    Viking Residential SprinklerInstallation Guide

     Trusted Above All TM www.vikinggroupinc.com

    January 13, 2012

  • 8/20/2019 installation guid.pdf

    2/18

    TECHNICAL DATA

    January 13, 2012

    The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

    Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

    FREEDOM ®  RESIDENTIAL

    SPRINKLER

    INSTALLATION GUIDE

    1. DESCRIPTIONViking residential automatic sprinklers are equipped with a “fast response” heat-sensitive operating element designed to respond

    individually and quickly to a specific high temperature. Viking residential sprinklers are designed to combine speed of operation with

    water distribution characteristics to help in the control of residential fires and to improve life safety by prolonging the time available

    for occupants to escape or be evacuated.

    2. LISTINGS AND APPROVALSRefer to the Approval Charts on the appropriate sprinkler technical data page(s) and/or approval agency listings.

     A. Viking residential sprinklers are intended for use in the following occupancies: one- and two-family dwellings and mobile homes

    with the fire protection sprinkler system installed in accordance with NFPA 13D; residential occupancies up to four stories in height

    with the fire protection system installed in accordance with NFPA 13R; or residential portions of any occupancy with the fire protec-

    tion system installed in accordance with NFPA 13. Information contained in this guide is based on NFPA 13, “Standard for the

    Installation of Sprinkler Systems”.

    B. The design criteria for residential sprinklers contained in the NFPA installation standards must be followed except as modifiedby the individual UL 1626 listing information provided in the technical data pages and this Residential Sprinkler Installation Guide

    For listed areas of coverage, technical data, and specific design and installation instructions, refer to the appropriate Viking techni-

    cal data page for the sprinkler model used.

    C. Viking residential sprinklers listed by Underwriters Laboratories, Inc. (UL) have passed fire tests designed to represent fire

    conditions for the sprinkler’s listed area of coverage. The standards for residential sprinkler performance and spray patterns are

    printed in Underwriters Laboratories Publication UL 1626, “Standard for Residential Sprinklers for Fire Protection Service”. Al

    listed Viking residential sprinklers meet or exceed UL 1626 performance requirements and spray pattern criteria for their listed

    areas of coverage.

    D. NFPA standards allow use of residential sprinklers with rates, design areas, areas of coverage, and minimum design pressures

    other than those specified in the standards when they have been listed for such specific residential installation conditions.

    3. TECHNICAL DATASpecifcations:

    Refer to the appropriate sprinkler technical data sheet.

    Material Standards:

    Refer to the appropriate sprinkler technical data sheet.

    4. INSTALLATIONA. Care and Handling (also refer to Bulletin - Care and Handling of Sprinklers, Form No. F_091699.)

    Sprinklers must be handled with care and protected from mechanical damage during storage, transport, handling, and after installation

    Store sprinklers in a cool, dry place in their original container.

    Use care when locating sprinklers near fixtures that can generate heat.

    Never install sprinklers that have been dropped, damaged in any way, or exposed to temperatures exceeding the maximum ambi

    ent temperature allowed (refer to Table 1.)

    Never install any glass-bulb sprinkler if the bulb is cracked or if there is a loss of liquid from the bulb. A small air bubble should be

    present in the glass bulb. Any sprinkler with a loss of liquid from the glass bulb or damage to the fusible element should be

    destroyed immediately. (Note: Installing glass bulb sprinklers in direct sunlight (ultraviolet light) may affect the color of the dyeused to color code the bulb. This color change does not affect the integrity of the bulb.)

    Viking residential sprinklers are intended for use on wet pipe residential systems only. Adequate heat must be provided for wet-

    pipe systems. DO NOT use Viking residential sprinklers on dry systems unless specifically allowed by recognized installation

    standards or the Authority Having Jurisdiction.

    Residential concealed sprinklers must be installed in neutral or negative pressure plenums only!

    Corrosion-resistant sprinklers must be installed when subject to corrosive atmospheres. NOTE: Viking residential sprinklers are

    not intended for use in corrosive environments.

    B. Installation Instructions

    Viking sprinklers are manufactured and tested to meet the rigid requirements of approving agencies. They are designed to be in-

    stalled in accordance with recognized installation standards NFPA 13, NFPA 13R, and NFPA 13D, and any associated TIAs.

    Form No. F_080190

    Viking Technical Data may be found on

    The Viking Corporation’s Web site at

    http://www.vikinggroupinc.com.

    The Web site may include a more recent

    edition of this Technical Data Page.

    Sprinkler RES1

    Replaces pages 1-17, dated April 30, 2010. (Updated to add sprinklers

    VK457 and VK4570 and updated reference to NFPA 13, 2010 edition.

    http://www.vikinggroupinc.com/databook/sprinklers/091699.pdfhttp://www.vikinggroupinc.com/databook/sprinklers/091699.pdf

  • 8/20/2019 installation guid.pdf

    3/18

    FREEDOM ®  RESIDENTIAL

    SPRINKLER

    INSTALLATION GUIDETECHNICAL DATA

    January 13, 2012

    The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

    Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

    TABLE 1: RESIDENTIAL SPRINKLER TEMPERATURE RATINGS

    Sprinkler Temperature

    Classification

    Sprinkler Nominal

    Temperature Rating1Maximum Ambient

    Ceiling Temperature3Bulb Color 

    Residential Glass Bulb Style Sprinklers

    Ordinary 155 °F (68 °C) 100 °F (38 °C) Red

    Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow

    Sprinkler TemperatureClassification

    Sprinkler Nominal TemperatureRating (Fusing Point)1

    Maximum AmbientCeiling Temperature3

    Residential Fusible Element Style Sprinklers

    Ordinary 165 °F (74 °C) 100 °F (38 °C)

