General Guide
The following guide illustrates how Wundafloor warm water underfloor heating systems can be coupled together
with the majority of central heating plumbing and control systems.
The majority of modern central heating systems make use of motorised valves, often called Zone valves, to divide
different heating systems and hot water generation ie. Radiators, Under Floor Heating and Hot water cylinder.
Systems using combination boilers will also need zone valves if separate systems of heating require different times
and temperatures.
Quite often ground and first floors are controlled separately as they may have different uses. The zone valve acts
like a relay, meaning any system can call the boiler/ heat source without other areas being activated.
If the underfloor system is being encorporated alongside a radiator system it is even more important that these
areas are controlled independently as ‘heat up’ and ‘cooling off’ times are different. We recommend the ‘S’ plan
layout is adopted as this allows for more variety in zoning, and should be very familiar to qualified plumber/
electricians. The schematics show typical S-plan heating systems with under floor heating encorporated.
NOTE:An Auto By-Pass valve (ABV) should be incorporated in all systems.
NOTE:If a Heat pump manifold has been supplied then there will be no pump on the manifold. Therefore the relay on
the H-Box wiring centre is used to switch on a shunt pump which will send primary water from a
buffer tank or the heatpump itself to the manifolds.
Wundafloor does not supply:• ‘S’ plan wiring centre
• Cylinder thermostat
• Hot water time clock
• Auto bypass valve
Motorised / Zone valves and Pipe stats are available if requested.
Plumbing and Wiring SchematicsSection ASystem Boiler with hot water cylinder, radiators & UFH1a) Plumbing Schematic
2a) Multi Zone Wiring Schematic
3a) Single Zone Wiring Schematic
Section BCombination Boiler with radiators & UFH1b) Plumbing Schematic
2b) Multi Zone Wiring Schematic
3b) Single Zone Wiring Schematic
Section CAdding Single Zone kit to exisiting radiator system1c) Plumbing Schematic
2c) Wiring Schematic
3c) Plumbing Schematic (Danfoss kit)
Section DH-Box-12 Wiring Schematics1d) H-Box-12 V1.2
2d) H-Box-12 (previous model)
Section EInstalling a Wet Room Thermostat
Section FSchematic - Wireless Control Centre E8.583RF
Section GSchematic - Wireless Receiver (single zone) E8.413RF / E8.423RF
E09Installation guide - wiring & plumbing
✆ 0800 5420 816 www.wundafloorheating.co.ukTHE BRAND YOU CAN TRUST
Revision Date: 5/10/2017
2
Radiators
Zone Valves
Circulationpump
HWC
BoilerABV
Under FloorHeating systemsupplied byWunda
Section A 1A : Schematic - System Boiler with hot water cylinder, radiators & UFH
E09Installation guide - wiring & plumbing
✆ 0800 5420 816 www.wundafloorheating.co.ukTHE BRAND YOU CAN TRUST
Revision Date: 5/10/2017
3
7
This drawing is forguidance only.All installationsshould be undertakenby aqualified person only.
Wiring Key
Orange
Grey
BrownB
O
G
L N E
230V50Hz
Some Earths & Neutralsomitted for clarity
1 2 3 4 5 6 7 8 9 10
BoilerRadiatorsRoom Stat
L N L1
M
B
O
GM
O
G
UnderfloorHeating pump
EL
N
N LHTon
HWSon
Time Clock 00:00
Hot waterCylinder Stat
1 C
RadiatorsZone Valve
M G
UFHZone Valve
O
B
CirculatingPumpOmitted forclarity
L N SL
B
Hot WaterZone Valve
L N L1
This drawing is forguidance only.All installationsshould be undertakenby aqualified person only.
Wiring Key
Orange
Grey
BrownB
O
G
L N E
230V50Hz
Some Earths & Neutralsomitted for clarity
1 2 3 4 5 6 7 8 9 10
BoilerRadiatorsRoom Stat
L N L1
M
B
O
GM
O
G
Wundafloor wiring centre used withmultiple Programmable thermostats onUFH system.
UnderfloorHeating pump
EL
N
N LHTon
HWSon
Time Clock 00:00
Hot waterCylinder Stat
1 C
RadiatorsZone Valve
M G
UFHZone Valve
O
B
CirculatingPumpOmitted forclarity
Switch Relay
PumpRelayL N SL
B
Hot WaterZone Valve
230vInput
Wundafloor ProgrammableThermostat
*
*Thermostat may be powered from a seperated (localised) fused spur.
**Standard dial thermostats may be power from a time clock.
**
2A Typical wiring scheme for multi zone UFH system with a System Boiler
3A Typical wiring scheme for single zone UFH system with a System Boiler
S-PlanWiring centre
S-PlanWiring centre
Section A 2A : Typical wiring scheme for multi-zone UHF system with a System Boiler
This drawing is for guidance only. All installations should be undertaken by a qualified person only.
