Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid Chillers CVGF-SVN02B-E4 X39640686020 Unit Model CVGF 400-1000 Ton Units (50 and 60 Hz)

Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

Embed Size (px)

Citation preview

Page 1: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

InstallationManual

Gear-DrivenCentrifugal Water-Cooled Liquid Chillers

CVGF-SVN02B-E4X39640686020

Unit ModelCVGF 400-1000 Ton Units(50 and 60 Hz)

Page 2: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4© 2004 American Standard Inc. All rights reserved.

Warnings andCautions

NOTICE: Warnings and Cautions appear at appropriate sections throughout this manual.

Read these carefully.

�� WARNING - Indicates a potentially hazardous situation which, if not avoided, could result indeath or serious injury.

�� CAUTION - Indicates a potentially hazardous situation which, if not avoided, may result inminor or moderate injury. It may also be used to alert against unsafe practices.

CAUTION - Indicates a situation that may result in equipment or property-damage-onlyaccidents.

Page 3: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4 3

Contents

Warnings and Cautions

General Information

Installation: Mechanical

Installation: Electrical

2

4

32

56

Page 4: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E44

GeneralInformation

Conversion ChartSI Multiply by METRICpsi 6.89 kPapsi .069 Barpsi .070 kg/cm²

degrees °F (F-32)×5/9 Degrees C

pound-ft 1.36 Nmpound-ft 0.138 kg-mpound-ft 0.0014 kN-m

gpm (US) 0.063 L/sgpm (US) 6.309 m³/secgpm (US) 63.09 cm³/sec

in-H²O 0.249 kPain-H²O 0.0361 psiin-H²O 0.0736 in-Hg

inches 25.4 mminches 2.54 cmfeet 0.305 metersfeet² 0.093 meters²

Microns 0.001 mm Hg

Safety Control Settings ChartControl Settings I-P Settings SIOil pressure control Cut-in 12 psi, Cut-in 151 kPa,

Cut-out 9 psi Cut-out 124 kPaHigh pressure control Cut-out 195 psi Cut-out 1344 kPaHigh oil temperature Cut-out 165°F Cut-out 74°CLow oil temperature Cut-out 5°F below set point Cut-out 2.8°C below set pointHigh motor temperature Cut-out 265°F ± 15°F Cut-out 130°C ± 8°C

Oil ChartUSA EuropeOil 0037 Oil 021EOil 0049 Oil 0020E

Page 5: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

MODEL: CVGF500MODEL NO: CVGF0500RA0U33809405C1B5C1C23A1A201E3AA0SERIAL NO: S.O. NO:

ELECTRICAL CHARACTERISTICS:RATED VOLTAGE: 380 VOLTS 50HZ 3PHNAMEPLATE NMKW: 338 kWVOLTAGE UTILIZATION RANGE: 345- 422 VACMINIMUM CIRCUIT AMPACITY: 726 AMPSMAXIMUM FUSE: 1200 AMPSMAXIMUM CIRCUIT BREAKER 1200 AMPSMAXIMUM OVERLOAD TRIP: 617 AMPS

MAX MAXVOLTS-AC HZ PH RLA LRAY

LRADCOMPRESSOR MOTOR 380 50 3 577 1048 3286OIL PUMP MOTOR 380 50 31.43 FLAOIL TANK HEATER 115 50 1000 WATTS TOTALCONTROL CIRCUIT 115 50 1500 VA MAX

WHEN MOTOR CONTROLLER PROVIDED BY OTHERSTRANE ENGINEERING SPEC. S6516-0360 APPLIES

GENERAL CHARACTERISTICS:REFRIGERANT SYSTEMTO BE FIELD CHARGED ACTUALLY CHARGEDWITH 340 KG OF R-134A WITH KG OF R-134A

MAXIMUM REFRIGERANT WORKING PRESSUREHI SIDE 15.2 BAR LOW SIDE 15.2 BAR

FACTORY TEST PRESSUREHI SIDE 16.7 BAR LOW SIDE 16.7 BARFIELD LEAK TEST PRESSURE 82.50 BAR MAX.

TESTED AT BARLEAK TEST AND CHARGING SPECIFICATION ARE SUPPLIEDIN CONTROL PANEL (SERVICE LITERATURE MANUAL)

MANUFACTURED UNDER ONE OR MORE OF THE FOLLOWING U.S. PATENTS: 4686834 4689967 4715190 5056032

5058031 5434738 5563489 5836382SERVICE LITERATUREINSTALLATION, OPERATION AND MAINTENANCE MANUAL:CVGF-SVN02A-EN AND CVGF-SVU02A-EN

“FOR INSTALLATION REQUIREMENTS, USE ELECTRICALCHARACTERISTICS NOT PRODUCT DESCRIPTION”

PRODUCT DESCRIPTION:

MODL CVGF DSEQ A0 NTON 500 VOLT 380HRTZ 50 CPKW 338 CPIM 940 EVSZ 500EVBS C EVTB TE25 EFLD WATE EVWB NM15EVWP 2 EVCO FLGE EVWA RERE CDSZ 500CDBS C CDTB TE28 CFLD WATE CDWB NM15CDCO FLGE CDWA RERE ORSZ 23 AGLT ULSPKGEXPS INSL YES OPTM YES WVUO YESTRMM TRMS LCLD CLDC LANG ENGL SRTY USTRSRRL 952 PNCO DISC TEST PTR3

Figure 1. Typical unit nameplate

CVGF-SVN02B-E4

Literature Change History

CVGF-SVX001-E4 (July 2000)

This manual describes theinstallation, operation, andmaintenance of CVGF units.

CVGF-SVN02A-E4 (2002)

Replaces CVGF-SVX001-E4.

About this Manual

This manual describes properinstallation of Model CVGF, 50 Hzand 60 Hz chillers with the TracerCH530 Controls platform. SeeFigures 2 and 3 for an illustrationof a CVGF Centrifugal Chillerwith the Tracer CH530 UnitControl Panel.

These chillers are equipped withmicrocomputer-based controlsystems. A careful review of thisinformation along with thesubmittal package provided forthe unit will assure that thechiller is correctly installed.

Unit Identification -Nameplates

When the unit arrives, compareall nameplate data with order,submittal and shippinginformation. A typical unitnameplate is shown in Figure 1.

5

GeneralInformation

Page 6: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4

Unit Nameplates

The CVGF unit nameplate(Figure 2 shows the nameplatelocation) is applied to theexterior surface of the controlpanel. The starter nameplate islocated inside the starter panel.

The unit nameplate provides thefollowing information:

• Unit model

• Unit serial number

• Unit device number - identifiesunit electrical requirements- Lists correct operatingcharges of HFC-134a andlubrication oil

- Lists unit test pressures andmaximum working pressures

The starter nameplate providesthe following information:

• Panel model number

• Rated load amps

• Voltage

• Electrical characteristics -starter type, wiring

• Options included

Unit Inspection

When the unit is delivered, verifythat it is the correct unit and thatit is properly equipped.

Inspect all exterior componentsfor visible damage. Report anyapparent damage or materialshortage to the carrier and makea “unit damage” notation on thecarrier’s delivery receipt. Specifythe extent and type of damagefound and notify the appropriateTrane Sales Office.

Do not proceed with installationof a damaged unit without salesoffice approval.

Inspection Checklist

To protect against loss due todamage incurred in transit,complete the pre-commissioningchecklist, which can be obtainedfrom your Trane representative.

• Inspect the individual pieces ofthe shipment before acceptingthe unit. Check for obviousdamage to the unit or packingmaterial.

• Inspect the unit for concealeddamage as soon as possibleafter delivery and before it isstored. Concealed damagemust be reported within 10days after receipt.

• If concealed damage isdiscovered, stop unpacking theshipment. Do not removedamaged material from thereceiving location. Take photosof the damage, if possible. Theowner must provide reasonableevidence that the damage didnot occur after delivery.

• Notify the Trane salesrepresentative and arrange forrepair. Do not repair the unit,however, until damage isinspected by the transportationrepresentative.

6

GeneralInformation

Page 7: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

Loose Parts Inventory

The loose parts items ship in themotor junction box for unitswithout a unit-mounted starter,or in the starter panel for unitsequipped with a unit-mountedstarter. This includes theisolation pads, extra oil filter,and any optional factory-shippeditems.

Unit Description

The CVGF units are single-compressor, gear-type, water-cooled liquid chillers designedfor installation indoors. Each unitis a completely assembled,hermetic package that is factory-piped, wired, leak-tested,dehydrated, oil-charged, andtested for proper controloperation before shipment.Note: high-voltage starters arenot unit-mounted beforeshipment.

Figure 2 and Figure 3 show atypical CVGF unit and itscomponents. Water inlet andoutlet openings are coveredbefore shipment. The oil tank isfactory-charged with 15 gallons(56.8L) of Trane Oil 37 and aholding charge of 5 psig (34 kPa)of dry nitrogen at 70°F (21°C).(See the Operation MaintenanceManual for equivalent oilspecification.)

CVGF-SVN02B-E4 7

GeneralInformation

Page 8: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E48

GeneralInformation

Figure 2. Component location for typical CVGF unit

Relief valves

Unit nameplate

Control Panel CH530

Evaporator

Oil Pump

Two-stage compressor

Unit-mounted starter (optional)

Condenser

Motor

Unit nameplate

Relief valves

Oil cooler

Economizer

Figure 3. Component location for typical CVGF unit (back view)

Page 9: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

H = (9th digit) Unit VoltageD = 380V-60 HzF = 460V-60 HzH = 575V-60 HzN = 4160V-60 HzP = 3300V-60 HzR = 380V-50 HzT = 400V-50 HzU = 415V-50 HzV = 3300V-50 HzX = 6600V-60 HzZ = 6600V-50 HzS = Special

A0 = (10th and 11th digit) DesignSequence

C = (12th digit) Control EnclosureC = Standard Control EnclosureS = Special

316 = (13th, 14th, and 15th digit)Compressor Motor Power (kw)221 = 221 CPKW254 = 254 CPKW285 = 285 CPKW316 = 316 CPKW357 = 357 CPKW401 = 401 CPKW240 = 240 CPKW266 = 266 CPKW301 = 301 CPKW338 = 338 CPKW374 = 374 CPKW430 = 430 CPKW444 = 444 CPKW484 = 484 CPKW511 = 511 CPKW532 = 532 CPKW574 = 574 CPKW594 = 594 CPKW641 = 641 CPKW674 = 674 CPKW719 = 719 CPKW751 = 751 CPKW808 = 808 CPKWSSS = Special

0900 = (16th, 17th, 18th, and 19thdigit) Compressor Impeller Cutback0880 CPIM0890 CPIM0900 CPIM0910 CPIM0920 CPIM0930 CPIM0940 CPIM0950 CPIM0960 CPIM0970 CPIM0980 CPIM0990 CPIM1000 through 1510 = Cutback is thesame as the FCOD for impellercutbackSSSS = Special

5 = (20th digit) Evaporator Shell Size1 = 1000 ton evaporator5 = 500 ton evaporator7 = 700 ton evaporatorS = Special

B = (21st digit) Evaporator TubeBundleA = Small bundleB = Medium bundleC = Large bundleD = Extra large bundleS = Special

1 = (22nd digit) Evaporator Tubes1 = .75 diameter .025 wall internallyenhanced cu tube2 = 1.00 diameter .025 wall internallyenhanced cu tubeS = Special

CVGF-SVN02B-E4 9

GeneralInformation

Model number digits are selectedand assigned in accordance with thefollowing definitions using thetypical model number exampleshown below:

CVGF0500HA0C31609005B1B5B1C2306G4A1E2CC0A0CL

C = (1st digit)

V = (2nd digit) Hermetic CentrifugalCompressor

G = (3rd digit) Gear Drive

F = (4th digit) Developmentsequence

0500 = (5th, 6th, 7th, and 8th digit)Nominal compressor tonnage0400 = 400 tons0500 = 500 tons0650 = 650 tons0800 = 800 tons1000 = 1000 tonsSSSS = Special

Page 10: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4

0 = (30th digit) Factory InstalledInsulation0 = NoneA = Factory installed insulation

1 = (31st digit) Control: OperatingStatus0 = None1 = Operating Status

G = (32nd digit) Control: GenericBAS0 = NoneG = Generic BAS

4 = (33rd digit) TracerCommunication Interface0 = None4 = COMM 45 = COMM 5

A = (34th digit) Chilled Water Reset -Outdoor Air Temperature Sensor0 = NoneA = Chilled Water Reset – WithOutdoor Air Temp Sensor

1 = (35th digit) Control: ExtendedOperation0 = None1 = Extended Operation

E = (36th digit) LanguageE = EnglishF = FrenchG = GermanT = ItalianP = SpanishS = Special

10

GeneralInformation

B = (23rd digit) EvaporatorWaterboxB = 150 PSI Non-Marine - 2 passC = 150 PSI Non-Marine - 3 passD = 150 PSI Marine - 2 passE = 150 PSI Marine - 3 passH = 300 PSI Marine - 2 passJ = 300 PSI Marine - 3 passL = 300 PSI Non-Marine - 2 passM = 300 PSI Non-Marine - 3 passS = Special

5 = (24th digit) Condenser Shell Size1 = 1000 ton condenser5 = 500 ton condenser7 = 700 ton condenserS = Special

B = (25th digit) Condenser TubeBundleA = Small bundleB = Medium bundleC = Large bundleD = Extra large bundleS = Special

1 = (26th digit) Condenser Tubes1 = .75 diameter .028 wall internallyenhanced cu tube2 = 1.00 diameter .028 wall internallyenhanced cu tube3 = .75 diameter .035 wall 90/10 cu/nitube4 = .75 diameter .028 wall titaniumtubeS = Special

C = (27th digit) Condenser WaterboxA = 150 PSI Marine - 2 passC = 150 PSI Non-Marine - 2 passE = 300 PSI Marine - 2 passG = 300 PSI Non-Marine - 2 passS = Special

23 = (28th and 29th digit) OrificeSeries13 Orifice series14 Orifice series15 Orifice series16 Orifice series17 Orifice series18 Orifice series19 Orifice series20 Orifice series22 Orifice series23 Orifice series25 Orifice series27 Orifice series28 Orifice series30 Orifice series31 Orifice series33 Orifice series35 Orifice series38 Orifice series40 Orifice series42 Orifice series44 Orifice series47 Orifice series49 Orifice series51 Orifice series56 Orifice seriesSS = Special

Page 11: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

A = (41st digit) Starter TypeA = Star-Delta - unit mountedB = Solid State - unit mountedC = Star-Delta - remote mountedE = X-line full volt - remote mountedF = Autotransformer - remotemountedG = Primary reactor - remotemountedM= Solid State Floor MountedN= Solid State Wall MountedR = Customer supplied

0 = (42nd digit) Additional PressureVessel Compliance0 = NoneN = Non-destructive Examination forChinaK = KHK Japanese pressure vesselcode

C = (43rd digit) Control: CondenserRefrigerant Pressure0 = NoneC = Condenser Refrigerant Pressure

L = (44th digit) ManufacturingLocationL = La Crosse, WisconsinT = Tai Cang, China

C = (39th digit) Impeller RimDiameter 2nd StageA = 9.5 Rim diameterB = 10.0 Rim diameterC = 10.6 Rim diameterD = 11.1 Rim diameterE = 11.6 Rim diameterF = 9.8 Rim diameterG = 10.4 Rim diameterH = 11.0 Rim diameterJ = 11.7 Rim diameterK = 12.7 Rim diameterL = 13.5 Rim diameterM = 14.3 Rim diameterN = 15.1 Rim diameterS = Special

0 = (40th digit) Special Options0 = NoneS = Special option

CVGF-SVN02B-E4 11

GeneralInformation

2 = (37th digit) Motor Frame Size2 = 400 Frame3 = 440E Frame4 = 5000 FrameS = Special

C = (38th digit) Impeller RimDiameter 1st StageA = 9.5 Rim diameterB = 10.0 Rim diameterC = 10.6 Rim diameterD = 11.1 Rim diameterE = 11.6 Rim diameterF = 9.8 Rim diameterG = 10.4 Rim diameterH = 11.0 Rim diameterJ = 11.7 Rim diameterK = 12.7 Rim diameterL = 13.5 Rim diameterM = 14.3 Rim diameterN = 15.1 Rim diameterS = Special

Page 12: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E412

GeneralInformation

Service Model Numbers –Solid State Motor StarterAn example of a typical Solid State“IT” starter model number is:

CVSR0035FAA01EA0E1Model Number Digit Identification -Model number digits are selectedand assigned in accordance with thefollowing definitions using themodel number example shownabove.

