60
Page 1 06/11 *2P0611* 506710−01 *P506710-01* E 2011 Lennox Industries Inc. Dallas, Texas, USA DOWNFLOW AIR FLOW CAUTION As with any mechanical equipment, personal injury can result from contact with sharp sheet metal edges. Be careful when you handle this equipment. This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in manuals, be alert to the potential for personal injury or death. INSTALLATION INSTRUCTIONS SL280DFV DAVE LENNOX SIGNATURE ® COLLECTION GAS FURNACE DOWNFLOW AIR DISCHARGE 506710−01 06/2011 Supersedes 01/2011 THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCE WARNING Improper installation, adjustment, alteration, service or maintenance can cause property damage, person- al injury or loss of life. Installation and service must be performed by a licensed professional installer (or equivalent), service agency or the gas supplier. NOTICE A thermostat is not included and must be ordered separately. D The Lennox icomfort Toucht thermostat must be used in communicating applications. D In non−communicating applications, the Lennox ComfortSense ® 7000 thermostat may be used, as well as other non−communicating thermostats. In all cases, setup is critical to ensure proper sys- tem operation. Field wiring for both communicating and non−com- municating applications is illustrated in diagrams, which begin on Page 23. Table of Contents Unit Dimensions 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Parts Arrangement 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SL280DFV Gas Furnace 4 . . . . . . . . . . . . . . . . . . . . . . . . . Shipping and Packing List 4 . . . . . . . . . . . . . . . . . . . . . . . . Safety Information 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Use of Furnace as a Construction Heater 5 . . . . . . . . . . . General 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Combustion, Dilution & Ventilation Air 6 . . . . . . . . . . . . . . Setting Equipment 10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Filters 11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Duct System 12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Venting 12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Gas Piping 19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical 21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Integrated Control Settings 32 . . . . . . . . . . . . . . . . . . . . . . . Blower Performance Data 35 . . . . . . . . . . . . . . . . . . . . . . . . Unit Start−Up 39 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Gas Pressure Adjustment 40 . . . . . . . . . . . . . . . . . . . . . . . . Proper Combustion 40 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . High Altitude 41 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Other Unit Adjustments 42 . . . . . . . . . . . . . . . . . . . . . . . . . . Heating Sequence of Operation 42 . . . . . . . . . . . . . . . . . . . Service 44 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Planned Service 47 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Repair Parts List 47 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Integrated Control Diagnostic Codes 48 . . . . . . . . . . . . . . . Program Unit Capacity/Size Mode 55 . . . . . . . . . . . . . . . . . Troubleshooting 56 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Litho U.S.A.

INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

  • Upload
    others

  • View
    11

  • Download
    0

Embed Size (px)

Citation preview

Page 1: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 1

06/11

��������506710−01

����������

� 2011 Lennox Industries Inc.

Dallas, Texas, USA

DOWNFLOW

AIR FLOW

CAUTIONAs with any mechanical equipment, personal injurycan result from contact with sharp sheet metaledges. Be careful when you handle this equipment.

This is a safety alert symbol and should never be ignored.When you see this symbol on labels or in manuals, be alertto the potential for personal injury or death.

INSTALLATIONINSTRUCTIONSSL280DFVDAVE LENNOX SIGNATURE®

COLLECTION GAS FURNACEDOWNFLOW AIR DISCHARGE

506710−0106/2011Supersedes 01/2011

THIS MANUAL MUST BE LEFT WITH THEHOMEOWNER FOR FUTURE REFERENCE

WARNINGImproper installation, adjustment, alteration, serviceor maintenance can cause property damage, person-al injury or loss of life. Installation and service mustbe performed by a licensed professional installer (orequivalent), service agency or the gas supplier.

NOTICEA thermostat is not included and must be orderedseparately.

� The Lennox icomfort Touch� thermostat must beused in communicating applications.

� In non−communicating applications, the LennoxComfortSense® 7000 thermostat may be used, aswell as other non−communicating thermostats.

In all cases, setup is critical to ensure proper sys-tem operation.

Field wiring for both communicating and non−com-municating applications is illustrated in diagrams,which begin on Page 23.

Table of ContentsUnit Dimensions 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Parts Arrangement 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SL280DFV Gas Furnace 4. . . . . . . . . . . . . . . . . . . . . . . . .

Shipping and Packing List 4. . . . . . . . . . . . . . . . . . . . . . . .

Safety Information 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Use of Furnace as a Construction Heater 5. . . . . . . . . . .

General 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Combustion, Dilution & Ventilation Air 6. . . . . . . . . . . . . .

Setting Equipment 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Filters 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Duct System 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Venting 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Gas Piping 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Electrical 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Integrated Control Settings 32. . . . . . . . . . . . . . . . . . . . . . . Blower Performance Data 35. . . . . . . . . . . . . . . . . . . . . . . . Unit Start−Up 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Gas Pressure Adjustment 40. . . . . . . . . . . . . . . . . . . . . . . . Proper Combustion 40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . High Altitude 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Other Unit Adjustments 42. . . . . . . . . . . . . . . . . . . . . . . . . . Heating Sequence of Operation 42. . . . . . . . . . . . . . . . . . . Service 44. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Planned Service 47. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Repair Parts List 47. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Integrated Control Diagnostic Codes 48. . . . . . . . . . . . . . . Program Unit Capacity/Size Mode 55. . . . . . . . . . . . . . . . . Troubleshooting 56. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Litho U.S.A.

Page 2: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 2

Unit Dimensions − inches (mm)

GAS PIPING INLET(Either Side)

FLUE OUTLET(Top)

ELECTRICAL INLET(Either Side)

RETURN AIROPENING

FRONT VIEW SIDE VIEW

TOP VIEW

A

B

C

D

3/4(19)

27−3/4(7705)

19−1/4(489)

6−5/8 (168) Right7−1/8 (181) Left

5−3/8 (137) Right2−1/8 (54) Left

33(838)

19−7/16(494)

9/16(14)

B

SupplyAir

SupplyAir

9/16(14)

9/16(14)

3−1/8(79)

9/16(14)

9/16(14)

19−7/16(494)

1−1/2 (38)Front Panel

Model No.A B C D

in. mm in. mm in. mm in. mm

SL280DF070V36A 14−1/2 368 13−3/8 340 13 330 4−3/4 121

SL280DF090V48B 17−1/2 446 16−3/8 416 16 406 6−1/4 159

SL280DF090V60CSL280DF110V60C

21 533 19−7/8 504 19−1/2 495 8 203

Page 3: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 3

Parts Arrangement

FIGURE 1

BLOWER ASSEMBLY

INTERNAL FLUEPIPE ASSEMBLY

FLUE CHASE

GASKET

DOOR INTERLOCK SWITCH

HEAT EXCHANGER

COMBUSTION AIR INDUCER

COMBUSTION AIR INDUCERPRESSURE SWITCHES

GAS VALVE

BURNER BOX ASSEMBLYINNER BLOWER ACCESS PANEL

ACCESS PANEL

CONTROL BOX

(Includes two−stage integrated control,

transformer and circuit breaker)

ROLLOUT SWITCH

PRIMARY LIMIT LOCATION

SECONDARY LIMIT

Page 4: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 4

SL280DFV Gas Furnace

The SL280DFV gas furnace is equipped with a two−stage,

variable speed integrated control. the control is compat-

ible with:

Communicating thermostats − icomfort Touch®.

Non−communicating thermostats − ComfortSense or oth-

er conventional thermostats.

Control systems − Harmony III� Zone Control System

(non−communicating). Each SL280DFV unit is shipped

ready for installation in the downflow position.

Shipping and Packing List

Package 1 of 1 contains

1 − Assembled SL280DFV unit

1 − Bag assembly containing the following:

2 − Screws

1 − Snap bushing

1 − Snap plug

1 − Wire tie

1 − Vent warning label

1 − Owner’s manual and warranty card

The following items may be ordered separately:

1 − Thermostat

1 − Propane/LP changeover kit

1 − Combustible flooring base

Check equipment for shipping damage. If you find any

damage, immediately contact the last carrier.

Safety Information

DANGERDanger of explosion.

There are circumstances in which odorant used withLP/propane gas can lose its scent. In case of a leak,LP/propane gas will settle close to the floor and maybe difficult to smell. An LP/propane leak detectorshould be installed in all LP applications.

WARNINGImproper installation, adjustment, alteration, serviceor maintenance can cause property damage, person-al injury or loss of life. Installation and service mustbe performed by a licensed professional installer (orequivalent), service agency or the gas supplier.

CAUTIONAs with any mechanical equipment, personal injurycan result from contact with sharp sheet metaledges. Be careful when you handle this equipment.

Certifications

SL280DFV units are CSA International certified.

In the USA, installation of gas furnaces must conform with

local building codes. In the absence of local codes, units

must be installed according to the current National Fuel

Gas Code (ANSI-Z223.1). The National Fuel Gas Code is

available from the following address:

American National Standards Institute, Inc.

11 West 42nd Street

New York, NY 10036

Clearances

Adequate clearance must be made around the air open-

ings into the vestibule area. In order to ensure proper unit

operation, combustion and ventilation air supply must be

provided according to the current National Fuel Gas Code.

Vent installations must be consistent with the venting

tables (in this instruction) and applicable provisions of local

building codes.

This furnace is CSA International certified for installation

clearances to combustible material as listed on the unit

nameplate and in the tables in figure 13. Accessibility and

service clearances must take precedence over fire protection

clearances.

Installed Locations

For installation in a residential garage, the furnace must

be installed so that the burner(s) and the ignition source

are located no less than 18 inches (457 mm) above the

floor. The furnace must be located or protected to avoid

physical damage by vehicles. When a furnace is installed

in a public garage, hangar, or other building that has a haz-

ardous atmosphere, the furnace must be installed accord-

ing to recommended good practice requirements and cur-

rent National Fuel Gas Code.

NOTE − Furnace must be adjusted to obtain a temperature

rise (high and low fire) within the range(s) specified on the unit

nameplate. Failure to do so may cause erratic limit operation

and may also result in premature heat exchanger failure.

This SL280DFV furnace must be installed so that its electri-

cal components are protected from water.

Installed in Combination with a Cooling Coil

When this furnace is used with cooling units, it shall be

installed in parallel with, or on the upstream side of, cooling

units to avoid condensation in the heating compartment.

With a parallel flow arrangement, a damper (or other

means to control the flow of air) must adequately prevent

Page 5: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 5

chilled air from entering the furnace (see figure 1). If the

damper is manually operated, it must be equipped to pre-

vent operation of either the heating or the cooling unit, un-

less it is in the full HEAT or COOL setting.

FIGURE 1

AIR HANDLERGAS UNIT

Dampers(open during cooling

operation only)

Dampers(open during heating

operation only)

When installed, this furnace must be electrically grounded

according to local codes. In addition, in the United States,

installation must conform with the current National Elec-

tric Code, ANSI/NFPA No. 70. The National Electric Code

(ANSI/NFPA No. 70) is available from the following ad-

dress:

National Fire Protection Association

1 Battery March Park

Quincy, MA 02269

NOTE − This furnace is designed for a minimum continu-

ous return air temperature of 60°F (16°C) or an intermit-

tent operation down to 55°F (13°C) dry bulb for cases

where a night setback thermostat is used. Return air tem-

perature must not exceed 85°F (29°C) dry bulb.

The SL280DFV furnace may be installed in alcoves, clos-

ets, attics, basements, garages, and utility rooms in the

downflow position.

This furnace design has not been CSA International certi-

fied for installation in mobile homes, recreational vehicles,

or outdoors.

Use of Furnace as Construction Heater

Lennox does not recommend the use of SL280DFV units

as a construction heater during any phase of construction.

Very low return air temperatures, harmful vapors and op-

eration of the unit with clogged or misplaced filters will dam-

age the unit.

SL280DFV units may be used for heating of buildings or

structures under construction, if the following conditions

are met:

� The vent system must be permanently installed per

these installation instructions.

� A room thermostat must control the furnace. The use of

fixed jumpers that will provide continuous heating is not

allowed.

� The return air duct must be provided and sealed to the

furnace.

� Return air temperature range between 60°F (16°C) and

80°F (27°C) must be maintained.

� Air filters must be installed in the system and must be

maintained during construction.

� Air filters must be replaced upon construction comple-

tion.

� The input rate and temperature rise must be set per the

furnace rating plate.

� One hundred percent (100%) outdoor air must be pro-

vided for combustion air requirements during construc-

tion. Temporary ducting may supply outdoor air to the

furnace. Do not connect duct directly to the furnace.

Size the temporary duct following these instructions in

section for Combustion, Dilution and Ventilation Air in a

confined space with air from outside.

� The furnace heat exchanger, components, duct system,

air filters and evaporator coils must be thoroughly

cleaned following final construction clean−up.

� All furnace operating conditions (including ignition, in-

put rate, temperature rise and venting) must be verified

according to these installation instructions.

General

These instructions are intended as a general guide and do

not supersede local codes in any way. Consult authorities

having jurisdiction before installation.

In addition to the requirements outlined previously, the fol-

lowing general recommendations must be considered

when installing a SL280DFV furnace:

� Place the furnace as close to the center of the air dis-

tribution system as possible. The furnace should also be

located close to the chimney or vent termination point.

� Do not install the furnace where drafts might blow direct-

ly into it. This could cause improper combustion and un-

safe operation.

� Do not block the furnace combustion air openings with

clothing, boxes, doors, etc. Air is needed for proper

combustion and safe unit operation.

� When the furnace is installed in an attic or other insu-

lated space, keep insulation away from the furnace.

NOTE − The Commonwealth of Massachusetts stipu-

lates these additional requirements:

� Gas furnaces shall be installed by a licensed plumb-

er or fitter only.

Page 6: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 6

� The gas cock must be �T handle" type.

� When a furnace is installed in an attic, the passage-

way to and service area surrounding the equipment

shall be floored.

WARNINGProduct contains fiberglass wool.

Disturbing the insulation in this product duringinstallation, maintenance, or repair will expose youto fiberglass wool. Breathing this may cause lungcancer. (Fiberglass wool is known to the State of Cal-ifornia to cause cancer.)

Fiberglass wool may also cause respiratory, skin,and eye irritation.

To reduce exposure to this substance or for furtherinformation, consult material safety data sheetsavailable from address shown below, or contact yoursupervisor.

Lennox Industries Inc.P.O. Box 799900Dallas, TX 75379−9900

Combustion, Dilution & Ventilation Air

In the past, there was no problem in bringing in sufficient out-

door air for combustion. Infiltration provided all the air that

was needed. In today’s homes, tight construction practices

make it necessary to bring in air from outside for combus-

tion. Take into account that exhaust fans, appliance vents,

chimneys, and fireplaces force additional air that could be

used for combustion out of the house. Unless outside air is

brought into the house for combustion, negative pressure

(outside pressure is greater than inside pressure) will build

to the point that a downdraft can occur in the furnace vent

pipe or chimney. As a result, combustion gases enter the liv-

ing space creating a potentially dangerous situation.

In the absence of local codes concerning air for combus-

tion and ventilation, use the guidelines and procedures in

this section to install SL280DFV furnaces to ensure effi-

cient and safe operation. You must consider combustion air

needs and requirements for exhaust vents. A portion of this

information has been reprinted with permission from the

National Fuel Gas Code (ANSI-Z223.1). This reprinted ma-

terial is not the complete and official position of the ANSI on

the referenced subject, which is represented only by the

standard in its entirety.

CAUTIONDo not install the furnace in a corrosive or contami-nated atmosphere. Meet all combustion and ventila-tion air requirements, as well as all local codes.

CAUTIONInsufficient combustion air can cause headaches,nausea, dizziness or asphyxiation. It will also causeexcess water in the heat exchanger resulting in rust-ing and premature heat exchanger failure. Excessiveexposure to contaminated combustion air will resultin safety and performance related problems. Avoidexposure to the following substances in the combus-tion air supply:

Permanent wave solutionsChlorinated waxes and cleanersChlorine base swimming pool chemicalsWater softening chemicalsDe-icing salts or chemicalsCarbon tetrachlorideHalogen type refrigerantsCleaning solvents (such as perchloroethylene)Printing inks, paint removers, varnishes, etc.Hydrochloric acidCements and gluesAntistatic fabric softeners for clothes dryersMasonry acid washing materials

All gas-fired appliances require air for the combustion pro-

cess. If sufficient combustion air is not available, the fur-

nace or other appliances will operate inefficiently and un-

safely. Enough air must be provided to meet the needs of all

fuel-burning appliances and appliances such as exhaust

fans which force air out of the house. When fireplaces, ex-

haust fans, or clothes dryers are used at the same time as

the furnace, much more air is necessary to ensure proper

combustion and to prevent a downdraft. Insufficient air

causes incomplete combustion which can result in carbon

monoxide.

In addition to providing combustion air, fresh outdoor air

dilutes contaminants in the indoor air. These contami-

nants may include bleaches, adhesives, detergents, sol-

vents and other contaminants which can corrode furnace

components.

The requirements for providing air for combustion and ven-

tilation depend largely on whether the furnace is installed in

an unconfined or a confined space.

Unconfined Space

An unconfined space is an area such as a basement or

large equipment room with a volume greater than 50 cubic

feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the com-

bined input rating of all appliances installed in that space.

This space also includes adjacent rooms which are not

separated by a door. Though an area may appear to be un-

confined, it might be necessary to bring in outdoor air for

combustion if the structure does not provide enough air by

infiltration. If the furnace is located in a building of tight

construction with weather stripping and caulking around

the windows and doors, follow the procedures in the air

from outside section.

Page 7: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 7

Confined Space

A confined space is an area with a volume less than 50 cu-

bic feet (1.42 m3) per 1,000 Btu (.29 kW) per hour of the

combined input rating of all appliances installed in that

space. This definition includes furnace closets or small

equipment rooms.

When the furnace is installed so that supply ducts carry air

circulated by the furnace to areas outside the space contain-

ing the furnace, the return air must be handled by ducts

which are sealed to the furnace casing and which terminate

outside the space containing the furnace. This is especially

important when the furnace is mounted on a platform in a

confined space such as a closet or small equipment room.

Even a small leak around the base of the unit at the platform

or at the return air duct connection can cause a potentially

dangerous negative pressure condition. Air for combustion

and ventilation can be brought into the confined space either

from inside the building or from outside.

EQUIPMENT IN CONFINEDSPACE ALL AIR FROM INSIDE

CHIMNEYOR GAS

VENT

FURNACE

WATERHEATER

OPENINGS(To Adjacent

Room)

NOTE − Each opening shall have a free area of at least one squareinch (645 mm2) per 1,000 Btu (.29 kW) per hour of the total input rat-ing of all equipment in the enclosure, but not less than 100 squareinches (64516 mm2).

