Relay Type Setting Setting Range Setting RemarksFunction Items Steps
InstantaneousPickup Value Block, 1~80[A] 1.0[A]
Operating Time 40~500[ms] 10[ms]OCR Pickup Value Block, 0.5~16[A] 0.1[A]
(50/51)Timed Operating Time
0.1~50.0[Tm] 0.1[Tm] NI,VI,EI0.1~50.0[s] 0.1[s] DT
Curves NI/VI/EI/DT
InstantaneousPickup Value Block, 0.5~40[A] 0.1[A]
Operating Time 40~500[ms] 10[ms]OCGR Pickup Value Block, 0.2~5[A] 0.1[A]
(50/51N)Timed Operating Time
0.1~50.0[Tm] 0.1[Tm] NI,VI,EI0.1~50.0[s] 0.1[s] DT
Curves NI/VI/EI/DTReference Angle 0~90[deg] 1[deg]Operation Angle 60~90[deg] 1[deg]
Pickup Value Block, 1~80[A] 1.0[A]DOCR Instantaneous Operating Time 40~500[ms] 10[ms](67P) Pickup Value Block, 0.5~16[A] 0.1[A]
Operating Time0.1~50.0[Tm] 0.1[Tm] NI,VI,EI
Timed 0.1~50.0[s] 0.1[s] DTCurves NI/VI/EI/DT
Pickup Value Block, 100~150[%] 1[%]OVR
Timed Operating Time0.1~50.0[Tm] 0.1[Tm] NI
(59) 0.1~50.0[s] 0.1[s] DTCurves NI/DT
Pickup Value Block, 10~100[%] 1[%]UVR
Timed Operating Time 0.1~50.0[Tm] 0.1[Tm] NI
(27) 0.1~50.0[s] 0.1[s] DTCurves NI/DT
NSOVRTimed
Pickup Value Block, 5~100[%] 1[%](47N) Operating Time 0.1~50.0[s] 0.1[s] DT
Instantaneous Pickup Value Block, 20~100[%] 1[%]
OVGRPickup Value Block, 5~40[%] 1[%]
(64G) Timed Operating Time 0.1~50.0[Tm] 0.1[Tm] NI0.1~50.0[s] 0.1[s] DT
Curves NI/DTReference Angle 0~45[deg] 1[deg]Operation Angle 60~90[deg] 1[deg]
Instantaneous Pickup Value Block, 0.5~40[A] 0.1[A]DGR Operating Time 40~500[ms] 10[ms](67N) Pickup Value Block, 0.2~5[A] 0.1[A]
TimedOperating Time
0.1~50.0[Tm] 0.1[Tm] NI,VI,EI0.1~50.0[s] 0.1[s] DT
Curves NI/VI/EI/DTReference Angle 0~60[deg] 1[deg]
SGROperation Angle 60~90[deg] 1[deg]
(67G)Pickup Current Block, 1~10[mA] 0.1[mA]
Timed Pickup Voltage 5~40[%] 1[%]Operating Time 0.1~50.0[s] 0.1[s] DT
Dynamic Characteristics
PROMET 4300-F
Relay Type Setting Setting Range Setting RemarksFunction Items Steps
InstantaneousPickup Value Block, 1~80[A] 1.0[A]
Operating Time 40~500[ms] 10[ms]OCR Pickup Value Block, 0.5~16[A] 0.1[A]
(50/51)Timed Operating Time
0.1~50.0[Tm] 0.1[Tm] NI,VI,EI0.1~50.0[s] 0.1[s] DT
Curves NI/VI/EI/DT
InstantaneousPickup Value Block, 0.5~40[A] 0.1[A]
Operating Time 40~500[ms] 10[ms]OCGR Pickup Value Block, 0.2~5[A] 0.1[A]
(50/51N)Timed Operating Time
0.1~50.0[Tm] 0.1[Tm] NI,VI,EI0.1~50.0[s] 0.1[s] DT
Curves NI/VI/EI/DTUpper Limit 0.2~5[A] 0.1[A]
UCRLower Limit 0.2~5[A] 0.1[A]
(37)Timed Operating Time 0.1~10.0[s] 0.1[s] DT
Instantaneous Pickup Value Block, 0.5~12[A] 0.1[A] NSOCR
Operating Time 0.1~50.0[Tm] 0.1[Tm] NI,VI,EI
(46) Timed 0.1~50.0[s] 0.1[s] DTCurves NI/VI/EI/DT
THRTimed Pickup Value Block, 0.5~10[A] 0.1[A]
(49)Heating Factor 0.5~60[min] 0.5[min]Cooling Factor 0.0~60[min] 0.5[min]
Pickup Value Block, 1~50.0[A] 0.2[A]
51LR Timed Operating Time0.1~50.0[Tm] 0.1[Tm] NI,VI,EI, DT0.1~50.0[s] 0.1[s] DT
Curves NI/VI/EI/LI/DTPickup Value Block, 1~80.0[A] 0.5[A]
48ST TimedOperating Time 0.1~50.0[s] 0.1[s] DT
LockedRotate Amp.