C = (1st digit)

V = 2nd digit)

S = (3rd digit)

R = (4th digit) DevelopmentSequenceR = Cutler Hammer Solid State “IT”starter for gear drive centrifugalchillers with CH530 controls0035 = (5th, 6th, 7th, and 8th digit)Starter Size

Use Rated Load Amps (RLA) value

F = (9th digit) Unit VoltageD = 380V-60Hz-3PhF = 460V-60Hz-3PhH = 575V-60Hz-3PhR = 380V-50Hz-3PhT = 400V-50Hz-3PhU = 415V-50Hz-3PhS = Special

A = (10th digit) Design SequenceA = Original Design

A = (11th digit) Starter TypeB = Unit MountedM = Remote Floor MountedN = Remote Wall MountedS = Special

0 = (12th digit) Connection Type0 = Terminal Block1 = Disconnect Switch - Non-Fused2 = Circuit Breaker3 = Circuit Breaker Current Limiting4 = Circuit Breaker High InterruptCap5 = Circuit Breaker Higher InterruptCapS = Special

1 = (13th digit) Agency Listing1 = UL & cUL Listed (Standard on allunits)2 = CE

E = (14th Digit) Power FactorCorrection Capacitor0 = NoneD = 25 KVARE = 30 KVARF = 35 KVARG = 40 KVARH = 45 KVAR

J = 50 KVARK = 60 KVARL = 70 KVARM = 75 KVARN = 80 KVARP = 90 KVARR = 100 KVART = 120 KVARU = 125 KVARV = 150 KVARS = Special

A = (15th Digit) Ground FaultProtection0 = NoneA = Ground Fault ProtectionS = Special

0 = (16th digit) Special Options0 = NoneS = Special Options ( See SalesOrder)

E = (17th digit) Literature LanguageE = EnglishF = FrenchG = GermanP = SpanishT = ItalianS = Special

1 = (18th digit) Oil Pump StarterCircuit1 = 1 HP Oil Pump Motor2 = 1.5 HP Oil Pump

Page 13: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4 13

GeneralInformation

Service Model Numbers -Wye-delta Motor Starter

An example of a typical chillerstarter model number is:

CVSN0035FAA01EA0E1Model Number Digit Identification -Model number digits are selectedand assigned in accordance with thefollowing definitions using themodel number example shownabove.

C = (1st digit)

V = 2nd digit)

S = (3rd digit)

N = (4th digit) DevelopmentSequenceN = Cutler-Hammer electrical-mechanical starter for gear drivecentrifugal chillers with CH530controls

0035 = (5th, 6th, 7th, and 8th digit)Starter Size

F = (9th digit) Unit VoltageD = 380V-60Hz-3PhF = 460V-60Hz-3PhH = 575V-60Hz-3PhR = 380V-50Hz-3PhT = 400V-50Hz-3PhU = 415V-50Hz-3PhS = Special

A = (10th digit) Design SequenceA = Original Design

A = (11th digit) Starter TypeA = Star-Delta - Unit MountedC = Star-Delta - Remote MountedS = Special

0 = (12th digit) Connection Type0 = Terminal Block1 = Disconnect Switch - Non-Fused2 = Circuit Breaker3 = Circuit Breaker Current Limiting4 = Circuit Breaker High InterruptCap5 = Circuit Breaker Higher InterruptCapS = Special

1 = (13th digit) Agency Listing1 = UL & cUL Listed (Standard on allunits)2 = CE.

E = (14th Digit) Power FactorCorrection Capacitor0 = NoneD = 25 KVARE = 30 KVARF = 35 KVARG = 40 KVARH = 45 KVAR

J = 50 KVARK = 60 KVARL = 70 KVARM = 75 KVARN = 80 KVARP = 90 KVARR = 100 KVART = 120 KVARU = 125 KVARV = 150 KVARS = Special

A = (15th Digit) Ground FaultProtection0 = NoneA = Ground Fault ProtectionS = Special

0 = (16th digit) Special Options0 = NoneS = Special Options (See SalesOrder)

E = (17th digit) Literature LanguageE = EnglishF = FrenchG = GermanP = SpanishT = ItalianS = Special

1 = (18th digit) Oil Pump StarterCircuit1 = 1 HP Oil Pump Motor2 = 1.5 HP Oil Pump Motor

Page 14: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E414

GeneralInformation

Installation Overview

For convenience, Table 1 summarizes responsibilities that are typically associated with the CVGF chillerinstallation process.

Table 1. Installation responsibility chart for CVGF unitsRequirement Trane-supplied, Trane-supplied, Field-supplied,

Trane-installed Field-installed Field-installedRigging Safety chains

Clevis connectors

Isolation Isolation pads Spring isolatorsSpring isolators

Electrical

Terminal lugsGround connection(s)Jumper barsBAS wiring (optional)IPC wiringControl voltage wiring

Optional relays and wiringWater piping Thermometers

Pressure Relief Relief valves

Insulation Insulation (optional) Insulation

Lifting beam equipment, skates,rollers, and other liftingoperations

Circuit breakers or non-fuseddisconnects (optional)

Circuit breakers or fusibledisconnects (optional)

Temperature sensor(optional outdoor air)

Remote-mounted starter(optional)

Chilled-water-pump contactor andwiringCondenser-water-pump contactorand wiring

Flow switches (may befield-supplied) Water flow pressure gauges

Isolation and balancing valveswater piping

Pressure relief valves (for waterboxes as required)Vent line and flexible connector

Unit-mounted starter(optional)

Vent and drain valves

Page 15: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4 15

Refer to the Mechanical andElectrical sections of this manualfor detailed instructions.

• Locate and maintain the looseparts such as, isolators, bulbwells, temperature sensors,flow sensors or other factory-ordered field-installed options,as required. Loose parts arelocated in the starter panel ifequipped with a unit-mountedstarter. If not equipped with aunit-mounted starter, looseparts are shipped in the motorjunction box.

• Install the unit on a foundationwith flat support surfaces, levelwithin 1/4" (6 mm) and ofsufficient strength and mass tosupport the chiller operatingweight. Place the manufacturer-supplied isolation-padassemblies under the unit.

• Install the unit per theinstructions outlined in theMechanical Installation section.

• Complete all water piping andelectrical connections.

Note: Field piping must bearranged and supported toavoid stress on the equipment.It is strongly recommendedthat the piping contractorprovide at least 3 feet (914 mm)of clearance between the pre-installation piping and theplanned location of the unit.This will allow for the proper fitupon arrival of the unit at theinstallation site. All necessarypiping adjustments can bemade at that time.

• Where specified, supply andinstall valves in the waterpiping, upstream anddownstream of the evaporatorand condenser water boxes, inorder to isolate the shells formaintenance and to balanceand trim the system.

• Supply and install flowswitches or equivalent devicesin both the chilled-water pipingand the condenser-waterpiping. Interlock each switchwith the proper pump starter, toensure that the unit can onlyoperate when water flow isestablished.

Note: reference graphs 1-16 inthe Installation Mechanicalsection for proper water flow.

• Supply and install taps forthermometers and a pressuregauge manifold in the waterpiping, adjacent to the inlet andoutlet connections of both theevaporator and the condenser.

• Supply and install drain valveson each water box.

• Supply and install vent cockson each water box.

• Where specified, supply andinstall strainers ahead of allpumps and automaticmodulating valves.

• Supply and install refrigerantpressure-relief piping from thepressure-relief valve to theatmosphere.

• If necessary, supply enoughHFC-134a refrigerant (1 pound= .45 kg) and dry nitrogen (75psig = 517 kPa maximum) forleak testing.

• Evacuate the unit to less than500 microns (0.5 mm Hg) oraccording to local code.

• Charge with refrigerant 134a.

• Go over the pre-commissioningcheck sheet and ensure that allitems have been completed.

• Start the unit under thesupervision of a qualifiedservice technician.

GeneralInformation

Page 16: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

Table 2. General data: 400 and 500 ton unitsNominal Tonnage 400 400 400 400 500 500 500 500

1.0 1.0 0.75 0.75 1.0 1.0 0.75 0.75

Two Three Two Three Two Three Two Three

Refrigerant Type R134a R134a R134a R134a R134a R134a R134a R134aRefrigerant Charge - 650 650 650 650 750 750 750 750pounds (kg) (295) (295) (295) (295) (295) (295) (295) (295)Oil Charge 15 15 15 15 15 15 15 15(gallon (l)) (56.8) (56.8) (56.8) (56.8) (56.8) (56.8) (56.8) (56.8)Overall Dimensions - Feet-Inch (mm)Length 15'- 10 13/16" 15'- 10 13/16" 15'- 10 13/16" 15'- 10 13/16" 15'- 10 13/16" 15'- 10 13/16" 15'- 10 13/16" 15'- 10 13/16"

(4800) (4800) (4800) (4800) (4800) (4800) (4800) (4800)Width 6' - 6 19/64" 6' - 6 19/64" 6' - 6 19/64" 6' - 6 19/64" 6' - 6 19/64" 6' - 6 19/64" 6' - 6 19/64" 6' - 6 19/64"

(1989) (1989) (1989) (1989) (1989) (1989) (1989) (1989)Height 6' - 10 1/2" 6' - 10 1/2" 6' - 10 1/2" 6' - 10 1/2" 6' - 10 1/2" 6' - 10 1/2" 6' - 10 1/2" 6' - 10 1/2"

(2096) (2096) (2096) (2096) (2096) (2096) (2096) (2096)2' - 7 1/8" 2' - 7 1/8" 2' - 7 1/8" 2' - 7 1/8" 2' - 7 1/8" 2' - 7 1/8" 2' - 7 1/8" 2' - 7 1/8"

(791) (791) (791) (791) (791) (791) (791) (791)8" 8" 8" 8" 8" 8" 8" 8"

(203) (203) (203) (203) (203) (203) (203) (203)2' - 1 1/2" 2' - 1 1/2" 2' - 1 1/2" 2' - 1 1/2" 2' - 1 1/2" 2' - 1 1/2" 2' - 1 1/2" 2' - 1 1/2"

(3060) (3060) (3060) (3060) (3060) (3060) (3060) (3060)10" 10" 10" 10" 10" 10" 10" 10"

(254) (254) (254) (254) (254) (254) (254) (254)

Weight - pounds (kg)) except WaterboxesCompressor/Motor 6220 6220 6220 6220 6220 6220 6220 6220

(2821) (2821) (2821) (2821) (2821) (2821) (2821) (2821)Evaporator 3948 3948 4228 4228 4193 4193 4568 4568

(1791) (1791) (1918) (1918) (1902) (1902) (2072) (2072)Condenser 2857 2857 3472 3472 3152 3152 3877 3877

(1296) (1296) (1575) (1575) (1430) (1430) (1759) (1759)Economizer 535 535 535 535 535 535 535 535

(243) (243) (243) (243) (243) (243) (243) (243)Starter Panel 500 500 500 500 500 500 500 500

(227) (227) (227) (227) (227) (227) (227) (227)Control Panel 70 70 70 70 70 70 70 70

(318) (318) (318) (318) (318) (318) (318) (318)2127 2127 2127 2127 2127 2127 2127 2127(965) (965) (965) (965) (965) (965) (965) (965)17867 17867 17867 17867 17867 17867 17867 17867(8104) (8104) (8104) (8104) (8104) (8104) (8104) (8104)21460 21460 21460 21460 22564 22564 22564 22564(9734) (9734) (9734) (9734) (10235) (10235) (10235) (10235)

Operational Data447 298 407 271 550 367 511 340(28) (20) (25.6) (17) (34) (23) (32) (21)

1638 1092 1493 995 2018 1346 1873 124895(103) (69) (94) (63) (127) (85) (118) (79)

499 499 487 487 606 606 586 586(31) (31) (31) (31) (38) (38) (37) (37)

1831 1831 1786 1786 2221 2221 2148 2148(115) (115) (113) (113) (140) (140) (135) (135)

CVGF-SVN02B-E416

GeneralInformation

Evaporator Water Pass

Evaporator WaterConnection (NPS)

Condenser NominalConnector Size (NPS)

Miscellaneous Item

Minimum EvaporatorFlow in gpm (l/sec)

Maximum EvaporatorFlow in gpm (l/sec)

Minimum CondenserFlow in gpm (l/sec)

Maximum CondenserFlow in gpm (l/sec)

Tube Outside Diameter(inch)

Evaporator InsideDiameter

Condenser InsideDiameter

Shipping Weight

Operating Weight

Page 17: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4 17

GeneralInformation

Table 2. General data: 400 and 500 ton units (continued)Nominal Tonnage 400 400 400 400 500 500 500 500