E09Installation guide - wiring & plumbing
✆ 0800 5420 816 www.wundafloorheating.co.ukTHE BRAND YOU CAN TRUST
C 1
Revision Date: 5/10/2017
4
7
This drawing is forguidance only.All installationsshould be undertakenby aqualified person only.
Wiring Key
Orange
Grey
BrownB
O
G
L N E
230V50Hz
Some Earths & Neutralsomitted for clarity
1 2 3 4 5 6 7 8 9 10
BoilerRadiatorsRoom Stat
L N L1
M
B
O
GM
O
G
UnderfloorHeating pump
EL
N
N LHTon
HWSon
Time Clock 00:00
Hot waterCylinder Stat
1 C
RadiatorsZone Valve
M G
UFHZone Valve
O
B
CirculatingPumpOmitted forclarity
L N SL
B
Hot WaterZone Valve
L N L1
This drawing is forguidance only.All installationsshould be undertakenby aqualified person only.
Wiring Key
Orange
Grey
BrownB
O
G
L N E
230V50Hz
Some Earths & Neutralsomitted for clarity
1 2 3 4 5 6 7 8 9 10
BoilerRadiatorsRoom Stat
L N L1
M
B
O
GM
O
G
Wundafloor wiring centre used withmultiple Programmable thermostats onUFH system.
UnderfloorHeating pump
EL
N
N LHTon
HWSon
Time Clock 00:00
Hot waterCylinder Stat
1 C
RadiatorsZone Valve
M G
UFHZone Valve
O
B
CirculatingPumpOmitted forclarity
Switch Relay
PumpRelayL N SL
B
Hot WaterZone Valve
230vInput
Wundafloor ProgrammableThermostat
*
*Thermostat may be powered from a seperated (localised) fused spur.
**Standard dial thermostats may be power from a time clock.
**
2A Typical wiring scheme for multi zone UFH system with a System Boiler
3A Typical wiring scheme for single zone UFH system with a System Boiler
S-PlanWiring centre
S-PlanWiring centre
Section A 3A : Typical wiring scheme for single zone UHF system with a System Boiler
This drawing is for guidance only. All installations should be undertaken by a qualified person only.
E09Installation guide - wiring & plumbing
✆ 0800 5420 816 www.wundafloorheating.co.ukTHE BRAND YOU CAN TRUST
C 1
Revision Date: 5/10/2017
E09Installation guide - wiring & plumbing
✆ 0800 5420 816 www.wundafloorheating.co.ukTHE BRAND YOU CAN TRUST
Revision Date: 5/10/2017
6
8
Wiring Key
Orange
Grey
BrownB
O
G
Wiring Schematic A
Some Earths & Neutralsomitted for clarity
1 2 3 4 5 6 7 8 9 10
Combi Boiler+ Time Clock
00:00L N SL SI
RAD roomstat
L N L1
M
B
O
GM
B
O
G
L N E230V50Hz
Wundafloor wiring centre used with multipleProgrammable thermostats on UFH system.
UnderfloorHeating pump
EL
N
UnderfloorZone valve
RadiatorsZone valve
Wiring Key
Orange
Grey
BrownB
O
G
1 2 3 4 5 6 7 8 9 10
Combi Boiler+ Time Clock
00:00L N SL SI
L N L1
RAD roomstat
L N L1
UnderfloorHeating pump
M
EL
N
B
O
GM
B
O
G
L N E
230V50Hz
SomeEarths &Neutrals
omitted forclarity
UnderfloorZone valve
RadiatorsZone valve
*Thermostat may be powered from a seperated (localised) fused spur.
**Standard dial thermostats may be power from a time clock.
***
Wundafloor ProgrammableThermostat
S-PlanWiring centre
S-PlanWiring centre
2B Typical wiring scheme for multi zone UFH with a combination boiler
3B Typical wiring scheme for single zone UFH with a combination boiler
This drawing is for guidance only.All installations should be undertaken by aqualified person only.
This drawing is for guidance only.All installations should be undertaken by aqualified person only.
Section B 2B : Typical wiring scheme for multi zone UHF system with a Combination Boiler
This drawing is for guidance only. All installations should be undertaken by a qualified person only.
Switch Relay
Pump Relay
230v Input
E09Installation guide - wiring & plumbing
✆ 0800 5420 816 www.wundafloorheating.co.ukTHE BRAND YOU CAN TRUST
Revision Date: 5/10/2017
7
8
Wiring Key
Orange
Grey
BrownB
O
G
Wiring Schematic A
Some Earths & Neutralsomitted for clarity
1 2 3 4 5 6 7 8 9 10
Combi Boiler+ Time Clock
00:00L N SL SI
RAD roomstat
L N L1
M
B
O
GM
B
O
G
L N E230V50Hz
Wundafloor wiring centre used with multipleProgrammable thermostats on UFH system.
UnderfloorHeating pump
EL
N
UnderfloorZone valve
RadiatorsZone valve
Wiring Key
Orange
Grey
BrownB
O
G
1 2 3 4 5 6 7 8 9 10
Combi Boiler+ Time Clock
00:00L N SL SI
L N L1
RAD roomstat
L N L1
UnderfloorHeating pump
M
EL
N
B
O
GM
B
O
G
L N E
230V50Hz
SomeEarths &Neutrals
omitted forclarity
UnderfloorZone valve
RadiatorsZone valve
*Thermostat may be powered from a seperated (localised) fused spur.
