Installation Guide
ECL Portal APIWeb interface for ECL Portal databases
1Danfoss District Energy VI.HX.I1.02 DEN-SMT/DK
1.0 Table of Contents ..................................................................................................................................................................................................................11.0 Introduction ...........................................................................................................................................................................................................................22.0 Version table ...........................................................................................................................................................................................................................23.0 Glossary ...................................................................................................................................................................................................................................24.0 General ...................................................................................................................................................................................................................................35.0 Security ...................................................................................................................................................................................................................................3
5.1 Creating third party code ...............................................................................................................................................................................................45.2 Assigning access to a third party ...............................................................................................................................................................................5
6.0 Interfaces .................................................................................................................................................................................................................................66.1 API format ............................................................................................................................................................................................................................76.2 Future versions ..................................................................................................................................................................................................................76.3 Time formats ......................................................................................................................................................................................................................7
7.0 Master data service .............................................................................................................................................................................................................97.1 getEclMasterData request parameters .....................................................................................................................................................................9
7.1.1 Examples of getEclMasterData request parameters ............................................................................................................................ 107.2 getEclMasterData response ....................................................................................................................................................................................... 10
7.2.1 Example of getEclMasterData response .................................................................................................................................................... 107.2.2 Master data ........................................................................................................................................................................................................ 11
7.3 Status codes for response ........................................................................................................................................................................................... 178.0 Readings ................................................................................................................................................................................................................................ 17
8.1 getReadings Request ................................................................................................................................................................................................... 188.2 getReadings Response ................................................................................................................................................................................................ 19
9.0 Using the interface ............................................................................................................................................................................................................ 219.1 Extracting master data .................................................................................................................................................................................................. 23
9.1.1 M-bus, Main meter house ............................................................................................................................................................................... 259.1.2 M-bus, Solar heating, small tank .................................................................................................................................................................. 269.1.3 M-bus, Solar heating, large tank .................................................................................................................................................................. 289.1.4 ECL log, A367.1 example e ............................................................................................................................................................................. 309.1.5 Extracting readings ........................................................................................................................................................................................... 339.1.6 Read the latest values for one or more sensors on a meter connected to the ECL controller............................................... 339.1.7 Reading the most recently measured outdoor temperature ............................................................................................................ 349.1.8 Reading of Energy, Volume, Flow temperature and Return temperature for the house’s main meter .............................. 359.1.9 Read the latest value for one or more sensors across meters connected to the ECL controller. .......................................... 359.1.10 Read a period of historical data for one or more sensors on one meter connected to the ECL controller. ................... 35
9.2 Format differences in data extracted ....................................................................................................................................................................... 39
1.0 Table of Contents
Installation Guide ECL Portal API
2 DEN-SMT/DK VI.HX.I1.02 Danfoss District Energy
1.0 Introduction
This document is a description for a third party for use when implementing software clients to extract data from the ECL Comfort 310 Portal (ECL Portal).
2.0 Version table
Version Date Change
1.00 25/09/2013 First version.
1.10 25/10/2013 Section added about the creation of third party code, future version, time formats. JSON examples added for requests and responses.
1.11 29/10/2013 Example added of difference in data extraction from ECL Portal and ECL Portal API.Example added of time format in readings.
1.12 01/04/2014 A few detailed explanations and examples added.
3.0 Glossary
API Application Programming Interface. An interface for the sharing of application-specific information.
Device A device. Typically used in connection with a log device.
ECL Comfort 310 A district heating controller model from Danfoss A/S.
HTTPS HyperText Transfer Protocol. An encrypted protocol used to transfer information.
Configurable input.
Some sensor inputs on an ECL Comfort 310 controller can be adjusted as an option to measure temperature, pulse, frequency, 0-10 V analogue signal or digital ON/OFF
Customer A person, company or municipality that wants data extracted from the ECL Portal.
JSON JavaScript Object Notation. An open data format for sharing data between a server and an Internet program.
M-bus A communication protocol typically used by heat and energy meters.
Paging Division into pages. In order to avoid too much information being transferred at one time, a volume of data is divided into a number of pages, only one of which is read at a time.
Reading A reading. Log data extracted from the web API from a log device.
Request A request to the web API.
Response Response from the web API server to a request.
REST Representational State Transfer. A software architecture style that can be used to design Internet services.
Server code A unique code issued by Danfoss to a third party.
SSL Secure Sockets Layer. Encryption for the secure sharing of information used, for example on the Internet (HTTPS).
Master data Base data for an ECL Comfort 310 controller.
Third party code A code created by the customer in the ECL Portal, which the customer issues to a third party.
URL Uniform Resource Locator. An Internet address.
UTC Coordinated Universal Time. A standard for coordinated time based in Greenwich, London. Time zones are expressed with reference to UTC.
Web API An API adapted for the Internet.
Third party An external company engaged by a customer to develop software to extract data from the ECL Portal to an external system. Can be the customer.
Installation Guide ECL Portal API
33Danfoss District Energy VI.HX.I1.02 DEN-SMT/DK
4.0 General
The data that is available via the ECL Portal web API depends on the ECL application key installed in the ECL Comfort 310 in question. I.e. the data set available is different for each ECL application type and can also depend on the various external data collection devices, such as M-bus meters and configurable inputs with which ECL controllers can be fitted.
The ECL Portal retrieves data from the ECL controllers once an hour just after the top of the hour. The integrated ECL Log contains application-specific signals such as temperatures measured and temperature references, as well as wind speed, pressure or flow, depending on the application installed. The ECL log contains data recorded at 15-minute intervals. If the customer has set up configurable inputs or connected M-bus meters, the current values of these will also be retrieved once an hour.
If it is not possible to retrieve data from an ECL controller because of a communication error or for some other reason, an attempt will be made to retrieve the ECL log when the next collection takes place one hour later. The internal ECL log in the ECL controller contains data for the last ten days, so if it has not been possible to retrieve the log from an ECL controller for ten days, data will be lost from the ECL portal and will thus not be available through the web API.
As soon as data is available on the ECL Portal, it will also be available through the ECL Portal web API. It is not possible to retrieve data through the web API that is not available on the ECL Portal. If, for example, a customer deletes an ECL log or M-bus meter on the ECL Portal, it will no longer be available through the web API either.
Data is not saved for configurable inputs and M-bus meters in the ECL controller, so historical values will not be read when the logs are next retrieved if there has been no contact with the ECL Portal.
Guides for individual ECL applications are available at www.ecl.doc.danfoss.com, if it is necessary for a third party to have more specific knowledge of the data that can be extracted from the ECL controllers.
A description of communication for ECL controllers may be found here:http://heating.danfoss.com/PCMPDF/VILGV402_ECL_Comfort_210_310_Communication.pdf or by Googling “ecl communication description” to find the latest version. The communication description contains, among other things, a general list of parameters that are logged by some applications.
5.0 Security
As this is an external interface from the ECL Portal server to the outside world, it is particularly important to make sure that it is not possible to gain access to other parties’ data.
The first element in securing data is identification, so that you can validate whether the client that is calling the ECL Portal web API is authorised to view the data being requested. You must therefore always specify the following in requests:• Servercode.ThisisissuedbyDanfosstoathirdpartyorcustomer,sothattheopeningofthedatainterfaceisanactiveprocessperformed by Danfoss. This involves a setup in connection with the conclusion of a legal contract. • ECLserialnumber.UsedtoidentifyanECLcontrollerofinterest.TheserialnumbermaybefoundinsidetheECLcontroller’smenuorat the ECL Portal• Thirdpartycode.CreatedbythecustomerintheECLPortalandissuedtoathirdparty.
Not only must the third party or customer have stated a server code and know the serial number, but the customer himself must link third party codes to the ECL controller. This provides the customer with the possibility of controlling which third party people and systems they wish to allow to extract the data by assigning them various third party codes, which can of course also be revoked individually.