1.0 1.0 0.75 0.75 1.0 1.0 0.75 0.75

Two Three Two Three Two Three Two Three

Water Volume - 150 pound Waterboxes101.7 101.49 95.7 95.4 117.2 116.9 111.2 110.9(385) (384) (361) (361) (444) (443) (421) (420)112 112 110.4 110.4 127.8 127.8 125.0 125.0

(424) (424) (418) (418) (484) (484) (473) (473)Evaporator 2-pass WeightSupply - pound 304 304 304 304 304 304 304 304

(kg) (138) (138) (138) (138) (138) (138) (138) (138)Return - pound 337 337 337 337 337 337 337 337

(kg) (153) (153) (153) (153) (153) (153) (153) (153)Evaporator 3-pass WeightSupply - pound 314 314 314 314 314 314 314 314

(kg) (142) (142) (142) (142) (142) (142) (142) (142)Return - pound 332 332 332 332 332 332 332 332

(kg) (151) (151) (151) (151) (151) (151) (151) (151)Condenser 2-pass WeightSupply - pound 304 304 304 304 304 304 304 304

(kg) (138) (138) (138) (138) (138) (138) (138) (138)Return - pound 341 341 341 341 341 341 341 341

(kg) (155) (155) (155) (155) (155) (155) (155) (155)300 pound Waterboxes

101.9 101.6 95.9 95.6 117.4 117.0 111.4 111.1(386) (385) (363) (362) (444) (443) (422) (421)112.3 112.3 110.6 110.6 128.0 128.0 125.3 125.3(425) (425) (419) (419) (485) (485) (474) (474)

Evaporator 2-pass WeightSupply - pound 427 427 427 427 427 427 427 427

(kg) (194) (194) (194) (194) (194) (194) (194) (194)Return - pound 446 446 446 446 446 446 446 446

(kg) (202) (202) (202) (202) (202) (202) (202) (202)Evaporator 3-pass WeightSupply - pound 448 448 448 448 448 448 448 448

(kg) (203) (203) (203) (203) (203) (203) (203) (203)Return - pound 448 448 448 448 448 448 448 448

(kg) (203) (203) (203) (203) (203) (203) (203) (203)Condenser 2-pass WeightSupply - pound 421 421 421 421 421 421 421 421

(kg) (191) (191) (191) (191) (191) (191) (191) (191)Return - pound 436 436 436 436 436 436 436 436

(kg) (198) (198) (198) (198) (198) (198) (198) (198)

Evaporator WaterStorage gallon (l)Condenser WaterStorage gallon (l)

Evaporator WaterStorage gallon (l)Condenser WaterStorage gallon (l)

Evaporator Water Pass

Tube Outside Diameter(inch)

Page 18: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E418

GeneralInformation

Table 3. General data: 650 ton unitsNominal Tonnage 650

1.0 0.75

Two Three Two Three

Refrigerant Type R134a R134a R134a R134aRefrigerant Charge - 975 975 975 975pounds (kg) (442.3) (442.3) (442.3) (442.3)Oil Charge 15 15 15 15gallon (l) (56.8) (56.8) (56.8) (56.8)Overall Dimensions - Feet-Inch (mm)Length 16' 16' 16' 16'

4877 4877 4877 4877Width 6' - 9 3/4 6' - 9 3/4 6' - 9 3/4 6' - 9 3/4

(2076) (2076) (2076) (2076)Height 7' - 5 11/32" 7' - 5 11/32" 7' - 5 11/32" 7' - 5 11/32"

(2270) (2270) (2270) (2270)3' - 1/4" 3' - 1/4" 3' - 1/4" 3' - 1/4"

(921) (921) (921) (921)10" 8" 10" 8"

(254) (203) (254) (203)2' - 1 1/2" 2' - 1 1/2" 2' - 1 1/2" 2' - 1 1/2"

(648) (648) (648) (648)12" 12" 12" 12"

(300) (300) (300) (300)

Weight - pounds (kg)) except WaterboxesCompressor/Motor 6800 6800 6800 6800

(3084) (3084) (3084) (3084)Evaporator 5461 5834 5461 5834

(2477) (2643) (2477) (2643)Condenser 3937 4763 3937 4763

(1786) (2161) (1786) (2161)Economizer 799 799 799 799

(362) (362) (362) (362)Starter Panel 542 542 542 542

(246) (246) (246) (246)Control Panel 70 70 70 70

(318) (318) (318) (318)2745 2745 2745 2745

(1245) (1245) (1245) (1245)24140 24140 24140 24140

(10950) (10950) (10950) (10950)28344 28344 28344 28344

(12857) (12857) (12857) (12857)Operational Data

625 417 566 378(39) (26) (36) (24)

2501 1529 1493 995(158) (97) (94) (63)

682 682 668 668(43) (43) (42) (42)

2501 2501 2450 2450(158) (258) (155) (155)

Evaporator WaterPass

Evaporator WaterConnection (NPS)

Condenser NominalConnector Size (NPS)

Miscellaneous Item

MinimumEvaporator Flow ingpm (l/sec)MaximumEvaporator Flow ingpm (l/sec)MinimumCondenser Flow ingpm (l/sec)MaximumCondenser Flow ingpm (l/sec)

Tube OutsideDiameter (inch)

Evaporator InsideDiameter

CondenserInside Diameter

Shipping Weight

Operating Weight

Page 19: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4 19

GeneralInformation

Table 3. General data: 650 ton units (continued)Nominal Tonnage 650

1.0 0.75

Two Three Two Three

Water Volume - 150 pound Waterboxes163.2 158.2 154.1 149.1(618) (599) (583) (564)185.1 185.1 188.5 188.5(701) (701) (714) (714)

Evaporator 2-pass WeightSupply - pound 304 304 304 304

(kg) (138) (138) (138) (138)Return - pound 337 337 337 337

(kg) (153) (153) (153) (153)Evaporator 3-pass WeightSupply - pound 314 314 314 314

(kg) (142) (142) (142) (142)Return - pound 332 332 332 332

(kg) (151) (151) (151) (151)Condenser 2-pass WeightSupply - pound 304 304 304 304

(kg) (138) (138) (138) (138)Return - pound 341 341 341 341

(kg) (155) (155) (155) (155)300 pound Waterboxes

163.2 158.2 154.1 149.1(618) (599) (583) (564)185.1 185.1 189.4 189.4(701) (701) (717) (717)

Evaporator 2-pass WeightSupply - pound 427 427 427 427

(kg) (194) (194) (194) (194)Return - pound 446 446 446 446

(kg) (202) (202) (202) (202)Evaporator 3-pass WeightSupply - pound 448 448 448 448

(kg) (203) (203) (203) (203)Return - pound 448 448 448 448

(kg) (203) (203) (203) (203)Condenser 2-pass WeightSupply - pound 421 421 421 421

(kg) (191) (191) (191) (191)Return - pound 436 436 436 436

(kg) (198) (198) (198) (198)

Evaporator WaterStorage gallon (l)Condenser WaterStorage gallon (l)

Evaporator WaterStorage (gallon (l))Condenser WaterStorage gallon (l)

Evaporator Water Pass

Tube OutsideDiameter (inch)

Page 20: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E420

GeneralInformation

Table 4. General data: 700 ton familyNominal Tonnage 560 560 560 560 630 630 630 630

1.0 1.0 0.75 0.75 1.0 1.0 0.75 0.75

Two Three Two Three Two Three Two Three

875 875 875 875 925 925 925 925(397) (397) (397) (397) 420) (420) (420) (420)

15 15 15 15 15 15 15 15(56.8) (56.8) (56.8) (56.8) (56.8) (56.8) (56.8) (56.8)

Overall Dimensions - Feet-Inch (mm)Length 16'11" 16'11" 16'11" 16'11" 16'11" 16'11" 16'11" 16'11"

(5153) (5153) (5153) (5153) (5153) (5153) (5153) (5153)Width 6'10" 6'10" 6'10" 6'10" 6'10" 6'10" 6'10" 6'10"

(2075) (2075) (2075) (2075) (2075) (2075) (2075) (2075)Height 7'5" 7'5" 7'5" 7'5" 7'5" 7'5" 7'5" 7'5"

(2269) (2269) (2269) (2269) (2269) (2269) (2269) (2269)36-1/4" 36-1/4" 36-1/4" 36-1/4" 36-1/4" 36-1/4" 36-1/4" 36-1/4"(921) (921) (921) (921) (921) (921) (921) (921)10" 8" 10" 8" 10" 8" 10" 8"

(254) (203) (254) (203) (254) (203) (254) (203)

29-1/2" 29-1/2" 29-1/2" 29-1/2" 29-1/2" 29-1/2" 29-1/2" 29-1/2"(749) (749) (749) (749) (749) (749) (749) (749)12" 12" 12" 12" 12" 12" 12" 12"

(304) (304) (304) (304) (304) (304) (304) (304)

Weight- pound (kg) 150 Lb. Waterboxes6440 6440 6440 6440 6440 6440 6440 6440

(2921) (2921) (2921) (2921) (2921) (2921) (2921) (2921)5949 5949 6283 6283 5940 5940 6480 6480

(2698) (2698) (2850) (2850) (2694) (2694) (2939) (2939)4651 4651 5515 5515 4875 4875 5824 5824

(2110) (2110) (2502) (2502) (2211) (2211) (2642) (2642)904 904 904 904 904 904 904 904

(410) (410) (410) (410) (410) (410) (410) (410)542 542 542 542 542 542 542 542

(246) (246) (246) (246) (246) (246) (246) (246)70 70 70 70 70 70 70 70

(318) (318) (318) (318) (318) (318)) (318) (318)1216 1216 1216 1216 1216 1216 1216 1216(552) (552) (552) (552) (552) (552) (552) (552)1867 1891 1867 1891 1867 1891 1867 1891(847) (858) (847) (858) (847) (858) (847) (858)298 298 298 298 298 298 298 298

(135) (135) (135) (135) (135) (135) (135) (135)22,024 22,048 23,222 23,246 22,239 22,263 23,728 23,750(9990) (10001) (10553) (10544) (10541) (10552) (10763) (10773)2608 2575 2519 2486 2809 2776 2689 2656

(1183) (1168) (1143) (1128) (1274) (1259) (1220) (1205)997 997 997 997 1047 1047 1047 1047

(452) (452) (452) (452) (475) (475) (475) (475)25,629 25,620 26,738 26,729 26,095 26,086 27,464 27,453(11625) (11621) (12128) (12124) (11836) (11832) (12457) (12452)

Evaporator WaterConnection size(NPS)

Condenser NominalConnector size(NPS)

Economizer weight

Starter panelweightControl panelweightI/C Piping andSupports Waterboxes

Miscellaneous Item

Total ShippingWeight Total WaterVolume Refrigerant and Oil

Total Weight

Evaporator WaterPass

Evaporator InsideDiameter

Condenser InsideDiameter

CompressorweightEvaporator weight

Condenser weight

Tube OutsideDiameter (inch)

Refrigerant Charge- pounds (kg)Oil charge -gallons (l)

Page 21: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4 21

GeneralInformation

Table 4. General data: 700 ton family (continued)Nominal Tonnage 560 560 560 560 630 630 630 630

1.0 1.0 0.75 0.75 1.0 1.0 0.75 0.75

Two Three Two Three Two Three Two Three

Operational Data625 417 566 378 706 471 628 419

(39.4) (26.3) (35.7) (23.8) (44.5) (29.7) (39.6) (26.4)2293 1529 2077 1385 2581 1726 2304 1536

(144.6) (96.4) (131) (87.4) (162.8) (108.9) (145.3) (96.9)682 682 668 668 764 764 744 744(43) (43) (42.1) (42.1) (48.2) (48.2) (47) (47)2501 2501 2450 2450 2801 2801 2727 2727

(157.7) (157.7) (154.5) (154.5) (176.7) (176.7) (172) (172)150 pound waterboxes

150.7 146.4 141.8 137.5 162.7 158.4 151 146.7(570.4) (554.2) (537) (520.5) (616) (600) (572) (555.3)162.8 162.8 161 161 174.9 174.9 172.2 172.2

(616.3) (616.3) (609.5) (609.5) (662.1) (662.1) (652) (652)

Evaporator 2-pass WeightSupply - pound 492.7 492.7 492.7 492.7 492.7 492.7 492.7 492.7

(kg) (223.5) (223.5) (223.5) (223.5) (223.5) (223.5) (223.5) (223.5)Return - pound 435.2 435.2 435.2 435.2 435.2 435.2 435.2 435.2

(kg) (197.4) (197.4) (197.4) (197.4) (197.4) (197.4) (197.4) (197.4)Evaporator 3-pass WeightSupply - pound 476.6 476.6 476.6 476.6 476.6 476.6 476.6 476.6

(kg) (216.2) (216.2) (216.2) (216.2) (216.2) (216.2) (216.2) (216.2)Return - pound 478.9 478.9 478.9 478.9 478.9 478.9 478.9 478.9

(kg) (217.2) (217.2) (217.2) (217.2) (217.2) (217.2) (217.2) (217.2)Condenser 2-pass WeightSupply - pound 500.2 500.2 500.2 500.2 500.2 500.2 500.2 500.2

(kg) (226.9) (226.9) (226.9) (226.9) (226.9) (226.9) (226.9) (226.9)Return - pound 437.6 437.6 437.6 437.6 437.6 437.6 437.6 437.6

(kg) (198.5) (198.5) (198.5) (198.5) (198.5) (198.5) (198.5) (198.5)300 pound Waterboxes

151 146.6 142.1 137.7 163 158.6 151.3 146.9(571.6) (554.9) (537.9) (521.3) (617) (600.4) (572.7) (556.1)163.4 163.4 161.6 161.6 175.5 175.5 172.8 172.8

(618.5) (618.5) (611.7) (611.7) (664.3) (664.3) (654.1) (654.1)Evaporator 2-pass WeightSupply - pound 625.9 625.9 625.9 625.9 625.9 625.9 625.9 625.9

(kg) (283.9) (283.9) (283.9) (283.9) (283.9) (283.9) (283.9) (283.9)Return - pound 590.5 590.5 590.5 590.5 590.5 590.5 590.5 590.5

(kg) (267.8) (267.8) (267.8) (267.8) (267.8) (267.8) (267.8) (267.8)Evaporator 3-pass WeightSupply - pound 624.9 624.9 624.9 624.9 624.9 624.9 624.9 624.9

(kg) (283.4) (283.4) (283.4) (283.4) (283.4) (283.4) (283.4) (283.4)Return - pound 627.2 627.2 627.2 627.2 627.2 627.2 627.2 627.2

