27
s Installation / Operation / Maintenance Instructions 21-115532-001 PR4018-06 SUPERCEDES 21-115532-001 PR4018-05 www . ElectricalPartManuals . com

Installation /Operation / Maintenance Instructions · ungrounded system. (Figure 4B) Three regulators in closed delta on a three-phase ungrounded system. (Figure 4C) Handling. Type

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

  • sInstallation / Operation / Maintenance

    Instructions

    21-115532-001PR4018-06

    SUPERCEDES21-115532-001

    PR4018-05

    www

    . Elec

    tricalP

    artM

    anua

    ls . c

    om

  • INTRODUCTION............................................. 1Inspection for Damage in Shipment……….…. 1Special FeaturesPolarized Disconnect SwitchAnd Hinged Control Panel………….........…... 13Remote Mounting of Control Equipment…….. 13Vari-AMPTM Position Indicator………………... 13Operation at Less Than Rated Voltage….…… 14Forced Air Cooling……………………………... 15Subbase Assembly…………………………….. 15Parts ListMajor Components…………………………….. 16Position Indicator………………………………. 17Type TLG Dial Switch…………………….……. 18Type TLG Quick Break Mechanism………….. 19Type TLF Dial Switch………………………….. 20Type TLF Quick Break Mechanism………….. 21Bypass Arresters………………………………. 22Bushings………………………………………… 23

    Special FeaturesPolarized Disconnect SwitchAnd Hinged Control Panel……....………..…... 13Remote Mounting of Control Equipment…….. 13Vari-AMPTM Position Indicator………………... 13Operation at Less Than Rated Voltage….…… 14Forced Air Cooling……………………………... 15Subbase Assembly…………………………….. 15Parts ListMajor Components…………………………….. 16Position Indicator………………………………. 17Type TLG Dial Switch……….…………………. 18Type TLG Quick Break Mechanism………….. 19Type TLF Dial Switch………………………….. 20Type TLF Quick Break Mechanism………….. 21Bypass Arresters………………………………. 22Bushings………………………………………… 23

    TABLE OF CONTENTS

    Page Page

    For Emergency ServiceCall: 1-800-241-4453

    Siemens Power Transmission & Distribution, Inc.

    THESE INSTRUCTIONS DO NOT PURPORT TO COVER ALL DETAILS OR VARIATIONS IN EQUIPMENT, NOR TO PR VIDE FOR EVERYPOSSIBLE CONTINGENCY TO BE MET IN CONNECTION WITH INSTALLATION, OPERATION OR MAl TENANCE. SHOULD FURTHER INFOR-MATION BE DESIRED OR PROBLEMS ARISE WHICH ARE NOT COVERED SUFI CIENTLY FOR THE PURCHASER’S PURPOSES, THE MATTERSHOULD BE REFERRED TO YOUR SIEMENS POWE TRANSMISSION & DISTRIBUTION LLC REPRESENTATIVE.

    THE CONTENTS OF THIS INSTRUCTION MANUAL SHALL NOT BECOME PART OF OR MODIFY ANY PRIOR OR EXI~ ING AGREEMENT,COMMITMENT OR RELATIONSHIP. THE SALES CONTRACT CONTAINS THE ENTIRE OBLIGATION ( SIEMENS POWER TRANSMISSION &DISTRIBUTION LLC. THE WARRANTY CONTAINED IN THE CONTRACT BETWEE THE PARTIES IS THE SOLE WARRANTY OF SIEMENSPOWER TRANSMISSION & DISTRIBUTION LLC. ANY STAT MENTS CONTAINED HERON DO NOT CREATE NEW WARRANTIES OR MODIFYTHE EXISTING WARRANTY.

    www

    . Elec

    tricalP

    artM

    anua

    ls . c

    om

  • Page 1

    INTRODUCTION

    Type JFR single-phase step-voltage regulators are designedto give dependable service and to make installation, opera-tion and maintenance as simple as possible.

    Technology advances, especially in the realm of the controlapparatus, make it efficient to provide a separate instructionmanual for the Accu/StatTM control provided with this JFR Regu-lator. For specific control information, refer to the Accu/StatTMcontrol manual included with the regulator.

    QUALIFIED PERSON

    Is trained in the proper care and use of protectiveequipment such as rubber gloves, hard hat, safetyglasses or face shields, flash clothing, etc., in accordancewith established safety practices.

    (b)

    Is trained in rendering first aid.(c)

    (a)

    This equipment contains hazardous voltages. Se-vere personal injury or property damage can result ifsafety instructions are not followed.

    To prevent:

    Do not service or touch until you have de-energizedhigh voltage, grounded all terminals and turned offcontrol voltage. Grounding terminals with line toground capacitors may produce a small arc.

    Only qualitifed personnel should work on or aroundthis equipment after becoming thoroughly familiarwith all maintenance procedures contained herein.

    WARNING

    Indicates an imminently hazardous situa-tion which, if not avoided, will result in deathor serious injury

    DANGER

    Indicates a potentially hazardous situation,which, if not avoided, could result in deathor serious injury.

