Upload
others
View
3
Download
0
Embed Size (px)
Citation preview
Citadel Architectural Products, Inc. ProCore™
Call (800) 446-8828 or visit www.citadelap.com
Installation Guidelines:One Piece & Two Piece Molding Systems
BE SURE TO READ, UNDERSTAND AND FOLLOW ALL GUIDELINES. Manufacturer guidelines may vary dependingupon specific application and project conditions. The manufacturer should be contacted with questions regardingconditions which vary from the guidelines set forth. Standard carpentry knowledge is required and good construc-tion practice for health, safety and welfare must be followed when installing ProCore™.
TECHNICAL ASSISTANCE
Citadel Architectural Products, Inc.3131-A North Franklin RoadIndianapolis, Indiana 46226phone: (317) 894-9400
(800) 446-8828fax: (317) 894-6333
(800) [email protected]
TABLE OF CONTENTS
Pre-Installation Guidelines.........................................General Work Guidelines...........................................Work Sequence: One Piece Moldings........................Work Sequence: Two Piece Moldings.......................Trim Moldings............................................................Recommended Tooling & Equipment........................Installation Accessories.............................................
259
13171919
SAFETY FIRSTProper protection (i.e. gloves, safety glasses)should be worn at all times to prevent injury fromsharp edges and/or metal shavings.
PROTECT MATERIALWhen installation is not in progress, all paneland accessory units must be kept under protec-tive cover and completely dry.
ENSURE PROPER FITProper fit is very important to the appearance ofthe system. Allowance for expansion is needed,as well as notching and/or mitering of trim.
LIBERALLY APPLY SEALANTALL joints must be sealed against moistureintrusion or the warranty will VOID. If donecorrectly, excess sealant will squeeze from thejoints (to be removed later in the sequence).
REMOVE PROTECTIVE FILMUpon completion, the protective film must beremoved from the painted surface. Failure to doso promptly may cause difficulty in removal andpossibly leave an adhesive residue.
•
•
•
•
•
KEY POINTS FOR ASUCCESSFUL INSTALLATION
MAIN STEPS OF THEINSTALLATION PROCESS
INSTALLATION GUIDELINES 1
FIRST: UNDERSTAND THE SYSTEMUnderstanding the panel system and determiningwhich attachment option has been specified isimperative for completing a proper installation.
SECOND: PRE-PLAN THE INSTALLATIONAfter receiving and properly storing the material,planning the work schedule, grid layout, and materialusage should be performed so that the sequence canproceed without significant delays and/or problems.
THIRD: READ THE GENERAL GUIDELINESThe general guidelines (i.e. fabrication, sealing, etc.)provide a groundwork for all types installations.Thoroughly read and understand these guidelinesbefore beginning the work sequence.
FOURTH: COMPLETE THE WORK SEQUENCEAfter reading the instructions set forth in the generalguidelines, continue to the appropriate work sequenceand complete the installation.
To request a complete Product Manual (whichincludes recommended SECTION and MOLDINGINTERSECTION details), contact the manufacturer.
NOTE:
©2
00
3 C
itad
el
Arc
hite
ctu
ral
Pro
du
cts,
In
c.
An
IS
O 9
00
1:2
00
0 R
eg
iste
red
Co
mpa
ny.
Pro
Co
re™
is
a t
rad
em
ark
of
Cita
de
l A
rch
itect
ura
l P
rod
uct
s, I
nc.
Pri
nte
d I
n T
he
U.S
.A.
Fo
rm #
7.0
3.I
N.B
R
ev.
(11
/06
) S
up
ers
ed
es
(06
/03
)
WARNING: FAILURE TO FOLLOW THESE GUIDELINESWILL VOID THE STANDARD WARRANTY.
Citadel Architectural Products, Inc.ProCore™
Call (800) 446-8828 or visit www.citadelap.com2 INSTALLATION GUIDELINES
VISUAL INSPECTION:Upon material arrival, all panel units and molding/accessory cartons should be visually inspected to verifythat the product is in good condition and free fromshipping damage, weather damage or defects.
Shipping damage and/or packaging issues should befirst noted on the bill of lading and then reported tothe distributor.
Should damage occur, the customer is responsiblefor filing a freight claim with the shipping companyWITHIN 24 HOURS from material receipt. Failure to doso may possibly result in forfeit of corrective action.
Any defective material should be reported directly tothe distributor from which the product was purchased.
NOTE:
•
•
•
MATERIAL INVENTORY:After verifying the condition of the product, inventory unitsagainst the packing slip to make sure that all material(including molding and accessory units) is received.
Notify the distributor from which the product waspurchased of any missing or incomplete shipmentsIMMEDIATELY. Failure to do so may result in forfeit ofcorrective action.
NOTE:
TRANSPORTING THE MATERIAL:ProCore™ is packaged from the manufacturer in quanti-ties of 40 pieces (or less) per unit, under cover andsecured with metal strapping (FIG. A). If possible, panelsshould remain in this original packing for transport.
If a forklift or pallet jack is unavailable, panel unit may bebroken and carried to storage by hand according to thefollowing guidelines.