    Sprinkler TemperatureClassification

    Sprinkler Nominal TemperatureRating (Fusing Point)

    Maximum AmbientCeiling Temperature3

    TemperatureIdentification Stamp

    Residential Flush Style Sprinklers

    Ordinary 165 °F (74 °C) 100 °F (38 °C)On Cover or

    Sprinkler Inlet (VK476)

    Intermediate 220 °F (104 °C) 150 °F (65 °C) On Cover  

    Sprinkler TemperatureClassification

    Sprinkler Nominal TemperatureRating (Fusing Point)

    Maximum AmbientCeiling Temperature3

    Cover Plate TemperatureRating

    Residential Concealed Style Sprinklers

    Ordinary 135 °F (57 °C)1

    , 140 °F (60 °C)2

    ,155 °F (68 °C)1, or 165 °F (74 °C)1

    100 °F (38 °C) 135 °F (57 °C)

    Footnotes

    1 The sprinkler temperature rating is stamped on the deflector or flow shaper.

    2 The temperature rating is stamped on the sprinkler.

    3 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.

    Refer to specific installation standards.

    Deviation from the standards or any alteration to the sprinklers or cover plate assemblies after they leave the factory including,

    but not limited to: painting, plating, coating, or modification, may render the sprinklers inoperative and will automatically nullify the

    approval and any guarantee made by Viking.

    The use of residential sprinklers may be limited due to occupancy and hazard. Residential fire protection systems must be designed

    and installed only by those who are completely familiar with the appropriate standards and codes, and thoroughly experienced in

    fire protection design, hydraulic calculations, and sprinkler system installation.

    Before installation, be sure to have the appropriate sprinkler model and style, with the correct K-Factor, temperature rating, and

    response characteristics. Viking residential sprinklers must be installed after the piping is in place to prevent mechanical damage.

    Keep sprinklers with protective caps or bulb shields contained within the caps or shields during installation and testing, and any time

    the sprinkler is shipped or handled.

    1a. For frame-style sprinklers, install escutcheon (if used), which is designed to thread onto the external threads of the sprinkler*.

      *Refer to the appropriate sprinkler technical data page to determine approved escutcheons for use with specific sprinkler models.

    1b. For flush and concealed style sprinklers: Cut the sprinkler nipple so that the ½” or 3/4” (15 mm or 20 mm) NPT** outlet of the

    reducing coupling is at the desired location and centered in the opening** in the ceiling or wall.  **Size depends on the sprinkler model used. Refer to appropriate sprinkler data page.

    Sprinkler RES2

  • 8/20/2019 installation guid.pdf

    4/18

    TECHNICAL DATA

    January 13, 2012

    The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

    Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

    FREEDOM ®  RESIDENTIAL

    SPRINKLER

    INSTALLATION GUIDE

    DESIGN CRITERIA

    For Systems Designed to NFPA 13D or NFPA 13R: Apply the listed areas of coverage and minimum water supply requirements shown in

    the approval charts on the residential sprinkler data pages. The sprinkler flow rate is the minimum required discharge from each of the total

    number of design sprinklers as specified in NFPA 13D or NFPA 13R.

    For Systems Designed to the latest edition of NFPA 13: The number of design sprinklers is to be the four most hydraulically demanding

    sprinklers. The minimum required discharge from each of the four sprinklers is to be the greater of the following:

    The flow rates given in the approval charts on the data pages for NFPA 13D and NFPA13R for each area of coverage listed, or 

    Calculated based on a minimum discharge of 0.1 gpm/sq. ft. over the “design area” in accordance with sections 8.5.2.1 or 8.6.2.1.2 of NFPA 13.

    The greatest dimension of the coverage area cannot be any greater than the maximum areas of coverage shown on the data pages.

    Flow Rates

     All residential sprinklers manufactured on or after July 12, 2002 are listed with a single minimum flow rate. Where rooms have more than one sprinkler,

    multiple-sprinkler calculations are still required, but the first sprinkler and any additional sprinkler or sprinklers must be calculated flowing at identical mini-mum flow rates, based on the area of sprinkler coverage, using the minimum flow and pressure listed for the sprinkler model used.

    Consult the appropriate standards and the Authorities Having Jurisdiction to determine the number of sprinklers to hydraulically calculate to verify ad-

    equate water supply for multiple-sprinkler operation.

    Operating Pressure: The minimum operating pressure of any sprinkler shall be the minimum operating pressure specified by the listing, or 7 psi (0.5

    bar), whichever is greater. The maximum allowable operating pressure is 175 psi (12 bar).

    Areas of Coverage

    If the actual area of coverage is less than the listed area of coverage, use the minimum water supply for the next larger area of coverage listed. DO NOT

    interpolate. Residential sprinkler systems must be hydraulically calculated according to NFPA standards to verify that the water supply is adequate for

    proper operation of the sprinklers. Hydraulic calculations are required to verify adequate water supply at the hydraulically most remote single sprinkler

    when it is operating at the minimum gpm and psi listed for single-sprinkler operation for the sprinkler model used.