This means that in order to obtain data from a given ECL controller, you must know its serial number, have a server code issued from Danfoss and have assigned yourself, your system or third party an ECL-specific third party code.
Just as with traditional user name/password combinations, data will only be able to fall into the wrong hands if the combination is compromised, as in such an eventuality an external party would only be able to use the same codes and perform his own requests. Security is thus dependent in this scenario on how the customer and the third party protect this information.
Server codes are issued to the customer/third party individually and may not be shared by a number of customers, as under the legal contract such party may be cancelled when the contract expires or in the event of abuse.
Data communication through the web API requires SSL support. If a client sends requests via HTTP, it will be redirected to HTTPS.
Installation Guide ECL Portal API
4 DEN-SMT/DK VI.HX.I1.02 Danfoss District Energy
5.1 Creating third party code
Use the “Third party codes” menu.
Give a name to the third party code in order to keep track of all codes, and select the setting “Enabled” to render the code active.
The code will now appear in the list of codes created.
Click on the “ECLs” link to go to the page where the code can be assigned to specific ECL controllers.
You can assign the same code here to several ECL controllers, and you can assign several codes to the same ECL controller, so that you can better control who has access to what.
Installation Guide ECL Portal API
55Danfoss District Energy VI.HX.I1.02 DEN-SMT/DK
5.2 Assigning access to a third party
a) If the customer has not previously provided the third party in question with access to data for some ECL controllers administered by the end customers, the end customer sets up a code for the third party under the menu item ECL > Third party codes.
b) The end customer links the relevant ECL controller to the relevant third party code. c) The end customer notifies the third party of the ECL serial number and the third party code.
With these three pieces of information (server code, ECL serial number, third party code), the third party now has the ability to access data for the ECL controller via the web API.
The conceptual interfaces that will be accessible via the web API are described here. Conceptual means what you can request, including which items of information are required in order to request, as well as which items of information you receive in return from such requests.
When you retrieve readings for a given period, it may be the case that the period includes a large number of readings, which is not suitable for transfer via an HTTP request in one action. It is therefore a good idea to operate using what is known as paging, i.e. when you make your request, in addition to indicating the period, you can indicate how many readings you wish to receive at a time. From the responses you receive in return, you can then see whether you have received all readings on the “first page” (/response) or whether you have to retrieve more, and how many you can expect to have to retrieve in total. On the basis of this you can then request the next page, and so on. At the same time, the system defines a default page size and a maximum page size, so you do not need to specify a page size, and nor do you run the risk that a client will ask for an unrealistically large load of data in one single request.
As an ECL controller can operate with several log devices and at different log frequencies, it is difficult to create a logical “page break” in the event that not all data can be returned at one time. When you retrieve readings, it is good to know in advance which devices are accessible on an ECL controller, which ones are active, etc. There is thus a need to be able to obtain this information when readings are to be retrieved, but also if a third party wishes to store/synchronise details of the ECL controllers, devices and channels – what is known as master data.
Examples of accessible devices and channels in an ECL Comfort 310 controller with a given application, which has connected two heat meters via M-bus:
Installation Guide ECL Portal API
6 DEN-SMT/DK VI.HX.I1.02 Danfoss District Energy
Device type Channels Description
EclLogDevice S1 These channels belong to sensors and reference values used by the application.
S2
S3
S4
S5
S6
S7
RefS3
RefS4
RefS5
RefS9
RefS10
EclConfigInputDevice S9 This input is not used by the application and can therefore be used as a configurable input.
EclConfigInputDevice S10 This input is not used by the application and can therefore be used as a configurable input.
EclConfigInputDevice S11 This input is not used by the application and can therefore be used as a configurable input. Requires ECA 32 module in ECL Comfort 310.
EclConfigInputDevice S12 This input is not used by the application and can therefore be used as a configurable input. Requires ECA 32 module in ECL Comfort 310.
EclConfigInputDevice S13 This input is not used by the application and can therefore be used as a configurable input. Requires ECA 32 module in ECL Comfort 310.
EclMBusDevice volume_flow These channels are accessible in the relevant heat meter, which is connected via M-bus.
flow_temperature
volume
EclMBusDevice volume_flow These channels are accessible in the relevant heat meter, which is connected via M-bus.
flow_temperature
volume
energy
return_temperature
6.0 Interfaces
Installation Guide ECL Portal API
77Danfoss District Energy VI.HX.I1.02 DEN-SMT/DK
For this reason, there will be a division of the services that the web API makes available. One service that operates with master data and one service that operates with readings. To make the transfer of readings as optimal as possible in terms of performance, these calls will only return the raw values. In order to interpret them (e.g. in terms of units, etc.), they must then be aligned with master data.
6.1 API format
The web API is a REST (REpresentational State Transfer) API via HTTPS(GET) requests, in which the argument is extracted as a combination of URL components and URL query parameters.
The response format will always be minimalist JSON due to performance. Later in this document there are examples of requests in the correct format.
When the third party has received the server code, third party code and serial number for an ECL controller, they can test the web API by pasting an example from a later section into a browser such as Chrome, after which they will receive a response. The JSON Viewer plug-in for Notepad++ can easily be used to format the JSON text received into an easily readable format.
6.2 Future versions
The interface is prepared for any changes in the future in the format, as an interface version must accompany the requests. The version indicator must be specified in the following form:
https://{host}/endpoint/{version}/...
in which {version} must be replaced by the name of the version format. The version name for the first version is “v1”. See examples where this is used in a later section. The endpoint can be either master data or readings, as described in subsequent sections.
When new versions are introduced, an end date will be announced for the old version, so that third party companies have a period during which they can update their software to the new version.
The old version will no longer be available after the end date. When a new version is available, this will be announced on the front page of the ECL Portal and/or the newsletter.
{host} must be replaced by eclwebapi.danfoss.dk for the web API linked to the Danish ECL Portal at ecl.portal.danfoss.dk.For the web API on the international ECL Portal, {host} must be replaced by eclwebapi.danfoss.com.It is not possible to access ECL controllers at the Danish portal through the web API for the international portal, or vice versa.
6.3 Time formats
Time stamps in the web API follow the ISO 8601 standard. This means that time stamps will be in UTC by default and will appear as:
2013-04-18T08:53:00.0Z
Time stamps in response messages will always be in UTC, and third party software may then convert to other time zones as required. In master data for individual ECL controllers, the time zone stated is the one that was specified under the ECL controller’s data by the owner/administrator on the ECL Portal.
It is possible to specify time stamps in other time zones, when you request data by specifying the local time zone. The above time stamp will then be expressed as
2013-04-18T10:53:00.0+02:00
The “+” symbol must be expressed as “%2B” in requests and the “-” symbol must be expressed as “%2D”
If the time in the ECL controller does not match, or the time zone in the ECL Portal is incorrect, the time stamps in the data extracted may be misleading.
Sample reading for ECL log taken from the ECL Portal API on 29/10/2013 at 09:40 Danish standard time.