PRE-INSTALLATION:TRANSPORTING & HANDLING
PRE-INSTALLATION:MATERIAL RECEIVING & INVENTORY
IS THE PRODUCT IN GOOD CONDITION?
IS THE PRODUCT CLEAN AND DRY?
IS THE PRODUCT FREE FROM DEFECTS?
...THE MOLDING & ACCESSORY UNITS?
ARE ALL OF THE PANEL UNITS PRESENT?
IS THE PIECE PER UNIT COUNT CORRECT?
HANDLING THE MATERIAL:A strippable protective film (or interleafed foam) isstandard on all panels. This film should remain on theproduct until instructed to take it off (during installationprocedure). This strippable film (FIG. B) is designed toprevent minor abrasions to the surface. However, panelsshould still be handled with care to avoid any majordings, dents or scratches.
FIGURE A.
FIGURE B.
CLEARPROTECTIVEFILM
PREFINISHEDSURFACE
UNITS ARE CRATEDAND SECURED WITHMETAL STRAPPING
ARROWS WILL BEPRESENT IF MATERIALIS DIRECTIONAL
Citadel Architectural Products, Inc. ProCore™
Call (800) 446-8828 or visit www.citadelap.com
MATERIAL STORAGE:If the units have been broken, material should berestacked, on a skid. Painted surfaces (strippable filmside) should be placed face to face and any interleafedfoam must be repositioned.
Failure to properly protect material from moistureintrusion may cause damage to the panel surfaceand/or core. Such damage is NOT covered under thestandard warranty.
NOTE:
If the material has become damp or wet during transpor-tation, the surface should be wiped dry before stacking toprevent any type of corrosion. Once the stacking iscompleted (or if the original packaging is still intact), theunits must be covered with a waterproof covering.
All units must be kept in a dry, well-ventilated area awayfrom exposure to the elements and/or any other construc-tion installations which may cause damage to theproduct.
PRE-INSTALLATION:STORING THE MATERIAL UNITS
INSTALLATION GUIDELINES 3
When handling panels, clean work gloves should beworn at all times to protect from sharp edges and toprevent any smudging of the painted finish.
When removing material from shipping units, DO NOTdrag/slide panels across stack underneath. Panelsmust be lifted up, then away to avoid any permanentdamage to the painted surface (FIG. C).
NOTE:
•
•
DETERMINING THE GRID:Before beginning the installation procedure, it is importantto plan the overall layout of the installation. Architecturaldrawings should be consulted to determine the correctgrid, where applicable.
If there are no drawings to work from, measure and verifyall field dimensions and develop a pattern to maximizeappearance and minimize fabrication. Consideration foraesthetics should be made in locating odd sized panels.
PRE-INSTALLATION:SCHEDULING & GRID LAYOUT
Once begun, work should not be delayed for longperiods of time at a point which might cause damageto the product if acted upon by external conditions(i.e. rain, snow, long periods of exposure to the sun).
NOTE:
COORDINATION OF WORK:In accordance with good construction practice, schedulethe work to coordinate with other trades so that installa-tion can proceed without significant interference/delay.
DO NOT use butting panels as a guide for grid layout.Actual panel size will vary slightly from grid size(FIG. D) due to the spacing needed for panel expan-sion (1/16”) and the molding/receiver width.
For example, a 4’ x 10’ o.c. grid pattern will result inan actual panel size of slightly less than a full 4’ x 10’.
NOTE:
FIGURE C.
PANELS MUST BELIFTED UP & THEN AWAY,NOT ACROSS THE STACK
FIGURE D.
PANEL DIM. PANEL DIM.
GRIDDIM.
1/4” (APPROX.)
ONE PIECE MOLDINGS TWO PIECE MOLDINGS
3/8”(APPROX.)
GRIDDIM.
Citadel Architectural Products, Inc.ProCore™
Call (800) 446-8828 or visit www.citadelap.com
CALCULATING MATERIAL USAGE:After identifying/determining the grid, begin to verify thatthe correct amount of material has been ordered for yourspecific application. Since material takeoffs and resultingquantities are based upon the grid layout, installing thematerial in another pattern may result in shortages.
Likewise, an approximate cut plan (for both panels andmoldings) should be determined before beginninginstallation to prevent such shortages which may causedelays in completion of the project.
When calculating molding usage, verticals typically passthrough horizontals (FIG. E), except at head and silllocations (see Typical Details). If the project is largeenough to require several lengths of moldings, splicesshould be staggered so that they do not match up withhorizontal/vertical molding intersections (see GeneralWork: Cutting & Fitting Extrusions).
4 INSTALLATION GUIDELINES
ALIGNING & MARKING THE GRID:Using the grid pattern derived, establish a base point inthe lowermost left corner of the elevation (typically).Using a chalk line, level, and a plumb bob, mark thecomplete grid (FIG. F) on the substrate. Doing so willallow for any necessary adjustment to be made prior toinstallation.
Installation may also be started at the center line of theelevation and worked in both directions from that point.
All surfaces of the substrate should be free from anyobstructions and/or projections which might interfere withpanel application. Note areas where shims may berequired to bring the panel system into a plumb, level,and consistent plane.