    WARNING

    Indicates a potentially hazardous situa-tion which, if not avoided, may result inminor or moderate injury.

    CAUTION

    FOR THE PURPOSE OF THIS MANUAL AND PRODUCTLABELS, A QUALIFIED PERSON IS ONE WHO IS FAMILIARWITH THE INSTALLATION, CONSTRUCTION AND OPERA-TION OF THE EQUIPMENT, AND THE HAZARDS INVOLVED.IN ADDITION, HE HAS THE FOLLOWING QUALIFICATIONS:

    Is trained and authorized to de-energize, clear, groundand tag circuits and equipment in accordance with es-tablished safety practices.

    Distinctive signal words (DANGER, WARNING, CAUTION) areused in this instruction book to indicate degrees of hazardthat may be encountered by the user. For the purpose of thismanual and product labels these signal words are definedbelow.

    www

    . Elec

    tricalP

    artM

    anua

    ls . c

    om

  • Page 2

    INTRODUCTION

    INSPECTION FORDAMAGE IN SHIPMENT

    Check each item with the shipping manifest immediatelyupon receipt of the regulator. Make a thorough visual in-spection of the regulator. Check for evidence of damageattributable to mishandling in shipment. Should any short-age or damage be found, notify the local agent of the carriermaking the delivery and make appropriate notation on thefreight bill. A claim should be made immediately with thecarrier. Siemens should be notified

    STORAGE PRIOR TOINSTALLATION

    The regulator may be stored without any particular pre-cautions or protection. Assure, however, that the controlcompartment enclosure is tightly closed.

    www

    . Elec

    tricalP

    artM

    anua

    ls . c

    om

  • Page 3INTRODUCTION

    DANGER

    Hazardous high voltage is present at the line terminalsof the bushings on the cover of the regulator.

    Will cause severe injury or death.

    To prevent:

    Isolate the regulator before servicing.

    Type JFR voltage regulators are routinely equipped with linebushing terminals per the following criteria.

    Clamp type terminals for use through 668 ampere arecapable of accepting an aluminum or copper conductor.

    Tank grounding provision consists of a 0.5-13NCtapped hole in a steel pad for regulators rated to 300amperes. Above 300 ampere ratings, a copper-facedpad with two 0.5-13NC tapped holes is provided.

    Type JFR regulators are commonly installed using anyof four electrical configurations.

    One regulator in single-phase application. (Figure 4D)

    Two regulators in open delta on a three-phaseungrounded system. (Figure 4B)

    Three regulators in closed delta on a three-phaseungrounded system. (Figure 4C)

    Handling. Type JFR regulators are designed to be liftedeither by a forklift at the base or by use of hangar bracketson the side of the tank. Each JFR regulator is providedwith either 2 or 4 lifting hooks on the side of the tank. Thenumber of hooks has been established to provide a mar-gin of safety on lifting when all hooks provided are used.

    PHYSICAL CONSIDERATIONS

    Location. Type JFR regulators are designed for outdoorinstallation. Any regulator may be platform or pedestalmounted. Regulators provided with hangar brackets aresuitable for pole mounting. When the regulator is to beinstalled in a substation on a pedestal it is recom-mended that a minimum elevation to the live connectionbe established, as required by applicable codes.

    Elevation. When the regulator will be used at an elevationabove 1000 meters (3300 feet) the kVA rating must bereduced to assure operating temperature limits are notexceeded.

    Falling unit can cause severe injury or damage.

    To prevent:

    Do not use cover lifting eyes tolift complete unit.Cover lifting eyes are for untanking of regulator only.

    Lift complete regulator by using all side tank hooks.

    WARNING

    For air cooled (OA) rating, derate kVA rating 0.4% for every100 meters (330 feet) elevation above 1000 meters.

    For forced air cooled (FA) rating, derate kVA rating 0.5% forevery 100 meters (330) feet elevation above 1000 meters.

    LINE TERMINALSAND CONNECTIONS

    Nameplate Line Current Rating

    50A to 300A 301A to 668A 669A to 1200A 1201 A to 2000A

    Conductor Size Range or Threaded Stud Size

    #2 to 477 MCM #2 to 800 MCM 1.125 - 12 UNF-2A 1.500 - 12 UNF-2A

    Three regulators in wye on a grounded-neutral three-phase system. (Figure 4D)

    ELECTRICAL CONSIDERATIONS

    Each of the four alternatives, when complete with switchingprovisions, will take the electrical configuration as shownon the next page.

    The descriptions 'S', 'L', and 'SL' are embossed into the coverfor user convenience at time of installation.ww

    w . E

    lectric

    alPar

    tMan

    uals

    . com

  • Page 4

    INSTALLATION DIAGRAMS

    INTRODUCTION

    (Figure 4A)

    (Figure 4B)

    (Figure 4B)

    (Figure 4D)

    www

    . Elec

    tricalP

    artM

    anua

    ls . c

    om

  • Page 5

    PROTECTIVE MEASURES

    Bypass Arrester. All JFR regulators are equipped with aproperly sized arrester, connected externally between the 'S'and 'L' line terminals. The arrester is provided to protect theseries winding of the regulator from line surges. Of itself,the bypass arrester does not provide lightning protection forthe regulator.