    Viking residential sprinklers may be listed for more than one area of coverage. Suggested practice in selecting area of coverage is to select the one

    that can be adequately supplied by the available water supply and still allow for the installation of as few sprinklers in a compartment as possible while

    observing all guidelines pertaining to obstructions and spacing. This maximizes the use of the available water supply, which is often limited on residential

    fire protection systems. After selecting an appropriate area of coverage, sprinklers must be spaced according to guidelines set forth in the installationstandards.

    Definition of “COMPARTMENT”: A space completely enclosed by walls and a ceiling. Openings to an adjoining space are allowed, provided the open-

    ings have a minimum lintel depth of 8 in. (203.2 mm) from the ceiling.

    Spacing Guidelines

    For guidelines concerning spacing of Viking residential sprinklers near beams, obstructions, heat sources, and sloped ceilings [slopes more than a

    2/12 (9.5°) pitch], refer to the Viking residential sprinkler data pages and installation guide, the appropriate NFPA standard, and the Authority Having

    Jurisdiction. NOTE: Sloped, beamed, and pitched ceilings could require special design features such as larger flow, or a design for more sprinklers to

    operate in the compartment, or both.

    Distance from Walls: Install not more than one-half the listed sprinkler spacing nor less than 4” (102 mm) from walls, partitions, or obstructions as

    defined in the standards.

    Minimum Sprinkler Spacing: The minimum distance between residential sprinklers to prevent cold soldering (i.e., the spray from one operating sprink-

    ler onto an adjacent sprinkler that could prevent its proper activation) is 8 ft. (2.4 m).

    Maximum Sprinkler Spacing: Locate adjacent sprinklers no farther apart than the listed spacing.

    Deflector Position: Install frame style residential pendent  sprinklers with the deflector between 1” and 4” (25.4 mm to 102 mm) below smooth ceilings,

    unless the sprinkler data page indicates otherwise. Install pendent sprinklers in the pendent position only, with the deflector oriented parallel with the ceiling

    or roof.

    Refer to the individual listings in the residential sprinkler data pages for horizontal sidewall sprinkler deflector or sprinkler centerline distance below

    the ceiling. Install horizontal sidewall sprinklers in the horizontal position only below smooth ceilings, with the leading edge of the deflector or element

    assembly oriented parallel with the ceiling.

    IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to the ap-

    propriate sprinkler data page. Viking sprinklers are to be installed in accordance with the latest edition of Viking

    technical data, the appropriate standards of NFPA and any other similar Authorities Having Jurisdiction, and also

    with the provisions of governmental codes, ordinances, and standards, whenever applicable. Final approval and

    acceptance of all residential sprinkler installations must be obtained from the Authorities Having Jurisdiction.

    Sprinkler RES3

    http://www.vikingcorp.com/databook/sprinklers/091699.pdfhttp://www.vikingcorp.com/databook/sprinklers/091699.pdf

  • 8/20/2019 installation guid.pdf

    5/18

    FREEDOM ®  RESIDENTIAL

    SPRINKLER

    INSTALLATION GUIDETECHNICAL DATA

    January 13, 2012

    The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

    Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

    2. Apply a small amount of pipe-joint compound or tape to the external threads of the sprinkler only, taking care not to allow a

    build-up of compound in the sprinkler inlet. NOTE: Sprinklers with protective caps or bulb shields must be contained within the

    caps or shields before applying pipe-joint compound or tape. Exception: For concealed sprinklers (i.e., VK457, VK458, VK468

    VK474, and VK4570) the protective cap is removed for installation.

    3. Care must be taken when installing sprinklers on CPVC and copper piping systems. Never install the sprinkler into the re-

    ducing fitting before attaching the reducing fitting to the piping. Sprinklers must be installed on CPVC systems after the

    reducing fitting has been installed and the primer and/or cement manufacturer’s recommended curing time has elapsed

    When installing sprinklers on copper piping systems, take care to brush the inside of the sprinkler supply piping and reducing

    fitting to ensure that no flux accumulates in the sprinkler orifice. Excess flux can cause corrosion and may impair the ability of

    the sprinkler to operate properly.

    4. Refer to the appropriate sprinkler technical data page to determine the correct sprinkler wrench for the model of sprinkler used

    DO NOT use the sprinkler deflector or fusible element to start or thread the sprinkler into a fitting.

    a. Install the sprinkler onto the piping using the special sprinkler wrench only, while taking care not to over-tighten or damage

    the sprinkler operating parts.

    b. Thread the flush or concealed sprinkler into the ½” or 3/4” (15 mm or 20 mm) NPT** outlet of the coupling by turning it clock

    wise with the special sprinkler wrench. NOTE: For flush and concealed sprinklers with protective shells, the internal diamete

    of the special flush and concealed sprinkler installation wrench is designed for use with the sprinkler contained within the

    shell. Exception: For concealed sprinklers VK457, VK458, VK468, VK474, and VK4570 the protective cap is removed for

    installation, and then placed back on the sprinkler temporarily.

    5. After installation, the entire sprinkler system must be tested. The test must be conducted to comply with the installation standards.

    a. Make sure the sprinkler has been properly tightened. If a thread leak occurs, normally the unit must be removed, new

    pipe-joint compound or tape applied, and then reinstalled. This is due to the fact that when the joint seal leaks, the sealing

    compound is washed out of the joint.

    b. Remove plastic protective sprinkler caps or bulb shields AFTER the wall or ceiling finish work is completed where

    the sprinkler is installed and there no longer is a potential for mechanical damage to the sprinkler operating ele-

    ments. To remove the bulb shields, simply pull the ends of the shields apart where they are snapped together. To remove caps

    from frame style sprinklers, turn the caps slightly and pull them off the sprinklers. SPRINKLER CAPS OR BULB SHIELDS

    MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE! Retain a protective cap o

    shield in the spare sprinkler cabinet.