Installation Guide ECL Portal API
8 DEN-SMT/DK VI.HX.I1.02 Danfoss District Energy
{“tracking”: { “serverRequestId”: “0af3a240-0a36-45ae-b8af-9e24f52103eb”, “from”: “2013-10-29T09:40:45.318+01:00”, “direction”: “reverse”, “page”: 1, “pageSize”: 1000, “resultReadings”: 1000, “totalReadings”: 69346, “totalPages”: 70},“data”: [{ “externalDeviceId”: “cfbd9943-9e49-4d19-a052-6424de7041e8”, “readings”: [{
“id”: 124280485, “timestamp”: “2013-10-29T07:45:00.0Z”, “receivedTime”: “2013-10-29T08:00:04.55Z”, “manualEntry”: false, “value1”: 192, “value2”: 48.09, “value3”: 90, “value4”: 192, “value5”: 28.5, “value6”: 192, “value7”: 50, “value8”: 192, “value9”: 0, “value10”: 0 }, { “id”: 124280484, “timestamp”: “2013-10-29T07:30:00.0Z”, “receivedTime”: “2013-10-29T08:00:04.52Z”, “manualEntry”: false, “value1”: 192, “value2”: 48.09, “value3”: 90, “value4”: 192, “value5”: 28.5, “value6”: 192, “value7”: 50, “value8”: 192, “value9”: 0, “value10”: 0 } ]}]}
The first “from” parameter is the current reading time, here shown with the time zone +01:00.“timestamp” is the ECL controller’s time for the sample in question.“receivedTime” is the time in the ECL Portal at the point in time when it extracted data from the ECL controller. As data is extracted once an hour, there will typically be four samples (one for each quarter of an hour) with the same “receivedTime” value, although if there has been a failure in data communication, more data may have been extracted at the same time.
If there is no data in the database for the specified time in the specified direction, the data field in the response will be empty.
Sample reading for ECL log extracted from the ECL Portal API on 01/01/2014 at 12:05 Danish Summer Time. The time in the ECL controller has been wrongly set here, and an incorrect time zone has been selected (UTC+02:00 instead of UTC+01:00) in the ECL Portal.
Installation Guide ECL Portal API
99Danfoss District Energy VI.HX.I1.02 DEN-SMT/DK
{ “tracking”: { “serverRequestId”: “07c49346-aa90-4e45-9f20-610931d5887e”, “from”: “2014-04-01T12:05:32.430+02:00”, “direction”: “reverse”, “page”: 1, “pageSize”: 1, “resultReadings”: 14 }, “data”: [{ “externalDeviceId”: “5a84dbcc-a9c0-474f-9c12-5db4884fc6ed”, “readings”: [{ “id”: 79779710, “timestamp”: “2012-10-04T02:15:00.0Z”, “receivedTime”: “2014-04-01T10:00:52.293Z”, “manualEntry”: false, “value1”: -1.25, “value2”: -9.46, “value3”: 26.17, “value4”: 26.66, “value5”: -24.21, “value6”: 45.84, “value7”: 17.8, “value8”: 40.24, “value9”: 10, “value10”: 50.83, “value11”: 30, “value12”: 0 }] }]}
The associated log extracted as an Excel file from the ECL Portal shows:
You can see here that the ECL controller’s time at the last sample was 2012-10-04 05:15:00, while the time in the data from the web API was 2012-10-04 02:15:00Z. There is thus a three-hour difference, which comes from the time zone (which is +2 hours) and summer time (+1 hour)By comparing the three times (from, timeStamp and receivedTime), you can check whether the time has been set correctly in the ECL controller, and whether the correct time zone has been selected in the ECL Portal.
7.0 Master data service
This section describes what the master data service can be used for. In this first version, the service has only one method. The method is getEclMasterData, and it retrieves all relevant master data for a given ECL controller, including connected meters. It also includes data that is necessary to interpret the readings that can be retrieved. Below is a description of the conceptual content of request and response.
7.1 getEclMasterData request parameters
Parameter Description Example
serverCode Part of identification cf. section 5 on security. CompanyA
eclSerial Part of identification cf. section 5 on security. 123456792
eclAccessCode Part of identification cf. section 5 on security. Code5
clientRequestId Optional text that can be used to implement traceability in third party systems that function asynchronously. Can be omitted, but would otherwise typically be an auto-generated unique ID.
555b7f4d-7e1a-4d76-a4f0-be8fb52b7c80
Date Outdoor temperature Kr 1, room temperature Kr 1, flow temperature Kr 2, domestic water temperaturetemperature
Installation Guide ECL Portal API
10 DEN-SMT/DK VI.HX.I1.02 Danfoss District Energy
7.1.1 Examples of getEclMasterData request parameters
Examples with version=v1, serverCode=CompanyA, eclSerial=123456792, eclAccessCode= Code5.
https://{host}/masterdata/{version}/{eclSerial}?serverCode={serverCode}&eclAccessCode={eclAccessCode}
https://eclwebapi.danfoss.dk/masterdata/v1/123456792?serverCode=FirmaA&eclAccessCode=Kode5
7.2 getEclMasterData response
The following information is returned in the response from the server for reasons of traceability.
Element Description Example
clientRequestId The ID that was sent during the actual request in order to permit traceability in the third party.
555b7f4d-7e1a-4d76-a4f0-be8fb52b7c80
serverRequestId The server itself assigns a unique ID to each request, as there is no requirement that you must send a unique client ID across customers. This ID can be used if you are in any doubt about the server’s handling of a request, as various pieces of statistical information will be logged about each request (see section 5.4 on traceability).
9cd4df10-09cc-4ec7-8b4e-c1180b21d9d9
7.2.1 Example of getEclMasterData response
Master data is described in greater detail in the next section.
{“tracking”: { “serverRequestId”: “d4b86aa4-f4a0-4ce8-9f14-3c7bd3cc3c80”},“masterData”: { “application”: “A376.1”, “applicationVersion”: “4.00”, “hardwareModel”: “ECL 310, 230 V”, “hardwareVersion”: “A”, “softwareBuild”: “7232”, “hardwareProductionTime”: “3.2010”, “firmwareVersion”: “1.48”, “serialNumber”: “123456792 ”, “createdOnPortal”: “2012-09-07T08:16:53.543Z”, “timezone”: “Europe/Copenhagen”, “location”: { “street”: “Solitudevej”, “streetNumber”: “13A”, “city”: “Andeby” }, “name”: “ECL name”, “portalGroup”: “Test ECL controllers”, “devices”: [List of log devices has been moved in this example] }}
Installation Guide ECL Portal API
1111Danfoss District Energy VI.HX.I1.02 DEN-SMT/DK
7.2.2 Master data
The following basic master data is also returned with the response for the actual ECL controller.
Element Description Example
application Which application the ECL controller is running.
A376.1
applicationVersion Version of the application 4.00
hardwareModel Hardware model number ECL 310, 230 V
hardwareVersion Hardware version A
softwareBuild * Software build number 7232
hardwareProductionTime Hardware production time 3.2010
firmwareVersion Firmware version number 1.48
serialNumber Serial number 123456792
createdOnPortal Date when the ECL controller was created on (first linked to) the portal
2013-04-18T08:53:00.0Z
timezone Time zone in which ECL controller is located (selected on ECL Portal)
Europe/Copenhagen
location:Street ** Street in which ECL controller is located (if entered on ECL Portal)
Solitudevej
location:StreetNumber ** House number at which ECL controller is located (if entered on ECL Portal)
13A
location:Zip ** Postcode at which ECL controller is located (if entered on ECL Portal)
6400
location:City ** Town/city in which ECL controller is located (if entered on ECL Portal)
Andeby
location:Country ** Country in which ECL controller is located (if entered on ECL Portal)
Denmark
name Name (entered on ECL Portal) Heating in basement
description ** Description (if entered on ECL Portal) Basement
portalGroup ** Group set up in EP to group ECL controllers
Group1
* This string was originally “hardwareBuild”, but has since been corrected to “softwareBuild”.** This data is only sent with master data if it has been entered in the ECL Portal.
Furthermore, for every device on the ECL controller, the following information about the actual device will be returned.
Installation Guide ECL Portal API
12 DEN-SMT/DK VI.HX.I1.02 Danfoss District Energy
Element Description Example
type Specifies the type of device. Possible results are “EclLogDevice”, “EclConfigInputDevice” and “EclMBusDevice”.