FIGURE F.
FIGURE E.
TOP OF ELEVATION (HEAD)
BOTTOM OF ELEVATION (SILL)
MARK GRID LINESPLUMB & LEVELON SUBSTRATE
Citadel Architectural Products, Inc. ProCore™
Call (800) 446-8828 or visit www.citadelap.com INSTALLATION GUIDELINES 5
GENERAL WORK:LIMITATIONS OF THE PANEL SYSTEM
USES & APPLICATIONS:ProCore™ is intended for use as a non-structural wallpanel. It may also be used in other applications wherethe slope does not exceed 25° (FIG. G) past vertical.
Also, the system must be kept a minimum of 12” awayfrom the finished landscaping grade. Other environmen-tal and application limitations may apply. Refer to theProduct Warranty.
GENERAL WORK:FABRICATION OF THE PANELS
SAFETY PRECAUTIONS:When performing fabricating procedures, it is necessaryto observe all general guidelines for safety. Cutting,drilling, or otherwise machining the panels and trimmoldings may produce flying chips, shavings, or dust.
In addition to work gloves and proper clothing, safetygoggles, ear protection, and possibly dust masks maybe needed when fabricating system components.
NOTE:
CUTTING & DRILLING OF PANELS:Cut-to-size panels are available from the manufacturer.When field cutting is required, it may be performed usingstandard carpentry tools equipped with carbide-tippedblades. Work surfaces should be padded (FIG. H) andfree from any debris which may damage the finish. Forcleaner cuts, backer blocks and straightedges
may be clamped to the panel surface. Caul blocks shouldbe used when necessary to protect the painted finish.After cutting, aluminum edges may need filing to removesharp projections and/or metal burrs (FIG. I) that mightprevent the panel from sliding into the molding channelproperly. Doing so will also reduce the risk of personalinjury.
When using a table saw to cut panels, the finished side(protective film) should be placed facing upward. Forhand held circular saws and jigsaws, the finish sideshould be facing down (FIG. J). If working with customcolor panels and a protective film is not present, theinterleafed foam should be placed in a position to protectthe painted finish.
For drilling operations, the finished side should be placedfacing upward and a backer block should be used whennecessary to minimize any tearout.
FIGURE I.
FIGURE G.
FIGURE H.
NOT TO EXCEED25° FROMVERTICAL
NO CLOSERTHAN 12” TO
FINISHEDGRADE
PANEL SYSTEM
WORK SURFACESTO BE PADDED
CAUL BLOCKSSHOULD BE USEDTO PROTECT FINISH
STRAIGHTEDGESSHOULD BE USEDFOR LONG CUTS
METAL BURRSSHOULD BE FILEDSMOOTH ALONGFACE SKIN
HOLD FILE AT ASLIGHT ANGLE
Citadel Architectural Products, Inc.ProCore™
Call (800) 446-8828 or visit www.citadelap.com6 INSTALLATION GUIDELINES
The appearance, quality and soundness of the panelsystem depends in large part upon the quality and fit ofthe trim moldings.
For accurate cutting, a miter or chop saw (with carbidetipped blade) is recommended to cut the moldings tolength. Notching of moldings may also be required forsome intersections. Metal snips and/or a miter saw maybe used to remove portions of the moldings so that theintersection can fit together properly (FIG. K).
GENERAL WORK:CUTTING & FITTING MOLDINGS
Whenever cutting, trimming, or installing moldings, itis important to make sure the joints are well fitted andthe intersections formed provide a clean channel intowhich the panel can be placed.
NOTE:
A visual representation of the most common intersectionscan be found in the Typical Details section of the ProductManual. If you have any questions about how yourparticular intersection should be fitted, contact ourtechnical staff for assistance.
SPLICING OF MOLDINGS:Depending on the grid size, several lengths of moldingsmay be required to complete a horizontal and/or verticalrun. Planning should be done to minimize the number ofsplices required.
When necessary, splices must occur no closer than 2”away from a horizontal/vertical intersection (FIG. L).Splices must be completely sealed against moisture.
NOTE:
As a barrier system, ProCore™ is an exterior claddingsystem designed to keep water away from the structuralwall system. Therefore, it is imperative that the followingguidelines be followed accurately to ensure the integrityof the system against moisture intrusion.
SELECTING THE RIGHT SEALANT:In order for the proper bond to be created between thesealant and the system components, be sure to use onlythe sealant recommended by the manufacturer.
GENERAL WORK:PROPER SEALANT APPLICATION
Failure to adequately seal ALL panel edges, moldingintersections & splices, cutouts, etc., will cause theinstallation to fail and will VOID THE WARRANTY.
NOTE:
FIGURE L.
INCORRECT SPLICING CORRECT SPLICING
FIGURE K.
FIGURE J.
CIRCULAR SAW - FINISH DOWN JIGSAW - FINISH DOWN
TABLE SAW - FINISH UP DRILLING - FINISH UP
HORIZTONAL MOLDING
VERTICAL MOLDING
MATERIAL TO BE REMOVED SO THEMOLDING FACES JOIN PROPERLY
2” MIN.