**Standard dial thermostats may be power from a time clock.
***
Wundafloor ProgrammableThermostat
S-PlanWiring centre
S-PlanWiring centre
2B Typical wiring scheme for multi zone UFH with a combination boiler
3B Typical wiring scheme for single zone UFH with a combination boiler
This drawing is for guidance only.All installations should be undertaken by aqualified person only.
This drawing is for guidance only.All installations should be undertaken by aqualified person only.
Section B 3B : Typical wiring scheme for single zone UHF system with a Combination Boiler
This drawing is for guidance only. All installations should be undertaken by a qualified person only.
E09Installation guide - wiring & plumbing
✆ 0800 5420 816 www.wundafloorheating.co.ukTHE BRAND YOU CAN TRUST
Revision Date: 5/10/2017
8
Radiators
Revision Date: 5/10/2017
Combi or System Boiler
ABV
Under FloorHeating systemsupplied byWunda
Connections to existing radiator flow & return
Section C 1C : Schematic - Adding single area UFH to an existing radiator system
*
*
*
HWC
E09Installation guide - wiring & plumbing
✆ 0800 5420 816 www.wundafloorheating.co.ukTHE BRAND YOU CAN TRUST
9
10
This is when a single zone underfloorheating kit is connected to an existingradiator system without an individual zonevalve for the UFH and therefore unable tocall the boiler/heat source independentlyfor heat.
Although a room thermostat or program-mable thermostat can be used to controlair temperature, this area can only be ONwhen the existing heating system is ON.
When this is the case, a pipe thermostatcan be attached to the heating mains flow,so that the new area of the underfloorknows when hot water is available andtherefore stops the pump running when noheat is available.
UnderfloorHeating pump
L N L1
EL
N
Pipe thermostatset at 35°C
L N E
230V50Hz
1 2 3 4 5 6 7 8 9 10
Wundafloor ProgrammableThermostat
*A standard dial thermostat may be power from a time clock.
*
2C wiring schematic for single zone kit added to radiator system
Terminal Block
Section C 2C : Wiring schematic for single zone kit added to radiator system
This is when a single zone underfloor heating kit is connected to an existing radiator system without an individual zone valve for the UFH and therefore unable to call the boiler/heat source independently for heat.
Although a room thermostat or programmable thermostat can be used to control air temperature, this area can only be ON when the existing heating system is ON.
When this is the case, a pipe thermostat can be attached to the heating mains flow, so that the new area of the underfloor knows when hot water is available and therefore stops the pump running when no heat is available.
This drawing is for guidance only. All installations should be undertaken by a qualified person only.
E09Installation guide - wiring & plumbing
✆ 0800 5420 816 www.wundafloorheating.co.ukTHE BRAND YOU CAN TRUST
Revision Date: 5/10/2017
10
Radiators
Danfoss FHV-R
HWC
Combi or System Boiler
ABV
Connections to existing radiator flow & return
This diagram show how a Danfoss FHV-R is connected to and existing radiator system.
Please note:• The valve should be used with a maximum of 100m of 16mm Wundapipe.• The valve must be positioned on the return from the heated floor.• It is recommended that isolation valves are used for filling and maintenance.• The supply pipework must not be less than 15mm.• The heating engineer must check that the is adquate flow available from the heating mains.
Section C 3C : Schematic - Danfoss FHV-R Kit to an existing radiator system
*
*
*
E09Installation guide - wiring & plumbing
✆ 0800 5420 816 www.wundafloorheating.co.ukTHE BRAND YOU CAN TRUST
Revision Date: 5/10/2017
11
11
Wiring centre - H-Box-12
LNL1L1N
Transformer
Ground
FUS
E (m
ax. 1
0A)
2 x
5mm
FA
ST
BLO
W
From main heating controlsPower input (230VAC, 50/60Hz)
LN
N L
Manifoldpump
Max. 4 actuators can belinked to one room stat
TimerRTS 80.70
LIVE - 1N - 2SL - 4
Boiler / zone valve switchVoltage free OR with link 230V
LN
L N
*Optional Link
*
Voltage Free SwitchWith Optional Link fitted - Can be used as a 230v switch live output to zone valve or boiler/heat sourceWithout Optional Link fitted - Can be used as low voltage switching for Boiler/heat source
*
V1.2
°L.E.D.
(Identifiable by model No. ZDA0003-V1.2 on PCB and addition of L.E.D.)
Dimension (mm) 310 W x 110 H x 55 DAmbient temperature 0°C-50°C
Relay Output(2 minutes delay) (230V AC, 3A)
Two Relays will be engaged whenever one or morethermostats call for heating.