FIGURE 2

Air from Inside

If the confined space that houses the furnace adjoins a

space categorized as unconfined, air can be brought in by

providing two permanent openings between the two

spaces. Each opening must have a minimum free area of 1

square inch (645 mm2) per 1,000 Btu (.29 kW) per hour of

total input rating of all gas−fired equipment in the confined

space. Each opening must be at least 100 square inches

(64516 mm2). One opening shall be within 12 inches (305

mm) of the top of the enclosure and one opening within 12

inches (305 mm) of the bottom. See figure 2.

Air from Outside

If air from outside is brought in for combustion and ventila-

tion, the confined space must have two permanent open-

ings. One opening shall be within 12 inches (305 mm) of the

top of the enclosure and one opening within 12 inches (305

mm) of the bottom. These openings must communicate di-

rectly or by ducts with the outdoors or spaces (crawl or at-

tic) that freely communicate with the outdoors or indirectly

through vertical ducts. Each opening shall have a minimum

free area of 1 square inch (645 mm2) per 4,000 Btu (1.17

kW) per hour of total input rating of all equipment in the en-

closure. See figures 3 and 4. When communicating with

the outdoors through horizontal ducts, each opening shall

have a minimum free area of 1 square inch (645 mm2) per

2,000 Btu (.56 kW) per total input rating of all equipment in

the enclosure. See figure 5.

When ducts are used, they shall be of the same cross−sec-

tional area as the free area of the openings to which they

connect. The minimum dimension of rectangular air ducts

shall be no less than 3 inches (75 mm). In calculating free

area, the blocking effect of louvers, grilles, or screens must

be considered. If the design and free area of protective cov-

ering is not known for calculating the size opening required,

it may be assumed that wood louvers will have 20 to 25 per-

cent free area and metal louvers and grilles will have 60 to

75 percent free area. Louvers and grilles must be fixed in the

open position or interlocked with the equipment so that they

are opened automatically during equipment operation.

Page 8: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 8

EQUIPMENT IN CONFINED SPACEALL AIR FROM OUTSIDE

(Inlet Air from Crawlspace and Outlet Air to Ventilated Attic)

NOTE−The inlet and outlet air openings shall each have a free area of at least one square inch (645mm2) per 4,000 Btu (1.17 kW) per hour of the total input rating of all equipment in the enclosure.

VENTILATION LOUVERS(Each end of attic)

OUTLETAIR WATER

HEATER

INLETAIR

CHIMNEY ORGAS VENT

FURNACE

VENTILATIONLOUVERS

(For unheated crawl space)

FIGURE 3

EQUIPMENT IN CONFINED SPACEALL AIR FROM OUTSIDE

(All Air Through Ventilated Attic)

NOTE−The inlet and outlet air openings shall each have afree area of at least one square inch (645 mm2) per 4,000Btu (1.17 kW) per hour of the total input rating of all equip-ment in the enclosure.

CHIMNEYOR GAS

VENT

WATERHEATER

OUTLETAIR

VENTILATION LOUVERS(Each end of attic)

INLET AIR(Ends 12 in.

above bottom)

FURNACE

FIGURE 4

EQUIPMENT INCONFINED SPACE

ALL AIR FROMOUTSIDE

OUTLET AIR

INLET AIR

WATERHEATER

CHIMNEYOR GAS

VENT

NOTE − Each air duct opening shall have a free area of at leastone square inch (645 mm2) per 2,000 Btu (.59 kW) per hour ofthe total input rating of all equipment in the enclosure. If theequipment room is located against an outside wall and the airopenings communicate directly with the outdoors, each open-ing shall have a free area of at least one square inch (645 mm2)per 4,000 Btu (1.17 kW) per hour of the total input rating of allother equipment in the enclosure.

FURNACE

FIGURE 5

Page 9: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 9

Downflow Installation

Downflow unit installs in three ways: on non−combustible

flooring, on combustible flooring using a downflow com-

bustible flooring base, or on a reverse−flow cooling cabinet.

Do not drag the unit across the floor.

Installation on Non−Combustible Flooring (Figure 6)

1 − Cut floor opening keeping in mind clearances listed on

unit rating plate. Also keep in mind gas supply connec-

tions, electrical supply, flue and air intake connections

and sufficient installation and servicing clearances.

See table 1 for correct floor opening size.

2 − Flange warm air plenum and lower the plenum into the

opening.

3 − Set the unit over the plenum and seal the plenum to

the unit.

4 − Ensure that the seal is adequate.

FIGURE 6

SL280DFV UNIT

SUPPLY AIRPLENUMOPENING

TABLE 1NON−COMBUSTIBLE FLOOR OPENING SIZE

Cabinet WidthFront to Rear Side to Side

in. mm in. mm

A (14.5") 19−3/4 502 13−1/4 337

B (17.5") 19−3/4 502 16−1/4 413

C (21") 19−3/4 502 19−3/4 502

NOTE − Door opening dimensions listed are 1/4 inch (6 mm) larger thanthe unit opening. See unit dimensions on page 2.

Installation on Combustible Flooring (Figure 7)

1 − When unit is installed on a combustible floor, a down-

flow combustible flooring base must be installed be-

tween the furnace and the floor. The base must be or-

dered separately.

See table 2 for opening size to cut in floor.

CAUTIONThe furnace and downflow combustible flooringbase shall not be installed directly on carpeting, tile,or other combustible material other than wood floor-ing.

SL280DFV UNIT

SUPPLY AIR PLENUM

DOWNFLOWCOMBUSTIBLE

FLOORING BASE

PROPERLYSIZED FLOOR

OPENING

FIGURE 7

TABLE 2COMBUSTIBLE FLOOR OPENING SIZE

Cabinet WidthFront to Rear Side to Side

in. mm in. mm

A (14.5") 22 559 15−3/4 400

B (17.5") 22 559 18−3/4 476

C (21") 22 559 22−3/4 578

NOTE − Floor opening dimensions listed are 1/4 inch (6 mm) larger thanunit opening. See unit dimensions on page 2.

2 − After opening is cut, set combustible flooring base into

opening.

3 − Check sealing strips on combustible flooring base to

make sure they are properly glued and positioned.

4 − Lower supply air plenum into downflow combustible

flooring base until plenum flanges seal against the

strips.

NOTE − Be careful not to damage sealing strips. Check

for a tight seal.

5 − Set the furnace over the plenum.

6 − Ensure that the seal between the furnace and plenum

is adequate.

Installation on Cooling Cabinet (Figure 8)

1 − Refer to reverse−flow coil installation instructions for

correctly sized opening in floor and installation of cabi-

net.

NOTE − Downflow combustible flooring kit is not used

2 − When cooling cabinet is in place, set and secure the

furnace according to the instructions that are provided

with the cooling coil. Secure the furnace to the cabinet.

3 − Seal the cabinet and check for air leaks.

Page 10: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 10

SL280DFV UNIT

COOLING COIL

PLENUM

FIGURE 8

PROPERLYSIZED FLOOR

OPENING

Return Air Opening −− Downflow Units

The following steps should be taken when installing ple-

num:

1 − Bottom edge of plenum should be flanged with a

hemmed edge (See figure 9).

SECURE FROM

OUTSIDE CABINET

HEMMED EDGE

PLENUM

SEALING STRIP

(Field Provided)

CABINET SIDE PANEL

Side View

FIGURE 9

2 − Sealing strip should be used.

3 − In all cases, plenum should be secured to top flanges

of furnace with sheet metal screws.

SECURE FROM IN-

SIDE CABINET

HEMMED EDGE

FIBERGLASS

SEALING STRIP

(Field Provided)CABINET SIDE

PANEL

PLENUM

Side View

FIGURE 10

4 − In closet installations, it may be impossible to install

sheet metal screws from the outside. In this case,

make plenum with a removable front and install

screws from the inside (See figure 10).

5 − Make certain that an adequate seal is made.

Setting Equipment

WARNINGDo not install the furnace on its front, back or in thehorizontal position. See figure 12. Do not connect thereturn air ducts to the back of the furnace. Doing sowill adversely affect the operation of the safety con-trol devices, which could result in personal injury ordeath.

Install the SL280DFV gas furnace as shipped in the

downflow position only. Do not install the furnace hori-

zontally.

Select a location that allows for the required clearances

that are listed on the unit nameplate. Also consider gas

supply connections, electrical supply, vent connection,

and installation and service clearances [24 inches (610

mm) at unit front]. The unit must be level.

NOTE − Units with 1/2 hp blower motors are equipped with

three flexible legs and one rigid leg. See figure 11. The rigid

leg is equipped with a shipping bolt and a flat white plastic

washer (rather than the rubber mounting grommet used

with a flexible mounting leg). The bolt and washer must

be removed before the furnace is placed into opera-

tion. After the bolt and washer have been removed, the rig-

id leg will not touch the blower housing.

FIGURE 11

RIGID LEGremove shipping bolt and washer

SL280DFV07036A WITH 1/2 HPBLOWER MOTOR

WARNINGThe blower access panel must be securely in placewhen the blower and burners are operating. Gasfumes, which could contain carbon monoxide, canbe drawn into living space resulting in personal inju-ry or death.

Page 11: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 11

FIGURE 12

Front BackHorizontal

Downflow Application

Allow for clearances to combustible materials as indi-

cated on the unit nameplate. Minimum clearances for

closet or alcove installations are shown in figure 13.

Downflow Application Installation Clearances

Top

Bottom

Left Side Right Side

Type of VentConnector

Type C Type B1

Top 1 in. (25 mm) 1 in. (25 mm)

*Front 2−1/4 in. (57 mm)** 2−1/4in. (57 mm)

Back 0 0

Sides 0† 0

Vent 6 in. (152 mm) 1 in. (25 mm)

Floor NC†† NC††

*Front clearance in alcove installation must be 24 in. (610 mm).Maintain a minimum of 24 in. (610 mm) for front service access.** 3−1/4 in. if single wall vent pipe is used.†Left side requires 3 in. if a single wall vent is used on 14 −1/2 in. cab-inets, or 2 in. if a single wall vent is used on 17 − 1/2 in. cabinets.††The furnace may be installed on a combustible wood floor if anoptional additive base is installed between the furnace and thecombustible floor.

FIGURE 13

WARNINGImproper installation of the furnace can result in per-sonal injury or death. Combustion and flue productsmust never be allowed to enter the return air systemor the living space. Use screws and joint tape to sealthe return air system to the furnace.In platform installations with bottom return air, thefurnace should be sealed airtight to the return air ple-num. A door must never be used as a portion of thereturn air duct system. The base must provide astable support and an airtight seal to the furnace. Al-low absolutely no sagging, cracks, gaps, etc.The return and supply air duct systems must neverbe connected to or from other heating devices suchas a fireplace or stove, etc. Fire, explosion, carbonmonoxide poisoning, personal injury and/or proper-ty damage could result.

Filters

This unit is not equipped with a filter or rack. A field−pro-

vided high−velocity filter is required for the unit to operate

properly. Table 3 lists recommended filter sizes.

A filter must be in place any time the unit is operating.

TABLE 3

Cabinet Width Return Air Filter Size (inches)

A (14−1/2") 14 x 25 x 1 (1)

B (17−1/2") 16 x 25 x 1 (1)

C (21") 20 x 25 x 1 (1)

Page 12: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 12

Duct System

Use industry-approved standards (such as those pub-

lished by Air Conditioning Contractors of America or Ameri-

can Society of Heating, Refrigerating and Air Conditioning

Engineers) to size and install the supply and return air duct

system. This will result in a quiet and low-static system that

has uniform air distribution.

NOTE − Do not operate the furnace in the heating mode

with an external static pressure that exceeds 0.8 inches

w.c. Higher external static pressures may cause erratic lim-

it operation.

Ensure that you have made a seal between the supply air

plenum and the furnace and between the furnace and the

return air plenum.

Return Air Plenum

Return air must not be drawn from a room where this

furnace, or any other gas−fueled appliance (i.e., water

heater), or carbon monoxide−producing device (i.e.,

wood fireplace) is installed. When return air is drawn

from a room, a negative pressure is created in the room. If

a gas appliance is operating in a room with negative pres-

sure, the flue products can be pulled back down the vent

pipe and into the room. This reverse flow of the flue gas

may result in incomplete combustion and the formation

of carbon monoxide gas. This toxic gas might then be dis-

tributed throughout the house by the furnace duct sys-

tem.

Venting

A 4−inch diameter flue transition is factory-installed on allmodels. Modifying or removing the flue transition willcause the unit to operate unsafely and will void the unitcertification. The vent connector does not require insula-tion.

The SL280DFV series units are classified as fan−assisted

Category I furnaces when vertically vented according to

the latest edition of National Fuel Gas Code (NFPA 54 /

ANSI Z223.1). A fan−assisted Category I furnace is an ap-

pliance equipped with an integral mechanical means to ei-

ther draw or force combustion products through the com-

bustion chamber and/or heat exchanger.

NOTE − Use these instructions as a guide. They do not su-

persede local codes. This furnace must be vented accord-

ing to all local codes, these installation instructions, and the

provided venting tables in these instructions

The venting tables in this manual were extracted from the

National Fuel Gas Code (NFPA 54 / ANSI Z223.1) and are

provided as a guide for proper vent installation. Proper ap-

plication, termination, construction and location of vents

must conform to local codes having jurisdiction. In the ab-

sence of local codes, the NFGC serves as the defining doc-

ument.

Refer to the tables and the venting information contained in

these instructions to properly size and install the venting

system.

IMPORTANTOnce the venting system is installed, attach the �Dis-connected Vent" warning sticker to a visible area ofthe plenum near the vent pipe. The warning stickeris provided in the bag assembly. Order kit 66W04 foradditional stickers.

WARNINGAsphyxiation hazard. The exhaust vent for this fur-nace must be securely connected to the furnace fluetransition at all times.

FLUE TRANSITIONCOLLAR

VENT CONNECTION “DISCONNECTED VENT”WARNINGSTICKER

FIGURE 14

Use self−drilling sheet metal screws or a mechanical fas-tener to firmly secure the vent pipe to the round collar of theflue transition. If self−drilling screws are used to attach thevent pipe, it is recommended that three be used. Drive oneself−drilling screw through the front and one through eachside of the vent pipe and collar. See figure 14.

Masonry chimneys used to vent Category I central fur-naces must be either tile-lined or lined with a listed metallining system or dedicated gas vent. Unlined masonrychimneys are prohibited. See figures 15 and 16 for com-mon venting.

Page 13: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 13

FIGURE 15

Common Venting Using Tile−Lined Interior Masonry Chimney and Combined Vent Connector

MINIMUM LENGTH = AS SHORT AS PRACTICAL. FOR MAXIMUM LENGTH SEE NOTE TO LEFT

INTERIOR TILE−LINEDMASONRY CHIMNEY

NOTE − the chimney must be properlysized per provided venting tables orlined with listed metal lining system.

PERMANENTLYSEALED FIREPLACEOPENING

VENTCONNECTOR

NOTE− Refer to provided ventingtables for installations.

FURNACE

OTHERAPPLIANCE

Venting Using a Masonry Chimney

The following additional requirements apply when a linedmasonry chimney is used to vent this furnace.

A chimney with one or more sides exposed to the outside ofthe structure is considered to be an exterior chimney.

An exterior masonry chimney that is not tile−lined must be

lined with B1 vent or a listed insulated flexible metal vent.

An exterior tile−lined chimney that is sealed and capped

may be lined with a listed uninsulated flexible metal vent.

If the existing chimney will not accommodate a listed metal

liner, either the chimney must be rebuilt to accommodate

one of these liners or an alternate approved venting meth-

od must be found.

Insulation for the flexible vent pipe must be an encapsu-

lated fiberglass sleeve recommended by the flexible vent

pipe manufacturer. See figure 16.

FIGURE 16

Common Venting Using Metal−Lined Masonry Chimney

4 in. (102 mm)minimum

MIN. LENGTH −− ASSHORT AS PRACTICAL

MAX. LENGTH−− SEE NOTE

BELOW.

SEALED

PERMANENTLYSEALED FIREPLACE

OPENING

EXTERIORCHIMNEY WITH

METALLINER

VENT CONNECTOR

NOTE 1 − Refer to the provided venting tables for installations.

OTHERAPPLIANCE

FURNACE

5 ft. (1.5 m)minimum

DO NOT insulate the space between the liner and the

chimney wall with puffed mica or any other loose gran-

ular insulating material

IMPORTANTSINGLE appliance venting of a fan-assisted furnaceinto a tile-lined masonry chimney (interior or outsidewall) is PROHIBITED. The chimney must first be linedwith either type B1 vent or an insulated single wallflexible vent lining system which has been sized ac-cording to the provided venting tables and the ventpipe manufacturer’s instructions.

A fan−assisted furnace may be commonly vented into anexisting lined masonry chimney if the following conditionsare met:

� The chimney is currently serving at least one drafthoodequipped appliance

� The vent connectors and chimney are sized accordingto the provided venting tables.

If type B1 double-wall vent is used inside a chimney, no oth-

er appliance can be vented into the chimney. The outer wall

of type B1 vent pipe must not be exposed to flue products.

A type B1 vent or masonry chimney liner shall terminate

above the roof surface with a listed cap or a listed roof as-

sembly according to the terms of their respective listings

and the vent manufacturer’s instructions.

When inspection reveals that an existing chimney is not

safe for the intended purpose, it shall be rebuilt to conform

to nationally recognized standards, lined or relined with

suitable materials, or replaced with a gas vent or chimney

suitable for venting SL280DFV series units. The chimney

passageway must be checked periodically to ensure that it

is clear and free of obstructions.

Do not install a manual damper, barometric draft regulator,

or flue restrictor between the furnace and the chimney.

Page 14: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 14

Never connect a Category I appliance to a chimney that isservicing a solid−fuel appliance. If a fireplace chimney flueis used to vent this appliance, the fireplace opening mustbe permanently sealed.

A type B or listed chimney lining system that passesthrough an unused masonry chimney flue is not consideredto be exposed to the outdoors.

General Venting Requirements

Vent all SL280DFV furnaces according to these instruc-

tions:

1 − Vent diameter recommendations and maximum allow-

able piping runs are found in the provided venting

tables.

2 − In no case should the vent or vent connector diameter

be less than the diameter specified in the provided

venting tables.

3 − The minimum vent capacity determined by the sizing

tables must be less than the low fire input rating and the

maximum vent capacity must be greater than the high

fire input rating.

4 − Single appliance vents − If the vertical vent or tile-lined

chimney has a larger diameter or flow area than the

vent connector, use the vertical vent diameter to de-

termine the minimum vent capacity and the vent

connector diameter to determine the maximum vent

capacity. The flow area of the vertical vent, however,

shall not exceed 7 times the flow area of the listed ap-

pliance categorized vent area, drafthood outlet area or

flue collar area unless designed according to approved

engineering methods.