    Lightning Protection. The number of lightning arresters usedwill be a judgmental decision on the part of the user, consid-ering such factors as isokeraunic level and degree of risk ofdamage to be accepted. The minimum recommended light-ning protection consists of a properly sized arrester betweenthe 'S' or 'L' bushing and ground on a single phase or a wyeconnected system. A delta connection system requires theuse of two arresters to accomplish minimum protection lev-els. Additional protection can be obtained with the use ofarresters at both the 'S' and 'L' terminals in single phase orwye systems and on all three terminals on a delta system.

    For best results, install lightning arresters on the mountinglugs adjacent to the bushings near the top of the tank. Thelugs are 0.5 - 13NC located on 2.5 inch centers. Ground thearrester(s) and the regulator tank solidly to the same groundconnection. Be careful to keep the ground lead connectionsas short as possible.

    Thru Fault. Type JFR regulators are rated under condition ofthru-faults for twenty five times the OA rated current for 2seconds or 40 times the OA rated current for 0.8 second to amaximum of 20,000 amperes rms symmetrical. The faultcurrent may be asymmetrical to the extent that the peak ofthe first current loop is equal to 2.26 times the rms value ofthe current wave.

    The user is advised to provide for additional source imped-ance, bus sectionalizing or other means of limiting the avail-able thru-fault current if these criteria are exceeded at theinstallation

    CONTROL CONNECTIONS

    Many regulators can be used at several different nominalsystem voltages. It is therefore necessary to assure that theregulator is properly connected at the 19 pin upper terminalblock for the system voltage on which the particular regulatorwill be used.

    For this purpose, it is necessary to use the nameplatedrawing and control diagram found in the control enclosure.

    Refer to the Nameplate Diagram. A column is indicatedto connect lead P2 to P( ), based on the applicablesystem voltage. The control diagram will aid in identifi-cation of the appropriate pin on the 19-pin terminal block.

    1.

    Depending on the regulator, there may be a secondcolumn indicating that lead U2 is to be connected toU ( ). The same procedure is followed.

    2.

    For regulator equipped with fans for forced-aircooling, another set of connections will be shown.

    3.

    Matters specifically relating to the Accu/StatTM control used in conjuntions with theregulator are not included in this manual.Refer to the appropriate control instructionmanual.

    NOTE

    INTRODUCTION

    Figure 5A

    www

    . Elec

    tricalP

    artM

    anua

    ls . c

    om

  • Page 6

    CONNECTION DIAGRAMS

    www

    . Elec

    tricalP

    artM

    anua

    ls . c

    om

  • Page 7

    CONNECTION DIAGRAMS

    www

    . Elec

    tricalP

    artM

    anua

    ls . c

    om

  • Page 8

    CONNECTION DIAGRAMS

    www

    . Elec

    tricalP

    artM

    anua

    ls . c

    om

  • Page 9

    PLACING THE REGULATOR IN SERVICE

    The following checks will be useful in assuring the regulatoris ready for use. The list cannot be all inclusive; careful at-tention on the part of a qualified operator remains impera-tive.

    BEFORE CONNECTING

    Check oil level at oil sight window. If low, add sufficientoil (ASTM D-3487 Type II) to bring level to that desired.

    Check dielectric strength of the oil per ASTM D-877. Iffound to be below 24 kV, filtering should be accomplishedand additional testing of oil integrity is justified. Note:This is not necessary if regulator is being installed im-mediately upon receipt from the factory.

    Take power factor reading of all bushings (common)against ground (tank). Reading should be less that 2.0%.

    Verify from the nameplate that the unit is connected forthe proper output voltage, motor voltage and control panelvoltage.

    Assure that the regulator is on the neutral tap position.This should be accomplished by observing the positionindication pointer and by powering the control from a120V external source and observing the NeutraliteTM tobe illuminated.

    Identify 'S', 'L' and 'SL' bushings on the cover. Make elec-trical connections per the appropriate installation dia-grams, page 4, first connecting 'SL' bushing.

    Set Vari-AmpTM limits on position indicator, if necessary.See Page 11.

    Set Accu/StatTM Control as desired. See Accu/StatTM

    instruction manual

    SWITCHING THE REGULATOR"ON THE LINE"

    It is absolutely imperative that the regulator be on the neutraltap position before switching the regulator on the line.

    CONNECTING

    High pressure or mechanical failure due to improper by-pass operation can cause death, severe injury or damage.

    To prevent:

    Energize regulator only with regulator on neutral tap posi-tion.

    Follow instructions:

    1. Make certain regulator is in neutral (N) position.2. Turn voltage source switch to "OFF".3. Remove power fuse.4. Close, sequentially, the source and load switches.5. Open the bypass switch.6. Visually observe that bypass circuit has opened.7. Replace power fuse.8. Place voltage source switch to normal.

    WARNING

    CHECKING REGULATOROPERATION

    Turn the transfer switch to MANUAL.