    6. For residential flush sprinklers, the ceiling ring can now be installed onto the sprinkler body. Align the ceiling ring with the sprin-

    kler body and thread on or push it on until the flange touches the ceiling. Note the maximum vertical adjustment is ½” (12,7

    mm) for sprinkler VK420 and 5/8” for VK476. DO NOT MODIFY THE UNIT. If necessary, re-cut the sprinkler drop nipples as

    required.

    7. For residential concealed sprinklers, the cover plate assembly can now be attached.

    a. Remove the cover plate assembly from the protective box, taking care not to damage the assembly.

    b. From below the ceiling, gently place the base of the cover plate assembly over the sprinkler protruding through the opening

    in the ceiling or wall.

    c. Carefully push the cover plate assembly onto the sprinkler, using even pressure with the palm of the hand, until the unfinished

    brass flange of the cover plate base touches the ceiling or wall.

    d. The maximum adjustment available for residential concealed sprinklers is ½” (12.7 mm) [1/4” (6.4 mm) for sprinkler VK480][1/4” (6.4 mm) for sprinkler VK480]

    DO NOT MODIFY THE UNIT. If necessary, re-cut the sprinkler nipples.

    NOTE: If it is necessary to remove the entire sprinkler unit, the system must be taken out of service. See Maintenance instructions

    below and follow all warnings and instructions.

    5. OPERATIONDuring fire conditions, the operating element fuses or shatters (depending on the type of sprinkler), releasing the pip cap and seal-

    ing assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector or flow shaper, forming a uniform, high-wal

    wetting spray pattern to extinguish or control the fire.

    Sprinkler RES4

  • 8/20/2019 installation guid.pdf

    6/18

    TECHNICAL DATA

    January 13, 2012

    The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

    Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

    FREEDOM ®  RESIDENTIAL

    SPRINKLER

    INSTALLATION GUIDE

    6. INSPECTIONS, TESTS AND MAINTENANCEINSPECTIONS, TESTS AND MAINTENANCERefer to NFPA 25 for Inspection, Testing and Maintenance requirements. NOTICE: The owner is responsible for having the fire-

    protection system and devices inspected, tested, and maintained in proper operating condition in accordance with this guide, and

    applicable NFPA standards. In addition, the Authority Having Jurisdiction may have additional maintenance, testing, and inspection

    requirements that must be followed.

     A. Sprinklers must be inspected on a regular basis for signs of corrosion, mechanical damage, obstructions, paint, etc. Frequency

    of the inspections may vary due to corrosive atmospheres, water supplies, and activity around the device.

    B. Sprinklers or cover plate assemblies that have been field painted, caulked, or mechanically damaged must be replaced im-

    mediately. Sprinklers showing signs of corrosion shall be tested and/or replaced immediately as required. Installation standards

    require sprinklers to be tested and, if necessary, replaced immediately after a specified term of service. Refer to NFPA 25 and

    the Authorities Having Jurisdiction for the specified period of time after which testing and/or replacement of residential sprinklers

    is required. Never attempt to repair or reassemble a sprinkler. Sprinklers and cover assemblies that have operated cannot be

    reassembled or re-used, but must be replaced. When replacement is necessary, use only new sprinklers and cover assemblies

    with identical performance characteristics.C. The sprinkler discharge pattern is critical for proper fire protection. Nothing should be hung from, attached to, or otherwise ob-

    struct the discharge pattern of the sprinkler. All obstructions must be immediately removed or, if necessary, additional sprinklers

    installed.

    D. When replacing existing sprinklers, the system must be removed from service. Refer to the appropriate system description and

    or valve instructions. Prior to removing the system from service, notify all Authorities Having Jurisdiction. Consideration should

    be given to employment of a fire patrol in the effected area.

    1. Remove the system from service, drain all water, and relieve all pressure on the piping.

    2a. For frame-style sprinklers, use the special sprinkler wrench and remove the old sprinkler by turning it counterclockwise to

    unthread it from the piping.

    2b. For residential flush pendent and concealed style sprinklers: Remove the ceiling ring or cover plate assembly before unthreading the

    sprinkler body from the piping. To remove a ceiling ring, grasp it from below the ceiling and gently turn it counterclockwise. Cove

     plates can be removed either by gently unthreading them or pulling them off the sprinkler body (depends on the sprinkler model used)

     After the ceiling ring or cover plate assembly has been removed from the sprinkler, use the sprinkler wrench to unthread

    the sprinkler from the piping. NOTE: For flush and concealed sprinklers with protective shells, the internal diameter of thespecial flush and concealed sprinkler installation wrench is designed for use with the sprinkler contained within the shell

    Place a plastic protective shell (from the spare sprinkler cabinet) over the sprinkler to be removed and then fit the sprinkle

    wrench over the shell. Exception: Concealed sprinklers VK457, VK458, VK468, VK474, and VK4570 are removed withou

    the plastic cap.

    3. Follow instructions in section 4B. Installation Instructions to install the new unit. Be sure the replacement sprinkler is the

    correct model and style, with the appropriate K-Factor, temperature rating, and response characteristics. A fully stocked

    sprinkler cabinet should be provided for this purpose. (For flush or concealed style sprinklers, stock of spare ceiling rings o

    cover plates should also be available in the spare sprinkler cabinet.)