Citadel Architectural Products, Inc. ProCore™
Call (800) 446-8828 or visit www.citadelap.com
The use of other sealants may require additional steps(such as priming of materials) or cause the installation tofail due to poor weatherability, staining and/or lack ofadequate bonding.
SEALANT APPLICATION:In general, sealant should be liberally applied whereverwater may be able to infiltrate the system (e.g. joints,molding splices, dissimilar material abutments, etc.).
To aid in applying the proper amount of sealant, the tip ofthe sealant tube should be cut at an angle from bothsides (FIG. M). Doing so will allow the tip to act as aguide (and prevent the sealant from getting spread toothin) when applying the bead.
Depending on the system, the amount of materialrequired to adequately seal the panel may vary slightly.However, squeeze out will always occur if the correctamount of sealant has been applied (FIG. N & O).
For one piece systems, the sealant should fill enough ofthe molding channel (FIG. N) so that squeeze out willoccur when the panel is inserted. For two piece systems,a continuous bead (a minimum of 1/4” x 1/4”) should beplaced along the panel edge before snapping thealuminum cover into place (FIG. O).
INSTALLATION GUIDELINES 7
Excess sealant may be cleaned up (FIG. P) after it ‘skinsover’ (approx. 45 minutes) using a non-marring scraper, aclean rag, and mineral spirits (if necessary).
Depending upon the fastening schedule and/or panelsize, an adhesive may be required in the field of thepanel. Either double-sided tape or construction adhesivemay be used to adhere the panel to the substrate. Ingeneral, a bead (or strip) of adhesive must be placed ateach intermediate location within the field of the panel(16”-24”o.c.). The approximate size of the bead shouldbe3/8” (min.) x 2/3 of the panel height. When a moisturebarrier is present, a strip of aluminum (approx. 2”-3” widex 2/3 panel height) must be fastened to the substrate(FIG. Q). The adhesive is then applied to the aluminum.
GENERAL WORK:PROPER ADHESIVE APPLICATION
FIGURE P.
SEALANT SHOULD‘SKIN OVER’ SLIGHTLYBEFORE CLEANING
When abutting dissimilar material (i.e. glazing, brick,etc.), allowances must be made for expansion/contraction(minimum 1/4”). Bond breaker tape should be applied tothe sheathing prior to the application of the receiver andan approved sealant applied after the panel and alumi-num cover are installed (see Typical Details).
FIGURE M.
CUT TIP AT 45° ANGLEFROM BOTH SIDES TOCREATE A GUIDEFOR BEAD SIZE
FIGURE N.
ONE PIECE - BEFORE ONE PIECE - AFTER
FIGURE O.
TWO PIECE - BEFORE TWO PIECE - AFTER
Citadel Architectural Products, Inc.ProCore™
Call (800) 446-8828 or visit www.citadelap.com8 INSTALLATION GUIDELINES
For the one piece molding system, panels are attached tothe substrate using construction adhesive and are held inplace by the perimeter molding. The moldings arefastened every 12” along its length.
GENERAL WORK:FASTENING THE PANELS & MOLDINGS
ALL panel fasteners must be driven snug to the panel.DO NOT countersink (or overdrive) the fastener headpast the aluminum skin.
NOTE:
FIGURE R.
3/16”
MAINTENANCE OF THEPANEL FINISH
REPAIR/TOUCH UP:Any minor scratches or dings which may occur duringinstallation can be repaired using touch-up paint availablefrom the manufacturer. Repainting of large areas with thetouch-up paint is not recommended. Finish characteris-tics of the repainted surface may vary from the prepaintedaluminum.
MAINTENANCE:Panels should be incorporated into an overall buildingwashing/maintenance schedule and cleaned in accor-dance with AAMA 610.1, Voluntary Guide Specificationfor Cleaning and Maintenance of Painted AluminumExtrusions and Curtain Wall Panels.
In general, panels may be cleaned using warm water anda mild detergrent (if necessary). For more aggressivematerials, a gentle brushing/scrubbing action may berequired. Abrasive detergents and/or harsh solventsshould not be used.
GENERAL WORK:THE PROTECTIVE FILM
When directed to do so (see Work Sequence), theprotective film must be removed from the panel surface.For ease of removal, pull the film back against itself in thesame plane as the panel.
Failure to remove the protective film promptly afterinstallation (or exposure to long periods of sunlight)may cause difficulties in removal and possibly leave anadhesive residue.
NOTE:
FIGURE S.
NO FASTENERSCLOSER THAN 1”FROM THECORNER
FASTENERS TOBE STAGGEREDACROSS THEJOINT 1”-2” APART
PVC RECEIVER
FIGURE Q.
