Installationsanleitung
ComAp, a.s. Kundratka 2359/17, 180 00 Praha 8, Czech RepublicTel: +420 246 012 111, Fax: +266 31 66 47E-mail: [email protected], www.comap.cz
Inteli New Technology
Modularer Controller für Gen-Sets
IG-NT, IG-NTC, IG-NT-BB, IG-NTC-BB, IS-NT, IS-NTC-BB, IM-NT, IM-NT-BB,
IM-NTC-BB
Softwareversion IGS-NT-3.0 und IM-NT-3.0, August 2014
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
2/141
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
3/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 3
InteliSys NT-Controller ................................................................................................................... 37 6.1.2
InteliVision 5..................................................................................................................... 38
6.1.3 InteliVision 8..................................................................................................................... 39 6.1 Verkabelung des Displays ........................................................................................................ 40
6.1.1 Verkabelung des IG-Displays .......................................................................................... 40 6.1.2
Verkabelung des IS-Displays ........................................................................................... 41
6.1.3
Verkabelung von InteliVision 5 ........................................................................................ 43 6.1.4 Verkabelung von InteliVision 8 ........................................................................................ 43
7 Übersicht über Klemmen, Jumper und E/A ............................................................................... 47 7.1 IG-NT GC ................................................................................................................................. 47
7.1.1
Schaltbilder ...................................................................................................................... 47
7.1.2 Klemmen, Eingänge und Ausgänge ................................................................................ 48 7.2 IG-NTC GC ............................................................................................................................... 49
7.2.1 Schaltbilder ...................................................................................................................... 49 7.2.2 Klemmen, Eingänge und Ausgänge ................................................................................ 50
7.3 IS-NT-BB .................................................................................................................................. 51 7.3.1
Schaltbilder ...................................................................................................................... 51
7.3.2 Klemmen, Eingänge und Ausgänge ................................................................................ 53 7.4 IG-NT-BB .................................................................................................................................. 54
7.4.1
Schaltbilder ...................................................................................................................... 54
7.4.2 Klemmen, Eingänge und Ausgänge ................................................................................ 55
7.5 IG-NTC-BB ............................................................................................................................... 56 7.5.1 Schaltbilder ...................................................................................................................... 56 7.5.2
Klemmen, Eingänge und Ausgänge ................................................................................ 57
7.6 IS-NTC-BB ................................................................................................................................ 58 7.6.1 Schaltbilder ...................................................................................................................... 58 7.6.2
Klemmen, Eingänge und Ausgänge ................................................................................ 59
7.7
IM-NT ........................................................................................................................................ 60
7.7.1 Schaltbilder ...................................................................................................................... 60 7.7.2 Klemmen, Eingänge und Ausgänge ................................................................................ 61
7.8
IM-NT-BB .................................................................................................................................. 62
7.8.1 Schaltbilder ...................................................................................................................... 62 7.8.2
Klemmen, Eingänge und Ausgänge ................................................................................ 63
7.9
IM-NTC-BB ............................................................................................................................... 64
7.9.1 Schaltbilder ...................................................................................................................... 64 7.10 Allgemeine Jumper-Einstellungen ............................................................................................ 65
7.10.1 Analogeingänge und -ausgänge ...................................................................................... 65 7.10.2
Drehzahlreglerausgang ................................................................................................... 66
8
Verkabelung für Messgeräte und Stromversorgung ................................................................ 67
8.1
General ..................................................................................................................................... 67
8.2 Erdung ...................................................................................................................................... 67 8.3 Stromversorgung ...................................................................................................................... 67 8.4 Sicherung der Versorgungsspannung ...................................................................................... 68 8.5 Magnetische Drehzahlaufnahme .............................................................................................. 69
8.6
Spannungs- und Stromeingänge .............................................................................................. 70 8.6.1
Verkabelung für Messgeräte ............................................................................................ 70 8.6.2 Geteilte Spannungsmessung........................................................................................... 72 8.6.3 Messung der Netzleistung und des Leistungsfaktors in IGS (z.B. SPtM-Anwendung) ... 72 8.6.4
Erdschluss-Schutz (z.B. MINT-Anwendung) ................................................................... 72
9
Empfohlene Verkabelung ............................................................................................................ 74
9.1
SPtM-Anwendung..................................................................................................................... 74
9.2 SPI-Anwendung ........................................................................................................................ 75 9.3 MINT-Anwendung..................................................................................................................... 76 9.4
Einphasige Anwendungen ........................................................................................................ 77
9.4.1 Empfohlene Verkabelung ................................................................................................ 77 9.5 InteliMains – MCB-Anwendung ................................................................................................ 78
9.5.1
Controller BaseBox .......................................................................................................... 78
9.5.2
Controller mit eingebautem Display ................................................................................. 79
9.6 InteliMains – MGCB-Anwendung ............................................................................................. 80
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
4/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 4
9.6.1 Controller BaseBox .......................................................................................................... 80 9.6.2
Controller mit eingebautem Display ................................................................................. 81
9.7 InteliMains – BTB-Anwendung ................................................................................................. 82 9.7.1 Controller BaseBox .......................................................................................................... 82 9.7.2 Controller mit eingebautem Display ................................................................................. 83
9.8
InteliMains – FDR-Anwendung ................................................................................................. 84
9.8.1
Controller BaseBox .......................................................................................................... 84 9.8.2 Controller mit eingebautem Display ................................................................................. 85
9.9
Verkabelung der Binäreingänge ............................................................................................... 86
9.10 Verkabelung der Binärausgänge .............................................................................................. 86 9.10.1 Controller ohne High-Side/Low-Side-Schaltung .............................................................. 86 9.10.2 Controller mit High-Side/Low-Side-Schaltung ................................................................. 87
9.11
Beispiele für die Verkabelung von Binäreingängen und -ausgängen ...................................... 89
9.11.1 Verkabelung von Binärausgängen bei I-RB16 ................................................................ 89 9.11.2 Verkabelung für Binäreingänge und -ausgänge .............................................................. 89
9.12 Binär -E/A bei IS-BIN16/8 .......................................................................................................... 90 9.12.1 Binäreingänge auf IST-BIN16/8 ....................................................................................... 90 9.12.2 Binärausgänge auf IST-BIN16/8 ...................................................................................... 91
9.13
Schutzfunktionen für Binärausgänge ....................................................................................... 91
9.14
Verkabelung von Analogeingängen und -ausgängen .............................................................. 92 9.15 Analogeingänge an IS-AIN8 ..................................................................................................... 94
10 Verbindung externer Module ................................................................................................. 96 10.1 Schutz gegen Verlust der Kommunikation ............................................................................... 96 10.2
IS-BIN16/8 und IS-AIN8 ........................................................................................................... 96
10.2.1 Adresseinstellung für IS-AIN8, IS-BIN8/16 ...................................................................... 97 10.2.2 Überprüfung der Softwareversion für IS-AIN8, IS-BIN8/16 ............................................. 97 10.2.3
Beispiel für Verkabelung .................................................................................................. 97
10.3
IGS-PTM und IGL-RA15........................................................................................................... 98
10.3.1 Beispiel für Verkabelung .................................................................................................. 98 10.4 Verbindung der Motorsteuereinheit (ECU) an CAN1 bei anderen verbundenen Modulen ...... 99
10.4.1
I-CB Verkabelung und Konfiguration ............................................................................... 99
11
Kommunikationsverbindungen .......................................................................................... 100 11.1
Verfügbare Kommunikationsanschlüsse ................................................................................ 100 11.2 Mögliche Anschlüsse pro Port ................................................................................................ 101
12 CAN-Bus ................................................................................................................................ 102 12.1 LED-Anzeige von CAN-Bus Tx, Rx ........................................................................................ 102 12.2 Verkabelung der Anschlüsse CAN und RS485 ...................................................................... 102
12.2.1 Beispiele für Verkabelung .............................................................................................. 103
13
Dongle-Installation ............................................................................................................... 105
14 Sensoren ............................................................................................................................... 106 14.1
Sensorfehlererkennung (FLS) ................................................................................................ 106
14.2 Standardsensoren .................................................................................................................. 106
15
Allgemeine Einstellungen für Drehzahlregler und AVR ................................................... 108
15.1 Anpassung der Synchronisierung/Lastregelung .................................................................... 108 15.1.1 Eigenschaften des Drehzahlregler-Ausgangs ............................................................... 108 15.1.2
Anpassung des Synchronisators ................................................................................... 108
15.1.3 Anpassung der Lastregelung ......................................................................................... 109 15.1.4 Aktive und reaktive Energie-Terminologie ..................................................................... 109
15.2
Anpassung der Volt/LF-Regelung .......................................................................................... 110
15.2.1
Verbindung des Ausgangs IG-AVRi .............................................................................. 110
15.2.2 Anpassung der Spannungsregelung ............................................................................. 111 15.2.3 Anpassung der LF-Regelung ......................................................................................... 112
16 Schnittstellenliste für Drehzahlregler ................................................................................. 113 16.1 Schnittstelle für Elektromotoren ............................................................................................. 113
16.1.1
Kommunikationsbrücke ................................................................................................. 113
16.2 Schnittstelle für Drehzahlregler .............................................................................................. 113 16.2.1 Ausgangsspannungsgrenzen für Drehzahlregler .......................................................... 113
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
5/141
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
6/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 6
Internetseite: HTTP://WWW.COMAP.CZ, E-Mail: [email protected]
DOKUMENTVERLAUF
REVISIONSNUMMER ENTSPRECHENDE SW-VERSION DATUM
1 3.0 1.5.2013
2 (r1) 3.0 13.8.2013
1.1 Erklärung der Anmerkungen und Hinweise
H INWEIS :
Diese Art Anmerkung gibt detaillierte Angaben, welche dem Benutzer die Installation bzw.Konfiguration erleichtern.