    Run the tapchanger in the lower direction, at least untilthe control is observed to go out of band "LOW".

    Turn the transfer switch to AUTO. After a time delay, theregulator will return to an "IN" band condition.

    Turn the transfer switch to MANUAL.

    Run the tapchanger in the raise direction, at least untilthe control is observed to go out of band "HIGH".

    Turn the transfer switch to AUTO. After a time delay, theregulator will return to an "IN" band condition.

    (Refer to applicable Accu/StatTM Control instruction manual.)

    1.

    2.

    3.

    4.

    5.

    6.

    www

    . Elec

    tricalP

    artM

    anua

    ls . c

    om

  • Page 10

    REMOVING THE REGULATOR FROM SERVICE

    WARNINGHigh pressure or mechanical failure due to improper by-pass operation can cause death, severe injury or damage.

    To prevent:

    Bypass regulator only with regulator on neutral tap posi-tion.

    Follow instructions:

    REMOVING THE REGULATORFROM THE LINE

    In order to remove a regulator from service without droppingload, it is imperative that the regulator be on the neutral posi-tion. The system must first be de-energized (load dropped)before removal. If the regulator being removed is in a closeddelta bank, it is necessary to bypass and isolate all regula-tors in the bank. The routine removal procedure is essen-tially the reverse of the procedure used to place the regulatoron the line.

    Run the regulator under normal voltage source to theneutral position, as revealed by the tap position indica-tor.

    1.

    Confirm via the NeutraliteTM indicator that the regula-tor is on neutral. If the independent checks of the po-sition indicator and NeutraliteTM indicator do not con-firm the neutral position, bypassing must not be at-tempted. In such event, de-energize the system to re-move the regulator from service.

    2.

    After assuring that the regulator is on neutral, closethe bypass switch.

    Open, sequentially, the load and source switches.

    3.

    4.

    5.

    6. Exercise appropriate care in the removal of theregulator. High voltage will still be present at thebypass witch and the source and load switchterminals. Remove the ground connection last.

    (b.) For a closed delta connection, be sure all regula-tors in the bank are bypasses and isolated.

    (a.) For a single phase or grounded wye connection,make sure that the high voltage disconnect switchesare opened.

    www

    . Elec

    tricalP

    artM

    anua

    ls . c

    om

  • Page 11MAINTENANCE

    GENERAL INSTRUCTIONS

    Failure to properly maintain the regulator can result in se-vere personal injury and product failure. The instructionscontained herein should be carefully reviewed, understoodand followed. The following maintenance procedures shouldbe performed regularly:

    1. Operational checks

    • Control performance

    • Tapchanger performance

    • Vari-AmpTM limit performance.

    2. Periodic inspection

    • Oil sample

    • Oil oxidation inhibitor addition

    • Contact wear

    • Fans

    This checklist does not represent an exhaustive survey ofmaintenance steps necessary to ensure safe operation ofthe regulator. Particular applications may require further pro-cedures. Should further information be desired or shouldparticular problems arise which are not covered sufficientlyfor the purchaser’s purposes, the matter should be referredto the local Siemens sales representative.

    When powered, dangerous voltages are present in the equip-ment that can cause severe personal injury, death, and prod-uct failure. Always de-energize and ground the equipmentbefore maintenance requiring access to high voltage parts.

    The use of unauthorized parts in the repair of the equipment,tampering by unqualified personnel, or faulty repair and ad-justments will result in dangerous conditions which cancause severe personal injury or equipment damage. Followall safety instructions contained herein.

    OPERATIONAL CHECKS

    Basic regulator operation can be checked while the regula-tor remains in service. Simply provide means to observe theoutput voltage (such as a voltmeter connected at the testterminals).

    • Observe that the voltmeter reads the voltage level settingrequired by the control, to within one-half of the band-width tolerance. Note 1: The control must be “in” band.Note 2: Line drop compensation must be set to zero if theregulator is carrying load.

    • Run the tapchanger several steps in one direction in themanual mode until the output voltage is outside of thebandwidth. Return the control to automatic mode. Afterthe predetermined time delay, the tapchanger motor willbe observed to return the output voltage in-band. Repeatthis operation, running the tapchanger in the oppositedirection.

    • Check the Vari-AmpTM limit switches by attempting to runthe tapchanger beyond the position to which the switchesare set. The limit switches should function to open thecircuit. Note: If the limit switch is set at the maximum 10%range and fails to function, the tapchanger will stall againsta mechanical stop. The motor is designed to stall con-tinuously without damage

    CAUTION

    WARNING

    Operation of the regulator at extreme tap positionscould produce a line voltage above or below desiredoperating limits at the load.

    To prevent:

    Operate the regulator only to judiciously determinedvoltage extremes.

    Regulator may have High Internal Pressure. Cancause serious personal injury or death, or damage tothe regulator.

    To prevent:

    Use pressure relief valve to vent regulator beforeuntanking.

    www

    . Elec

    tricalP

    artM

    anua

    ls . c

    om

  • Page 12

    A sample of oil from the regulator should be subjected todielectric breakdown test, per ASTM D-877. It is recom-mended that oil testing less than 24 kV be filtered. Othertests, especially Neutralization Number, Interfacial Tensionand Power Factor are also useful and may be preferred byparticular users.