(kg) (284.5) (284.5) (284.5) (284.5) (284.5) (284.5) (284.5) (284.5)Condenser 2-pass WeightSupply - pound 625.1 625.1 625.1 625.1 625.1 625.1 625.1 625.1

(kg) (283.5) (283.5) (283.5) (283.5) (283.5) (283.5) (283.5) (283.5)Return - pound 594.4 594.4 594.4 594.4 594.4 594.4 594.4 594.4

(kg) (269.6) (269.6) (269.6) (269.6) (269.6) (269.6) (269.6) (269.6)

Minimum EvaporatorFlow GPM (l/s)Maximum EvaporatorFlow GPM (l/s)Minimum CondenserFlow GPM (l/s)Maximum CondenserFlow GPM (l/s)

Evaporator WaterStorage gallons (l)Condenser WaterStorage gallons (l)

Evaporator WaterStoragegallons (l)Condenser WaterStorage gallons (l)

Evaporator WaterPass

Tube Outside Diameter(inch)

Page 22: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E422

GeneralInformation

Table 4. General data: 700 ton family (continued)Nominal Tonnage 700

1.0 0.75

Two Three Two Three

975 975 975 975 (442) (442) (442) (442)

15 15 15 15(56.8) (56.8) (56.8) (56.8)

Overall Dimensions - Feet-Inch (mm)Length 16'11" 16'11" 16'11" 16'11"

(5153) (5153) (5153) (5153)Width 6'10" 6'10" 6'10" 6'10"

(2075) (2075) (2075) (2075)Height 7'5" 7'5" 7'5" 7'5"

(2269) (2269) (2269) (2269)36-1/4" 36-1/4" 36-1/4" 36-1/4"(921) (921) (921) (921)10" 8" 10" 8"

(254) (203) (254) (203)

29-1/2" 29-1/2" 29-1/2" 29-1/2"(749) (749) (749) (749)12" 12" 12" 12"

(304) (304) (304) (304)

Weight- pound (kg) 150 Lb. Waterboxes6440 6440 6440 6440

(2921) (2921) (2921) (2921)6320 6320 6701 6701

(2867) (2867) (3040) (3040)5077 5077 6122 6122

(2303) (2303) (2777) (2777)904 904 904 904

(410) (410) (410) (410)542 542 542 542

(246) (246) (246) (246)70 70 70 70

(318) (318) (318) (318)1216 1216 1216 1216(552) (552) (552) (552)1867 1891 1867 1891(847) (858) (847) (858)298 298 298 298

(135) (135) (135) (135)22,821 22,845 24,247 24,271(10351) (10362) (10998) (11009)

2999 2966 2866 2833(1360) (1345) (1300) (1285)1097 1097 1097 1097(498) (498) (498) (498)

26,917 26,908 28,210 28,201(12209) (12205) (12796) (12792)

Evaporator WaterConnection size(NPS)

Condenser NominalConnector size(NPS)

Economizer weight

Starter panelweightControl panelweightI/C Piping andSupports Waterboxes

Miscellaneous Item

Total ShippingWeight Total Water Volume

Refrigerant and Oil

Total Weight

Evaporator WaterPass

Evaporator InsideDiameter

Condenser InsideDiameter

Compressor weight

Evaporator weight

Condenser weight

Tube Outside Diameter(inch)

Refrigerant Charge- pounds (kg)Oil charge - gallons (l)

Page 23: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4 23

GeneralInformation

Table 4. General data: 700 ton family (continued)Nominal Tonnage 700

1.0 0.75

Two Three Two Three

Operational Data784 523 698 465

(49.5) (33) (44) (29.3)2874 1916 2559 1706

(181.3) (120.9) (161.4) (107.6)838 838 816 816

(52.9) (52.9) (51.5) (51.5)3071 3071 2993 2993

(193.7) (193.7) (188.8) (188.8)150 pound waterboxes

174.4 170.1 161.5 157.2(660.2) (644) (611.3) (595.1)185.8 185.8 183 183

(703.3) (703.3) (693) (693)

Evaporator 2-pass WeightSupply - pound 492.7 492.7 492.7 492.7

(kg) (223.5) (223.5) (223.5) (223.5)Return - pound 435.2 435.2 435.2 435.2

(kg) (197.4) (197.4) (197.4) (197.4)Evaporator 3-pass WeightSupply - pound 476.6 476.6 476.6 476.6

(kg) (216.2) (216.2) (216.2) (216.2)Return - pound 478.9 478.9 478.9 478.9

(kg) (217.2) (217.2) (217.2) (217.2)Condenser 2-pass WeightSupply - pound 500.2 500.2 500.2 500.2

(kg) (226.9) (226.9) (226.9) (226.9)Return - pound 437.6 437.6 437.6 437.6

(kg) (198.5) (198.5) (198.5) (198.5)300 pound Waterboxes

174.7 170.3 161.8 157.4(661.3) (644.7) (612.5) (595.8)186.4 186.4 183.6 183.6

(705.6) (705.6) (695) (695)Evaporator 2-pass WeightSupply - pound 625.9 625.9 625.9 625.9

(kg) (283.9) (283.9) (283.9) (283.9)Return - pound 590.5 590.5 590.5 590.5

(kg) (267.8) (267.8) (267.8) (267.8)Evaporator 3-pass WeightSupply - pound 624.9 624.9 624.9 624.9

(kg) (283.4) (283.4) (283.4) (283.4)Return - pound 627.2 627.2 627.2 627.2

(kg) (284.5) (284.5) (284.5) (284.5)Condenser 2-pass WeightSupply - pound 625.1 625.1 625.1 625.1

(kg) (283.5) (283.5) (283.5) (283.5)Return - pound 594.4 594.4 594.4 594.4

(kg) (269.6) (269.6) (269.6) (269.6)

Minimum EvaporatorFlow GPM (l/s)Maximum EvaporatorFlow GPM (l/s)Minimum CondenserFlow GPM (l/s)Maximum CondenserFlow GPM (l/s)

Evaporator WaterStorage gallons (l)Condenser WaterStorage gallons (l)

Evaporator WaterStoragegallons (l)Condenser WaterStorage gallons (l)

Evaporator WaterPass

Tube OutsideDiameter (inch)

Page 24: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E424

Table 5. General data: 800 ton unitsNominal Tonnage 800

1.0 0.75

Two Three Two Three

Refrigerant Type R134a R134a R134a R134aRefrigerant Charge- 975 975 975 975pounds (kg) (442.3) (442.3) (442.3) (442.3)Oil Charge 15 15 15 15 gallon (l) (56.8) (56.8) (56.8) (56.8)Overall Dimensions - Feet-Inch (mm)Length 16' 16' 16' 16'

4877 4877 4877 4877Width 6' - 9 3/4" 6' - 9 3/4" 6' - 9 3/4" 6' - 9 3/4"

(2076) (2076) (2076) (2076)Height 7' - 5 11/32" 7' - 5 11/32" 7' - 5 11/32" 7' - 5 11/32"

(2270) (2270) (2270) (2270)3' - 1/4" 3' - 1/4" 3' - 1/4" 3' - 1/4"(9208) (9208) (9208) (9208)

10" 8" 10" 8"(250) (203) (250) (203)

2' - 5 1/2" 2' - 5 1/2" 2' - 5 1/2" 2' - 5 1/2"(749) (749) (749) (749)12" 12" 12" 12"

(305) (305) (305) (305)

Weight - pounds (kg) except WaterboxesCompressor/Motor 6800 6800 6800 6800

(3084) (3084) (3084) (3084) Evaporator 5835 6275 5835 6275

(2647) (2846) (2647) (2846) Condenser 4375 5400 4375 5400

(1985) (2449) (1985) (2449) Economizer 799 799 799 799

(362) (362) (362) (362) Starter Panel 542 542 542 542

(246) (246) (246) (246) Control Panel 70 70 70 70

(318) (318) (318) (318)Miscellaneous Item 2745 2745 2745 2745

(1245) (1245) (1245) (1245)Shipping Weight 25218 25218 25218 25218

(11439) (11439) (11439) (11439)Operating Weight 29924 29924 29924 29924

(13573) (13573) (13573) (13573)Operational Data

784 523 698 465 (50) (33) (44) (29)

3071 1916 1873 1248 (194) (121) (118) (79)

838 838 816 816(53) (53) (52) 52)

3071 3071 2993 2993(194) (194) (189) (189)

GeneralInformation

Tube Outside Diameter(Inch)Evaporator Water Pass

Evaporator InsideDiameterEvaporator WaterConnection (NPS) Condenser InsideDiameterCondenser NominalConnector Size (NPS)

Minimum EvaporatorFlow in gpm (l/sec)

Maximum EvaporatorFlow in gpm (l/sec)

Minimum CondenserFlow in gpm (l/sec)

Maximum CondenserFlow in gpm (l/sec)

Page 25: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4 25

GeneralInformation

Table 5. General data: 800 ton units (continued)Nominal Tonnage 800

1.0 0.75

Two Three Two Three

Water Volume - 150 pound Waterboxes190.4 185.4 177.4 172.4 (721) (702) (672) (653)213.5 213.5 218.0 218.0(808) (808) (828) (828)

Evaporator 2-pass WeightSupply - pound 303.57 303.57 303.57 303.57

(kg) (137.7) (137.7) (137.7) (137.7)Return - pound 337.16 337.16 337.16 337.16

(kg) (152.9) (152.9) (152.9) (152.9)Evaporator 3-pass WeightSupply - pound 313.56 313.56 313.56 313.56

(kg) (142.2) (142.2) (142.2) (142.2)Return - pound 331.72 331.72 331.72 331.72

(kg) (150.5) (150.5) (150.5) (150.5)Condenser 2-pass WeightSupply - pound 303.69 303.69 303.69 303.69

(kg) (137.8) (137.8) (137.8) (137.8)Return - pound 340.67 340.67 340.67 340.67

(kg) (154.5) (154.5) (154.5) (154.5)300 pound Waterboxes

190.4 185.4 177.4 172.4(721) (702) (672) (653)214.5 214.5 219.0 219.0(812) (812) (829) (829)

Evaporator 2-pass WeightSupply - pound 426.69 426.69 426.69 426.69

(kg) (193.5) (193.5) (193.5) (193.5)Return - pound 446.20 446.20 446.20 446.20

(kg) (202.4) (202.4) (202.4) (202.4)Evaporator 3-pass WeightSupply - pound 447.81 447.81 447.81 447.81

(kg) (203.1) (203.1) (203.1) (203.1)Return - pound 447.98 447.98 447.98 447.98

(kg) (203.2) (203.2) (203.2) (203.2)Condenser 2-pass WeightSupply - pound 421.43 421.43 421.43 421.43

(kg) (191.2) (191.2) (191.2) (191.2)Return - pound 436.11 436.11 436.11 436.11

(kg) (197.8) (197.8) (197.8) (197.8)

Evaporator Water Pass

Evaporator Water Storagegallon (l)Condenser Water Storagegallon (l)

Evaporator Water Storagegallon (l)Condenser Water Storagegallon (l)

Tube Outside Diameter(inch)

Page 26: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E426

GeneralInformation

Table 6. General data: 1000 ton familyBundle A A A A B B B B

1.0 1.0 0.75 0.75 1.0 1.0 0.75 0.75

Two Three Two Three Two Three Two ThreeOverall Dimensions - Feet-Inch (mm)Length 17' - 5 13/32" 17' - 5 13/32" 17' - 5 13/32"17' - 5 13/32" 17' - 5 13/32" 17' - 5 13/32" 17' - 5 13/32" 17' - 5 13/32"

(5320) (5320) (5320) (5320) (5320) (5320) (5320) (5320)Width 7' - 6 39/64" 7' - 6 39/64" 7' - 6 39/64" 7' - 6 39/64" 7' - 6 39/64" 7' - 6 39/64" 7' - 6 39/64" 7' - 6 39/64"

(2301) (2301) (2301) (2301) (2301) (2301) (2301) (2301)Height 8' - 4" 8' - 4" 8' - 4" 8' - 4" 8' - 4" 8' - 4" 8' - 4" 8' - 4"

(2540) (2540) (2540) (2540) (2540) (2540) (2540) (2540)3' 7 3/4" 3' 7 3/4" 3' 7 3/4" 3' 7 3/4" 3' 7 3/4" 3' 7 3/4" 3' 7 3/4" 3' 7 3/4"(1111) (1111) (1111) (1111) (1111) (1111) (1111) (1111)

12" 10" 12" 10" 12" 10" 12" 10"(305) (250) (305) (250) (305) (250) (305) (250)

2' - 11 1/4" 2' - 11 1/4" 2' - 11 1/4" 2' - 11 1/4" 2' - 11 1/4" 2' - 11 1/4" 2' - 11 1/4" 2' - 11 1/4"(895) (895) (895) (895) (895) (895) (895) (895)

14" 14" 14" 14" 14" 14" 14" 14"(356) (356) (356) (356) (356) (356) (356) (356)

Weight - pounds (kg) 150 pound Waterboxes9493 9493 9493 9493 9493 9493 9493 9493

(4306) (4306) (4306) (4306) (4306) (4306) (4306) (4306)7537 7537 8190 8190 7787 7787 8474 8474

(3419) (3419) (3715) (3715) (3532) (3532) (3844) (3844)6571 6571 7707 7707 6816 6816 8148 8148

(2981) (2981) (3496) (3496) (3092) (3092) (3696) (3696)1461 1461 1461 1461 1461 1461 1461 1461(663) (663) (663) (663) (663) (663) (663) (663)

Evaporator Water pass

Evaporator WaterConnection size (NPS)

Condenser NominalConnector size (NPS)

Compressorweight Evaporator weight

Condenser weight

Economizer weight

Condenser InsideDiameter

Tube OutsideDiameter (inch)

Evaporator InsideDiameter

Page 27: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4 27

GeneralInformation

Table 6. General data: 1000 ton family (continued)Bundle C C C C D D D D

1.0 1.0 0.75 0.75 1.0 1.0 0.75 0.75

Two Three Two Three Two Three Two ThreeOverall Dimensions - Feet-Inch (mm)Length 17' - 5 13/32" 17' - 5 13/32" 17' - 5 13/32" 17' - 5 13/32" 17' - 5 13/32" 17' - 5 13/32" 17' - 5 13/32" 17' - 5 13/32"

(5320) (5320) (5320) (5320) (5320) (5320) (5320) (5320)Width 7' - 6 39/64" 7' - 6 39/64" 7' - 6 39/64" 7' - 6 39/64" 7' - 6 39/64" 7' - 6 39/64" 7' - 6 39/64" 7' - 6 39/64"

(2301) (2301) (2301) (2301) (2301) (2301) (2301) (2301)Height 8' - 4" 8' - 4" 8' - 4" 8' - 4" 8' - 4" 8' - 4" 8' - 4" 8' - 4"