1.0~10.0[pu] 0.1[pu]
Pickup Value Block, 10~100[%] 1[%]UVR
Timed Operating Time0.1~50.0[Tm] 0.1[Tm] NI
(27) 0.1~50.0[s] 0.1[s] DTCurves NI/DT
NSOVRTimed
Pickup Value Block, 5~100[%] 1[%](47N) Operating Time 0.1~50.0[s] 0.1[s] DT
Reference Angle 0~45[deg] 1[deg] Operation Angle 60~90[deg] 1[deg]
InstantaneousPickup Value Block, 0.5~40[A] 0.1[A]
DGR Operating Time 40~500[ms] 10[ms](67N) Pickup Value Block, 0.2~5[A] 0.1[A]
Timed Operating Time 0.1~50.0[Tm] 0.1[Tm] NI,VI,EI0.1~50.0[s] 0.1[s] DT
Curves NI/VI/EI/DTReference Angle 0~60[deg] 1[deg]
SGROperation Angle 60~90[deg] 1[deg]
(67G)Pickup Current Block, 1~10[mA] 0.1[mA]
Timed Pickup Voltage 5~40[%] 1[%]Operating Time 0.1~50.0[s] 0.1[s] DT
PROMET 4300-M
Neopis IED (Intelligent Electronic Device)Neopis IED (Intelligent Electronic Device)
IED (Intelligent Electronic Device) 5
Relay Type Setting Setting Range Setting RemarksFunction Items Steps
Instan- Pickup Value Block, 5~100[A] 0.5[A] OP time: within 40 mstaneous Operating Time 40~500[ms] 10[ms]
Pickup Value Block, 0.5~10[A] 0.05[A]
RDRSlope 1 5~100[%] 1[%]
(87T)Timed Slope 2 OFF, 50~200[%] 1[%]
Knee Point 5~100[A] 0.5[A]Operating Time 0.05~10[s] 0.01[s] DT
Restrain 2th Block % OFF, 5~100[%] 1[%]Harmonic 5th Block % OFF, 5~100[%] 1[%]Instan- Pickup Value Block, 1~80[A] 1.0[A]taneous Operating Time 40 ~500[ms] 10[ms]
OCR(1) Pickup Value Block, 0.5~16[A] 0.1[A](50/51)
Timed Operating Time0.1~50.0[Tm] 0.1[Tm] NI,VI,EI0.1~50.0[s] 0.1[s] DT
Curves NI/VI/EI/DTInstan- Pickup Value Block, 0.5~40[A] 0.1[A]taneous Operating Time 40~500[ms] 10[ms]
OCGR(1) Pickup Value Block,0.2~5[A] 0.1[A](50/51N)
Timed Operating Time0.1~50.0[Tm] 0.1[Tm] NI,VI,EI0.1~50.0[s] 0.1[s] DT
Curves NI/VI/EI/DTInstan- Pickup Value Block, 1~80[A] 1.0[A]taneous Operating Time 40~500[ms] 10[ms]
OCR(2) Pickup Value Block, 0.5~16[A] 0.1[A](50/51)
Timed Operating Time0.1~50.0[Tm] 0.1[Tm] NI,VI,EI0.1~50.0[s] 0.1[s] DT
Curves NI/VI/EI/DTInstan- Pickup Value Block, 0.5~40[A] 0.1[A]taneous Operating Time 40~500[ms] 10[ms]
OCGR(2) Pickup Value Block, 0.2~5[A] 0.1[A](50/51N)
Timed Operating Time0.1~50.0[Tm] 0.1[Tm] NI,VI,EI0.1~50.0[s] 0.1[s] DT
Curves NI/VI/EI/DT