    The oxidation inhibitor in the oil will be depleted over a pe-riod of a few years and should be replaced. The inhibitor is2, 6-ditertiary-butyl-para-cresol (DBPC) at a concentrationlevel of 0.2 to 0.3%.

    The time interval between internal inspections will dependupon frequency of tapchanger operation and the load on theregulator. Regulators subjected to numerous overloads anda high load factor may require more frequent inspectionsthan those carrying normal loads. While internal inspectionis not a necessity, preventive maintenance inspections willhelp assure the continuity of service.

    PERIODIC INSPECTION

    If cover top cap is removed, make certain the cap is properlysealed when replaced on cover. Siemens recommends ap-plying pipe sealant (Loctite PST or equivalent) around thethreads of the adapter. Furthermore, it is recommended thatthe seal be tested by applying 5 psig pressure through thepressure relief valve fitting for 5 minutes, with no loss inpressure. Failure to assure seal may allow moisture to bepulled into the unit during a cool-down cycle.

    Remove the regulator from service as described on Page 7.

    Place the regulator in a position where energizedoverhead lines will not interfere.

    1.

    2.

    Operate pressure relief valve to vent regulator beforeuntanking

    3.

    Remove the three mounting bolts holding the controlbox onto the main tank.

    4.

    Loosen all cover bolts and turn outward 180 degrees.5.

    The regulator can now be pulled from the main tankby the cover lifting eyes.

    6.

    When inspecting, check to be certain all hardware and con-nections are tight. The principal point of the internal inspec-tion will be the condition of the arcing contacts on thetapchanger. Since numerous factors influence the rate ofcontact tip wear, no one criteria can be stated to recom-mend when a contact should be changed.

    The following figure shows the possible condition of con-tact wear after a period of operation. If a contact surface hasburned down so that only a 1/8 inch wide line contact arearemains, the contact will probably be giving adequate ser-vice at low contact temperatures, but much further deterio-ration will probably result in decreased spring pressure andpossibly faulty operation. Therefore, the contact should defi-nitely be replaced. (See Figure in next column.)

    Contacts, both movable and stationary, show normalburning and wear after 1,500,000 operations. If for anyreason A1 dimensions exceeds 4/5 of A, the stationarycontact should be replaced.

    SEALED REGULATORS WITHPRESSURE RELIEF VALVE

    To untank a JFR regulator, proceed as folllows:

    The fans used for cooling (on some regulators) require aminimum of attention. Fans with plain sleeve bearings orOil-Lite sleeve bearings should be oiled at least once ayear with a good grade of SAE 10-W mineral engine oilwhich does not thicken in cold weather. Oil must be addedto sleeve bearings before starting motor for the first timeafter installation.

    Fans equipped with ball bearing motors are packed withgrease before shipment and should be greased at leastonce a year with a soda-soap, ball-bearing grease of me-dium consistency furnished by a reliable supplier.

    For fans that are seldom used, the frequency for greasing oroiling may be less than outlined above, but it is recom-mended that this lubrication be placed on a yearly schedule.It is often possible to determine by inspection whether lubri-cation is required.

    • FANS

    MAINTENANCE

    www

    . Elec

    tricalP

    artM

    anua

    ls . c

    om

  • Page 13

    SPECIAL FEATURES

    The Accu/StatTM control panel is hinged and may be re-moved completely from the regulator control box by remov-ing the wing nuts on the polarized jack plug and pulling thejack from its fixed portion. This will automatically de-energizethe control. It is not necessary to bypass or de-energize theregulator to remove the control.

    A spring-loaded shorting bar in the plug automatically shortcircuits the current transformer secondary when the jack isremoved.

    The Accu/StatTM control may beremotely mounted. Remotecable is available in standardlengths of 18, 25 and 30 feetincorporating oil and moistureresistant, color-coded conduc-tors.

    REMOTE MOUNTINGOF CONTROLEQUIPMENT

    VARI-AMPTM POSITION INDICATOR

    The Vari-AmpTM feature provides a method of operating theregulator at increased load by decreasing the range of op-eration. It provides operator flexibility by allowing the range ofregulation to be adjusted in 1 1/4 percent increments. Thevarious regulation ranges together with the correspondingcurrent capacities for standard regulators are listed on page11. All that is necessary to adjust the range of regulationanywhere from ±5 percent to ±10 percent is to turn the ad-justing knobs until the proper range of regulation is shownon the side of the position indicator. The upper and lowerlimits need not be the same.It is not necessary to remove the regulator from service tomake this adjustment. The switches are, however, in themotor power circuit so the motor should not be running whilethe switches are being set.