    4. Place the system back in service and secure all valves. Check for and repair all leaks.

    E. Sprinkler systems that have been subjected to a fire must be returned to service as soon as possible. The entire system mus

    be inspected for damage, and repaired or replaced as necessary. Sprinklers that have been exposed to corrosive products of

    combustion or high ambient temperatures, but have not operated, should be replaced. Refer to the Authority Having Jurisdiction

    for minimum replacement requirements.

    7. AVAILABILITYViking Residential Sprinklers are available through a network of domestic and international distributors. See The Viking Corporation

    web site for the closest distributor or contact The Viking Corporation.

    8. GUARANTEEFor details of warranty, refer to Viking’s current list price schedule or contact Viking directly.

    Sprinkler RES5

  • 8/20/2019 installation guid.pdf

    7/18

    FREEDOM ®  RESIDENTIAL

    SPRINKLER

    INSTALLATION GUIDETECHNICAL DATA

    January 13, 2012

    The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

    Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

    Sprinkler RES6

    Table 2Rise Over Run Conversion to Degrees of Slope

  • 8/20/2019 installation guid.pdf

    8/18

    TECHNICAL DATA

    January 13, 2012

    The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

    Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

    FREEDOM ®  RESIDENTIAL

    SPRINKLER

    INSTALLATION GUIDE

    SPACING OF RESIDENTIAL SPRINKLERS LISTED FOR USEBELOW SLOPED CEILINGS UP TO AN 8/12 (33.7°) PITCH

    (Refer to the appropriate residential sprinkler technical data page for listings.)

    SPACING OF RESIDENTIAL SPRINKLERS BELOW SLOPED

    CEILINGS WITH GREATER THAN 8/12 (33.7°) PITCH(NOTE: Refer to NFPA 13D or NFPA 13R, and the Authority Having Jurisdiction.)

    Pendent Sprinklers

    Figure 1

    (A) One-half listed spacing of sprinkler maximum, 0’-4” (0-102 mm) minimum.

    (B) Listed spacing of sprinkler, maximum, 8’-0” (2.4 m) minimum.

    (C) Where angle “C” is greater than an 8/12 (33.7°) pitch, see Figure 2 below.

    Horizontal Sidewall Sprinklers(Spray Across the Slope)

    Figure 2

    (A) One-half listed spacing of sprinkler, maximum.

    (B) 3’-0” (.91 m) maximum.

    (C) 0’-4” (0-102 mm) minimum.

    (D) Slopes greater than an 8/12 (33.7°) pitch.

    (E) For distance less than 8’-0” (2.4 m), baffle required.

    Single Slope

    Multiple Slope

    Sprinkler RES7

  • 8/20/2019 installation guid.pdf

    9/18

    FREEDOM ®  RESIDENTIAL

    SPRINKLER

    INSTALLATION GUIDETECHNICAL DATA

    January 13, 2012

    The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

    Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

    SPACING OF RESIDENTIAL SPRINKLERS LISTED FOR USEBELOW SLOPED CEILINGS UP TO AN 8/12 (33.7°) PITCH

    (Refer to the appropriate residential sprinkler technical data page for listings.)

    SPACING OF RESIDENTIAL PENDENT SPRINKLERS AT PEAK OF SLOPEDCEILINGS WITH PITCH LESS THAN 8/12 (33.7°)

    (Refer to the appropriate residential sprinkler technical data page for listings.)

    Figure 3

    (A) One-half listed spacing of sprinkler, maximum.

    (B) 8’-0” (2.4 m) minimum.

    (C) 0’-4” (0-102 mm) minimum.

    (D) 3’-0” (.91 m) maximum.

    (E) Acceptable for slopes of 0/12 to 8/12 (0° to 33.7°) pitch.

    Figure 4

    (A) Listed spacing of sprinkler, maximum.

    (B) One-half listed spacing of sprinkler, maximum.

    (C) 0’-4” minimum.

    (D) Refer to page 10 for minimum distance between sprinkler and intersecting sloped ceiling.

    (E) Refer to the appropriate residential sprinkler technical data page for deflector distance below ceiling.

    (F) 8’-0” minimum.

    (G) Reference: 4/12 (18.0°) pitch maximum for 12’ (3.7 m) spacing.

      2.5/12 (12.0°) pitch maximum for 14’ (4.3 m) spacing.

      2/12 (10.0°) pitch maximum for 16’ (4.9 m) spacing.

      2/12 (10.0°) pitch maximum for 18’ (5.5 m) spacing.

      1.9/12 (9.0°) pitch maximum for 20’ (6.1 m) spacing. 

     Angles based on sprinklers installed 0’-4” (0-102 mm) from peak.

    NOTE: Whenever possible, utilize design as shown in Figure 3 above.

    Pendent Sprinklers

    Multiple Slope

    Multiple Slope

    Sprinkler RES8

    Horizontal Sidewall Sprinklers

    (Spray Across the Slope)

  • 8/20/2019 installation guid.pdf

    10/18

    TECHNICAL DATA

    January 13, 2012

    The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

    Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

    FREEDOM ®  RESIDENTIAL

    SPRINKLER

    INSTALLATION GUIDE

    SPACING OF RESIDENTIAL SPRINKLERS BELOW SLOPED CEILINGS WITH GREATER THAN8/12 (33.7°) PITCH WITH NO BAFFLE AND A MAXIMUM OF 2 SPRINKLERS IN THE ROOM

    (NOTE: Refer to NFPA 13D or NFPA 13R, and the Authority Having Jurisdiction.)