5 − Multiple appliance vents − The flow area of the largest

section of vertical vent or chimney shall not exceed 7

times the smallest listed appliance categorized vent

area, drafthood outlet area or flue collar area unless de-

signed according to approved engineering methods.

6 − The entire length of single wall metal vent connector

shall be readily accessible for inspection, cleaning,

and replacement.

7 − Single appliance venting configurations with zero lat-

eral lengths (tables 5 and 6) are assumed to have no

elbows in the vent system. For all other vent configura-

tions, the vent system is assumed to have two 90° el-

bows. For each additional 90° elbow or equivalent (for

example two 45° elbows equal one 90° elbow) beyond

two, the maximum capacity listed in the venting table

should be reduced by 10% (0.90 x maximum listed ca-

pacity).

8 − The common venting tables (7, 8, 9, and 10) were gen-

erated using a maximum horizontal vent connector

length of 1−1/2 feet (.46 m) for each inch (25 mm) of

connector diameter as follows:

TABLE 4

Connector Diameterinches (mm)

Maximum HorizontalConnector Length feet (m)

3 (76) 4−1/2 (1.37)

4 (102) 6 (1.83)

5 (127) 7−1/2 (2.29)

6 (152) 9 (2.74)

7 (178) 10−1/2 (3.20)

9 − If the common vertical vent is offset, the maximum

common vent capacity listed in the common venting

tables should be reduced by 20%, the equivalent of two

90° elbows (0.80 x maximum common vent capacity).

The horizontal length of the offset shall not exceed

1-1/2 feet (.46 m) for each inch (25 mm) of common

vent diameter.

10 − The vent pipe should be as short as possible with the

least number of elbows and angles required to com-

plete the job. Route the vent connector to the vent us-

ing the shortest possible route.

11 − A vent connector shall be supported without any dips

or sags and shall slope a minimum of 1/4 inch (6.4 mm)

per linear foot (305 mm) of connector, back toward the

appliance.

12 − Vent connectors shall be firmly attached to the furnace

flue collar by self−drilling screws or other approved

means, except vent connectors of listed type B vent

material which shall be assembled according to the

manufacturer’s instructions. Joints between sections

of single wall connector piping shall be fastened by

screws or other approved means.

13 − When the vent connector used for Category I ap-

pliances must be located in or pass through a crawl-

space or other areas which may be cold, that portion of

the vent connector shall be constructed of listed

double-wall type B vent material or material having

equivalent insulation qualities.

14 − All venting pipe passing through floors, walls, and ceil-

ings must be installed with the listed clearance to com-

bustible materials and be fire stopped according to lo-

cal codes. In absence of local codes, refer to NFGC

(Z223.1).

15 − No portion of the venting system can extend into, or pass

through any circulation air duct or plenum.

16 − Vent connectors serving Category I appliances shall

not be connected to any portion of mechanical draft

systems operating under positive pressure such as

Category III or IV venting systems.

17 − If vent connectors are combined prior to entering the

common vent, the maximum common vent capacity

listed in the common venting tables must be reduced by

10%, the equivalent of one 90° elbow (0.90 x maximum

common vent capacity).

Page 15: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 15

18 − The common vent diameter must always be at least as

large as the largest vent connector diameter.

19 − In no case, shall the vent connector be sized more than

two consecutive table size diameters over the size of

the draft hood outlet or flue collar outlet.

20 − Do not install a manual damper, barometric draft regu-

lator or flue restrictor between the furnace and the

chimney.

21 − When connecting this appliance to an existing dedi-

cated or common venting system, you must inspect the

venting system’s general condition and look for signs

of corrosion. The existing vent pipe size must conform

to these instructions and the provided venting tables. If

the existing venting system does not meet these re-

quirements, it must be resized.

TABLE 5

Capacity of Type B Double−Wall Vents with Type B Double−Wall Connectors

Serving a Single Category I Appliance

HeightH

(feet)

LateralL

(feet)

Vent and Connector Diameter − D (inches)

3 Inch 4 Inch 5 Inch 6 Inch

Appliance Input Rating in Thousands of Btu Per Hour

MIN MAX MIN MAX MIN MAX MIN MAX

6

0 0 78 0 152 0 251 0 375

2 13 51 18 97 27 157 32 232

4 21 49 30 94 39 153 50 227

6 25 46 36 91 47 149 59 223

8

0 0 84 0 165 0 276 0 415

2 12 57 16 109 25 178 28 263

5 23 53 32 103 42 171 53 255

8 28 49 39 98 51 164 64 247

10

0 0 88 0 175 0 295 0 447

2 12 61 17 118 23 194 26 289

5 23 57 32 113 41 187 52 280

10 30 51 41 104 54 176 67 267

15

0 0 94 0 191 0 327 0 502

2 11 69 15 136 20 226 22 339

5 22 65 30 130 39 219 49 330

10 29 59 40 121 51 206 64 315

15 35 53 48 112 61 195 76 301

20

0 0 97 0 202 0 349 0 540

2 10 75 14 149 18 250 20 377

5 21 71 29 143 38 242 47 367

10 28 64 38 133 50 229 62 351

15 34 58 46 124 59 217 73 337

20 48 52 55 116 69 206 84 322

30

0 0 100 0 213 0 374 0 587

2 9 81 13 166 14 283 18 432

5 21 77 28 160 36 275 45 421

10 27 70 37 150 48 262 59 405

15 33 64 44 141 57 249 70 389

20 56 58 53 132 66 237 80 374

30 NR NR 73 113 88 214 104 346

NOTE − Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all othervent configurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for example two 45°elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maxi-mum listed capacity).

Page 16: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 16

TABLE 6

Capacity of Type B Double−Wall Vents with Single−Wall Metal Connectors

Serving a Single Category I Appliance

HeightH

(feet)

LateralL

(feet)

Vent and Connector Diameter − D (inches)

3 Inch 4 Inch 5 Inch 6 Inch

Appliance Input Rating in Thousands of Btu Per Hour

MIN MAX MIN MAX MIN MAX MIN MAX

6

0 38 77 59 151 85 249 126 373

2 39 51 60 96 85 156 123 231

4 NR NR 74 92 102 152 146 225

6 NR NR 83 89 114 147 163 220

8

0 37 83 58 164 83 273 123 412

2 39 56 59 108 83 176 121 261

5 NR NR 77 102 107 168 151 252

8 NR NR 90 95 122 161 175 243

10

0 37 87 57 174 82 293 120 444

2 39 61 59 117 82 193 119 287

5 52 56 76 111 105 185 148 277

10 NR NR 97 100 132 171 188 261

15

0 36 93 56 190 80 325 116 499

2 38 69 57 136 80 225 115 337

5 51 63 75 128 102 216 144 326

10 NR NR 95 116 128 201 182 308

15 NR NR NR NR 158 186 220 290

20

0 35 96 54 200 78 346 114 537

2 37 74 56 148 78 248 113 375

5 50 68 73 140 100 239 141 363

10 NR NR 93 129 125 223 177 344

15 NR NR NR NR 155 208 216 325

20 NR NR NR NR 186 192 254 306

30

0 34 99 53 211 76 372 110 584

2 37 80 55 164 76 281 109 429

5 49 74 72 157 98 271 136 417

10 NR NR 91 144 122 255 171 397

15 NR NR 115 131 151 239 208 377

20 NR NR NR NR 181 223 246 357

30 NR NR NR NR NR NR NR NR

NOTE − Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all othervent configurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for example two 45°elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maxi-mum listed capacity).

Page 17: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 17

TABLE 7

Vent Connector Capacity

Type B Double−Wall Vents with Type B Double−Wall Connectors

Serving Two or More Category I Appliances

VentHeight

H(feet)

ConnectorRise

R(feet)

Vent and Connector Diameter − D (inches)

3 Inch 4 Inch 5 Inch 6 Inch

Appliance Input Rating in Thousands of Btu Per Hour

MIN MAX MIN MAX MIN MAX MIN MAX

6

1 22 37 35 66 46 106 58 164

2 23 41 37 75 48 121 60 183

3 24 44 38 81 49 132 62 199

8

1 22 40 35 72 49 114 64 176

2 23 44 36 80 51 128 66 195

3 24 47 37 87 53 139 67 210

10

1 22 43 34 78 49 123 65 189

2 23 47 36 86 51 136 67 206

3 24 50 37 92 52 146 69 220

15

1 21 50 33 89 47 142 64 220

2 22 53 35 96 49 153 66 235

3 24 55 36 102 51 163 68 248

20

1 21 54 33 99 46 157 62 246

2 22 57 34 105 48 167 64 259

3 23 60 35 110 50 176 66 271

30

1 20 62 31 113 45 181 60 288

2 21 64 33 118 47 190 62 299

3 22 66 34 123 48 198 64 309

TABLE 8

Common Vent Capacity

Type B Double−Wall Vents with Type B Double−Wall Connectors

Serving Two or More Category I Appliances

VentHeight

H(feet)

Common Vent Diameter − D (inches)

4 Inch 5 Inch 6 Inch 7 Inch

Appliance Input Rating in Thousands of Btu Per Hour

FAN + FAN FAN + NAT FAN + FAN FAN + NAT FAN + FAN FAN + NAT FAN + FAN FAN + NAT

6 92 81 140 116 204 161 309 248

8 101 90 155 129 224 178 339 275

10 110 97 169 141 243 194 367 299

15 125 112 195 164 283 228 427 352

20 136 123 215 183 314 255 475 394

30 152 138 244 210 361 297 547 459

Page 18: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 18

TABLE 9

Vent Connector Capacity

Type B Double−Wall Vents with Single−Wall Metal Connectors

Serving Two or More Category I Appliances

HeightH

(feet)

LateralL

(feet)

Vent and Connector Diameter − D (inches)

3 Inch 4 Inch 5 Inch 6 Inch

Appliance Input Rating in Thousands of Btu Per Hour

MIN MAX MIN MAX MIN MAX MIN MAX

6

1 NR NR NR NR NR NR NR NR

2 NR NR NR NR NR NR 168 182

3 NR NR NR NR 121 131 175 198

8

1 NR NR NR NR NR NA NR NR

2 NR NR NR NR 125 126 184 193

3 NR NR NR NR 130 138 191 208

10

1 NR NR NR NR 119 121 182 186

2 NR NR 84 85 124 134 189 203

3 NR NR 89 91 129 144 197 217

15

1 NR NR 79 87 116 138 177 214

2 NR NR 83 94 121 150 185 230

3 NR NR 87 100 127 160 193 243

20

1 49 56 78 97 115 152 175 238

2 52 59 82 103 120 163 182 252

3 55 62 87 107 125 172 190 264

30

1 47 60 77 110 112 175 169 278

2 51 62 81 115 117 185 177 290

3 54 64 85 119 122 193 185 300

NOTE − Single appliance venting configurations with zero lateral lengths are assumed to have no elbows in the vent system. For all othervent configurations, the vent system is assumed to have two 90° elbows. For each additional 90° elbow or equivalent (for example two 45°elbows equal one 90° elbow) beyond two, the maximum capacity listed in the venting table should be reduced by 10 percent (0.90 x maxi-mum listed capacity).

TABLE 10

Common Vent Capacity

Type B Double−Wall Vents with Single−Wall Metal Connectors

Serving Two or More Category I Appliances

VentHeight

H(feet)

Common Vent Diameter − D (inches)

4 Inch 5 Inch 6 Inch 7 Inch

Appliance Input Rating in Thousands of Btu Per Hour

FAN + FAN FAN + NAT FAN + FAN FAN + NAT FAN + FAN FAN + NAT FAN + FAN FAN + NAT

6 NA 78 NA 113 200 158 304 244

8 NA 87 NA 126 218 173 331 269

10 NA 94 163 137 237 189 357 292

15 121 108 189 159 275 221 416 343

20 131 118 208 177 305 247 463 383

30 145 132 236 202 350 286 533 446

Page 19: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 19

Removal of the Furnace from Common Vent

In the event that an existing furnace is removed from a

venting system commonly run with separate gas ap-

pliances, the venting system is likely to be too large to

properly vent the remaining attached appliances.

Conduct the following test while each appliance is operat-

ing and the other appliances (which are not operating) re-

main connected to the common venting system. If the

venting system has been installed improperly, you must

correct the system as indicated in the general venting re-

quirements section.

WARNINGCARBON MONOXIDE POISONING HAZARD

Failure to follow the steps outlined below for eachappliance connected to the venting system beingplaced into operation could result in carbon mon-oxide poisoning or death.The following steps shall be followed for each ap-pliance connected to the venting system beingplaced into operation, while all other appliancesconnected to the venting system are not inoperation:

1 − Seal any unused openings in the common venting sys-

tem.

2 − Inspect the venting system for proper size and horizontal

pitch. Determine that there is no blockage, restriction,

leakage, corrosion, or other deficiencies which could

cause an unsafe condition.

3 − Close all building doors and windows and all doors be-

tween the space in which the appliances remaining

connected to the common venting system are located

and other spaces of the building. Turn on clothes dry-

ers and any appliances not connected to the common

venting system. Turn on any exhaust fans, such as

range hoods and bathroom exhausts, so they will oper-

ate at maximum speed. Do not operate a summer ex-

haust fan. Close fireplace dampers.

4 − Follow the lighting instructions. Turn on the appliance

that is being inspected. Adjust the thermostat so that

the appliance operates continuously.

5 − After the main burner has operated for 5 minutes, test

for leaks of flue gases at the draft hood relief opening.

Use the flame of a match or candle, or smoke from a

cigarette, cigar, or pipe.

6 − After determining that each appliance connected to the

common venting system is venting properly, (step 3)

return all doors, widows, exhaust fans, fireplace damp-

ers, and any other gas−burning appliances to their pre-

vious mode of operation.

7 − If a venting problem is found during any of the preced-

ing tests, the common venting system must be modi-

fied to correct the problem.

Resize the common venting system to the minimum

vent pipe size determined by using the appropriate

tables in Appendix G. (These are in the current stan-

dards of the National Fuel Gas Code ANSI Z223.1.

Gas Piping

CAUTIONIf a flexible gas connector is required or allowed bythe authority that has jurisdiction, black iron pipeshall be installed at the gas valve and extend outsidethe furnace cabinet. The flexible connector can thenbe added between the black iron pipe and the gassupply line.

Gas Supply

1 − This unit is shipped standard for left or right side instal-

lation of gas piping. Connect the gas supply to the pip-

ing assembly.

2 − When connecting the gas supply piping, consider fac-

tors such as length of run, number of fittings, and fur-

nace rating to avoid excessive pressure drop. Table 11

lists recommended pipe sizes for typical applications.

3 − The gas piping must not run in or through air ducts,

clothes chutes, gas vents or chimneys, dumb waiters,

or elevator shafts.

4 − The piping should be sloped 1/4 inch (6.4 mm) per 15

feet (4.57 m) upward toward the meter from the fur-

nace. The piping must be supported at proper intervals

[every 8 to 10 feet (2.44 to 3.01 m)] with suitable hang-

ers or straps. Install a drip leg inside vertical pipe runs

to the unit.

5 − A 1/8" N.P.T. plugged tap or pressure post is located

on the gas valve to facilitate test gauge connection.

See figures 26 and 27.

6 − In some localities, codes may require the installation of

a manual main shut-off valve and union (furnished by

the installer) external to the unit. The union must be of

the ground joint type.

IMPORTANTCompounds used on threaded joints of gas pipingmust be resistant to the actions of liquified petro-leum gases.

Page 20: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 20

TABLE 11

Gas Pipe Capacity − ft3/hr (m3/hr)

NominalIron Pipe

Sizeinches(mm)

InternalDiameterinches(mm)

Length of Pipe − feet (m)

10(3.048)

20(6.096)

30(9.144)

40(12.192)

50(15.240)

60(18.288)

70(21.336)

80(24.384)

90(27.432)

100(30.480)

1/2(12.7)

.622(17.799)

175(4.96)

120(3.40)

97(2.75)

82(2.32)

73(2.07)

66(1.87)

61(1.73)

57(1.61)

53(1.50)

50(1.42)

3/4(19.05)

.824(20.930)

360(10.19)

250(7.08)

200(5.66)

170(4.81)

151(4.28)

138(3.91)

125(3.54)

118(3.34)

110(3.11)

103(2.92)

1(25.4)

1.049(26.645)

680(919.25)

465(13.17)

375(10.62)

320(9.06)

285(8.07)

260(7.36)

240(6.80)

220(6.23)

205(5.80)

195(5.52)

1−1/4(31.75)

1.380(35.052)

1400(39.64)

950(26.90)

770(21.80)

660(18.69)

580(16.42)

530(15.01)

490(13.87)

460(13.03)

430(12.18)

400(11.33)

1−1/2(38.1)

1.610(40.894)

2100(59.46)

460(41.34)

1180(33.41)

990(28.03)

900(25.48)

810(22.94)

750(21.24)

690(19.54)

650(18.41)

620(17.56)

2(50.8)

2.067(52.502)

3950(111.85)

2750(77.87)

2200(62.30)

1900(53.80)

1680(47.57)

1520(43.04)

1400(39.64)

1300(36.81)

1220(34.55)

1150(32.56)

2−1/2(63.5)

2.469(67.713)

6300(178.39)

4350(123.17)

3520(99.67)

3000(84.95

2650(75.04)

2400(67.96)

2250(63.71)

2050(58.05)

1950(55.22)

1850(52.38)

3(76.2)

3.068(77.927)

11000(311.48)

7700(218.03)

6250(176.98)

5300(150.07)

4750(134.50)

4300(121.76)

3900(110.43)

3700(104.77)

3450(97.69)

3250(92.03)

NOTE − Capacity given in cubic feet (m3 ) of gas per hour and based on 0.60 specific gravity gas.

GROUNDJOINTUNION

AUTOMATICGAS VALVE(with manual

shut−off valve)

FIELDPROVIDED

AND INSTALLED

GROUNDJOINTUNION

Left Side Piping(Standard)

Right Side Piping(Alternate)

AUTOMATICGAS VALVE(with manual

shut−off valve)

DRIP LEG

DRIP LEG

MANUALMAIN SHUT−OFF

VALVE

MANUALMAIN SHUT−OFF

VALVE

NOTE − BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET

FIGURE 17

Page 21: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 21

Leak Check

After gas piping is completed, carefully check all piping

connections (factory− and field−installed) for gas leaks. Use

a leak detecting solution or other preferred means.

NOTE − If emergency shutoff is necessary, shut off the main

manual gas valve and disconnect the main power to the

furnace. The installer should properly label these devices.

CAUTIONSome soaps used for leak detection are corrosive tocertain metals. Carefully rinse piping thoroughly af-ter leak test has been completed. Do not usematches, candles, flame or other sources of ignitionto check for gas leaks.