The relays will be disengaged when all the zonethermostats stop heating activity
Technical Data.Supply voltage 230V AC, 50/60HzOutput voltage 230V AC,50/60HzMax.Load 4ANumber of zone outputs 12 zones
Left Hand: 1 x potential free relay outputRight Hand:1 x independent relay output
Current Model
L N L1
Room thermostat Terminal Note
T6360C 2 6 3 Link 3-5
RTC86.13 1 2 4 Sensor 6 - 7
1 2 4 Sensor 6 - 7
RTC75.713T
Button room stat
E91.713Touch screen room ‘stat
1 2 3 Sensor 6 - 7
RTC84.13 1 2 4 -
11
Wiring centre - H-Box-12
LNL1L1N
Transformer
Ground
FUS
E (m
ax. 1
0A)
2 x
5mm
FA
ST
BLO
W
From main heating controlsPower input (230VAC, 50/60Hz)
LN
N L
Manifoldpump
Max. 4 actuators can belinked to one room stat
TimerRTS 80.70
LIVE - 1N - 2SL - 4
Boiler / zone valve switchVoltage free OR with link 230V
LN
L N
*Optional Link
*
Voltage Free SwitchWith Optional Link fitted - Can be used as a 230v switch live output to zone valve or boiler/heat sourceWithout Optional Link fitted - Can be used as low voltage switching for Boiler/heat source
*
V1.2
°L.E.D.
(Identifiable by model No. ZDA0003-V1.2 on PCB and addition of L.E.D.)
Dimension (mm) 310 W x 110 H x 55 DAmbient temperature 0°C-50°C
Relay Output(2 minutes delay) (230V AC, 3A)
Two Relays will be engaged whenever one or morethermostats call for heating.
The relays will be disengaged when all the zonethermostats stop heating activity
Technical Data.Supply voltage 230V AC, 50/60HzOutput voltage 230V AC,50/60HzMax.Load 4ANumber of zone outputs 12 zones
Left Hand: 1 x potential free relay outputRight Hand:1 x independent relay output
Current Model
L N L1
Room thermostat Terminal Note
T6360C 2 6 3 Link 3-5
RTC86.13 1 2 4 Sensor 6 - 7
1 2 4 Sensor 6 - 7
RTC75.713T
Button room stat
E91.713Touch screen room ‘stat
1 2 3 Sensor 6 - 7
RTC84.13 1 2 4 -
11
Wiring centre - H-Box-12
LNL1L1N
Transformer
Ground
FUS
E (m
ax. 1
0A)
2 x
5mm
FA
ST
BLO
W
From main heating controlsPower input (230VAC, 50/60Hz)
LN
N L
Manifoldpump
Max. 4 actuators can belinked to one room stat
TimerRTS 80.70
LIVE - 1N - 2SL - 4
Boiler / zone valve switchVoltage free OR with link 230V
LN
L N
*Optional Link
*
Voltage Free SwitchWith Optional Link fitted - Can be used as a 230v switch live output to zone valve or boiler/heat sourceWithout Optional Link fitted - Can be used as low voltage switching for Boiler/heat source
*
V1.2
°L.E.D.
(Identifiable by model No. ZDA0003-V1.2 on PCB and addition of L.E.D.)
Dimension (mm) 310 W x 110 H x 55 DAmbient temperature 0°C-50°C
Relay Output(2 minutes delay) (230V AC, 3A)
Two Relays will be engaged whenever one or morethermostats call for heating.
The relays will be disengaged when all the zonethermostats stop heating activity
Technical Data.Supply voltage 230V AC, 50/60HzOutput voltage 230V AC,50/60HzMax.Load 4ANumber of zone outputs 12 zones
Left Hand: 1 x potential free relay outputRight Hand:1 x independent relay output
Current Model
L N L1
Room thermostat Terminal Note
T6360C 2 6 3 Link 3-5
RTC86.13 1 2 4 Sensor 6 - 7
1 2 4 Sensor 6 - 7
RTC75.713T
Button room stat
E91.713Touch screen room ‘stat
1 2 3 Sensor 6 - 7
RTC84.13 1 2 4 -
*Voltage Free Switch• With Optional Link fitted - Can be used as a 230v switch live output to zone valve or boiler/heat source
• Without Optional Link fitted - Can be used as low voltage switching for Boiler/heat source
RTC75.713TButton room stat
E91.713Touch screen room stat
Sensor 6 - 71 2 3
E09Installation guide - wiring & plumbing
✆ 0800 5420 816 www.wundafloorheating.co.ukTHE BRAND YOU CAN TRUST
Transformer
N L
11
Wiring centre - H-Box-12
LNL1L1N
Transformer
Ground
FUS
E (m
ax. 1
0A)
2 x
5mm
FA
ST
BLO
W
From main heating controlsPower input (230VAC, 50/60Hz)
LN
N L
Manifoldpump
Max. 4 actuators can belinked to one room stat
TimerRTS 80.70
LIVE - 1N - 2SL - 4
Boiler / zone valve switchVoltage free OR with link 230V
LN
L N
*Optional Link
*
Voltage Free SwitchWith Optional Link fitted - Can be used as a 230v switch live output to zone valve or boiler/heat sourceWithout Optional Link fitted - Can be used as low voltage switching for Boiler/heat source
*
V1.2
°L.E.D.