EclLogDevice
externalDeviceId External ID number for the device. Must be used, for example, to be able to retrieve readings for the device.
c0f6563e-2bd0-4514-9539-db2c0c700d78
name Name of the device. For an ECL log, the name is always “EclLog”. For other types, any name can be used when created on the ECL Portal.
EclLog
active Denotes whether the device is in use. Possible values are “false”/“true”.Only one ECL log device may be active at a time, although several EclConfigInputDevices or EclMBusDevices can be created at the same time. The active ECL log corresponds to the portal application currently selected.
True
createdOnPortal Creation time for device in ISO 8601 format. 2013-04-18T08:53:00.0Z
lastRead Time last read in ISO 8601 format. 2013-04-18T08:53:00.0Z
logAppName Portal application currently selected. There are many different possibilities, so they will not be mentioned here.
A376.1 example a
configInputType Possible values are: 0-10V ADC
-Pt 1000
-0-10V ADC
-Digital
-Flow switch
-Pulse
-Frequency
If it is an unknown type, “7” is returned.
For EclConfigInputDevices only.
configInputDefinedMaxValue* For EclConfigInputDevices of the type 0-10 V ADC only. 4
configInputDefinedMinValue ** For EclConfigInputDevices of the type 0-10 V ADC only. 2
configInputCircuitCloseText For EclConfigInputDevices of the type “Digital” or “Flow switch” for status “close” only.
Signal OK
configInputCircuitOpenText For EclConfigInputDevices of the type “Digital” or “Flow switch” for status “open” only.
No signal
configInputSensorId For EclConfigInputDevices only. Indicates at which input the configurable input has been created.
S9
mbusAddress For EclMBusDevices only. The address of the M-bus network. 15
mbusSerialNumber For EclMBusDevices only. Unique serial number for the M-bus meter. 06120815
mbusType *** For EclMBusDevices only. Type of M-bus meter. Consists of manufacturer code and type code.
KAM-08-0c
channels Channel information is shown in a later table below.
* This parameter indicates which actual value 10 V represents for 0-10 V ADC input.** This parameter indicates which actual value 0 V represents for 0-10 V ADC input.*** Known types are:
Installation Guide ECL Portal API
1313Danfoss District Energy VI.HX.I1.02 DEN-SMT/DK
ABB-02-02 ABB meterABB-06-02 ABB DBMABB-07-02 ABB ODACW-09-04 Actaris meterACW-0b-04 Actaris meterACW-0b-0c Actaris meterACW-0f-04 Actaris meterACW-14-07 Actaris meterAXI-04-04 Axis SKS3BHG-05-04 Brunata meterBHG-3d-04 Brunata HGQBHG-3d-0c Brunata meterBHG-3d-16 Brunata meterDEI-14-02 Deif APM 380DFS-01-04 Danfoss meterDFS-01-0c Danfoss meterDFS-20-04 Danfoss Sonometer 1100 Heat meter DFS-20-0a Danfoss Sonometer 1100 Cooling meter DFS-25-07 Hydrometer HydrusDFS-2b-04 Danfoss Sonometer 1000DFS-2b-0c Danfoss meterDFS-2f-04 Danfoss Sonometer 1100DFS-41-04 Danfoss Sonometer 500DFS-43-0c Danfoss M-Cal CompactDFS-50-04 Danfoss Infocal 6DFS-52-04 Danfoss Infocal 8EMH-00-02 EMH KIZHYD-20-04 Danfoss Sonometer 1100 Heat meter HYD-20-0a Danfoss Sonometer 1100 Cooling meter HYD-20-0c Hydrometer meterHYD-2b-04 Danfoss Sonometer 1000HYD-2f-04 Danfoss Sonometer 1100HYD-2f-0c Hydrometer meterHYD-50-04 Danfoss Infocal 6HYD-52-04 Danfoss Infocal 8HYD-95-02 Hydrometer HydroportINV-40-07 Sensus HRI b1ITR-18-04 Itron meterKAM-01-02 Kamstrup meterKAM-01-04 Kamstrup meterKAM-01-0c Kamstrup Multical IIIKAM-02-04 Kamstrup Multical 401KAM-07-04 Kamstrup meterKAM-07-0c Kamstrup meterKAM-08-04 Kamstrup meterKAM-08-0c Kamstrup Multical 601KAM-0b-04 Kamstrup Multical 402KAM-0b-0c Kamstrup meterKAM-0f-04 Kamstrup meterKAM-0f-0c Kamstrup Multical 801KAM-0f-16 Kamstrup meterKAM-11-04 Kamstrup meterKAM-11-0c Kamstrup meterKAM-15-04 Kamstrup meterKAM-1b-16 Kamstrup Multical 21KAM-1c-04 Kamstrup Multical 602LDR-01-02 Unknown meterLSE-10-04 Landis & Staefa electronic meterLUG-02-04 Landis & GyrLUG-04-04 Landis & Gyr meterREL-41-07 Relay meterUNKNOWN Label for unknown M-bus meter typeSEN-0e-04 Sensus meterSEN-52-07 Sensus meterSVM-30-0c Svensk Värmemätning SVM meterWZG-03-07 Neumann & Co. Wasserzähler meter
Installation Guide ECL Portal API
14 DEN-SMT/DK VI.HX.I1.02 Danfoss District Energy
The list of known M-bus meters will probably be extended in future, as more are added.
Furthermore, for every single channel on the device, the following information about the actual channel will be returned.
Element Description Example
name * Name of channel. Current volume.
readingValueIndex Which of the up to 16 values in a reading belong to this channel. Min. = 1 and max. = 16. If 4, the value is -4 in a reading from this channel.
4
unit Specifies the unit in which values are measured. Depends on the M-bus meter type, so new meters may contain new values. Possible values are: -watt-watt_hour-kilo_watt-kilo_watt_hour-mega_watt-mega_watt_hour-giga_watt-giga_watt_hour-cubic_metre-litre-hour-kelvin-degree_celsius-cubic_metre_per_hour-cubic_metre_per_minute-litre_per_hour-litre_per_minute-joule-kilo_joule-mega_joule-giga_joule-day-bar-pascal-hertz-kilo_hertz-mega_hertz-giga_hertz-count-unknown-none-ph-pcs-pci-calorie-kilo_calorie-mega_calorie-giga_calorie-metre_per_second-percentage-relative_humidity-default
watt_hour
Installation Guide ECL Portal API
1515Danfoss District Energy VI.HX.I1.02 DEN-SMT/DK
mbusChannelType Used for M-bus devices to specify the channel type. Depends on the M-bus meter type, so new meters may contain new values. Possible values are:-ENERGY-VOLUME-MASS-POWER-VOLUME_FLOW-VOLUME_FLOW_EXT-MASS_FLOW-FLOW_TEMPERATURE-RETURN_TEMPERATURE-TEMPERATURE_DIFFERENCE-EXTERNAL_TEMPERATURE-PRESSURE-DATE_TIME-ON_TIME-OPERATING_TIME-VOLTAGE-CURRENT-DATE-STATUS-SUBUNIT-TARIFF
VOLUME_FLOW
* ) The name depends on factors including the device type, as explained below.
For EclConfigInput devices, the name can be entered by the owner/administrator of the ECL Portal.For EclLog devices, the name depends on the sensor number. Sensor 1 is called S1, sensor 2 is called S2, etc. The reference value for sensor 2 is RefS2, the reference value for Sensor 3 is RefS3, etc. Furthermore, some applications log certain signals that do not come directly from the sensors. These signals are named after their PNU/ID. For example, the PNU 11098, which is the calculated wind strength, is logged in A230.1.
It is therefore named “11098”. It is not possible to name all logged signals for all applications, which is why simple names should be specified.