The furnace must be isolated from the gas supply system

by closing its individual manual shut-off valve during any

pressure testing of the gas supply system at pressures less

than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.).

IMPORTANTWhen testing pressure of gas lines, gas valve mustbe disconnected and isolated. See figure 18. Gasvalves can be damaged if subjected to pressuresgreater than 1/2 psig (3.48 kPa, 14 inches w.c.).

MANUAL MAINSHUT−OFF VALVEWILL NOT HOLDNORMAL TEST

PRESSURE

CAP

ISOLATEGAS VALVE

FURNACE

FIGURE 18

1/8 NPT PLUG

Electrical

ELECTROSTATIC DISCHARGE (ESD)

Precautions and Procedures

CAUTIONElectrostatic discharge can affect elec-tronic components. Take precautions toneutralize electrostatic charge bytouching your hand and tools to metalprior to handling the control.

The unit is equipped with a field make−up box on the left

hand side of the cabinet. The make−up box may be moved

to the right side of the furnace to facilitate installation. If the

make−up box is moved to the right hand side, clip the wire

ties that bundle the wires together. Secure the excess wire

to the existing harness to protect it from damage.

Refer to figure 24 for unit field wiring. See figures 21 and 22

for icomfort Touch® thermostat wiring in communicating

applications. Table 13 shows DIP switch and on−board link

settings for non−communicating thermostat applications.

Typical wiring schematic is shown in figure 23.

FIGURE 19

INTERIOR MAKE−UP BOX INSTALLATION(Left Side)

MAKE−UPBOX

INTERIOR MAKE−UP BOX INSTALLATION(Right Side)

FIGURE 20

MAKE−UPBOX

Cut the two wire ties to extend power wires for right side only

1 − The power supply wiring must meet Class I restric-

tions. Protected by either a fuse or circuit breaker, se-

lect circuit protection and wire size according to unit

nameplate.

NOTE − Unit nameplate states maximum current draw.

Maximum over−current protection allowed is shown in table

12.

TABLE 12

SL280DF ModelMaximum Over−Current

Protection (Amps)

070V36A 15

090V48B, 090V60C, 110V60C 20

Page 22: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 22

2 − Holes are on both sides of the furnace cabinet to facili-

tate wiring.

3 − Install a separate (properly sized) disconnect switch

near the furnace so that power can be turned off for

servicing.

4 − Before connecting the thermostat or the power wiring,

check to make sure the wires will be long enough for

servicing at a later date. Remove the blower access

panel to check the length of the wire.

5 − Complete the wiring connections to the equipment.

Use the provided unit wiring diagram and the field wir-

ing diagrams shown in table 13 and figure 24. Use

18−gauge wire or larger that is suitable for Class II ra-

ting for thermostat connections.

6 − Electrically ground the unit according to local codes or,

in the absence of local codes, according to the current

National Electric Code (ANSI/NFPA No. 70). A green

ground wire is provided in the field make−up box.

NOTE − The SL280DFV furnace contains electronic

components that are polarity sensitive. Make sure

that the furnace is wired correctly and is properly

grounded.

7 − One line voltage �ACC" 1/4" spade terminal is providedon the furnace integrated control. Any electronic aircleaner or other accessory rated up to one amp can beconnected to this terminal with the neutral leg of the cir-cuit being connected to the one of the provided neutralterminals. See figure 25 for control configuration. Thisterminal is energized when the indoor blower is operat-ing.

8 − An unpowered, normally open (dry) set of contacts witha 1/4" spade terminal �HUM" are provided for humidifi-er connections and may be connected to 24V or 120V.Any humidifier rated up to one amp can be connectedto these terminals. In 120V humidifier applications theneutral leg of the circuit can be connected to one of theprovided neutral terminals. This terminal is energizedin the heating mode.

9 − Install the room thermostat according to the instruc-tions provided with the thermostat. See table 13 forfield wiring connections in varying applications. If thefurnace is being matched with a heat pump, refer to theinstruction packaged with the dual fuel thermostat.

Thermostat Selection

CAUTIONField wiring for both communicating and non−com-municating applications is illustrated in diagrams,which begin on Page 23.

Non−Communicating

In non−communicating applications the SL280DFV is de-signed to operate in a SINGLE−STAGE mode or TWO−STAGE mode using a conventional thermostat.

For optimal performance in non−communicating applica-

tions, Lennox recommends use of a ComfortSense® 7000

high quality electronic digital thermostat or any other with

adjustable settings for 1st stage / 2nd stage on / off differen-

tials and adjustable stage timers.

Lennox recommends the following two−stage thermostatsettings:First heat stage differential set to 1/2 to 1 degree F; secondheat stage differential set to 1/2 or 1 degree F; second heatstage upstage timer disabled, or set to maximum (1 hr mini-mum).

Communicating

In communicating applications the icomfort Touch® ther-

mostat must be used. Refer to the instructions provided

with the thermostat for installation, set−up and operation. In

communicating system all unused thermostat wire in the

wire bundle needs to be terminated inside and out. The ex-

tra wires can terminate on the ’C" terminal of the icomfort�

communication terminal strip. (RSBus). Using an addition-

al wire come off "C" terminal and wire nut all the extra wires

together. Termination on the outdoor control must match

the indoor control.

Indoor Blower Speeds

Non−Communicating

1 − When the thermostat is set to �FAN ON," the indoorblower will run continuously at a field selectable per-centage of the second−stage cooling speed when thereis no cooling or heating demand. The factory defaultsetting is 38% of cool speed.

2 − When the SL280DFV is running in the heating mode,the indoor blower will run on the heating speed desig-nated by the positions of DIP switches 11, 12 and 13.First stage heating will run at 91% heat speed.

3 − When there is a cooling demand, the indoor blower willrun on the cooling speed designated by the positionsof DIP switches 5 and 6. First stage cooling will run at70% cool speed.

Communicating

NOTE − When the SL280DFV is used with icomfort

Touch® thermostat, proper indoor blower speed selec-

tions are made by the communicating thermostat.

1 − When the thermostat is set to �FAN ON," the indoorblower will run at setting determined during systemconfiguration.

2 − When there is a heating demand the fan will run onheating speeds for firing rate.

3 − When there is a cooling demand, the fan will run on thefirst stage and second stage cooling speed set usingthe icomfort Touch® thermostat in the installer setupmode. The factory default is based upon 400 CFM aton.

Page 23: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 23

Generator Use − Voltage Requirements

The following requirements must be kept in mind when

specifying a generator for use with this equipment:

� The furnace requires 120 volts (Range: 102 volts to132 volts)

� The furnace operates at 60 Hz + 5% (Range: 57 Hz to63 Hz)

� The furnace integrated control requires both correctpolarity and proper ground. Both polarity and propergrounding should be checked before attempting to op-erate the furnace on either permanent or temporarypower

� Generator should have a wave form distortion of lessthan 5% THD (total harmonic distortion)

FIGURE 21

icomfort Touch® Thermostat with SL280DFVand Non−Communicating Outdoor Unit

icomfort�−ENABLEDSL280DFVFURNACE

icomfort Touch®THERMOSTAT

NON−COMMUNICATINGOUTDOOR AIR

CONDITIONING UNIT −1 OR 2 STAGE

icomfort Touch® Thermostaticomfort�−Enabled SL280DFV Indoor FurnaceNon−Communicating Outdoor Air Conditioner

OPTIONALOUTDOOR

AIR SENSOR

OPTIONALDISCHARGEAIR SENSOR

icomfort Touch® Thermostat with SL280DFVand icomfort�−ENABLED Outdoor Unit

icomfort Touch® Thermostaticomfort�−Enabled SL280DFV Indoor Furnaceicomfort�−Enabled Outdoor Air Conditioner or Heat Pump

icomfort�−ENABLEDSL280DFVFURNACE

icomfort�− ENABLEDOUTDOOR AIR CONDITIONING

OR HEAT PUMP UNIT

OPTIONALOUTDOOR

AIR SENSOR

OPTIONALDISCHARGEAIR SENSOR

CLIP ON−BOARD LINKW915 (Y1 TO Y2) FOR

TWO−STAGE OPERATION

icomfort Touch®THERMOSTAT

icomfort� Integrated Control

icomfort Touch®

Outdoor Unit

NOTE − On communicating systems, extra wires must terminate on the "C" RSBus terminal. Use an additional wire and comeoff "C" terminal and wire nut all the extra wires together. Termination on the outdoor control must match the indoor control.

Page 24: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 24

FIGURE 22

Optional Accessories for use with any icomfort Touch® System

NOTE: 24V UV LIGHTAPPLICATIONS

In an icomfort by Lennox� system,

neither furnace nor air handler trans-

former will have adequate VA to

power 24V UV light applications. An

additional transformer for UV light

applications is required.

icomfort Touch®

THERMOSTAT

Discharge AirSensor (Required

for even heat)

NOTE: icomfort Touch® THERMOSTAT SENSES HUMIDITY& CONTROLS HUM CONTACTS TO CYCLE HUMIDIFIERBASED ON DEMAND. NO OTHER CONTROL OR HUMIDIS-TAT REQUIRED.

OPTIONAL OUTDOOR AIR SENSOR FOR USE WITH HU-MIDIFIER (IF NOT ALREADY IN THE SYSTEM FOR OTHERFUNCTIONS. BUILT INTO ALL icomfort by Lennox� OUT-DOOR UNITS).

Maximum totallength of all con-nections on theRSBus is limitedto 1500ft.

Wire gauge ofRSBus wire is 18.

RSBus

Rf

WG

hG

sC

fH

VA

C E

QU

IP

DEHUMIDIFIERCONTROL

HVACEQUIPMENT

DH

STANDARD 1 OR 2STAGE AC OR HP UNIT

*24V IN

JUMPER

icomfort� ENABLEDSL280DFV FURNACE

icomfort� ENABLEDSL280DFV FURNACE

icomfort Touch®

THERMOSTAT

CONVENTIONALNON−COMMUNI-CATING SYSTEM

COMMUNICATING SYSTEM

CS 7000THERMOSTAT

*24V IN jumper not used in non−communicating configuration

24V HUMIDIFIER CONNECTIONS

120V CONNECTIONS

HEPA BYPASS FILTER X2680 HEPA INTERLOCK KIT

PASS INDOOR BLOWERMOTOR COMMON WIRETHROUGH CURRENT LOOP.

SEE HEPA INTERLOCK KITFOR INSTALLATION DE-TAILS

icom

fort�

EN

AB

LE

DS

L280D

FV

FU

RN

AC

E

LVCS VENTILATION CONTROL SYSTEMSEE LVCS VENTILATIONINSTRUCTIONS FORDAMPER & SENSOR WIRING

icom

fort�

EN

AB

LE

DS

L280D

FV

FU

RN

AC

E

icomfort �ENABLED OUTDOOR

AIR CONDITIONING ORHEAT PUMP UNIT

(POWER COMPANY INTERRUPTION SYSTEMSARE WIRED SAME AS OVERFLOW SWITCH)ic

om

fort�

EN

AB

LE

DS

L280D

FV

FU

RN

AC

E

CUTR−DSW914

DS

R

2 STAGE FURNACE

COMMUNICATINGSYSTEM WIRING

NON−COMMUNICATINGSYSTEM WIRING

�HUM" CONTACT ISCLOSED ANYTIMEHUMIDITY DEMANDIS PRESENT

Page 25: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 25

TABLE 13

SL280 Field Wiring Applications With Conventional Thermostat

Thermostat

DIP Switch Settings and On−Board Links (See figure 25)

Wiring Connections

DIP Switch 1Thermostat

HeatingStages

On Board Links Must Be Cut To SelectSystem Options

1 Heat / 1 Cool

NOTE − Use DIPswitch 2 to setsecond−stageheat ON delay.OFF−7 minutes.ON−12 minutes.

ON

DO NOT CUT ANYON−BOARD LINKS

S1T’STAT

FURNACETERM. STRIP

OUTDOORUNIT

*

1 Heat / 2 Cool

NOTE − Use DIPswitch 2 to setsecond−stageheat ON delay.OFF−7 minutes.ON−12 minutes.

ON

CUT ON−BOARD LINKW915

2 STAGECOMPR

S1T’STAT

FURNACETERM. STRIP

OUTDOORUNIT

*

1 Heat / 2 Coolwith t’stat withhumidity control

NOTE − Use DIPswitch 2 to setsecond−stageheat ON delay.OFF−7 minutes.ON−12 minutes.

ONCUT ON−BOARD LINK

W9152 STAGECOMPR

CUT ON−BOARD LINKW914

DEHUMOR

HARMONY

S1T’STAT

FURNACETERM. STRIP

OUTDOORUNIT

o

*

* Not required on all units.

Page 26: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 26

TABLE 13

SL280 Field Wiring Applications With Conventional Thermostat (Continued)

Thermostat

DIP Switch Settings and On−Board Links (See figure 25)

Wiring Connections

DIP Switch 1Thermostat

HeatingStages

On Board Links Must Be Cut To SelectSystem Options

2 Heat / 2 Cool OFF

CUT ON−BOARD LINKW915

2 STAGECOMPR

S1T’STAT

FURNACETERM. STRIP

OUTDOORUNIT

*

2 Heat / 2 Coolwith t’stat withhumidity control

OFFCUT ON−BOARD LINK

W9152 STAGECOMPR

CUT ON−BOARD LINKW914

DEHUMOR

HARMONY

S1T’STAT

FURNACETERM. STRIP

OUTDOORUNIT

o

*

2 Heat / 1 Coolwith t’stat withhumidity control

OFF

CUT ON−BOARD LINKW914

DEHUMOR

HARMONY

S1T’STAT

FURNACETERM. STRIP

OUTDOORUNIT

o

*

2 Heat / 1 Cool OFF

DO NOT CUT ANYON−BOARD LINKS

S1T’STAT

FURNACETERM. STRIP

OUTDOORUNIT

*

* Not required on all units.

Page 27: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 27

TABLE 13

SL280 Field Wiring Applications With Conventional Thermostat (Continued)

Thermostat

DIP Switch Settings and On−Board Links (figure 25)

Wiring ConnectionsDIP Switch 1Thermostat

HeatingStages

On Board Links Must Be Cut To SelectSystem Options

Dual FuelSingle StageHeat Pump

ComfortSense7000 L7724Uthermostat w/dual fuel capa-bilitiesCapable of 2stage gas heatcontrol

OFF

CUT ON−BOARD LINKW951HEATPUMP

L7724UT’STAT

FURNACETERM. STRIP

HEAT PUMP

67M41*

Y

H

L

Y2

D

B

L

Y2

T

T

outdoorsensor

Dual FuelTwo StageHeat Pump

ComfortSense7000 L7724Uthermostat w/dual fuel capa-bilitiesCapable of 2stage gas heatcontrol

OFF

CUT ON−BOARD LINKW951HEATPUMP

CUT ON−BOARD LINKW915

2 STAGECOMPR

FURNACETERM. STRIP HEAT PUMP

out blue

67M41*

H

L

Y2

D

B

L

Y2

T

T

outdoorsensor

L7724UT’STAT

* Connect W1 to W1 ONLY if using defrost tempering kit 67M41

NOTE − Do NOT make a wire connection between the room thermostat L terminal and the L terminal of the SL280

integrated control.

Page 28: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 28

TABLE 13

SL280 Field Wiring Applications With Conventional Thermostat (Continued)

Thermostat

DIP Switch Settings and On−Board Links (figure 25)

Wiring ConnectionsDIP Switch 1Thermostat

HeatingStages

On Board Links Must Be Cut To SelectSystem Options

Dual FuelSingle StageHeat Pump

ComfortSense7000 L7724Uthermostat w/dual fuel capa-bilitiesCapable of 2stage gas heatcontrol w/dehu-midificationcontrol

OFF

CUT ON−BOARD LINKW951HEATPUMP

CUT ON−BOARD LINKW914

DEHUMOR

HARMONY

L7724UT’STAT

FURNACETERM. STRIP

HEAT PUMP

67M41*

Y

H

L

Y2

D

B

L

Y2

T

T

outdoorsensor

Dual FuelTwo StageHeat Pump

ComfortSense7000 L7724Uthermostat w/dual fuel capa-bilitiesCapable of 2stage gas heatcontrol w/dehu-midification

OFF

CUT ON−BOARD LINKW914

DEHUMOR

HARMONY

CUT ON−BOARD LINKW951HEATPUMP

CUT ON−BOARD LINKW915

2 STAGECOMPR

FURNACETERM. STRIP HEAT PUMP

out blue

67M41*

H

L

Y2

D

B

L

Y2

T

T

outdoorsensor

L7724UT’STAT

* Connect W1 to W1 ONLY if using defrost tempering kit 67M41

NOTE − Do NOT make a wire connection between the room thermostat L terminal and the L terminal of the SL280

integrated control.

Page 29: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 29

SL280DFV Schematic Wiring Diagram

FIGURE 23

Page 30: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 30

TYPICAL SL280DFV FIELD WIRING DIAGRAM

FIGURE 24

FIELD INSTALLED CLASS II 24V

FIELD INSTALLED LINE VOLTAGE

Page 31: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 31

Integrated Control

FIGURE 25

THERMOSTAT CONNECTIONS (TB1)

1/4" QUICK CONNECT TERMINALS

RS−BUS LINK (TB82, future use)

I+ = DATA HIGH CONNECTIONI − = DATA LOW CONNECTION

RS−BUS OUTDOOR (TB83)

R = 24VACI + = DATA HIGH CONNECTIONI − = DATA LOW CONNECTIONC = 24VAXC COMMON

RS−BUS INDOOR (TB84)

R = 24VACI + = DATA HIGH CONNECTIONI − = DATA LOW CONNECTIONC = 24VAXC COMMON

FLAME SENSE

DIP SWITCHES

OUTDOOR AIRSENSOR

TERMINALS

DISCHARGE AIRSENSOR

TERMINALS

INDOORBLOWER

CONNECTOR

NEUTRAL

DIAGNOSTICPUSH BUTTON

TB83COMMUNICATING

OUTDOOREQUIPMENT

TB84COMMUNICATING

INDOORTHERMOSTAT

DS = DEHUMIDIFICATION SIGNAL

W2 = HEAT DEMAND FROM 2ND STAGE T/STAT

W1 = HEAT DEMAND FROM 1ST STAGE T/STAT

R = CLASS 2 VOLTAGE TO THERMOSTAT

G = MANUAL FAN FROM T’STAT

C = THERMOSTAT SIGNAL GROUND CONNECTED TOTRANSFORMER GRD (TR) & CHASIS GROUND (GRD)

Y1 = THERMOSTAT 1ST STAGE COOL SIGNAL

Y2 = THERMOSTAT 2ND STAGE COOL SIGNAL

O = THERMOSTAT SIGNAL TO HEAT PUMPREVERSING VALVE

L = USE ONLY WITH A COMMUNICATING THERMOSTATAND A NON−COMMUNICATING OUTDOOR UNIT

DH = DEHUMIDIFICATION OUTPUT COMMUNICATINGTHERMOSTAT ONLYHUM = UNPOWERED NORMALLY OPEN (DRY) CONTACTS

XMFR = 120 VAC OUTPUT TO TRANSFORMER

LI = 120 VAC INPUT TO CONTROL

ACC = 120 VAC OUTPUT TO OPTIONAL ACCESSORY

NEUTRALS = 120 VAC NEUTRAL

W915 Y1 TO Y22 STAGE COMPR

W951 R TO OHEAT PUMP

W914 R TO DSDEHUM ORHARMONYW1 W2 G Y2 Y1 C C R DH L O DSR I + I − C R I + I − C

7 SEGMENT LED

ACC

LINE 1

HUM

12 PIN LOWVOLTAGE

CONNECTOR

NON−COMMUNICATINGNG24V TERMINALS

HS/ CAI

. . . . . . . . . . . . .