(2540) (2540) (2540) (2540) (2540) (2540) (2540) (2540)3' 7 3/4" 3' 7 3/4" 3' 7 3/4" 3' 7 3/4" 3' 7 3/4" 3' 7 3/4" 3' 7 3/4" 3' 7 3/4"(1111) (1111) (1111) (1111) (1111) (1111) (1111) (1111)

12" 10" 12" 10" 12" 10" 12" 10"(305) (250) (305) (250) (305) (250) (305) (250)

2' - 11 1/4" 2' - 11 1/4" 2' - 11 1/4" 2' - 11 1/4" 2' - 11 1/4" 2' - 11 1/4" 2' - 11 1/4" 2' - 11 1/4"(895) (895) (895) (895) (895) (895) (895) (895)

14" 14" 14" 14" 14" 14" 14" 14"(356) (356) (356) (356) (356) (356) (356) (356)

Weight - pounds (kg) 150 pound Waterboxes9493 9493 9493 9493 9493 9493 9493 9493

(4306) (4306) (4306) (4306) (4306) (4306) (4306) (4306)7537 7537 8190 8190 7787 7787 8474 8474

(3419) (3419) (3715) (3715) (3532) (3532) (3844) (3844)6571 6571 7707 7707 6816 6816 8148 8148

(2981) (2981) (3496) (3496) (3092) (3092) (3696) (3696)1461 1461 1461 1461 1461 1461 1461 1461(663) (663) (663) (663) (663) (663) (663) (663)

Evaporator Water pass

Evaporator WaterConnection size (NPS)

Condenser NominalConnector size (NPS)

Compressorweight Evaporator weight

Condenser weight

Economizer weight

Condenser InsideDiameter

Tube OutsideDiameter (inch)

Evaporator InsideDiameter

Page 28: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E428

GeneralInformation

Table 6. General data: 1000 ton family (continued)Bundle A A A A B B B B

1.0 1.0 0.75 0.75 1.0 1.0 0.75 0.75

Two Three Two Three Two Three Two Three

542 542 542 542 542 542 542 542(246) (246) (246) (246) (246) (246) (246) (246)

70 70 70 70 70 70 70 70(318) (318) (318) (318) (318) (318) (318) (318)

1430 1430 1439 1439 1430 1430 1439 1439(649) (649) (653) (653) (649) (649) (653) (653)

Waterboxes 3222 3274 3222 3274 3222 3274 3222 3274pound (kg) (1461) (1485) (1461) (1485) (1461) (1485) (1461 (1485)

520 520 520 520 520 520 520 520(236) (236) (236) (236) (236) (236) (236) (236)

30933 30985 32731 32783 31428 31480 33456 33508(14031) (14055) (14846) (14870) (14256) (14279) (15175) (15199)

3797 3745 3867 3816 4059 4008 4136 4085(1722) (1699) (1754) (1731) (1841) (1818) (1876) (1853)

1347 1347 1347 1347 1397 1397 1397 1397(611) (611) (611) (611) (634) (634) (634) (634)

36077 36077 37945 37946 36884 36885 38989 38990(16364) (16364) (17212) (17212) (16730) (16731) (17685) (17686)

Starter panel -pound (kg)

Evaporator Waterpass

Control panel -pound (kg)

I/C Piping andSupports - pound(kg)

MiscellaneousItem - pound (kg)

Total WaterVolume - pound(kg)Refrigerant andOil - pound (kg)

Total Shipping -pound (kg)

Tube OutsideDiameter (inch)

Total Weight -pound (kg)

Page 29: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4 29

GeneralInformation

Table 6. General data: 1000 ton family (continued)Bundle C C C C D D D D

1.0 1.0 0.75 0.75 1.0 1.0 0.75 0.75

Two Three Two Three Two Three Two Three542 542 542 542 542 542 542 542

(246) (246) (246) (246) (246) (246) (246) (246)

70 70 70 70 70 70 70 70(318) (318) (318) (318) (318) (318) (318) (318)

1430 1430 1439 1439 1430 1430 1439 1439(649) (649) (653) (653) (649) (649) (653) (653)

3222 3274 3222 3274 3222 3274 3222 3274(1461) (1485) (1461) (1485) (1461) (1485) (1461) (1485)

520 520 520 520 520 520 520 520(236) (236) (236) (236) (236) (236) (236) (236)

32101 32153 34189 34241 32639 32691 34656 34708(14561) (14584) (15508) (15531) (14805) (14828) (15720) (15743)

4405 4353 4411 4359 4686 4635 4599 4547(1998) (1974) (2001) (1977) (2126) (2102) (2086) (2062)

1447 1447 1447 1447 1497 1497 1497 1497(656) (656) (656) (656) (679) (679) (679) (679)

37953 37953 40047 40047 38822 38823 40752 40752(17215) (17215) (18165) (18165) (17609) (17610) (18484) (18485)

Starter panelweight - pound(kg)

EvaporatorWater pass

Control panelweight - pound(kg)I/C Piping andSupports - pound(kg)

MiscellaneousItem - pound (kg)

Total WaterVolume - pound(kg)Refrigerant andOil - pound (kg)

Total Shipping -pound (kg)

Tube OutsideDiameter (inch)

Waterboxes -pound (kg)

Total Weight -pound (kg)

Page 30: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E430

GeneralInformation

Table 6. General data: 1000 ton family (continued)Bundle A A A A B B B B

1.0 1.0 0.75 0.75 1.0 1.0 0.75 0.75

Two Three Two Three Two Three Two Three1225 1225 1225 1225 1275 1275 1275 1275(556) (556) (556) (556) (578) (578) (578) (578)

15 15 15 15 15 15 15 15(56.8) (56.8) (56.8) (56.8) (56.8) (56.8) (56.8) (56.8)781 521 822 548 896 598 921 614

(2956) (1972) (3112) (2074) (3392) (2264) (3486) (2324) 2864 1909 3013 2009 3287 2191 3377 2251

(10841) (7226) (11405) (7605) (12443) (8294) (12783) (8521)925 925 938 938 1020 1020 1056 1056

(3502) (3502) (3551) (3551) (3861) (3861) (3997) (3997)3391 3391 3441 3441 3741 3741 3874 3874

(12836) (12836) (13026) (13026) (14161) (14161) (14665) (14665)150 pound waterboxes

216.5 210.3 222.5 216.4 233.7 227.6 237.3 231.2(819.5) (796.1) (842.3) (819.2) (884.7) (861.6) (898.3) (875.2) 238.6 238.6 241 241 252.8 252.8 258.5 258.5

(903.2) (903.2) (912.3) (912.3) (957.0) (957.0) (978.5) (978.5)Evaporator 2-pass WeightSupply - pound 849.3 849.3 849.3 849.3 849.3 849.3 849.3 849.3

(kg) (385.2) (385.2) (385.2) (385.2) (385.2) (385.2) (385.2) (385.2)Return - pound 758.2 758.2 758.2 758.2 758.2 758.2 758.2 758.2

(kg) (343.9) (343.9) (343.9) (343.9) (343.9) (343.9) (343.9) (343.9)Evaporator 3-pass WeightSupply - pound 827.1 827.1 827.1 827.1 827.1 827.1 827.1 827.1

(kg) (375.2) (375.2) (375.2) (375.2) (375.2) (375.2) (375.2) (375.2)Return - pound 831.8 831.8 831.8 831.8 831.8 831.8 831.8 831.8

(kg) (377.3) (377.3) (377.3) (377.3) (377.3) (377.3) (377.3) (377.3)Condenser 2-pass WeightSupply - pound 854.2 854.2 854.2 854.2 854.2 854.2 854.2 854.2

(kg) (387.5) (387.5) (387.5) (387.5) (387.5) (387.5) (387.5) (387.5)Return - pound 760.8 760.8 760.8 760.8 760.8 760.8 760.8 760.8

(kg) (345.1) (345.1) (345.1) (345.1) (345.1) (345.1) (345.1) (345.1)300 pound Waterboxes

217 210.7 223.1 216.7 234.3 228 237.9 231.6(821.4) (797.6) (844.5) (820.3) (886.9) (863.1) (900.5) (876.7) 239.3 239.3 241.6 241.6 253.4 253.4 259.2 259.2

(905.8) (905.8) (914.6) (914.6) (959.2) (959.2) (981.2) (981.2)Evaporator 2-pass WeightSupply - pound 1041.7 1041.7 1041.7 1041.7 1041.7 1041.7 1041.7 1041.7

(kg) (472.5) (472.5) (472.5) (472.5) (472.5) (472.5) (472.5) (472.5)Return - pound 983.5 983.5 983.5 983.5 983.5 983.5 983.5 983.5

(kg) (446.1) (446.1) (446.1) (446.1) (446.1) (446.1) (446.1) (446.1)Evaporator 3-pass WeightSupply - pound 1041.7 1041.7 1041.7 1041.7 1041.7 1041.7 1041.7 1041.7

(kg) (472.5) (472.5) (472.5) (472.5) (472.5) (472.5) (472.5) (472.5)Return - pound 1045.7 1045.7 1045.7 1045.7 1045.7 1045.7 1045.7 1045.7

(kg) (474.3) (474.3) (474.3) (474.3) (474.3) (474.3) (474.3) (474.3)Condenser 2-pass WeightSupply - pound 1004.8 1004.8 1004.8 1004.8 1004.8 1004.8 1004.8 1004.8

(kg) (455.8) (455.8) (455.8) (455.8) (455.8) (455.8) (455.8) (455.8)Return - pound 986.1 986.1 986.1 986.1 986.1 986.1 986.1 760.8

(kg) (447.3) (447.3) (447.3) (447.3) (447.3) (447.3) (447.3) (447.3))Note: Immediately report any unit damage incurred during handling or installation at the job site to Trane sales office.

Refrigerant Oil charge -pound (kg)

Evaporator Waterpass

Oil charge -gallons (l)Mininum EvaporatorFlow - GPM (l/s)Maximum EvaporatorFlow - GPM (l/s)Minimum Condenserflow - GPM (l/s)Maximum Condenserflow - GPM (l/s)

Evaporator WaterStorage - gallons (l)Condenser WaterStorage - gallons (l)

Evaporator WaterStorage - gallons (l)Condenser WaterStorage - gallons (l)

Tube Outside Diameter(inch)

Page 31: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4 31

GeneralInformation

Table 6. General data: 1000 ton family (continued)Bundle C C C C D D D D

1.0 1.0 0.75 0.75 1.0 1.0 0.75 0.75

Two Three Two Three Two Three Two Three1325 1325 1325 1325 1375 1375 1375 1375 (601) (601) (601) (601) (624) (624) (624) (624)

15 15 15 15 15 15 15 15(56.8) (56.8) (56.8) (56.8) (56.8) (56.8) (56.8) (56.8)1003 669 1021 681 1115 744 1136 757

(3797) (2532) (3865) (2578) (4221) (2816) (4300) (2866)3678 2452 3745 2497 4090 2726 4165 2777

(13923) (9282) (14176) (9452) (15482) (10319) (15766) (10512))1192 1192 1176 1176 1307 1307 1213 1213

(4512) (4512) (4452) (4452) (4948) (4948) (4592) (4592)4372 4372 4311 4311 4792 4792 4447 4447

(16550) (16550) (16319) (16319) (18140) (18140) (16834) (16834)150 pound waterboxes

249.7 243.5 252.4 246.2 266.5 260.4 269.5 263.3(945.2) (921.7) (955.4) (932.0) (1009) (985.7) (1020) (996.7)278.3 278.3 276.3 276.3 295.2 295.2 281.8 281.8(1054) (1054) (1046) (1046) (1118) (1118) (1067) (1067)

Evaporator 2-pass WeightSupply - pound 849.3 849.3 849.3 849.3 849.3 849.3 849.3 849.3

(kg) (385.2) (385.2) (385.2) (385.2) (385.2) (385.2) (385.2) (385.2)Return - pound 758.2 758.2 758.2 758.2 758.2 758.2 758.2 758.2

(kg) (343.9) (343.9) (343.9) (343.9) (343.9) (343.9) (343.9) (343.9)Evaporator 3-pass WeightSupply - pound 827.1 827.1 827.1 827.1 827.1 827.1 827.1 827.1

(kg) (375.2) (375.2) (375.2) (375.2) (375.2) (375.2) (375.2) (375.2)Return - pound 831.8 831.8 831.8 831.8 831.8 831.8 831.8 831.8

(kg) (377.3) (377.3) (377.3) (377.3) (377.3) (377.3) (377.3) (377.3)Condenser 2-pass WeightSupply - pound 854.2 854.2 854.2 854.2 854.2 854.2 854.2 854.2

(kg) (387.5) (387.5) (387.5) (387.5) (387.5) (387.5) (387.5) (387.5)Return - pound 760.8 760.8 760.8 760.8 760.8 760.8 760.8 760.8

(kg) (345.1) (345.1) (345.1) (345.1) (345.1) (345.1) (345.1) (345.1)300 pound Waterboxes

250.2 243.9 252.9 246.6 267 260.7 270 263.7(947.1) (923.3) (957.3) (933.5) (1011) (986.9) (1022) (998.2)278.9 278.9 276.9 276.9 295.9 295.9 282.4 282.4(1056) (1056) (1048) (1048) (1120) (1120) (1069) (1069

Evaporator 2-pass WeightSupply - pound 1041.7 1041.7 1041.7 1041.7 1041.7 1041.7 1041.7 1041.7

(kg) (472.5) (472.5) (472.5) (472.5) (472.5) (472.5) (472.5) (472.5)Return - pound 983.5 983.5 983.5 983.5 983.5 983.5 983.5 983.5

(kg) (446.1) (446.1) (446.1) (446.1) (446.1) (446.1) (446.1) (446.1)Evaporator 3-pass WeightSupply - pound 1041.7 1041.7 1041.7 1041.7 1041.7 1041.7 1041.7 1041.7

(kg) (472.5) (472.5) (472.5) (472.5) (472.5) (472.5) (472.5) (472.5)Return - pound 1045.7 1045.7 1045.7 1045.7 1045.7 1045.7 1045.7 1045.7

(kg) (474.3) (474.3) (474.3) (474.3) (474.3) (474.3) (474.3) (474.3)Condenser 2-pass WeightSupply - pound 1004.8 1004.8 1004.8 1004.8 1004.8 1004.8 1004.8 1004.8

(kg) (455.8) (455.8) (455.8) (455.8) (455.8) (455.8) (455.8) (455.8)Return - pound 986.1 986.1 986.1 986.1 986.1 986.1 986.1 760.8

(kg) (447.3) (447.3) (447.3) (447.3) (447.3) (447.3) (447.3) (447.3)Note: Immediately report any unit damage incurred during handling or installation at the job site to Trane sales office.

