In-duct air cleaning devices: Ozone emission rates and test

methodology

Glenn Morrison, PI Missouri S&T

Richard Shaughnessy, PI University of Tulsa

Jeff Siegel, PI University of Texas at Austin

California Air Resources Board Project #09-342 Final project presentation

1

Page 2: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Overview: electronic in-duct devices

• California regulates ozone emitting air cleaners – Excludes in-duct air cleaners due to lack of test

method or lab/field data on ozone emissions

• Central objectives of project – Develop test method: ozone emission rate

– Obtain lab and field data on emission rates and resulting indoor concentrations

• Benefits to California – Test method and data to support possible inclusion of

in-duct devices in ARB air cleaner regulation

2

Page 3: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Ozone

• Ozone toxicology highlights

– 40 ppb NOAEL (Adams, 2002)

• Ozone epidemiology highlights (ambient) (EPA, 2011)

– Wheezing, difficulty breathing in infants

– Increased asthma related symptoms and asthma hospital admissions

– Short term increased mortality

3

U.S. EPA. Integrated Science Assessment of Ozone and Related

Photochemical Oxidants (Second External Review Draft). U.S.

Environmental Protection Agency, Washington, DC, EPA/600/R-

10/076B, 2011.

Page 4: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

ARB and UL 867

• ARB air cleaner regulation (2007)

– Devices tested using UL 867 must meet 50 ppb ozone concentration limit 2” from face

Air cleaner

ozone

50 ppb max ozone well mixed

Test chamber

4

50 ppb 2” from face

Page 5: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Emission rates of air cleaners

0.01

0.1

1

10

100

Ozo

ne

em

issi

on

rate

(mg

/h) Ozone injection rate

typical of outdoor infiltration

Britigan et al., 2006; Waring et al., 2007; Phillips et al., 1999; Niu et al. 2001a, 2001b; Tung et al., 2005; Yu et al., 2005; Mullen et al., 2005; Siegel et al., 2005.

5

Page 6: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

In-duct, electrically connected air cleaners

• Multiple types – Plate and wire electrostatic precipitator

– Ozone generator

– Ion generator

• Existing measurements – 0-60 mg h-1

• Viner et al. (1992), Hanley et al. (1995), Bowser et al. (1999)

– Up to 200 ppb O3 in house with device installed as directed by manufacturer • Emmerich and Nabinger et al. (2000)

6

Page 7: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Specific Objectives

1) develop and test a method of measuring the ozone emission of in-duct electrically-connected air cleaners (“device”) and

2) obtain real-world data on ozone concentration increases due to use of these devices in field sites

3) apply the method to a number of commercially available units in the lab to measure emission rates, and

4) model the impact of in-duct air cleaners in California buildings.

7

Page 8: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Tasks

• Task 1. Candidate device survey of in-duct electronic air cleaners

• Task 2. Laboratory development of test method (Objective 1 and 3)

• Task 3. Field testing of in-duct devices and development of field test method (Objective 2)

• Task 4. California field test of 7 homes and 1 commercial building (Objective 2)

• Task 5. Analysis of California homes characteristics and anticipated indoor ozone concentrations (Objective 4)

• Task 6. Project management and reporting

8

Page 9: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Methods

9

Page 10: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 1 Candidate device survey

• Candidate device survey based on – Opinions and experience of California installers

• 72 contacted, 34 responded

• “What brands of electronic air cleaners do you sell”

• “What are your most popular products”

– California distributors

– Contacts with manufacturers

– Opinions and expressed testing interests of agencies (ARB, CPSC, Health Canada, National Research Council of Canada, EPA)

10

Page 11: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 2

• Develop standard test method

– Laboratory based

– Ducted system

– Realistic operational conditions

– Range of flow rates

– Emission rate based on increase in ozone concentration across device:

