    General Technical Specification

    3.0 mtpy steel plant at Nagarnar

    Chapter 03 part I 2010 MECON Limited All rights reserved

    Electrics, Drives & Control Page 91 of 236

    converters for transmission of signals in HMI .

    24.0 Feedback devices Encoder for position feedback Tacho for speed feedback

    25.0 Communication bus Profibus / Controlnet / Modbus compatibility.In case of making compatible with PLC communicationbus , required hardware and software to be provided .

    26.0 Cable entry Top or bottom cable entry with no additional cubicle

    9.4 INTELLIGENT TYPE MCC

    A. General1.0 Type Metal clad . Drawout / Non drawout type2.0 Construction Modular construction. Fully compartmentalized with

    metal / insulating material partition.3.0 Enclosure class IP54.4.0 Type of execution Single front.

    5.0 Mounting Floor mounting. Free standing with ISMC 75.6.0 Installation Indoor.

    B. Constructional Features :-

    Sheet steelThickness 2.0 mm for load bearing members.

    1.6 mm for non load bearing members.

    1.0

    Material CRCA2.0 Cable entry Incomer :- Bottom cable entry.

    Outgoing :- Bottom cable entry.3.0 Design Separate cable alley.

    Extendable at both ends.Rear access through removable rear hinged cover doorAll the components shall be accessible from front .Motor controller shall be flush mounted on therespective doorInterchangeable facility of same type of feeder modulesEach module to have covering at the bottom.ACB cubicle door shall close when the ACB is inisolated position.

    4.0 Interlocking & protection

    Module door interlocked with main power isolating

    devices.Power circuit isolation device to have pad locking in theOFF position with door closed.

    5.0 Operating height Minimum :- 300mmMaximum :- 2000 mm.

    6.0 Gland plate Undrilled removable bottom gland plates (3 mm thick)7.0 Miscellaneous Neosprene rubber gasket shall be provided for all the

    doors , removable covers & between adjacent coversLifting hooks for all the shipping sectionsDoors shall have concealed hinges .

  • 7/27/2019 IMCC - ETS

    2/7

    General Technical Specification

    3.0 mtpy steel plant at Nagarnar

    Chapter 03 part I 2010 MECON Limited All rights reserved

    Electrics, Drives & Control Page 92 of 236

    8.0 Labelling Clear legible identification labels (anodized aluminium

    with white letters engraved on black background ) withletter sizes of :-25-50 mm for MCC panel in front and back side of thepanel .5 mm for components and module name plates.Danger board on front and rear sides in English, Hindi& regional language.

    9.0 Earthing Two separate earthing terminals will be provided.Bolted joints with tooth spring washers for good earthcontinuity.Earth bus to run in all cable alley of the panel .

    10. Shipping length To be limited to 2.4 M.11. Limiting dimensions Width of MCC :- 800 mm

    Width of Module :- 500 mmWidth of Cable alley :- 275 mmHeight of module :- 400 mm (min)Depth of MCC :- 600 mm , maximumHowever depth of incoming ACB panel will be 1200 mm(minimum).

    12. Panel space heater In each panel with thermostat , fuse , switch.

    C. Busbars

    (i) Main horizontal & vertical busbars1.0 Arrangement Three phase & neutral.2.0 Material High conductivity electrolytic aluminium alloy confirming

    to grade E91E as per IS-5082 -1981.

    3.0 Phase Busbar Rating Shall be able to carry continuously the connected load(considering diversity factor) plus a 25% margin

    Max. current density shall be :-1.0 A/sq.mm for Aluminium1.5 A/sq.mm for Copper .

    4.0 Neutral Busbar Rating 50 % of phase busbar rating5.0 Short circuit rating 50 kA for 1 sec.6.0 Busbar configuration Red-yellow-blue from front to back or top to bottom or

    left to right as viewed from front.7.0 Busbar insulation Heat shrinkable PVC

    R,Y,B coloured sleeves for phases.Black for neutral.8.0 Busbar supporting

    insulatorsNon-hygroscopic, Flame retardedTrack resistant

    High strengthSheet moulded compound or equivalent polyster fibreglass moulded type .

    9.0 Max. temp. rise of bus Not to exceed 40 deg. C. above ambient of 50 deg.C.10. Air clearance for bare

    busbarPhase to phase :- 25.4 mm (minimum)Phase to earth :- 19.0 mm (minimum)

    11.0 Joints and tap off points Busbar joints and tap off points shall be shrouded andbolted ( with cadmium coated bolts with plain andspring washers and locknuts).

  • 7/27/2019 IMCC - ETS

    3/7

    General Technical Specification

    3.0 mtpy steel plant at Nagarnar

    Chapter 03 part I 2010 MECON Limited All rights reserved

    Electrics, Drives & Control Page 93 of 236

    Bimetallic connectors for connection between dissimilar

    metals .Anti oxide grease for all bus connections .

