INSTALLATION INSTRUCTIONS 2 PORT ZONE VALVE VAL222MV VAL228MV VAL222MV and VAL228MV are 2 port spring return zone valves with 22mm and 28mm compression fittings and an auxiliary switch. This is for general purpose flow control applications or central heating systems. When correctly wired with an appropriate room thermostat, cylinder thermostat and programmer the valve will control the water flow from the boiler to hot water and from boiler to central heating. INSTALLATION Before fitting the valve, read through the plumbing and wiring instructions. When replacing the valve actuator only, set the Auto/Manual lever to the “Manual Open” position before removal. On the replacement actuator set the Auto/Manual lever to “Manual Open” position before fitting. WIRING All wiring should be carried out to IEE Regulations Brown - live Orange - end switch out Grey - end switch in Blue - neutral Green & Yellow - earth PLUMBING When connecting to pipe work do not use the actuator for leverage. Valves should be held by wrench flats on body. Place the AUTO/MAN lever in the MAN position when filling, venting or draining the system TAKE CARE NOT TO OVERTIGHTEN SPECIFICATIONS Supply voltage 240V. AC 50Hz Power consumption: 6W Operating temperature range: +5 to +88 0 C Cable length one metre Max. differential pressure for 22mm = 1Bar Max. static pressure 10.0 Bar Max. fluid temperature 100 0 C Max. ambient temperature 52 0 C WARNING All controls must be earthed. All valves should have a means of disconnection from electrical mains supply which incorporates a contact separation of at least 3mm in all Poles. All wiring must be carried out by a competent electrician. TFC GROUP LTD Tower House, Vale Rise, Tonbridge, Kent, TN9 1TB, Telephone: 01732 359888 Fax: 01732 354445 Typical circuit using two zone Valves (VAL222MV) Programmer, Room Thermostat and Cylinder Thermostat 45 0 45 0 88 60 93 55 55 A B PROGRAMMER HEATNG H, WATER L N ON OFF ON OFF L N 240V AC 50 Hz Supply fused at 3A CALL = THERMOSTAT DEMAND SAT = THERMOSTAT NO DEMAND COM = COMMON COM COM CALL CALL SAT SAT BROWN GREY BLUE ORANGE GRN/YLO BROWN GREY BLUE ORANGE GRN/YLO PERMANENT LIVE NEUTRAL P B NEUTRAL (P=PUMP) NEUTRAL (B=BOILER) Valve Valve ALL DIMENSIONS IN MM Cylinder Thermostat

INSTALLATION INSTRUCTIONS 2 PORT ZONE VALVE VAL222MV · PDF fileINSTALLATION INSTRUCTIONS 2 PORT ZONE VALVE VAL222MV VAL228MV ... When correctly wired with an appropriate room thermostat,

Embed Size (px)

Citation preview

Page 1: INSTALLATION INSTRUCTIONS 2 PORT ZONE VALVE VAL222MV · PDF fileINSTALLATION INSTRUCTIONS 2 PORT ZONE VALVE VAL222MV VAL228MV ... When correctly wired with an appropriate room thermostat,

INSTALLATION INSTRUCTIONS 2 PORT ZONE VALVE VAL222MV VAL228MV

VAL222MV and VAL228MV are 2 port spring return zone valves with 22mm and 28mm compression fittings and an auxiliary switch. This is for general purpose flow control applications or central heating systems. When correctly wired with an appropriate room thermostat, cylinder thermostat and programmer the valve will control the water flow from the boiler to hot water and from boiler to central heating.

INSTALLATION Before fitting the valve, read through the plumbing and wiring instructions. When replacing the valve actuator only, set the Auto/Manual lever to the “Manual Open” position before removal. On the replacement actuator set the Auto/Manual lever to “Manual Open” position before fitting. WIRING All wiring should be carried out to IEE Regulations Brown - live Orange - end switch out Grey - end switch in Blue - neutral Green & Yellow - earth PLUMBING When connecting to pipe work do not use the actuator for leverage. Valves should be held by wrench flats on body. Place the AUTO/MAN lever in the MAN position when filling, venting or draining the system TAKE CARE NOT TO OVERTIGHTEN

SPECIFICATIONS • Supply voltage 240V. AC 50Hz • Power consumption: 6W • Operating temperature range: +5 to +88 0C • Cable length one metre • Max. differential pressure for 22mm = 1Bar • Max. static pressure 10.0 Bar • Max. fluid temperature 100 0C • Max. ambient temperature 52 0C

WARNING All controls must be earthed. All valves should have a means of disconnection from electrical mains supply which incorporates a contact separation of at least 3mm in all Poles. All wiring must be carried out by a competent electrician.