Refrigerant Oil charge -pound (kg)

Evaporator Waterpass

Oil charge -gallons (l)Mininum EvaporatorFlow - GPM (l/s)Maximum EvaporatorFlow - GPM (l/s)Minimum Condenserflow - GPM (l/s)Maximum Condenserflow - GPM (l/s)

Evaporator WaterStorage - gallons (l)Condenser WaterStorage - gallons (l)

Evaporator WaterStorage - gallons (l)Condenser WaterStorage - gallons (l)

Tube Outside Diameter(inch)

Page 32: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

Location Requirements

Noise Considerations

• Locate the unit away fromsound-sensitive areas.

• Install the isolation pads orisolation springs under theunit.

• Use rubber boot-type isolatorsfor all water piping at the unit.

• Use flexible electrical conduitfor final connection to the UPC.

Note: Consult an acousticalengineer for critical applications.

Foundation

Provide rigid, non-warpingmounting pads or a concretefoundation of sufficient strengthand mass to support the chilleroperating weight (includingcompleted piping and fulloperating charges of refrigerant,oil and water).

Storage

If the chiller is to be stored for atleast one month prior toinstallation, observe thefollowing precautions:

• Do not remove the protectivecoverings from the electricalpanel.

• Store the chiller in a dry,vibration-free, secure area.

• At least every three months,attach a gauge to the servicevalve and manually check thepressure of dry nitrogen in therefrigerant circuit. If thepressure is below 5 psig (34kPa) at 70°F (20°C), call aqualified service organizationand the appropriate Trane salesoffice.

After the chiller is in place, levelthe chiller within 1/4" (6 mm)over its length and width.

Trane is not responsible forequipment problems resultingfrom an improperly designed orconstructed foundation.

Vibration Eliminators

• Use rubber boot-type isolatorsfor all water piping at the unit.

• Use flexible electrical conduitfor final connection to the UPC.

• Isolate all pipe hangers and besure they are not supported bymain structural beams thatcould introduce vibration intooccupied spaces.

• Make sure that the piping doesnot put additional stress on theunit.

Note: Do not use metal braided-type eliminators on the waterpiping. Metal braidedeliminators are not effective atthe frequencies at which the unitwill operate.

CVGF-SVN02B-E432

Installation:Mechanical

Page 33: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

Installation:Mechanical

CVGF-SVN02B-E4 33

Clearances

Provide enough space aroundthe unit to allow the installationand maintenance personnelunrestricted access to all servicepoints. Refer to submittaldrawings for the unitdimensions.

Allow adequate clearance forcondenser and compressorservicing. A minimum of 36"(914 mm) is recommended forcompressor service and toprovide sufficient clearance forthe opening of control paneldoors. Refer to Figures 4 and 5,Tables 7 and 8 for minimumclearances required forcondenser tube service. In allcases, local codes will takeprecedence over theserecommendations.

Notes: Required verticalclearance above the unit is 36"(914 mm). There should be nopiping or conduit located overthe compressor motor.

If the room configurationrequires a variance to theclearance dimensions, contactyour Trane sales officerepresentative.

Page 34: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E434

Installation:Mechanical

36" (914 mm)Recommended

clearance

Height

Width

18" (457 mm)Recommended

clearance

CL1/CL2 Length CL1/CL2

48" (1219 mm)Recommended

clearance

Table 7. Dimensions for figure 4

Clearance Tube PullFeet-Inch (mm)

Compressor Shell Size CL1 CL2 Length Height Width400-500 500 13' 11" 3' 7" 13' 5" 6' 11" 6' 6"

(4.235) (1.092) (4.083) (1.790) (1.984)560-700 700 13' 11" 3' 7" 13' 5" 6' 11" 6' 10"

(4.235) (1.092) (4.083) (1.790) (2.083)740-1000 1000 13' 11" 3' 7" 13' 5" 8' 4" 7' 6-3/4"

(4.235) (1.092) (4.083) (2.540) (2.305)Notes:CL1 at either end of the machine and is required for tube pull clearance.CL2 is always at the opposite end of the machine from CL1 and is required for service clearance.Add 14-5/8" (37.1 cm) on each end for the water box.

Unit Dimensions With UnitMounted Starters

Figure 4. Recommended operating and service clearances – Model CVGF with unit-mounted starters

Dimensions Feet-Inch (m-meters)

Page 35: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4 35

Installation:Mechanical

Figure 5. Recommended operating and service clearances – Model CVGF without unit-mounted starters

36" (914 mm)Recommended

clearance

Height

Width

18" (457 mm)Recommended

clearance

CL1/CL2 Length CL1/CL2

36" (914 mm)Recommended

clearance

Table 8. Dimensions for figure 5

Clearance Tube PullFeet-Inch (mm)

Compressor Shell Size CL1 CL2 Length Height Width400-500 500 13' 11" 3' 7" 13' 5" 6' 11" 6' 3"

(4.235) (1.092) (4.083) (1.790) (1.913)560-700 700 13' 11" 3' 7" 13' 5" 6' 11" 6' 7"

(4.235) (1.092) (4.083) (1.790) (2.028)740-1000 1000 13' 11" 3' 7" 13' 5" 8' 4" 7' 5"

(4.235) (1.092) (4.083) (2.540) (2.261)Notes:CL1 at either end of the machine and is required for tube pull clearance.CL2 is always at the opposite end of the machine from CL1 and is required for service clearance.Add 14-5/8" (37.1 cm) on each end for the water box.

Unit Dimensions Without UnitMounted Starters

Dimensions Feet-Inch (m-meters)

Page 36: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E436

Installation:Mechanical

Water Pipe Connections

Table 9 applies to all CVGFchiller tonnage sizes 500, 700and 1000.Refer to Table 9 for water pipeconnection sizing informationand evaporator and condenserwater pass information. Allmeasurement are in either USor metric equivalents.

Ventilation

The unit produces heat eventhough the compressor iscooled by the refrigerant. Makeprovisions to remove heatgenerated by unit operationfrom the equipment room.Ventilation must be adequate tomaintain an ambienttemperature lower than 122°F(50°C).

Vent the unit pressure reliefvalves in accordance with alllocal and national codes.

Make provisions in theequipment room to keep thechiller from being exposed tofreezing temperatures of 32°F(0°C).

Water Drainage

Locate the unit near a large-capacity drain for water vesseldrain-down during shutdown orrepair. Condensers andevaporators are provided withdrain connections. All local andnational codes apply.

Moving and Rigging

The Model CVGF chiller shouldbe moved by lifting atdesignated lift points only. Referto the rigging diagram that shipswith each unit for specific perunit weight data.

Table 9. Model CVGF water connection pipe size (mm)Shell Size

500 700 1000Water Passes

Nominal Pipe Size (inches) NPSEvaporator

2-pass 8" 10" 12" (DN200) (DN250) (DN300)

3-pass 8" 8" 10"(DN200) (DN200) (DN250)

Condenser

2-pass 10" 12" 14" (DN250) (DN300) (DN350)

�� WARNING

Heavy Objects!

Do not use cables (chains orslings) except as shown. Each ofthe cables (chains or slings)used to lift the unit must becapable of supporting the entireweight of the unit. Lifting cables(chains or slings) may not be ofthe same length. Adjust asnecessary for even unit lift.Other lifting arrangements maycause equipment or property-only damage. Failure to properlylift unit may result in death orserious injury. See detailsbelow:

• Follow the procedures anddiagrams in this manual and inthe submittal.

• Always use lifting equipmentwith a capacity exceeding theunit lifting weight by anadequate safety factor. (+10%).

Page 37: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4 37

5/16-3/8"(8-10 mm)

Installation:Mechanical

Chiller Isolation

To minimize sound and vibrationtransmission through thebuilding structure, and to assureproper weight distribution overthe mounting surface, installisolation pads or spring isolatorsunder the chiller feet.

Note: Isolation pads areprovided with each chiller unlessspring isolators are specified onthe sales order.

Specific isolator loading data isprovided in the until submittalpackage. Also refer to Table 10. Ifnecessary, contact your localTrane sales office for furtherinformation.

Isolation Pads

When the unit is ready for finalplacement, position isolationpads end-to-end under the fulllength of the chiller leg. Thepads measure 6" x 18" (152 x 457mm). See Figure 6. No gapsshould be present betweenpads.

Remember that the chiller mustbe level within 1/4" (6 mm) overits length and width after it islowered onto the isolation pads.In addition, all piping connectedto the chiller must be properlyisolated and supported so that itdoes not place any stress on theunit.

Spring Isolators

Spring isolators should beconsidered whenever chillerinstallation is planned for anupper-story location. Springisolator selection and placementinformation is presented inFigure 7 and Figure 8.

Note: Three types of springisolators, shown in Tables 11-13are used. Each type has its ownmaximum loadingcharacteristics.

Spring isolators are typicallyshipped assembled and readyfor installation. To install andadjust the isolators properly,follow the instructions given.

Note: Do not adjust the isolatorsuntil the chiller is piped andcharged with refrigerant andwater.

1. Position the spring isolatorsunder the chiller as shown inFigure 7 and Figure 9. Makesure that each isolator iscentered in relation to thetube sheet.

2. Set isolators on the sub-base;shim or grout them asnecessary to provide a flat,level surface as the sameelevation for all mountings. Besure to support the fullunderside of the isolator baseplate; no not straddle gaps orsmall shims.

3. If required, bolt the isolatorsto the floor through the slotsprovided, or cement the pads.

Note: fastening the isolatorsto the floor is not necessaryunless specified.

4. If the chiller must be fastenedto the isolators, insert capscrews through the chillerbase and into the holestapped in the upper housingof each isolator. Do not allowthe screws to protrude belowthe underside of the isolatorupper housing. An alternativemethod of fastening the chillerto the isolators is to cementthe neoprene pads.

5. Set the chiller on the isolators;refer to the "Rigging" sectionfor lifting instructions.

The weight of the chiller willforce the upper housing ofeach isolator down, perhapscausing it to rest on theisolator's lower housing.Figure 9 illustrates springisolator construction.

Figure 6. Isolation pad

Page 38: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E438

6. Check the clearance on eachisolator. If this dimension isless than 1/4" (6 mm) on anyisolator, use a wrench to turnthe adjusting bolt onecomplete revolution upward.

Repeat this operation until a1/4" (6 mm) clearance isobtained at all isolators.

7. After the minimum requiredclearance is obtained on eachof the isolators, level thechiller by turning the adjustingbolt on each of the isolatorson the low side of the unit. Besure to work from one isolatorto the next.

Remember that the chillermust be level to within 1/4" (6mm) over its length and widthand that clearance of eachisolator must be 1/4" (6 mm).

Figure 7. Chiller foot or isolator orientationSide View of Unit End View of Unit

Centertubesheetsupportleg

End oftube sheet

Outside edgeof tube sheet

Center of IsolatorSpring

Note: The spring isolator must becentered in relation to the tube sheet. Donot align the isolator with the flat part ofthe chiller foot, because the tube sheet isoften off-center.

Note: Place isolator near outside edge oftube sheet as shown.

Installation:Mechanical

Page 39: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4 39

Installation:Mechanical

CT-12 Spring Isolators

Free Height

1/4"(6.3mm)Acousticalnonskidneoprenepad (topandbottom)

(2) 1-B UNC Adjustingand Leveling Bolts

Figure 8. Typical spring isolator construction

CT-7 Spring Isolators

C-C Foundation Bolts

Free Height

Adjust isolator so that the upperhousing clears the lower housing by atleast 1/4" (6.3mm) and not more than 1/2"(12.7mm)

1/4" (6.3mm) Acoustical nonskidneoprene pad (top and bottom)

3/4" (19.0mm)10 UNC Adjusting and leveling bolt

Page 40: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E440

Installation:Mechanical

Table 11. Selected spring isolators – CVGF 500Deflection

inches (mm)CT-12-27 X10350665-030 9000 (4082) 1.06 (27) Orange A & CCT-12-28 X10350665-040 10800 (4898.8) 1.02 (26) Green B & D

Note: Each type CT-12 spring isolator has 12 springs.

Isolator typeand size

Trane Part#

Maximum Loadlbm (kg)

Spring ColorCoding

LocationUsed

Table 12. Selected spring isolators – CVGF 700Deflection

inches (mm)CT-7-31 X10350664-050 7700 (3492.7) 0.83 (21) Gray A, B, C, D

Note: Each type CT-7 spring isolator has 7 springs.

Isolator typeand size

Trane Part#

Maximum Loadlbm (kg)

Spring ColorCoding

LocationUsed

Table 13. Selected spring isolators – CVGF 1000Deflection

inches (mm)CT-12-28 X10350665-040 10000 (4535.9) 1.02 (26) Green ACT-12-31 X10350665-050 13200 (5987.4) 0.83 (21) Gray B, C, D

Note: Each type CT-12 spring isolator has 12 springs.

Isolator typeand size

Trane Part#

Maximum Loadlbm (kg)

Spring ColorCoding

LocationUsed

Figure 9. Load points - 500, 700 and 1000 ton families (reference table 10)

Condenser

Evaporator

Top View

A

B

C

D

Table 10. Isolation loads - 500, 700 and 1000 ton families (reference figure 9)

500 Ton Family 700 Ton Family 1000 Ton FamilyMaximum Load - Maximum Load - Maximum Load -

pound (kg) pound (kg) pound (kg)A 5905 (2679) 8388 (3805) 10750 (4846)B 7005 (3177) 9431 (4278) 12665 (5745)C 6090 (2762) 8991 (4078) 11500 (5216)D 7225 (3277) 10340 (4690) 13545 (6144)

LocationPoint

Page 41: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4 41

Installation:Mechanical

CVGF Rigging

1. Dimensions are in millimeters(mm). Figure 10.

�� WARNING

Heavy Objects!

Do not use cables (chains orslings) except as shown. Each ofthe cables (chains or slings)used to lift the unit must becapable of supporting the entireweight of the unit. Lifting cables(chains or slings) may not be ofthe same length. Adjust asnecessary for even unit lift.Other lifting arrangements maycause equipment or property-only damage. Failure to properlylift unit may result in death orserious injury. See details below.

1. Use a 3600 mm lifting beamand adjust the chains (cables)

for an even, level lift.

2. 900 mm recommendedclearance above highest point ofcompressor.

3. Attach safety chains or cablesas shown, and without tension.The safety chain is not used forlifting, but is there to preventthe unit from rolling.