• Emission rate = concentration increase* volumetric flow rate

11

Page 12: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 2

• Test apparatus

– Closed loop

– Flow up to ~3000 m3 h-1

– Able to adjust temperature and RH

– Activated carbon filtration

– Able to accommodate wide variety of in-duct air cleaners

– Ability to measure ozone across installed device

12

Page 13: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 2 • Test apparatus

13

Air Handling Unit #2

Air Handling Unit #1

Downstream Sampling Upstream

Sampling

Activated Carbon

HEPA Filter

Flow Station

Air Flow

Device

Page 14: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 2

• Test apparatus

14

Air Handling Units

Air Cleaner Test Section

Activated Carbon and HEPA Filters

Page 15: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 2 • Devices

– based results of Task 1

15

Air Cleaner Technology

1 Ultraviolet light

2a Photohydroionization

2b Photohydroionization

2c Photohydroionization

3 Electrostatic Precipitation

4 Photocatalytic Oxidation

5a Ultraviolet light

5b Ultraviolet light

6a Ozone generator

6b Ozone generator

7 UV / PCO / Carbon

8 Ultraviolet light

Page 16: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Some devices tested

11/6/2013 16

Page 17: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 3

• Field tests

– Method development in Tulsa field site

• Site selection

• Incremental increase in ozone concentration

• In-situ ozone emission rate (OER)

– Application of method in California field homes

• Site selection

• Incremental increase in ozone concentration

• In-situ ozone emission rate (OER)

11/6/2013 17

Page 18: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 3

• Tulsa field site

– Similar to small California homes

– Presence of central air system

– Access to air handler

– Reviewed 10 houses, chose 1

11/6/2013 18

Page 19: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 3

• Field test method (highlights) – Measurement objectives

• Incremental increase in ozone concentration

• Effective ozone emission rate (OER)

– Building prep • Close windows, doors, fans off (reduce air exchange)

• Install device

• Set CO2 and O3 sampling locations – Supply

– Return

– Room center

– Outdoor

19

Page 20: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 3

• Field test method (highlights) – Specific measurements

• Ozone concentration with device on and off

• Indoor/outdoor measurements

• Simultaneous measurement of – Ozone decay rate (ODR)

– Air exchange rate (AER)

– Effective ozone emission rate (OER) • OER1= V[(CO3)(AER+ODR)-P(AER) CO3,out]

• OER2 = (CO3-CO3,o)(AER+ODR)V

20

Page 21: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 4

• California home selection – Installer recommendations

• Homes with devices already installed

– Convenience sample • List-serves

• Emails to colleagues

– Vetting • Access, unoccupied during tests

• Smaller homes (800-1500 ft2)

• Appropriate central air facilities

21

Page 22: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 4

• California sites selected

– 6 homes

• Single-family residences

• Davis/ Sacramento area

• 990 – 2345 ft2

• Closet or attic access to air handler

• 1 to 2 devices tested per home

– 1 school

• commercial system pre-installed

22

Page 23: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 4

23

Page 24: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 5

• Building simulations

– Single zone

• Standard mass balance model

• California home characteristics

• Predict range of indoor ozone concentrations

– Multiple zone

• Identify complex phenomena

• Wind induced spatial/temporal “hot spots”

24

Page 25: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Air exchange rate

Ozone decay rate (reactions in gas and with surfaces)

Penetration Outdoor ozone concentration

Effective emission rate

Task 5 Analysis of California homes characteristics and estimated indoor

ozone concentrations

Duct/filter/HVAC losses

25

𝐶 =𝑉𝜆𝐶𝑜𝑃𝑏 + 𝑆

𝜆 + 𝑘𝑖𝐶𝑖𝑉

𝑛𝑖=1 + 𝑣𝑑,𝑗

𝐴𝑗𝑉

𝑚𝑗=1 + 1 − 𝑃𝑟 𝜆𝑟 𝑉

Page 26: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 5 • Single zone: model inputs

26

Low Middle High Standard House

At Risk House

Source emission rate (S’), mg h-1

0 100 300 100 50

Air exchange rate (l), h-1

0.1 0.5 3 0.5 0.1

Volume (V), m3 75 350 900 350 150 Penetration (P) 0.6 0.8 1.0 0.8 1.0 Decay rate (kd), h-1

1 4 12 4 1.5

Recirculation air exchange (lr), h

-1

2 5.7 9 5.7 2

HVAC penetration (Pr)

0.75 0.85 0.95 0.85 1

Outdoor concentration (Co), ppb

0 60 140 0 0

Page 27: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 5

• Multiple zone

– Model framework: CONTAM 3.0 (NIST)