(Identifiable by model No. ZDA0003-V1.2 on PCB and addition of L.E.D.)
Dimension (mm) 310 W x 110 H x 55 DAmbient temperature 0°C-50°C
Relay Output(2 minutes delay) (230V AC, 3A)
Two Relays will be engaged whenever one or morethermostats call for heating.
The relays will be disengaged when all the zonethermostats stop heating activity
Technical Data.Supply voltage 230V AC, 50/60HzOutput voltage 230V AC,50/60HzMax.Load 4ANumber of zone outputs 12 zones
Left Hand: 1 x potential free relay outputRight Hand:1 x independent relay output
Current Model
L N L1
Room thermostat Terminal Note
T6360C 2 6 3 Link 3-5
RTC86.13 1 2 4 Sensor 6 - 7
1 2 4 Sensor 6 - 7
RTC75.713T
Button room stat
E91.713Touch screen room ‘stat
1 2 3 Sensor 6 - 7
RTC84.13 1 2 4 -
11
Wiring centre - H-Box-12
LNL1L1N
Transformer
GroundFU
SE
(max
. 10A
)2
x 5m
m F
AS
T B
LOW
From main heating controlsPower input (230VAC, 50/60Hz)
LN
N L
Manifoldpump
Max. 4 actuators can belinked to one room stat
TimerRTS 80.70
LIVE - 1N - 2SL - 4
Boiler / zone valve switchVoltage free OR with link 230V
LN
L N
*Optional Link
*
Voltage Free SwitchWith Optional Link fitted - Can be used as a 230v switch live output to zone valve or boiler/heat sourceWithout Optional Link fitted - Can be used as low voltage switching for Boiler/heat source
*
V1.2
°L.E.D.
(Identifiable by model No. ZDA0003-V1.2 on PCB and addition of L.E.D.)
Dimension (mm) 310 W x 110 H x 55 DAmbient temperature 0°C-50°C
Relay Output(2 minutes delay) (230V AC, 3A)
Two Relays will be engaged whenever one or morethermostats call for heating.
The relays will be disengaged when all the zonethermostats stop heating activity
Technical Data.Supply voltage 230V AC, 50/60HzOutput voltage 230V AC,50/60HzMax.Load 4ANumber of zone outputs 12 zones
Left Hand: 1 x potential free relay outputRight Hand:1 x independent relay output
Current Model
L N L1
Room thermostat Terminal Note
T6360C 2 6 3 Link 3-5
RTC86.13 1 2 4 Sensor 6 - 7
1 2 4 Sensor 6 - 7
RTC75.713T
Button room stat
E91.713Touch screen room ‘stat
1 2 3 Sensor 6 - 7
RTC84.13 1 2 4 -
Section D 1D : Schematic - Wiring Centre - H-Box-12 V1.2 PCB version H-Box-12 V1.4 (Current model)
(Identifiable by model no. H-box212_V1.4 on PCB)
11
Section D 1D : Schematic - Wiring Centre - H-Box-12 V1.2 (current model)
11
Wiring centre - H-Box-12
LNL1L1N
Transformer
Ground
FUS
E (m
ax. 1
0A)
2 x
5mm
FA
ST
BLO
W
From main heating controlsPower input (230VAC, 50/60Hz)
LN
N L
Manifoldpump
Max. 4 actuators can belinked to one room stat
TimerRTS 80.70
LIVE - 1N - 2SL - 4
Boiler / zone valve switchVoltage free OR with link 230V
LN
L N
*Optional Link
*
Voltage Free SwitchWith Optional Link fitted - Can be used as a 230v switch live output to zone valve or boiler/heat sourceWithout Optional Link fitted - Can be used as low voltage switching for Boiler/heat source
*
V1.2
°L.E.D.
(Identifiable by model No. ZDA0003-V1.2 on PCB and addition of L.E.D.)
Dimension (mm) 310 W x 110 H x 55 DAmbient temperature 0°C-50°C
Relay Output(2 minutes delay) (230V AC, 3A)
Two Relays will be engaged whenever one or morethermostats call for heating.
The relays will be disengaged when all the zonethermostats stop heating activity
Technical Data.Supply voltage 230V AC, 50/60HzOutput voltage 230V AC,50/60HzMax.Load 4ANumber of zone outputs 12 zones
Left Hand: 1 x potential free relay outputRight Hand:1 x independent relay output
Current Model
L N L1
Room thermostat Terminal Note
T6360C 2 6 3 Link 3-5
RTC86.13 1 2 4 Sensor 6 - 7
1 2 4 Sensor 6 - 7
RTC75.713T
Button room stat
E91.713Touch screen room ‘stat
1 2 3 Sensor 6 - 7
RTC84.13 1 2 4 -
11
Wiring centre - H-Box-12
LNL1L1N
Transformer
Ground
FUS
E (m
ax. 1
0A)
2 x
5mm
FA
ST
BLO
W
From main heating controlsPower input (230VAC, 50/60Hz)
LN
N L
Manifoldpump
Max. 4 actuators can belinked to one room stat
TimerRTS 80.70
LIVE - 1N - 2SL - 4
Boiler / zone valve switchVoltage free OR with link 230V
LN
L N
*Optional Link
*
Voltage Free SwitchWith Optional Link fitted - Can be used as a 230v switch live output to zone valve or boiler/heat sourceWithout Optional Link fitted - Can be used as low voltage switching for Boiler/heat source
*
V1.2
°L.E.D.