HINWEIS: Diese Art Anmerkung macht den Leser auf einen Hinweis oder ein verwandtes Thema aufmerksam.
VORSICHT! Diese Art Anmerkung bezieht sich auf einen Vorgang, eine Anpassung etc., welche(r) zu einemSchaden oder einer Fehlfunktion führen kann, wenn diese Maßnahme nicht korrekt durchgeführt wird,wobei dies möglicherweise nicht auf den ersten Blick erkennbar ist.
WARNUNG!
Diese Art Anmerkung weist auf Dinge, Vorgänge, Anpassungen etc. hin, die eine besondere hohe Aufmerksamkeit erfordern, da es sonst zu Verletzungen oder sogar Lebensgefahr führen kann.
T YP TEXT-ANMERKUNG
Parameter im Text Parametergruppe:Parametername
Werte im Text Wertegruppe:Wertname
Logische binäre/analoge Eingangs-/Ausgangsfunktionen im
Text LOGISCHE
FUNKTION
http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/http://www.comap.cz/
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
7/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 7
Option zur Einstellung der Parameter OPTION
1.2 Symbole
In diesem Handbuch verwendete Symbole:
Symbol fürErdungspunkt
Symbol fürWechselspannung(AC)
Symbol fürGleichspannung(DC)
1.3 Konformitätserklärung
Die folgende Maschine entspricht den angemessenen, grundlegenden Sicherheits-und Gesundheitsanforderungen der EG-Niederspannungsrichtlinie Nr. 73/23 / EECund der Richtlinie über elektromagnetische Verträglichkeit 89/336 / EEC, basierend aufdem Design und Typ, mit dem sie von uns in Umlauf gebracht wird.
1.4 Anmerkungen zur Revision
In dieser Revision sind alle Änderungen gelb markiert.
Die überarbeitete Version enthält neue Informationen zur AVR-Verbindung auf Seite 117.
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
8/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 8
2 Verfügbare ergänzendeDokumentation
PDF-Dateien Beschreibung
IGS-NT-SPTM-3.0 Reference Guide.pdf
Allgemeine Beschreibung der SPtM- Anwendungen für InteliGenNT und InteliSysNT.Beschreibung der Motor- undGeneratorsteuerung, Leistungssteuerung imNetzparallelbetrieb. Liste aller Parameter,Werte, logischen Binär e Ein- und Ausgänge.
IGS-NT-SPI-3.0 Reference Guide.pdf
Allgemeine Beschreibung der SPI- Anwendungen für InteliGenNT und InteliSysNT.
Beschreibung der Motor- undGeneratorsteuerung, Leistungssteuerung imNetzparallelbetrieb, Liste aller Parameter,Werte, logischen Binär e Ein und -Ausgänge.
IGS-NT-MINT-3.0 Reference Guide.pdf
Allgemeine Beschreibung der MINT- Anwendungen für InteliGenNT und InteliSysNT.Beschreibung der Motor- undGeneratorsteuerung, Energieverwaltung, Listealler Parameter, Werte, logischenBinäreingänge und -ausgänge.
IGS-NT-Combi-3.0 Reference Guide.pdf
Allgemeine Beschreibung der Kombi- Anwendungen für InteliGenNT und InteliSysNT.
Beschreibung der Motor- undGeneratorsteuerung im SPTM-, SPI- und MINT-Modus, Energieverwaltung, Liste allerParameter, Werte, logischen Binäreingänge und-ausgänge.
IGS-NT-COX-3.0 Reference Guide.pdf
Allgemeine Beschreibung der COX- Anwendungen für InteliGenNT und InteliSysNT.Beschreibung der Motor- undGeneratorsteuerung, Energieverwaltung, Listealler Parameter, Werte, logischenBinäreingänge und -ausgänge.
IGS-NT Application Guide 05-2013.pdf
Anwendungen von InteliGen , InteliSys undInteliMainsNT, Beispiele für Verkabelung,Beschreibung der SPS-Funktionen, virtuelle undgemeinsame Peripheriegeräte.
IGS-NT Operator Guide 05-2013.pdfBedienungsanleitung für alle Hardwarevariantenvon InteliGen
NT und InteliSys
NT, InteliVision 5
und InteliVision 8.
IGS-NT Installation Guide 05-2013.pdf
Genaue Beschreibung der Installation sowietechnische Informationen über InteliGenNT,InteliSys
NT und InteliMains
NT und relevantes
Zubehör.
IGS-NT Communication Guide 05-2013.pdf
Genaue Beschreibung der Datenkommunikation
für InteliGenNT, InteliSysNT und InteliMainsNT undrelevantes Zubehör.
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
9/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 9
IGS-NT Troubleshooting Guide 05-2013.pdfHinweise zur Behebung der häufigsten Fehlerbei den Controllern InteliGen
NT und InteliSys
NT.
Inkl. Liste der Alarmmeldungen.
IGS-NT & ID-DCU Accessory Modules 05-2013.pdf
Genaue Beschreibung der Erweiterungsmoduleder Produktfamilie IGS
NT, technische Daten,
Informationen zur Installation der Module, Anschluss an den Controller und korrekteKonfiguration.
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
10/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 10
3 Allgemeine Richtlinien
3.1 Sicherheitshinweise
WICHTIGE SICHERHEITSHINWEISE
DIESE ANLEITUNG AUFBEWAHREN - Diese Anleitung enthält wichtige Hinweise für dieController-Produktserie IGS-NT, die bei der Installation und Wartung von Inteli NT-Controllern für Gen-Sets zu befolgen sind.
Diese Anweisungen sind für die Verwendung durch das mit der Konstruktion von Schalttafelnfür Gen-Sets und das mit der Installation, Bedienung und Wartung des Gensets betrautePersonal gedacht.
WARNUNG
Fernsteuerung
Der Controller kann ferngesteuert werden. Wenn Wartungsarbeiten an dem Generator vorgenommenwerden, ist sicherzustellen, dass der Motor nicht gestartet werden kann.
Gehen Sie dazu folgendermaßen vor:
Trennen Sie die Fernbedienung von dem RS232-Anschluss oder anderenKommunikationsverbindungen.Trennen Sie den Eingang REMOTE START/STOP
oder
Trennen Sie die Ausgänge STARTER, GCB CLOSE/OPEN und MCB CLOSE/OPEN.
Beachten Sie, dass durch eine unqualifizierten Manipulation des Systems die Last von derVersorgung getrennt werden kann.
VORSICHT! Der Controller enthält zahlreiche konfigurierbare Parameter (Sollwerte), weswegen es unmöglich ist,alle möglichen Anwendungen zu beschreiben. Die Funktionen des Controllers können sich je nachSoftwareversion unterscheiden. Diese Anleitung beschreibt ausschließlich das Produkt, und es wirdnicht gewährleistet, dass es für die von Ihnen gewünschte Anwendungsart passend ist.
!!! ACHTUNG !!!
Gefährliche Spannung
Die Klemmen für Spannungs- und Strommessung dürfen auf keinen Fall berührt werden.
Verbinden Sie die Erdungsklemmen ordnungsgemäß.
Trennen Sie die Stromwandler-Klemme (CT) des Controllers unter keinen Umständen.
Konfiguration der Parameter
Alle Parameter sind werksseitig auf ihre typischen Werte eingestellt. Doch die Parameter der Gruppe"Basic settings (Grundeinstellungen)" !!müssen!! vor dem ersten Start des Gen-Sets angepasstwerden.
!!! DURCH FALSCHE EINSTELLUNG DER GRUNDLEGENDEN PARAMETER KANN DASGEN-SET ZERSTÖRT WERDEN !!!
Die folgenden Anweisungen sind nur für qualifiziertes Personal gedacht.Um Verletzungen zuvermeiden, führen Sie keine Aktionen aus, die nicht in diesem Benutzerhandbuchangegebenen sind !!!
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
11/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 11
WARNUNG - SEHR WICHTIG !!!
Beachten Sie, dass sich der Zustand der Binärausgänge während und nach derNeuprogrammierung der Software ändern kann. Stellen Sie sicher, dass die angemesseneKonfiguration und die korrekten Parametereinstellungen im Controller eingestellt werden,
bevor Sie das Gerät erneut in Betrieb nehmen.
Jedes Mal, wenn Sie folgende Klemmen des Controllers trennen möchten:
Messung der Netzspannung und / oder
Binärausgang für MCB-Steuerung und / oder
MCB-Feedback
Beachten Sie, dass der MCB ausgeschaltet ist und das Gen-Sets gestartet werden kann !!!
Schalten Sie den Controller in den Modus MAN und trennen Sie die Binärausgänge STARTER undFUEL oder betätigen Sie die Taste EMERGENCY STOP (NOTHALT), um einen plötzlichenautomatischen Start des Gen-Setss und ein Schließen des GCB während der Arbeiten oder
Wartungstätigkeiten an dem Gen-Sets oder der Schalttafel zu verhindern.