Instantaneous Pickup Value Block, 20 ~100[%] 1[%] OP time: within 50 ms
OVGRPickup Value Block, 5~40[%] 1[%]
(64G) Timed Operating Time0.1~50.0[Tm] 0.1[Tm] NI0.1~50.0[s] 0.1[s] DT
Curves NI/DTInstan- Pickup Value Block, 1~80[A] 1.0[A]taneous Operating Time 40~500[mS] 10[ms]
OCR(3) Pickup Value Block, 0.5~16[A] 0.1[A](50/51)
Timed Operating Time0.1~50.0[Tm] 0.1[Tm] NI,VI,EI0.1~50.0[s] 0.1[s] DT
Curves NI/VI/EI/DTInstan- Pickup Value Block, 0.5~40[A] 0.1[A]taneous Operating Time 40~500[ms] 10[ms]
OCGR(3) Pickup Value Block,0.2~5[A] 0.1[A](50/51N)
Timed Operating Time0.1~50.0[Tm] 0.1[Tm] NI,VI,EI0.1~50.0[s] 0.1[s] DT
Curves NI/VI/EI/DT
PROMET 4300-T
** 3-Wired Tr.
PROMET43006
●Overcurrent Normal Inverse (NI) ●Overcurrent Very Inverse (VI)
●Overcurrent Extremely Inverse (EI) ●Overvoltage Normal inverse (NI)
OCR (50/51),OCGR (50N/51N), NSOCR (46)
t : Operating TimeI : Input CurrentIs : Setting CurrentTm : Time Lever
t 0.14( )I Is/ 0.02
1Tm10
OCR (50/51),OCGR (50N/51N), NSOCR (46)
t : Operating TimeI : Input CurrentIs : Setting CurrentTm : Time Lever
t 13.5( )I Is/ 1
Tm10
OCR (50/51),OCGR (50N/51N), NSOCR (46), Locked Rotator (51LR)
t : Operating TimeI : Input CurrentIs : Setting CurrentTm : Time Lever
t 80( )I Is/ 2
1Tm10
OVR (59)
t : Operating TimeV : Input VoltageVs : Setting VoltageTm: Time Lever
t 10.5( )VVs/ 2
1Tm10
Intelligent Electronic Device
PROMET4300 Characteristic curve
IED (Intelligent Electronic Device) 7
Neopis IED (Intelligent Electronic Device)
●Undervoltage Normal Inverse (NI) ●Gound-Overvoltage Normal Inverse (NI)
[V/Vs] [V/Vs]
●Directional Relays
UVR (27)
t : Operating TimeV : Input VoltageVs : Setting VoltageTm: Time Lever
t 8( )VVs/ 2
1Tm10
OVGR (64)
t : Operating TimeV : Input VoltageVs : Setting VoltageTm: Time Lever
t 11.5( )VVs/ 2
1Tm10
SGR (67G), DGR (67N) I1 : Primary Current,
I2 : Secondary CurrentI3 : Tertiary Current
RDR (87T)
Id=I differential = I1 - I2 (Vector sum.)
Ir=I restraint = I1 + I2 (Scalar sum.)
I differential
I restraintSLOPE=
[2-Wired Tr.]
Id=I differential = I1 - I2- I3 (Vector sum.)
Ir=I restraint = I1 + I2 + I3 (Scalar sum.)
I differential
I restraintSLOPE=
[3-Wired Tr.]
