Industrial Control Panels

IEC/EN 61439

Dirk Müller

UL 508A Online Certifications Directory

The 61439 series

Slide 3

IEC Description Old IEC Standard New IEC Standard

UL Description UL Standard

General Rules IEC 60439-1 IEC 61439-1 Ed2 NA NA

Power Switchgear & Controlgear Assemblies

IEC 60439-1 IEC 61439-2 Ed2 Motor Control Centres

Switchgear Assemblies, Metal Enclosed LVPCB Type

ANSI / UL 845

ANSI / UL 1558

Distribution Boards IEC 60439-3 IEC 61439-3 Panel Boards UL 67

Assemblies for Construction SItes

IEC 60439-4 IEC 61439-4 N.A. N.A.

Assemblies for power distribution in public networks

IEC 60439-5 IEC 61439-5

( Ed1: 2010-11-29)

N.A. N.A.

Busbar Trunking Systems

IEC 60439-2 IEC 61439-6 Busways UL 857

Requirements Manual - Specifier’sGuide

IEC /TR 61439-0

(Ed1: 2010-10-05 )

N.A. N.A.

UL 508A Online Certifications Directory

Ways to comply with 61439 series (per 10.1)

Slide 6

All requirements and

instructions from the OEM

are meet by the Assembly

manufacturer:

No new type test needed.

Assembly manufacturer(panel builder)

OEM

manufacturer

Contractor and

Client (User)

Type Test

Report

(for Modifications

only)

Routi

ne

ver

ific

atio

n

Type Test

Report (for

Original System)

Specifier

UL 508A Online Certifications Directory

Slide 9

Requirements for Enclosures

• Usage of an IEC 62208 enclosure or

• Design Verification

• Resistance against corrosion

- Damp heat cycling (IEC 60068-2-30)

- Saltspray test (IEC 60068-2-11)

• Resistance to heat

- Dry heat test plus cloth ribbing and normal heat (IEC 60068-2-2, -2-10)

- Glow-wire test (IEC 60695-2-10) or pre-selection

• UV radiation (ISO 4892-2)

• Lifting per 10.2.5

• Mechanical Impact (IEC 62262)

• IP rating (IEC 60529)

UL 508A Online Certifications Directory

Why do we need to repeat tests already

conducted at component level ?• Test with components are mainly done without an enclosure

• Usage within a specific enclosure may change test results (more

difficult or less difficult).

Slide 11

UL 508A Online Certifications Directory

Verification of temperature rise (10.10)

Slide 12

Options

Testing per 10.10.2 Test

with current or

10.10.3 Derivation from

tested design

InA ≤ 630A

and Single

compartement

Calculation per 10.10.4.2

using IEC 60890

InA ≤ 1600A

and Single

compartement

Calculation of the total

power loss per 10.10.4.2

Several Restrictions – difficult to meet

UL 508A Online Certifications Directory

SCPD (Short-circuit protective device)

• Not dependent on a SCPD

• SCPD upstream (supply side of the Assembly)

• SCPD included in incoming field

• SCPD included in outgoing functional units

Slide 13

UL 508A Online Certifications Directory

Slide

14

Verification of Short-circuit withstand

No short-circuit test required if:

UL 508A Online Certifications Directory

What‘s coming next

• IEC 61439 3rd edition in voting process

Slide 16

UL 508A Online Certifications Directory

Slide 18

UL Services – IEC-CB Test report / Certificate

CB – Certificate – UL – Second largest issuer of CB reports

UL 508A Online Certifications Directory

UL TYPE

EXAMINATION

CERTIFICATE

Can be

additionally

combined with

UL Classification

Mark to

demonstrate

continued

compliance

UL 508A Online Certifications Directory

UL Classification after Type Examination

CoC to demonstrate

use of the UL Mark

on Panel