For EclMBusDevices, the channel is named on the basis of what the M-bus meter says it is. The name therefore depends on the specific meter type being used. Possible names are: -power -return_temperature -temperature_difference -voltage -volume_flow -volume -current -energy -flow_temperature -on_time -operating_time -statusThe list of possible names may be extended in future if new M-bus meters make this necessary.
Installation Guide ECL Portal API
16 DEN-SMT/DK VI.HX.I1.02 Danfoss District Energy
Examples of ECL log devices from master data: ECL log
{“type”: “EclLogDevice”,“externalDeviceId”: “eff82977-bf82-40ff-a23c-21a0c9a4065b”,“name”: “EclLog”,“active”: true,“createdOnPortal”: “2011-09-07T08:21:16.318Z”,“logAppName”: “A376.1 example a”,“lastRead”: “2013-10-23T08:45:00.0Z”,“channels”: [{ “name”: “RefS4 (13254)”, “readingValueIndex”: 6, “unit”: “degree_celsius”},{ “name”: “S2 (11202)”, “readingValueIndex”: 2, “unit”: “degree_celsius”},{ “name”: “RefS5 (11255)”, “readingValueIndex”: 8, “unit”: “degree_celsius”},{ “name”: “RefS3 (11253)”, “readingValueIndex”: 4, “unit”: “degree_celsius”},{ “name”: “RefS10 (12260)”, “readingValueIndex”: 11, “unit”: “degree_celsius”},{ “name”: “S9 (10209)”, “readingValueIndex”: 13},{
“name”: “S4 (10204)”, “readingValueIndex”: 5},{ “name”: “S10 (10210)”, “readingValueIndex”: 10},{ “name”: “RefS9 (12259)”, “readingValueIndex”: 14, “unit”: “degree_celsius”},{ “name”: “S1 (11201)”, “readingValueIndex”: 1, “unit”: “degree_celsius”},{ “name”: “S7 (12207)”, “readingValueIndex”: 12, “unit”: “degree_celsius”},{ “name”: “S6 (10206)”, “readingValueIndex”: 9},{ “name”: “S5 (10205)”, “readingValueIndex”: 7},{ “name”: “S3 (10203)”, “readingValueIndex”: 3}]}
Examples of ECL log devices from master data: Configurable input
{“type”: “EclConfigInputDevice”,“externalDeviceId”: “c4c3e66a-940f-4943-a058-60577ea6fea5”,“name”: “S7”,“active”: true,“createdOnPortal”: “2012-11-09T06:30:38.109Z”,“lastRead”: “2013-10-23T08:57:00.139Z”,“configInputType”: “Pt 1000”,“configInputSensorId”: “S7”,“channels”: [{ “name”: “S7”, “readingValueIndex”: 1, “unit”: “degree_celsius”}]}
Installation Guide ECL Portal API
1717Danfoss District Energy VI.HX.I1.02 DEN-SMT/DK
Examples of ECL log devices from master data: M-bus meter
{“type”: “EclMBusDevice”,“externalDeviceId”: “eda5c8c6-120f-4a7f-ad80-796939458f49”,“name”: “M68”,“active”: true,“createdOnPortal”: “2013-02-20T10:43:35.694Z”,“lastRead”: “2013-08-28T10:00:00.660Z”,“mbusAddress”: “68”,“mbusSerialNumber”: “41681168”,“mbusType”: “DFS-25-07”,“channels”: [{ “name”: “volume_flow”, “readingValueIndex”: 2, “unit”: “cubic_metre_per_hour”, “mbusChannelType”: “VOLUME_FLOW”, “mbusSubUnit”: 0},{ “name”: “flow_temperature”, “readingValueIndex”: 3, “unit”: “degree_celsius”, “mbusChannelType”: “FLOW_TEMPERATURE”, “mbusSubUnit”: 0},{ “name”: “volume”, “readingValueIndex”: 1, “unit”: “cubic_metre”, “mbusChannelType”: “VOLUME”, “mbusSubUnit”: 0}]}
As an ECL can have several old log devices of all types, which are no longer active, the owner/administrator should make sure that old devices on the ECL Portal are deleted if there is no longer any use for their data content.
7.3 Status codes for response
Errors will be responded to in accordance with the HTTP standard, i.e. the response must be able to have one of the following HTTP status codes (for all codes other than code 200, the response will not contain data, but typically a text explaining the problem in detail). • 200–OK• 400–Badrequest,typicallybecauseaparameterismissing.• 401–Unauthorised,i.e.theservercodeorthirdpartycodeisnotcorrect.• 404–ECLnotfound• 500–Otherunknownerror
8.0 Readings
This section describes what the readings service can be used for.
In this first version, the service has only one method. The method is getReadings and it retrieves readings for a device for a given period. In order to optimise data transfer, the result is kept as simple as possible, and you will typically have to know the master data for the ECL controller in order to be able to process the values received. Below is a description of the conceptual content of request and response.
Installation Guide ECL Portal API
18 DEN-SMT/DK VI.HX.I1.02 Danfoss District Energy
8.1 getReadings Request
Parameter Description Example
serverCode Part of identification cf. section 5.3 on security.
CompanyA
eclSerial Part of identification cf. section 5.3 on security.
123456792
eclAccessCode Part of identification cf. section 5.3 on security.
Code5
externalDeviceId The external ID number for the device (see master data).
Default = “*”, which means that you are interested in data from all devices for the ECL controller. This is all permitted when pageSize = 1, in all other cases you must identify a specific device.
c0f6563e-2bd0-4514-9539-db2c0c700d78
from * Start time (inclusive) in ISO 8601 format for reading from API. The default value is the current time.
2013-04-18T08:53:00.0Z
direction If you want readings from the start time and thereafter (forward) or before (reverse). Please note that the sort results of readings in the response depend on this selection. Default = “reverse”.
forward
page Specifies which page you want to have. If, for example, pageSize is 1000 and you state that you want to have page 2, you will typically skip the first 1000 readings (typically because you have received them in a previous request). Default = 1. Min = 1.
1
pageSize The page size, i.e. the number of readings per page. Default = 1. Min = 1. Max = 15,000. Please note that each reading can have up to 16 values, depending on the number of channels for the device.
1000
clientRequestId Optional text ID that can be used to implement traceability in third party systems that function asynchronously, as this is sent with the response. Can be omitted, but would otherwise typically be an auto-generated unique ID.
555b7f4d-7e1a-4d76-a4f0-be8fb52b7c80
* If you have performed a recent extraction of master data, you will also know when you last received data (lastRead from the device).
Example of request following the last reading from a specific device.
https://{host}/readings/{version}/{eclSerial}?serverCode={serverCode}&eclAccessCode={eclAccessCode}&externalDeviceId={externalDeviceId}
https://eclwebapi.danfoss.dk/readings/v1/123456792?serverCode=FirmaA&eclAccessCode=Kode5&externalDeviceId= c0f6563e-2bd0-4514-9539-db2c0c700d78
Installation Guide ECL Portal API
1919Danfoss District Energy VI.HX.I1.02 DEN-SMT/DK
Example of request following the last reading from all devices on an ECL controller.
https://{host}/readings/{version}/{eclSerial}?serverCode={serverCode}&eclAccessCode={eclAccessCode}
Example of request for data from a specific device from a given date and back in time.
https://{host}/readings/{version}/{eclSerial}?serverCode={serverCode}&eclAccessCode={eclAccessCode}& externalDeviceId={externalDeviceId}&from={from}&pageSize={pageSize}&page=1
Example of request for data from a specific device from a given date and ahead in time.
https://{host}/readings/{version}/{eclSerial}?serverCode={serverCode}&eclAccessCode={eclAccessCode}&externalDeviceId={externalDeviceId}&direction=forward&from={from}&pageSize={pageSize}&page=1
If there is no data in the database for the specified time, the API will deliver the next set of data in the specified direction (forward/reverse).