●Differential curve
PROMET43008
Item Present Error Rates Remarks
3-Phase Voltages 0 - 999.99[kV] ± 0.5%Phase-to-Neutral Voltages &
Phase-to-Phase Voltages
V0 0 - 999.99[V] ± 1.0%
3-Phase Currents 0 - 999.99[kA] ± 0.5%
In 0 - 999.99[A] ± 0.1%
Active Power 0 - 999.99[MW] ± 0.5%
Reactive Power 0 - 999.99[MVAR] ± 0.5%
Active Energy 0 - 9,999.99[MWH] ± 1.0% Import/Export Active Energy
Reactive Energy 0 - 9,999.99[MVARH] ± 1.0% Import/Export Reactive Energy
Power Factor Lead/Lag 0 - 100[%] ± 0.5% Instantaneous Power Factor
& Average Power Factor
Frequency 45.0 - 65.0[Hz] ± 1.0Hz
THD 0 ‐ 100.0[%] -
Harmonics 0 ‐ 100.0[%] - 2 ~ 23th Harmonics V, I
Vca Ic
Vbc
Vablalb
Intelligent Electronic Device
PROMET4300 Features
Metering
IED (Intelligent Electronic Device) 9
Neopis IED (Intelligent Electronic Device)
Digital Input�Photo-isolated Binary Input
�CB On/Off Status Monitoring
�Programmable Contact input : 16 Port
�Input Circuits
-AC 220V or DC 250V
-AC 110V or DC 125V
Control Output�Trip, CB On/Off Control: 3Port
-20 A 250 VAC
�Programmable Contact output
-8 Port
-5 A 250VAC
�Application
-Relay Operation Alarm
-Sequence Output by DI Contacts
-Remote Control Output
Analog Input (Option)�AI: 4 port
�Isolated Circuit: Surge Protected
�Analog Inputs like Temperature, Pressure
Analog Output (Option)�AO: 4 port
�Analog Outputs like V,I and Power
Fault Record
Operating Record�Total Events of IED Operation
�Sequence Of Event (1mS Resolution)
�Max 1024 Events Backup
�Event Items- CB ON/OFF Control - Setting Value Updates- Local/Remote Change- IED Restart- Self-Diagnosis Result- Binary Input Change- Fault Occurrence - Fault Reset- etc
Item Data Max. Storage
Operated Relays
Fault Fault Elements and Fault Phaseup to 1024
Information Fault I,V values and Phase
with Time Tag
OscillographicOperated Relays with Time Tag
Up to 6 waves
Fault Wave3-Phase Voltages, V0, 3-Phase
160 Cycle per recordCurrents and I0 Waves
Supervise and Control
Load Profile
Records
Item Electrical Values Storage
Peak Demand I, V, Power, Energy, Power Factor, Frequency Time Tagged Peak Values
Demand Power, Energy, Power Factor, Frequency 90 Days Demand Datas
You can check and control many display and setting usinggraphic LCD, LED and function keys. Additionally, the Windows-based PROMET4300 software allows complete access to relaysetting and fault information.
PROMET430010
Intelligent Electronic Device
PROMET4300
�Desktop, Laptop
�RS232C Port
�115,200 bps
�Measure Value Check
�Check DI Status
�Auto Update Values
�Communication Transaction View
�Relay Characteristic Curve Check
�Relay Operating Time Check
�Check Operated Relay
�Operating Time Check Bar
�Fault Wave Analysis
�Setting Relay Parameters
�Default Setting Value Button
�Setting Range Check Function
Features
User Interface
RS232C (115200bps)
IED (Intelligent Electronic Device) 11
Neopis IED (Intelligent Electronic Device)
Wiring
PROMET4300-F, M
http : //www.neopis.com NEOPIS CO., LTD2011. 09
4F, Neo Bd, Jeonpa-ro 24beon-gil, Anyang7-Dong, Manan-Ku, Anyang-City, Kyonggi-Do, KoreaTel +82-31-445-2100 Fax +82-31-445-2103
Dimension
Ordering
Top view
Front view
Rear view
Side view
Panel cut
PROMET4300PROMET4300F : INCOMMING FEEDER
Protection
M : MOTOR Protection
T : Transformer Protection