WHEN MOISTURE BARRIER IS PRESENT OVER SUBSTRATE
STRIP OF ALUMINUMFASTENED TO THESUBSTRATE
CONSTRUCTIONADHESIVE
The two piece molding system is applied using pvcreceivers and aluminum extrusions that are ‘snapped’ intoplace after the panel is installed. Prior to fastening,reinforcing rods are placed in the core of the panel toprevent fasteners from dimpling the face skin. A pilothole is then drilled at the anchor location. Panel fasten-ers are placed 12”-16” around the perimeter 3/16” fromthe panel edge (FIG. R) and adhesive is applied in thefield at 24” o.c. minimum. Perimeter fasteners should bestaggered 1”-2” (FIG. S) across the joint for two adjoiningpanels. Fasteners should not be placed within 1” of thecorner as panel tearout may occur.
DRILL HOLE & INSERTREINFORCING ROD
PRE-DRILL PILOTHOLE
Citadel Architectural Products, Inc. ProCore™
Call (800) 446-8828 or visit www.citadelap.com INSTALLATION GUIDELINES 9
STEP 1: ATTACHING THE BOTTOMHORIZONTAL & THE LEFT VERTICAL MOLDINGS
Since the installation is progressive, the panel is encap-sulated on all four sides by the one piece moldings.Therefore, the first step in the work sequence is creatingan ‘L’ shaped pocket into which the panel will be placed.
In order to move the installation up, and then across theelevation, the first two moldings to be attached are thebottom horizontal and the left vertical (FIG. 1).
Miter or notch the moldings as needed and then fastenthem to the substrate. Keep in mind that verticals ‘passthrough’ horizontals except at head and sill locations.
The required molding length will vary dependent uponcondition and grid layout.
WORK SEQUENCE:ONE PIECE EXTRUDED MOLDINGS
These guidelines are set forth to show the intent and general sequence of installation. The procedure for eachindividual application and condition may vary. For special conditions or for those not discussed (parapet,dissimilar material, etc.), refer to the General Work Guidelines, Typical Details or contact the manufacturer.
- Nailable Substrate- Non-Nailable Substrate (fastened directly to studs)- Substrate (either type) with Moisture Barrier (special instructions apply)- Furring Strips on Masonry (16”-24” o.c.)
Possible Substrates:
- Panel Fastening (non-mechanical): Panels are attached to the substrate using construction adhesive and are held in place by the perimeter molding.- Molding Fastening: Every 12” along length of molding
- Metal Framing: #S-1000 (1”) or #S-1580 (1-5/8”)- Wood Framing & Sheathing: #S-1001 (1-5/8”)
Types Of Fasteners:
Fastening Schedules:
- Non-Structural, Barrier System
System Type:
- Progressive, moving up and across the elevation beginning at a bottom corner (typical).
Work Flow:
- #5000 (Franklin Titebond™)- #5003-D (Double Sided Tape) A bead (or strip) approx. 2/3 the panel height is placed at intermediate (16”-24”o.c.) locations.
Adhesive:
- #5002 (Tremco® Spectrem® 2) The entire system must be properly sealed against moisture for the warranty to remain valid.
Sealant:- 1/16” between panel perimeter edge and moldingExpansion/Contraction Spacing:
INSTALLATION SPECIFICATIONS:
FIGURE 1.
THE BASE MOLDINGIS INSTALLED 1ST...
THE LEFT VERTICAL IS 2ND
THE APPROPRIATENOTCH/MITER IS TOBE MADE
STOP! READ BEFORE PROCEEDING WITH WORK SEQUENCE
Citadel Architectural Products, Inc.ProCore™
Call (800) 446-8828 or visit www.citadelap.com10 INSTALLATION GUIDELINES
STEP 4: INSERTING THE PANEL INTO THEMOLDING CHANNELS
Insert the panel into the moldings (a non-marring scrapermay assist in guiding the panel into the channel). If thecorrect amount of sealant is applied, it should squeeze(FIG. 4) from the molding in a continual bead around thepanel perimeter. The excess will be removed in a laterstep.
STEP 2: PREPARING THE PANEL & APPLYINGTHE SEALANT
Begin by cutting the panel to the proper dimension withallowance made for expansion/contraction. Peel theprotective film away from all four edges of the panel. Donot remove it completely.
Place a large, continuous bead of approved sealant intoboth the bottom horizontal and left vertical moldings(FIG. 2). If the moldings extend past the first panellength/width, apply only enough sealant for one panel.
Failure to adequately seal ALL panel edges will causethe installation to fail and will VOID THE WARRANTY.
NOTE:
STEP 3: APPLYING THE PANEL ADHESIVE
Place a large bead (or strip if using double-sided tape)of panel adhesive onto the substrate at each intermediatelocation (FIG. 3).
The adhesive bead should not be allowed to set upbefore the panel is applied.
NOTE:
FIGURE 4.
FIGURE 2.
FIGURE 3.
ENOUGH SEALANT SHOULD BEAPPLIED SO THAT IT SQUEEZES OUTA CONTINUAL BEAD WHEN THEPANEL IS INSERTED
ADHESIVE ORDOUBLE-SIDED TAPE
SQUEEZE OUT SHOULDOCCUR AT MOLDING EDGE
PROTECTIVE FILM TO BEPULLED BACK FROM PERIMETER
24”MAX.