(Identifiable by model No. ZDA0003-V1.2 on PCB and addition of L.E.D.)
Dimension (mm) 310 W x 110 H x 55 DAmbient temperature 0°C-50°C
Relay Output(2 minutes delay) (230V AC, 3A)
Two Relays will be engaged whenever one or morethermostats call for heating.
The relays will be disengaged when all the zonethermostats stop heating activity
Technical Data.Supply voltage 230V AC, 50/60HzOutput voltage 230V AC,50/60HzMax.Load 4ANumber of zone outputs 12 zones
Left Hand: 1 x potential free relay outputRight Hand:1 x independent relay output
Current Model
L N L1
Room thermostat Terminal Note
T6360C 2 6 3 Link 3-5
RTC86.13 1 2 4 Sensor 6 - 7
1 2 4 Sensor 6 - 7
RTC75.713T
Button room stat
E91.713Touch screen room ‘stat
1 2 3 Sensor 6 - 7
RTC84.13 1 2 4 -
(identifiable by model No. ZDA0003-V1.2 on PCB and addition of L.E.D.)
*Voltage Free Switch• With Optional Link fitted - Can be used as a 230v switch live output to zone valve or boiler/heat source
• Without Optional Link fitted - Can be used as low voltage switching for Boiler/heat source
RTC75.713TButton room stat
E91.713Touch screen room stat
Sensor 6 - 71 2 3
E09Installation guide - wiring & plumbing
✆ 0800 5420 816 www.wundafloorheating.co.ukTHE BRAND YOU CAN TRUST
Revision Date: 5/10/2017
11
Section D 1D : Schematic - Wiring Centre - H-Box-12 V1.2 (current model)
11
Wiring centre - H-Box-12
LNL1L1N
Transformer
Ground
FUS
E (m
ax. 1
0A)
2 x
5mm
FA
ST
BLO
W
From main heating controlsPower input (230VAC, 50/60Hz)
LN
N L
Manifoldpump
Max. 4 actuators can belinked to one room stat
TimerRTS 80.70
LIVE - 1N - 2SL - 4
Boiler / zone valve switchVoltage free OR with link 230V
LN
L N
*Optional Link
*
Voltage Free SwitchWith Optional Link fitted - Can be used as a 230v switch live output to zone valve or boiler/heat sourceWithout Optional Link fitted - Can be used as low voltage switching for Boiler/heat source
*
V1.2
°L.E.D.
(Identifiable by model No. ZDA0003-V1.2 on PCB and addition of L.E.D.)
Dimension (mm) 310 W x 110 H x 55 DAmbient temperature 0°C-50°C
Relay Output(2 minutes delay) (230V AC, 3A)
Two Relays will be engaged whenever one or morethermostats call for heating.
The relays will be disengaged when all the zonethermostats stop heating activity
Technical Data.Supply voltage 230V AC, 50/60HzOutput voltage 230V AC,50/60HzMax.Load 4ANumber of zone outputs 12 zones
Left Hand: 1 x potential free relay outputRight Hand:1 x independent relay output
Current Model
L N L1
Room thermostat Terminal Note
T6360C 2 6 3 Link 3-5
RTC86.13 1 2 4 Sensor 6 - 7
1 2 4 Sensor 6 - 7
RTC75.713T
Button room stat
E91.713Touch screen room ‘stat
1 2 3 Sensor 6 - 7
RTC84.13 1 2 4 -
11
Wiring centre - H-Box-12
LNL1L1N
Transformer
Ground
FUS
E (m
ax. 1
0A)
2 x
5mm
FA
ST
BLO
W
From main heating controlsPower input (230VAC, 50/60Hz)
LN
N L
Manifoldpump
Max. 4 actuators can belinked to one room stat
TimerRTS 80.70
LIVE - 1N - 2SL - 4
Boiler / zone valve switchVoltage free OR with link 230V
LN
L N
*Optional Link
*
Voltage Free SwitchWith Optional Link fitted - Can be used as a 230v switch live output to zone valve or boiler/heat sourceWithout Optional Link fitted - Can be used as low voltage switching for Boiler/heat source
*
V1.2
°L.E.D.
(Identifiable by model No. ZDA0003-V1.2 on PCB and addition of L.E.D.)
Dimension (mm) 310 W x 110 H x 55 DAmbient temperature 0°C-50°C
Relay Output(2 minutes delay) (230V AC, 3A)
Two Relays will be engaged whenever one or morethermostats call for heating.
