10
AG-Präsentation ENERCON Energy for the World Proposal for IEC 61400-25 LN Wind Power Plant Control and Monitoring System Werner Bohlen Frank Fischer • Control of Wind Power Plants • Introduction of LN WCMS • Modification of LN WTUR

IEC Hamburg 260303 Hambu… · AG-Präsentation ENERCON Energy for the World Control of Wind Power Plants • WPP Active Power Management (installed ratedpower ofthe WTGS of a WPP

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: IEC Hamburg 260303 Hambu… · AG-Präsentation ENERCON Energy for the World Control of Wind Power Plants • WPP Active Power Management (installed ratedpower ofthe WTGS of a WPP

AG-Präsentation

ENERCON

Energy for the World

Proposal for IEC 61400-25LN Wind Power Plant Control and Monitoring System

Werner Bohlen Frank Fischer

• Control of Wind Power Plants

• Introduction of LN WCMS

• Modification of LN WTUR

Page 2: IEC Hamburg 260303 Hambu… · AG-Präsentation ENERCON Energy for the World Control of Wind Power Plants • WPP Active Power Management (installed ratedpower ofthe WTGS of a WPP

AG-Präsentation

ENERCON

Energy for the World

Control of Wind Power Plants

Page 3: IEC Hamburg 260303 Hambu… · AG-Präsentation ENERCON Energy for the World Control of Wind Power Plants • WPP Active Power Management (installed ratedpower ofthe WTGS of a WPP

AG-Präsentation

ENERCON

Energy for the World

Control of Wind Power Plants

• WPP Active Power Management (installed rated power of the WTGS of a WPP extends grid capacity)

• WPP Active Power Management (control of active power initiated by the utility due to grid status, e.g. e.on Erzeugungsmanagement)

• WPP Reactive Power Management (control of reactive power initiated by the utility due to grid status, e.g. e.on extended grid connection rules)

• WPP Reactive Power Management (voltage control)• WPP Controlling Power Range Management

Page 4: IEC Hamburg 260303 Hambu… · AG-Präsentation ENERCON Energy for the World Control of Wind Power Plants • WPP Active Power Management (installed ratedpower ofthe WTGS of a WPP

AG-Präsentation

ENERCON

Energy for the World

Control of Wind Power Plants

WCMS Feature:

• Controller using setpoint values (from utility) and actual values (from measurement unit).

Page 5: IEC Hamburg 260303 Hambu… · AG-Präsentation ENERCON Energy for the World Control of Wind Power Plants • WPP Active Power Management (installed ratedpower ofthe WTGS of a WPP

AG-Präsentation

ENERCON

Energy for the World

Control of Wind Power Plants

WCMS Feature:

• Process Data Interface (to the utility) collecting data from the WTGs of theWPP (resp. from subordinate WPPs) to generate values for available activeand reactive power of the WPP for controlling power range management.

Page 6: IEC Hamburg 260303 Hambu… · AG-Präsentation ENERCON Energy for the World Control of Wind Power Plants • WPP Active Power Management (installed ratedpower ofthe WTGS of a WPP

AG-Präsentation

ENERCON

Energy for the World

Control of Wind Power Plants

WCMS Feature:

• Process Data Interface (to the utility) for active power gradients.

Page 7: IEC Hamburg 260303 Hambu… · AG-Präsentation ENERCON Energy for the World Control of Wind Power Plants • WPP Active Power Management (installed ratedpower ofthe WTGS of a WPP

AG-Präsentation

ENERCON

Energy for the World

Introduction of LN WCMSMeasured Values / Processed Values

Available active power of WPP at PCC

Available reactive power generating of WPP at PCC

Available reactive power absorbing of WPP at PCC

Available power factor generating of WPP at PCC

Available power factor absorbing of WPP at PCC

Controls

Start command to the WPP

Stop command to the WPP

Settings

Demand value of active power generation of WPP at PCC

Demand value of reactive power generation of WPP at PCC

Demand value of power factor at PCC

Maximum allowable active power gradient after start of WPP

Minimum allowable active power gradient after change of demand value of active power generation ofWPP

Page 8: IEC Hamburg 260303 Hambu… · AG-Präsentation ENERCON Energy for the World Control of Wind Power Plants • WPP Active Power Management (installed ratedpower ofthe WTGS of a WPP

AG-Präsentation

ENERCON

Energy for the World

Modification of LN WTUR

• Generating values for available active and reactive power of the WTGS (controlling power range management of the WPP).

• Two data sets containing setpoint data for P, Q, cos ϕ

(1) Default values for WTGS operation when the communication is interrupted resp. the WTGS is part of the WPP, but not subjected to WPP control

(2) Demand values for WTGS operation when the WTGS is subjected to WPP control

Page 9: IEC Hamburg 260303 Hambu… · AG-Präsentation ENERCON Energy for the World Control of Wind Power Plants • WPP Active Power Management (installed ratedpower ofthe WTGS of a WPP

AG-Präsentation

ENERCON

Energy for the World

Modification of LN WTUR

Measured Values / Processed Values

TotPwrAt

TotPwrRt

Available active power of WTGS* NEW

Available reactive power generating of WTGS* NEW

Available reactive power absorbing of WTGS* NEW

Available power factor generating of WTGS* NEW

Available power factor absorbing of WTGS* NEW

* computed value depending on wind conditions etc.

Page 10: IEC Hamburg 260303 Hambu… · AG-Präsentation ENERCON Energy for the World Control of Wind Power Plants • WPP Active Power Management (installed ratedpower ofthe WTGS of a WPP

AG-Präsentation

ENERCON

Energy for the World

Modification of LN WTURControls

...

WCMS activated NEW

Settings

DmdPwrAt Demand value of active power generation of WTGS – Default value

DmdPwrRt Demand value of reactive power generation of WTGS – Default value

DmdPF Demand value of power factor of WTGS – Default value

MaxGdPwrAt Maximum allowable active power gradient after start of WTGS – Default value

Minimum allowable active power gradient after change of maximum value of active power generation ofWTGS – Default value NEW

Demand value of active power generation of WTGS – WCMS value NEW

Demand value of reactive power generation of WTGS – WCMS value NEW

Demand value of power factor of WTGS – WCMS value NEW

Maximum allowable active power gradient after start of WTGS – WCMS value NEW

Minimum allowable active power gradient after change of maximum value of active power generation ofWTGS – WCMS value NEW