Page 32: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 32

Integrated Control DIP Switch Settings −Conventional Thermostat (non−communi-cating)

SL280DFV units are equipped with a two−stage, variablespeed integrated control. This control manages ignitiontiming, heating mode fan off delays and indoor blowerspeeds based on selections made using the control dipswitches and jumpers. The control includes an internalwatchguard feature which automatically resets the ignitioncontrol when it has been locked out. After one hour of con-tinuous thermostat demand for heat, the watchguard willbreak and remake thermostat demand to the furnace andautomatically reset the control to relight the furnace.

Note: All icomfort� settings are set at the icomfort Touch®

thermostat. See icomfort� installation instruction. In icom-

fort� communication system all DIP switch and clippable

link settings are ignored. For conventional thermostats pro-

ceed with DIP switch and clippable link settings as outlined

in the following.

Heating Operation DIP Switch Settings

Switch 1 −− Thermostat Selection −− This unit may be used

with either a single−stage or two−stage thermostat. The

thermostat selection is made using a DIP switch which

must be properly positioned for the particular application.

The DIP switch is factory−positioned for use with a two−

stage thermostat. If a single−stage thermostat is to be used,

the DIP switch must be repositioned.

Select �OFF" for two−stage heating operation con-trolled by a two−stage heating thermostat (factory set-ting);

b − Select �ON" for two−stage heating operation con-trolled by a single−stage heating thermostat. This set-ting provides a timed delay before second−stage heatis initiated.

Switch 2 −− Second Stage Delay (Used with Single−

Stage Thermostat Only) −− This switch is used to deter-

mine the second stage on delay when a single−stage ther-

mostat is being used. The switch is factory−set in the OFF

position, which provides a 7−minute delay before second−

stage heat is initiated. If the switch is toggled to the ON

position, it will provide a 12−minute delay before second−

stage heat is initiated. This switch is only activated when

the thermostat selector jumper is positioned for SINGLE−

stage thermostat use.

Switches 3 and 4 −− Blower−Off Delay −− The blower−on

delay of 30 seconds is not adjustable. The blower−off delay

(time that the blower operates after the heating demand

has been satisfied) can be adjusted by moving switches 3

and 4 on the integrated control. The unit is shipped from the

factory with a blower−off delay of 90 seconds. The blower

off delay affects comfort and is adjustable to satisfy individ-

ual applications. Adjust the blower off delay to achieve a

supply air temperature between 90° and 110°F at the exact

moment that the blower is de−energized. Longer off delay

settings provide lower supply air temperatures; shorter set-

tings provide higher supply air temperatures.Table 14 pro-

vides the blower off timings that will result from different

switch settings.

TABLE 14Blower Off Delay Switch Settings

Blower Off Delay(Seconds)

Switch 3 Switch 4

60 On Off

90 (Factory) Off Off

120 Off On

180 On On

Indoor Blower Operation DIP Switch Settings

Switches 5 and 6 −− Cooling Mode Blower Speed −− The

unit is shipped from the factory with the dip switches posi-

tioned for high speed (4) indoor blower motor operation

during the cooling mode. Table 15 provides the cooling

mode blower speeds that will result from different switch

settings. Switches 5 and 6 set the blower cfm for second−

stage cool. The integrated control automatically ramps

down to 70% of the second−stage cfm for first−stage cfm.

Refer to tables for corresponding cfm values.

TABLE 15Cooling Mode Blower Speeds

Speed Switch 5 Switch 6

Low On On

Medium Low Off On

Medium High On Off

High (Factory) Off Off

Switches 7 and 8 −− Cooling Blower Speed Adjustment

−− The unit is shipped from the factory with the dip switches

positioned for NORMAL (no) adjustment. The dip switches

may be positioned to adjust the blower speed by +10% or

−10% to better suit the application. Table 16 below provides

blower speed adjustments that will result from different

switch settings. Refer to tables for corresponding cfm val-

ues.

TABLE 16Cooling Blower Speed Adjustment

Adjustment Switch 7 Switch 8

+10% (approx.) On Off

Factory Default Off Off

−10% (approx.) Off On

Switches 9 and 10 −− Cooling Mode Blower Speed

Ramping −− Blower speed ramping may be used to en-

hance dehumidification performance. The switches are

factory set at option A which has the greatest effect on de−

humidification performance. Table 17 provides the cooling

mode blower speed ramping options that will result from

different switch settings. The cooling mode blower speed

ramping options are detailed on the next page.

Page 33: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 33

NOTE − The off portion of the selected ramp profile also ap-

plies during heat pump operation in dual fuel applications.

TABLE 17Cooling Mode Blower Speed Ramping

Ramping Option Switch 9 Switch 10

A (Factory) Off Off

B Off On

C On Off

D On On

Ramping Option A (Factory Selection)

� Motor runs at 50% for 30 seconds.

� Motor then runs at 82% for approximately 7−1/2 minu-

tes.

� If demand has not been satisfied after 7−1/2 minutes,

motor runs at 100% until demand is satisfied.

� Once demand is met, motor runs at 50% for 30 sec-

onds then ramps down to stop.

OFFOFF

1/2 MIN50% CFM

COMPRESSOR DEMAND

7 1/2 MIN82% CFM

100% CFM

1/2 MIN50% CFM

Ramping Option B� Motor runs at 82% for approximately 7−1/2 minutes. If

demand has not been satisfied after 7−1/2 minutes,

motor runs at 100% until demand is satisfied.

� Once demand is met, motor ramps down to stop.

OFFOFF 82%CFM100% CFM

COMPRESSOR DEMAND

7 1/2 MIN

Ramping Option C

� Motor runs at 100% until demand is satisfied.

� Once demand is met, motor runs at 100% for 45 sec-

onds then ramps down to stop.

OFFOFF100% CFM 100% CFM

45 SEC.COMPRESSOR

DEMAND

Ramping Option D

� Motor runs at 100% until demand is satisfied.

� Once demand is met, motor ramps down to stop.

OFFOFF100% CFM

COMPRESSOR DEMAND

Switches 11, 12 and 13 −− Heating Mode Blower Speed −−

The switches are factory set to the OFF position which pro-

vides normal heat speed. Refer to table 18 for switches 11,

12 and 13 that provided the corresponding increases or de-

crease to both high and low heat demand.

TABLE 18Heating Mode Blower Speeds

Heat SpeedSwitch

11Switch

12Switch

13

Increase 24% On On On

Increase 18% On On Off

Increase 12% On Off On

Increase 6% On Off Off

Factory Default Off Off Off

Decrease 6% Off Off On

Decrease 12% Off On Off

Decrease18% Off On On

Switches 14 and 15 −− Continuous Blower Speed −−

Table 19 provides continuous blower speed adjustments

that will result from different switch settings.

TABLE 19Continuous Blower Speed

ContinuousBlower Speed

Switch 14 Switch 15

28% of High Cool Speed Off On

38% of High Cool Speed(Factory)

Off Off

70% of High Cool Speed On Off

100% of High Cool Speed On On

Page 34: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 34

On−Board Links

Note: In icomfort� systems with a conventional outdoor

unit (non−communicating), the on−board clippable links

must be set to properly configure the system

WARNINGCarefully review all configuration information pro-vided. Failure to properly set DIP switches, jumpersand on−board links can result in improper operation!

On−Board Link W914 Dehum or Harmony (R to DS)

On−board link W914, is a clippable connection between ter-minals R and DS on the integrated control. W914 must becut when the furnace is installed with either the HarmonyIII� zone control or a thermostat which features humiditycontrol. If the link is left intact the PMW signal from the Har-mony III control will be blocked and also lead to controldamage. Refer to table 20 for operation sequence in ap-plications including SL280DFV, a thermostat which fea-tures humidity control and a single−speed outdoor unit.Table 21 gives the operation sequence in applications witha two−speed outdoor unit.

On−Board Link W951 Heat Pump (R to O)

On−board link W951 is a clippable connection between ter-minals R and O on the integrated control. W951 must be cutwhen the furnace is installed in applications which include aheat pump unit and a thermostat which features dual fueluse. If the link is left intact, terminal �O" will remain ener-gized eliminating the HEAT MODE in the heat pump.

On−Board Link W915 2 Stage Compr (Y1 to Y2)

On−board link W915 is a clippable connection between ter-

minals Y1 and Y2 on the integrated control. W915 must becut if two−stage cooling will be used. If the Y1 to Y2 link isnot cut the outdoor unit will operate in second−stage coolingonly.

Diagnostic LED (Figure 25)

The seven−segment diagnostic LED displays operatingstatus, target airflow, error codes and other information.The table beginning on Page 48 lists diagnostic LEDcodes.

Diagnostic Push Button (Figure 25)

The diagnostic push button is located adjacent to theseven−segment diagnostic LED. This button is used to en-able the Error Code Recall �E" mode and the Flame Signal�F" mode. Press the button and hold it to cycle through amenu of options. Every five seconds a new menu item willbe displayed. When the button is released, the displayeditem will be selected. Once all items in the menu have beendisplayed, the menu resumes from the beginning until thebutton is released.

Error Code Recall Mode

Select "E" from the menu to access the most recent 10 errorcodes. Select �c" from the Error Code Recall menu to clearall error codes. Button must be pressed a second timewhile �c" is flashing to confirm command to delete codes.Press the button until a solid �≡" is displayed to exit the ErrorCode Recall mode.

Flame Signal Mode

Select "F" from the menu to access the flame signal mode.The integrated control will display the flame current on 7segment LED in in micro amps (uA).

Flame signal mode is exited after the following:

� Power is reset

� Pressing and holding push button until 3 horizontal lines �≡" are displayed

� 10 minutes of entering the flame sense mode.

Page 35: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 35

BLOWER DATASL280DF070V36A BLOWER PERFORMANCE (less filter)0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

HEATING1 Heating Speed

DIP Switch Settings

First Stage Heating Speed - cfm Second Stage Heating Speed - cfm

+24% 1065 1170+18% 1010 1115+12% 960 1055+6% 910 1000

Factory Default 860 945–6% 805 885

–12% 755 830–18% 705 775

COOLING1 Cooling Speed

DIP Switch Settings

First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm

Low Medium-Low Medium-High 2 High Low Medium-Low Medium-High 2 High

+ 745 870 1025 1075 1100 1240 1425 1515Factory Default 665 780 925 985 1015 1115 1305 1380

– 590 690 815 865 900 1025 1170 12501 Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specific DIP Switch

Settings.2 Factory default setting.NOTES - The effect of static pressure is included in air volumes shown.

First stage HEAT is approximately 91% of the same second stage HEAT. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 500 cfm. Lennox Harmony III™ Zone Control Applications - Minimum blower speed is 425 cfm.

SL280DF090V48B BLOWER PERFORMANCE (less filter)0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

HEATING1 Heating Speed

DIP Switch Settings

First Stage Heating Speed - cfm Second Stage Heating Speed - cfm

+24% 1360 1500+18% 1285 1415+12% 1220 1350+6% 1135 1285

Factory Default 1075 1200–6% 1030 1110–12% 960 1050–18% 890 975

COOLING1 Cooling Speed

DIP Switch Settings

First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm

Low Medium-Low Medium-High 2 High Low Medium-Low Medium-High 2 High

+ 740 905 1040 1220 1085 1330 1545 1730Factory Default 690 820 950 1110 990 1200 1400 1,595

– 610 745 855 1005 895 1075 1270 14601 Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specific DIP Switch

Settings.2 Factory default setting.NOTES - The effect of static pressure is included in air volumes shown.

First stage HEAT is approximately 91% of the same second stage HEAT. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 500 cfm. Lennox Harmony III™ Zone Control Applications - Minimum blower speed is 455 cfm.

Page 36: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 36

BLOWER DATASL280DF090V60C BLOWER PERFORMANCE (less filter)0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

HEATING1 Heating Speed

DIP Switch Settings

First Stage Heating Speed - cfm Second Stage Heating Speed - cfm

+24% 1540 1695+18% 1465 1615+12% 1390 1530+6% 1320 1450

Factory Default 1245 1365–6% 1170 1285

–12% 1095 1205–18% 1020 1120

COOLING1 Cooling Speed

DIP Switch Settings

First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm

Low Medium-Low Medium-High 2 High Low Medium-Low Medium-High 2 High

+ 1125 1250 1400 1590 1585 1770 2000 2275Factory Default 1020 1135 1285 1445 1420 1610 1845 2,050

– 900 1005 1155 1280 1305 1395 1645 18751 Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specific DIP Switch

Settings.2 Factory default setting.NOTES - The effect of static pressure is included in air volumes shown.

First stage HEAT is approximately 91% of the same second stage HEAT. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 500 cfm. Lennox Harmony III™ Zone Control Applications - Minimum blower speed is 480 cfm.

SL280DF110V60C BLOWER PERFORMANCE (less filter)0 through 0.8 in. w.g. (Heating) and 0 through 1.0 in. w.g. (Cooling) External Static Pressure Range

HEATING1 Heating Speed

DIP Switch Settings

First Stage Heating Speed - cfm Second Stage Heating Speed - cfm

+24% 1645 1810+18% 1565 1720+12% 1485 1635+6% 1405 1545

Factory Default 1325 1460–6% 1245 1370

–12% 1170 1285–18% 1090 1195

COOLING1 Cooling Speed

DIP Switch Settings

First Stage Cooling Speed - cfm Second Stage Cooling Speed - cfm

Low Medium-Low Medium-High 2 High Low Medium-Low Medium-High 2 High

+ 1075 1225 1370 1530 1500 1755 1915 2120Factory Default 945 1120 1230 1385 1360 1585 1770 1960

– 880 985 1135 1235 1225 1405 1595 17601 Cooling and heating speeds are based on a combination of DIP switch settings on the furnace control. Refer to Installation Instructions for specific DIP Switch

Settings.2 Factory default setting.NOTES - The effect of static pressure is included in air volumes shown.

First stage HEAT is approximately 91% of the same second stage HEAT. First stage COOL (two-stage air conditioning units only) is approximately 70% of the same second stage COOL speed position. Continuous Fan Only speed is selectable at 28%, 38%, 70% and 100% of the selected second stage cooling speed - minimum 500 cfm. Lennox Harmony III™ Zone Control Applications - Minimum blower speed is 485 cfm.

Page 37: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 37

TABLE 20SL280DFV, Non−Communicating Thermostat with Humidity Control Feature and Single−Speed Outdoor Unit

OPERATINGSEQUENCE

SYSTEM DEMAND SYSTEM RESPONSE

SystemCondition

Step

Thermostat Demand Relative Humidity

CompressorBlowerCFM

(COOL)Comments

Y1 O GW1

Status D

NO CALL FOR DEHUMIDIFICATION

Normal Operation 1 On On On Acceptable24

VACHigh 100%

Compressor and indoorblower follow thermostatdemand

BASIC MODE (only active on a Y1 thermostat demand)

Normal Operation 1 On On On Acceptable24

VACHigh 100% ComfortSense® 7000

thermostat energizes Y1and de−energizes D on acall for de−humidification

DehumidificationCall

2 On On On Demand0

VACHigh 70%*

PRECISION MODE (operates independent of a Y1 thermostat demand)

Normal Operation 1 On On On Acceptable24

VACHigh 100% Dehumidification mode

begins when humidity isgreater than set pointDehumidification

call2 On On On Demand

0VAC

High 70%*

Dehumidificationcall ONLY

1 On On On Demand0

VACHigh 70%*

ComfortSense® 7000thermostat will try to main-tain room humidity set-point by allowing the roomspace to maintain a coolerroom thermostat set-point**

Jumpers at indoor unit with a single stage outdoor unitWith Condensing unit − Cut W914 (R to DS) on SureLight® boardWith Heat Pump − Cut W914 (R to DS) & W951 (R to O) on SureLight® board

ComfortSense® 7000 thermostat to use for this application − Y2081 4 heat / 2 cool

*Dehumidification blower speed is 70% of COOL speed for all units .

**In Precision mode, ComfortSense® 7000 thermostat will maintain room temperature up to 2 °F (1.2°C) cooler than room

setting.

Page 38: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 38

TABLE 21SL280DFV, Non−Communicating Thermostat with Humidity Control Feature and Two−Speed Outdoor Unit

OPERATINGSEQUENCE

SYSTEM DEMAND SYSTEM RESPONSE

SystemCondition

Step

Thermostat Demand Relative Humidity

CompressorBlowerCFM

(COOL)Comments

Y1 Y2 O GW1

W2

Status D

NO CALL FOR DEHUMIDIFICATION

Normal Operation −Y1

1 On On On Acceptable24

VACLow 70%* Compressor and indoor

blower follow thermostatdemandNormal Operation −

Y22 On On On On Acceptable

24VAC

High 100%

ROOM THERMOSTAT CALLS FOR FIRST STAGE COOLING

BASIC MODE (only active on a Y1 thermostat demand)

Normal Operation 1 On On On Acceptable24

VACLow 70%* ComfortSense® 7000

thermostat energizes Y2and de−energizes D on acall for de−humidification

DehumidificationCall

2 On On On On Demand0

VACHigh 70%**

PRECISION MODE (operates independent of a Y1 thermostat demand)

Normal Operation 1 On On On Acceptable24

VACLow 70%* Dehumidification mode

begins when humidity isgreater than set pointDehumidification

call2 On On On On Demand

0VAC

High 70%**

Dehumidificationcall ONLY

1 On On On On Demand0

VACHigh 70%**

ComfortSense® 7000thermostat will try tomaintain room humiditysetpoint by allowing theroom space to maintaina cooler room thermostatsetpoint***

ROOM THERMOSTAT CALLS FOR FIRST AND SECOND STAGE COOLING

BASIC MODE (only active on a Y1 thermostat demand)

Normal Operation 1 On On On On Acceptable24

VACHigh 100% ComfortSense® 7000

thermostat energizes Y2and de−energizes D on acall for de−humidification

DehumidificationCall

2 On On On On Demand0

VACHigh 70%**

PRECISION MODE (operates independent of a Y1 thermostat demand)

Normal Operation 1 On On On Acceptable24

VACLow 70%* Dehumidification mode

begins when humidity isgreater than set pointDehumidification

call2 On On On On Demand

0VAC

High 70%**

Dehumidificationcall ONLY

1 On On On On Demand0

VACHigh 70%**

ComfortSense® 7000thermostat will try tomaintain room humiditysetpoint by allowing theroom space to maintaina cooler room thermostatsetpoint***

Jumpers at indoor unit with a two stage outdoor unitCut factory jumper from Y1 to Y2 or cut W915 (Y1 to Y2)With Condensing unit − Cut W914 (R to DS) on SureLight® boardWith Heat Pump − Cut W914 (R to DS) & W951 (R to O) on SureLight® control

ComfortSense® 7000 thermostat to use for this application − Y2081 4 heat / 2 cool

*Normal operation first stage cooling blower speed is 70% COOL speed.