    SPACING OF RESIDENTIAL SPRINKLERS BELOW CEILINGS WITH SLOPES EXCEEDING 8/12(33.7°) PITCH WITH NO BAFFLE AND A MAXIMUM OF 3 SPRINKLERS IN THE ROOM

    (NOTE: Refer to NFPA 13D or NFPA 13R, and the Authority Having Jurisdiction.)

    Figure 5

    (A) One-half listed spacing of sprinkler, maximum.

    (B) 8’-0” (2.4 m) minimum.

    (C) 0’-4” (0-102 mm) minimum.

    (D) 3’-0” (.91 m) maximum.

    (E) Acceptable for slopes greater than an 8/12 (33.7°) pitch.

    (F) When this design is used, refer to the appendices of NFPA 13D or NFPA 13R, and the Authority

    Having Jurisdiction regarding the number of design sprinklers to hydraulically calculate.

    Figure 6

    (A) 0’-4” (0-102 mm) minimum, to one-half listed spacing, maximum.

    (B) One-half listed spacing, maximum, 8’-0” (2.4 m) minimum.

    (C) 0’-4” (0-102 mm) minimum.

    (D) Listed spacing maximum, 8’-0” (2.4 m) minimum.

    (E) 3’-0” (.91 m) maximum.

    (F) Slopes greater than 8/12 up to a 21/12 (33.7° up to 60°) pitch.

    NOTES: In addition to the above limits, rooms requiring this type of installation must be hydraulically cal-

    culated to supply a minimum of three operating sprinklers. Layout similar for horizontal sidewall sprinklers

    with throw across slope. Refer to the appropriate residential sprinkler technical data sheets.

    Multiple Slope

    Multiple Slope

    Sprinkler RES9

  • 8/20/2019 installation guid.pdf

    11/18

    FREEDOM ®  RESIDENTIAL

    SPRINKLER

    INSTALLATION GUIDETECHNICAL DATA

    January 13, 2012

    The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

    Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

    SPACING OF RESIDENTIAL SPRINKLERS BELOW CEILINGS WITH SLOPES EXCEEDING8/12 (33.7°) PITCH WITH NO BAFFLE AND A MAXIMUM OF 2 SPRINKLERS IN THE ROOM

    (NOTE: Refer to NFPA 13D or NFPA 13R, and the Authority Having Jurisdiction.)

    Figure 7

    (A) 0’-4” (0-102 mm) minimum, to one-half listed spacing, maximum.

    (B) One-half listed spacing, maximum, 8’-0” (2.4 m) minimum.

    (C) 0’-4” (0-102 mm) minimum.

    (D) Slopes greater than 8/12 pitch up to a 21/12 (33.7° up to a 60°) pitch.

    (E) 3’-0” (.91 m) maximum.

    (F) When dimension “F” exceeds 16’ (4.9 m), utilize design configuration shown in Figure 6.

    NOTES: Layout similar for horizontal sidewall sprinklers with throw across slope. Refer to the appropriate

    residential sprinkler technical data sheets.

    Figure 8

    (A) One-half listed spacing, maximum.

    (B) Refer to the appropriate residential sprinkler technical data pages for listings of sprinklers for

    use below slopes up to and including a 8/12 (33.7°) pitch.

    (C) 3’-0” (.91 m) maximum.

    (D) 0’-4” (0-102 mm) minimum.

    (E) 8’-0” (2.4 m) minimum without baffle.

    NOTES: Layout similar for horizontal sidewall sprinklers with throw across slope. Refer to the appropriate

    residential sprinkler technical data sheets.

    Multiple Slope

    Multiple Slope Single SlopeMultiple Slope

    Sprinkler RES10

  • 8/20/2019 installation guid.pdf

    12/18

    TECHNICAL DATA

    January 13, 2012

    The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

    Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

    FREEDOM ®  RESIDENTIAL

    SPRINKLER

    INSTALLATION GUIDE

    MINIMUM DISTANCE BETWEEN SPRINKLER AND INTERSECTING SLOPED CEILINGS

    NOTES: For any ceiling slope under 7/12 (30°),

    distribution is considered Not Unduly Obstructed.

    A B

    4’ (1.2 m)

    3’ (.91 m)

    2’ (.61 m)

    30 35 40 45

    20’ (6.1 m)

    18’ (5.5 m)

    16’ (4.9 m)

    14’ (4.3 m)

    12’ (3.7 m)

       (   A   )   M   i  n   i  m  u  m    D

       i  s   t  a  n  c  e   t  o   C   h  a  n  g  e   i  n   S   l  o  p  e   (   f  e  e   t   )

    AB

    DISTRIBUTION NOT

    UNDULY OBSTRUCTED

    DISTRIBUTION

    OBSTRUCTED

       M  a  x   i  m  u  m    S

      p  r   i  n   k   l  e  r   S  p

      a  c   i  n  g   U  s  e   d   (   f  e  e   t   )

       (   A   )   D   i  s   t  a  n  c  e   D  o

      w  n   S   l  o  p  e   (   f  e  e   t   )

    NOT UNDULY OBSTRUCTED

    OBSTRUCTED

    6’ (1.8 m)

    4’ (1.2 m)

    2’ (.61 m)

    0’

    0 5 10 15

    20’ (6.1 m)

    18’ (5.5 m)

    16’ (4.9 m)

    14’ (4.3 m)