The relays will be disengaged when all the zonethermostats stop heating activity
Technical Data.Supply voltage 230V AC, 50/60HzOutput voltage 230V AC,50/60HzMax.Load 4ANumber of zone outputs 12 zones
Left Hand: 1 x potential free relay outputRight Hand:1 x independent relay output
Current Model
L N L1
Room thermostat Terminal Note
T6360C 2 6 3 Link 3-5
RTC86.13 1 2 4 Sensor 6 - 7
1 2 4 Sensor 6 - 7
RTC75.713T
Button room stat
E91.713Touch screen room ‘stat
1 2 3 Sensor 6 - 7
RTC84.13 1 2 4 -
(identifiable by model No. ZDA0003-V1.2 on PCB and addition of L.E.D.)
*Voltage Free Switch• With Optional Link fitted - Can be used as a 230v switch live output to zone valve or boiler/heat source
• Without Optional Link fitted - Can be used as low voltage switching for Boiler/heat source
RTC75.713TButton room stat
E91.713Touch screen room stat
Sensor 6 - 71 2 3
E09Installation guide - wiring & plumbing
✆ 0800 5420 816 www.wundafloorheating.co.ukTHE BRAND YOU CAN TRUST
(Previous model)
(Identifiable by model no. ZDA0003-V1.2)
2D
Revision Date: 5/10/2017
12
13
Section D 3D : Schematic - Wiring Centre - H-Box-12 (previous m- no LED on PCB)
12
Wiring centre - H-Box-12Technical Data.
Supply voltage 230V AC, 50/60HzOutput voltage 230V AC,50/60HzMax.Load 4ANumber of zone outputs 12 zones
Left Hand: 1 x potential free relay outputRight Hand:1 x independent relay output
LNL1L1N
Transformer
Ground
FUS
E (m
ax. 1
0A)
2 x
5mm
FA
ST
BLO
W
From main heating controlsPower input (230VAC, 50/60Hz)
LN
N L
Manifoldpump
Max. 4 actuators can belinked to one room stat
TimerRTS 80.70
LIVE - 1N - 2SL - 4
Boiler / zone valve switchVoltage free OR with link 230V
LN
Optional Link*
Voltage Free SwitchWith Optional Link fitted - Can be used as a 230v switch live output to zone valve or boiler/heat sourceWithout Optional Link fitted - Can be used as low voltage switching for Boiler/heat source
*
*
Dimension (mm) 310 W x 110 H x 55 DAmbient temperature 0°C-50°C
Relay Output(2 minutes delay) (230V AC, 3A)
Two Relays will be engaged whenever one or morethermostats call for heating.
The relays will be disengaged when all the zonethermostats stop heating activity
Previous model
L N L1
Room thermostat Terminal Note
T6360C 2 6 3 Link 3-5
RTC86.13 1 2 4 Sensor 6 - 7
1 2 4 Sensor 6 - 7
RTC75.713T
Button room stat
E91.713Touch screen room ‘stat
1 2 3 Sensor 6 - 7
RTC84.13 1 2 4 -
12
Wiring centre - H-Box-12Technical Data.
Supply voltage 230V AC, 50/60HzOutput voltage 230V AC,50/60HzMax.Load 4ANumber of zone outputs 12 zones
Left Hand: 1 x potential free relay outputRight Hand:1 x independent relay output
LNL1L1N
Transformer
Ground
FUS
E (m
ax. 1
0A)
2 x
5mm
FA
ST
BLO
W
From main heating controlsPower input (230VAC, 50/60Hz)
LN
N L
Manifoldpump
Max. 4 actuators can belinked to one room stat
TimerRTS 80.70
LIVE - 1N - 2SL - 4
Boiler / zone valve switchVoltage free OR with link 230V
LN
Optional Link*
Voltage Free SwitchWith Optional Link fitted - Can be used as a 230v switch live output to zone valve or boiler/heat sourceWithout Optional Link fitted - Can be used as low voltage switching for Boiler/heat source
*
*
Dimension (mm) 310 W x 110 H x 55 DAmbient temperature 0°C-50°C
Relay Output(2 minutes delay) (230V AC, 3A)
Two Relays will be engaged whenever one or morethermostats call for heating.
The relays will be disengaged when all the zonethermostats stop heating activity
Previous model
L N L1
Room thermostat Terminal Note
T6360C 2 6 3 Link 3-5
RTC86.13 1 2 4 Sensor 6 - 7
1 2 4 Sensor 6 - 7
RTC75.713T
Button room stat
E91.713Touch screen room ‘stat
1 2 3 Sensor 6 - 7
RTC84.13 1 2 4 -
*Voltage Free Switch• With Optional Link fitted - Can be used as a 230v switch live output to zone valve or boiler/heat source
• Without Optional Link fitted - Can be used as low voltage switching for Boiler/heat source
RTC75.713TButton room stat
E91.713Touch screen room stat
Sensor 6 - 71 2 3
E09Installation guide - wiring & plumbing
✆ 0800 5420 816 www.wundafloorheating.co.ukTHE BRAND YOU CAN TRUST
(Old model)
Revision Date: 5/10/2017
14
Section E Installing Wet Room Thermostats
For floor temperature sensing, place probe midway between pipe circuit runs to monitor average floor temperature.
