2
Model# PF-2800 Specification & Application Data PowerForce ® Corporate Office 9200 Liberty Drive Liberty MO 64068 Ph 816.781.8070 Fax 816.781.2207 Model: PF-2800 Photo depicts a typical model but may not include certain options Engine Specificaons Manufacturer MTU Engine Model 20V4000G83 Type Diesel 4-cycle Number of cylinders & arrangement 20 V Aspiraon Turbo-charged/aſter-cooled Nominal horse power 4035 hp Speed 1800 rpm Radiator ambient rang F° (C°) 122° (55°) Alternator Specificaons Manufacturer Marathon 1020FDL 1004 Type Brushless 4-pole Voltages (3 Phase Wye) 277/480 V Power Factor 0.80 Insulaon Class H Winding Temperature Rise (Standby) 130°C Bearing Single-bearing Skid Design Base - structural I-beam Heavy duty powder coated Handling Forkliſt pockets Exhaust System Arrangement Overhead design Type Carbon steel silencer with rain cap Starng Voltage 24 V Starter and 55A Alternator Baeries 4-Group 31 Cold cranking amps 4200 each Reserve Capacity 34 minutes Starng current amps 1140 Baery enclosure 2-Fully enclosed rail mounted Standard Accessories Fuel Filtraon Engine mounted Air filter System Single Stage replaceable filter Oponal equipment available Block Heater Kim Hotstart 6000W; 7.2A; 480V Starng Air Starter Shutdown Emergency air shut down system Circuit Breaker Supplied to suit applicaon Charging 24 V Automac baery charger Generator End 347/600V 3-phase 60Hz www. powerforce .com Rating Data of Industrial Generators: Voltage Ph Starng skVA (30% voltage dip) PF Prime Standby kW kVA kW kVA 277/480 3 5400 0.8 2520 3150 2800 3500 347/600 3 N.A N.A N.A N.A. N.A N.A. Prime - Prime ratings are applicable for supplying continuous power with a 105 ˚ C alternator temperature rise. 10% overload available for 1 hour in 12. Standby - The standby rating is applicable to varying loads for the duration of a power outage. No overload capability for standby rating 130 ˚ C alternator temperature rise POWERFORCE ® MTU Detroit Diesel Series Generator Sets for Industrial Applications: POWERFORCE ® industrIal generators are designed to meet the rugged demands of the industrial environment, such as Oil & Gas drilling. Each model has been designed to provide reliable continuous power to typical industrial application electrical loads. All models are extensively tested to ensure they meet the performance requirements of the industry. POWERFORCE ® generators are packaged in a purpose built generator assembly and test facility. Each set goes through a fully documented test procedure before leaving our plant. Industrial models utilize the MTU Diesel engines governed to run at 1800 rpm for long life and durability. All industrial generators are designed and packaged as Prime Power & Standby Rated sets. See ratings below for the prime power & standby kW. INDUSTRIAL GENERATOR MTU DIESEL GENERATOR SETS

INDUSTRIAL GENERATOR - PowerForce · Industrial models utilize the MTU Diesel engines governed to run at 1800 rpm for long life and durability. All industrial generators are designed

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: INDUSTRIAL GENERATOR - PowerForce · Industrial models utilize the MTU Diesel engines governed to run at 1800 rpm for long life and durability. All industrial generators are designed

Model# PF-2800

Specification & Application Data

PowerForce® Corporate Of f ice ▪ 9200 Liber ty Dr ive ▪ L iber ty ▪ MO 64068 ▪ Ph 816.781.8070 ▪ Fax 816.781.2207

Model: PF-2800

Photo depicts a typical model but may not include certain options

Engine SpecificationsManufacturer MTU

Engine Model 20V4000G83

Type Diesel 4-cycle

Number of cylinders & arrangement 20 V

Aspiration Turbo-charged/after-cooled

Nominal horse power 4035 hp

Speed 1800 rpm

Radiator ambient rating F° (C°) 122° (55°)