3.2 Erforderl iche und opt io nale Modu le
3.2.1 Inteli New Technology Controller
Controller Beschreibung Standard / optional
IG-NTIG-NTCIM-NT
Zentraleinheiten des Controllers mit integriertemDisplay Standard
IG-NT-BBIG-NTC-BBIS-NT-BBIS-NTC-BBIM-NT-BBIM-NTC-BB
Zentraleinheit des Controllers ohne integriertesDisplay
Standard
3.2.2 Zubehör
Zubehör undModule
Beschreibung Standard /optional
IG-Display Zusätzliches Display für IG-NT/NTC/EE/EEC, IM-NT OptionalIS-Display Zusätzliches Display für IS-NT-BB OptionalInteliVision 5 Zusätzliches Farbdisplay für IS-NT-BB, IG-
NT/NTC/EE/EEC, IM-NT, IS-NTC-BB, IG-NT-BB, IG-NTC-BB
Optional
InteliVision 8 Zusätzliches Farbdisplay für IS-NT-BB, IG-NT/NTC/EE/EEC, IM-NT, IS-NTC-BB, IG-NT-BB, IG-NTC-BB
Optional
IG-AVRi AVR-Schnittstelle des Controllers Optional
IG-AVRi-TRANS/LVIG-AVRi-TRANS/100
Spannungswandler für die Versorgung des AVRi-Moduls
Optional
AT LINK-KABEL1,8m
Datenkabel RS232 (InteliMonitor, GenConfig)(nicht im Lieferumfang des Controllers enthalten)
Optional
IS-AIN8 Externe analoge Eingangseinheit OptionalIS-BIN16/8 Externe binäre E/A-Einheit Optional
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
12/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 12
I-LB+ Ersetzt IG-MU und I-LB (RS232/RS485-Datentransport wird auf 57600 Bit/s erhöht);Kommunikation mehrerer Controller mit einemlokalen PC.
Optional
IG-IB Internetbrücke OptionalI-CB/CAT-Benzin
I-CB/CAT-DieselI-CB/MTUI-CB/MTU-SIAM4000I-CB/DeutzTEMe
Inteli - Kommunikationsbrücke:Schnittstelleneinheit für manche Motoren ohneMotorsteuergerät (ECU) (ohne J1939)
Optional
IGL-RA15 Remote-Signalgeber Optional
IGS-PTM Externe analoge, binäre Ein- bzw. Ausgangseinheit OptionalI-AOUT8 8-fache Analogausgangseinheit Optional
IG-MTU Spannungswandler für die galvanische trennung derSpannungsmessung für Netz- undGeneratorstappnung
Optional
IG-MTU-2-1 Spannungswandler mit Spannungsverhältnis 2:1 fürdie galvanische trennung der Spannungsmessungfür Netz- und Generatorspannung
Optional
H INWEIS :
Die Zentraleinheit des Controllers enthält die komplette Hardware für alle Anwendungen. Die Anzahlder Ein- und Ausgänge kann durch die Zusatzmodule AIN8, IS -BIN16/8, IGS-PTM, IGL-RA15, I-
AOUT8 erweitert werden.
3.2.3 Überblick über Dongle
Dongle Funktion
Keine Für eine einfache Parallelschaltung zum Netz (SPtM) ist kein Dongle
erforderlich. Für die Hauptantriebsmaschine (MINT in SPM- Anwendung) ist kein Dongle erforderlich.IGS-NT-LSM+PMS Dongle für mehrere MINT-Anwendungen mit Lastausgleich,
Blindleistungsverteilung und Energieverwaltungsfunktion. DieserDongle sollte für SUS und GeCon MINT-Anwendungen mit derVersionen SUS-1.3 und GeCon-3.0 verwendet werden (Schifffahrtund terrestrisch)
IGS-NT-SUS-LSM+PMS
Obsolet. Dongle für mehrere Anwendungen SUS MINT mitLastausgleich, Blindleistungsverteilung undEnergieverwaltungsfunktion
IGS-NT-SUS-PCM Obsolet. Dongle für SUS mit einfacher Parallelschaltung zum Netz.Ab Version SUS-1.3 nicht mehr erforderlich
IGS-NT-GeCon-
LSM+PMS
Obsolet. Dongle für mehrere GeCon MINT-Anwendungen mit
Lastausgleich, Blindleistungsverteilung undEnergieverwaltungsfunktion
IGS-NT-SUS-PCM Obsolet. Dongle für GeCon mit einfacher Parallelschaltung zumNetz. Ab Version GeCon-3.0 nicht mehr erforderlich (Schifffahrtund terrestrisch)
Siehe Kapitel Dongle-Installation für detaillierte Informationen über den Einbau des Dongle in denController.
3.2.4 Verfügbare PC-Software
Name FunktionGenConfig Konfigurationstool (offline) für die Familien IGS-NT und IM-NT.
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
13/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 13
Name Funktion
InteliMonitor Überwachungstool (online) für die Familien IGS-NT und IM-NT.
WinScope Grafisches Überwachungs- und Aufnahmetool.
IGS-Log PC-Protokoll-Software für die IGS-NT-Produktfamilie.
IBConfig Konfigurationstool für Internetbrücke.
Gm_setup Setup-Tool für GSM-Modem.
ICBEdit Konfigurationstool für I-CB.
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
14/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 14
4 Anmerkungen bezüglichAnwendungen in der Schifffahrt
Das IGS-NT System und seine Komponenten können für Steuerung, Überwachung und Schutz füreinzelne und mehrfache Generatoranwendungen verwendet werden, gemäß der Marine -Typzulassungsverordnung.
Der Controller muss entsprechend geprüft und zugelassen werden:
Für den Einsatz in Maschinenräumen und Kontrollräumen - Einbauklasse B.Gemäß EMV-Regeln für allgemeine Stromversorgungszonen.
4.1 Sicherheitsanforderungen
Zusätzliche, unabhängige Sicherheits- und Schutzvorrichtungen sind notwendig, um dieSicherheitsanforderungen sowie die Regeln und Vorschriften der Marine-Klassifikationsgesellschaftenzu erfüllen. Die Sensoren und Stromkreise, die für den Alarm der zweiten Stufe verwendet werden,müssen von jenen, die für den Alarm der ersten Stufe verwendet werden, unabhängig sein (LRRulefinder 2008 - V9.10).
HINWEIS: Der Projekt-Designer ist dafür verantwortlich, dass die Vorschriften bezüglich der Schifffahrt beachtetwerden, was die Verkabelung sowie die Konfiguration und Anpassung der Parameter für InteliGen-NToder InteliSys-NT betrifft.
Normalerweise ist es notwendig, zusätzliche, unabhängige Geräte für Nothalt, Überdrehzahlschutz,
niedrigen Öldruck und Überstromschutz zu verwenden.
Überwachungsgeräte für Ölnebel und Lagertemperaturmesser müssen bereitgestellt werden, wennder Einbau so vorgenommen wird, dass die automatische Abschaltung im Falle einer exzessivenVerringerung des Schmieröldrucks aufgehoben wird (oder für Motoren über 2250 kW). Die Aufhebungdieser Schutzfunktion muss unabhängig sein.
Erforderlichen Alarme und Schutzvorrichtungen für Hilfsmotoren.
Schmieröl-Eintrittstemperatur hoch
Schmieröl-Eintrittsdruck hoch
Kühlmittel/Austrittstemperatur hoch
Kühlmitteldruck oder -durchfluss niedrig
Abgastemperatur hoch
Die maximale Kabellänge für binäre (analoge) Ein- und Ausgänge darf höchstens 10 Meter betragen;ansonsten muss ein Trennrelais oder eine andere Schutzvorrichtung verwendet werden.
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
15/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 15
+ 2 4 V D C
0 V D C
B O 1
B O 2
B O 3
B O 4
B O 5
B O 6
B O 7
B O 8
B O 9
B O 1 0
B O 1 2
B O 1 3
B O 1 4
B O 1 5
B O 1 6
B O 1 1
+ P W R B O U T
+ P W R B O U T
B I 1
B I 2
B I 3
B I 4
B I 5
B I 6
B I 7
B I 8
B I 9
B I 1 0
B I 1 2
B I 1 3
B I 1 4
B I 1 5
B I 1 6
B I 1 1
+ -
IS-NT (IG-NT)
I-RB16 ( I-RB8 )
K17 K18
Max wire length < 10m
Max wire length < 10m
1 2 3
Bei längeren Kabeln muss die zusätzliche Schutzvorrichtung für Signaleingänge und
-ausgänge in der Nähe der Controllerklemmen angebracht werden. Die Schutzvorrichtungen sind auf Anfrage bei ComAp erhältlich.
IG-NT or IS-NT
Controller box shielding
BIN.INPBIN.OUT ANA.INP
0V SUPPLY AI COM
1 N 4 0 0 7
3 x
1 4 D K 3 9 0
3 3
M / 5 0
1 4 D K 2 2 0
1 4 D K 3 9 0
1 4
D K 3 9 0
22uH
P6KE12CA
ANA.OUT
AOUT COM
BIN.INP
BIN.OUT ANA.INP
ANA.OUT
AOUT COM
4.1.1 Stromversorgung
Um einen vollwertigen Überspannungsschutz ±2kV für die Versorgungsspannungsklemmen desControllers zu garantieren, muss eine externe Komponente (z.B. zwei DK4/35 U S14 K60 vonWeidmüller für DIN-Schiene) angeschlossen werden.
+24VB from battery
-24VB from battery
IG-NT or IS-NT controller
Controller box shielding
+24VB
0VB
Die Modul I-LBA (Niederspannungsadapter) wird verwendet, wenn ein
Versorgungsspannungseinbruch von bis zu 200ms erforderlich ist. Ein Spannungseinbruch von bis zu100ms ist für IG-NT- oder IS-NT-Controller akzeptabel.