For air temperature, place unit on outside wall of wet room in desired location at height of 1500 mm from floor level.
Check distance between thermostat’s terminal block and probe casing location of wet room’s interior wall is no more than 3 metres.
Do not trim probe sensor to length to ensure the probe wire is long enough to span the distance between the unit’s terminal block, to go through prepared hole through wall and exit into supplied probe housing fixed onto interior wall of wet room at 1500 mm from wet room floor level.
*Bathroom Stat
Unit can be used as a floor temperature sensor or an air temperature sensor.
Bathroom stat on outside of wet room wall
Ensure hole is sealed between wall space and probe housing so that only the wet room air temperature is detected
Probe housing on inside of wet room wall
1500mm 1500mm
* models: RTC86.13, RTC75.713T & E91.713 can be used with a probe
3000mm Probe Probe Housing
Probe Housing
Stat
Max 3000mm distance
E09Installation guide - wiring & plumbing
✆ 0800 5420 816 www.wundafloorheating.co.ukTHE BRAND YOU CAN TRUST
Revision Date: 5/10/2017
Section F Schematic - Wireless Control Centre E8.583RF
Manifold Pump
Max 3 actuators can be connectedto one channel
Boiler / zone valve switch Voltage freeOR with link 230v
*Optional Link
AC230V Input
*Voltage Free Switch• With Optional Link fitted - Can be used as a 230v switch liveoutput to zone valve or boiler/heat source• Without Optional Link fitted - Can be used as low voltage switching for boiler/heat source
Wireless Control Centre E8.583RFParametersVoltage : AC230VCurrent : Max 3AWireless Frequency Output: 433MhzEffective Transmission Distance: 200m empty spaceAmbient Temperature : -5~50°CPump Linkage: 230V sub-outputBoiler/Zone Valve Linkage: Volt free or 230V with linkProtective Housing: Ip40Weight : 1 KG
E8.413RF/E8.423RF Wireless Receiver (Single Zone)
Technical Data
Voltage : AC230V
Current : Max 3A
Wireless Frequency Output: 433Mhz
Effective Transmission Distance: 200m empty space
Ambient Temperature : -5~50°C
Pump Linkage: 230V sub-output
Boiler/Zone Valve Linkage: Volt free or 230V with link
Protective Housing: Ip40
Weight : 1 KG
* Voltage Free Switch• With Optional Link fitted - Can be used as a 230v switch live output to zone valve or boiler/heat source
• Without Optional Link fitted - Can be used as low voltage switching for Boiler/heat source
AC230V Input
Boiler / zone valve switch Voltage freeOR with link 230vMax 3 actuators can be connected
to one channel
Manifold Pump
*Optional link
15
NOTE:Pump and switch relays have a 3 minute delay.
E09Installation guide - wiring & plumbing
✆ 0800 5420 816 www.wundafloorheating.co.ukTHE BRAND YOU CAN TRUST
Revision Date: 5/10/2017
Section G Schematic - Wireless Receiver (single zone) E8.413RF / E8.423RF
Manifold Pump
Max 3 actuators can be connectedto one channel
Boiler / zone valve switch Voltage freeOR with link 230v
*Optional Link
AC230V Input
*Voltage Free Switch• With Optional Link fitted - Can be used as a 230v switch liveoutput to zone valve or boiler/heat source• Without Optional Link fitted - Can be used as low voltage switching for boiler/heat source
Wireless Control Centre E8.583RFParametersVoltage : AC230VCurrent : Max 3AWireless Frequency Output: 433MhzEffective Transmission Distance: 200m empty spaceAmbient Temperature : -5~50°CPump Linkage: 230V sub-outputBoiler/Zone Valve Linkage: Volt free or 230V with linkProtective Housing: Ip40Weight : 1 KG
E8.413RF/E8.423RF Wireless Receiver (Single Zone)
7 6 5 4 3 2 1
7 6 5 4 3 2 1
Sensor*(External Probe)
Sensor*(External Probe)
Potential freeoutput 3A
Main Controlcircuit
L1 N13A
3A
N L
N LL1
E8.413RF
E8.423RF
16
Technical Data
Voltage : AC230V
Current : Max 3A
Wireless Frequency Output: 433Mhz
Effective Transmission Distance: 200m empty space
*External Limitation Value: 300C, 400C and 500C if external probe is fitted. (Factory setting 300C)
Limitation Switch Differential: -20C
Ambient Temperature: -50C – 500C
Protective housing: Ip20
Housing Material: Anti Flammable PC
*OPTIONAL (not supplied with receiver)
E09Installation guide - wiring & plumbing
✆ 0800 5420 816 www.wundafloorheating.co.ukTHE BRAND YOU CAN TRUST