    12.0 Neutral bus isolation Through disconnecting link .13.0 Vertical busbar Rear side

    (ii) Earth bus1.0 Material GI / Al.2.0 Size Minimum 50 x 6 mm with extension at both ends .

    (iii) Control bus

    1.0 Material Copper.2.0 Size Minimum 25 x 3 mm .3.0 Segment Control bus shall be sectionalized and each bus shall

    be fed from control trafo of respective section, however

    selector switch in one module shall be available toselect the feed of both sections of control bus fromeither of control trafo also.

    4.0 Selector Switch 4 position ( Trafo -1, Trafo -2, Individual, OFF) and asdescribed above.

    (iv) Power supply bus for motor controller (from UPS)

    1.0 Voltage 240 V AC , 50 Hz.1.0 Material Copper.2.0 Size Minimum 25 x 3 mm .

    D. Insulation level1.0 Rated insulation voltage 1100 V2.0 Impulse withstand voltage 4 kV as per IS-13947 (Part I) 19933.0 One minute power

    frequency withstandvoltage

    2.5 kV for power circuit & 500 V for control circuit

    E. Pollution Degree

    1.0 Pollution Degree Pollution Degree 3As per IS-13947 (Part-1) : 1993 ;unless otherwise stated

    E Intelligent Controllers

    1. Type Modular type2. Wiring Contacts from components (breakers , contactors etc)

    shall be hardwired to I/O terminal block of thecontroller.All the potential transformer PT's , protection CT's

    (phase CT and neutral CT) shall be hard wired directlyto the controller or the controller module shall havebuiltin CT and PT for protection & metering purpose .

    3. Power supply Separate power supply source (240 V AC ) from UPSthrough MCB (for controller only).Separate power supply (for interrogation voltage at 240V AC) from MCC itself .

    4. Inputs and outputs The controller shall have :-Minimum 12 digital inputs & 2 analog inputs (12 DI +

  • 7/27/2019 IMCC - ETS

    4/7

    General Technical Specification

    3.0 mtpy steel plant at Nagarnar

    Chapter 03 part I 2010 MECON Limited All rights reserved

    Electrics, Drives & Control Page 94 of 236

    2AI)

    One thermistor/RTD input shall also be available as perrequirement.Minimum 4 relay outputs ( 240 V AC , 10 A ).One Analogue output(For increasing/achieving the desired number of I/Osextended module can be added)

    5. Functions in controller Protection, Control,Metering & Annunciations

    9. Fault memory Faults to be stored in memory on FIFO sequence.10. LED indications Controller healthy

    Controller faultController power supply healthy

    11. Communication Each motor controller (motor / feeder) unit shallcommunicate on the communication bus (Device net /Modbus / Profibus DP) with PLC/DCS directly.

    12. Communication Port 1 nos. RS 485 serial port13. Communication

    configurationSingle Trunk line configuration to each module howeverY link/RLM shall be provided at the beginning of MCCfrom where communication to DCS/PLC shall be onredundant communication bus

    14. Communication speed Max. configurable speed of the node shall not be lessthan 5Mbps

    16. Control - From 16 character keypad and backlit LCDalphanumeric display provided on the controller.The keypad shall have the facility to start and stop

    the motor through a separate key (touch screen type)or separate PBs are to be provided for the same onthe front door of the module .

    - From HMI (located in control room).

    17. Software All the configuration and monitoring shall be donethrough inbuilt software .All the required software required for operation andcommunication shall be provided with latest versionavailable.

    F. Feeder arrangement

    Incomers and Buscoupler

    1.0 Isolating Equipment 3 pole ACB motor operated spring charging.4 pole ACB in case of DG source as second Incomer.Both the Incomers and Buscoupler shall be drawouttype .

    2.0 Quantity Two incomer3.0 Bus coupler Required.4.0 Interlocking Required.

    Normally only one Incomer shall be ON . Afterincoming power failure of any Incomer or ACB trips ,

  • 7/27/2019 IMCC - ETS

    5/7

    General Technical Specification

    3.0 mtpy steel plant at Nagarnar

    Chapter 03 part I 2010 MECON Limited All rights reserved

    Electrics, Drives & Control Page 95 of 236

    second Incomer shall be made ON manually.

    5.0 Interlocking type Electrically .Mechanical (through castle key)

    6.0 Indication Lamps LED cluster type indicating lamps for :-Incoming Power ON: R / Y / B .MCCB / ACB ON /OFF/TRIP

    7.0 Meters and selectorswitches

    144 sq.mm size voltmeter with 7 position selectorswitches144 sq.mm size ammeter with 4 position selectorswitches

    8.0 Current transformer 3 numbers for protection .3 numbers for metering .1 number neutral CT.1 number interposing CT (if required)

    9.0 Potential transformer 1 number10.0 Relays (mounted in each

    ACB)Microprocessor based relay withO/LS/CE/Fprotections .The relays shall have communication facility with PLCon communication bus.