    POLARIZED DISCONNECT SWITCH(JACK PLUG) AND HINGEDCONTROL PANEL

    www

    . Elec

    tricalP

    artM

    anua

    ls . c

    om

  • Page 14

    SPECIAL FEATURES

    CatalogNumber VARI-AMPTM RANGE AND CURRENT RATINGS AVAILABLEIncludes

    Voltage & kVA±10% ±83/4% ±71/2% ±61/4% ±5%

    10-02.5-050.0 200 220 240 270 32010-02.5-075.0 300 330 360 405 48010-02.5-100.0 400 440 480 540 64010-02.5-167.0 668 668 668 668 66810-02.5-250.0 1000 1000 1000 1000 100010-02.5-333.0 1332 1332 1332 1332 133211-02.5-416.3 1665 1665 1665 1665 1665

    10-05.0-050.0 100 110 120 135 16010-05.0-100.0 200 220 240 270 32010-05.0-167.0 334 367 401 451 53410-05.0-250.0 500 550 600 668 66810-05.0-333.0 668 668 668 668 66811-05.0-416.3 835 835 835 835 835

    10-07.6-038.1 50 55 60 68 8010-07.6-057.2 75 83 90 102 12010-07.6-076.2 100 110 120 135 16010-07.6-114.3 150 165 180 203 24010-07.6-167.0 219/232 241/255 263/278 296/313 351 /37110-07.6-250.0 328/347 361/381 394/416 443/468 525/55510-07.6-333.0 437/463 481/509 524/556 590/625 668/66810-07.6-416.3 546/578 601 /636 656/668 668/668 668/66810-07.6-500.0 656 668 668 668 66810-07.6-667.0 875 875 875 875 87511-07.6-889.0 1167 1167 1167 1167 1167

    10-13.8-069.0 50 55 60 68 8010-13.8-138.0 100 110 120 135 16010-13.8-207.0 150 165 180 203 24010-13.8-276.0 200 220 240 270 320

    10-14.4-072.0 50 55 60 68 8010-14.4-144.0 100 110 120 135 16010-14.4-288.0 200 220 240 270 32010-14.4-333.0 231 254 277 312 37010-14.4-432.0 300 330 360 405 48010-14.4-576.0 400 440 480 540 64010-14.4-720.0 500 550 600 668 66810-14.4-833.0 578 636 668 668 668

    10-19.9-100.0 50 55 60 68 8010-19.9-200.0 100 110 120 135 16010-19.9-333.0 167 184 201 226 26810-19.9-400.0 200 220 240 270 32010-19.9-667.0 335 368 402 452 53610-19.9-833.0 418 459 502 565 668

    OPERATION AT LESSTHANRATED VOLTAGE

    JFR regulators may be operated at lessthan the voltage for which they were de-signed. All system voltages for whichcontrol system taps have been providedare shown on the nameplate. When thisis to be accomplished it may be neces-sary to reconnect particular leads at theupper 19-pin terminal block as illustratedon page 5. When operating the regula-tor at reduced voltage it must be notedthat the regulator carries a maximumcurrent rating which rules regardless ofthe voltage (see table at right). It maytherefore be necessary to operate theregulator at less than its nameplate kVArating.

    Units with catalog number starting with10 are self cooled11 are forced-air cooled

    Regulators can be modified at factory for50 Hz operation with appropriate deratingof voltage.

    *Capab le o f car ry ing cur ren tcorresponding to rated kVA when operatedat 7200/12470 volts grounds wye.

    www

    . Elec

    tricalP

    artM

    anua

    ls . c

    om

  • Page 15

    SPECIAL FEATURES

    Certain regulators may be equipped for forced-air coolingand include fans mounted on the radiators. The fans areusually automatically controlled by means of the change inoil temperature (see Connection Diagram). The thermom-eter located in the top transformer oil contains two identicalswitches which control fan operation when fan controlswitch is in “Auto” position.

    The switches are normally set to start the fans at 65°C andto stop them at 55°C top oil temperature, but may be ad-justed plus or minus 5°C.

    A thermal overload relay is mounted on each fan motor. Anyfan that develops trouble will be automatically disconnectedfrom the line without affecting the other fans of the system.One fan can be removed from the radiators without affectingthe operation of the others. When fans are out of service,care must be exercised to prevent overloading the regulator.Fan should be removed and replaced carefully to preventdamage to the radiators.

    FORCED AIR COOLING SUBBASE ASSEMBLY

    Subbase assemblies are available in 4-inch high incrementsfrom 21 through 49 inches for most JFR regulators. Theproper height is selected by picking the elevation that willprovide required clearance from foundation to the live part ofthe regulator bushing.

    Figure 15A

    Figure 15B

    www

    . Elec

    tricalP

    artM

    anua

    ls . c

    om

  • Page 16

    PARTS LIST

    MAJOR COMPONENTS PARTS LIST

    INSTRUCTIONS FOR ORDERING PARTS

    When ordering parts give the quantity of parts required, theregulator serial number, parts list item number, completedescription, and method of shipping. State whether foremergency repair, maintenance, spare part, etc.