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
16/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 16
IS-NT (IG-NT)
+ 2 4 V D C
0 V D C
- +Controller box shielding
4.2 Standardkonf igurat ion
VORSICHT! Verwenden Sie die standardmäßige IG-MINT-Marine-2.3.ant (oder höher) oder IS-MINT-Marine-2.3.ant (oder höher), um inkorrekte Systemeinstellungen und -konfigurationen zu vermeiden.
Die Standardkonfiguration kann mit der PC-Software GenConfig-2.3 (oder höher) angepasst werden.Bitte beachten Sie folgende Positionen, die in der standardmäßigen Konfigurationsdatei enthaltensind:
Die Funktion "Virtual Peripheries" ("Virtuelle Peripheriegeräte") darf nicht für Anwendungen inder Schifffahrt verwendet werden.
Der automatische Start des Generators nach Bestätigung des Alarms muss verhindert werden(Basic settings: FltResGoToMAN = ENABLED (AKTIVIERT)).
Die gemeinsamen Alarmkontakte mit Schnittstellen mit dem Maschinenalarmsystem müssenbei Auftreten eines neuen Alarms erneut ausgelöst werden (BO5 = Alarm blinkt).
4.2.1 Überbrückungsfunktion
Die Funktion “Sd override” (Überbrückungsfunktion für Abschaltung) ist in der Standardkonfigurationdem Binäreingang BI7 zugewiesen. Die aktivierte Überbrückungsfunktion ist durch " ! " auf demDisplay und am Binärausgang BO4 Common SdOvr gekennzeichnet.
Die standardmäßige Überüberbrückungsfunktion blockiert alle Schutzvorrichtungen, außerÜberdrehzahlschutz, Notabschaltung sowie alle als "SD Override" konfigurierte analoge oder binäreSchutzfunktionen.
H INWEIS :
Es wird empfohlen, die Bezeichnungen dieser Werte so abzuändern, dass sie mit den BuchstabenSDO beginnen oder enden – z.B. "WaterTemp SDO".
Verwenden Sie die integrierte SPS-Funktion, wenn eine unabhängige Übersteuerungsfunktionerforderlich ist, z.b. für Lagertemperaturen.
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
17/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 17
5 Geräte und Abmessungen
5.1 Control ler-Klemmen und Abm essungen
5.1.1 IG-NT, IG-NTC, IM-NT
170 (6,7")
185 (7,3")
1 2 3 ( 4 , 8
“ ) R
S 2 3 2
U S B
6 8
2 , 7
“
Cutout for IG-XX/IM-NT113 x 175 mm
4,4 x 6,9”
1 2 3 ( 4 , 8
“ )
1 1 0 ( 4 , 3
“ )
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
18/141
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
19/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 19
5.1.2.2 IS-NT mit InteliVision 8
5.1.3 IG-NT-BB (IG-NTC-BB, IS-NTC-BB)
R S 2 3 2
56.5223
1 1 0
R S 2 3 2
U S B
R J 4 5
68.5
1 4 2
1 6 6
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
20/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 20
5.1.3.1 IG-NT-BB mit InteliVision 5
R S 2 3 2
1 1 4
5.1.4 IM-NT
170 (6,7")
185 (7,3")
1
2 3 ( 4 , 8
“ )
R S 2 3 2
U S B
6 8
2 , 7
“
Cutout for IG-XX/IM-NT113 x 175 mm
4,4 x 6,9”
1 2 3 ( 4 , 8
“ )
1 1 0 ( 4 , 3
“ )
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
21/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 21
5.1.5 IM-NT-BB und IM-NTC-BB
R S 2 3 2
56.5223
1 1 0
R S 2 3
2
U S B
R J 4 5
68.5
1 4 2
1 6 6
IM-NTC-BB only
IM-NTC-BB only
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
22/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 22
5.2 Display-Klemm en und Abmessungen
5.2.1 IG-Display
170 (6,7")
185 (7,3")
Cutout for IG-DISPLAY113 x 175 mm
4,4 x 6,9”
1 2 3 ( 4 , 8
“ )
1 1 0 ( 4 , 3
“ )
5.2.2 IS-Display
3 0
1 , 2
“
1 7 6 ( 6 , 9
“ )
290 (114,2")
280 (11")
1 8 4 ( 7 2 , 4
4 “ )
Cutout for IS-DISPLAY
178 x 282
7,0 x 11,1”
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
23/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 23
5.2.3 InteliVision 5
5.2.4 InteliVision 8
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
24/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 24
5.3 Klemmen und Abmessungen für Peripheriemodule
5.3.1 IG-AVRi + IG-AVRi TRANS
A V R i -
A V R i +
O U T 1
O U T 2
A C 1
A C 2
O C O M
LB5
Primäre Klemmen
230-277 VAC / 400-480 VAC
Frequenz: 50 – 60 – 400Hz
0 - 18
43 (1,7”) 43 (1,7”)
3 6 ( 1 , 4
” )
0 - 230/277 - 400/480
IG-AVRiTRANS/LV
Sekundäre Klemmen
18 VAC
Die beiden Geräte können auf einer DIN-Schiene (35mm) montiert werden.
5.3.2 Inteli AIN8
Inteli AIN8 kann auf einer DIN-Schiene (35mm) montiert werden.
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
25/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 25
5.3.3 Inteli Ain8TC
Inteli AIN8TC kann auf einer DIN-Schiene (35mm) montiert werden.
5.3.4 Inteli IO8/8 (kann auf IO16/0 umgeschaltet werden)
Inteli IO8/8 kann auf einer DIN-Schiene (35mm) montiert werden.
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
26/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 26
5.3.5 IS-BIN16/8
45 (1,8")146 (5,7")
1 6 0 ( 6 , 3
" ) 40 (1,6")
25 (1,0")
I N 1 -
R P M +
I N 2
I N 1 +
R P M
-
IS-BIN16/8 kann auf einer DIN-Schiene (35mm) montiert werden.
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
27/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 27
5.3.6 IS-AIN8
46,4 (18,3")
40 (15,7")
25 (9,8")
70 (27,5")
146(57,5")
1 6 0 ( 6
3 " )
POWER8 - 36V DC
C O M
CAN1 H L
+
iS-AIN8
IS-AIN8 kann auf einer DIN-Schiene (35mm) montiert werden.
5.3.7 IGL RA15 Remote-Signalgeber
Remote (CAN-Bus, bis zu 200 m) 15 LED-Statusanzeiger. Das Gerät IGL-RA15 kann über CAN alsBinärausgangsgruppe mit den Adressen 1+2 oder 3+4 oder 5+6 oder 7+8 angeschlossen werden.
Für die Konfiguration von IGL-RA15 verwenden Sie "GenConfig -> Modules -> Available modules",wählen Sie das Modul IGL-RA15 und fügen Sie es durch Betätigen der Einfügetaste hinzu. GenConfigfügt die Binärausgänge für IGL-RA15 automatisch der Konfiguration hinzu.
Für weitere Informationen zur IGL-RA15 sehen Sie das Handbuch (IGL-RA15-2.0.pdf) und die Listeder neuen Funktionen (IGL-RA15-2.0-Neue Funktionen.pdf).
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
28/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 28
165 (6,5”)
3 8 ( 1 , 5
” )
4 0 ( 1 , 6
” )
~ 7 5 ( 3 , 0
” )
~ 3 5 ( 1 , 4
” )
180 (7,1”)
185 (7,3”)
1 0 6 ( 4 , 2
” )
44 (1,7”)
54 (2,1”)
~ 2 5 ( 1 , 0
” )
1 2 0 ( 4 , 7
” )
1 2 5 ( 4 , 9
” )
Cutout
for Remote Annunciator
167 x 108 mm(6,6 x 4,3)”
5.3.8 IGS-PTM
95 mm(3,7´´)
43 mm(1,7´´)
9 6 m m (
3 , 8
´ ´ )
COMPENSATION
G N D
POWER
8-36V DC
BINARY OUTPUTS
BINARY INPUTS ANALOG INPUTS
A I 4
B I 8
B I 7
B I 6
B I 5
B I 4
B I 3
B I 2
B I 1
0-20 mA ANALOG OUT
B O 8
B O 1
B O 2
B O 3
B O 4
B O 5
B O 6
B O 7
C A N
R x
T x
C A N
L
H
C O M
LB 4
A O -
A O +
iGS-PTM
IGS-PTM kann auf einer DIN-Schiene (35mm) montiert werden.
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
29/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 29
5.3.9 IG-IB Internetbrücke
95 mm(3,7´´)
43 mm(1,7´´)
9 6 m m (
3 , 8 ´ ´ )
H INWEIS :Weitere Informationen sind dem Inteli-Kommunikationshandbuch zu entnehmen.
Es wird empfohlen, die IG-IB Firmwareversion 2.0 zu verwenden.
IG-IB kann auf einer DIN-Schiene (35 mm) montiert werden.
5.3.10 Lokale Brücke I-LB+
I-LB+ ist das Nachfolgemodell von IG-MU und I-LB und für die Verwendung mit den Controllern IG/IS-NT und IM-NT gedacht.
Er verfügt über zusätzliche Datenanschlüsse und erlaubt höhereDatenübertragungsgeschwindigkeiten.
Die Geschwindigkeit einer direkten Verbindung bzw. Modemverbindung kann bis zu 57600 Bit/s (nur19200 Bit/s bei IG-MU) betragen.
95 mm(3,7´´)
43 mm(1,7´´)
9 6 m m (
3 , 8
´ ´ )
D1D2P1P2P3P4P5P6
P7 1 2 0
1 2 0 RxD
TxD
RxC
TxC
Tx
Rx
LED-Anzeiger:
TxC, RxC Zeigt an, dass Daten über CAN übertragen werden.