**Dehumidification blower speed is, reduced to 70% of COOL.

***In Precision mode, ComfortSense® 7000 thermostat will maintain room temperature up to 2 °F (1.2°C) cooler than room

setting.

Page 39: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 39

Unit Start−Up

FOR YOUR SAFETY READ BEFORE LIGHTING

WARNINGDo not use this furnace if any part has been underwa-ter. Immediately call a licensed professional servicetechnician (or equivalent) to inspect the furnace andto replace any part of the control system and any gascontrol which has been under water.

WARNINGIf overheating occurs or if gas supply fails to shut off,shut off the manual gas valve to the appliance beforeshutting off electrical supply.

CAUTIONBefore attempting to perform any service or mainte-nance, turn the electrical power to unit OFF at dis-connect switch.

WARNINGDuring blower operation, the ECM motor emits ener-gy that may interfere with pacemaker operation. In-terference is reduced by both the sheet metal cabinetand distance.

BEFORE LIGHTING smell all around the appliance area for

gas. Be sure to smell next to the floor because some gas is

heavier than air and will settle on the floor.

The gas valve on the SL280DFV unit will be equipped with

either a gas control switch. Use only your hand to move the

control switch. Never use tools. If the switch will not turn or if

the switch will not move by hand, do not try to repair it.

Force or attempted repair may result in a fire or explosion.

Placing the furnace into operation:

SL280DFV units are equipped with an automatic ignition

system. Do not attempt to manually light burners on these

furnaces. Each time the thermostat calls for heat, the

burners will automatically light. The ignitor does not get

hot when there is no call for heat on units with an automatic

ignition system.

WARNINGIf you do not follow these instructions exactly, a fireor explosion may result causing property damage,personal injury or death.

Gas Valve Operation (Figures 26 and 27)

1 − STOP! Read the safety information at the beginning of

this section.

2 − Set the thermostat to the lowest setting.

3 − Turn off all electrical power to the unit.

4 − This furnace is equipped with an ignition device which

automatically lights the burners. Do not try to light the

burners by hand.

5 − Remove the access panel.

6 − Move switch on gas valve to OFF. Do not force. See

figure 26 or 27.

7 − Wait five minutes to clear out any gas. If you then smell

gas, STOP! Immediately call your gas supplier from a

neighbor’s phone. Follow the gas supplier’s instruc-

tions. If you do not smell gas go to next step.

FIGURE 26

GAS VALVE SHOWN IN ON POSITION

INLET PRESSURE POSTHIGH FIRE ADJUSTMENT

SCREW(under cap)

MANIFOLDPRESSURE TAP

WHITE RODGERS GAS VALVE

GAS VALVE SHOWN IN ON POSITION

MANIFOLDPRESSURE

TAP ONSIDE

HIGH FIREADJUSTING SCREW

(under cap)

INLET PRESSURE TAPON SIDE

HONEYWELL GAS VALVE

FIGURE 27

8 − Move switch on gas valve to ON. Do not force. See fig-

ure 26 or 27.

9 − Replace the access panel.

10 − Turn on all electrical power to to the unit.

11 − Set the thermostat to desired setting.

NOTE − When unit is initially started, steps 1 through 11

may need to be repeated to purge air from gas line.

Page 40: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 40

12− If the appliance will not operate, follow the instructions

�Turning Off Gas to Unit" and call your service techni-

cian or gas supplier.

Turning Off Gas to Unit

1 − Set the thermostat to the lowest setting.

2 − Turn off all electrical power to the unit if service is to be

performed.

3 − Remove the upper access panel.

4 − Move switch on gas valve to OF. Do not force. See fig-

ure 26 or 27.

5 − Replace the upper access panel.

Failure To Operate

If the unit fails to operate, check the following:

1 − Is the thermostat calling for heat?

2 − Are access panels securely in place?

3 − Is the main disconnect switch closed?

4 − Is there a blown fuse or tripped circuit breaker?

5 − Is the filter dirty or plugged? Dirty or plugged filters willcause the limit control to shut the unit off.

6 − Is gas turned on at the meter?

7 − Is the manual main shut-off valve open?

8 − Is the internal manual shut-off valve open?

9 − Is the unit ignition system in lock out? If the unit locks outagain, call the service technician to inspect the unit forblockages.

10 −Is pressure switch closed? Obstructed flue will causeunit to shut off at pressure switch. Check flue and outletfor blockages.

11 − Is the rollout switch tripped? If the switch is tripped callthe service technician to inspect the unit.

Gas Pressure Adjustment

Gas Flow (Approximate)

Furnace should operate at least 5 minutes before check-

ing gas flow. Determine time in seconds for two revolu-

tions of gas through the meter. (Two revolutions assures a

more accurate time.) Divide by two and compare to time

in table 22 below. If manifold pressure matches table 24

and rate is incorrect, check gas orifices for proper size and

restriction. Remove temporary gas meter if installed.

NOTE − Shut unit off and remove manometer as soon as anaccurate reading has been obtained. Take care to replacepressure tap plug.

TABLE 22GAS METER CLOCKING CHART

SL280Unit

Seconds for One Revolution

Natural LP

1 cu ftDial

2 cu ftDial

1 cu ftDial

2 cu ftDIAL

−045 80 160 200 400

−70 55 110 136 272

−90 41 82 102 204

−110 33 66 82 164

−135 27 54 68 136

Natural−1000 btu/cu ft LP−2500 btu/cu ft

Supply Line Pressure

White Rodgers Gas Valve

An inlet post located on the gas valve provides access to

the supply pressure. See figure 27. Back out the 3/32 hex

screw one turn, connect a piece of 5/16 tubing and connect

to a manometer to measure supply pressure. See table 24

for supply line pressure.

Honeywell Gas Valve

A threaded plug on the inlet side of the gas valve provides

access to the supply pressure tap. Remove the threaded

plug, install a field−provided barbed fitting and connect a

manometer to measure supply pressure. See table 24 for

supply line pressure. Replace the threaded plug after mea-

surements have been taken.

Manifold Pressure

NOTE − Pressure test adapter kit (10L34) is available from

Lennox to facilitate manifold pressure measurement.

1 − Connect test gauge to manifold pressure post (figure

26) or tap (figure 27) on gas valve.

2 − Ignite unit on high fire and let run for 5 minutes to allow

for steady state conditions.

3 − After allowing unit to stabilize for 5 minutes, record

manifold pressure and compare to value given in table

24.

4 − If necessary, make adjustments. Figures 26 and 27

show location of high fire adjustment screw.

5 − If an adjustment is made on high fire, re−check man-

ifold pressure on low fire. Do not adjust low fire man-

ifold pressure. If low fire manifold pressure is more

than 1/2" above or below value specified in table 24,

replace valve.

Proper Combustion

Furnace should operate minimum 15 minutes with correct

manifold pressure and gas flow rate before checking com-

bustion. Table 23 shows acceptable combustion for ALL

SL280DFV models.

TABLE 23

Firing Rate CO2% For Nat CO2% For L.P.

High Fire 6.0 − 7.4 6.9 − 8.4

Low Fire 4.8 − 6.0 5.7 − 7.0

The carbon monoxide reading should not exceed 50 ppm.

Page 41: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 41

High Altitude

The manifold pressure, gas orifice and pressure switch

may require adjustment or replacement to ensure proper

operation at higher altitudes. Tables 24 through 27 shows

manifold pressure, pressures switch and gas conversion

kits at all altitudes.

IMPORTANTFor safety, shut unit off and remove manometer assoon as an accurate reading has been obtained.Take care to replace pressure tap plug.

TABLE 24

Manifold Pressure Settings

UnitInput

GasOrifice Size0 − 7500 ft.

Orifice Size7501 −

10,000 ft.1

ManifoldPressure in.wg.

0−4500 ft.

ManifoldPressure in.wg.

4501−7500 ft.

ManifoldPressure in.wg.7501 − 10,000 ft.2

Supply LinePressurein. w.g.

LowFire

HighFire

LowFire

HighFire

LowFire

HighFire

Min Max

070Natural .063 .055 1.7 3.5 1.6 3.4 1.7 3.5 4.5 13.0

LP/propane3 .039 .037 4.9 10.0 4.9 10.0 4.9 10.0 11.0 13.0

090Natural .063 .055 1.7 3.5 1.5 3.0 1.7 3.5 4.5 13.0

LP/propane3 .039 .037 4.9 10.0 4.9 10.0 4.9 10.0 11.0 13.0

110Natural .063 .055 1.7 3.5 1.5 3.2 1.7 3.5 4.5 13.0

LP/propane3 .039 .037 4.9 10.0 4.9 10.0 4.9 10.0 11.0 13.0

1 This is the only permissible derate for these units.

2 Natural gas high altitude orifice kit required.

3 A natural to L.P. propane gas changeover kit is necessary to convert this unit. Refer to the changeover kit installation instruction for the conversion

procedure.

NOTE − Units may be installed at altitudes up to 4500 ft. above sea level without modifications.

TABLE 25

High Altitude Pressure Switch Kits

UnitInput

High AltitudePressure Switch Kit

0 − 4500 ft. 4501 − 7500 ft. 7501 − 10,000 ft.

070 No Change No Change 73W36

090 No Change 69W56 73W36

110 No Change 69W56 73W35

TABLE 26

Honeywell Gas Valve Conversion Kits

UnitInput

High AltitudeNatural GasOrifice Kit

Natural Gas toLP/ Propane Kit

LP/Propaneto

Natural GasKit

7501 −10,000 ft.

0 − 7500 ft.7501 −

10,000 ft.0 − 7500 ft.

070 73W37 51W02 73W38 69W79

090 73W37 51W02 73W38 69W79

110 73W37 51W02 73W38 69W79

TABLE 27

White Rodgers Gas Valve Conversion Kits

UnitInput

High AltitudeNatural GasOrifice Kit

Natural Gas toLP/ Propane Kit

LP/Propaneto

Natural GasKit

7501 −10,000 ft.

0 − 7500 ft.7501 −

10,000 ft.0 − 7500 ft.

070 77W05 77W07 77W11 77W09

090 77W05 77W07 77W11 77W09

110 77W05 77W07 77W11 77W09

Page 42: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 42

Other Unit Adjustments

Primary and Secondary Limits

The primary limit is located on the heating compartment

vestibule panel. The secondary limits (if equipped) are lo-

cated in the blower compartment, attached to the back side

of the blower. These limits are factory set and require no

adjustment.

Flame Rollout Switch

This manually reset switch is located on the burner box. If

tripped, check for adequate combustion air before reset-

ting.

Pressure Switches

The pressure switch assembly (includes two switches) is

located in the heating compartment adjacent to the com-

bustion air inducer. These switches check for proper com-

bustion air inducer operation before allowing ignition trial.

The switches are factory−set and require no adjustment.

Temperature Rise

Place the unit into operation with a second−stage heating de-

mand. After supply and return air temperatures have stabi-

lized, check the temperature rise. If necessary, adjust the

heating blower speed to maintain the temperature rise within

the range shown on the unit nameplate. Increase the blower

speed to decrease the temperature rise. Decrease the blow-

er speed to increase the temperature rise. Failure to properly

adjust the temperature rise may cause erratic limit operation

and may result in premature heat exchanger failure.

Thermostat Heat Anticipation

Set the heat anticipator setting (if adjustable) according to

the amp draw listed on the wiring diagram that is attached

to the unit.

Heating Sequence of Operation

Electronic IgnitionThe two−stage, variable speed integrated control used inSL280DFV units has an added feature of an internal Watch-guard control. The feature serves as an automatic reset de-vice for ignition control lockout caused by ignition failure.This type of lockout is usually due to low gas line pressure.After one hour of continuous thermostat demand for heat,the Watchguard will break and remake thermostat demandto the furnace and automatically reset the control to beginthe ignition sequence.NOTE − The integrated control thermostat selection DIP switchis factory−set in the �TWO−STAGE" position.

Applications Using a Two−Stage ThermostatSee figure 28 for ignition control sequence

A − Heating Sequence −− Integrated Control ThermostatSelection DIP Switch 1 OFF in �Two−Stage" Position(Factory Setting) 1 − On a call for heat, thermostat first−stage contacts close

sending a signal to the integrated control. The inte-grated control runs a self-diagnostic program andchecks high temperature limit switches for normallyclosed contacts and pressure switches for normallyopen contacts. The combustion air inducer is ener-gized at low speed.

2 − Once the control receives a signal that the low pres-sure switch has closed, the combustion air inducer be-gins a 15−second pre−purge in low speed.NOTE − If the low fire pressure switch does not closethe combustion air inducer will switch to high fire. Aftera 15 second pre−purge the high fire pressure switchwill close and the unit will begin operation on high fire.After 10 to 20 seconds of high fire operation the unitwill switch to low fire..

3 − After the pre−purge is complete, a 20−second initial ig-nitor warm−up period begins. The combustion air in-ducer continues to operate at low speed.

4 − After the 20−second warm−up period has ended, the gasvalve is energized on low fire (first stage) and ignition oc-curs. At the same time, the control module sends a sig-nal to begin an indoor blower 30−second ON−delay.When the delay ends, the indoor blower motor is ener-gized on the low fire heating speed, the HUM contactsclose energizing the humidifier and 120V ACC termi-nal is energized. The furnace will continue this opera-tion as long as the thermostat has a first−stage heatingdemand.

5 − If second−stage heat is required, the thermostat sec-ond−stage heat contacts close and send a signal to theintegrated control. The integrated control initiates a30−second second−stage recognition delay.

6 − At the end of the recognition delay, the integrated con-trol energizes the combustion air inducer at highspeed. The control also checks the high fire (secondstage) pressure switch to make sure it is closed. Thehigh fire (second stage) gas valve is energized and theindoor blower motor is energized for operation at thehigh fire heating speed.

7 − When the demand for high fire (second stage) heat issatisfied, the combustion air inducer is switched to thelow−fire heating speed and the high−fire (secondstage) gas valve is de−energized. The low−fire (firststage) gas valve continues operation. The indoorblower motor is switched to the low−fire heating speed.

8 − When the thermostat demand for low−fire (first stage)heat is satisfied, the gas valve is de−energized and thefield−selected indoor blower off delay begins. Thecombustion air inducer begins a 5−second post−purgeperiod.

9 − When the combustion air post−purge period is com-plete, the inducer, the HUM contacts as well as the120V ACC terminals are de−energized. The indoorblower is de−energized at the end of the off delay.

Page 43: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 43

Applications Using A Single−Stage ThermostatSee figure 29 for ignition control sequence

B − Heating Sequence −− Control Thermostat SelectionDIP Switch 1 ON in �Single−Stage" PositionNOTE − In these applications, two−stage heat will be initi-ated by the integrated control if heating demand has notbeen satisfied after the field adjustable period (7 or 12 min-utes). 1 − On a call for heat, thermostat first−stage contacts close

sending a signal to the integrated control. The inte-grated control runs a self-diagnostic program andchecks high temperature limit switches for normallyclosed contacts and pressure switches for normallyopen contacts. The combustion air inducer is ener-gized at low speed.

2 − Once the control receives a signal that the low pres-sure switch has closed, the combustion air inducer be-gins a 15−second pre−purge in low speed.NOTE − If the low fire pressure switch does not closethe combustion air inducer will switch to high fire. Aftera 15 second pre−purge the high fire pressure switchwill close and the unit will begin operation on high fire.After 10 to 20 seconds of high fire operation the unitwill switch to low fire.

3 − After the pre−purge is complete, a 20−second initial ig-nitor warm−up period begins. The combustion air in-ducer continues to operate at low speed.

4 − After the 20−second warm−up period has ended, the gasvalve is energized on low fire (first stage) and ignition oc-curs. At the same time, the control module sends a sig-nal to begin an indoor blower 30−second ON−delay.When the delay ends, the indoor blower motor is ener-gized on the low fire heating speed and the HUM con-tacts are energized. The integrated control also initi-ates a second−stage on delay (factory−set at 7minutes; adjustable to 12 minutes).

5 − If the heating demand continues beyond the second−stage on delay, the integrated control energizes thecombustion air inducer at high speed. The control alsochecks the high fire (second stage) pressure switch tomake sure it is closed. The high fire (second stage)gas valve is energized and the indoor blower motor isenergized for operation at the high fire heating speed.

6 − When the thermostat heating demand is satisfied, thecombustion air inducer begins a 5−second low speedpost−purge. The field−selected indoor blower off delaybegins. The indoor blower operates at the low−fireheating speed.

7 − When the combustion air post−purge period is com-plete, the inducer, the HUM contacts as well as the120V ACC terminals are de−energized. The indoorblower is de−energized at the end of the off delay.

1 stg heat demand

2 stg heat demand

15

ON

OFFÉÉÉÉ

low speed CAI

351

Pre−PurgeIgnitor Warm−up

30* secondblower

�on" delayPost

Purge

5 SEC80

ignitor

HEATING OPERATION WITH TWO−STAGE THERMOSTAT

low fire gas valveindoor blower low heat

high speed CAI

high fire gas valve

indoor blower high heat

39

Trial ForIgnition

blower�off"delay

RECOGNITION PERIOD30 seconds

FIGURE 28

* Conventional thermostat 30 seconds, icomfort Touch® thermostat set for 30 adjustable 15 to 45 seconds.

heat demand

15

ON

OFFÉÉlow speed CAI

351

Pre−Purge Ignitor Warm−up30* second

blower�on" delay

Post Purge

5 SEC80

ignitor

HEATING OPERATION WITH SINGLE STAGE THERMOSTAT

low fire gas valve

high speed CAI

high fire gas valveindoor blower high heat

39

Trial ForIgnition

7 or 12 minutes after heating demand begins, furnace switches to high fire (depends on setting)

blower�off"delay

FIGURE 29

indoor blower low heat

* Conventional thermostat 30 seconds, icomfort Touch® thermostat set for 30 adjustable 15 to 45 seconds.