Citadel Architectural Products, Inc. ProCore™
Call (800) 446-8828 or visit www.citadelap.com INSTALLATION GUIDELINES 11
STEP 7: CLEANING UP THE EXCESS SEALANTAND REMOVING THE PROTECTIVE FILM
Once the fastening is complete, the excess sealant canbe cleaned from the panel surface using a non-marringscraper, clean rag, and mineral spirits (if necessary).
The scraper should be held at a low angle (FIG. 7) andrun along the perimeter of the panel using the molding asa guide.
Once completed, remove the protective film by pulling itback against itself along the panel.
STEP 6: ATTACHING THE RIGHTVERTICAL MOLDING
After preparing (cutting, applying sealant), the rightvertical should be fastened to the substrate (FIG. 6).
The final molding in the sequence (the right vertical)should never extend past the top horizontal (FIG. 6).Doing so will create a ‘U’ shaped channel and preventthe next panel in the vertical sequence from beinginstalled properly.
NOTE:
STEP 5: ATTACHING THE TOPHORIZONTAL MOLDING
Since verticals typically dominate, the top horizontalmolding should be notched/mitered to ‘dive into’ the leftvertical molding. Likewise the other end of the moldingshould be notched/mitered after being cut to length toreceive the right vertical molding to be attached next.
After the molding has been prepared, apply the properamount of sealant into the channel (only the side facingthe panel) and place it over the edge (FIG. 5). As in theprevious step, sealant squeeze out should occur.
Fasten the top molding to the substrate.
FIGURE 6.
FIGURE 5.
SLIDE THE TOP MOLDINGOVER THE PANEL EDGE
RIGHT VERTICAL SHOULDNOT EXTEND PASTTOP HORIZONTAL
FIGURE 7.
SEALANT SHOULD BE ALLOWEDTO ‘SKIN OVER’ SLIGHTLYBEFORE CLEANING
Citadel Architectural Products, Inc.ProCore™
Call (800) 446-8828 or visit www.citadelap.com12 INSTALLATION GUIDELINES
STEP 8: MOVING UP AND ACROSSTHE ELEVATION
Once the first panel is installed, repeat the work se-quence and move vertically in the grid. Upon completionof the first column, move again to the bottom of theelevation and begin at the next column.
Each individual application may vary depending uponlayout. However, moving vertically across the elevationrequires the least amount of setup and may prove themost efficient use of scaffolding and/or power lifts.
FIGURE 8.
COMPLETE THEVERTICAL RUN...
...THEN MOVE TO THE NEXT‘COLUMN’ AND WORK UP &ACROSS THE ELEVATION
Citadel Architectural Products, Inc. ProCore™
Call (800) 446-8828 or visit www.citadelap.com INSTALLATION GUIDELINES 13
STEP 1: ATTACHING THE PLASTIC RECEIVERSTO THE SUBSTRATE
Being a non-progressive system, the panels are set uponplastic receivers and the edge is encapsulated by analuminum cover molding.
First, attach the bottom horizontal receiver to the sub-strate using a small brad or staple. Next, attach the leftvertical (verticals dominate except at head and silllocations) followed by the right vertical.
Then measure, cut, and attach the top horizontal.
Do not install receivers for more than 3-4 panels at atime. Long exposure to sun may cause misalignment.
NOTE:
WORK SEQUENCE:TWO PIECE EXTRUDED MOLDINGS
These guidelines are set forth to show the intent and general sequence of installation. The procedure for eachindividual application and condition may vary. For special conditions or for those not discussed (parapet,dissimilar material, etc.), refer to the General Work Guidelines, Typical Details or contact the manufacturer.
- Nailable Substrate- Non-Nailable Substrate (fastened directly to studs)- Substrate (either type) with Moisture Barrier (special instructions apply)- Furring Strips on Masonry (16”-24” o.c.)
Possible Substrates:
- Panel Fastening: 12”-16” around panel perimeter—located 3/16” away from edge, driven snug to the panel between the reinforcing rods, not countersunk (no fasteners within 1” of corner)- Receiver Fastening (temporary): Every 24”-36” along length, using brads/staples
- Metal Framing: #S-1000 (1”) or #S-1580 (1-5/8”)- Wood Framing & Sheathing: #S-1001 (1-5/8”)
Types Of Fasteners:
Fastening Schedules:
- Non-Structural, Barrier System
System Type:
- Non-Progressive, moving up and across the elevation beginning at a bottom corner (typical).
Work Flow:
- #5000 (Franklin Titebond™)- #5003-D (Double Sided Tape) A bead (or strip) approx. 2/3 the panel height is placed at intermediate (16”-24”o.c.) locations.
Adhesive:
- #5002 (Tremco® Spectrem® 2) The entire system must be properly sealed against moisture for the warranty to remain valid.
Sealant:- 1/16” between panel perimeter edge and receiver
Expansion/Contraction Spacing:
INSTALLATION SPECIFICATIONS:
FIGURE 1.
...VERTICALS 2ND...
INSTALL BOTTOM 1ST...