4. More details weightinformation is available onrequest.

2. Each chain or cable used to liftthe unit must be capable ofsupporting the entire weightof the chiller.

3. Use a 3600 mm lifting beamand adjust the chains orcables for an even, level lift.

4. 900 mm recommendedclearance above highest pointof compressor.

5. Attach safety chains or cablesas shown in Figure 11, andwithout tension. The safetychain is not used for lifting,but is there to prevent the unitfrom rolling.

6. More detailed weightinformation is available uponrequest.

Figure 10. Rigging diagram with anchor holeand bolt detail

See anchor holedetail

MotorTerminal Box

ControlPanel

Optional unit-mountedstarter

Figure 11. Rigging diagram with safety chain placement

Anchor Bolt Detail

Nuts should not be tight.Leave 2 to 3 mm gap.

Unit mounting pad 13 mmthick (by Trane)

Vibration isolator (by Trane)

75 mm steel pipe

152 × 152 × 19 mmsteel plate

Concrete

To meetlocal codes

Recommended procedure to allow forthermal expansion. (Unless otherwisespecified, parts are furnished by thecustomer.)

Anchor Hole Detail

4 × 22 mmdiameter holes foranchoring the unit

Evaporatortubesheet

Dimensions are typical for each corner

Page 42: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E442

Installation:Mechanical

Water Pressure Drop Data

Pressure drop for CVGF 500 Condensers with 0.75 inch ODtubes and 2 pass waterboxes

Pre

ssu

re D

rop

(in

fee

t o

f w

ater

)

Flow (in GPM)

Pressure drop for CVGF 500 Evaporators with 0.75 inch ODtubes and 2 pass waterboxes

Pre

ssu

re d

rop

(in

fee

t o

f w

ater

)

Bundle C

Flow (in GPM)

Graph 1.

Graph 2.

Bundle A Bundle B

Bundle CBundle A Bundle B

Page 43: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4 43

Installation:Mechanical

Water Pressure Drop Data

Pressure drop for CVGF 500 Evaporators with 1.0 inch ODtubes and 2 pass waterboxes

Flow (in GPM)

Pressure drop for CVGF 500 Condensers with 1.0 inch ODtubes and 2 pass waterboxes

Pre

ssu

re d

rop

(in

fee

t o

f w

ater

)

Flow (in GPM)

Pre

ssu

re d

rop

(in

fee

t o

f w

ater

)

Graph 3.

Graph 4.

Bundle CBundle A Bundle B

Bundle CBundle A Bundle B

Page 44: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E444

Installation:Mechanical

Water Pressure Drop Data

Pressure drop for CVGF 700 Evaporators with 3/4 inch ODtubes and 2 pass waterboxes

Pre

ssu

re d

rop

(in

fee

t o

f w

ater

)

Flow (in GPM)

Pressure drop for CVGF 700 Condensers with 3/4 inch OD tubesand 2 pass waterboxes

Pre

ssu

re d

rop

(in

fee

t o

f w

ater

)

Flow (in GPM)

Graph 5.

Graph 6.

Bundle CBundle A Bundle B

Bundle CBundle A Bundle B

Page 45: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4 45

Installation:Mechanical

Water Pressure Drop Data

Pressure drop for CVGF 700 Evaporators with 3/4 inch ODtubes and 3 pass waterboxes

Pre

ssu

re d

rop

(in

fee

t o

f w

ater

)

Flow (in GPM)

Pressure drop for CVGF 700 Evaporators with 1.0 inch ODtubes and 2 pass waterboxes

Pre

ssu

re d

rop

(in

fee

t o

f w

ater

)

Flow (in GPM)

Graph 7.

Graph 8.

Bundle CBundle A Bundle B

Bundle CBundle A Bundle B

Page 46: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E446

Installation:Mechanical

Water Pressure Drop Data

Pressure drop for CVGF 700 Condensers with 1.0 inch OD tubesand 2 pass waterboxes

Pre

ssu

re d

rop

(in

fee

t o

f w

ater

)

Flow (in GPM)

Pressure drop for CVGF 700 Evaporators with 1.0 inch ODtubes and 3 pass waterboxes

Pre

ssu

re d

rop

(in

fee

t o

f w

ater

)

Flow (in GPM)

Graph 9.

Graph 10.

Bundle CBundle A Bundle B

Bundle CBundle A Bundle B

Page 47: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4 47

Installation:Mechanical

Water Pressure Drop Data

Pressure drop for CVGF 1000 Evaporators with 3/4 inch ODtubes and 2 pass waterboxes

Pre

ssu

re d

rop

(in

fee

t o

f w

ater

)

Flow (in GPM)

Pressure drop for CVGF 1000 Evaporators with 3/4 inch ODtubes and 3 pass waterboxes

Pre

ssu

re d

rop

(in

fee

t o

f w

ater

)

Flow (in GPM)

Graph 11.

Graph 12.

Bundle CBundle A Bundle B Bundle D

Bundle CBundle A Bundle B Bundle D

Page 48: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

Pressure drop for CVGF 1000 Condensers with 3/4 inch ODtubes and 2 pass waterboxes

CVGF-SVN02B-E448

Installation:Mechanical

Water Pressure Drop Data

Pre

ssu

re d

rop

(in

fee

t o

f w

ater

)

Flow (in GPM)

Pressure drop for CVGF 1000 Evaporators with 1.0 inch ODtubes and 2 pass waterboxes

Pre

ssu

re d

rop

(in

fee

t o

f w

ater

)

Flow (in GPM)

Graph 13.

Graph 14.

Bundle CBundle A Bundle B Bundle D

Bundle CBundle A Bundle B Bundle D

Page 49: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4 49

Installation:Mechanical

Pressure drop for CVGF 1000 Condensers with 1.0 inch ODtubes and 2 pass waterboxes

Water Pressure Drop Data

Pre

ssu

re d

rop

(in

fee

t o

f w

ater

)

Flow (in GPM)

Pressure drop for CVGF 1000 Evaporators with 1.0 inch ODtubes and 3 pass waterboxes

Pre

ssu

re d

rop

(in

fee

t o

f w

ater

)

Flow (in GPM)

Graph 15.

Graph 16.

Bundle CBundle A Bundle B Bundle D

Bundle CBundle A Bundle B Bundle D

Page 50: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E450

Installation:Mechanical

Evaporator PipingComponents

Note: Ensure that all pipingcomponents are between theshutoff valves, so that both thecondenser and the evaporatorcan be isolated.

Piping components include alldevices and controls used toprovide proper water-systemoperation and unit operatingsafety. These components andtheir general locations aredescribed below.

Entering Chilled-Water Piping• Air vents (to bleed air from

system)• Water pressure gauges

manifolded with shutoff valves• Pipe unions• Vibration eliminators (rubber

boots)• Shutoff (isolation) valves• Thermometers• Cleanout tees• Pipe strainer

Leaving Chilled-Water Piping• Air vents (to bleed air from

system)• Water pressure gauges

manifolded with shutoff valves• Pipe unions• Vibration eliminators (rubber

boots)• Shutoff (isolation) valves• Thermometers• Cleanout tees• Balancing valve• Pressure relief valve• Flow switch

CAUTION

Equipment damage!

To prevent evaporator damage,do not exceed 150 psig (1035kPa) evaporator water pressurefor standard water boxes. Themaximum pressure for high-pressure water boxes is 300 psig(2100 kPa). To prevent tubedamage by erosion, install astrainer in the evaporator waterinlet piping.

Connecting Groove Pipes

CAUTION

Piping damage!

To prevent damage to waterpiping, do not overtighten theconnections.

Note: Make sure that all piping isflushed and cleaned prior tostarting the unit.

CAUTION

Equipment damage!

To prevent equipment damage,bypass the unit if using an acidicflushing agent.

Vents and Drains

Install pipe plugs or ball valves,with National Pipe Thread (NPT)to water hose threadconnections, in evaporator andcondenser water box drain andvent connections before fillingthe water systems.

To drain water, remove the ventand drain plugs or open the ballvalves. Install an NPT connectorsin the drain connection, andconnect a hose to it.

Page 51: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4 51

Installation:Mechanical

Condenser PipingComponents

Piping components include alldevices and controls used toprovide proper water-systemoperation and unit operatingsafety. These components andtheir general locations are givenbelow.

Entering condenser-water piping• Air vents (to bleed air from

system)• Water pressure gauges

manifolded with shutoff valves• Pipe unions• Vibration eliminators (rubber

boots)• Shutoff (isolation) valves, one

per pass• Thermometers• Cleanout tees• Pipe strainer

Leaving condenser-water piping• Air vents (to bleed air from

system)• Water pressure gauges with

manifolded shutoff valves• Pipe unions• Vibration eliminators (rubber

boots)• Shutoff (isolation) valves, one

per pass• Thermometers• Cleanout tees• Balancing valve• Pressure relief valve• Flow switch

CAUTION

Condenser damage!

To prevent condenser damage,do not exceed 150 psig (1035kPa) water pressure forstandard water boxes. Themaximum pressure for high-pressure water boxes is 300 psig(2100 kPa).

To prevent tube damage, installa strainer in the condenserwater inlet piping.

To prevent tube corrosion,ensure that the initial water fillhas a balanced pH.

Water Treatment

CAUTION

Water Treatment!

Do not use untreated orimproperly treated water. Use ofuntreated or improperly treatedwater may result in equipmentdamage.

Using untreated or improperlytreated water in these units mayresult in inefficient operationand possible tube damage.

Consult a qualified water-treatment specialist todetermine whether treatment isneeded. The followingdisclamatory label is providedon each CVGF unit:

The use of improperly treated oruntreated water in thisequipment may result in scaling,erosion, corrosion, algae, orslime. The services of a qualifiedwater-treatment specialistshould be engaged to determinewhat treatment, if any, isadvisable. The Trane Companywarranty specifically excludesliability for corrosion, erosion, ordeterioration of Traneequipment. Trane assumes noresponsibility for the results ofthe use of untreated, improperlytreated, saline, or brackishwater.

Page 52: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E452

Installation:Mechanical

Figure 12. Typical thermometer, valving, and manifold pressure gauge set-up

Evaporatorwaterflow

Pressuredifferentialgauge

Thermometers Reliefvalve

Shutoffvalves

ManifoldFlowswitch

Reliefvalve

Condenserwater flow

Pressuredifferentialgauge

Thermometers

Shutoffvalves

ManifoldFlow switchIsolationvalves

Water Pressure Gaugesand Thermometers

Install field-suppliedthermometers and pressuregauges (with manifoldswhenever practical) as shown inFigure 12. Locate pressuregauges or taps in a straight runof pipe; avoid placement nearelbows, and so forth. Be sure toinstall the gauges at the sameelevation on each shell if theshells have opposite-end waterconnections.

To read manifolded waterpressure gauges, open one valveand close the other (dependingupon the reading desired). Thiseliminates errors resulting fromdifferently calibrated gaugesinstalled at unmatchedelevations.

Water Pressure-ReliefValves

CAUTION

Shell Damage!

Install a pressure-relief valve inboth the evaporator andcondenser water systems.Failure to do so could result inshell damage.

Install a water pressure-reliefvalve in one of the condenser,and one of the evaporator, waterbox drain connections, or on theshell side of any shutoff valve.Water vessels with close-coupled shutoff valves have ahigh potential for hydrostaticpressure buildup during a watertemperature increase. Refer toapplicable codes for pressure-relief valve installationguidelines.

Flow-Sensing Devices

Use field provided flow switchesor differential pressure switcheswith pump interlocks to sensesystem water flow. Flow switchlocations are schematicallyshown in Figure 12.

To provide chiller protection,install and wire flow switches inseries with the water pumpinterlocks, for both chilled-waterand condenser-water circuits(refer to the Installation Electricalsection). Specific connectionsand schematic wiring diagramsare shipped with the unit.

Page 53: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4 53

Installation:Mechanical

Flow switches must stop orprevent compressor operation ifeither system water flow dropsbelow the required minimumthat is shown on the pressuredrop curves. Follow themanufacturer’srecommendations for selectionand installation procedures.General guidelines for flowswitch installation are outlinedbelow.

• Mount the switch upright, witha minimum of 5 pipe diametersof straight, horizontal run oneach side.

• Do not install close to elbows,orifices, or valves.

Note: The arrow on the switchmust point in the direction of thewater flow.

• To prevent switch fluttering,remove all air from the watersystem

Note: The CH530 provides a six-second time delay on the flowswitch input before shuttingdown the unit on a loss-of-flowdiagnostic. If machineshutdowns persist, contact yourlocal Trane representative.

• Adjust the switch to open whenwater flow falls below nominal.Refer to the General Datatables for minimum flowrecommendations for specificwater-pass arrangements. Flowswitch contacts are closedwhen there is proof of waterflow.

Page 54: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E454

Installation:Mechanical

Refrigerant Pressure-ReliefValve Venting

�� WARNING

Possible refrigerantasphyxiation!

Relief valve venting must bevented outdoors. Refrigerant isheavier than air and willdisplace available oxygen tobreathe, causing asphyxiation orother health risks. Each chilleror Multiple chillers must havetheir own separate relief valvesand vent piping. Consult localregulations for any special relief-line requirements. Failure tovent relief valves outdoors couldresult in death and seriousinjury.

Note: Vent pipe size mustconform to the ANSI/ASHRAEStandard 15 for vent pipe sizing.All country, federal, state, andlocal codes take precedence overany suggestions stated in thismanual.

All relief valve venting is theresponsibility of the installingcontractor.

All CVGF units use evaporatorand condenser pressure-reliefvalves that must be vented tothe outside of the building.

Relief valve connection sizes andlocations are shown in the unitsubmittals. Refer to local codesfor relief valve vent line sizinginformation.

CAUTION

Do not exceed vent piping codespecifications. Failure to heedspecifications could result incapacity reduction, unit damage,and relief valve damage.

After the relief valve has opened,it will reclose when pressure isreduced to a safe level.

Note: Relief valves tend to leak ifthey have opened and must bereplaced.

Thermal Insulation

All CVGF units are available withoptional factory installedthermal insulation. If the unit isnot factory insulated, installinsulation over the areas withdesignated dotted lines in Figure13. Refer to Table 14 for typesand quantities of insulationrequired. All CVGF units comefrom the factory with oil sumpinsulation.

Notes: Refrigerant chargingvalves, water temperaturesensors, and drain and ventconnections, when insulated,must remain accessible forservice.

Use only water-base latex painton factory applied insulation.Failure to do so may result ininsulation shrinkage.

Note: Units in environmentswith higher humidity mayrequire additional insulation.