8.2 getReadings Response
As a response to a reading request, one tracking object and one data object are returned.Tracking object:
Element Description Example
clientRequestId The optional text ID that was sent during the actual request in order to permit traceability in the third party.
555b7f4d-7e1a-4d76-a4f0-be8fb52b7c80
serverRequestId The server itself assigns a unique ID to each request, as there is no requirement that you must send a unique client ID across customers. This ID can be used if you are in any doubt about the server’s handling of a request, as various pieces of statistical information will be logged about each request (see section 5.4 on traceability).
9cd4df10-09cc-4ec7-8b4e-c1180b21d9d9
from Repeat of the request parameter or default value, so that you can check the starting point.
2013-04-18T08:53:00.0Z
direction Repeat of the request parameter or default value, so that you can check the direction.
forward
page * Repeat of the request parameter or default value, so that you can check how far you have “browsed”.
1
pageSize Repeat of the request parameter or default value, so that you can check the page size.
1000
resultReadings The number of readings contained in this response (this page – typically pageSize except the last page).
1000
totalReadings ** The total number of readings available if you browse through all pages. 5642
totalPages ** The total number of pages needed to read all readings. 6
*) To continue to the next set of data, you will thus use the same request parameters, but increase the page by one for each reading. **) Only specified for the response on page 1, so that the rows for each page are not counted again. Also specified only if externalDeviceId is different from * (as there is no support anyway for paging when submitting requests to several devices simultaneously).
Installation Guide ECL Portal API
20 DEN-SMT/DK VI.HX.I1.02 Danfoss District Energy
Data object
Element Description Example
externalDeviceId ID used to identify the device. See master data. c0f6563e-2bd0-4514-9539-db2c0c700d78
readings A compilation of readings belonging to the device. See next table for contents
For each reading, the following information will also be contained in the response.
Element Description Example
timestamp The ECL controller’s time stamp for the reading. 2013-04-18T08:53:00.0Z
receivedTime When the ECP Portal logged the reading. 2013-04-18T08:55:32.9Z
manualEntry Only for EclConfigInput devices of the “Pulse” type, for which you can enter values manually via the ECL Portal.
False
value1 Value 1, i.e. the value measured for the channel that has readingValueIndex = 1. 41.82
… 15 Other value fields as above, up to value16, which is the last one.
There is no dependency on the log frequency. The readings will only be listed ascending or descending (depending on what you have requested) in chronological order. I.e. there can in theory be a change in the log frequency over a period.
Errors will be responded to in accordance with the HTTP standard, i.e. the response must be able to have one of the following HTTP status codes (for all codes other than code 200, the response will not contain data, but typically a text explaining the problem in detail). • 200–OK• 400–Badrequest,typicallybecauseaparameterismissingorincorrectlyformatted.• 401–Unauthorised,i.e.theservercodeorthirdpartycodeisnotcorrect.• 404–ECLordevicenotfound• 500–Otherunknownerror
Example of a reading response
{“tracking”: { “clientRequestId”: “555b7f4d-7e1a-4d76-a4f0-be8fb52b7c80”, “serverRequestId”: “9cd4df10-09cc-4ec7-8b4e-c1180b21d9d9”, “from”: “2013-04-18T08: 53: 00.0Z”, “direction”: “forward”, “page”: 1, “pageSize”: 1000, “resultReadings”: 1000, “totalReadings”: 5642, “totalPages”: 6},“data”: [{ “externalDeviceId”: “c0f6563e-2bd0-4514-9539-db2c0c700d78”, “readings”: [{ “timestamp”: “2013-04-18T08: 53: 00.0Z”, “receivedTime”: “2013-04-18T08: 55: 32.9Z”, “manualEntry”: false, “value1”: 41.82, “value2”: 0.00000042, “value3”: 32800000, “value4”: 12 }, …more readings from the same device here…]},…data from other devices here…]}
Installation Guide ECL Portal API
2121Danfoss District Energy VI.HX.I1.02 DEN-SMT/DK
9.0 Using the interface
This section describes/provides examples of different scenarios for using the API.
The API can be used to request data from any ECL controller. The actual scenarios described later in this document are based on the following setup:
This is an A367.1 example e, to which 3 M-bus-based heat meters have been linked together with one pulse-based water meter. On the ECL Portal, the ECL controller appears with the following log units (referred to in web API terms as devices) under ECL > Log:
example e
Main water meter (S17)
Installation Guide ECL Portal API
22 DEN-SMT/DK VI.HX.I1.02 Danfoss District Energy
There are two ECL log devices here, because first of all the port application has been changed from example a to example e, as the user felt that this was more suitable for the system in question. Only one ECL log is active (True), and the other only contains old data. All log devices can be read through the web API. To read a specific log device, you must use the correct externalDeviceId, which can be found by reading master data, which also specifies which log devices are active.
Each log device has a number of channels for which values are logged. These can best be viewed on the Portal as a list under Graph > User-defined graph > Create new graph; the list is shown below, as based on our example ECL:
Installation Guide ECL Portal API
2323Danfoss District Energy VI.HX.I1.02 DEN-SMT/DK
9.1 Extracting master data
Before you extract the readings for an ECL controller, it will be relevant to retrieve the latest master data. Retrieving the master data for the above ECL controller takes place by making one single call to the web API. This can take the form of a request to the REST endpoint, and the response will be in JSON format.
Installation Guide ECL Portal API
24 DEN-SMT/DK VI.HX.I1.02 Danfoss District Energy
As mentioned earlier, master data is returned for the actual ECL controller together with each of the linked devices/log devices (in this instance 6 devices, as master data is also returned for inactive devices).
As described in section 7.1, the server code, ECL serial number, third party code and possibly a clientRequestId are sent as parameters in the request. This includes a description of which information is contained in the response from the web API. Information that includes what can be seen in the portal (cf. screenshots earlier on in this document) and additional details.
Request:
https://eclwebapi.danfoss.dk/masterdata/v1/123456792?serverCode=FirmaA&eclAccessCode=Kode5
For reasons of traceability, the following request ID information is returned in the response from the server. This does not relate to master data registered on the portal, but only to the actual master data request, and will therefore be different for each request.
Element Value
clientRequestId 555b7f4d-7e1a-4d76-a4f0-be8fb52b7c80
serverRequestId 9cd4df10-09cc-4ec7-8b4e-c1180b21d9d9
The following basic master data is returned for the actual ECL controller.
Element Example
application A367.1
applicationVersion 1.00
hardwareModel ECL 310, 230 V
hardwareVersion B
softwareBuild 6884
hardwareProductionTime 51.2010
firmwareVersion 1.46
serialNumber (rendered anonymous)
externalEclId cb829044-b117-4ac7-b265-7b4b23e6338c
createdOnPortal 2011-04-18T12:55:32.9Z
timezone Europe/Copenhagen
locationStreet (rendered anonymous)
locationStreetNumber 8
locationZip 6400
locationCity Sønderborg
locationCountry Denmark
name (rendered anonymous)
Description and portalGroup are not entered for this ECL controller, so they will not be included. Furthermore, for every device/log device on the ECL controller, a number of items of information about the actual device and underlying channels will be returned.
Installation Guide ECL Portal API
2525Danfoss District Energy VI.HX.I1.02 DEN-SMT/DK
9.1.1 M-bus, Main meter house
Element Example
type MBusDevice
externalDeviceId 8dbb8b99-96a4-498c-b75b-c7453e1ad6c1
name Main meter house
active true
createdOnPortal 2012-10-22T09:28:07.0Z
lastRead 2013-04-29T09:05:00.0Z
mbusAddress 61
mbusSerialNumber 38925461
mbusType Danfoss Sonometer 1100
Installation Guide ECL Portal API
26 DEN-SMT/DK VI.HX.I1.02 Danfoss District Energy
The following information is returned about the 4 channels.
