19
Impact of Voltage Transients and System Impedance Ratio on Zone 1 Distance Relay Reach 56 th Minnesota Power Systems Conference November 3, 2020 Pratap G. Mysore, P.E., Pratap Consulting Services, LLC & John U. Berzins P.E., Xcel Energy, MN

Impact of Voltage Transients and System Impedance Ratio ...ccaps.umn.edu/documents/CPE-Conferences/MIPSYCON...Impact of Voltage Transients and System Impedance Ratio on Zone 1 Distance

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

  • Impact of Voltage Transients and System Impedance Ratio on Zone 1 Distance Relay Reach

    56th Minnesota Power Systems ConferenceNovember 3, 2020

    Pratap G. Mysore, P.E., Pratap Consulting Services, LLC

    &

    John U. Berzins P.E., Xcel Energy, MN

  • Source to Line Impedance Ratio - SIR

    2

    §Also defined as the system impedance ratio§ for a fault at the end of the relay reach, ZL, the voltage at the relay

    location,

    § VR = !

    (#$%#&)∗ 𝑍𝐿 = = (!"

    !#%)= (

    (*+,%))--- (1)

    § where, E is the phase to ground voltage§ and ZS is the Impedance behind the relay location

    E

    ZLZS

    Relay Location

    VR

  • SIR

    3

    §Voltage at the Relay Inversely proportional to SIR

    § Three phase and phase-phase Fault, ZS = ZS1; ZL = ZL1

    § Single line to ground fault,ZS = (2ZS1+ZS0) and ZL = (2ZL1+ZL0).

    VR =(

    [!!"!#"∗[ $%&$%' %)]

    where, p = 0!"0!#

    and q = 0$"0$#

    § SIR –depends on fault type

  • Voltage magnitude on Distance Relay

    4

    § Fault Program – Best way to figure out the lowest voltage for end zone fault.

    § SIR = [E/V -1]

    §Relay manufacturers provided operating times based on the fault location with reference to setting and at various SIRs.

    0.1

    0.2

    0.3

    0.4

    0.5

    0.6

    0.7

    0.8

    0.9

    1.0

    0.01 0.1 1.0 10 100

    Boundary

    SIR ZS/ZL

    Faul

    t Loc

    atio

    n (P

    U o

    f the

    Rea

    ch

    Setti

    ng)

    20 mS

    15 ms

    10

    20

    10 20 30 40 50 60 70 80 90 100

    Fault location (Percentage of the reach setting)Re

    lay

    oper

    atin

    g Ti

    me

    (ms)

    Microprocessor Relay

    Electro Mechanical Relay

    Static

  • Distance relay

    5

    §Operating Quantity: (IZ-V) also known as Compensated voltage;

    § I – Current§ Single Line to Ground Fault(A-G): IA+K0IN, K0= Zero Seq. Compensation Factor§ Line –Line Fault (B-C): (IB-IC)§ Three Phase – Same as Phase-Phase fault

    §V –Voltage§ A-G Fault: VA§ B-C Fault: (VB-VC)§ Three Phase fault: same as line to line

    §Reference quantity : § Voltage input (Mho)§ Curent based input (Quadrilateral)

  • Variation of (IZ-V)

    6

    0

    20

    40

    60

    80

    100

    0 0.2 0.4 0.6 0.8 1 1.2(IZ-V

    ) -%

    of N

    omin

    al V

    Fault Location, M

    (IZ-V) for fault location, M (M as PU of the Reach Setting)

    IZ-V for SIR=0.1 IZ-V for SIR=1

    V-IZ for SIR =5 V-IZ for SIR =10

    V-IZ for SIR =20 V-IZ for SIR =30

    § (IZ-V) = ("#$)(&'()")

    𝐸; M -fault location from the relay.

    § (IZ-V) =IZ for a fault at the relay location; M=0

    § Decreases as fault location is moved away from the relay location.

    § Positive up to the Reach.§ Negative beyond the Reach.§ Will be Zero at the reach; M=1§ Slope decreases with the

    increase in SIR

  • (IZ-V) at 80% of the Reach set to 80% of the Line Impedance

    7

    SIR 0.1 1 5 10 20 30%(IZ-V) 18.2% 10% 3.3% 1.8% 0.95% 0.65%

    § Relay Zone 1set to 80% of the line Impedance.

    Observation:§ Fault at 80% of Zone-1 reach (64% of the line impedance).§ Differential voltage between the 80% of the reach and the

    reach location reduces as SIR increases.§ If the error exceeds these numbers, zone-1 operates for faults

    beyond the protected line section.

  • Current Error in (IZ-V)

    8

    §CT Errors: C-Class CTs are used for protection; Errors specified at

    rated burden

    § 10% at 100A and 3% at 5A (Relay always sees less current than the

    actual Value).

    § CT saturation: Relay always estimates lower currents

    § DC offsets – Replica Impedance, Digital mimic filters

    § Relay measuring errors

    Assume worst case CT error: 5%

  • Impedance Error in(IZ-V)

    9

    § Z: Setting error 3%; Impedance calculation error: 5%

    § Total error of IZ: (1+0.05)*(1+0.08) -1 = 0.134; Error: 13.4%

    § The relay will overreach by 13.4%.