...THEN THE TOP LAST
STOP! READ BEFORE PROCEEDING WITH WORK SEQUENCE
Citadel Architectural Products, Inc.ProCore™
Call (800) 446-8828 or visit www.citadelap.com14 INSTALLATION GUIDELINES
STEP 2: PREPARING THE PANEL AND APPLYINGTHE ADHESIVE
Begin by cutting the panel to the proper dimension withallowance made for expansion/contraction.
Next, mark the locations of the perimeter fasteners andinsert the reinforcing rods into the core (a hole may needdrilled in the core to receive the rods). Then, drill the pilothole through the panel and in between the rods at eachlocation.
Peel the protective film away from all four edges of thepanel. Do not remove it completely.
Finally, place a large bead (or strip if using double-sidedtape) of panel adhesive onto the substrate at eachintermediate location (FIG. 2).
STEP 3: ATTACHING THE PANEL TOTHE SUBSTRATE
Place the panel onto the receivers (a shim may be helpfulin maintaining the proper spacing (FIG. 3) around theperimeter) and fasten it to the substrate.
STEP 4: REPEATING THE PROCESSFOR ADJOINING PANELS
Because the aluminum covers snap over the edges oftwo panels (with the exception of the perimeter molding),it is necessary to install one or more adjoining panelsbefore continuing.
Repeat STEPS 1-3, installing additional panels in thegrid. Remember to align the vertical receivers so thatthey ‘pass through’ the horizontals (FIG. 4).
The adhesive bead should not be allowed to set upbefore the panel is applied.
DO NOT overdrive fasteners. Doing so will cause theface of the panel to dimple.
NOTE:
•
•
FIGURE 4.
FIGURE 2.
FIGURE 3.
ADHESIVE OR DOUBLE- SIDED TAPE
24”MAX.
SHIMS MAY BE USEDFOR PROPER SPACING
INSTALL ADJOININGPANELS
Citadel Architectural Products, Inc. ProCore™
Call (800) 446-8828 or visit www.citadelap.com INSTALLATION GUIDELINES 15
STEP 5: CUTTING THE MOLDING & APPLYINGTHE PERIMETER SEALANT
Once the adjoining panels are installed, cut the appropri-ate cover moldings to length making any necessarymiters (if required).
Next, liberally apply a large bead of sealant around thepanel perimeter (FIG. 5).
STEP 6: SNAPPING THE ALUMINUMCOVER INTO PLACE
Once the proper amount of sealant has been applied, thecover molding may be ‘snapped’ into place. Begin at oneend and ‘tap’ the cover molding into place using a rubbermallet, moving along its length (FIG. 6). If the properamount of sealant was applied, a continuous bead shouldsqueeze out from the joint.
STEP 7: CLEANING UP THE EXCESS SEALANTAND REMOVING THE PROTECTIVE FILM
Once the aluminum cover is snapped into place, theexcess sealant can be cleaned from the panel surfaceusing a non-marring scraper, clean rag, and mineralspirits (if necessary).
The scraper should be held at a low angle (FIG. 7) andrun along the perimeter of the panel using the molding asa guide.
Once completed, remove the protective film by pulling itback against itself along the panel.
Apply sealant only to those areas/panels where thecover will be immediately installed.
NOTE:
FIGURE 6.
FIGURE 7.
FIGURE 5.
SEAL ONLY THE PANELEDGES FOR THE 1STSET OF COVERS
TAP MOLDING COVERSINTO RECEIVER MOVINGALONG ITS LENGTH
SEALANT SHOULD BEALLOWED TO ‘SKIN OVER’SLIGHTLY BEFORE CLEANING
Citadel Architectural Products, Inc.ProCore™
Call (800) 446-8828 or visit www.citadelap.com16 INSTALLATION GUIDELINES
STEP 8: MOVING UP AND ACROSSTHE ELEVATION
Once the first panel is installed, repeat the work se-quence and move vertically in the grid. Upon completionof the first column, move again to the bottom of theelevation and begin at the next column.
Each individual application may vary depending uponlayout. However, moving vertically across the elevationrequires the least amount of setup and may prove themost efficient use of scaffolding and/or power lifts.
FIGURE 8.
COMPLETE THEVERTICAL RUN...