TxD, RxD Zeigt an, dass Daten über RS232 übertragen werden.Tx, Rx Zeigt an, dass Daten über USB übertragen werden.
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
30/141
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
31/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 31
I-RB16 kann auf einer DIN-Schiene (35 mm) montiert werden. Das Gerät besteht aus zwei Teilen(separate Leiterplatten). An jedem auf einer gemeinsamen Kunststoffbasis montierten Teil befindensich 8 Relais.
I-RB16 ist von der DIN-Schiene aus 60mm hoch.
16
X17
11 1 11 1 11
1 +
X18
11 1 11 1 11
R E 1
R E 2
R E 3
E R 4
R E 5
R E 6
R E 7
R E 8
R E 9
R E 1 0
R E 1 1
E R 1 2
R E 1 3
R E 1 4
R E 1 5
R E 1 6
X3 X1X2X6 X4X5X8 X7X11 X9X10X14 X12X13X16 X15
9 + 8
16 X18 9 +View B
X18
8 X17 1 +
View B
3 X1 1
X1 X2 X3 X4 X5 X6 X7 X8 X9 X10 X11 X12 X13 X14 X15 X16
View A
3 X2 1 3 X3 1 3 X4 1 3 X5 1 3 X6 1 3 X7 1 3 X8 1 3 X9 1 3 X10 1 3 X11 1 3 X12 1 3 X13 1 3 X14 1 3 X15 1 3 X16 1
View A
300
9 5
X17
H INWEIS :
I-RB besteht aus zwei verschiedenen Leiterplatten mit je 8 Relais. Es kann auch als I-RB8 bestelltwerden.
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
32/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 32
5.3.13 I-CR CAN-Repeater
Durch das I-CR-Modul kann die CAN-Bus-Leitung auf
CAN1-Erweiterungsmodule von bis zu 200 Meter ausgeweitet werden, bzw. auf
CAN2-Intercontroller auf über 200/900 Meter (im 32C/8C-Modus).Nähere Informationen zur Anwendung sind dem separaten Handbuch “CAN-Bus-Erweiterung” sowie
dem Kommunikationshandbuch für die Controller IGS und IM zu entnehmen.
95 mm(3,7´´)
43 mm(1,7´´)
9 6 m m (
3 , 8
´ ´ )
I-CR kann auf einer DIN-Schiene (35 mm) montiert werden.
5.3.14 I-AOUT8
5.3.14.1 Allgemeine Beschreibung
I- AOUT8 ist ein Erweiterungsmodul mit 8 Analogausgängen. Jeder einzelne Analogeingang kanndurch einen Jumper auf folgende Werte geschaltet werden.
0 bis 20 mA
0 - 10 VDC
PWM (Puls mit Modulation auf 1,2 kHz)
Das Modul I-AOUT8 ist an IGS-NT oder IM-NT über CAN1 (Peripheriegeräte) angeschlossen. Dieentsprechende Moduladresse 1 bis 4 (Standardeinstellung: 1) muss auf dem Modul (durch Jumper
von Adr.1 und Adr.2) und in der Controller-Konfiguration eingestellt werden. Ein Kommunikationsfehlerwird in der Alarmliste des Controllers und durch Binärausgänge angezeigt. Verwenden Sie die PC-Software "GenConfig", um den Controller zu konfigurieren.
Bis zu vier I-AOUT8-Geräte können an einen Controller angeschlossen werden.
I-AOUT8 kann auf einer DIN-Schiene (35 mm) montiert werden.
Auf CAN1 ist werksseitig ein 120 Ohm-Widerstandsjumper angeschlossen. Die AGND-Klemmenliegen auf demselben Potenzial.
Anzahl der Analogausgänge 8, keine galvanische TrennungTyp der Analogausgänge (Über Jumper einstellbar)
UIp
0 - 10VDC ± 1% , max. 5 mA 0 - 20 mA ± 1% , max. 500 Ohm PWM 1200 Hz, 5V-Stufe, max. 10 mA
Stromversorgung 8 - 36 VDC
Stromverbrauch 100 ÷ 300 mA bei 24 VDC
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
33/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 33
Kommunikationsschnittstelle CAN1, mit über Jumper wählbarer Adresse 1 bis 4 Durch Jumper wählbarer Abschlusswiderstand 120Ohm.
RS232-Schnittstelle TTL, Firmware-Upgrade über AT-Link.Betriebstemperaturbereich: -40 bis +70°C
Aktualisierung der
Analogausgänge
Max. 300 ms
95 mm (3,7´)43 mm(1,7´)
9 6
m m
( 3 , 8 ' )
Power
supply
I-AOUT8ComAp
HW:
SW:
+ 8 - 3 6 V D
C
G N D
A G N D
A O U T 5
A G N D
A O U T 6
A G N D
A O U T 7
A G N D
A O U T 8
ANALOG OUTPUTS
A O U T 1
A G N D
A O U T 2
A G N D
A O U T 3
A G N D
A O U T 4
A G N D
ANALOG OUTPUTS
C A N L
C C O M
C A N H
CAN
U - I - p U - I - p U - I - p U - I - p
p - I - U p - I - U p - I - U p - I - U
1 2 Pwr
120 ohm
5.3.14.2 Verbindung mit mehreren Geräten Bis zu vier Module können an einen Controller angeschlossen werden. Stellen Sie die CAN-Adressedes Moduls je nach Konfiguration gemäß folgender Tabelle ein:
CAN-Adresse Jumper 1 Jumper 21 Nein Nein
2 Ja Nein
3 Nein Ja
4 Ja Ja
5.3.14.3 Analogausgang- Änderung (U, I, PWM)
Beachten Sie die p-I-I-U-Symbole auf dem Aufkleber des Moduls. Es gibt zwei gleichwertige
Positionen für die mA-Messung.
AOUT-Jumper Symbol Funktionp Pwm
Pulsweitenmodulation
I 0 bis 20 mA
U 0 - 10 VDC
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
34/141
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
35/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 35
5.3.15 I-LBA
Für Verbindungen mit 12V DC-Versorgungsspannung kann ein I-LBA-Modul an die Stromanschlüssendes Controllers angeschlossen werden, um es diesem zu ermöglichen, mit dem Betrieb während dem
Anlassen fortzufahren, wenn ein Batteriespannungseinbruch auftritt.
Controller, die von dem I-LBA-Modul versorgt werden können:
Steuergerät IG-NT/IG-NT-BB
IG-NTC/IG-NTC-BB
IS-NT-BB/IS-NTC-BB
IS-NT IG-CU IS-CU IL-CU/IL-NT
Verbindunganwendbar
JA JA JA NEIN JA NEIN JA
H INWEIS :Die I-LBA-Einheit ist für die Versorgung eines einzigen Controllers gedacht.
Es wird nicht empfohlen, +PWR BOUT- Ausgänge an dem Controller als Quelle für Relais zuverwenden, da deren Verbrauch die I-LBA-Kondensatoren bald ausschöpfen würde.
Es wird außerdem davon abgeraten, die oben erwähnten Controller mit LT-Niedrigtemperatur-Displays auszustatten, da diese einen hohen Stromverbrauch aufweisen.
Siehe auch Kapitel "Sicherung der Versorgungsspannung".
A V R i -
A V R i +
O U T 1
O U T 2
A C 1
A C 2
O C O M
LB5
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
36/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 36
6 Schnittstelle
HINWEIS:
In diesem Handbuch werden die Standard-Frontplatten der Controller und der InteliVision-Displaysgezeigt. Es kann möglicherweise davon abweichende Anwendungen geben (z.B. Controller mit nureinem Trennschalter bei MINT- Anwendung) und Kunden können Änderungen an den Frontplatten derController und den InteliVision-Displays vornehmen.
6.1 Frontplatten
HINWEIS: Die Bilder sind verglichen mit dem tatsächlichen Produkt nicht maßstabsgetreu!
6.1.1 InteliGen NT-Controller
InteliGen-Controllertypen IG-NT, IG-NTC
InteliGen – Remote-Display IG-DISPLAY, INTELIVISION 5 und 8Verfügbar für folgende
Anwendungen:SPI, SPTM, MINT, COX, Combi
6.1.1 InteliMains NT-Controller
InteliMains Controllertypen IM-NT
InteliMains – Remote-Display
IG-DISPLAY, INTELIVISION 5 und 8
Verfügbar für folgende
Anwendungen:
MCB, MGCB, BTB
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
37/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 37
InteliSys NT-Controller
InteliSys-Controllertypen IS-NT
InteliSys – Remote-Display IS-DISPLAY, INTELIVISION 5 und 8Verfügbar für folgende
Anwendungen:SPI, SPTM, MINT, COX, Combi
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
38/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 38
6.1.2 InteliVision 5
Abnehmbares farb Displays. Verfügbar für folgende Geräte:
GERÄT ANZAHL DERDISPLAYS
DISPLAY-ADRESSE
IG-NT(C)-BB 2 1 und 2IS-NTC-BB 3 1, 2, 3
IM-NT(C)-BB 2 1 und 2
IG-NT(C) 1 2
IS-NT-BB 3 1, 2 ,3
IM-NT 1 2
H INWEIS :
Das Display kann nur über RS-485 mit dem Gerät verbunden werden! Verwenden Sie den RS485- Anschluss für die Kommunikation mit Displays.
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
39/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 39
6.1.3 InteliVision 8
Abnehmbares farb Displays. Erhältlich für alle InteliGen-, InteliSys- und InteliMains-Controller.
Verbindungstyp: CAN2, RS 485, RS 232.