  • Voltage Errors in (IZ-V)

    10

    §Wound PT: Errors defined between 90% -110% voltage range

    §Accuracy class: 0.3% -1.2%

    §No data – V< 90%

    §Check with manufacturers

  • Capacitive Voltage Transformers

    11

    §Most common source of voltage input

    L

    C1

    C2

    Ferro Resonance Suppression Filter

    Active Passive

    CVT Errors§ Steady State 0.3% error from 5-100% VNOM§ Steady state error 0.6% at 2% VNOM§ Transient Errors:10%§ always defined at one cycle after the disturbance.§ Special Class: 0.4% at 0.5 Cycle and 0.2% at one

    cycle.

  • Relay Protection Design- Signal to Noise Ratio

    12

    § Today many utilities still used the 66.4V taps on CVTs for line protection needs § Due to limitations on older electromechanical relays§ Microprocessor relays have an upper limit above 250V

    § The use of full tap increases the signal to noise ratio of the relay terminal voltage by 1.73 (assumes CVT with 115V/66.4V taps)

    § Example: For a line with SIR of 20, for end zone fault, the voltage at the relay would be 0.048 PU§ Using the CVT’s 66.4V tap: the actual secondary voltage would be 3.1 V § Using the CVT’s 115V tap: the actual secondary voltage would be 5.5 V

  • PSCAD Line Model Study

    13

    Modeled 230kV 2-mile line with an infinite system

    The source impedance behind the relay location was varied to provide SIR from 1 to 40 in steps of 5

    Zone 1 phase and ground distance elements were set to 85% and 125% of the line impedance

    Single line to ground fault and three phase faults were simulated at the end of the line

    Fault incidence angles were varied from 00 to 1500 for each SIR value for all fault types

    Potential Transformer

    PTR 2000

    0.85*ZL – Zone 1 reach Impedance

    0.15*ZL –Line impedance beyond Zone 1

    Ground Fault Switch (1-Ph or 3-Ph) with

    variable fault initiating angle

    *- Wound PT, CCVT with Active filter and CCVT with Passive filter were used

    Variable Source Impedance

    CTR2000:5

    NOTE:- Line impedance Z1: 0.775@ 83.180 ohms/mile; Z0:[email protected] ohms/mile- line length considered: 2miles - Source impedance varied based on SIR from 1 to 40 in discreet steps.-Homogenous system considered- source and line angles are considered same.

    Strong Remote Source Impedance,

    Zpos=Z0 = 0.5168Ω@830

  • Simulated Case Study 1

    14

    Remote end three phase fault at an SIR of 40

    The faults inception was at a voltage zero crossing

    CVT with active ferro-resonance suppression filter

    No transient detection logic or with no zone-1 time delay

  • Simulated Case Study 2

    15

    Remote end three-phase fault, an SIR of 40, with an active CVT

    No transient detection logic or with any zone-1 time delay

    Transient impedance trajectory would be inside the zone-1 mho for roughly a ¼ cycle before swinging out again

    Actions prevented the relay from overreaching:

    Addition of a 1 cycle delay on the zone-1 elements prevent an over operation

    Pulling back the reach to 80% or less for SIRs at or above 30

    Enabling transient detection logic in the relay

  • Simulated Case Study 3

    16

    Remote end single line to ground (SLG), an SIR of 40, with an active CVT

    No transient detection logic or with any zone-1 time delay enabled

    Zone-1 over operated when set and tested at 60%

    Zone-1 element picks for roughly 33ms after the fault's initiation.

    Zone-1 element remained picked up for about 6.5ms

  • ACTUAL CASESTUDY 1

    17

    Actual 345kV, 21.4-mile long line with a remote SLG fault

    Zone-1 ground element reach set at 80%

    The voltage input was from an active CVT, 66.4V tap

    SIR is calculated from pre-fault and fault voltage magnitude SIR = 206.667/38.59 -1 = 4.35

    Ground zone-1 mho was picked up less than a ¼ cycle

    Roughly 1 cycle after the fault initiation, the impedance was around 98.9% (12.82 Ωpri)

  • ACTUAL CASESTUDY 2

    18

    Actual 345kV, 20.8-mile long line with a remote line to line fault

    Sub-cycle static relays with zone-1 phase element reaches set at 83%

    The voltage input was from an active CVT, 66.4V tap

    SIR is calculated from pre-fault and fault voltage magnitude SIR was calculated to be 2.17

    These static relays have no settable zone delay

    The zone-1 reaches were reduced to 70%

  • Conclusion

    19

    § CVT generate transient for one to two cycles after a disturbance due to stored energy in capacitance.

    § In systems with high source to line impedance ratios, CVT transients may dominate during the transient period

    § CVT designs with lower capacitance values and with active ferro-resonance suppression filters tend to increase overreach issues

    § Use of full secondary voltage instead of tapped value improves signal to noise ratio.

    § CVT transient mitigation:§ Add intentional delays to zone-1 elements or/and reduction in zone 1

    reach – This could be a setting in the relay or an added delay§ Reduction of zone-1 reach may be necessary.