Alternator SpecificationsManufacturer Marathon 1020FDL 1004

Type Brushless 4-pole

Voltages (3 Phase Wye) 277/480 V

Power Factor 0.80

Insulation Class H

Winding Temperature Rise (Standby) 130°C

Bearing Single-bearing

Skid DesignBase - structural I-beam Heavy duty powder coated

Handling Forklift pockets

Exhaust SystemArrangement Overhead design

Type Carbon steel silencer with rain cap

StartingVoltage 24 V Starter and 55A Alternator

Batteries 4-Group 31

Cold cranking amps 4200 each

Reserve Capacity 34 minutes

Starting current amps 1140

Battery enclosure 2-Fully enclosed rail mounted

Standard AccessoriesFuel Filtration Engine mounted

Air filter System Single Stage replaceable filter

Optional equipment availableBlock Heater Kim Hotstart 6000W; 7.2A; 480V

Starting Air Starter

Shutdown Emergency air shut down system

Circuit Breaker Supplied to suit application

Charging 24 V Automatic battery charger

Generator End 347/600V 3-phase 60Hz

w w w . p o w e r f o r c e . c o m

Rating Data of Industrial Generators:Voltage Ph Starting skVA (30% voltage dip) PF

Prime StandbykW kVA kW kVA

277/480 3 5400 0.8 2520 3150 2800 3500

347/600 3 N.A N.A N.A N.A. N.A N.A.

Prime - Prime ratings are applicable for supplying continuous power with a 105˚C alternator temperature rise. 10% overload available for 1 hour in 12.Standby - The standby rating is applicable to varying loads for the duration of a power outage. No overload capability for standby rating 130˚C alternator temperature rise

POWERFORCE® MTU Detroit Diesel Series Generator Sets for Industrial Applications:POWERFORCE® industrIal generators are designed to meet the rugged demands of the industrial environment, such as Oil & Gas drilling.

Each model has been designed to provide reliable continuous power to typical industrial application electrical loads. All models are extensively tested to ensure they meet the performance requirements of the industry.

POWERFORCE® generators are packaged in a purpose built generator assembly and test facility. Each set goes through a fully documented test procedure before leaving our plant.

Industrial models utilize the MTU Diesel engines governed to run at 1800 rpm for long life and durability.

All industrial generators are designed and packaged as Prime Power & Standby Rated sets. See ratings below for the prime power & standby kW.

INDUSTRIAL GENERATORMTU DIESEL GENERATOR SETS

Page 2: INDUSTRIAL GENERATOR - PowerForce · Industrial models utilize the MTU Diesel engines governed to run at 1800 rpm for long life and durability. All industrial generators are designed

W L

H

POWERFORCE ® - The right generator for the job© 2013 POWERFORCE® a registered brand of Central Power Systems & Services. All rights reserved.Specifications are subject to change without notice.

Fuel Tank Data (if supplied) Generator Set Dimensions * (All dimensions are in inches and are approximate)

Run Time Hours Capacity (Gals) L = Length W = Width H = Height Weight lbs dBA

N/A N/A 301” 122” 141” 62,056dry 97.5

* All measurements are approximate and for estimation purposes only. Weights are without fuel tank. Sound levels measured at 23ft (7m) and does not account for ambient site conditions.

Model: PF-2800 Open Set key dimensions and sound levels

Generator Digital Control Panel - for manual, automatic and remote control Control Model# 44000-005

POWERFORCE ® Generator Sets comply with applicable codes and standards

PowerForce Standard Control Panel:

The POWERFORCE® control box was developed specifically for rugged environments such as the Oil & Gas market that require very robust control systems.

The control box has the capability to control the generator set manually, remotely or automatically.

Standard specification includes:

• Stainless Steel NEMA 4 type Box

• Digital gauges for oil pressure, coolant temperature, battery voltage, engine speed, and hour meter

• Yellow and red engine alarm lights

• Left or right side control box mounting (Field changeable)

• Emergency stop button

• Remote input capable controller

Available control panel & electrical options:

• Line circuit breaker

• Battery charger

• SAM communication

PowerForce® Corporate Of f ice ▪ 9200 Liber ty Dr ive ▪ L iber ty ▪ MO 64068 ▪ Ph 816.781.8070 ▪ Fax 816.781.2207 Ref# DS- 10065

w w w . p o w e r f o r c e . c o m

All data subject to change without notice. The information in this white-page specification is believed to be accurate but all recommendations are made without warranty, since the conditions of use are beyond Central Power Systems & Services control. Central Power Systems & Services disclaims any liability in connection with the use of this information, and does not warrant against infringement by reason of the use of any of its products in combination with other material or in any process. Central Power Systems & Services warrants only that the product complies with specifications agreed to in contracts of sale. Central Power Systems & Services reserves the right to change any of the technical information and data detailed in this paper.