– Wind speed

– Wind direction

– Ambient ozone

– Variable air handling unit duty cycle

– Surface reactivity

27

Page 28: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 5

• Building AH-14 (CONTAM)

28

Parameter Exterior wall leakage area

0.25 in2/ft2 17.4 cm2/m2

Interior wall leakage area

0.5 in2/ft2 34.7 cm2/m2

Total AHU flowrate 1243 cfm 2113 m3/h Floor area 1039 ft2 96.5 m2 Volume 8282 ft3 25.0 m3 Interior surface area 4736 ft2 440 m2 Ambient temperature 68 F 20 C Absolute pressure 14.7 psi 101325 Pa

Page 29: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 5

• Ambient ozone

• Simulation parameters

29

Wind angle (degrees) Wind

Speed (m/s) Ambient

ozone

Deposition Velocity

(m/h)

AHU duty Cycle (%)

0 90 135 180 270 2 5 8 0.72 2.0 0 20 50 100 Steady State

Dynamic

Page 30: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Results

30

Page 31: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 1

• Devices that may generate ozone

– Electrostatic precipitators (EP)

– Electronically enhanced filters (EEF)

– Ultraviolet light bulbs (UV)

– Photocatalytic oxidation (PCO)

– Dedicated generators of ozone, hydroxyl radicals, hydroperoxide, etc.

– Hybrid systems (e.g. EP + UV + PCO)

31

Page 32: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 1

• Type of devices tested

32

Air Cleaner Technology

1 Ultraviolet light

2a Photohydroionization

2b Photohydroionization

2c Photohydroionization

3 Electrostatic Precipitation

4 Photocatalytic Oxidation

5a Ultraviolet light

5b Ultraviolet light

6a Ozone generator

6b Ozone generator

7 UV / PCO / Carbon

8 Ultraviolet light

Page 33: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 2

• Standard test method – Major sections of device

• Device test and ozone measurement, Air treatment, Flow generation, Optional conditioning section

– Measurements and specifications • Ozone, Temperature, Flow rates, Relative humidity,

Electrical power

– Detailed reporting and calculations

– Method qualification and quantification limits

– Device emission rates over range of flow rates

33

Page 34: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 2 • Qualification of test apparatus

– MQL = 2.3 mg h-1

– Repeatability (shown Device 5)

34

Page 35: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 2

• Emission rate results

35

Page 36: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 2 • Emission rate dependence on flow rate

36

Page 37: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 2 • Dependence of emission rate on T, RH and

flow rate (air cleaner 3)

37

Page 38: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 2: Summary of results

• Emission rates vary from < MQL to 350 mg h-1

• Highest emission rates from “ozone generators” using UV lamps

• Two devices exhibited flow dependence (opposite directions)

• One device exhibited temperature and RH dependence

38

Page 39: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 3 and 4 • House characteristics: air exchange rates

39

Page 40: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 3 and 4 • Field tests: ozone decay rates

40

Page 41: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 3 and 4 • Field tests: incremental increase in ozone

41

Page 42: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 3 and 4 • Ozone emission rates (OER 1 and 2)

42

Page 43: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 3 and 4 • Evidence of temperature dependence

(Device 8)

California Air Resources Board Project #09-342 Kick Off Meeting

43

Page 44: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 3 and 4: Summary of results

• Field method developed in Tulsa test house

• Two devices increased indoor ozone > 50 ppb

– Both were intentional ozone generators using UV lamps

• Same two devices exhibited emission rates > 100 mg h-1 in multiple homes

• Evidence of temperature effect

– Peak concentration >200 ppb for device 8

44

Page 45: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 5 • Single zone model: standard house

45

Page 46: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 5 • Single zone model: at risk house

46

Page 47: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 5

• Multiple zone

– 100 % AHU on, steady state

47

Page 48: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 5

• Multiple zone model

– AHU off, device on

– Steady state

48

Page 49: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 5

• Multiple zone model

– AHU off, device on

– Steady state

49

135º

Page 50: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 5: dynamic results

50

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 240

0.01

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.09

0.1AHS 1h no ambient O3 source 1h

Time [h]