Element Example
name Energy
readingValueIndex 1
unit Wh
unitKey watt_hour
mbusChannelType ENERGY
Element Example
name Volume
readingValueIndex 2
unit m³
unitKey cubic_metre
mbusChannelType VOLUME
Element Example
name Return flow temperature
readingValueIndex 4
unit °C
unitKey degree_celsius
mbusChannelType RETURN_TEMPERATURE
Element Example
name Flow temperature
readingValueIndex 3
unit °C
unitKey degree_celsius
mbusChannelType FLOW_TEMPERATURE
9.1.2 M-bus, Solar heating, small tank
Element Example
type MBusDevice
externalDeviceId c76c6a87-270c-4123-be57-d39f8f551f43
name Solar heating, small tank
active true
Installation Guide ECL Portal API
2727Danfoss District Energy VI.HX.I1.02 DEN-SMT/DK
Element Example
createdOnPortal 2012-10-19T13:54:30.0Z
lastRead 2013-04-29T09:05:00.0Z
mbusAddress 2
mbusSerialNumber 34326094
mbusType Danfoss Sonometer 1000
The following information is returned about the 6 channels:
Element Example
name Energy
readingValueIndex 1
unit Wh
unitKey watt_hours
mbusChannelType ENERGY
Element Example
name Volume
readingValueIndex 2
unit m³
unitKey cubic_metre
mbusChannelType VOLUME
Element Example
name Flow temperature
readingValueIndex 5
unit °C
unitKey degree_celsius
mbusChannelType FLOW_TEMPERATURE
Element Example
name Current volume.
readingValueIndex 4
unit m³/h
unitKey cubic_metre_per_hour
mbusChannelType VOLUME_FLOW
Installation Guide ECL Portal API
28 DEN-SMT/DK VI.HX.I1.02 Danfoss District Energy
Element Example
name Current output
readingValueIndex 3
unit W
unitKey watt
mbusChannelType POWER
Element Example
name Return flow temperature
readingValueIndex 6
unit °C
unitKey degree_celsius
mbusChannelType RETURN_TEMPERATURE
9.1.3 M-bus, Solar heating, large tank
Element Example
type MBusDevice
externalDeviceId 64365d4b-b991-4512-b3ea-456ee6c83b33
name Solar heating, large tank
active true
createdOnPortal 2012-10-19T13:53:30.0Z
lastRead 2013-04-29T09:05:00.0Z
mbusAddress 1
mbusSerialNumber 34326095
mbusType Danfoss Sonometer 1000
The following information is returned about the 6 channels:
Element Example
name Volume
readingValueIndex 2
unit m³
unitKey cubic_metre
mbusChannelType VOLUME
Installation Guide ECL Portal API
2929Danfoss District Energy VI.HX.I1.02 DEN-SMT/DK
Element Example
name Current output
readingValueIndex 3
unit W
unitKey watt
mbusChannelType POWER
Element Example
name Return flow temperature
readingValueIndex 6
unit °C
unitKey degree_celsius
mbusChannelType RETURN_TEMPERATURE
Element Example
name Energy
readingValueIndex 1
unit Wh
unitKey watt_hours
mbusChannelType ENERGY
Element Example
name Current volume.
readingValueIndex 4
unit m³/h
unitKey cubic_metre_per_hour
mbusChannelType VOLUME_FLOW
Element Example
name Flow temperature
readingValueIndex 5
unit °C
unitKey degree_celsius
mbusChannelType FLOW_TEMPERATURE
Installation Guide ECL Portal API
30 DEN-SMT/DK VI.HX.I1.02 Danfoss District Energy
9.1.4 ECL log, A367.1 example e
Element Example
type EclLogDevice
externalDeviceId 2cc34b74-2c42-4ad1-a6c4-f27876b1c799
name EclLog
active true
createdOnPortal 2011-12-13T07:07:29.0Z
lastRead 2013-04-29T09:00:00.0Z
logAppName A367.1 example e
The following information is returned about the 14 channels:
Element Example
name Kr 2, return temperature
readingValueIndex 10
unit °C
unitKey degree_celsius
Element Example
name Kr 3, upper tank temperature
readingValueIndex 7
unit °C
unitKey degree_celsius
Element Example
name Kr 2, return temperature ref.
readingValueIndex 11
unit °C
unitKey degree_celsius
Element Example
name Kr 1, room temperature
readingValueIndex 2
unit °C
unitKey degree_celsius
Installation Guide ECL Portal API
3131Danfoss District Energy VI.HX.I1.02 DEN-SMT/DK
Element Example
name Kr 2, flow temperature ref.
readingValueIndex 13
unit °C
unitKey degree_celsius
Element Example
name Kr 1, flow temperature
readingValueIndex 3
unit °C
unitKey degree_celsius
Element Example
name Outdoor temperature
readingValueIndex 1
unit °C
unitKey degree_celsius
Element Example
name Kr 2, flow temperature
readingValueIndex 12
unit °C
unitKey degree_celsius
Element Example
name Kr 3, upper tank temperature ref.
readingValueIndex 8
unit °C
unitKey degree_celsius
Element Example
name Kr 3, lower tank temperature
readingValueIndex 9
unit °C
Element Example
name Kr 2, room temperature
readingValueIndex 14
unit °C
unitKey degree_celsius
Installation Guide ECL Portal API
32 DEN-SMT/DK VI.HX.I1.02 Danfoss District Energy
Element Example
name Kr 1, flow temperature ref.
readingValueIndex 4
unit °C
unitKey degree_celsius
Element Example
name Kr 1, supply, return temperature ref.
readingValueIndex 6
unit °C
unitKey degree_celsius
Element Example
name Kr 1, supply, return temperature
readingValueIndex 5
unit °C
unitKey degree_celsius
ECL configurable input, Main water meter
Element Example
type EclConfigInputDevice
externalDeviceId 77df9535-9333-4222-b0a5-b5d6d08da1b3
name Main water meter
active true
createdOnPortal 2013-03-22T06:59:33.0Z
lastRead 2013-04-29T09:06:00.0Z
configInputType Pulse
configInputSensorId S17
Element Example
name Main water meter
readingValueIndex 1
unit m³
unitKey cubic_metre
configSensorId S17
Installation Guide ECL Portal API
3333Danfoss District Energy VI.HX.I1.02 DEN-SMT/DK
9.1.5 Extracting readings
This section describes the use of the web API to extract readings.
In order to be able to extract readings for a given period (rather than, for example, just the last reading), it is a requirement that you know the device’s external ID (which is contained in the master data), and under all circumstances you need to know which values in a reading represent what (which channel), and in which unit it is measured (also contained in the master data).
There is thus a need to know the master data for one reason or another. Whether you retrieve master data for an ECL controller immediately before retrieving data for it, or you use cached master data, depends on the user scenario in the third party application. There will, however, be a need to retrieve updated master data at intervals, as the customer may make changes to the setup without informing the third party. However, if readings are to be requested over several pages, it is not necessary to request master data for each page. The following scenarios assume that you have master data available for the ECL controller, in one way or another, before retrieving the data for the readings.
9.1.6 Read the latest values for one or more sensors on a meter connected to the ECL controller
Retrieving the latest reading (which contains one value for each sensor/channel) for a meter/device connected to the ECL controller takes place by making one single call to the web API. This can take the form of a request to the REST endpoint, and the response will be in JSON format.
Many of the input parameters are essentially set up to read the latest value, which is why you only need to define a few parameters in the call. In addition to the identification parameters (server code, ECL serial number and third party code), only the meter’s/device’s external ID (externalDeviceId) from the master data needs to be specified in the call.
