Hydrologie(elias jamhour)

Embed Size (px)

Citation preview

  • 8/14/2019 Hydrologie(elias jamhour)

    1/10

    Lebanese University.

    Faculty of Engineering.

    Department-1-

    Hydro-thermal energy.Heat transfer system.

    By: Elias Jamhour

    1/31/2010

  • 8/14/2019 Hydrologie(elias jamhour)

    2/10

    Overview on Traditional systems:

    Traditional water-source heat pumps use a fossil-fuel-fired boiler as a heat source

    during the winter and an evaporative cooling tower to reject heat during the

    summer. This is sometimes referred to as a boiler/tower system; The water loop

    temperature is maintained between 60 and 90F. When the loop temperature falls

    below 60F, the boiler adds heat, and when the loop temperature exceeds 90F, the

    cooling tower rejects heat.

    How the Geothermal system works?

    The earth has the ability to absorb and store heat energy. To use that stored energy,

    heat is extracted from the earth through a liquid medium and is pumped to the heat

    pump heat exchanger. There, the heat is used to heat buildings and homes.

  • 8/14/2019 Hydrologie(elias jamhour)

    3/10

    And reversely, in summer the process is reversed and indoor heat is extracted from

    the building and transferred to the earth through the liquid.

    Advantage of the system:

    A GHP heat pump system is a water-loop system where the boiler and cooling

    tower have been replaced with a buried earth heat exchanger (ground loops).

    Heat is absorbed from or rejected to the ground, and the external energy needed to

    operate a boiler or cooling tower is eliminated.

    we should note that: heat pumps must work harder to move heat up a steeper

    temperature gradient, and if the gradient is too steep a heat pump will not work at

    all.

  • 8/14/2019 Hydrologie(elias jamhour)

    4/10

    As we know, during the times of the year when heating and cooling are required,

    ground temperatures are nearer room temperature than outdoor air temperatures.

    Thus during the summer cooling season, the ground is cooler than the air, and the

    ground loop is able to condense the refrigerant at lower temperatures which meansthat less compressor power is needed to pressurize the refrigerant vapor.

    Ground-source(geothermal)heat pump in cooling mode.

    Likewise during the winter heating season, the ground is warmer than the air, and

    the ground loop is able to evaporate the refrigerant at higher temperatures, whichagain means that less compressor power is needed, since the pressure drop through

    the expansion valve can be less and still vaporize the refrigerant liquid.

  • 8/14/2019 Hydrologie(elias jamhour)

    5/10

    Ground-source (geothermal) heat pump in heating mode.

    As a conclusion, geothermal heat pumps are 3.5 5 times as efficient as the most

    efficient fossil fuel furnace. Instead of burning a combustible fuel to make heat,

    they simply move heat that already exists. By doing so, they provide 3.5 5 units

    of energy for every unit used to power the heat-pump system.

  • 8/14/2019 Hydrologie(elias jamhour)

    6/10

    Principal parts of the system:

    The water/refrigerant heat exchanger, refrigerant/air heat exchanger, and all

    refrigerant loop components are contained in a single enclosure, which can be

    mounted horizontally (above a dropped ceiling), vertically (in a utility closet), or as

    a console (against the wall or under a window). Maintenance experience with GHP

    systems suggests that horizontal units should NOT be mounted above the dropped

    ceiling in classrooms, because this makes access difficult, adding considerable

    time (and labor cost) to routine servicing of the heat pump units. Vertical and

    console units are easier to service and should be used if possible. When horizontal

    units must be used, they should be mounted above hallways adjacent to the rooms

    they serve.

  • 8/14/2019 Hydrologie(elias jamhour)

    7/10

    Horizontal GHP unit installation above Vertical GHP unit installation in a mechanical utility

    a dropped ceiling.

  • 8/14/2019 Hydrologie(elias jamhour)

    8/10

    Console GHP unit.

    GHP refrigerant fluids

    The refrigerant working fluid used in geothermal heat pumps is R22, which also is

    the most popular refrigerant for packaged air conditioners and air-source heat

    pumps and which was made as a substitute for R12. It can produce more cooling

    capacity from the same size compressor with no significant power penalty.

    Because R-22 contains some chlorine, it is classified as an HCFC (hydro-chloro-

    fluoro-carbon).

    The ozone depletion potential of R22 is only 5.5% compared with the depletion

    potential of R11 and R12 (CFC-11 and CFC-12), which are the two refrigerants

    thought to be most responsible for atmospheric ozone layer depletion.

    A long-term substitute for R22 is R410a, a chlorine-free blend of two HFC

    refrigerants (R32 and R125), which is safe and easy to use, with no ozone-depletion potential. R410a has up to 6% greater refrigeration capacity than R22

    and its Energy Efficiency Ratio (EER) is 5-6% higher, offering improved

    performance in addition to its environmental benefits.

    But its operating pressures are nearly 50% higher than R22, requiring a redesign of

    the compressor as well as other components. In addition, there are compatibility

  • 8/14/2019 Hydrologie(elias jamhour)

    9/10

    issues with the lubricants, cleaners and other fluids used in the heat pump

    manufacturing process.

    Ground loups:

    An open-loop system that consumes water from a well.

    A closed-loop system continuously circulates its heat transferring solution in

    pressurized pipe.The term closed-loop is used to describe a geothermal heat

    pump system that uses a continuous loop of special buried plastic pipe as a heat

    exchanger. The pipe is connected to the indoor heat pump to form a sealed,

    underground loop through which water or an anti-freeze solution is circulated.

    Several forms of closed loops are figuring in this picture:

    Trenches are normally four to six feet deep [0.5 1.8 meters]. One of the

    advantages of a horizontal loop system is being able to lay the trenches according

    to the shape of the land. As a rule of thumb, 125-300 feet of trench are required

    per ton of heat pump capacity [11-27 meters per kW of capacity].

  • 8/14/2019 Hydrologie(elias jamhour)

    10/10

    1 to 6 pipes pre trench may be used, depending upon the optimal design for the

    yard. More pipes per trench shorten the total amount of trench required.

    Closed loop systems can also be vertical. Holes are bored to about 150 300 feet

    per ton of heat pump capacity [13 27 meters per kW of capacity]. U-shaped

    loops of pipe are inserted in the holes. The holes are then back-filled with a sealing

    solution (grouting material).

    Piping material:

    Closed-loop systems should only be installed using the appropriate high-density

    polyethylene pipe. Properly installed these pipes will last over 50 years. They are

    inert to chemicals normally found in soil and have good heat conducting

    properties. PVC pipe should not be used under any circumstances.

    The only acceptable method to connect pipe sections is by thermal fusion. Pipe

    connections are heated and fused together to form a joint stronger than the original

    pipe. Mechanical joining of underground pipe for an earth loop is never an

    accepted practice. The use of barbed fittings, clamps and glued joints is certain to

    result in loop failure due to leaks.

    References:

    http://www.geo4va.vt.edu/A3/A3.htm

    http://www.geo4va.vt.edu/A3/A3.htmhttp://www.geo4va.vt.edu/A3/A3.htm