Page 44: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 44

Service

WARNINGELECTRICAL SHOCK, FIRE,OR EXPLOSION HAZARD.

Failure to follow safety warnings exactly could resultin dangerous operation, serious injury, death orproperty damage.Improper servicing could result in dangerous opera-tion, serious injury, death, or property damage.Before servicing, disconnect all electrical power tofurnace.When servicing controls, label all wires prior to dis-connecting. Take care to reconnect wires correctly.Verify proper operation after servicing.

At the beginning of each heating season, a licensed profes-

sional technician (or equivalent) should check the system

as follows:

Blower

Check the blower wheel for debris and clean if necessary.

The blower motors are prelubricated for extended bearing

life. No further lubrication is needed.

WARNINGThe blower access panel must be securely in placewhen the blower and burners are operating. Gasfumes, which could contain carbon monoxide, canbe drawn into living space resulting in personal inju-ry or death.

Filters

All SL280DFV filters are installed external to the unit. Fil-

ters should be inspected monthly. Clean or replace the fil-

ters when necessary to ensure that the furnace operates

properly. Replacement filters must be rated for high veloc-

ity airflow. Table 3 lists recommended filter sizes.

Flue And Chimney

1 − Check flue pipe, chimney and all connections for tight-ness and to make sure there is no blockage.

2 − Check unit for proper draft.

Electrical

1 − Check all wiring for loose connections.

2 − Check for the correct voltage at the furnace (furnace

operating). Correct voltage is 120VAC + 10%.

3 − Check amp−draw on the blower motor with inner blow-er access panel in place.Unit Nameplate__________Actual__________

Cleaning the Heat Exchanger and Burners

NOTE − Use papers or protective covering in front of the fur-

nace during cleaning.

1 − Turn off both electrical and gas power supplies to fur-nace.

2 − Remove flue pipe, top cap, flue chase and internal flue

pipe assembly from the unit.

3 − Label the wires from gas valve, rollout switches, prima-

ry limit switch and make−up box then disconnect them.

4 − Remove the screws that secure the combustion air in-

ducer/pressure switch assembly to the collector box.

Carefully remove the combustion air inducer to avoid

damaging blower gasket. If gasket is damaged, it must

be replaced to prevent leakage.

5 − Remove the collector box located behind the combus-

tion air inducer. Be careful with the collector box gas-

ket. If the gasket is damaged, it must be replaced to

prevent leakage.

6 − Disconnect gas supply piping. Remove the screw se-

curing the burner box cover and remove cover. Re-

move the four screws securing the burner manifold as-

sembly to the vestibule panel and remove the

assembly from the unit.

7 − Remove screws securing burner box and remove

burner box.

8 − Remove screws from both sides, top and bottom of

vestibule panel.

9 − Remove heat exchanger. It may be necessary to

spread cabinet side to allow more room. If so, remove

five screws from the left side or right side of cabinet.

See figure 31.

10− Back wash using steam. Begin from the burner opening

on each clam. Steam must not exceed 275°F.

11− To clean burners, run a vacuum cleaner with a soft brush

attachment over the face of burners. Visually inspect in-

side the burners and crossovers for any blockage

caused by foreign matter. Remove any blockage. Figure

30 shows burner detail.

Page 45: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 45

SL280DFV BURNER, COMBUSTION AIR INDUCER ASSEMBLY &HEAT EXCHANGER REMOVAL

FIGURE 30

heat exchanger

gasket

collector box

orifice plate

internal flue pipe

pressure switch

combustion air inducer

burners

burner box assembly

burner box cover plate

manifold and gas valve

gasket

retention rings

cross over

heat exchanger

gasket

collector box

orifice plate

internal flue pipe

pressure switch

combustion air inducer

burners

burner box assembly

burner box cover plate

manifold and gas valve

gasket

flue chase

gasket

ignitorrollout switch

sensor

Page 46: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 46

12− To clean the combustion air inducer visually inspect and

using a wire brush clean where necessary. Use com-

pressed air to clean off debris and any rust.

13− Reinstall heat exchanger in vestibule. (Replace the

five screws in the cabinet from step 10 if removed).

14− Reinstall collector box, combustion air assembly, inter-

nal flue pipe and flue chase. Seal with high tempera-

ture RTV. Reinstall all screws to the collector box and

combustion air inducer. Failure to replace all screws

may cause leaks. Inspect gaskets for any damage and

replace if necessary.

15− Reinstall burner box, manifold assembly and burner box

cover.

16− Reconnect all wires.

17− Reconnect top cap and vent pipe to combustion air in-

ducer outlet.

18− Reconnect gas supply piping.

19− Turn on power and gas supply to unit.

20− Set thermostat and check for proper operation.

20− Check all piping connections, factory and field, for gas

leaks. Use a leak detecting solution or other preferred

means.

CAUTIONSome soaps used for leak detection are corrosive tocertain metals. Carefully rinse piping thoroughly af-ter leak test has been completed. Do not usematches, candles, flame or other sources of ignitionto check for gas leaks.

21− If a leak is detected, shut gas and electricity off and

repair leak.

22− Repeat steps 21 and 23 until no leaks are detected.

23− Replace access panel.

FIGURE 31

Remove five screws if necessary(either side of cabinet)

1

2

3

4

5

Page 47: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 47

Planned Service

The following items should be checked during an annual inspection. Power to the unit must be shut off for the service techni-

cian’s safety.

Fresh air grilles and louvers (on the unit and in the room

where the furnace is installed) − Must be open and unob-

structed to provide combustion air.

Burners − Must be inspected for rust, dirt, or signs of water.

Vent pipe − Must be inspected for signs of water, damaged

or sagging pipe, or disconnected joints.

Unit appearance − Must be inspected for rust, dirt, signs

of water, burnt or damaged wires, or components.

Blower access door − Must be properly in place and pro-

vide a seal between the return air and the room where the

furnace is installed.

Return air duct − Must be properly attached and provide

an air seal to the unit.

Operating performance − Unit must be observed during

operation to monitor proper performance of the unit and the

vent system.

Combustion gases − Flue products must be analyzed and

compared to the unit specifications.

Problems detected during the inspection may make it nec-

essary to temporarily shut down the furnace until the items

can be repaired or replaced.

Instruct the homeowners to pay attention to their

furnace. Situations can arise between annual furnace in-

spections that may result in unsafe operation. For instance,

items innocently stored next to the furnace may obstruct

the combustion air supply. This could cause incomplete

combustion and the production of carbon monoxide gas.

Repair Parts List

The following repair parts are available through independent Lennox dealers. When ordering parts, include the complete

furnace model number listed on the CSA International nameplate −− Example: SL280DF070V36A.

All service must be performed by a licensed professional installer (or equivalent), service agency, or gas supplier.

Cabinet Parts

Upper access panel

Blower panel

Top cap

Control Panel Parts

Transformer

Two−stage, variable speed integrated control

Door interlock switch

Circuit breaker

Blower Parts

Blower wheel

Blower housing

Motor

Motor electronics

Power choke (1 hp only)

Motor mounting frame

Blower housing cutoff plate

Heating Parts

Flame Sensor

Heat exchanger assembly

Gas manifold

Two−speed combustion air inducer

Two−stage gas valve

Main burner cluster

Main burner orifices

Pressure switch

Ignitor

Primary limit control

Flame rollout switch

Secondary limit

Page 48: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 48

Integrated Control Diagnostic Modes

Display Action (when button released)

No change (idle)* Remain in idle mode

Solid �E" Enter diagnostic recall mode

Solid �D" Discharge Air Installed

Solid �F" Enter flame signal mode

Solid �P" (variable speed only) Program unit capacity/size (Unit Code)**

* No change implies the display will continue to show whatever is currently being displayed for normal operation (blinking

decimal, active error code, heat state, etc..)

** After the �P" is selected (by releasing the push button) the integrated control will start flashing the �P" on display for 90

seconds. If push button is pressed again and held during that time, the control will start to display characters corresponding

to different variable speed furnace models for 3 seconds each. While the wanted character−model is displayed push button

has to be released. Selected option will flash display for 10 seconds and during that time push button has to be pressed

and held for 5 seconds. Once control accepts new setting it will store data in non−volatile memory and reset itself. If 10 sec-

onds expires or push button is held less than 5 seconds, control will exit filed test mode and go in idle without programming

the unit size.

Integrated Control Diagnostic Codes

Press the diagnostic push button and hold it to cycle through a menu of options. Every five seconds a new menu item will bedisplayed. Release the button when the desired mode is displayed. When a solid "P" is displayed, the furnace capacity / size is programmed.When the solid �E" is displayed, the control enters the Diagnostic Recall (Alarm History). Diagnostic Recall mode menuoptions: No change (displaying error history) remains in Diagnostic Recall mode; solid � = " exits Diagnostic Recall mode;and solid �c" clears the error history. Must press button while flashing �c" is displayed to clear error codes. When the solid �F" is displayed, the control enters the Flame Signal Mode. The Flame Signal Mode is exited: with powercycle/reset, by pressing and holding the push button until 3 horizontal line are displayed �= �, after 10 minutes of enteringflame signal mode.

Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover

. Idle mode (Decimal blinks at 1 Hertz −− 0.5 second ON, 0.5 second OFF).

A Cubic feet per minute (cfm) setting for indoor blower (1 second ON, 0.5second OFF) / cfm setting for current mode displayed.

C Cooling stage (1 second ON, 0.5 second OFF) / 1 or 2 displayed / Pause/ cfm setting displayed / Pause / Repeat codes).

d Dehumidification mode (1 second ON) / 1 second OFF) / cfm setting dis-played / Pause / Repeat Codes).

h Heat pump stage (1 second ON, 0.5 second OFF) / % of input rate dis-played / Pause / cfm setting / Pause / Repeat codes.

H Gas Heat Stage (1 second ON, 0.5 second OFF) / 1 or 2 displayed /Pause / cfmsetting displayed / Pause / Repeat codes. Blinking during ignition.

dF Defrost mode.

U Discharge Air Temperature

Page 49: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 49

Integrated Control Diagnostic Codes (continued)

Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover

E 105 Device communication problem − No other devices on RS BUS (Commu-nicationsystem).

Equipment is unable to communicate. Indicatesnumerous message errors. In most cases errors arerelated to electrical noise. Make sure high voltagepower is separated from RSBus. Check for mis−wired and/or loose connections between the stat,indoor unit and outdoor unit. Check for a high volt-age source of noise close to the system. Faultclears after communication is restored.

E 110 Low line voltage. Line Voltage Low (Voltage lower than nameplaterating). Check power line voltage and correct. Alarmclears 5 seconds after fault recovered.

E 111 Line voltage polarity reversed. Reverse line power voltage wiring. System resumesnormal operation 5 seconds after fault recovered.

E 112 Ground not detected System shuts down. Provide proper earth ground.System resumes normal operation 5 seconds afterfault recovered.

E 113 High line voltage. Line Voltage High (Voltage higher than nameplaterating). Provide power voltage within proper range.System resumes normal operation 5 seconds afterfault recovered.

E 114 Line voltage frequency out−of−range. No 60 Hertz Power. Check voltage and line powerfrequency. Correct voltage and frequency problems.System resumes normal operation 5 seconds afterfault recovered.

E 115 Low 24V − Control will restart if the error recovers. 24−Volt Power Low (Range is 18 to 30 volts). Checkand correct voltage. Check for additional power−rob-bing equipment connected to system. May requireinstallation of larger VA transformer to be installed infurnace / air handler. Clears after fault recovered.

E 116 High 24V. 24 Volt Power High (Range is 18 to 30 volts). Checkand correct voltage. Check for proper line voltage(120V, 240V, etc.) to equipment. Clears when con-trol senses proper voltage.

E 117 Poor ground detected (Warning only) Provide proper grounding for unit. Check for properearth ground to the system. Warning only will clear30 seconds after fault recovered.

E 120 Unresponsive device. Communication only. Usually caused by delay in outdoor unit respondingto indoor unit poling. Recycle power. Check all wir-ing connections. Cleared after unresponsive deviceresponds to any inquiry.

E 124 Active communicating thermostat signal missing for more than 3 min-utes.

Equipment lost communication with the thermostat.Check four wiring connections, ohm wires and cyclepower at the thermostat. Alert stops all services andwaits for heartbeat message from thermostat (sub-net controller). Cleared after valid thermostat (sub-net controller) message is received.

E 125 Control failed self−check, internal error, failed hardware. Will restart iferrorrecovers. Integrated control not communicating. Covers hardware errors(flame sense circuit faults, pin shorts, etc.).

Hardware problem on the control. Cycle power oncontrol. Replace if problem prevents service and ispersistent. Critical alert. Cleared 300 seconds afterfault recovered.

E 126 Control internal communication problem. Hardware problem on the control. Cycle power oncontrol. Replace if problem prevents service and ispersistent. Cleared 300 seconds after fault recov-ered.

Page 50: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 50

Integrated Control Diagnostic Codes (continued)

E 131 Corrupted control parameters (Verify configuration of system). Communi-cating only.

Reconfigure the system. Replace control if heatingor cooling is not available. Only applicable in thecommunicating mode, not in startup. Exit from Com-missioning and Execute ’Set Factory Default mode’.Control will still operate on default parameter set-tings.

E 180 Outdoor air temperature sensor failure. Only shown if shorted or out−of−range.

Compare outdoor sensor resistance to temperature/resistance charts in unit installation instructions.Replace sensor pack if necessary. At beginning of(any) configuration, furnace or air handler controlwill sense outdoor air and discharge air temperaturesensor(s). If detected (reading in range), appropri-ate feature will be set as ’installed’ and that couldbe seen in ’About’ screen. In normal operation aftercontrol recognizes sensors, alarm will be sent ifvalid temperature reading is lost. To get rid of set-ting and alarm, redo configuration and make surethat temperature sensor is marked as ’not installed’in Indoor Unit ’About’ screen. When Indoor unit con-trol is replaced, thermostat will ’tell’ new control iftemperature sensor is in system or not. Clears 30seconds after fault recovered.

E 200 Hard lockout − Rollout circuit open or previously open. Correct cause of rollout trip, or replace flame rolloutswitch. Test furnace operation. Cleared after faultrecovered.

E 201 Indoor blower communication failure − Unable to communicate with blow-er motor.

Indoor blower communication failure (including pow-er outage). Lost communication with indoor blowermotor. Possible causes: motor not powered, loosewiring. Problem may be on control or motor side.Cleared after fault recovered.

E 202 Indoor blower motor mis−match − Indoor motor horsepower does notmatch unit capacity. See Page 55.

Incorrect appliance capacity code selected. Checkfor proper configuring under: Unit Size Codes forFurnace/Air Handler on configuration guide or ininstallation instructions. Cleared after the correctmatch is detected following a reset. (Remove ther-mostat from system while applying power and re-programming.)

E 203 Appliance capacity / size is NOT programmed. Invalid unit codes refer toconfiguration flow chart. See Page 55.

No appliance capacity code selected. Check forproper configuring under: Unit Size Codes for Fur-nace on configuration guide or in installation instruc-tions. Critical Alert. Cleared after valid unit code isread following a reset. (Remove thermostat fromsystem while applying power and reprogramming.)

E 204 Gas valve mis−wired. Check gas valve operation and wiring. Clears whenrepaired.

E 205 Gas valve control relay contact shorted. Check wiring on control and gas valve. If wiring iscorrect, replace control.

E 206 Gas valve second−stage relay failure Furnace will operate on 1st stage for remainder ofthe heating demand. Will clear after fault recovered.If unable to operate 2nd stage, replace control.

E 207 Hot surface ignitor sensed open − Refer to troubleshooting. See Page 56. Measure resistance of hot surface ignitor. Replace ifopen or not within specified range found in IOM.Resumes normal operation after fault is cleared.

Page 51: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 51

Integrated Control Diagnostic Codes (continued)

Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover

E 223 Low pressure switch failed open. Check pressure (inches w.c.) of low pressure switchclosing on heat call. Measure operating pressure(inches w.c.). Inspect vent and combustion air in-ducer for correct operation and restriction. Re-sumes normal operation after fault is cleared

E 224 Low pressure switch failed closed − Refer to troubleshooting. SeePage 56.

Check operation of low pressure switch to see if it isstuck closed on heat call longer than 150 seconds.Measure operating pressure (inches w.c.). Inspectvent and combustion air inducer for correct opera-tion and restriction. Resumes normal operation afterfault is cleared.

E 225 High pressure switch failed open − Refer to troubleshooting. SeePage 56.

Check pressure (inches w.c.) of high pressureswitch closing on heat call. Measure operating pres-sure (inches w.c.). Inspect vent and combustion airinducer for correct operation and restriction. Re-sumes normal operation after fault is cleared.

E 226 High pressure switch failed closed − Refer to troubleshooting. SeePage 56.

Check operation of high pressure switch closing onheat call. Measure operating pressure (inches w.c.).Inspect vent and combustion air inducer for correctoperation and restriction. Resumes normal opera-tion after fault is cleared.

E 227 Low pressure switch open during trial for ignition or run mode. Refer totroubleshooting. See Page 56.

Check pressure (inches w.c.) of low pressure switchclosing on heat call. Measure operating pressure(inches w.c.). Inspect vent and combustion air in-ducer for correct operation and restriction. Re-sumes normal operation after fault is cleared.

E 228 Combustion air inducer calibration failure Unable to perform pressure switch calibration.Check vent system and pressure switch wiring con-nections. Resumes normal operation after fault iscleared.

E 229 Ignition on high fire IFC switched to high fire ignition because low firepressure switch did not close in allowed time. Noaction is needed.

E 240 Low flame current − Run mode − Refer to troubleshooting. See Page 56. Check micro−amperes of flame sensor using controldiagnostics or field−installed mode. Clean or replacesensor. Measure voltage of neutral to ground to en-sure good unit ground. Alert clears after currentheat call has been completed.

E 241 Flame sensed out of sequence − Flame still present. Shut off gas. Check for gas valve leak. Replace, ifnecessary. Alert clears when fault is recovered.

E 250 Limit switch circuit open − Refer to troubleshooting. Check for proper firing rate on furnace. Ensurethere is no blockage in heater. Check for proper airflow. If limit not closed within 3 minutes, unit will gointo 1−hour soft lockout. Resumes normal operationafter fault is cleared.

E 252 Discharge air temperature too high (gas heat only). Check temperature rise, air flow and input rate.Cleared when heat call is finished.