Installation Guide ECL Portal API
34 DEN-SMT/DK VI.HX.I1.02 Danfoss District Energy
9.1.7 Reading the most recently measured outdoor temperature
The outdoor temperature is measured via the ECL log, which has the externalDeviceId = 2cc34b74-2c42-4ad1-a6c4-f27876b1c799, cf. the master data, which is why this value is included in the request.
Request:
https://eclwebapi.danfoss.dk/readings/v1/123456792?serverCode=FirmaA&eclAccessCode=Kode5&externalDeviceId=2cc34b74-2c42-4ad1-a6c4-f27876b1c799
The following master data is returned:
direction backward
page 1
pageSize 1
resultReadings 1
The following reading is also returned in the same response message:
Element Example
timestamp 2013-04-29T09:00:00.0Z
receivedTime 2013-04-18T09:08:31.0Z
manualEntry False
value1 9.84
value2 192
value3 63.95
value4 65
value5 39.14
value6 65
value7 44.98
value8 50
value9 54
value10 28.48
value11 27.16
value12 32.61
value13 31.53
value14 192
Because the master data defines that the device in question has 14 channels, each reading for this device will have 14 values. It can also be seen from the master data that the outdoor temperature has readingValueIndex = 1, and that the unit is °C, i.e. that the value in °C must exist as value1 (the others are not of interest in this case), which in this case is 9.84.
Installation Guide ECL Portal API
3535Danfoss District Energy VI.HX.I1.02 DEN-SMT/DK
9.1.8 Reading of Energy, Volume, Flow temperature and Return temperature for the house’s main meter
The main meter for the house is the M-bus device with externalDeviceId = 8dbb8b99-96a4-498c-b75b-c7453e1ad6c1. The request thus takes place in the same way as above, although with a different ID for the device:
Request:
https://eclwebapi.danfoss.dk/readings/v1/123456792?serverCode=FirmaA&eclAccessCode=Kode5&externalDeviceId=8dbb8b99-96a4-498c-b75b-c7453e1ad6c1
The following master data is returned:
Element Example
timestamp 2013-04-29T09:05:00.0Z
receivedTime 2013-04-18T09:08:35.0Z
manualEntry False
value1 1.9378E7
value2 1546.838
value3 61.3
value4 42.4
Interest has been expressed here in all 4 values, and according to the master data the following was read at 9:05: • Energy(readingValueIndex1):1.9378E7Wh• Volume(readingValueIndex2):1546.838m³• Flowtemperature(readingValueIndex3):61.3°C• Returnflowtemperature(readingValueIndex4):42.4°C
9.1.9 Read the latest value for one or more sensors across meters connected to the ECL controller.
Reading of the latest value across meters/devices takes place according to exactly the same principle as for one single device. The difference in the request is that you enter * instead of a specific externalDeviceId. There will still be just one request and one response from the server. The difference in the response message is that you will receive not just one reading, but instead one reading per device, which in our example will mean 6 readings (3 x M-bus, 2 x ECL log and 1 configurable input) in same message.
Request:
https://eclwebapi.danfoss.dk/readings/v1/123456792?serverCode=FirmaA&eclAccessCode=Kode5&externalDeviceId=*
9.1.10 Read a period of historical data for one or more sensors on one meter connected to the ECL controller.
Just as when reading the last reading, the readings in this case also include values for all channels/sensors on the meter, if several channels are available. But when reading data for a given period, it will not be possible to request across devices on the ECL controller, but always only one log device at a time. It is the same method being called, but with several arguments, and you may have to call the method several times in order to “cover” the desired period (depending on page size, log frequency and the length of the period).
Installation Guide ECL Portal API
36 DEN-SMT/DK VI.HX.I1.02 Danfoss District Energy
Our starting point is that we want to retrieve all data for the main water meter. There is, cf. the master data, a configurable input module (of the pulse type with externalDeviceId = 77df9535-9333-4222-b0a5-b5d6d08da1b3), that has only 1 channel, where pulses are measures converted into m3. We can also see from the master data that the latest data is from 2013-04-29T09:06:00.0Z, and that it was first sensed by the portal at 2013-03-22T06:59:33.0Z. In this example we assume that a page size of 500 is most suitable for the third party client.
Request:
https://eclwebapi.danfoss.dk/readings/v1/123456792?serverCode=FirmaA&eclAccessCode=Kode5&externalDeviceId=77df9535-9333-4222-b0a5-b5d6d08da1b3&direction=forward&from=2013-03-22T00:00:00.0Z&pageSize=500&page=1
We start by requesting data as follows:
Parameter Example
serverCode CompanyA
eclSerial 123456792
eclAccessCode Code5
externalDeviceId 77df9535-9333-4222-b0a5-b5d6d08da1b3
from * 2013-03-22T00:00:00.0Z
direction forward
page 1
pageSize 500
clientRequestId 355b7f4d-7e1a-4d76-a4f0-be8fb52b7c80
Installation Guide ECL Portal API
3737Danfoss District Energy VI.HX.I1.02 DEN-SMT/DK
The following master data is returned:
Element Example
clientRequestId 355b7f4d-7e1a-4d76-a4f0-be8fb52b7c80
serverRequestId 9cd4df10-09cc-4ec7-8b4e-c1180b21d9f9
from 2013-03-22T00:00:00.0Z
direction forward
page 1
pageSize 500
resultReadings 500
totalReadings 915
totalPages 2
The following readings are also returned in the same response message:
Element Example
timestamp 2013-03-22T07:06:00.0Z
receivedTime 2013-03-22T07:08:24.0Z
manualEntry False
value1 0
… 498 other readings…
Element Example
timestamp 2013-04-12T02:08:00.0Z
receivedTime 2013-04-12T02:10:12.0Z
manualEntry False
value1 10.05
We then request one more page of data, as the first response indicated that there were 2 pages of data available:
Request:
https://eclwebapi.danfoss.dk/readings/v1/123456792?serverCode=FirmaA&eclAccessCode=Kode5&externalDeviceId=77df9535-9333-4222-b0a5-b5d6d08da1b3&direction=forward&from=2013-03-22T00:00:00.0Z&pageSize=500&page=2
Installation Guide ECL Portal API
38 DEN-SMT/DK VI.HX.I1.02 Danfoss District Energy
Parameter Example
serverCode CompanyA
eclSerial 123456792
eclAccessCode Code5
externalDeviceId 77df9535-9333-4222-b0a5-b5d6d08da1b3
from * 2013-03-22T00:00:00.0Z
direction forward
page 2
pageSize 500
clientRequestId 855b7f4d-7e1a-4d76-a4f0-be8fb52b7c80
The following master data is returned:
Element Example
clientRequestId 855b7f4d-7e1a-4d76-a4f0-be8fb52b7c80
serverRequestId 1bd4df10-09cc-4ec7-8b4e-c1180b21d9f9
from 2013-03-22T00:00:00.0Z
direction forward
page 2
pageSize 500
resultReadings 415
The following readings are also returned in this second response message, together with the above master data:
Element Example
timestamp 2013-04-12T03:08:00.0Z
receivedTime 2013-04-12T03:10:31.0Z
manualEntry False
value1 10.05
… 413 other readings…
Element Example
timestamp 2013-04-29T09:06:00.0Z
receivedTime 2013-04-29T09:08:35.0Z
manualEntry False
value1 15.32
Installation Guide ECL Portal API
3939Danfoss District Energy VI.HX.I1.02 DEN-SMT/DK
9.2 Format differences in data extracted
Data extracted through the ECL Portal and the download in, for example, Excel format will be scaled to have only one decimal place, but data extracted through the ECL Portal API can contain a number of decimals depending on the raw data contained in the database.
Example of data download via the ECL Portal:
The same data downloaded via the web API:
Also note that the header for the data is different, cf. section 7.2.2 Master data.