GERÄT RS232 RS485(2) DISPLAY – RS485(1) CAN2
IG-NT und IM-NT 1 N/V 1 4
IG-NT-BB und IM-NT-BB 1 N/V 2 4
IG-NTC-BB und IM-NTC-BB 1 1 2 4
IS-NT-BB 1-2* 0*-1 3 4
IS-NTC-BB 1 1 3 4
* Die Ports RS232 und RS485 sind als gemeinsamer Anschluss zusammengefasst (kann entwederals 485(2) oder RS232 konfiguriert werden)
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
40/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 40
6.1 Verkabelung des Displays
6.1.1 Verkabelung des IG-Displays
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
41/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 41
6.1.2 Verkabelung des IS-Displays
6.1.2.1 Eingebautes und Remote-Display
6.1.2.2 Einzelnes Remote-Display
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
42/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 42
6.1.2.3 Mehrere Remote-Displays
H INWEIS :
Der Zustand von "BI Alternative Brightness" ("alternative Helligkeit") wirkt sich nur auf dasentsprechende Display aus.
IS-NT-BB Einheit verfügt über kein internes Display. Für IG/IS-NT-Hardwareoptionen siehe IGS-NT-x.y-Anwendungshandbuch.pdf.
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
43/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 43
6.1.3 Verkabelung von InteliVision 5
6.1.4 Verkabelung von InteliVision 8
6.1.4.1 Allgemeine Richtlinien
RS232
RS485 CAN
L HA B
120 Ω
120 Ω
To RS485(1)or (2)
To CAN2
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
44/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 44
6.1.4.2 Verbindung mit IG-NT
R S 2 3 2
RS485
CAN1
Extension
CAN2
Intercontroller
Terminal 1*:
InteliVision 8
Communication:
InteliVision 8
Channel 1
InteliVision 8
Channel 2
InteliVision 8
Channel 3
InteliVision 8
Channel 4
InteliVision 8
H INWEIS :
*Nur ein externes Display kann über den Anschluss RS485(1)– IG-DISP mit der Steuereinheitverbunden werden.
6.1.4.3 Verbindung mit IG-NTC
R S 2 3 2 ( 1 )
RS485(1)
CAN1
Extension
CAN2
Intercontroller
Terminal 1*:
InteliVision 8
Channel 1
InteliVision 8
Channel 2
InteliVision 8
Channel 3
InteliVision 8
Channel 4
InteliVision 8
Communication:
InteliVision 8
R S 2 3 2 ( 2 )Communication:
InteliVision 8
RS485(2)
Communication:
InteliVision 8
H INWEIS :
*Nur ein externes Display kann über den Anschluss RS485(1)– IG-DISP mit der Steuereinheitverbunden werden.
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
45/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 45
6.1.4.4 Verbindung mit IG-NT-BB
RS485
Display only
CAN1
Extension
modules
CAN2
Intercontroller
and
monitoring R S 2 3 2
Terminal 1*:
InteliVision 8
Communication:
InteliVision 8
Channel 1
InteliVision 8
Channel 2
InteliVision 8
Channel 3
InteliVision 8
Channel 4
InteliVision 8
H INWEIS :
* Ein oder zwei Displays können über RS485 (Display-Klemme) mit den Adressen 1 und 2 derSteuereinheit IG-NT-BB verbunden werden.
6.1.4.5 Verbindung mit IS-NT-BB
R S 2 3 2 ( 1 )
RS485(1)
CAN1
Extension
CAN2
Intercontroller
Terminal 1*:
InteliVision 8
Channel 1
InteliVision 8
Channel 2
InteliVision 8
Channel 3
InteliVision 8
Channel 4
InteliVision 8
Communication:
InteliVision 8
R S 2 3 2 ( 2 )
Communication:
InteliVision 8
RS485(2)
Communication:
InteliVision 8
H INWEIS :
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
46/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 46
*Bis zu drei Displays können über RS 485(1) – Display mit IS-NTC-BB verbunden werden. DieKommunikation über RS232(2) kann auf RS485(2) umgeschaltet werden, also kann nur einInteliVision-Gerät über diese beiden Ports angeschlossen werden.
6.1.4.6 Verbindung mit IG-NTC-BB und IS-NTC-BB
RS485 (2)
Display only
CAN1
Extension
modules
CAN2
Intercontroller
and
monitoring R S 2 3 2
U S B
E t h e r n e t
Communication:
InteliVision 8
Terminal 1*:InteliVision 8
Channel 1InteliVision 8
Channel 2InteliVision 8
Channel 3InteliVision 8
Channel 4InteliVision 8
Communication:
InteliVision 8
RS485(2)
H INWEIS :
* Bis zu drei Displays können über RS 485(1) – Display mit IS-NTC-BB verbunden werden. ZweiDisplay können mit IG-NTC-BB über den Anschluss RS 485(1) – Display verbunden werden. EinInteliVision-Gerät kann mit dem Anschluss RS485(2) verbunden werden.
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
47/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 47
7 Übersicht über Klemmen, Jumperund E/A
7.1 IG-NT GC
7.1.1 Schaltbilder
SPEEDGOVERNOR
B I 7
RPM IN
R S 2 3 2 ( 1 )
BINARYOUTPUTS
PICK-UP
ANALOGINPUTS
DONGLE
+ P W R B O U T
IG-DISPLAY
L B 9 B
1
CAN1EXTENSION
CAN2INTERCONTROLLER
Use Copper Conductors Only
CAUTION -
InteliGenNT
www.comap.czMADE IN THE EU
Order code: IG-NT GC
BINARYINPUTS
A 1
L 1
H 1
L 2
SENSOR RPM COM
AI3
AI2
AI1
AI COM
SG OUT
SG COM
Risk of Electric Shock, Do Not Remove Cover.No User Serviceable Parts Inside.
Refer servicing To Qualified Service Personnel.
C O M R 1
C O M C 1
C O M C 2
B I 8
B I 9
B I 1 0
B I 1 1
B I 1 2
B 0 8
B 0 9
B 0 1 0
B 0 1 1
B 0 1 2
B 0 7
For Use on a Flat Surface of a Type 1 Enclosure.Max. ambient temperature 70º C
Refer to installation instructions for torque values
H 2
B I 1
B I 2
B I 3
B I 4
B I 5
B I 6
GENERATORVOLTAGE
MAINS (BUS)VOLTAGE
N NL1 L1L2 L2L3 L3
BINARYINPUTS
L B 9
3x277 /480 V 3x277 /480 V
A V R I C O M
A V R I O U T
MAX 0.74A
for details
8 - 36 V L B 9POWERGENERATOR CURRENT
0 - 5 ABINARY
OUTPUTS
B 0 1
B 0 2
B 0 3
B 0 4
B 0 5
B 0 6
L 1 k
L 1 I
L 2 k
L 2 I
L 3 k
B 3 I
I N k
I N I
+ P W R B O U T
See instructions
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
48/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 48
Links nach rechts: "Pull down"-Vorspannungswert (Bias) / 120Ω / "Pull up"-Vorspannungswert(Bias) / 120Ω / 120Ω
Unten: AI3-Einstellung / AI2-Einstellung / AI1-Einstellung
Stromeingang 0-25mA
Spannungseingang 0-5V
Widerstandseingang 0-2400 Ω
Einstellung SG OUT
PWM VoutR VOut
Für nähere Informationen, sieheKapitel "Drehzahlreglerausgang"
Boot-Jumper
7.1.2 Klemmen, Eingänge und Ausgänge
Funktion Klemmen AnmerkungGeneratorspannung L1,L2,L3, (N) 3x 277 Ph-N oder 480 Ph-Ph VAC
(neutral nicht erforderlich), max. 350 / 600VAC *,CAT III
Netz-/Bus-Spannung L1,L2,L3, (N) 3x 277 Ph-N oder 480 Ph-Ph VAC
(neutral nicht erforderlich), max. 350 / 600VAC,CAT III
Generatorstrom L1k,L1l, L2k,L2l,L3k,L3l
0 ÷ 5 Ampere, max. 10 A permanent, 150 A - 2Sek. lang
Neutral-/Netzstrom LNk,LNl 0 ÷ 5 Ampere, max. 10 A permanent, 150 A - 2Sek. lang
IG-AVRi-Schnittstelle AVRI-OUT, AVRI-COM TTL (5V PWM) Schnittstelle für IG-AVRiStromversorgung + , - 8 ÷ 36 VDC D+ D plus
Ein- und Ausgänge Binäreingänge BI1 ÷ BI6
BI7 ÷ BI12 Aktivierung bei schaltung des negativen Potentials.
Binärausgänge BO1 ÷ BO6 BO7 ÷ BO12
Es wird auf negatives potential geschaltet.
Analogeingänge AI1 ÷ AI3 Wiederstands-, Strom- oder Spannungssoren. Analogausgänge SG-OUT, SG-COM Ausgangsschnittstelle für Drehzahlregler ( 10V /
5V PWM; 500 – 3000Hz)U/min RPM-IN, RPM-COM Min. 2 Vpk-pk (von 4 Hz bis 4 kHz)
Kommunikationsschnittstelle
RS232 (1) D SUB9 (Stecker) PC: InteliMonitor, GenConfig oderModem, GSM-Modem oderECU (z.B. Cummins ModBus) oder InteliVision 8
RS485 (1) ** A1, B1, COMR1 IG-Display (Remote-Display) oder InteliVision 8(Remote-Display) oder für PC (über RS485-
Anschluss) = umgeleitetes RS232 (1)
siehe Grundlegende Einstellungen:RS485(1)conv.Für das IG-Display und InteliVision 8 muss derParameter "RS485 (1)" auf den Wert DISABLED(deaktiviert) gesetzt werden.
