option X)

    B Adds 20-mesh screen between upper and lowerhalves of the unit (81557-20)

    N Adds adapter kit for installing un it into 12 or 13 inchAvery Hardoll pits with 3 inch ANSI mounting flangeCan not be used with options G, H, K or L.

    C Adds six-position product selection (44290) P Adds 4 inch spool piece to convert inlet flange to mawith 6 inch 300-lb ASA raised face flange (47199).Resultant valve height is 16 inches (special order on60554-2D & 3D).

    G Adds spool piece to convert inlet flange to matewith 6 inch 300-lb. ANSI flange to meet IP standard(44364) (special order on 60554-2D & 3D)

    Q Changes upper half housing (adapter) to one pieceductile iron (special order - not available on Model60554-3D)

    H Adds 4-mesh stone guard to inlet. Available onlywith option G above (43578).

    R Changes upper hal f housing (adapter) to two-pieceductile iron/stainless steel (not available on Model60554-3D special order)

    K Adds adapter kit to D, E or F options only, to mateAvery Hardoll 12 inch pits. Can not be used withoption U.

    S Changes upper hal f housing (adapter) to 316 stainlessteel (43214-4) (special order)

    L Adds adapter kit to D, E or F options only, to mateAvery Hardoll 13 inch pits. Can not be used withoption U.

    T Adds fusible plug to air port to either E, F, J or Uoptions only (not available on option X)

    Example: 60554BDGH IP standard unit with 6 inch inlet, manually operated pilot valve, stone guard and 20-mesh screen

    Ordering Data

    Superseding Data

    Since the late 1960s,

    Eatons Carter brand hasdesigned and manufactureda series of hydrant valves.Several of these valves areno longer manufacturedand spare part support hasbeen discontinued. Thelist of hydrant valve partnumbers (right) provides thesuperseding data to allowone to specify and procurethe latest units of the series.Use this list to obtain theappropriate current modelnumber (60554 or 61654) and

    then refer to the appropriatetable of options for eitherModel 60554 or 61654 hydrantvalves to complete the partnumber. (For Model 61654options, see catalog sheetTF100-86A).

    Model Description Superseded by - Comments

    60550 4x4 inch API adapter with manual butterfly isolation

    valve at inlet

    No longer supported with spare parts. Replace with

    appropriate Model 60554 hydrant valve.

    60551 4x4 inch API outlet adapter with dual flapper,lanyard operated inlet valve

    No longer supported with spare parts. Replace withappropriate Model 60554 hydrant valve.

    60552 Same as Model 60551 except added interlockto close hydrant should coupler be inadvertentlyremoved

    No longer supported with spare parts. Replace withappropriate Model 60554 hydrant valve.

    60553 4x4 inch API outlet adapter with air operated inletvalve utilizing dual externally mounted cylinders

    No longer supported with spare parts. Replace withappropriate Model 60554 hydrant valve.

    60554-1 Air operated Model 60554 type hydrant valve except6x4 inch with outer housings and poppet materialper ASTM A536-72, grade 80-55-06

    Spare parts common to standard Model 60554. Fornew orders use Model 61654EK (part number changeonly).

    60554SPECIAL/ 60554-2D

    Same as Model 60554 series except material forouter housings per ASTM A395

    60555 Aluminum inlet to mate 6 inch 300 lb. flange x 4 inchAPI outlet, in accordance with IP standard

    Spare parts support continues for all parts except inlehousing. Inlet housing can be replaced with a kit ofcurrent ductile iron parts.