    All shipments will be made F.O.B Factory

    Item01-11 Description

    5050A50815083508450855087508850925094B509552465287 17 80 81A 90A

    Control Compartment GasketMain Cover GasketPressure Relief ValveTerminal Box GasketNameplateSampling DeviceGrounding Lug Terminal (not shown)Terminal Block ClampTerminal Block StudsTerminal Block GasketMotor Capacitor TLGMotor Capacitor TLFDrain ValveOil Sight GlassOil Sight Gauge GasketJ-Bolt Assy - Stainless Steel

    Figure 16A

    www

    . Elec

    tricalP

    artM

    anua

    ls . c

    om

  • Page 17

    PARTS LIST

    POSITION INDICATOR PARTS LIST

    Item01-11508350605061506250655067506850695071507250735274

    DescriptionPosition Indicator - CompleteSolenoid HousingGasketDrag Hand Solenoid CoilAdjusting KnobFaceplateWindowClamping RingVari-AmpTM Adjusting SwitchLimit Switch (each)Flang GasketSpacer Ring (not shown)

    Item01-11 Description

    5063C5062C5065C5067C5068C5069C5071C5072C5073C5079C

    Position Indicator - CompleteDrag Hand Solenoid CoilAdjusting KnobFaceplateWindowClamping RingVari-AmpTMAdjusting Switch (each)Limit Switch (each)Flange GasketWindow Gasket

    www

    . Elec

    tricalP

    artM

    anua

    ls . c

    om

  • Page 18

    PARTS LIST

    TYPE TLG DIAL SWITCH

    Item01-11 Description

    Item01-11 Description

    *5320*5320B5317A5321532253235324532553265327

    Phenolic PanelGlass Polyester PanelReversing Main ShaftMain Stationary ContactsReversing Stationary Contact RReversing Stationary Contact LNeutral Stationary ContactCollector RingCollector HubReversing Switch Arm

    5328A 5328B*5329*5329A*5329B 5330 5331 5332 5333 5334 5336

    Reversing Switch Finger AssemblyReversing Switch Hub Finger AssemblyDrive Arm - PhenolicDrive Arm - PhenolicDrive Arm - Glass PhenolicHub Finger SupportRing Finger SupportMain Moving Finger AssemblyHub Finger AssemblyRing Finger AssemblyPhenolic Drive Pin

    www

    . Elec

    tricalP

    artM

    anua

    ls . c

    om

  • Page 19

    PARTS LIST

    TYPE TLG QUICK BREAK MECHANISM

    Item01-11 Description

    Item01-11 Description

    *5320*5320B 5317A 5321 5322 5323 5324 5325 5326 5327

    Phenolic PanelGlass Polyester PanelReversing Main ShaftMain Stationary ContactsReversing Stationary Contact RReversing Stationary Contact LNeutral Stationary ContactCollector RingCollector HubReversing Switch Arm

    5328A5328B53295329A5329B533053315332533353345336

    Reversing Switch Finger AssemblyReversing Switch Hub Finger AssemblyDrive Arm - PhenolicDrive Arm - PhenolicDrive Arm - Glass PhenolicHub Finger SupportRing Finger SupportMain Moving Finger AssemblyHub Finger AssemblyRing Finger AssemblyPhenolic Drive Pin

    www

    . Elec

    tricalP

    artM

    anua

    ls . c

    om

  • Page 20

    PARTS LIST

    Item01-11 Description

    Item01-11 Description

    53515352535353545355535653575358A53595360A

    PanelStationary ContactNeutral Stationary ContactStationary Contact - LHStationary Contact - RHCollector RingShaft AssemblyMain Finger Assembly (each)Contact Finger Assembly Collector RingContact Finger Assembly Collector Hub

    *5363 5364 5365*5366 5366A 5367 5368 5369 5370 5373

    Drive PlateContact Finger Assembly - Rev. SwitchContact Support AssemblyReversing Drive PinReversing Drive PinReversing ShaftSpacerContact Finger SupportContact Finger SupportReversing Switch Stop

    TYPE TLF DIAL SWITCH

    FIGURE 20A

    www

    . Elec

    tricalP

    artM

    anua

    ls . c

    om

  • Page 21

    PARTS LIST

    TYPE TLF QUICK BREAK MECHANISM

    5323A5243B5251525252565257525952605262526352645265

    Counter Switch AssemblyNeutral Switch*Mounting FrameMotorDrive Spring TubeDrive SpringSpacerNotched Index PlateLatchLatch SpringLatch PinReversing Switch Drive Arm

    *5266 5267 5275 5276 5278 5285 5286**5287 5288 5289 5290 5291 5600

    Interlock Disc and Drive Sprocket AssemblyQuick Break Mechanism ShaftActuating Arm AssemblySpacerA-FrameDrive Chain for Position IndicatorMotor SprocketMotor Capacitor (may be located in control box)Actuating Disc and SprocketMain Drive ChainPosition Indicator Drive MechanismReversing Switch Spring AssemblyFlexible Shaft

    Item01-11

    Item01-11 Description

    Description

    *This neutral switch switch became effectivewith type TLF-30D quick break mechanism.

    *Include regulator serial number when ordering, and specify whether brown phenolic or gray polyester material. **Motor capacitor located in control box - effective with S/N 05582.