Page 55: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4 55

Table 14. Recommended insulation typesSquare Feet

Location Type (Square m)3/4" wall (19 mm) 160 (15)

3/4" wall (19 mm) 20 (2)

3/4" wall (19 mm) 10 (1)

Installation:Mechanical

Figure 13. Typical CVGF insulation requirements

Suction line pipe

Suction cover

Evaporator water boxEvaporator Evaporator water box

Oil sump casing Oil sumpcasing

Oil sump casing

Gear Housing – Front View

Gear Housing – Side View

Insulate where dotted lines are indicated.

Evaporator, waterboxes and tube sheets

Compressor suction elbow and suction cover

All components and piping on low side of system

Page 56: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E456

Installation:Electrical

All field-installed wiring mustconform to National ElectricCode (NEC) guidelines, as wellas to any applicable state andlocal codes. Be sure to satisfyproper equipment groundingrequirements per NEC.

All field-installed wiring must bechecked for proper terminations,and for possible shorts orgrounds.

Do not modify or cut enclosureto provide electrical access.Removable panels have beenprovided for this purpose.Modify these panels only; awayfrom enclosure. Refer toinstallation information shippedwith the starter or submittaldrawings.

CAUTION

TO AVOID DAMAGE TOSTARTER COMPONENTS,remove debris inside the starterpanel. Failure to do so maycause an electrical short thatseriously damages the startercomponents.

�� WARNING!

Rotating Components!

During installation, testing,servicing and troubleshooting ofthis product it may be necessaryto measure the speed ofrotating components. Have aqualified or licensed serviceindividual who has beenproperly trained in handlingexposed rotating components,perform these tasks. Failure tofollow all safety precautionswhen exposed to rotatingcomponents could result indeath or serious injury.

As you review this manual,along with the wiringinstructions presented in thissection, keep in mind that:

General Requirements

�� WARNING!

Live ElectricalComponents!

During installation, testing,servicing and troubleshooting ofthis product, it may benecessary to work with liveelectrical components. Have aqualified licensed electrician orother individual who has beenproperly trained in handling liveelectrical components performthese tasks. Failure to follow allelectrical safety precautionswhen exposed to live electricalcomponents could result indeath or serious injury.

Page 57: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4 57

Installation:Electrical

Power Supply Wiring

To assure that power supplywiring to the starter panel isproperly installed andconnected, review and follow theguidelines outlined below.

3-Phase Power Source

1. Verify that the starternameplate ratings arecompatible with the powersupply characteristics and withthe electrical data on the unitnameplate.

2. If the starter enclosure mustbe cut to provide electricalaccess, exercise care toprevent debris from fallinginside the enclosure. If thestarter cabinet has aremovable panel, be sure toremove the panel from theunit before drilling holes.

CAUTION

Damage to Startercomponents!

To avoid damage remove debrisinside the starter panel. Failureto do so may cause an electricalshort that seriously damages thestarter components.

3. Use copper conductors toconnect the 3-phase powersupply to the remote or unit-mounted starter panel.

CAUTION

Use Copper ConductorsOnly!

Unit terminals are not designedto accept other types ofconductors. Failure to usecopper conductors may result inequipment damage.

4. Size the power supply wiringin accordance with theMinimum Circuit Ampacity(MCA) shown on the unitnameplate.

(MCA = (RLA x 1.25) + ControlPower Load)

5. Make sure that the incomingpower wiring is properlyphased; each power supplyconduit run to the starter mustcarry the correct number ofconductors to ensure equalphase representation. SeeFigure 14.

6. As you install the powersupply conduit, make surethat this position does notinterfere with theserviceability of any of theunit components, nor withstructural members andequipment.

Also, assure that the conduit islong enough to simplify anyservicing that may be necessaryin the future (for example,starter removal).

Note: Use flexible conduit toenhance serviceability andminimize vibration transmission.

Circuit Breakers andFusible Disconnects

Size the circuit breaker or fusedisconnect in compliance withNEC or local guidelines.

Figure 14. Proper phasing for starter power supply wiring andconduit loading

Page 58: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E458

Installation:Electrical

Optional PFCCs

Power factor correctioncapacitors (PFCCs) are designedto provide power factorcorrection for the compressormotor. They are available as anoption.

Note: Remember that the PFCCnameplate voltage rating mustbe greater than or equal to thecompressor voltage ratingstamped on the unit nameplate.See Table 15 to determine whatPFCC is appropriate for eachcompressor voltage application.

CAUTION

Motor of safety overloaddamage!

PFCC must be wired into thestarter correctly. Failure to do somay cause misapplication ofthese capacitors and result in aloss of motor overloadprotection and subsequentlycause motor damage.

Table 15. PFCC design voltage sizing per compressor voltageapplication

PFCC Design Voltage Compressor Motor Rating(See Unit Nameplate)

480V/60 Hz 380V/60 Hz440V/60 Hz460V/60 Hz480V/60 Hz

600V/60 Hz 575V/60 Hz600V/60 Hz

2400V/60 Hz 2300V/60 Hz2400V/60 Hz

PFCC Rating Compressor Motor Rating(See Unit Nameplate)

480V/50 Hz 346V/50 HZ380V/50 HZ400V/50 Hz415V/50 Hz

4160V/60 Hz 3300V/60 Hz4160V/60 Hz6600V/60 Hz

4160V/50 Hz 3300V/50 Hz6600V/50 Hz

Figure 15. PFCC leads routed through overload current transformer

Line

PFCC

OverloadCurrentTransformer

MotorLoad

- OR -

Line

PFCC

OverloadCurrentTransformer

Motor Load

Note: See the attached wiring diagram for more detail.

Page 59: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4 59

Installation:Electrical

Interconnecting Wiring

Typical equipment room conduitlayouts with and without unit-mounted starters are shown inFigures 15 and 16, respectively.

IMPORTANT

Keep in mind that theinterconnecting wiring betweenthe starter panel, compressorand UCP control panel is factory-installed with unit-mountedstarters but must be field-installed when a remote-mounted starter is used.

Figure 16. Typical equipment room layout with unit-mounted, Wye-Delta

Line Side PowerConduits

Unit ControlPanel

Unit MountedStarter

Note: See Starter submittal drawing for location of incoming wiring to the starter.

Page 60: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E460

Installation:Electrical

Figure 17. Typical equipment room layout with remote-mountedWye-Delta starter

Line sidepowerwiring

Remote-mounted starter

Load powerwiring

115 Volt controlconduitSee Note 2

IPC circuitconduit <30VSee Note 3

Motor terminal box

Notes:

1. Refer to the unit field connection diagram for approximate UCPknockout locations.

2. 115-volt conduit must enter the higher than 30 Vdc Class I portionof the unit control panel.

3. IPC circuit conduit must enter the Low Voltage Class II portion ofthe UCP.

4. See starter submittal drawing for location of incoming wiring tothe starter.

Page 61: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4 61

Installation:Electrical

Starter to Motor (Remote-Mounted Starters Only)

Ground Wire Terminal Lugs Ground wire lugs are provided inthe motor terminal box and inthe starter panel.

Terminal Clamps Terminal clamps are suppliedwith the motor terminals toaccommodate either bus bars orstandard motor terminal wirelugs. Terminal clamps provideadditional surface area tominimize the possibility ofimproper electrical connections.

Wire Terminal LugsWire terminal lugs must be field-supplied.

1. Use field-provided crimp-typewire terminal lugs properlysized for the application.

Note: Wire size ranges for thestarter line and load-side lugsare listed on the startersubmittal drawings suppliedby the starter manufacturer orTrane. Carefully review thesubmitted wire lug sizes forcompatibility with theconductor sizes specified bythe electrical engineer orcontractor.

2. A terminal clamp with a 3/8"bolt is provided on eachmotor terminal stud; use thefactor-supplied Bellevillewashers on the wire lugconnections.

Figure 18 illustrates thejuncture between a motorterminal stud and terminalclamp.

3. Tighten each bolt to 24 foot-pounds.

4. Install but do not connect thepower leads between thestarter and compressor motor.(These connections will becompleted under supervisionof a qualified Trane serviceengineer after the prestartinspection).

CAUTION

Correct motor wireterminations!

Ensure the power supply wiringand output motor wiring areconnected to the properterminals. Failure to do so willcause catastrophic failure of thestarter and, or the motor.

Bus BarsInstall bus bars between themotor terminals when a low-voltage “across-the-line,”“primary reactor/resistor,” “autotransformer,” customer-suppliedsolid-state starter, or customer-supplied AFD are field applied.

Be sure to bus motor terminal T1to T6, T2 to T4, and T3 to T5.

Note: Bus bars are not needed inhigh-voltage applications sinceonly 3 terminals are used in themotor and starter.

Starter to UCP (Remote-Mounted Starters Only)

Electrical connections requiredbetween the remote-mountedstarter and the unit control panelare shown in an example of apoint-to-point starter-to-UCPconnection diagram as shown atthe end of the manual.

Note: Install control voltageconduit into control voltagesection of chiller control paneland starter panel. Do not routewith low voltage (30 volts)conduit wires.

When sizing and installing theelectrical conductors for thesecircuits, follow the guidelineslisted.

Unless otherwise specified use14 ga. wire for 120 V controlcircuits.

Page 62: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E462

Installation:Electrical

CAUTION

Damage to Startercomponents!

To avoid damage remove debrisinside the starter panel. Failureto do so may cause an electricalshort that seriously damagesthe starter components.

1. If the starter enclosure mustbe cut to provide electricalaccess, exercise care toprevent debris from fallinginside the enclosure.

2. Use only shielded twisted pairfor the interprocessorcommunication (IPC) circuitbetween the starter and theUCP on remote mountedstarters. Recommended wireis Beldon Type 8760, 18 AWGfor runs up to 1000 feet.

Note: The polarity of the IPCwire pair is critical for properoperation.

3. Separate low-voltage (lessthan 30V) wiring from the115V wiring by running eachin its own conduit.

4. As you route the IPC circuitout of the starter enclosure,make sure that it is at least 6"from all wires carrying ahigher voltage.

5. For UCP IPC shielded twistedpair wiring, the shield shouldbe grounded on one end onlyat UCP at 1X1-G. The otherend should be unterminatedand taped back on the cablesheath to prevent any contactbetween shield and ground.

6. Oil Pump Interlock - Allstarters must provide aninterlock (N.O.) contact withthe chiller oil pump connectedto the UCP at Terminals 1A-J2-7 and 1A9-J2-9.

The purpose of this interlock isto power the oil pump on thechiller in the event that a starterfailure, such as welded contacts,keeps the chiller motor runningafter the controller interrupts therun signal.

CAUTION

Electrical Noise!

Maintain at least 6 inchesbetween low-voltage (<30V) andhigh voltage circuits. Failure todo so could result in electricalnoise that may distort thesignals carried by the low-voltage wiring, including theIPC.

Page 63: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4 63

Installation:Electrical

Figure 18. Terminal stud, clamp and lug assembly

Bellevillewasher

3/8"* Bolt

Terminallugs

Bellevillewasher

Motorterminalstud

Terminalclamp

Front View

Mid VoltageRXL RATR RPIR CXL CATR CPIR

Page 64: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E464

Installation:Electrical

Optional Relay Circuits

Optional Control and OutputCircuits

Install various optional wiring asrequired by the owner’sspecifications.

Optional TracerCommunication Interface

This control options allows theunit control panel to exchangeinformation such as chillerstatus and operating set pointswith a Tracer system.

Figure 19 illustrates how such acommunication control networkmight appear.

Note: The circuit must be run inseparate conduit to preventelectrical noise interference.

Additional information about theTracer Communication optionsis published in the installationmanual and operator’s guidethat ships with the Tracer.

Unit Start-Up

All phases of initial unit start-upmust be conducted under thesupervision of a qualified localservice engineer. This includespressure testing, evacuation,electrical checks, refrigerantcharging, actual start-up andoperator instruction.

Advance notification is requiredto assure that initial start-up isscheduled as close to therequested date as possible.

Starter ModuleConfiguration

The starter LLID configurationsettings will be checked (andconfigured for Remote Starters)during start-up commissioning.To configurate starter module,and perform other starterchecks, it is recommended thatthe line voltage three phasepower be turned off and secured(locked out), and then a separatesource control power (115 Vac)be utilized to power up thecontrol circuit. To do this,remove control coil circuit fuse,typically 2F4, and then connectseparate source power cord tostarter terminal block 2X1-1 (H),2X1-2 (N), and Ground. Use theas-built starter schematic toassure correct fuse andterminals. Verify correct fuse isremoved, control circuitconnections are correct, thenapply the 115 Vac separatesource power to service thecontrols.

Forms Information

Samples of start-up andoperating forms along withother helpful forms are found inthe Operation Maintenancemanual which can be obtainedfrom the nearest Trane office.

It is recommended that theserviceman contact the localTrane office to obtain the mostrecent printing date of the form.The forms in the operation andmaintenance manual are onlycurrent at the time of printing ofthe manual.

After obtaining the most recentform, complete all theinformation and forward it toyour local Trane office.

Page 65: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

CVGF-SVN02B-E4 65

Installation:Electrical

Figure 19 – Illustrates communication control network to chiller units with CH530

R

Modem

Remote PCWorkstation

PC WorkstationNotebook PCWorkstation Database Server for

Multiple Sites

BCU

Modem

BuildingControl Unit

Chilled WaterSupply (CHW)

and ReturnWater

TemperatureSensors Chiller 1 Chiller 2

LAN

AI

BO

BO

ChilledWaterPump

CondenserWater Pump

Chilled WaterSupply (CHW)

and ReturnWater

TemperatureSensors

AI

BO

BO

ChilledWaterPump

CondenserWaterPump

Page 66: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4
Page 67: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4
Page 68: Installation Manual Gear-Driven Centrifugal Water- Cooled Liquid · PDF file · 2005-10-03Installation Manual Gear-Driven Centrifugal Water-Cooled Liquid Chillers X39640686020 CVGF-SVN02B-E4

Literature Order Number

File Number

Supersedes

Stocking Location

Trane has a policy of continuous product and product data improvement and reserves the right tochange design and specifications without notice. Only qualified technicians should perform theinstallation and servicing of equipment referred to in this publication.

Société Trane – Société Anonyme au capital de 41500 000 F – Siege Social: 1 rue des Amériques –88190 Golbey – France – Siret 306 050 188-00011 – RSC Epinal B 306 050 188Numéro d’identification taxe intracommunanutaire: FR 83 3060501888

TraneA business of American Standard Companieswww.trane.com

For more information contact your local Trane office or e-mail us at [email protected]

Literature Order Number

File Number

Supersedes

Stocking Location

CVGF-SVN02B-E4

SL-RF-CTV-CVGF-SVN02B-E4-604

CVGF-SVN02A-E4

La Crosse