    12’ (3.7 m)

    20 25 30 35 40 45

    8’ (2.4 m)

    10’ (3.05 m)

    12’ (3.7 m)

    (B) Slope of Ceiling (degrees)

    MAXIMUM DISTANCE DOWN SLOPE TO AVOID OBSTRUCTION TO SPRINKLER DISCHARGE

    1’ (305 mm)

    3’-6” (1.06 m)

    2’-6” (.76 m)

    1’-6” (.46 m)

    12/12 (inches(B) Slope of Ceiling (degrees)

    Sprinkler RES11

  • 8/20/2019 installation guid.pdf

    13/18

    FREEDOM ®  RESIDENTIAL

    SPRINKLER

    INSTALLATION GUIDETECHNICAL DATA

    January 13, 2012

    The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

    Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

    AVOIDING OBSTRUCTIONS TO SPRINKLER DISCHARGE(Obstruction rules for residential sprinklers are found in section 8.10 of the 2010 edition of NFPA 13.)

    Positioning Residential Pendent Sprinklers - Obstructions at the Ceiling

    A

    B

    Residential pendent sprinklers may be

    located on opposite sides of continuous

    obstructions up to 4 ft. (1.2 m) wide at the

    ceiling, as long as the distance from the

    centerline of the obstruction to the sprinklers

    (A) does not exceed one-half the maximum

    spacing allowed between sprinklers.

    Positioning Residential Pendent Sprinklers - Obstructions Along Walls

    A

      B

    (A) Distance from centerline of sprinkler to side of obstruction.(B) Distance from deflector to bottom of obstruction.

    (C) Width of the obstruction.

    Obstructions up to 30 in. (.8 m) wide (C)

    located against the wall are permitted

    to be protected when (A) is greater than

    or equal to (C) minus 8 in. (.2 m) plus (B).

    C < 30 in. for metric C < .8 m

     A > (C - 8 in.) + B A > (C - .2 m) + B

    A A

    B

    A

    Distance from Sprinkler

    to Side of Ceiling

    Obstruction (Dimension A)

    Maximum Distance from

    Deflector to Bottom of Ceiling

    Obstruction (Dimension B)

    Inches mm

    Less than 1 ft. 6 in.(Less than 457 mm)

    0 0

    1 ft. 6 in. to less than 3 ft.

    (457 mm to less than .94 m)

    1 25.4

    3 ft. to less than 4 ft.(.91 m to less than 1.2 m)

    3 76

    4 ft. to less than 4 ft. 6 in.(1.2 m to less than 1.37 m)

    5 127

    4 ft. 6 in. to less than 6 ft.(1.37 m to less than 1.8 m)

    7 178

    6 ft. to less than 6 ft. 6 in.(1.8 m to less than 2 m)

    9 229

    6 ft. 6 in. to less than 7 ft.(2 m to less than 2.1 m)

    11 279

    7 ft. or greater(2.1 m or greater)

    14 356

    C

    Sprinkler RES12

    4’ Max.

  • 8/20/2019 installation guid.pdf

    14/18

    TECHNICAL DATA

    January 13, 2012

    The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

    Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

    FREEDOM ®  RESIDENTIAL

    SPRINKLER

    INSTALLATION GUIDE

    AVOIDING OBSTRUCTIONS TO SPRINKLER DISCHARGE(Obstruction rules for residential sprinklers are found in section 8.10 of the 2010 edition of NFPA 13.)

    A

    B

    Positioning Residential Horizontal SidewallSprinklers - Obstructions Along Walls

    (A) Distance from sprinkler to side of obstruction.

    (B) Distance from deflector to bottom of obstruction.

    A

    B

    A

    Distance from Sprinkler to

    Side of Ceiling Obstruction

    (Dimension A)

    Maximum Distance from Deflector

    to Bottom of Ceiling Obstruction

    (Dimension B)

    Inches mm

    Less than 8 ft.

    (Less than 2.4 m)No Obstructions Allowed

    8 ft. to less than 10 ft.(2.4 m to less than 3.05 m)

    1 25.4

    10 ft. to less than 11 ft.(3.05 m to less than 3.35 m)

    2 50.8

    11 ft. to less than 12 ft.(3.35 m to less than 3.7 m)

    3 76

    12 ft. to less than 13 ft.(3.7 m to less than 4 m)

    4 102

    13 ft. to less than 14 ft.(4 m to less than 4.3 m)

    6 152

    14 ft. to less than 15 ft.(4.3 m to less than 4.6 m)

    7 178

    15 ft. to less than 16 ft.(4.6 m to less than 4.9 m)

    9 229

    16 ft. to less than 17 ft.(4.9 m to less than 5.2 m)

    11 279

    17 ft. or greater(5.2 m or greater)

    14 356

    (A) Distance from sprinkler to side of obstruction.

    (B) Distance from deflector to bottom of obstruction.

    Ceiling or Roof.

    Obstruction

    Wall

    Distance from Sprinkler to

    Side of Obstruction Along

    Wall (Dimension A)

    Maximum Distance from

    Deflector to Bottom of

    Obstruction (Dimension B)

    Inches mm

    Less than 1 ft. 6 in.

    (Less than 457 mm)0 0

    1 ft. 6 in. to less than 3 ft.(457 mm to less than .94 m)

    1 25.4

    3 ft. to less than 4 ft.