    F. Outgoing feeder arrangements

    (i) Motor Starter feeders

    1.0 Circuit breaker Three pole MCCB (or MPCB upto 45 KW).Three pole ACB (for rating above 630 A) .

    2.0 Power contactor AC3/AC4 as per requirement.3 pole.Minimum 25 A at AC-3 duty.Contactor coil rating for 240 V AC .2NO + 2NC auxiliary contacts.Mechanically interlocked for reversible drives.

    3.0 Auxiliary contactors Required nos. as per scheme.4.0 Control supply isolation

    deviceMCB

    5.0 Test PB Inside module for testing of power contactor when themodule incoming power breaker is OFF

    6.0 Space heater powerprovision

    For motor feeders of 45 KW and above :-Through separate MCB and interlock with main power

    contactor .7.0 Ammeter in LCS Interposing CT (middle phase) shall be provided in the

    feeder module for motor rating 45 KW and above.

    8.0 Motor controllerA. Protections Thermal overload

    Adjustable overload prealarmEarth faultStallingUnbalance

  • 7/27/2019 IMCC - ETS

    6/7

    General Technical Specification

    3.0 mtpy steel plant at Nagarnar

    Chapter 03 part I 2010 MECON Limited All rights reserved

    Electrics, Drives & Control Page 96 of 236

    Short circuit

    Single phase preventionUnder currentToo many startsUnder voltageUnder voltage lockoutBreaker or contactor failure alarmTrip failure alarmOver temperatureWinding and bearing temperature (if applicable formotor).

    B. Display data Voltage, FrequencyPower factorsPower consumption , KW

    Thermal capacityTemperaturePhase and average Amp.Earth fault current% motor load% unbalancePeak current during startingStarting timePre trip values

    C. Fault / alarm historydescription

    No. of tripsNo. of operations ( Forward / reverse)Hours run

    Hours run last startKilowatt hoursKilowatt peak demandAlarm / trip history (with date and time)Alarm / trip descriptionReference start curve (in graphics)Start curve (in graphics)Time to trip / reset

    (ii) Power supply feeders1.0 Circuit breaker Three pole MCCB (or MPCB upto 45 KW).

    Three pole ACB (for rating above 630 A) .2.0 Indications ON/OFF/TRIP indication lamp.

    G. Panel wiring

    1.0 Power / current transformercircuit

    1.1kV grade single core , black colour PVC insulated ,stranded copper conductor of minimum size 2.5 sq.mm.For feeder rating 100A and above all the power circuitshall be through rigid busbar .

    2.0 Control and potential circuit 1.1kV grade single coreBlack colour PVC insulatedStranded copper conductor of minimum size 1.5sq.mm.

    3.0 Ferrules Numbered plastic/ceramic ferrules.

  • 7/27/2019 IMCC - ETS

    7/7

    General Technical Specification

    3.0 mtpy steel plant at Nagarnar

    Chapter 03 part I 2010 MECON Limited All rights reserved

    Electrics, Drives & Control Page 97 of 236

    Self locking type.

    4.0 Marking Wiring will be properly marked as per relevant IS.5.0 Spare contacts All spare contacts of relays, selector switches &

    contactors will be wired upto the terminal block.Each components shall have at least one potential freespare contacts.

    6.0 Terminals Power & control terminals shall be segregated byinsulating material like hylam/bakelite sheet.Power terminals will be stud type.Control terminals will be ELMEX type suitable forconnecting two cores of 2.5 sq.mm wires.Minimum 20 % spare terminals will be provided.The minimum rating of control terminal shall be 10Amps.

    7.0 Cable glands Double compression cable glands for receiving externalpower and control cables

    H. Control Supply

    1.0 Control transformer 1 nos. of 415V/240V control transformer of minimum2.5 KVA in each section.Secondary unearthed.

    2.0 Input and output sideisolation device

    Input side :- MCCB/MPCBOutput side :- MCB

    3.0 Control supply changeoversystem

    Manual changeover through contactor logic andthrough selector switch respectively (Sel.sw. shall havea contact rating of 25 A at 240 V AC).

    CONVENTIONAL MCC:All the features of IMCC shall also be applicable for Conventional MCC except thatEOCR shall be provided (instead of Motor Controller) and interface with Automationsystem shall be through RI/O panel ( instead of field-bus communication).In absence of motor controller an Ammeter shall also be provided for all Motor feedersabove 15 kW in Intelligent MCC.

    9.5 STAND ALONE STARTER OR MCP PANEL

    A. General :-

    1.0 Type - Metal clad .

    -Non drawout type.

    2.0 Construction - Modular construction .- Fully compartmentalized with metal / insulating

    material partition.3.0 Enclosure class IP52.4.0 Type of execution Single front.

    5.0 Mounting - Floor mounting.- Free standing with ISMC 75.