Ozo

ne [

pp

m]

bedroom1: mean =0.0375 ppm, maximum =0.0656 ppm

kitchen: mean =0.0358 ppm, maximum =0.0657 ppm

bedroom2: mean =0.0454 ppm, maximum =0.0722 ppm

bathroom: mean =0.0411 ppm, maximum =0.0664 ppm

Living room: mean =0.0474 ppm, maximum =0.0765 ppm

Source zone: mean =0.0508 ppm, maximum =0.0917 ppm

• 50% AHU duty cycle • Device tied to AHU operation • Ambient ozone = 0

Page 51: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 5 summary

• Single zone model

– Standard home: need ~150 mg/h to achieve 50 ppb

– At risk home: need ~ 27 mg/h to achieve 50 ppb

• Multiple zone model

– Wind direction can result in substantial differences among rooms

– Short-term peaks can occur when AHU turns on

51

Page 52: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Discussion • Comparison field/laboratory

52

Page 53: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Discussion • Predicted and realized incremental increase in

ozone

53

Page 54: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Summary

• Test method and apparatus • Device testing

– 12 devices – Emission rates ~ < 2.3 to > 350 mg h-1

• Field tests – Incremental concentration increase up to 170 ppb – Some devices had erratic emission rates

• Simulations – Small, low reactivity, low AER houses more at risk – Typical house requires 150 mg h-1 to reach 50 ppb

54

Page 55: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Conclusions

• Electrically connected in-duct devices can increase residential ozone concentrations > 50 ppb – Further field tests not necessary

• Laboratory test method adequate to predict field impact

• Need better understanding of installed device occurrence – Consumer installation of devices

55

Page 56: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Acknowledgements

• California Air Resources Board • Occupants and homeowners • David Reisdorph, Nishanthini Vijayakumar

Shakila, Adcharee Karnjanapiboonwong, Mikhil Shetty, Atila Novoselac, Kristia Parker, Joshua Rhodes, Megan Gunther, Christina Phensy, Mark Jackson, Shahana Khurshid, April Rocha

• Deborah Bennett, UC Davis • Jonathan Reyes, Sawyer Heating • Donations from dealers and manufacturers

56

Page 57: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Questions?

57

Page 58: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Extra slides

58

Page 59: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Indoor ozone concentration depends on device emission rate, S

d

outsideindoors

kV

SPCC

Air exchange rate

Ozone decay rate (reactions with surfaces)

Penetration Outdoor ozone concentration

Air cleaner

Device emission rate

59

Page 60: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 5 • Single zone model: influence of ambient O3

60

Page 61: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 5: dynamic results

61

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 240

0.5

1

1.5AHS 1h no ambient O3 source on

Time [h]

Ozo

ne [

pp

m]

bedroom1: mean =0.0481 ppm, maximum =0.071 ppm

kitchen: mean =0.0463 ppm, maximum =0.0712 ppm

bedroom2: mean =0.0637 ppm, maximum =0.0877 ppm

bathroom: mean =0.0665 ppm, maximum =0.0981 ppm

Living room: mean =0.0604 ppm, maximum =0.083 ppm

Source zone: mean =0.62 ppm, maximum =1.5 ppm

• 50% AHU duty cycle • Device ON all the time • Ambient ozone = 0

Page 62: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 5: dynamic results

California Air Resources Board Project #09-342 Kick Off Meeting

62

• 50% AHU duty cycle • Device ON all the time • Ambient ozone = 0

Page 63: In-duct air cleaning devices: Ozone emission rates and ... · PDF fileIn-duct air cleaning devices: Ozone emission rates and test ... (ambient) (EPA, 2011) ... Duct/filter/HVAC losses

Task 5: dynamic results

63

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 240

0.005

0.01

0.015

0.02

0.025

0.03

0.035

0.04

0.045

0.05AHS 20DC ambient O3 source 20DC

Time [h]

Ozo

ne

[p

pm

]

bedroom1: mean =0.029 ppm, maximum =0.0463 ppm

kitchen: mean =0.0293 ppm, maximum =0.0468 ppm

bedroom2: mean =0.0267 ppm, maximum =0.0407 ppm

bathroom: mean =0.0267 ppm, maximum =0.0436 ppm

Living room: mean =0.029 ppm, maximum =0.0427 ppm

• 20% AHU duty cycle • Device tied to AHU operation • Ambient ozone realistic