    (.91 m to less than 1.2 m)

    3 76

    4 ft. to less than 4 ft. 6 in.(1.2 m to less than 1.37 m)

    5 127

    4 ft. 6 in. to less than 6 ft.(1.37 m to less than 1.8 m)

    7 178

    6 ft. to less than 6 ft. 6 in.(1.8 m to less than 2 m)

    9 229

    6 ft. 6 in. to less than 7 ft.(2 m to less than 2.1 m)

    11 279

    7 ft. or greater(2.1 m or greater)

    14 356

      B

    Positioning Residential HorizontalSidewall Sprinklers - Obstructions

    at the Ceiling

    Sprinkler RES13

  • 8/20/2019 installation guid.pdf

    15/18

    FREEDOM ®  RESIDENTIAL

    SPRINKLER

    INSTALLATION GUIDETECHNICAL DATA

    January 13, 2012

    The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

    Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

    LOCATING RESIDENTIAL SPRINKLERS NEAR HEAT SOURCES

    Heat Source

    Minimum Distance from

    Edge of Source to Ordinary

    Temperature Rated Sprinkler 

    Minimum Distance from

    Edge of Source to Intermediate

    Temperature Rated Sprinkler 

    Inches metric Inches metric

    Side of open or recessed fireplace 36 .91 m 12 305 mm

    Front of recessed fire place 60 1.5 m 36 .91 m

    Coal- or wood-burning stove 42 1.1 m 12 305 mm

    Kitchen range 18 457 mm 9 229 mm

    Wall oven 18 457 mm 9 229 mm

    Hot air flues 18 457 mm 9 229 mm

    Uninsulated heat ducts 18 457 mm 9 229 mm

    Uninsulated hot water pipes 12 305 mm 6 152 mm

    Side of ceiling- or 

    wall-mounted hot air diffusers24 .61 m 12 305 mm

    Front of wall-mounted hot air diffusers 36 .91 m 18 457 mm

    Hot water heater or furnace 6 152 mm 3 76 mm

    Light fixture less than 250W 6 152 mm 3 76 mm

    Light fixture 250W to 499W 12 305 mm 6 152 mm

    Where residential sprinklers will be exposed to the rays of the sun passing through glass or plastic skylights, use inter-

    mediate temperature rated sprinklers.

    When locating residential sprinklers in an unventilated concealed compartment, under an unventilated attic or unin-

    sulated roof, where the maximum ambient temperature does not exceed 150 °F, use intermediate temperature rated

    sprinklers.

    Ordinary temperature rated residential sprinklers (135 °F to 170 °F rated) are only to be installed where the maximum ambient

    ceiling temperature will not exceed 100 °F. Where the maximum ambient ceiling temperature will be from 101 °F to 150 °F, use

    intermediate temperature rated residential sprinklers (175 °F to 225 °F rated).

    Residential sprinklers must be positioned a sufficient distance away from heat sources that include fireplaces, stoves, kitchen

    ranges, wall ovens, hot water pipes, water heaters, furnaces and associated flues and ducts, and light fixtures. The following

    minimum distances must be maintained for both ordinary and intermediate temperature rated residential sprinklers as indicated.

    Sprinkler RES14

  • 8/20/2019 installation guid.pdf

    16/18

    TECHNICAL DATA

    January 13, 2012

    The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

    Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

    FREEDOM ®  RESIDENTIAL

    SPRINKLER

    INSTALLATION GUIDE

    NOTE: The dimensions shown are intended to apply to residential sprinklers installed in ceilings above fireplaces used to burn

    products that cause elevated temperatures at or near the ceiling in areas surrounding the fireplace. The recommendations should

    not be construed to apply to decorative non-opening fireplaces such as gas fire units that will not cause elevated temperatures

    at the ceiling.

    3’-0” (.91 m)

    Sprinklers near an open hearth fireplace must be located outside of the shaded area or be intermediate degree rated.

    3’-0” (.91 m)

    Side of fireplace

    Front of fireplace

    3’-0” (.91 m)

    5’-0” (1.5 m)

    Sprinklers near a recessed hearth fireplace must be located outside of the shaded area [at least 3’-0” (.91 m)] from the side

    of a recessed fireplace and at least 5’-0” (1.5 m) from the front) or be intermediate degree rated.

    Top View

    Front View

    Front View

    Top View

    Sprinkler RES15

  • 8/20/2019 installation guid.pdf

    17/18

    FREEDOM ®  RESIDENTIAL

    SPRINKLER

    INSTALLATION GUIDETECHNICAL DATA

    January 13, 2012

    The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

    Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

    Sprinklers near a furnace or water heater must be located outside of the shaded area or be intermediate degree rated.

    1’-6” (457 mm) TYP

    Edge of coal- or wood-burning stove

    3’-6” (1.1 m)

    3’-6” (1.1 m)

    Sprinklers near a coal- or wood-burning stove must be located outside of shaded area or be intermediate degree rated.

    2’-6” (.8 m) TYP

    1’-6” (457 mm) TYP

    3’-6” (1.1 m)

    Edge of coal- or wood-burning stove

    Front View

    Top View

    Front View

    Top View

    Sprinkler RES16

  • 8/20/2019 installation guid.pdf

    18/18

    TECHNICAL DATA

    January 13, 2012

    The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

    Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

    FREEDOM ®  RESIDENTIAL

    SPRINKLER

    INSTALLATION GUIDE

    Sprinklers near a range or wall oven must be located outside of shaded areas or be intermediate degree rated.

    1’-6” (457 mm)

    1’-6” (457 mm) TYP

    Front View

    Top View

    Sprinkler RES17