TFC GROUP LTD Tower House, Vale Rise, Tonbridge, Kent, TN9 1TB, Telephone: 01732 359888 Fax: 01732 354445

Typical circuit using two zone Valves (VAL222MV) Programmer, Room Thermostat and Cylinder Thermostat

450 450

88 60

93

55

55

A B

PROGRAMMER HEATNG H, WATER L N ON OFF ON OFF

L N

240V AC 50 Hz Supply fused

at 3A

CALL = THERMOSTAT DEMAND SAT = THERMOSTAT NO DEMAND COM = COMMON

COM COM

CALL

CALL SAT

SAT

BROWN

GREY

BLUE

ORANGE

GRN/YLO

BROWN

GREY

BLUE

ORANGE

GRN/YLO

PERMANENT LIVE

NEUTRAL

P B NEUTRAL (P=PUMP) NEUTRAL (B=BOILER)

Val

ve

Val

ve

ALL DIMENSIONS IN MM

Cylinder Thermostat

Page 2: INSTALLATION INSTRUCTIONS 2 PORT ZONE VALVE VAL222MV · PDF fileINSTALLATION INSTRUCTIONS 2 PORT ZONE VALVE VAL222MV VAL228MV ... When correctly wired with an appropriate room thermostat,

INSTALLATION INSTRUCTIONS MID-POSITION VALVE VAL322MP VAL328MP

INSTALLATION Before fitting the valve, read through the plumbing and wiring instructions. When replacing the valve actuator only, set the Auto/Manual lever to the “Manual Open” position before removal. On the replacement actuator set the Auto/Manual lever to “Manual Open” position before fitting. WIRING All wiring should be carried out to IEE Regulations White - Room Thermostat Call / Heating on Grey - Cylinder Thermostat Sat / Hot water off Orange - Cylinder Thermostat Call / Boiler and Pump Blue - Neutral Green & Yellow - Earth PLUMBING When connecting to pipe work do not use the actuator for leverage. Valves should be held by wrench flats on body. Place the AUTO/MAN lever in the MAN position when filling, venting or draining the system. TAKE CARE NOT TO OVERTIGHTEN

SPECIFICATIONS • Supply voltage 240V. AC 50Hz • Power consumption: 6W • Operating temperature range: +5 to +88 0C • Cable length one metre • Max. differential pressure for 22mm = 1Bar • Max. static pressure 10.0 Bar • Max. ambient temperature 52 0C

MOUNTING OPTIONS Valves may be mounted vertically, or horizontally within the limits shown in the diagram. WARNING All controls must be earthed. All valves should have a means of disconnection from electrical mains supply which incorporates a contact separation of at least 3mm in all Poles. All wiring must be carried out by a competent Electrician.

TFC GROUP LTD Tower House, Vale Rise, Tonbridge, Kent, TN9 1TB, Telephone: 01732 359888 Fax: 01732 354445

88 60

55

55

43.5

122

93

All dimensions in MM Port AB = Pumped flow from boiler Port A = Heating circuit Port B = Domestic hot water circuit

A B

AB

Mid - position Valve Typical circuit showing Programmer, Room and Cylinder Thermostats as control elements

PROGRAMMER HEATING H,WATER

L N ON OFF OFF ON

INCLUDE IF PROGRAMMER HAS A HEATING ONLY SELECTION

240V AC 50Hz Supply fused

At 3A

COM

SAT CALL

ROOM THERMOSTAT

COM

CALL SAT

CYLINDER THERMOSTAT

TO BOILER & PUMP VALVE

GR

N /

YLO

BLU

E

WH

ITE

OR

ANG

E

GR

EY

450 450

VAL322MP and VAL328MP are 3 port spring return mid-position valves with 22mm and 28mm compression fittings and switched output. These are for use on fully pumped systems which when correctly wired with an appropriate room thermostat, cylinder thermostat and programmer will control the water flow from the boiler to either to hot water only, heating only, or to both simultaneously.