CAN1 L1, H1, COMC1 Erweiterungsmodule: IS-AIN, IS-BIN,IGS-PTM,IGL-RA15, I-AOUT
CAN2 L2, H2, COMC2 Interne Controller-Kommunikation (Lastausgleich,Blindleistungsverteilung und Energieverwaltung)und Überwachung (IG-IB, I-LB) und bis zu 4InteliVision 8-Displays
HINWEIS: * IG-MTU oder IG-MTU-2-1 können für drei Kabelsysteme verwendet werden; Systeme mit separatemNullleiter oder wenn eine galvanische Trennung zwischen Generatoren oder zwischen dem Stromnetzund dem Generator erforderlich ist.
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
49/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 49
** Wenn mehrere Geräte angeschlossen an RS485 angeschlossen sind, sollte nur ein Jumper für denVorspannungswiderstand geschlossen werden.
7.2 IG-NTC GC
7.2.1 Schaltbilder
A 2
B 2
C O M R 2
RS 485(2)
SPEEDGOVERNOR
B I 7
RPM IN
R S 2 3 2 ( 1 )
BINARYOUTPUTS
PICK-UP
ANALOGINPUTS
DONGLE
+ P W R B O U T
IG-DISP
L B 8 B
1
CAN1EXTENSION
CAN2INTERCONTROLLER
Use Copper Conductors Only
CAUTION -
Refer to installation instructions for torque values
InteliGenNTC
Order code: IG-NTC GC
BINARYINPUTS
A 1
L 1
H 1
L 2
SENSOR RPM COM
AI3
AI2
AI1
AI COM
SG OUT
SG COM
Risk of Electric Shock, Do Not Remove Cover.No User Serviceable Parts Inside.
Refer servicing To Qualified Service Personnel.
C O M R 1
C O M C 1
C O M C 2
B I 8
B I 9
B I 1 0
B I 1 1
B 0 8
B 0 9
B 0 1 0
B 0 1 1
B 0 1 2
B 0 7
For Use on a Flat Surface of a Type 1 Enclosure.Max. ambient temperature 70º C
RS485(1)
B I 1 2
R S 2 3 2 ( 2 )
USB
B I 1
B I 2
B I 3
B I 4
B I 5
B I 6
H 2
www.comap.czMade in EU, Czech Republic
+ P W R B
O U T
A V R I C O
M
A V R I O U
T
MAX 0.74Afor details
8 - 36 VPOWERGENERATOR CURRENT
0 – 1/0 - 5 A
BINARY
OUTPUTS
B 0 1
B 0 2
B 0 3
B 0 4
B 0 5
B 0 6
L 1 k
L 1 I
L 2 k
L 2 I
L 3 k
L 3 I
I N k
I N I
See instructions
L B 8
GENERATORVOLTAGE
MAINS (BUS)VOLTAGE
N NL1 L1L2 L2L3 L3
BINARYINPUTS
L B 8
3x277 /480 V or 120 /207 V 3x277 /480 V or 120 /207 V
Links nach rechts: "Pull down"-Vorspannungswert (Bias) / 120Ω / "Pull up"-Vorspannungswert(Bias) / 120Ω / 120Ω
Unten: AI3-Einstellung / AI2-Einstellung / AI1-Einstellung
Stromeingang 0-25mA
Spannungseingang 0-5V
Widerstandseingang 0-2400 Ω
Einstellung SG OUT
PWM VoutR VOutFür nähere Informationen, sieheKapitel "Drehzahlreglerausgang"
Boot-Jumper (unterer, die restlichen Jumper sind nur für die interne Verwendung bestimmt)
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
50/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 50
Links nach rechts: "Pull up"-Vorspannungswert (Bias) / 120Ω / "Pull down"-Vorspannungswert(Bias)
7.2.2 Klemmen, Eingänge und Ausgänge
Funktion Klemmen AnmerkungGeneratorspannung L1,L2,L3, (N) 3x120 / 277 Ph-N oder 208 / 480 Ph-Ph VAC
(neutral nicht erforderlich), max. 350 / 600VAC *,CAT III
Netz-/Bus-Spannung L1,L2,L3, (N) 3x120 / 277 Ph-N oder 208 / 480 Ph-Ph VAC(neutral nicht erforderlich), max. 350 / 600VAC,CAT III
Generatorstrom L1k,L1l, L2k,L2l,L3k,L3l
0 ÷ 5 Ampere, max. 10 A zu jeder Zeit, 150 A - 2Sek. lang0 ÷ 1 Ampere, max. 2 A zu jeder Zeit
Neutral-/Netzstrom LNk,LNl 0 ÷ 5 Ampere, max. 10 A zu jeder Zeit, 150 A - 2Sek. lang0 ÷ 1 Ampere, max. 2 A zu jeder Zeit
IG-AVRi-Schnittstelle AVRI-OUT, AVRI-COM TTL (5V PWM) Schnittstelle für IG-AVRiStromversorgung + , - 8 ÷ 36 VDC D+ D plus
Ein- und Ausgänge Binäreingänge BI1 ÷ BI6
BI7 ÷ BI12 Aktivierung bei schaltung des negativen Potentials.
Binärausgänge BO1 ÷ BO6 BO7 ÷ BO12
Es wird auf negatives potential geschaltet.
Analogeingänge AI1 ÷ AI3 Wiederstands-, Strom- oder Spannungssoren. Analogausgänge SG-OUT, SG-COM Ausgangsschnittstelle für Drehzahlregler ( 10V /
5V PWM; 500 – 3000Hz)U/min (RPM) RPM-IN, RPM-COM Min. 2 Vpk-pk (von 4 Hz bis 4 kHz)
KommunikationsschnittstelleRS232 (1) D SUB9 (Stecker) PC: InteliMonitor, GenConfig oder
Modem, GSM-Modem oderECU (z.B. Cummins ModBus) oder InteliVision 8
RS232 (2) D SUB9 (Stecker) PC: InteliMonitor, GenConfig oderModem, GSM-Modem oder InteliVision 8
RS485 (1) **nicht isoliert
A1, B1, COMR1 IG-Display (Remote-Display) oder InteliVision 8(Remote-Display) oderfür PC (via RS485-Konverter) = umgeleitetesRS232 (1)siehe Grundlegende Einstellungen:RS485(1)conv.Für das IG-Display und InteliVision 8 muss der
Parameter "RS485 (1)" auf den Wert DISABLED(deaktiviert) gesetzt werden.
RS485 (2) **isoliert
A2, B2, COMR2 Umgeleitetes RS232 (2) - siehe GrundlegendeEinstellungen: RS485(2)conv. PC: InteliMonitor, GenConfigoder Modem, GSM-Modem oder InteliVision 8
USB 2.0 Slave PC: InteliMonitor, GenConfig
CAN1 L1, H1, COMC1 Erweiterungsmodule: IS-AIN, IS-BIN,IGS-PTM,IGL-RA15, I-AOUT
CAN2 L2, H2, COMC2 Interne Controller-Kommunikation (Lastausgleich,Blindleistungsverteilung und Energieverwaltung)und Überwachung (IG-IB, I-LB) und bis zu 4InteliVision 8-Displays
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
51/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 51
HINWEIS: * IG-MTU oder IG-MTU-2-1 können für drei Kabelsysteme verwendet werden; Systeme mit separatemNullleiter oder wenn eine galvanische Trennung zwischen Generatoren oder zwischen dem Stromnetzund dem Generator erforderlich ist.
** Wenn mehrere Geräte an dem RS485-Jumper für den Vorspannungswiderstand angeschlossensind, sollte nur eines davon geschlossen werden.
7.3 IS-NT-BB
7.3.1 Schaltbilder
InteliSys BaseBox
NT
Order code: IS-NT-BB
L B 6
CAUTION -
( PROG. CNTRL.)4XC2
No User Serviceable Parts Inside.
Refer servicing To Qualified Service Personnel.
Risk of Electric Shock, Do Not Remove Cover.
www.comap.czMade in EU, Czech Republic
L B 7
L B
7
Links nach rechts: "Pull down"-Vorspannungswert (Bias) / 120Ω / "Pull up"-Vorspannungswert(Bias) / 120Ω / 120Ω
Unten: AI4-Einstellung / AI3-Einrichtung / AI2-Einstellung / AI1-Einstellung
Stromeingang 0-25mA
Spannungseingang 0-5V
Widerstandseingang 0-2400 Ω
Einstellung SG OUT
PWM VoutR VOutFür nähere Informationen, siehe
Kapitel "Drehzahlreglerausgang"
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
52/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 52
Boot-Jumper (unterer, die restlichen Jumper sind nur für die interne Verwendung bestimmt)
Links nach rechts: "Pull up"-Vorspannungswert (Bias) / 120Ω / "Pull down"-Vorspannungswert(Bias)
AOUT-Einstellung
Spannung 0-10VDC
Stromstärke 0-20mA
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
53/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 53
7.3.2 Klemmen, Eingänge und Ausgänge
Funktion Klemmen AnmerkungGeneratorspannung L1,L2,L3, (N) 3x120 / 277 Ph-N oder 208 / 480 Ph-Ph VAC, CAT
III(neutral nicht erforderlich), max. 350 / 600VAC *
Netz-/Bus-Spannung L1,L2,L3, (N) 3x120 / 277 Ph-N oder 208 / 480 Ph-Ph VAC(neutral nicht erforderlich), max. 350 / 600VAC,CAT III
Generatorstrom L1k,L1l, L2k,L2l,L3k,L3l
0 ÷ 5 Ampere, max. 10 A zu jeder Zeit, 150 A - 2Sek. lang0 ÷ 1 Ampere, max. 2 A zu jeder Zeit
Neutral-/Netzstrom LNk,LNl 0 ÷ 5 Ampere, max. 10 A zu jeder Zeit, 150 A - 2Sek. lang0 ÷ 1 Ampere, max. 2 A zu jeder Zeit
IG-AVRi-Schnittstelle AVRI-OUT, AVRI-COM TTL (5V PWM) Schnittstelle für IG-AVRiStromversorgung + , - 8 ÷ 36 VDC
D+ D plusEin- und Ausgänge Binäreingänge BI1 ÷ BI6
BI7 ÷ BI16 Aktivierung bei schaltung des negativen Potentials.