...THEN MOVE TO THE NEXT‘COLUMN’ AND WORK UP &ACROSS THE ELEVATION
Citadel Architectural Products, Inc. ProCore™
Call (800) 446-8828 or visit www.citadelap.com INSTALLATION GUIDELINES 17
PA-8X O/S CORNER PA-9X I/S CORNERFace Legs:Back Legs:Length:
1/2” (13mm)1” (25mm)10’ (3048mm)
Inside Legs:Back Legs:Length:
1/2” (13mm)1” (25mm)10’ (3048mm)
PA-12X HORZ/VERT PA-15BX PERIMETER JFace Leg:Height:Length:
3/4” (19mm)1-3/8” (35mm)10’ (3048mm)
Face Leg:Back Leg:Length:
3/4” (19mm)1-3/8” (35mm)10’ (3048mm)
ONE PIECE EXTRUDED ALUMINUM MOLDINGS
SR-701MX HORZ/VERT
R20-406 PVC RECEIVER: 12’
Height:Reveal:Length:
2” (51mm)1/2” (13mm)10’ (3048mm)
SR-703MX PERIMETER J
R20-407 PVC RECEIVER: 12’
Height:Reveal:Length:
1-1/2” (38mm)1/2” (13mm)10’ (3048mm)
ST-601MX HORZ/VERT
R20-401 PVC RECEIVER: 12’
STANDARD TWO PIECE EXTRUDED ALUMINUM MOLDINGS
Height:Length:
1-1/2” (38mm)10’ (3048mm)
ST-603MX PERIMETER J
R20-403 PVC RECEIVER: 12’
Height:Length:
1” (25mm)10’ (3048mm)
ST-605MX I/S CORNER
R20-404 PVC RECEIVER: 12’
I/S Legs:Length:
3/4” (19mm)10’ (3048mm)
ST-607MX O/S CORNER
R20-405 PVC RECEIVER: 12’
O/S Legs:Length:
1-1/4” (32mm)10’ (3048mm)
Citadel Architectural Products, Inc.ProCore™
Call (800) 446-8828 or visit www.citadelap.com18 INSTALLATION GUIDELINES
ST-201MX HORZ/VERT
R20-401 PVC RECEIVER: 12’
TWO PIECE EXTRUDED ALUMINUM MOLDINGS
Height:Length:
2” (51mm)12’ (3658mm)
ST-203MX PERIMETER J
R20-403 PVC RECEIVER: 12’
Height:Length:
1-1/4” (32mm)12’ (3658mm)
ST-205MX I/S CORNER
R20-404 PVC RECEIVER: 12’
I/S Legs:Length:
1” (25mm)12’ (3658mm)
ST-207MX O/S CORNER
R20-405 PVC RECEIVER: 12’
O/S Legs:Length:
1-1/2” (38mm)12’ (3658mm)
Citadel Architectural Products, Inc. ProCore™
Call (800) 446-8828 or visit www.citadelap.com
Length: 1-5/8” (41mm)Pieces Per Box: 500Weight: 2 lbs.
Item #
MECHANICAL FASTENERS
S-1000CLIMASEALSCREW
S-1580CLIMASEALSCREW
S-1001HI-LOSCREW
Length: 1-5/8” (41mm)Pieces Per Box: 500Weight: 2 lbs.
Length: 1” (25mm)Pieces Per Box: 500Weight: 2 lbs.
Fastening thepanel to woodframing
Fastening thepanel to metalframing
Fastening thepanel to metalframing
Description Application
Small nails or brads (available at a local hardware store) may be used for temporarily attaching the plastic receivers to the substrate.Note: Fasteners shown actual size.
INSTALLATION GUIDELINES 19
Recommended Tooling:
TOOLING & EQUIPMENT
Note: Depending upon your installation, some items may be optional.
Safety GlassesWork GlovesDust MaskHearing Protection
Safety:
ScaffoldingPower LiftPlastic/CanvasCover(s)
Jobsite:
Mild DetergentMineral SpiritsNon-Marring ScraperClean Shop Rags
CleanUp:
Tape Measure(16’ minimum)Laser/Handheld Level(4’ minimum)Chalk LinePlumb BobT-SquareFraming Square
Measuring/Marking:
Framing Hammer(non-marring tip)Rubber Mallet
Hand Tools:
Table SawCircular SawMiter/Chop SawJigsawPower DrillScrew Gun
Power Tools:(carbide tipped blades)
Recommended Equipment:
Caulking GunBox KnifeMetal FileMetal Snips
SawhorsesScrap Sheets OfPlywood (3/4”)Clamps (with cauls)StraightedgePlastic/Wood Shims
Fabrication:
7013-PCPROCORE™REINFORCINGROD
Length: 1” (25mm)Pieces Per Box: 100Weight: 2 lbs.
Inserted into core toprevent the screw fromdimpling the surface
Citadel Architectural Products, Inc.ProCore™
Call (800) 446-8828 or visit www.citadelap.com20 INSTALLATION GUIDELINES
SEALANTS, ADHESIVES AND TOUCH-UP
Item # Description
5000 CONSTRUCTIONADHESIVE
Tube Size: 10.5 oz.(approx. 30 lineal ft. pertube at a 1/4” bead)
Application
Along with mechanical fasteners, the panel isadhered to the substrate/stud framework usingconstruction grade adhesive.Franklin Titebond™
5002 SEALANT Tube Size: 11 oz.(approx. 30 lineal ft. pertube at a 1/4” bead)
Proper application of approved sealant is critical tothe integrity of the panel system. Failure to do sowill void the product warranty.
Tremco® Spectrem® 2
5003-D DOUBLE SIDED TAPE 1/8” x 1” x 54’roll
As an alternative to construction adhesive, doublesided tape may be used in some applications toadhere the panel to the substrate.
PA-46 POLYESTERTOUCH-UP PAINT
Container: 7 oz. During installation, minor scratches, abrasions,and/or dings may occur. If necessary, repairscan be performed using small bottles of colormatched paint. Touch-up paint should not beused for painting large areas or trim.
Kynar 500® may also be available.Contact Inside Sales for pricing.