E 270 Soft lockout − Exceeded maximum number of retries. No flame currentsensed.

Check for proper gas flow. Ensure that ignitor islighting burner. Check flame sensor current. Clearswhen heat call finishes successfully.

E 271 Soft lockout − Exceeded maximum number of retries. Last retry failed dueto the pressure switch opening.

Check pressure (inches w.c.) of low pressure switchclosing on heat call. Measure operating pressure(inches w.c.). Inspect vent and combustion air in-ducer for correct operation and restriction. Clearswhen heat call finishes successfully.

Page 52: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 52

Integrated Control Diagnostic Codes (continued)

E 272 Soft lockout − Exceeded maximum number of recycles. Last recycle dueto the pressure switch opening.

Check operation of low pressure switch to see if it isstuck closed on heat call. Check pressure (inchesw.c.) of high pressure switch closing on heat call.Measure operating pressure (inches w.c.). Inspectvent and combustion air inducer for correct opera-tion and restriction. Clears when heat call finishessuccessfully.

E 273 Soft lockout − Exceeded maximum number of recycles. Last recycle dueto flame failure.

Check micro−amperes of flame sensor using controldiagnostics or field−installed mode. Clean or replacesensor. Measure voltage of neutral to ground to en-sure good unit ground. Clears when heat call finish-es successfully.

E 274 Soft lockout − Exceeded maximum number of recycles. Last recyclefailed due to the limit circuit opening or limit remained open longer than3 minutes.

Shut down system. 1−hour soft lockout. Check firingrate and air flow. Check for blockage. Clears whenheat call finishes successfully.

E 275 Soft lockout − Flame sensed out of sequence. Flame signal is gone. Shut off gas. Check for gas valve leak. 1−hour softlockout. Clears when flame has been proven stable.

E 276 Watchguard calibration failure. Unable to perform pressure switch calibration.Check vent system and pressure switch wiring con-nections. 1−hour soft lockout. Clears when calibra-tion has finished successfully.

E 290 Ignitor circuit fault − Failed ignitor or triggering circuitry. Measure resistance of hot surface ignitor. Replace ifopen or not within specifications. 1−hour soft lock-out. Clears when flame has been proven stable.

E 291 Heat air flow restricted below the minimum. Check for dirty filter and air flow restriction. Checkblower performance. 1−hour soft lockout. Clearedwhen heat call finishes successfully.

E 292 Indoor blower motor unable to start due to obstructed wheel, seizedbearings.

Indoor blower motor unable to start (seized bear-ing, stuck wheel, etc.). Replace motor or wheel ifassembly does not operate or meet performancestandards. 1−hour soft lockout. Clears after circula-tor successfully starts.

E 294 Combustion air inducer over current. Check combustion blower bearings, wiring andamps. Replace if does not operate or does not meetperformance standards. Clears after inducer currentis sensed to be in−range after the ignition followingthe soft lockout or reset.

E 295 Indoor blower motor temperature is too high. Indoor blower motor over temperature (motortripped on internal protector). Check motor bearingsand amps. Replace if necessary. Cleared afterblower demand is satisfied.

E 310 Discharge error temperature sensor failure. Only shown if shorted orout of range.

Compare outdoor sensor resistance to temperature/resistance charts in installation instructions. Re-place sensor if necessary. Cleared in Communicat-ing mode: 30 seconds after fault recovered. In Non−Communicating mode: Cleared after the currentheat call is completed.

E 311 Heat rate reduced to match indoor blower air flow. Warning Only. Furnace blower in cutback mode dueto restricted airflow. Reduce firing rate every 60seconds to match available CFM. Check filter andduct system. To clear, replace filter if needed or re-pair/add duct. 2−stage controls will reduce firing rateto 1st stage. Clears when heat call finishes success-fully.

Page 53: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 53

Integrated Control Diagnostic Codes (continued)

Code Diagnostic Codes/Status of Equipment Action Required to Clear and Recover

E 312 Restricted air flow in cooling or continuous fan mode is lower than cfmsetting.

Warning Only. Restricted airflow − Indoor blower isrunning at a reduced CFM (Cutback Mode − Thevariable speed motor has pre−set speed and torquelimiters to protect the motor from damage causedby operating outside of design parameters (0 to 0.8"W.C.. total external static pressure). Check filter andduct system. To clear, replace filter if needed or re-pair/add duct. Cleared after the current service de-mand is satisfied.

E 313 Indoor or outdoor unit capacity mismatch. Communication only. Incorrect indoor/outdoor capacity code selected.Check for proper configuring in installation instruc-tions. Alarm is just a warning. The system will oper-ate, but might not meet efficiency and capacity pa-rameters. Alarm will clear when commissioning isexited. Cleared after commissioning is complete.

E 331 Global network connection − Communication link problem. For Future Use.

E 334 Relay �Y1" stuck on interated control. Replace integrated control.

E 347 No 24 Volt output on Y1 of "integrated control" with non communicatingoutdoor unit.

Operation stopped. Y1 relay / Stage 1 failed. (Pilotrelay contacts did not close or the relay coil did notenergize; no input back to IFC chip). Critical Alert.Cleared after reset and Y1 input sensed.

E 348 No 24 Volt output on Y2 of "integrated control" with non?communicatingoutdoor unit.

Y2 relay / Stage 2 failed. (Pilot relay contacts didnot close or the relay coil did not energize; no inputback to IFC chip). Critical Alert. Cleared after resetand Y1 input sensed.

E 349 No 24 Volts between R & O on "integrated control" with non communi-cating outdoor unit (Dual fuel module required for heat pump application).

Configuration link R to O needs to be restored. Re-place link or hard−wire. Applicable in non communi-cating mode. Critical Alert.

E 370 Interlock switch sensed open for 2 minutes. Control sees the loss of 24VAC for 2 minutes .Ter-minate all services and wait for interlock switch toclose. The alarm will clear when 24VAC is continu-ously sensed on DS terminal for a minimum of 10seconds or on a power reset.

E 400 LSOM − Compressor internal overload tripped. Thermostat demand Y1 is present; but, compressoris not running. Check power to outdoor unit. Clearsthe error after current is sensed in both RUN andSTART sensors for at least 2 seconds, or after ser-vice is removed, or after power reset.

E 401 LSOM Compressor long run cycle or low system pressure. Compressor ran more than 18 hours to satisfy asingle thermostat demand. Critical Alert. Clears theerror after 30 consecutive normal run cycles orpower reset. Also monitors low pressure switchtrips.

E 402 LSOM − Outdoor unit system pressure trip. Discharge or suction pressure out−of−limits, or com-pressor overloaded. Clears the error after 4 consec-utive normal compressor run cycles.

E 403 LSOM − Compressor short−cycling. .(Running less than 4 minutes). Out-door unit pressure trip

Compressor runs less than 3 minutes to satisfy athermostat demand. Clears the error after 4 consec-utive normal run cycles or power reset.

E 404 LSOM − Compressor rotor locked. Compressor short−cycling. (Runningless than 4 minutes).

Compressor rotor locked up due to run capacitorshort, bearings are seized, excessive liquid refriger-ant, etc. Clears the error after 4 consecutive normalrun cycles or after power reset.

E 405 LSOM − Compressor open circuit. Compressor circuit open (due to power disconnec-tion, open fuse, etc.) Clears the error after 1 normalcompressor run cycle.

Page 54: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 54

Integrated Control Diagnostic Codes (continued)

E 406 LSOM − Compressor open start circuit. Required amount of current is not passing throughStart current transformer. Clears the error after cur-rent is sensed in START sensor, or after power re-set.

E 407 LSOM − Compressor open run circuit. Required amount of current is not passing throughRun current transformer. Clears the error after cur-rent is sensed in RUN sensor, or 1 normal compres-sor run cycle, or after power reset.

E 408 LSOM − Compressor contactor is welded. Compressor runs continuously. Clears the errorafter 1 normal compressor run cycle or after powerreset.

E 409 LSOM − Compressor low voltage. Secondary voltage is below 18VAC. After 10 min-utes, operation is discontinued. Clears the codeafter voltage is higher than 20 VAC for 2 seconds orafter power reset.

Page 55: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 55

Program Unit Capacity/Size Mode

Power−Up − Number displayed represents by integrated control unit size code (furnace modeland capacity). If three horizontal bars are displayed followed by continuous E203, furnacecontrol does not recognize unit size code. Configure per the following:

Furnace control in IDLE mode No heating, cooling or indoor fan

operation)

To enter Program UnitCapacity/Size: pushand hold button next to7−segment LED displayuntil solid �P" symbolappears. Releasebutton.

Turn room thermostat to OFF

Solid P startsblinking on7−Segment LED

Push and hold button. Integrated control willdisplay unit size code number for eachfurnace model for three seconds.

When the correct unit size code is displayed, releasebutton. Selected code will flash for 10−second period.During that period, press and hold push button for 5seconds. Integrated control will store code inmemory and will automatically exit Program UnitCapacity/Size Mode and reset. (If second periodexpires or push button is held less than five seconds,control will automatically exit ProgramCapacity/Size Mode and go into IDLE mode withoutstoring unit size code. If this happens, programmingfunction must be repeated).

Verify that the selected unit size code is correctand stored in non−volatile memory by cyclingthe 24 volt power to the furnace control. (At 24volt power−up of the furnace control, the7−segment LED will display a unit size code. Ifthree horizontal bars display, board does notrecognize unit size code. Programmingfunction must be repeated)

Yes No

IMPORTANT: Field replacement controls mayneed to be manually configured to validatefurnace unit size code.

FURNACE MODEL

SL280DF070V36A

SL280DF090V48B

SL280DF090V60C

SL280DF110V60C

UNIT SIZE CODE

A

b

C

d

−−−

_

P

−−−

FINISHED

Page 56: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 56

Troubleshooting: Heating Sequence of Operation

HIGHLIMIT SWITCH

CLOSED?

LOWPRESSURE

SWITCHOPEN?

INDUCER ON

PRE−PURGE(15 SECONDS)

1ST STAGE GASVALVE ENERGIZED

FLAME

SENSED WITHIN

4 SECONDS?

(LOW HEAT SPEED)

HEAT FAN OFF DELAY(LOW HEAT SPEED)

AFTER HEAT FANOFF DELAY (LOW

HEAT SPEED)

YES

YES

YES

YES

ERRORCODE

FLASHES ON(LOW HEATSPEED)

NO

NO

NO

NO

CALLFOR HEAT

ENDS?

ERROR CODEFLASHES (AFTER

5 SECONDS)

5TH

UNSUCCESSFUL

TRIAL?

POSTPURGE(5 SECONDS)

INDUCEROFF

NO

YES

NO

NO

ROLLOUTCIRCUITSCLOSED?

DE−ENERGIZEGAS VALVE

ERRORCODE

FLASHESINDOOR BLOWER ON (LOW HEAT

SPEED)

INDUCER ON (HIGH SPEED)

LIMIT

SWITCH

CLOSED WITHIN 3

MINUTES?

CALL FOR 1ST STAGE HEAT

(LOW FIRE)

NO

GAS VALVEDE−ENERGIZED

H.S.I. OFF

H.S.I. ON(20 SECONDS)

WATCHGUARD −ERROR CODE FLASHES

CALL FOR HEAT SATISFIED

IGNITION TRIAL BEGINS (H.S.I. ON)

HEAT FAN ON DELAYTIMER STARTED

INTERPURGE(15 SECONDS)

H.S.I. OFF

NOINDUCER OFFAFTER POST

PURGE

HARD LOCKOUT − ERROR CODE FLASHES

YES

YES

YES

1

2

1

LOW PRESSURE SWITCH OPENS

1

2 HARD LOCKOUT REQUIRES THERMOSTAT RESET OR CYCLING OF POWER TO RESET THE LOCKOUT.

3 IN CASE HIGH SPEED INDUCER IS RUNNING AT THE TIME THE GAS VALVE GETS ENERGIZED,2ND STAGE GAS VALVE IS ENERGIZED INSTEAD OF 1ST STAGE. 20 SECONDS AFTER FLAMEIS SENSED, INDUCER SWITCHES TO LOW SPEED, AND GAS VALVE SWITCHES TO 1ST STAGE.

1

2

1

NO

LOWPRESSURE SWITCHCLOSED WITHIN 120

SECONDS? LOW & HIGHPRESSURE SWITCHCLOSED WITHIN 30

SECONDS?

HIGHPRESSURE

SWITCHOPEN

BEFOREINDUCER WASTURNED ON?

INDUCER TOHIGH SPEED−ERROR CODE

FLASHES

NO

INDUCER OFF−WAIT

5 MINUTESERROR CODE

FLASHES

YES

YES

YES

YES

NO

3

INDOOR BLOWER OFF AFTER

INDOORBLOWER OFF

INDOORBLOWER

ROLLOUTCIRCUITCLOSES(MANUALRE−SET)

NO

LOW SPEED

INDOOR BLOWEROFF AFTER HEATOFF DELAY

YES

INDOORBLOWER

ON?

WATCHGUARD −ERROR CODE FLASHES

INDOORBLOWER

ON?

INDOORBLOWER ON 45 SEC.

WATCHGUARD LOCKOUT AUTOMATICALLY RESETS AFTER ONE HOUR

CALL FOR FIRST−STAGE HEAT

INDOORBLOWER

OFF AFTERHEAT FAN

OFF DELAY

Page 57: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 57

Troubleshooting: Heating Sequence of Operation (Continued)

WHEN USED WITH A SINGLE STAGE THERMOSTAT, SET SW1 TO THE ON POSITION IN DIP SWITCH S4.

IF THE HIGH FIRE PRESSURE SWITCH DOES NOT CLOSE WITHIN 5 ATTEMPTS, THE SYSTEM WILL OPERATE ATLOW FIRE FOR THE REMAINDER OF THE CALL FOR HEAT REQUEST.

2ND STAGE GAS VALVEENERGIZED

ONLY FOR 1STREQUEST FOR

2ND STAGE HEAT

YES

CALL FOR HEAT SATISFIED

INDUCER SWITCHEDTO HIGH SPEED

SINGLE STAGETHERMOSTAT2 STAGE THERMOSTAT

NOINDUCER SWITCHED

TO LOW SPEED5 MINUTE DELAY

(ERROR CODE FLASHES)

HIGHPRESSURE SWITCHCLOSED WITHIN 10

SECONDS?

2ND STAGEON DELAYEXPIRED?

CALL FOR 2ND STAGE HEAT(HIGH FIRE)

2

3

1

2

3

1

2

3

YESYES

CALL FOR SECOND−STAGE HEAT

RECOGNITION DELAY(30 SECONDS)

EXPIRED?

INDOOR BLOWER ENERGIZEDON HIGH HEAT SPEED

SYSTEM WILL ALWAYS LIGHT ON LOW FIIRE, EVEN IF 2ND STAGE HEAT IS IN PLACE.

Page 58: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 58

Troubleshooting: Heating Sequence of Operation (Continued)

2ND STAGE HEAT

RUN MODE:1ST OR 2ND STAGE CALL FOR HEAT.ALL INPUTS MONITORED (LIMIT, PRESSURE,CALL FOR HEAT/COOL, FLAME LEVEL)

2ND STAGECALL FOR HEAT

SATISFIED?

NO

YES

DE−ENERGIZE 2ND STAGEGAS VALVE

INDUCER SPEED SWITCHEDTO LOW SPEED

1

2 3

1ST STAGE HEAT

1ST STAGECALL FOR HEAT

SATISFIED?

NO

YES

GAS VALVEDE−ENERGIZED

INDUCER OFF AFTER5 SECOND POST PURGE

CALL FOR HEAT SATISFIED

FIRST−STAGE HEAT SECOND−STAGE HEAT

INDOOR BLOWER SWITCHEDTO LOW HEAT SPEED

INDOOR BLOWER OFFAFTER FIELD SELECTABLE

OFF DELAY

Page 59: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 59

Troubleshooting: Cooling Sequence of Operation (Continued)

1ST STAGE COOLINGREQUEST RECEIVED

ENERGIZE 1ST STAGECOOLING CONTACTOR(COMPRESSOR & FAN)

2ND STAGECOOLINGREQUEST?

NO

YES

YES

YES

NO

1ST STAGECOOLING REQUEST

STILL ACTIVE?

NO

YES

YES

ENERGIZE 2ND STAGECOOLING CONTACTOR(COMPRESSOR & FAN)

DE−ENERGIZE 2NDSTAGE COOLING

CONTACTOR(COMPRESSOR & FAN)

NO

CONTROL WILL NOT RESPOND TO A 2ND STAGE COOLING REQUEST UNLESS A 1ST STAGECOOLING REQUEST IS ACTIVE.

AND SPEED RAMPING PROFILES. THE SPECIFIC PROFILE IS SELECTED USING THE

1

1

2

2

1

1

1

2

2

DE−ENERGIZE 1STSTAGE COOLING

CONTACTOR(COMPRESSOR & FAN)

2ND STAGECOOLING REQUEST

STILL ACTIVE?

COOLING REQUESTSTILL ACTIVE?

CALL FOR COOLING

WAIT FOR COMPRESSOR TIMEDOFF DELAY TO EXPIRE

INDOOR BLOWER 2SECOND ON DELAY

YES

1ST STAGE

DE−ENERGIZE INDOORBLOWER

INDOOR BLOWER LOW COOLING MODE AND HIGH COOLING MODE HAVE SPECIFIC ON, OFF

ENERGIZE INDOOR BLOWER(LOW COOLING MODE)

ENERGIZE INDOOR BLOWER(HIGH COOLING MODE)

MAINTAIN INDOOR BLOWER(HIGH COOLING MODE)

ENERGIZE AND MAINTAININDOOR BLOWER AT

(LOW COOLING MODE)

DIP SWITCHES ON THE CONROL.

MAINTAIN INDOORBLOWER

(LOW COOLING MODE)

Page 60: INSTALLATION INSTRUCTIONS - Lennox · installation must conform with the current National Elec-tric Code, ANSI/NFPA No. 70. The National Electric Code (ANSI/NFPA No. 70) is available

Page 60

Troubleshooting: Continuous Fan Sequence of Operation

CALL FOR FAN

CALL FOR FANREMOVED?

YES

NO

NO

REQUESTFOR HEATRECEIVED?

REQUESTFOR COOLING

RECEIVED?

GO TO CALL FOR 1ST STAGE HEAT

YESGO TO CALL FOR COOLING

1

1

1

4

YES

NO

CALL FOR FAN

INDOOR BLOWER ONCONTINUOUS FAN

SPEED

MAINTAIN INDOORBLOWER AT

CONTINUOUS FAN

MAINTAIN INDOORBLOWER AT

CONTINUOUS FAN

INDOOR BLOWER OFF

DE−ENERGIZE INDOORBLOWER