    Figure 21A

    www

    . Elec

    tricalP

    artM

    anua

    ls . c

    om

  • Page 22

    PARTS LIST

    Bypass Arrester Assembly 3 kV MOVBypass Arrester Crystal, 3 kV MOVMounting Bracket AssemblyBypass Arrester Assembly, 3 kV MOVBypass Arrester Crystal, 3 kV MOVMounting Bracket AssemblyBypass Arrester Assembly, 6 kV MOVBypass Arrester Crystal, 6 kV MOVMounting Bracket Assembly

    2,500, 5,000, 7,620

    12,000-13,800-14,400

    19,920

    I t e m01-11 Description Volts

    Include regulator serial number when ordering

    Polymer arresters now used on voltage regulators.Supersedes previous porcelain arresters.

    NOTE: 1.5 kV porcelain arresters superseded by3.0 kV MOV polymer arresters.

    BYPASS ARRESTERS

    54205421542254235424542554285428A5429

    Figure 22A

    Figure 22B

    www

    . Elec

    tricalP

    artM

    anua

    ls . c

    om

  • Page 23

    PARTS LIST

    BUSHINGS

    5400P

    5400R

    5400S

    5401P

    5401R

    5401S54105419541154185426

    5430

    54274034

    Bushing Assembly for 15 kV

    Bushing Assembly for 15 kV

    Bushing Assembly for 15 kV

    Bushing Porcelain for 15 kV

    Bushing Porcelain for 15 kV

    Bushing Porcelain for 15 kVClamping Ring for 5400 and R RatingsClamping Ring for 5400S RatingCushion SpringCap ScrewBushing Cap Line Terminal for 5400P RatingBushing Cap Line Terminal for 5400R and S RatingsGasketGasket

    5 038.1 thru 76.2

    69 thru 1385 0

    100114.3 thru 167

    7 54145 0

    38.1 thru 76.269 thru 138

    5 0100

    114.3 thru 1677 5

    414

    50007620

    13,8002500500076202500

    13,80050007620

    13,8002500500076202500

    13800

    Item01-11 Description kVA Volts

    Figure 23A

    www

    . Elec

    tricalP

    artM

    anua

    ls . c

    om

  • Page 24

    PARTS LIST

    5400T

    5400U5400V

    5400W

    5400X5400Y

    5400YY5400Z5400AB5400AC5401T

    5401U5401V

    5401W

    5401X5401Y

    5401YY5401Z5401AB5401AC4025

    4026

    4028

    40304027403240344035

    5430

    5426

    5418

    Bushing Assembly 15 kV

    Bushing Assembly, 15 kVBushing Assembly, 23 kV

    Bushing Assembly 15 kV

    Bushing Assembly, 23 kVBushing Assembly, 23 kV

    Bushing Assembly, 15 kVBushing Assembly, 23 kVBushing Assembly, 23 kVBushing Assembly, 15 kVBushing Porcelain, 15 kV

    Bushing Porcelain, 15 kVBushing Porcelain, 23 kV

    Bushing Porcelain, 15 kV

    Bushing Porcelain, 23 kVBushing Porcelain, 23 kV

    Bushing Porcelain, 15 kVBushing Porcelain, 23 kVBushing Porcelain, 23 kVBushing Porcelain, 15 kVClamping Ring for 5400T X, Z and AB RatingsClamping Ring for 5400U V, W (SL Bushing only), Y and YY RatingsClamping Ring for 5400W Rating S and L Bushings onlyCushion SpringGasketGasketGasket*Bushing Cap Line Terminal for 5400T X, YY and AB Ratings*Bushing Cap Line Terminal for 5400U, Y and Z ratings*Bushing Cap Line Terminal for 5400V RatingCap Screw

    100 thru 167167

    250 thru 509207-276

    72 thru 144100 thru 200

    333 thru 416.3250 thru 416.3576 thru 833

    288333 thru 400

    333333 thru 432667 thru 833

    667-889100 thru 167

    167250 thru 509

    207-27672 thru 144

    100 thru 200250 thru 416.3250 thru 416.3576 thru 833

    288333 thru 400

    333333 thru 432667 thru 833

    2500500

    762013,80014,40019,92025005000

    14,40014,40019,92012,00014,40019,9207620250050007620

    13,80014,40019,92025005000

    14,40014,40019,92012,00014,40019,9207620

    BUSHINGS

    I t e m01-11 Description k V A Volts

    *Units rated 250 kVA and above, 2500 and 5000 volts are not supplied with line terminals

    Indicate Regulator Serial Number

    Figure 24A

    www

    . Elec

    tricalP

    artM

    anua

    ls . c

    om

  • Siemens Power Transmission & Distribution, Inc.P.O. Box 6289Jackson, MS 39288-6289Phone: 601-939-0550Fax: 601-939-3606

    ACCU/STAT, DATA/PAK, NEUTRALITEand VARI-AMP are trademarks ofSiemens Power Transmission &Distribution, Inc.

    s

    PR4018-06PR4018-05PR4018-04June/01

    PRINTED IN U.S.A.

    www

    . Elec

    tricalP

    artM

    anua

    ls . c

    om