Binärausgänge BO1 ÷ BO6 BO7 ÷ BO16
Es wird auf negatives potential geschaltet.
Analogeingänge AI1 ÷ AI4 Wiederstands-, Strom- oder Spannungssoren. Analogausgänge SG-OUT, SG-COM
AOUT+, AOUT-COM
Ausgangsschnittstelle für Drehzahlregler ( 10V /5V PWM; 500 – 3000Hz)Konfigurierbarer Analogausgang, mA, V.
U/min (RPM) RPM-IN, RPM-COM Min. 2 Vpk-pk (von 4 Hz bis 4 kHz)
Kommunikationsschnittstelle
RS232 (1) D SUB9 (Stecker) PC: InteliMonitor, GenConfig oder
Modem, GSM-Modem oderECU (z.B. Cummins ModBus) oder InteliVision 8
RS232 (2) D SUB9 (Stecker) PC: InteliMonitor, GenConfigoder Modem, GSM-Modem oder InteliVision 8
RS485 (1) ** A1, B1, COMR1 Bis zu 3 IS-Displays (Remote-Display), bis zu 3InteliVision 8-Displays (Remote-Display)
RS485 (2) ** A2 ,B2 ,COMR2 Umgeleitetes RS232 (2) - siehe GrundlegendeEinstellungen: RS485(2)conv. PC: InteliMonitor, GenConfigoder Modem, GSM-Modem oder InteliVision 8
USBNicht isoliert
2.0 Slave PC: InteliMonitor, GenConfig
CAN1 L1, H1, COMC1 Erweiterungsmodule: IS-AIN, IS-BIN,IGS-PTM,IGL-RA15, I-AOUT
CAN2 L2, H2, COMC2 Interne Controller-Kommunikation (Lastausgleich,Blindleistungsverteilung und Energieverwaltung)und Überwachung (IG-IB, I-LB) und bis zu 4InteliVision 8-Displays
HINWEIS: * IG-MTU oder IG-MTU-2-1 können für drei Kabelsysteme verwendet werden; Systeme mit separatemNullleiter oder wenn eine galvanische Trennung zwischen Generatoren oder zwischen dem Stromnetzund dem Generator erforderlich ist.
** Wenn mehrere Geräte an dem RS485-Jumper für den Vorspannungswiderstand angeschlossensind, sollte nur eines davon geschlossen werden.
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
54/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 54
7.4 IG-NT-BB
7.4.1 Schaltbilder
LB 8
InteliGen
NT
(1)EXTENSIONMODULES
INTERCONTROLLER& MONITORINGDISPLAY
L H L H
BaseBox
( PROG. CNTRL.)4XC2
Made in EU, Czech Republic
Order code: IG-NT-BB
8
MAX 0,74 A
8
8 8
Links nach rechts: "Pull down"-Vorspannungswert (Bias) / 120Ω / "Pull up"-Vorspannungswert(Bias) / 120Ω / 120Ω
Unten: AI4-Einstellung / AI3-Einrichtung / AI2-Einstellung / AI1-Einstellung
Stromeingang 0-25mA
Spannungseingang 0-5V
Widerstandseingang 0-2400 Ω
Einstellung SG OUT
PWM VoutR VOutFür nähere Informationen, sieheKapitel "Drehzahlreglerausgang"
Boot-Jumper (oberer, die restlichen Jumper sind nur für die interne Verwendung bestimmt)
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
55/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 55
7.4.2 Klemmen, Eingänge und Ausgänge
Funktion Klemmen AnmerkungNetzspannung L1,L2,L3, (N) 277 Ph-N oder 480 Ph-Ph VAC
(neutral nicht erforderlich), max. 600VAC*, CAT III
Bus-Spannung L1,L2,L3, (N) 277 Ph-N oder 480 Ph-Ph VAC
(neutral nicht erforderlich), max. 600VAC, CAT IIINetzstrom L1k,L1l, L2k,L2l, L3k,L3l 0 ÷ 5 Ampere, max. 10 A zu jeder Zeit, 150 A - 2
Sek. lang
Neutral-/Netzstrom INk,INl 0 ÷ 5 Ampere, max. 10 A zu jeder Zeit, 150 A - 2Sek. lang
IG-AVRi-Schnittstelle AVRI-OUT, AVRI-COM TTL (5V PWM) Schnittstelle für IG-AVRiStromversorgung + , - 8 ÷ 36 VDC D+ D plus
Ein- und Ausgänge Binäreingänge BI1 ÷ BI6 Aktivierung bei schaltung des negativen
Potentials.
Binärausgänge BO1 ÷ BO6 BO7 ÷ BO12
Es wird Positiv oder negative geschaltet (definiertin GenConfig “Output type” Low/High Level).
Analogeingänge AI1 ÷ AI3 Wiederstands-, Strom- oder Spannungssoren. Analogausgänge SG-OUT, SG-COM Ausgangsschnittstelle für Drehzahlregler ( 10V /
5V PWM; 500 – 3000Hz)U/min RPM-IN, RPM-COM Min. 2 Vpk-pk (von 4 Hz bis 4 kHz)
Kommunikationsschnittstelle
RS232 (1) D SUB9 (Stecker) PC: InteliMonitor, GenConfig oderModem, GSM-Modem oderECU (z.B. Cummins ModBus) oder InteliVision 8
RS485 (Display) **nicht isoliert
A , B, COM IG-Display (Remote-Display) oder InteliVision 8(Remote-Display) oder für PC (über RS485-
Anschluss) = umgeleitetes RS232 (1)siehe Grundlegende Einstellungen:
RS485(1)conv.Für das IG-Display und InteliVision 8 muss derParameter "RS485 (1)" auf den Wert DISABLED(deaktiviert) gesetzt werden.
CAN1 L, H, COM Erweiterungsmodule: IS-AIN8, IS-BIN16/8,IGS-PTM, IGL-RA15, I-AOUT8, ECU
CAN2 L, H, COM Interne Controller-Kommunikation (Lastausgleich,Blindleistungsverteilung und Energieverwaltung)und Überwachung (IG-IB, I-LB) und bis zu 4InteliVision 8-Displays
HINWEIS: * IG-MTU oder IG-MTU-2-1 können für drei Kabelsysteme verwendet werden; Systeme mit separatemNullleiter oder wenn eine galvanische Trennung zwischen Generatoren oder zwischen dem Stromnetzund dem Generator erforderlich ist.
** Wenn mehrere Geräte an dem RS485-Jumper für den Vorspannungswiderstand angeschlossensind, sollte nur eines davon geschlossen werden.
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
56/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 56
7.5 IG-NTC-BB
7.5.1 Schaltbilder
(1)
L H L H
LB 9
( PROG. CNTRL.)4XC2
9
MAX 0,74 A
9
99
Links nach rechts: "Pull down"-Vorspannungswert (Bias) / 120Ω / "Pull up"-Vorspannungswert(Bias) / 120Ω / 120Ω
Unten: AI4-Einstellung / AI3-Einrichtung / AI2-Einstellung /
AI1-Einstellung
Stromeingang 0-25mA
Spannungseingang 0-5V
Widerstandseingang 0-2400 Ω
Einstellung SG OUT
PWM VoutR VOutFür nähere Informationen, sieheKapitel "Drehzahlreglerausgang"
Boot-Jumper (oberer, die restlichen Jumper sind nur für die interne Verwendung bestimmt)
Links nach rechts: "Pull up"-Vorspannungswert (Bias) / 120Ω / "Pull down"-Vorspannungswert(Bias)
8/15/2019 IGS-NT Installation Guide 05-2013r2_DE.pdf
57/141
IGS-NT, SW-Version 3.0IGS-NT Installationsanleitung 05-2013.pdf, ©ComAp – August 2014 57
7.5.2 Klemmen, Eingänge und Ausgänge
Funktion Klemmen AnmerkungGeneratorspannung L1,L2,L3, (N) 3x120 / 277 Ph-N oder 207 / 480 Ph-Ph VAC
(neutral nicht erforderlich), max. 350 / 600VAC *,CAT III
Netz-/Bus-Spannung L1,L2,L3, (N) 3x120 / 277 Ph-N oder 207 / 480 Ph-Ph VAC(neutral nicht erforderlich), max. 350 / 600VAC,CAT III
Generatorstrom L1k,L1l, L2k,L2l,L3k,L3l
0 ÷ 5 Ampere, max. 10 A zu jeder Zeit, 150 A - 2Sek. lang0 ÷ 1 Ampere, max. 2 A zu jeder Zeit
Neutral-/Netzstrom LNk,LNl 0 ÷ 5 Ampere, max. 10 A zu jeder Zeit, 150 A - 2Sek. lang0 ÷ 1 Ampere, max. 2 A zu jeder Zeit
IG-AVRi-Schnittstelle AVRI-OUT, AVRI-COM TTL (5V P